Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and...

14
Series 10A6100 PurgemasterTM n n n n n n adjustable over the entire meter range. or Dual (min. & max) alarm sensors are Adjustable Alarms - Single (min. or max.) to give reliable flow control regardless of changes in upstream pressure. Differential Pressure Regulator is designed Versatile Flow Controller - The optional Control Valve - The optional control valve provides a smooth fine degree of adjustment. tube is removed. (Not available with outlet control valve.) and draining of process fluid when metering Internal Back check - Restricts back flow materials of stainless steel and KYNAR® and 10 inch scale lengths and end fitting Optimum Variety - Available in 1-1/2, 3, 5, the downtime needed to clean the meter tube or to change the meter range. "Snap-in" Tube Construction - Minimizes alignment and resistance to pipe strain. High Strength Stainless Steel Body - Rigid construction to maintain tube n 10A6100 IT BFP Global Purgemaster Variable Area Flowmeters Field Data Sheet D-FV-10A6100_2

Transcript of Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and...

Page 1: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

Series 10A6100PurgemasterTM

n

n

n

n

n

n

adjustable over the entire meter range.or Dual (min. & max) alarm sensors areAdjustable Alarms - Single (min. or max.)

to give reliable flow control regardless ofchanges in upstream pressure.

Differential Pressure Regulator is designedVersatile Flow Controller - The optional

Control Valve - The optional control valveprovides a smooth fine degree of adjustment.

tube is removed. (Not available with outletcontrol valve.)

and draining of process fluid when meteringInternal Back check - Restricts back flow

materials of stainless steel and KYNAR®

and 10 inch scale lengths and end fittingOptimum Variety - Available in 1-1/2, 3, 5,

the downtime needed to clean the metertube or to change the meter range.

"Snap-in" Tube Construction - Minimizes

alignment and resistance to pipe strain.

High Strength Stainless Steel Body -Rigid construction to maintain tube

n

10A6100

IT

BFP Global Purgemaster Variable Area Flowmeters

Field Data Sheet D-FV-10A6100_2

Page 2: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

2

the listed combination limits must not be exceeded.

Maximum Process Temperature and Pressure: Temperature and pressure are interdependent but

Minimum Pressure: Full vacuum. If vacuum conditions require a control valve, it should be in theoutlet fitting.

Minimum Temperature: 32°F (0°C)

Ambient Temperature Limits: 32°F to 140°F (0ºC to 60°C)

Operational Limits:

Rangeability: 10 to 1 or greater

*Process wetted parts

Shield: Acrylic

Body: 304 stainless steel

Internal Back check*: Teflon

Valve Stem*: Stainless steel with stainless fittings; KYNAR® tip over stainless steel (non-process wetted) with KYNAR® fittings.

Optional: Butyl Rubber, Ethylene Propylene Rubber and Kalrez.®

O-Ring*: Viton when stainless or KYNAR® end fittings are specified.

Tube Rest Gasket: Teflon

Float Stop*: 1-1/2 and 3 inch meters 316 stainless steel with stainless steel end fittings, Hastelloy "C" with KYNAR® end fittings; 5 and 10 inch meter - Teflon.

OptionalStandardScale Length 1-1/2” (38 mm)

3” (75 m) 5” (127 mm)

Accuracy

10% 10% 2%*

10” (250 mm) 2% *Except tube number FP-1/8-038-G-6 and FP-1/8-041-G-6 which have ±5% standard accuracy and ±2% optional accuracy.

Accuracy

4% 4% 1%* 1%

ACCURACY STATEME T N±Percent of Full Scale

Accuracy:

Repeatability: 0.5% of full scale reading.

Performance:

Engineering Specifications

Tube Adaptor Spring*: 316 stainless steel with stainless steel end fittings, Hastelloy "C" with KYNAR® end fittings.

