Data Center DesignLast Update 2012.10.24
1.1.0
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com
1
![Page 2: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/2.jpg)
Objectives
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 2
• To see how the basic design principles should be adjusted for a data center
![Page 3: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/3.jpg)
What is a Data Center
• A data center is a place where the data stores and other controlled shared resources are placed
• The trend on where the data center should be goes back and forth from centralization to decentralization
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 3
![Page 4: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/4.jpg)
What is a Data Center
• The argument, to which there is no answer, is between lower cost through centralization as desired by IT and control of resources through decentralization that is desired by the business units
• One side will win the battle, then the other side
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 4
![Page 5: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/5.jpg)
What is a Data Center
• This back and forth cycles on about a five year basis because there are compelling advantages on each side
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 5
![Page 6: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/6.jpg)
Mainframe Data Center
• Data centers began with the mainframe era beginning in the 1950s
• In the early days of computer networks the computers were too expensive for everyone to have
• Therefore a single computer was shared by many users
• This single large shared computer was called a mainframe
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 6
![Page 7: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/7.jpg)
Mainframe Data Center
• These original data centers were centralized in one location
• Users requested information or asked for jobs to be done by the mainframe computer by interacting with it through a terminal for real time processing or by submitting a job for processing using punch cards
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 7
![Page 8: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/8.jpg)
Mainframe Data Center
• This job processing could be immediate or overnight
• This type of data center still exists although the method of interaction has moved from terminals and punch cards to PCs
• The data center format is still used because of its processing power and high availability
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 8
![Page 9: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/9.jpg)
Mainframe Data Center
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 9
![Page 10: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/10.jpg)
Client Server Data Center
• The next iteration of the data center was the client/server model
• Applications were installed on servers in a data center
• These applications were accessed by users with client software running on their PCs
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 10
![Page 11: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/11.jpg)
Client Server Data Center
• In many cases these application servers were distributed rather than centralized because of high cost of WAN links and application performance issues
• These distributed servers could be individual computers the size of PCs with more robust hardware or mid range size computers that were between mainframes and PCs in size and computing power
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 11
![Page 12: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/12.jpg)
Client Server Data Center
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 12
![Page 13: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/13.jpg)
Web Based Data Center
• In the current model for the data center the servers are once again centralized as the cost of WAN links has dropped while their speed has increased
• Further the number of physical servers is being reduced as single servers are being moved to blade servers running virtual machines
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 13
![Page 14: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/14.jpg)
Web Based Data Center
• The driving force here as always is to reduce the cost
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 14
![Page 15: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/15.jpg)
Web Based Data Center
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 15
![Page 16: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/16.jpg)
Virtualization in the Data Center
• Virtualization in the data center is moving from just virtual servers to include– Server virtualization– Storage virtualization– Network virtualization
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 16
![Page 17: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/17.jpg)
Unified Fabric
• The physical infrastructure used in the data center has included Ethernet based LANs, Fibre Channel based SANs, and other proprietary connection types
• The trend is toward using Ethernet as the single infrastructure with the storage data running on FCoE – Fibre Channel Over Ethernet
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 17
![Page 18: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/18.jpg)
Topology
• Here is the suggested topology as illustrated in the Official Cert Guide for the CCDA test by Bruno and Jordon from Cisco Press
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 18
![Page 19: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/19.jpg)
Topology
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 19
![Page 20: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/20.jpg)
Topology
• Here is how they describe this data center topology– At the top layer, we have virtual machines
which are software entities that have hardware level abstraction capable of running a guest OS on top of a resource scheduler also known as a hypervisor
– Within the unified computing resources, the service profile defines the identity of the server
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 20
![Page 21: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/21.jpg)
Topology
– The identity contains many items such as memory, CPU, network cards, storage information, and boot image
– 10 Gigabit Ethernet, FCoE, and Fibre Channel technologies provide the unified fabric and is supported on the Cisco Nexus 5000
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 21
![Page 22: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/22.jpg)
Topology
– FCoE is one of the key technologies that allow native Fibre Channel frames to be used on 10G Ethernet networks
– Virtualization technologies such as VLANs and VSANs provide for virtualized LAN and SAN connectivity by logically segmenting multiple LANs and SANs on the same physical equipment
– Each VLAN and VSAN operates independently from one another
