Data Center Cabling Specification

36
Generic Data Center Specification Tyco Electronics Corporation provides this information as a courtesy to its customers and potential customers. Customer should review the information to ensure conformity to the project specifications and current industry standards. Tyco Electronics reserves the right to change the programs or products mentioned at any time without notice. TYCO ELECTRONICS DISCLAIMS ALL WARRANTIES, EXPRESSED OR IMPLIED INCLUDING, WITHOUT LIMITATION, THOSE OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT. TYCO ELECTRONICS SHALL NOT BE LIABLE FOR ANY INDIRECT, SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGES INCLUDING, WITHOUT LIMITATION, LOST PROFITS OR REVENUES, COSTS OF REPLACEMENT GOODS, OR DAMAGES RESULTING FROM USE OF OR RELIANCE ON THE INFORMATION. AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 1 of 36

Transcript of Data Center Cabling Specification

Page 1: Data Center Cabling Specification

GenericData Center Specification

Tyco Electronics Corporation provides this information as a courtesy to its customers and potential customers. Customer should review the

information to ensure conformity to the project specifications and current industry standards. Tyco Electronics reserves the right to change the

programs or products mentioned at any time without notice.

TYCO ELECTRONICS DISCLAIMS ALL WARRANTIES, EXPRESSED OR IMPLIED INCLUDING, WITHOUT LIMITATION, THOSE OF

MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT. TYCO ELECTRONICS SHALL NOT BE LIABLE FOR ANY INDIRECT, SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGES

INCLUDING, WITHOUT LIMITATION, LOST PROFITS OR REVENUES, COSTS OF REPLACEMENT GOODS, OR DAMAGES RESULTING FROM

USE OF OR RELIANCE ON THE INFORMATION.

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 1 of 24

Page 2: Data Center Cabling Specification

GenericData Center Specification

Telecommunications Cabling System Technical Specification – Data Center & Storage Area Network (SAN)

1.0 INTRODUCTION

1.1 PURPOSE

The intent of this document is to provide assistance in completing a specification for an AMP NETCONNECT Data Center cabling system.

This document provides the minimum performance criteria for the components and sub-systems comprising a complete cabling system. When the complete telecommunication cabling system is installed by an authorized contractor in accordance with the manufacturer’s instructions, the cabling system shall be warranted per the Tyco Electronics 25-Year System warranty. The system warranty shall be facilitated by the Contractor and be established between the Customer and the cabling system Manufacturer.

Product part numbers, general design considerations, and installation guidelines are provided in this document.

This document also provides pertinent information to allow the Contractor to bid the labor, tooling, and miscellaneous mounting hardware and consumables to install a complete system. It is the responsibility of the Contractor to propose any and all items required for a complete system if not identified in this specification.

The Contractor shall maintain current status with the warranting manufacturer, including all training requirements, for the duration of the Cable Infrastructure Project. The Contractor shall staff each installation crew with the appropriate number of trained personnel, in accordance with their manufacturer/warranty contract agreement, to support the 25-Year System Warranty requirements. After installation, the Contractor shall submit all documentation to support the warranty in accordance with the manufacturer’s warranty requirements and to apply for said warranty on behalf of the customer. The system warranty will cover the components and labor associated with the repair/replacement of any failed link as a result of a defective product when a valid warranty claim is submitted within the warranty period.

[Text appearing in blue and within brackets requires a choice in options or features](Text in violet indicates amplifying information)

1.2 SCOPE

This document defines the cabling system and subsystem components to include cable assemblies, termination hardware, supporting hardware, and miscellany that Customer will furnish to install a complete telecommunications system. The intent of this document is to provide all pertinent information to allow the Vendor to bid the labor, tooling, and miscellaneous mounting hardware and consumables to install a complete system. However, it is the responsibility of the Vendor to propose any and all items required for a complete system if not identified in this specification.

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 2 of 24

Page 3: Data Center Cabling Specification

GenericData Center Specification

1.3 REFERENCES

Design, manufacture, test, and install data distribution systems per manufacturer’s requirements and in accordance with NFPA 70 (National Electric Code), state codes, local codes, requirements of authorities having jurisdiction, and particularly the following specifications.