Tube Adaptor*: 316 stainless steel or KYNAR® with stainless end fittings, KYNAR® with Kynar end fittings

End Fittings*: 316 stainless steel and KYNAR®

Floats*: Refer to Capacity Tables (Table I, II, III, & IV)

Tube*: Borosilicate glass

Meter

Materials of Construction:

KYNAR

KYNAR

316SS

KYNAR

316SS

316SS

---

---

250(1724)

--- 150(65)

200(93)

250(120)

150ºF 200ºF 250ºF(65ºC) (93ºC) (120ºC)

250 (1724)

200 (1380)

250 (1724)

225 (1550)

150 (1034)

Max. Maximum Fluid Pressure PSIG (kPa)Fluid Operating Temperature ºF(ºC)

<100ºF (38ºC)

250 (1724)

250 (1724)

200 (1380)

Temp.ºF(ºC)

TypeAdaptorMat’l

EndFittingMat’l

The Purgemaster is ideal for such applications as the purging of control lines and instrument enclosures. Their use is easily extended into fluid sampling, liquid specific gravity, and level measurement and similar services.

an excellent selection of material and scale lengthsin a single product family design. They provide optimum flexibility with minimum component proliferation. The meter features a corrosion resistant, high strength stainless steel body, quick, easy snap-in tube construction and a safety tested operator protection shield.

The Purgemaster Purge Meters are low capacity variable area flowmeters for both liquid and gas with

PURGEMASTER™

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100

Page 3: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

3

Note 1: When combined with a 53R2110 Differential PressureRegulator, the PURGEMASTER can control a flow of liquid or gasthat is subject to varying line pressure. However, due to gascompressibility, the true value of mass flow rate of a gas can bemeasured only if the downstream pressure remains constant.

Purge Meter with Regulator: Add 2-1/2 lb (1.15kg)to weights listed above.

0.80

0.65

0.45

0.45

Kglb 1.0 1.0 1.4 1.8

Scale Length 1-1/2” (38 mm)

3” (75 mm) 5” (127 mm)

10” (250 mm)

Weight (Approximation)Purge Meter Only

1/4" NPT internal threads

Differential Pressure Regulator Body: 316 stainless steel Diaphragm: Viton (with stainless body); Buna-N(optional). Ball Valve: 316 stainless steel Springs: Type 316 stainless steel Max Pressure: 200 psig (1380kPa) at 100°F (38°C)Maximum Differential Pressure: 100 psi (690 kPa) Pipe Connection:

1

Housing: Crastin, blackProtective Class: NEMA 4X/IP67 Weight: 150 g (approximate)

(3000 m) possible)Cable: 6 1/2 feet (2m) standard (max. 9800 feetAmbient temp. limit: -14°F(-26° C) to 158°F(70°C)Self Capacitance: 150 nFSelf Inductance: 100 µHRepeatability: £ 0.01 mm

FM Approved forClass I, Div 1, Groups A, B, C and D; Class II, Div 1, Groups E, F, and G Class III, Div 1

Power supply requirements: 5 to 25 V dc Load Current (current range): £ 0.01mA, ³ .3 mA

Ring sensorRC-10-14-N for 1/8 inch meter tubes, RC-10-15-N for 1/4 inch meter tubes Bistable Switching Action

Alarm Specifications

operation possible.body. No automatically adjustability during

• Integrated clamp device directly to the meter

Design Features• Sensor height 14 mm, therefore only small

coverage of the scale.

are required.10A6133 are recommended if both alarm operationsminimum or a maximum alarm. Models 10A6132 ormetering tube, type 10A6131 is suitable either as aintrinsically safe circuit. Due to the relatively shortring sensor used is an intrinsically safe switch withExplosion hazardous operation is feasible, since the

into the normal operating range. The actual floatposition - above or below the trigger level - is precisely indicated.

level. The relay will drop out as soon as the floatcrosses the trigger level from the opposite direction, and moves back from the alarm zone

float reaches the trigger level and remains in thatposition, even if the float continues to move towards the alarm zone, thus leaving the trigger

picks up the relay in the amplifier when the ballThe ring sensors with a bistable switching actionPrinciple of operation

Alarms

Scale Length: 1-1/2, 3, 5, and 10 inch. Scales (on tube): As indicated in capacity tables.(Optional metal scale for 5 and 10" rear panel mounting)

Connections: 1/4 inch NPT. Inlet and outlet fittings are horizontal and face back. Mounting: In-line; wall or front of panel throughmounting holes in back of the body; or rear of panelmounting.