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 22
![Page 23: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/23.jpg)
Topology
– At the lowest layer, we have virtualized hardware where storage devices can be virtualized into storage pools and network devices are virtualized using virtual device contexts (VDC)
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 23
![Page 24: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/24.jpg)
Layout
• A typical data center layout is shown in this slide by Commscope from an October 2012 webinar
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 24
![Page 25: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/25.jpg)
Layout
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 25
![Page 26: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/26.jpg)
Problem Areas
• As data center are centralized issues arise such as– Physical rack space– Electrical power required– Equipment cooling– Limits to scale– Security– Virtualization support– Management effort required
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 26
![Page 27: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/27.jpg)
Problem Areas
• Here is what Bruno and Jordan say on these issues– Server growth is consistently rising which is
requiring more power, which is driving the need for energy efficiency for most data center server deployments
– Although rack servers are low cost and provide high performance, unfortunately they take up space and consume a lot of energy to operate
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 27
![Page 28: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/28.jpg)
Problem Areas
– Because both rack space and power cost money, efficiency gains need to be considered in these areas
– Blade servers provide similar computing power when compared to rack mount servers, but require less space, power, and cabling
– The chassis in most blade servers allows for shared power, Ethernet LAN, and Fibre Channel SAN connections, which reduce the number of cables needed
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 28
![Page 29: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/29.jpg)
Problem Areas
– With both rack-mounted servers and blade servers, server virtualization software provides for better utilization of hardware resources, which requires less physical hardware to deploy servers, which in turn increases efficiency
– Server virtualization also enables server scalability because more rack and cabinet space is available to deploy new ESX hosts running additional virtual machines
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 29
![Page 30: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/30.jpg)
Facility Planning
• When planning the physical facility consideration must be given to– Floor space needed– How much load the raised floor can support– Electrical power required– Cooling capacity required– The cabling that will be needed and how to
manage it• For example
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 30
![Page 31: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/31.jpg)
Raised Floor
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
31
![Page 32: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/32.jpg)
Raised Floor
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
32
![Page 33: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/33.jpg)
Raised Floor
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
33
![Page 34: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/34.jpg)
Raised Floor Layout
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
34
![Page 35: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/35.jpg)
Raised Floor v Overhead Rack
• Over the last few years opinion has coalesced around the idea that power cables should go under the raised floor and the data cables overhead in basket racks such as these
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
35
![Page 36: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/36.jpg)
Overhead Cable Racks
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
36
![Page 37: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/37.jpg)
Facility Planning
• The environmental conditions in the data center is determined by the equipment as certain operating temperatures and humidity levels need to be maintained in the data center
• The physical security of the data center must be planned from the beginning
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 37
![Page 38: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/38.jpg)
Facility Planning
• Here is how Bruno and Jordan summarizes this
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 38
![Page 39: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/39.jpg)
Facility Planning
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 39
![Page 40: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/40.jpg)
Floor Space
• The floor space needed is determined by– The number of servers, amount of storage
equipment, and networking equipment that will be needed
– The space needed for non-infrastructure areas such as • Shipping and receiving• Server and network staging• Storage rooms, break rooms, and bath rooms• Employee office space
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 40
![Page 41: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/41.jpg)
Equipment
• As the authors state the equipment used will guide much of this as we consider– Weight of the rack and equipment– Heat expelled from equipment– Amount and type of power needed– Automatic transfer switch for equipment that
has single power supplies– Uninterruptible power supplies (UPS)– Redundant power distribution units (PDU)
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 41
![Page 42: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/42.jpg)
Electrical Power
• Several factors determine how much electrical power will be required including
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 42
![Page 43: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/43.jpg)
Electrical Power
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 43
![Page 44: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/44.jpg)
Electrical Power
• Redundant power supplies are needed in the form of dual electrical supplies to the equipment
• UPS based battery backup for short term power
• Generator based backup for longer term power
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 44
![Page 45: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/45.jpg)
Cooling
• Bruno and Jordan point out these considerations when designing the cooling system– Cooling is used to control the temperature
and humidity of the devices, and it is applied to zones, racks, or individual devices
– Environmental conditions need to be considered and measured by using probes to measure temperature changes, hot spots, and relative humidity
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 45
![Page 46: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/46.jpg)