1. This Technical Specification and Associated Drawings2. ANSI/TIA-568-C.0, Generic Telecommunications Cabling for Customer Premises3. ANSI/TIA/568-C.1, Commercial Building Telecommunications Cabling Standard4. ANSI/TIA/568-C.2, Copper Cabling Components Standard 5. ANSI/TIA/568-C.3, Optical Fiber Cabling Components Standard 6. ANSI/TIA/EIA-569-B, Commercial Building Standard for Telecommunications Pathways and

Spaces7. ANSI/TIA/EIA-606-A, Administration Standard for the Telecommunications Infrastructure of

Commercial Buildings8. ANSI/J-STD-607-A, Commercial Building Grounding (Earthing) and Bonding Requirements

for Telecommunications9. Building Industries Consulting Services International (BICSI) Telecommunications

Distribution Methods Manual (TDMM) 10. AMP NETCONNECT Design and Installation Contractor Agreement 11. ANSI/TIA-942, Telecommunications Infrastructure Standard for Data Centers

The Contractor is responsible to determine and adhere to the most recent edition of these standards when developing their responses.

2.0 SYSTEM COMPONENTS

2.1 MRJ21 COPPER SYSTEM

Customer shall deploy MRJ21 circuits consisting of trunk cables, patch panels, and patch cords as a standard configuration. Typical end-to-end data circuits begins at the end equipment and are constructed using [standard or AMPTRAC] Category 5e patch cords, [standard or AMPTRAC] MRJ21 patch panels, MRJ21 trunk cables, [standard or AMPTRAC] MRJ21 patch panels, and [standard or AMPTRAC] Category 5e patch cords connecting to the end equipment at the far end.

[Standard or AMPTRAC] MRJ21 [patch panels or cassettes] shall support [4-pair (10/100/1000BASE-T) or 2-pair (10/100BASE-T)] applications.

The factory terminated trunk cable assembly shall be comprised of 25-pair Gigabit Ethernet cable terminated to a MRJ21 connector on one end and [MRJ21 connector or six RJ45 modular plug connectors] terminated to the other end.

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 3 of 24

Page 4: Data Center Cabling Specification

GenericData Center Specification

2.2 MPO FIBER SYSTEM

Deploy optical fiber circuits consisting of trunk cables, cassettes, patch cords and optical fiber patch panels as a standard configuration. A typical end-to-end data circuit will begin at the end equipment and be constructed using [standard, MPO SECURE, or AMPTRAC] components that include a patch cord, a cassette, trunk cable, another cassette, and another patch cord, which terminates in the end equipment at the far end. Single-mode circuits shall contain single-mode fiber, cables, cassettes, and patch cords as well as single-mode adapters in patch panels. Multimode circuits shall contain [62.5/125μm, 50/125μm, or XG (850nm LO 50/125μm)] fiber, cables, cassettes, and patch cords.

The trunk cables shall be comprised of optical fiber cable terminated with the appropriate number of 12-fiber multi-fiber push-on [MPO or MPO SECURE] connectors.

[AMPTRAC cassettes or The cassettes] shall be comprised of optical fibers terminated in one or two [MPO or MPO SECURE] connectors on one end and [SC duplex, ST, MT-RJ, MT-RJ SECURE, LC or LC SECURE] connectors on the other end. The optical fibers and connectors shall be fully contained in a protective metal modular housing.

[AMPTRAC Patch cords or Patch cords] shall be duplex (two-fiber) cable assemblies with [SC, ST, MT-RJ, MT-RJ SECURE, LC or LC SECURE] connectors on one end and [SC, ST, MT-RJ, or LC] connectors on the other end. Hybrid patch cords (patch cords with different connectors on each end) may be used between the electronics and the first cassette if necessary to match the end equipment interface.

3.0 PRODUCT SPECIFICATIONS

3.1 MRJ21 TRUNK CABLES

The trunk cable shall be factory terminated to a MRJ21 connector on one end and [a MRJ21 connector or six RJ45 modular plug connectors] terminated to the other end. MRJ21 connectors and RJ45 modular plug connectors shall be manufactured by Tyco Electronics.

