COMPARATO NELLO SRL 1 UNI EN ISO 9001: CERTIFIED COMPANY 2015 Not only have the Diamix L and Compamix L mixing/thermoregulating valves a fixed point regulation function, but they also feature a specific software which allows the servocontrol to independently carry out all the thermal disinfection processes in plants with recirculation rings, thus significantly reducing the danger of outbreak and proliferation of legionella bacteria. There are so many variables connected to the construction of plants where our equipment can be implemented, that it is impossible to totally rule out the risk. This version is completed by two semi-conductor temperature feelers: one on the mixed way - for normal regulation - and one on the final section of the recirculation ring - for sampling during the thermal disinfection process. The disinfection function can be started manually or be programmed weekly/daily: the default value is during the night between Sunday and Monday at 2:00 AM, because, statistically, this is the time users draw less water. This function can be turned off, if desired. The duration of the disinfection depends on the characteristics of the installation, because the Legionella bacterium reacts differently according to the maximum temperature reached in the final section of the ring. The higher the temperature, the shorter the disinfection process: • more than 70°C - the disinfection takes 30 minutes • 65°C to 70°C - the disinfection takes 60 minutes • 60°C to 65°C - the disinfection takes 120 minutes • 57,5°C to 60°C - the disinfection takes 180 minutes • 65°C to 57.5°C - the disinfection takes 240 minutes The valve features a relay which supplies the recirculation pump during the disinfection and outlet signals which trigger in case of failure, for instance if the disinfection process cannot be completed because the reached water temperature isn’t high enough. The valve carries out a test to check that the procedure has been properly carried out according to the set criteria. At the end of the di- sinfection process the valve resumes its mixing function. In order to avoid scalds, if water is drawn during the thermal disinfection process, it is advisable to install an anti-scald safety device for each user. OPERATION Diamix L available for 1/2” • 3/4" • 1" diameters. Compamix L available for 1"1/4 • 1"1/2 • 2" diameters. VERSIONS Diamix L - Compamix L Data Sheet 11B.16 - 18 USE Thermoregulating/mixing motorized valves such as Diamix L and Compamix L can be used for: sanitary hot water mixing in plants with recirculation, where it is necessary to carry out a programmed thermal disinfec- tion according to the national guidelines for Legionellosis prevention and control. THERMORAGULATING/MIXING VALVES FOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION

Transcript of Data Sheet 11B.16 - 18 Diamix L - Compamix...

Page 1: Data Sheet 11B.16 - 18 Diamix L - Compamix Lcomparato.com/.../2018/09/DIAMIX-L_COMPAMIX-L_eng.pdf · When replacing thermostatic mixers in existing systems, you need to check the

COMPARATO NELLO SRL

1UNI EN ISO 9001: CERTIFIED COMPANY 2015

Not only have the Diamix L and Compamix L mixing/thermoregulating valves a fixed point regulation function, butthey also feature a specific software which allows the servocontrol to independently carry out all the thermal disinfection processesin plants with recirculation rings, thus significantly reducing the danger of outbreak and proliferation of legionella bacteria.There are so many variables connected to the construction of plants where our equipment can be implemented, that it isimpossible to totally rule out the risk.This version is completed by two semi-conductor temperature feelers: one on the mixed way - for normal regulation - and one on thefinal section of the recirculation ring - for sampling during the thermal disinfection process. The disinfection function can be startedmanually or be programmed weekly/daily: the default value is during the night between Sunday and Monday at 2:00 AM, because,statistically, this is the time users draw less water. This function can be turned off, if desired. The duration of the disinfection depends on the characteristics of the installation, becausethe Legionella bacterium reacts differently according to the maximum temperature reached in the final section of the ring. The higherthe temperature, the shorter the disinfection process: • more than 70°C - the disinfection takes 30 minutes • 65°C to 70°C - the disinfection takes 60 minutes • 60°C to 65°C - the disinfection takes 120 minutes • 57,5°C to 60°C - the disinfection takes 180 minutes • 65°C to 57.5°C - the disinfection takes 240 minutesThe valve features a relay which supplies the recirculation pump during the disinfection and outlet signals which trigger in case offailure, for instance if the disinfection process cannot be completed because the reached water temperature isn’t high enough. Thevalve carries out a test to check that the procedure has been properly carried out according to the set criteria. At the end of the di-sinfection process the valve resumes its mixing function. In order to avoid scalds, if water is drawn during the thermal disinfectionprocess, it is advisable to install an anti-scald safety device for each user.