Cooling
– A major issue with high-density computing is overheating
– There are more hot spots, and therefore more heat overall is produced
– The increase in heat and humidity threatens equipment life spans
– Computing power and memory requirements demand more power and thus generate more heat output
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 46
![Page 47: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/47.jpg)
Cooling
– Space-saving servers increase the server density possible in a rack, but keep in mind that density = heat
– It might not be a big deal for one chassis at 3 kilowatt (kW), but with five or six servers per rack, the heat output increases to 20 kW
– In addition, humidity levels can affect static electricity in the data center
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 47
![Page 48: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/48.jpg)
Cooling
– So, it is recommended that relative humidity level be in the range of 40 percent to 55 percent
– High levels of static electricity can cause damage to data center equipment
– Proper airflow is required to reduce the amount of heat generated by the high-density equipment
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 48
![Page 49: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/49.jpg)
Cooling
– Sufficient cooling equipment must be available to produce acceptable temperatures within the data center
– The cabinets and racks should be arranged in the data center with an alternating pattern of “cold” and “hot” aisles
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 49
![Page 50: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/50.jpg)
Cooling
– The cold aisle should have equipment arranged face to face, and the hot aisle should have equipment arranged back to back. In the cold aisle, there should be perforated floor tiles drawing cold air from the floor into the face of the equipment
– This cold air passes through the equipment and flushes out the back into the hot aisle
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 50
![Page 51: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/51.jpg)
Cooling
– The hot aisle does not have any perforated tiles, and this design prevents the hot air from mixing with the cold air
• For example
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 51
![Page 52: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/52.jpg)
Air Flow Options
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
52
![Page 53: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/53.jpg)
Air Flow Options
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
53
![Page 54: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/54.jpg)
Cabling
• Data center cabling is migrating from everything under the floor to moving the data cabling to overhead wireframe tracks
• This helps air flow under the floor as well as making it easier to run and check data cables
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 54
![Page 55: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/55.jpg)
• The presentation on Equipment Installation has much more detail on the facility issues briefly discussed here
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 55
![Page 56: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/56.jpg)
Design Layers
• The data center follows the traditional three layer model
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 56
![Page 57: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/57.jpg)
Design Layers
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 57
![Page 58: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/58.jpg)
Virtualization
• Virtualization is widely used in data centers for these reasons
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 58
![Page 59: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/59.jpg)
Virtualization
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 59
![Page 60: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/60.jpg)
Virtualization
• Areas that can be virtualized include– Servers– Network– Storage
Copyright 2011 Kenneth M. Chipps Ph.D. www.chipps.com 60
![Page 61: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/61.jpg)
Standards
• The TIA-942 standard along with the other structured cabling standards provide a guide to the setup of a data center
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
61
![Page 62: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/62.jpg)
Design Specifications
• The standard calls for these specifications for the telecommunications room or closet– This room should only be used for
telecommunications functions– Equipment not related to telecommunications
shall not be installed, pass through or enter the telecommunications room
– Multiple closets on the same floor shall be interconnected by a minimum of one 78mm conduit, or equivalent pathway
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
62
![Page 63: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/63.jpg)
Design Specifications
– Minimum one closet per floor to house telecommunications equipment and cable terminations and associated cross-connect cable and wire
– Located near the center of the area being served.
– Horizontal pathways shall terminate in the telecommunications room on the same floor as the area served
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
63
![Page 64: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/64.jpg)
Design Specifications
– One wall should have 20mm (0.75 in.) A-C plywood 2.4m (8 ft.) high
– Lighting shall be a minimum of 500 lx (50 foot candles) at 1m (3 ft.) above finished floor (AFF)
– False ceilings shall not be provided– Minimum door size 910mm (36 in.) wide and
2000mm (80 in.) high without sill, hinged to open outwards, or slide side-to-side or removable, and fitted with a lock
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
64
![Page 65: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/65.jpg)
Design Specifications
– Minimum of two dedicated 120V nominal non-switched duplex electrical outlet receptacles or equivalent, each on separate branch circuits
– Additional convenience duplex outlets placed at 1.8m (6 ft.) intervals around perimeter, 150mm (6 in.) above floor
– Access to the telecommunications grounding system as specified by ANSI-J-STD-607-A
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
65
![Page 66: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/66.jpg)
Design Specifications
– HVAC requirements to maintain temperature the same as adjacent office area
– A positive pressure shall be maintained with a minimum of one air change per hour or per code
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
66
![Page 67: Data Center Design Last Update 2012.10.24 1.1.0 Copyright 2011 Kenneth M. Chipps Ph.D. 1.](https://reader035.fdocuments.in/reader035/viewer/2022062619/55189f35550346881f8b47d9/html5/thumbnails/67.jpg)
Design Specifications
Copyright 2000 - 2010 Kenneth M. Chipps Ph.D. www.chipps.com
67