MRJ21 trunk cables shall be [180° back shell to 180° back shell or 180° back shell to 45° back shell.] Trunk cables shall be [CMR (Riser) or CMP (Plenum)] rated with a [blue or gray] jacket color.

Each trunk cable shall have protective devices to prevent damage to the connectorized ends during installation.

Trunk cables shall meet all ANSI/TIA-568-C.2 Enhanced Category 5 requirements.

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 4 of 24

Page 5: Data Center Cabling Specification

GenericData Center Specification

MRJ21 trunk cables shall be AMP NETCONNECT part number(s) [see Table 2].

Description Left Connector

Right Connector

UL/NEC Ratings

Cable Color Part Number

MRJ21 Trunk Cable

MRJ21 180° MRJ21 180° CMR (Riser) Gray 1499515-XMRJ21 180° MRJ21 180° CMP (Plenum) Blue 1499518-XMRJ21 180° MRJ21 45° CMR (Riser) Gray 1499517-XMRJ21 180° MRJ21 45° CMP (Plenum) Blue 1933061-XMRJ21 180° 6 RJ45 CMR (Riser) Gray 1499520-XMRJ21 180° 6 RJ45 CMP (Plenum) Blue 1933056-XMRJ21 45° 6 RJ45 CMR (Riser) Gray 1499508-X

X denotes length in meters:-1 = 1, -2 = 2, -3 = 3, -4 = 4, -5 = 5, -6 = 6, -7 = 7, -8 = 8, -9 = 9, 1- -0 = 10, 1- -2 = 12, 1- -5 = 15, 1- -7 = 17,

2- -0 = 20, 2- -5 = 25, 3- -0 = 30, 3- -5 = 35, 4- -0 = 40, 5- -0 = 50, 6- -0 = 60, 7- -0 = 70, 8- -0 = 80, 9- -0 = 90

TABLE 2TRUNK CABLE PART NUMBERS

3.2 MRJ21 PATCH PANELS

[AMPTRAC] MRJ21 patch panels shall be a [straight, angled, or three cassette holder type] panel design. Panels shall provide [24 or 48] modular jack ports and support a [10/100BASE-T 2-pair or 10/100/1000BASE-T Gigabit Ethernet 4-pair] platform.

[AMPTRAC] MRJ21 patch panels shall be AMP NETCONNECT part number(s) [see Table 3].

[MRJ21 cassettes shall be [6 port or 12 port] and support a [10/100BASE-T 2-pair or 10/100/1000BASE-T Gigabit Ethernet 4-pair] platform. Cassettes shall be AMP NETCONNECT part number [1479459-1 or 1479452-1, see Table 3.]]

[Patch panels and/or Cassettes] shall meet all ANSI/TIA-568-C.2 Enhanced Category 5 requirements. Patch panels must be UL Listed under file number E81956.

[Straight or Angled] 1U label holder panel shall be rack mounted after each [24 or 48] port MRJ21 patch panel. 1U Label holder panels shall be AMP NETCONNECT part number(s) [1777040-1, 1777054-1, see Table 3.]

Description Supporting Platform Rack Space Part Number

3 Cassette Holder Panel - 1U 1479451-1MRJ21 Cassette, 6 Port 10/100/1000BASE-T 4-pair - 1479459-1MRJ21 Cassette, 12 Port 10/100BASE-T 2-pair - 1479452-124 Port, Straight, Standard 10/100/1000BASE-T 4-pair 1U 1777029-124 Port, Straight, AMPTRAC 10/100/1000BASE-T 4-pair 1U 1777029-248 Port, Straight, Standard 10/100/1000BASE-T 4-pair 1U 1435971-148 Port, Straight, AMPTRAC 10/100/1000BASE-T 4-pair 1U 1777041-148 Port, Straight, Standard 10/100BASE-T 2-pair 1U 1435965-148 Port, Straight, AMPTRAC 10/100BASE-T 2-pair 1U 1777042-1Straight Label Holder Panel - 1U 1777040-148 Port, Angled, Standard 10/100/1000BASE-T 4-pair 1U 1777052-148 Port, Angled, AMPTRAC 10/100/1000BASE-T 4-pair 1U 1777053-1Angled label Holder Panel - 1U 1777054-1

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 5 of 24

Page 6: Data Center Cabling Specification

GenericData Center Specification

TABLE 3MRJ21 PANEL PART NUMBERS

Equipment racks shall be augmented with [horizontal and] vertical cable management hardware, both front and rear, to properly dress patch cords and MRJ21 trunk cables.