Warning Operating the meter without the protection

shield may result in operator bodily injury.

NEVER BE USED FOR AMMONIA SERVICE

conditions, can occur if the wrong material isused. For example, VITON O-rings MUST

Meter damage, with potential resulting unsafematerials are compatible with the process fluid.It is important that the process wetted parts

Caution

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100

Page 4: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

4

Glass tubes are not recommended for either hot or strong Caution

alkalies; fluorine, or hydrofluoric acid. Meter tubes should beperiodically inspected for signs of wear. Erosion, stress cracks or nicks provide early warning for tube replacement. With certain fluids, the glass may erode unevenly so that wear is not visibly noticeable. If wear is suspected, the tube should be replaced.

Viton O-rings with stainless steel and KYNAR® end fitting. Always required with Differential Pressure Regulator 2

1

When constant Differential Pressure Regulator is required, Add: A stainless steel constant Differential Pressure Regulator shall be provided to maintain a constant flow rate with varying line pressures.

When integral control valve is required,2 Add: an integral (stainless steel) (KYNAR®) control valve shall be provided.

Flow rate shall be (range and units) of (fluid) metered at (temperature and pressure). Maximum temperature and pressure shall be (specify).

Meter scale length shall be (1-1/2inches percent only), (3 inches) (5 inches) (10 inches) with (percent) (mm) (direct reading) scale inked directly on the tube.

The metering tube shall be easily removable for range change or cleaning without removing the meter from the line or without the use of tools.

The purge meter shall have 304 stainless steel body, (KYNAR®) (316 stainless steel) end fittings and (Buna-N) (Viton) O-rings.1

Typical Specifications

Ordering Information: When ordering, please specify:

Complete model number. Materials of construction (end fittings, regulator body). Maximum capacity and unit of flow. Mounting. Type of scale. Accessories. Operating conditions such as:

Fluid measured Operating and maximum temperature Operating and maximum pressure Fluid density Fluid viscosity

Type: Pepperl + Fuchs model (s) KFA 5 (6)-SR2- Ex.W

Contact rating: max. 250 VA, max. 2A Supply Voltage: 120 Vac, 240 Vac, ±15%,

45 - 65 Hz Response Time: Energize approximately 20 ms,

De-energized approximately 20 ms Output Type: Single Pole Double Throw (SPDT) Ambient temp. limits: -4°F (-20°C) to + 140°F

(60°C) Maximum Wire Size: 2.5 mm2 (14 AWG) Approvals: IP20; Hazardous field circuit EExia IIC and FM Class I, Div. 1, Groups A to G. The KFA relay amplifiers must be installed in the non- hazardous area when connected to the RC-10 sensors. Housing Material: Makrolon Weight: 150 g. (5.2 oz.)

Switching amplifier

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100

Page 5: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

Variable Area Flowmeters Purgemaster - Series 10A6100 D-FV-10A6100_2

1-1/2 INCH SCALE METERScales (On Tube) Standard: Percentage, for all capacities

TABLE 11-1/2” SCALE LENGTH CAPACITIES (MAXIMUM FLOW RATES)

Liquid @ 1.0 sp.gr. & v Metering Tube Nomenclature

FP-1/16-08-P-1-½ FP-1/16-08-P-1-½ FP-1/16-08-P-1-½ FP-1/16-30-P-1-½ FP-1/26-30-P-1-½ FP-1/16-30-P-1- ½FP-1/8-21-P-1-½ FP-1/8-21-P-1-½ FP-1/8-21-P-1-½ FP-5/32-40-P-1-½ FP-5/32-40-P-1- ½FP-1/2-28-P-1-½ FP-1/4-41-P-1-½ FP-1/4-41-P-1-½