OPERATION

Diamix L available for 1/2” • 3/4" • 1" diameters.Compamix L available for 1"1/4 • 1"1/2 • 2" diameters.

VERSIONS

Diamix L - Compamix LData Sheet 11B.16 - 18

USEThermoregulating/mixing motorized valves such asDiamix L and Compamix Lcan be used for:sanitary hot water mixing inplants with recirculation, whereit is necessary to carry out aprogrammed thermal disinfec-tion according to the nationalguidelines for Legionellosisprevention and control.

THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION

Page 2: Data Sheet 11B.16 - 18 Diamix L - Compamix Lcomparato.com/.../2018/09/DIAMIX-L_COMPAMIX-L_eng.pdf · When replacing thermostatic mixers in existing systems, you need to check the

COMPARATO NELLO SRL

2UNI EN ISO 9001: CERTIFIED COMPANY 2015

Power supply (110 V and 60 Hz on request)Maximum power consumption

45 sec.8,9 VA (230V) • 9,4 VA (24V) 10 VA (230V) • 10,6 VA (24V)

Operating times (90° rotation) *Degree of protection IP 67

35 sec.

230V • 24V 50 Hz

-10°C to +50°C-15°C to +85°C

Operational room temperature for lowertemperatures, please contact out technical officeAdjustment rangeTemperature probe

TECHNICAL FEATURES Compamix LDiamix L

Diamix L - Compamix LData Sheet 11B.16 - 18

* more operating times available upon request

Valve bodies

3-WAY VERTICAL MIXED OUTLET,COMPARATO CONNECTION

FULL FLOWØ 3/4" • 1"

3-WAY VERTICAL MIXED OUTLETISO 5211 CONNECTION

FULL FLOWØ 1/2" • 3/4" • 1"• 1"1/4 • 1"1/2 • 2"

MATERIALI IMPIEGATI

THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION

YESAutomatic calculation of disinfection timeoptionalImmersion probe

daily / weeklyDisinfection cycle programming

contact-type NTC 10kΩPIDElectronic adjuster

1 BODY BRASS CW617N UNI 5705CHROMED NICKEL

2 COUPLING BRASS CW617N UNI 5705 3 BALL BRASS CW617N UNI EN

5705 CHROMED NIKEL 4 BALL SEAL P.T.F.E. 5 ANTI-FRICTION

SEAL P.T.F.E. 6 O-RING EPDM

1 BODY CW617N UNI EN 12165 2 COUPLING CW617N UNI EN 12165 3 BALL CW617N UNI EN 12165 4 BALL SEAL P.T.F.E. 5 ANTI-FRICTION

SEAL P.T.F.E. 6 ROD SEAL P.T.F.E. 7 BUSHING

PACKING CW614N UNI EN 12164 8 O-RING FKN

Page 3: Data Sheet 11B.16 - 18 Diamix L - Compamix Lcomparato.com/.../2018/09/DIAMIX-L_COMPAMIX-L_eng.pdf · When replacing thermostatic mixers in existing systems, you need to check the

COMPARATO NELLO SRL

3UNI EN ISO 9001: CERTIFIED COMPANY 2015

Diamix L - Compamix LData Sheet 11B.16 - 18

DIAMIX L - COMPAMIX L MOUNTING

AB

C

D

EF

min.

150

mm

1

234

Allowed positions

NOTES:The pipe section where the temperature probe will be installed has to be made of metal. The following part of the pipe can be of any type, provided it is suitable for its intended use.Once the valve body has been installed, the servocontrol can be rotated 180°. Mounting the servocontrol facing downwards is not allowed.