Each patch panel shall have a rear rack mounted cable support bar to support the MRJ21 trunk cables. Support bars shall be [6”, 9”, 12”, or 16”] deep (staggered lengths are recommended). Cable support bar shall be AMP NETCONNECT part number [see Table 5].

[Each straight patch panel shall be separated vertically on the rack by a [1U (for 24 port patch panels) or 2U (for 48 port patch panels)] horizontal finger duct cable management panel.]

Cable management panels shall be AMP NETCONNECT part number(s) [see Table 5.]

Description Rack Mount Units

Part Numbers

Horizontal Cable Management Panel, Single Sided

1U 1933530-12U 1933532-1

Vertical Cable Management, Double Sided, 6” W - 1933534-1

Vertical Cable Management, Double Sided, 10” W - 1933536-1

MRJ21 Support Bar, 6” Deep - 1933352-1MRJ21 Support Bar, 9” Deep - 1933352-2MRJ21 Support Bar, 12” Deep - 1933352-3MRJ21 Support Bar, 16” Deep - 1933352-4

TABLE 5CABLE MANAGEMENT PART NUMBERS

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 6 of 24

Page 7: Data Center Cabling Specification

GenericData Center Specification

3.3 COPPER PATCH CORDS

Patch cords at the telecommunication rack shall be [Enhanced Category 5, 24 AWG, 4-pair assemblies or AMPTRAC Category 6, 24 AWG, 4-pair assemblies.] Patch cords shall be factory-assembled by the manufacturer of the cabling system. Modular plugs shall be 50um gold-plated contacts and wired to T568A wiring pattern. Cords shall utilize colored cable and "snagless" cable boots that match the color of the cable. Patch cords shall meet all ANSI/TIA-568-C.2 [Enhanced Category 5 or Category 6] requirements. Patch cords shall be AMP NETCONNECT part number(s) [see Table 6 (X denotes length)].

Description Color Part Number

Standard Cat 5e Patch Cables

Black 406483-XGray 219241-XBlue 219242-X

Green 219243-XRed 219244-X

White 219245-XYellow 219246-XOrange 219184-XViolet 1499094-X

AMPTRAC Cat 6 Patch Cables

Black 1435864-XGray 1435835-XBlue 1435861-X

Green 1435860-XRed 1435862-X

White 1435834-XYellow 1435863-XOrange 1435918-XViolet 1435919-X

X denotes length in feet:-2 = 2, -3 = 3, -4 = 4, -5 = 5, -6 = 6, -7 = 7, -8 = 8, -9 = 9, 1- -0 = 10, 1- -2 = 12, 1- -4 = 14, 1- -5 = 15, 1--16=16 2- -0 = 20, 2- -5 = 25, 3- -0 = 30, 4- -0 = 40, 5- -0 = 50

TABLE 6

PATCH CORD PART NUMBERS

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 7 of 24

Page 8: Data Center Cabling Specification

GenericData Center Specification

3.4 OPTICAL FIBER TRUNK CABLES

The optical fiber cable used in construction of the optical fiber trunk cables shall contain [12, 24, 48, or 72], [50/125µm, 62.5/125µm, XG (850nm laser-optimized 50/125µm), or single-mode] fibers. The cable shall meet the requirements of GR-409-CORE and UL/NEC rating for [Riser or Plenum] applications. The cable jacket shall be [orange (for 50/125um and 62.5/125um) or Aqua (for XG) or yellow (for single-mode)].

Trunk Assemblies shall be tested to comply with the most recent revision of TIA/EIA-568-C.3 and ISO/IEC 11801 standards, and their published addenda.

The trunk cables shall be terminated in the appropriate number of 12-fiber, [MPO-style or MPO SECURE style] connectors. Each [MPO-style or MPO SECURE style] connector shall terminate 12 fibers.