Float1 isc. 1 cps(1m as) Air @ 1013 mbarAir @ 14.7 psia & 70ºF DP Inches

of WaterPCode

& 0ºCCC/MI GPH Code SCC/MIN N

0.8*#Code SCFH Code NCC/MIN Code

1.0*#

2AA 2FA

0.013*# 0.016*#

2BA 2GA

4.0*#

2LA

0.065*

2MA 7.0#

2AB

#0.11#

2BB

13.0

2FB

0.21

2GB 22.0

2LB

0.34

2MB

38.0

2AC

0.60

2BC 60.0

120.0 2FC 2LC

0.95 1.9

2GC 2MG 0

3 190.0 2AD 2BD 450.0 850*

2FD 2AE

7 2GD 2BE

1600*

2AF13.5* 25*

2BF

2FF

2GF 2200*## 34*##

65*# 95*#

BG SA SS BG SA SS BG SA SS BG SS SS SS CA

2CA 0.14*# 2DA 1.265# 2EA

180*#2HA 0.20*# 2JA 1.390*# 2KA

420#

2NA 0.38*# 2PA 1.7170*# 2QA

5602CB 0.90# 2DA 1.5400# 2EA

900

2HB 1.20 2JB 1.7550 2KB

2100 2NB 1.90 2PB 2850 2QB2CC 4.40 2DC 22000 2EC

2600 4000

2HC 5.50 2JC 3.52600 2KC2NC 8.50 2PC 7.53800 2QC

8000 2CD 17 2DD 148000 2ED15000 2HD 32 2FD 5015000 2KD28000* 48000*

2CE 60* 2DE 10028000* 2EE

7000*## 2CF 100* 2DF 21045000* 2EF2HF 150##* 2JF 47570000*## 2KF

* # # #1

Not available with 53RT 2110 regulator Specify low capacity valves for all stainless steel end fittingsSpecify standard capacity valves for KYNAR end fittingsKey to float nomenclature; BG = black glass; SS = stainless steel; SA = sapphire; CA = carbolloy

5

Page 6: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

6

Specify standard capacity valves for all capacities and all materials

These capacities are not available with flow regulator Key float nomenclature; BG = black glass; SS = stainless steel; SA = sapphire; CA = carbolloy

* 1 2

CA

SSSS

SSBGBGSSBGSSBGFP-1/8-08-P-3

FP-1/8-08-P-3 FP-1/8-20-P-3 FP-1/8-20-P-3 FP-1/4-15-P-3 FP-1/4-20-P-3 FP-1/4-15-P-3 FP-1/4-20-P-3 FP-1/4-41-G-3 FP-1/4-41-G-3 3XE

------

---------------------

Code

2*

------

---------------------

SCFM

3HE

3HD3DE

3HC3DD3DC3HB3DB3HA3DA

CodeSCFH 0.8 1.9 3.4 7.0 15 22 27 40 85*

120*

Code 3BA 3FA 3BB 3FB 3BC 3BD 3FC 3FD 3BE 3FE

SCC/MIN. 380 900

1600 3200 7000

10500 13000 19000 40000* 56000*

Code 3CA 3GA 3CB 3GB 3CC 3CD 3GC 3GD 3CE 3GE

GPH 0.07 0.32 0.46 1.4 2.4 3.8 6.5 9.0 20* 29*

Code 3AA 3EA 3AB 3EB 3AC 3AD 3EC 3ED 3AE 3EE

CC/MIN. 4.6 20 29 90

150 240 400 580

1250* 1800*

1FloatTube

---

------

---------------

3XA---

Code

---

------

---------------

2.5---

SCFH

10 psig @70ºFMaximum Capacities Air @ 14.7 psia & 70ºFLiquid @ 1.0 sp.gr.