1 MIXING PROBE 2 ANTI-LEGIONELLA PROBE 3 CHECK VALVE 4 RECIRCULATION PUMP

A: hot sanitary water inlet from boilerB: cold sanitary water inlet/recirculation returnC: mixed water outlet to usersD: recirculation/cold water inlet to boilerE: recirculation returnF: cold sanitary water inlet

Diamix L • COMPARATO connection

OVERALL SIZE [mm]

Diamix L • ISO 5211 connection Compamix L

VERTICAL mixed COMPARATO connection

20 3/4" 1" 38 105 145 84 74 25 1" 1"1/4 42 117 164 94 82

MODEL øTANGSDN ø

VALVE BODIES A B C D EVALVE BODIES

D - E: dimensions refer to the valve body without tangs and caps.

VERTICAL mixed ISO 5211 connection

BR

AS

SVA

LVE

BODI

ES

15 1/2" 31 65 64 Diamix L 20 3/4" 42 82 74 Diamix L 25 1" 45 92 89 Diamix L 32 1"1/4 50 103 100 Compamix L 40 1"1/2 61 123 110 Compamix L 50 2" 67 140 130 Compamix L

MODEL DN Ø A B C

THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION

Diamix L

SERVOCONTROL

Page 4: Data Sheet 11B.16 - 18 Diamix L - Compamix Lcomparato.com/.../2018/09/DIAMIX-L_COMPAMIX-L_eng.pdf · When replacing thermostatic mixers in existing systems, you need to check the

COMPARATO NELLO SRL

4UNI EN ISO 9001: CERTIFIED COMPANY 2015

Diamix L - Compamix LData Sheet 11B.16 - 18

SPACER FOR INSULATIONE

SPACER FOR INSULATION AND MANUAL OPENING

h 90 mm h 90 mm h 90 mm

h 90 mm h 90 mm h 60 mm

THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION

ACCESSORIESOPTIONAL SPACERS FOR INSULATION AND/OR MANUAL OPENING

DIAMIX L COMPARATO CONNECTION

COMPAMIX L

OPTIONAL INLETS/OUTLETS CABLESINLET DESCRIPTIONFUNCTION

1Manual

activationdisinfection cycle

2 Forcing towards hot

If you close the inlet for at least 2 seconds, the disinfectioncycle activates

If you close the inlet for at least 2 seconds, the disinfectioncycle activates towards the hot way (during this phase thetemperature control is disabled); the display showsthe“Man” message.

3 Forcing towards cold

If you close the inlet, the geared motor activates: the valveis turned clockwise (during this phase the temperaturecontrol is disabled); the display shows the “Man” message.

OUTLET DESCRIPTIONFUNCTION

1 Disinfection cycle

2 Disinfection alarm

The outlet is activated during the disinfection cycle. The outlet is activated if there is a power shortage (“Ald”) during the disinfection cycle.

3 Temperaturealarm

The outlet is activated if the set point temperature is not reached within P2 time (“AL t”)

BRASS IMMERSION PROBE WITH CONNECTOR

Ø 5,5

1711,5G 1/8” NOTE:well not included

8 x 0,25 mm2

DIAMIX L ISO 5211CONNECTION

Page 5: Data Sheet 11B.16 - 18 Diamix L - Compamix Lcomparato.com/.../2018/09/DIAMIX-L_COMPAMIX-L_eng.pdf · When replacing thermostatic mixers in existing systems, you need to check the

COMPARATO NELLO SRL

5UNI EN ISO 9001: CERTIFIED COMPANY 2015

Diamix L - Compamix LData Sheet 11B.16 - 18

APPLICATION EXAMPLES

Hot water production system with return connection for recirculation pipelines

Hot water production system without return connectionfor recirculation pipelines

12

3 3

12

1 SANITARY SURGE CHAMBER 2 BUFFER TANK 3 TEMPERATURE CONTROL PROBE

RECIRCULATION ONLY FOR DIAMIX L ANDCOMPAMIX L PRO

Tank capacityØ1/2" 10÷20 litres 3/4" 10÷20 litres 1" 20÷30 litres 1"1/4 25÷40 litres 1"1/2 30÷50 litres 2" 40÷60 litres

Warning: for a proper operation, you need to choose the right valve body diameter accordingto the flow. You can download our DimMix software at www.comparato.com,: it will help youmake the right choice.When replacing thermostatic mixers in existing systems, you need to check the presence ofsanitary recirculation, as per the diagram, and choose the valve body diameter according tothe Kvs values (see the table of fluid-dynamic features).BUFFER TANKIf necessary, it is possible to mount a buffer tank (2) on the outlet pipeline. This will avoidany fluctuation of the reference temperature value when the drawing flow is very low. Its useis recommended when the water volume inside the recirculation plant is limited.Here you can find the capacity values of the buffer tank recommended based on the diame-ters of the mixing valves.

THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION

PROBE

EARTH

BLUE

BROWN

PHASE

NEUTRAL

1

2

1 MIXING PROBE 2 ANTI-LEGIONELLA PROBE

ELECTRICAL CONNECTIONS

Should power fail, the actuator remains in the position it waswhen the power outage occurred.When the power is restored, the servocontrol resumes its normaloperation keeping the programmed settings.

1 : 2-pole terminal block for connection(free contact)

1

Anti-legionella cycle control of sanitary recirculation pump:the contact closes when the anti-legionella bacterium disinfectioncycle is active. This allows to force the activation of the recircu-lation pump, which must be ON while the cycle is carried out.Caution: Diamix L and Compamix L can work with the sanitarywater recirculation pump active 24h a day. It is possible to ma-nage the recirculation pump according to a time schedule, usingthe relevant timer (not included).

RECIRCULATIONPUMP

Page 6: Data Sheet 11B.16 - 18 Diamix L - Compamix Lcomparato.com/.../2018/09/DIAMIX-L_COMPAMIX-L_eng.pdf · When replacing thermostatic mixers in existing systems, you need to check the

CARATTERISTICHE FLUIDODINAMICHEKvS (m3/h with ∆p = 100kPa = 1bar)

In order for the mixing process to run properly, make sure that the pressure values at the two inlets of the mixing valve areas constant and similar as possible.

KvSm3/hModel DNVERTICALmixedCOMPARATOconnection

VERTICALmixedISO 5211connection

Diamix L - Compamix LData Sheet 11B.16 - 18

Model Spacer WITH manualcontrol / opening

- 10° C ÷ +100° C

Spacer WITHOUT manualcontrol / opening

VERTICAL mixedCOMPARATO connection - 20° C ÷ +120° C

- 10° C ÷ +100° CVERTICAL mixedISO 5211 connection - 20° C ÷ +120° C

FLUID TYPE AND TEMPERATURESWater

20 11,5

25 18,315 620 11,525 18,332 27,240 47,350 73

Δp max[bar]Model PNDN

15 25 25 20 16 16 25 16 16 32 10 10 40 10 6 50 10 4

20 16 16 25 16 16

VERTICALmixedCOMPARATOconnection

PRESSURES

VERTICALmixedISO 5211connection

THERMORAGULATING/MIXING VALVESFOR HOT SANITARY WATER WITH ANTI-LEGIONELLA FUNCTION

• Operating torque: Torque which can be occasionally provided by the actuator, with no risk of breaks nor permanent deformation of the actuator components.

• : Flow coefficient when the valve is completely open (2-way valve) or when the flow is completely deviated on a perpendicular (3-way valve).

• PN: Nominal operating pressure.

• ∆p max: Maximum differential operating pressure.

In o

rder

to p

rovid

e an

up-

to-d

ate

serv

ice, C

ompa

rato

Nell

o S.

r.l. re

serv

es th

e rig

ht to

mod

ify te

chnic

al da

ta, d

rawi

ngs,

grap

hs a

nd p

hoto

s of

this

instru

ction

man

ual a

t any

time,

with

out p

rior n

otice

. and

pho

togr

aphs

of th

is ca

talog

ue a

t any

time

and

with

out p

rior n

otice

.

6

HYDROTHERMAL SYSTEMS

COMPARATO NELLO SRL17014 CAIRO MONTENOTTE (SV) ITALIA VIALE DELLA LIBERTÀ • LOCALITÀ FERRANIA • Tel. +39 019 510.371 - FAX +39 019 517.102

www.comparato.com e-mail:[email protected] UNI EN ISO 9001: CERTIFIED COMPANY 2015

UPDATED DATA SHEETS AVAILABLE AT www.comparato.com

GLOSSARY