425.0

55.0222.0

25.018.08.35.02.52.21.4

kPa 0.35 0.55 0.62 1.2 2.1 4.5 6.2

13.7 54.7

105.7

InchesH 2O

Pressure Drop Across Meter

with Valve-Wide Open

3” SCALE LENGTH CAPACITIES (MAXIMUM FLOW RATES)TABLE II

Scales (On Tube) Standard: Percentage, for all capacities Optional: See Capacity Table II for available stan- dard direct reading scales. Optional direct reading-other than shown on Table II.

3 Inch Scale Meter

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100

Page 7: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

7

* # ## Specify high capacity valves for all stainless steel end fittings.

Specify standard capacity valves for KYNAR end fittings.

Not available with 53RT 2110 regulator Specify low capacity valves for all stainless steel end fittings.Specify standard capacity valves for KYNAR end fittings.

50 56 71

113 189 385

1.2 1.2 1.3 1.6 1.7 1.3 1.5 1.5 1.9 2.2 2.5 3.4 4.0 3.3 4.8 6.7

12.0 18.0 33.0

Π inches of Water

SS BG SS CA SS CA

BG BG SA SS SS BG SA BG BG SA BG SS SS BG SS BG BG BG SS

Float

FP-1/4-40-G-6FP-1/4-40-G-6FP-1/4-25-G-5FP-1/4-25-G-5FP-1/4-40-G-6FP-1/4-20-G-5

FP-1/4-16-G-5FP-1/4-25-G-5FP-1/4-20-G-5FP-1/4-16-G-5FP-1/8-25-G-5FP-1/4-10-G-5FP-1/8-20-G-5FP-1/8-16-G-5FP-1/8-25-G-5FP-1/8-16-G-5FP-1/8-16-G-5FP-1/8-12-G-5FP-1/8-08-G-5FP-1/8-08-G-5

FP-1/8-041-G-6FP-1/8-038-G-6FP-1/8-041-G-6FP-1/8-041-G-6FP-1/8-038-G-6

Tube

5FH5DH5DG5FG5BH5DM

5DF5BG5BM5BF5DD5BE5BL5DC5BD5FC5BC5BB5DA5BA5FK5DJ5DK5BK

5BJCode

135*##96*70*504939

SCFH1450012600960074003800410029002150195014501080720

540#390#250*#185*#128*#78*#55*#

SCC/MIN.

Air @ 14.7 psia & 70ºF

5CM 5AH 5EG 5CG 5CH 5EH

Code 5AJ 5AK 5CK 5CJ 5EK 5AA 5CA 5AB 5AC 5EC 5AD 5CC 5AL 5AE 5CD 5AF 5AM 5AG 5CF

550 570 720

1060* 1340*

2000*##

CC/MIN. 0.65*# 1.06*# 2.05*# 3.3*# 4.7*# 6.0#

10.8# 14.0 22.5 35.0 43.0 61 82 88

110 170 225 300 420

Liquid @ 1.0 sp. gr. Maximum Capacities

5” SCALE LENGTH CAPACITIES (MAXIMUM FLOW RATES)TABLE III

Optional: See Capacity Table III for available standard direct reading scales.Optional direct reading - Other than shown on Table III. Percent scale considered as non-standard direct reading.

Scales (On Tube) Standard: Millimeter scales with standard air and water curves

5 Inch Scale Meter

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100

Page 8: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

Variable Area Flowmeters Purgemaster - Series 10A6100 D-FV-10A6100_2

10 Inch Scale Meter

Scales (On Tube) Standard: Millimeter scales with standard air and water curvesOptional: See Capacity Table IV for available standard direct reading scales.Optional direct reading - Other than shown on Table IV. Percent scale considered as non-standard direct reading.

TABLE IV10” SCALE LENGTH CAPACITIES (MAXIMUM FLOW RATES)

Maximum CapacitiesΠ inche sof water Liquid @ 1.0 sp. gr. Air @ 14.7 psia & 70ºF

Float Tube

CC/MIN. Code 1AA 1CA

SCC/MIN. Code6.0# BG

SA 1.5 1.8

365# 1BA FP-1/8-077-G-1010.4# 510# 1DA FP-1/8-077-G-10

SCFH16.4 21.2 28.0 44.0 48.5 73.0 91.0 122 184 224 365 535 590 800*

1300* 1880*##

1AB 1EA 1CB 1EB 1AC 1EC 1AD 1CC 1GC 1AE 1CD 1EE 1AF 1CE 1CF 1EF

BG SS SA SS BG SA BG SS CA BG CA SS BG CA SS CA

1.9 2.2 2.3 3.0 3.4 4.8 2.6 7.9 9.0

11.5 18.4 49 63 75

225 465

1.8 1BB FP-1/8-13.3-G-101.7 1FA FP-1/8-077-G-102.4 1DB FP-1/8-13.3-G-103.7 1FB FP-1/8-13.3-G-104.6 1BC FP-1/8-32-G-106.0 1FC FP-1/8-32-G-109.2 1BD FP-1/4-10-G-109.3 1DC FP-1/8-32-G-10

13.8 1HC FP-1/8-32-G-1020 1BE FP-1/4-19-G-1025 1DD FP-1/4-10-G-10

37.5 1FE FP-1/4-19-G-1052.2 1BF FP-1/4-40-G-1053.5* 1DE FP-1/4-19-G-1092* 1DF FP-1/4-40-G-10

132*## 1FF FP-1/4-40-G-10

* #

Not available with 53RT 2110 regulator Specify low capacity valves for all stainless steel end fittings.Specify standard capacity valves for KYNAR end fittings.

## Specify high capacity valves for all stainless steel end fittings.Specify standard capacity valves for KYNAR end fittings.

8

Page 9: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

9

Design Level .................................................................................................................... BTube Size

1/8" ....................................................................................................................................... 11/4" ....................................................................................................................................... 21/16" (Only w/ 1-1/2" and 5" length) (Requires low capacity valve) ..................................... 35/32" (Only w/1-1/2" length) ................................................................................................. 4

Materials of Construction Fittings/O-Rings/Adaptors

316ss/Viton/SS ........................................................................................................................... B *Kynar/Viton/Kynar (NPT only) ................................................................................................... D 316ss/Buna/SS ........................................................................................................................... E *Kynar/Buna/Kynar (NPT only) ................................................................................................... G 316SS/Viton/Kynar ..................................................................................................................... H 316SS/Buna/Kynar ..................................................................................................................... J *316SS/EPR/SS ......................................................................................................................... L Special ........................................................................................................................................ Z

*Not available with Regulator Mounting (Meter & Regulator)

In-Line (Pipe) ........................................................................................................................................ 1 Wall Mount ............................................................................................................................................ 2 Rear Panel Mount ................................................................................................................................. 3 Front Panel Mount ................................................................................................................................ 4

Regulator Piping No Regulator ................................................................................................................................................. X Stainless Steel .............................................................................................................................................. A

Process Connection 1/4" NPT ..................................................................................... 3Specials ...................................................................................... Z

Meter Tube, Scale Length 3" scale .................................................................................................. 15" scale .................................................................................................. 210" scale ................................................................................................ 31-1/2"scale ............................................................................................. 4

Valve Location (Note 1) Without Valve .................................................................................................. AOutlet Valve, Std. Capacity .............................................................................. MInlet Valve, Std. Capacity ................................................................................ NOutlet Valve, Low Capacity .............................................................................. CInlet Valve, Low Capacity ................................................................................ DOutlet Valve, High Capacity ............................................................................. EInlet Valve, High Capacity ............................................................................... F

____ __ __ ________10A61PURGEMASTER Flowmeter

Model Number Designation

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100

Page 10: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

10

Notes: 1. Specials, low and high capacity valves are not available in KYNAR.

Alarm Option* (Includes Ring Sensor) (Not available with 1-1/2" size. 1/8 and 1/4" diameter tube only

Not Required .............................................................. 00Minimum Alarm .......................................................... 10Maximum Alarm ......................................................... 20Minimum & Maximum Alarm (5 & 10" Tubes Only) ... 30Modified for Alarms without Sensor or Relay ............ 90*Must use Metallic Floats, SS, Ca

Connection Accessories Not Required ......................................................................... A

ABB Logo Tag ....................................................................................... ALanguage

English ....................................................................................................... EAlarm Relay (Power Requirements)

Not Required .......................................................................................................... X110 Vac .................................................................................................................. 3220 Vac .................................................................................................................. 4

External Metal Scale (Rear Panel Mount. 5 & 10" Only)Not Required ..................................................................................................................... BRequired .......................................................................................................................... C

Calibration Standard Accuracy (+10%, 1-1/2 & 3" scale +2%, 5 & 10" scale)

Except 1/16-G5 Tubes, 1/8-038-G6 & 1/8-041-G6 are +5%) .............................................. 1Calibrated Accuracy (+4%, 1-1/2 and 3" Scale) ......................................................................... 2Calibrated Accuracy (+1%, 5 & 10" Scale Except 1/16-G5 tubes,

1/8-038-G6 & 1/8-041-G6 are +2%) .................................................................................... 3Scales

Not Required ........................................................................................................................................... X Direct Reading (Standard Scales listed in Spec Sheet) ......................................................................... B Direct Reading (Special Scales) ............................................................................................................. C Millimeter ................................................................................................................................................ D Percent ................................................................................................................................................... E Dt/Df ........................................................................................................................................................ F

Standard Ranges 2.5 scfh Air @ 10psig & 70°F (3" Only) .......................................................................................................... 3XA 2.0 scfm Air @ 14.7psia & 70°F (3" Only) ...................................................................................................... 3XE 240 cc/min Water (3" Only) ............................................................................................................................ 3AD Other (Supply 3 Digit Code or leave blank for factory sizing) ......................................................................... XXX

_____ __ ____EAA10A61_ _ _ _ _ _ _ _ _ _PURGEMASTER Flowmeter

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100

Page 11: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

11

7.6.

gain access to holes in backplate. Use #8 flat h d screws.eaThis drawing is third angle projection shown. asConnections are available in 1/4 NPT.

5.4.

3.2.

Dimensions are in inches, unless otherwise spec ied.ifDimensions in parentheses ( ) are in millimeters. All dimensions subject to manufac ring tolerance of ± 1/8 inchtu(3mm) unless otherwise specified. Dimensions guaranteed only if this print is certified. To panel mount meter, white background must be removed to

1.Note:

32020794

mm

12-19/328-5/32

3-23/32Inch

D

29418158

mm

11-9/167-1/8

2-11/16Inchmm

125 238 351

CB Inch

4-15/16 9-3/8

13-13/16

mm 151 264 376

A Inch

6-15/16 10-3/8

14-13/16

NOM Sca leL ngth

mm 76

127 254

ech In

3 5 10

7.6.

5.4.

3.2.

Dimensions are in inches, unless otherwise spec ied. ifDimensions in parentheses ( ) are in millimeters. All dimensions subject to manufac ring tolerance of ± 1/8 inchtu(3mm) unless otherwise specified. Dimensions guaranteed only if this print is certified. To panel mount meter, white background must be rem ved to gainoaccess to holes in backplate. Use #8 flat head s ews. crThis drawing is third angle projection as shown. Connections are available in 1/4 NPT.

1.Note:

320

94207

mm---

12-19/32

3-23/328-5/32

Inch---

D

294

68181

mm37

C

11-9/16

2-11/167-1/8

Inch1-15/32

mm 94

125 238 351

Inch 3-23/32 4-15/16

9-3/8 13-

13/16

mm 121 151 264 376

B A Inch 4-3/4

5-15/16 10-3/8

14-13/16

NOM Sca length

mm 38 76

127 254

LeInch

1- /2 13 5 10

DIMENSIONS

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100

Page 12: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

12 Dwg. No: OD-10-2716

7. Connections are available in 1/4 NPT6. Panel hardware for max 5/16 panel.

4. Dimensions guaranteed only if this print is certified.5. For outline dimensions of meter and panel cut-out, see dwg.

no. OD-10-2715.

of + 1/8 inch (3mm), unless otherwise specified.3. All dimensions subject to manufacturing tolerance2. Dimensions in parentheses ( ) are in millimeters.

specified.1. Dimensons are in inches, unless otherwise

Notes:

mm 149±6 149±6 118±6 188±6

Inch 5-7/8±1/4 5-7/8±1/4

4-21/32±1/4 4-21/32±1/4

B

373

260

149

149

mm

14-11/16

10-1/4

5-7/8

5-7/8

Inch

A

25410

1275

763

381-1/2

mmInch

LengthNOM Scale

FIGURE 4REAR PANEL MOUNT PURGEMASTER WITH REGULATOR

6. Connections are available in 1/4 NPT.C-OD-10-2711 & OD-10-2750.

5. For outline dimensions of meter, see dwg. no.4. Dimensions guaranteed only if this print is certified.

Notes:1. Dimensons are in inches, unless otherwise specified. 2. Dimensions in parentheses ( ) are in millimeters.3. All dimensions subject to manufacturing tolerance of + 1/8

inch (3mm), unless otherwise specified.mm 190 225 338 451

Inch 7-1/2 8-7/8

13-5/16 17-3/4

A NOM Sca leength

mm 38 76

127 254

LInch 1-1/ 2

3 5

10

Dwg. No: OD-10-2713

WALL MOUNT PURGEMASTER WITH REGULATORFIGURE 3

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100

Page 13: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

Variable Area Flowmeters Purgemaster - Series 10A6100 D-FV-10A6100_2

FIGURE 5REAR PANEL MOUNTING OF PURGEMASTER

N Sca A B C om

Inch

leength Notes:

1. Dimensons are in inches, unless otherwise spec . ified2. Dimensions in parentheses ( ) are in millimeters. 3. All dimensions subject to manufacturing tolerance of + 1/8 inch (3mm),

unless otherwise specified.4. Dimensions guaranteed only if this print is certified. 5. Dotted line indicates rear of panel clearance requirements. 6. Panel hardware for max 5/16 panel.7. This drawing is third angle projection as shown. 8. Connections are available in 1/4 NPT.

DL

1-1/mm 38

Inch 4-31/32 10-5/8

6-3/16

15-1/16

mm 126 157 270 383

mm 94

125 238 351

Inch 4-27/32 6-1/16 10-1/2

14-15/16 2

5

3

76

127 254

mm129

Inch5-3/32

Inch3-23/32

mm123

10

1606-5/164-15/16 15427310-3/49-3/8 26738615-3/1613-13/16 379

FIGURE 6 ALARM RING SENSOR

FIGURE 7 ALARM, SWITCHING AMPLIFIER Diameter

A (mm) 1/8” 10

1/4"15

13

Page 14: Data Sheet IT D-FV-10A6100 2 Field Variable Area ... · the purging of control lines and instrument. enclosures. Their use is easily extended into fluid. sampling, liquid specific

D-FV-10A6100_2ABB LtdHoward Road, S Neots t.Cambridge hire sPE19 8EU UK Tel: +44 (0)1480 475321 Fax: +44 (0)1480 217948

14

BFP INDUSTRIAL VALLE PERDIDO 61 VALLE DE ARAGON 3ª S

CATEPEC EDO MEX E MEXICO Tel: +(55) 5120 0045 Fax: +(55) 5121 4422

© ABB 2003

Printed in USA (10.20.03)

information contained herein without notice.improvement and the right is reserved to modify theThe Company�s policy is one of continuous productABB has Sales & Customer Support

expertise in over 100 countries worldwide www.abb.com

NOTES

D-FV-10A6100_2Variable Area Flowmeters Purgemaster - Series 10A6100