Trunk cable polarity shall be pair-flipped AB/BA. Each trunk cable shall have protective devices to prevent damage to the connectorized ends during installation. MPO trunk cables shall be AMP NETCONNECT part number(s) [see Tables 7 and 8 (X denotes length)].

Description Fiber Type UL/NEC Ratings Jacket Color Part Number

12-Fiber, Pair-Flipped AB/BA)

50/125µm Plenum (OFNP) Orange 6435028-XXG (850nm LO

50/125µm) Plenum (OFNP) Aqua 1907404-X

62.5/125µm Plenum (OFNP) Orange 6435024-XSingle-mode Plenum (OFNP) Yellow 6435070-X

24-Fiber, Pair-Flipped(AB/BA)

50/125µm Plenum (OFNP) Orange 6435029-XXG (850nm LO

50/125µm) Plenum (OFNP) Aqua 1754687-X

62.5/125µm Plenum (OFNP) Orange 6435025-XSingle-mode Plenum (OFNP) Yellow 6754882-X

72-Fiber, Pair-Flipped(AB/BA)

50/125µm Plenum (OFNP) Orange 6435031-X50/125µm Riser (OFNR) Orange 6435039-X

XG (850nm LO 50/125µm) Plenum (OFNP) Aqua 1828803-X

62.5/125µm Plenum (OFNP) Orange 6435027-X62.5/125µm Riser (OFNR) Orange 6435035-X

X denotes length in feet:-1 = 10, -2 = 20, -3 = 30, -4 = 40, -5 = 50, -6 = 60, -7 = 70, -8 = 80, -9 = 90, 1- -0 = 100, 1- -1 = 110,1- -2 = 120, 1- -3 = 130, 1- -4 = 140, 1- -5 = 150, 1- -6 = 160, 1- -7 = 170, 1- -8 = 180, 1- -9 = 190, 2- -0 = 200, 2- -1 = 210, 2- -2 = 220, 2- -3 = 230, 2- -4 = 240, 2- -5 = 250, 2- -6 = 260, 2- -7 = 270, 2- -8 = 280, 2- -9 = 290, 3- -0 = 300

TABLE 7MPO TRUNK ASSEMBLY PART NUMBERS

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 8 of 24

Page 9: Data Center Cabling Specification

GenericData Center Specification

Description Fiber TypeMPO SECURE

Plug Color/Keying

Part Number

12-Fiber 24-Fiber

MPO SECURETrunk Cable Assembly (OFNP)

50/125um

Red 6754273-X 6754281-XYellow 6754276-X 6754284-XGreen 6754274-X 6754282-XBlue 6754275-X 6754283-XRose 1918741-X 1918759-XAqua 1918742-X 1918760-XBrown 1918743-X 1918761-XViolet 1918744-X 1918762-X

Orange 1918745-X 1918763-XSlate 1918746-X 1918764-X

XG (850nm LO 50/125um)

Red 6754420-X 6754424-XYellow 6754421-X 6754425-XGreen 6754422-X 6754426-XBlue 6754423-X 6754427-XRose 1918753-X 1918771-XAqua 1918754-X 1918772-XBrown 1918755-X 1918773-XViolet 1918756-X 1918774-X

Orange 1918758-X 1918775-XSlate 1918759-X 1918776-X

62.5/125um

Red 6754269-X 6754277-XYellow 6754272-X 6754280-XGreen 6754270-X 6754278-XBlue 6754271-X 6754279-XRose 1918747-X 1918765-XAqua 1918748-X 1918766-XBrown 1918749-X 1918767-XViolet 1918750-X 1918768-X

Orange 1918751-X 1918769-XSlate 1918752-X 1918770-X

X denotes length in feet:-1 = 10, -2 = 20, -3 = 30, -4 = 40, -5 = 50, -6 = 60, -7 = 70, -8 = 80, -9 = 90, 1- -0 = 100, 1- -1 = 110,1- -2 = 120, 1- -3 = 130, 1- -4 = 140, 1- -5 = 150, 1- -6 = 160, 1- -7 = 170, 1- -8 = 180, 1- -9 = 190, 2- -0 = 200, 2- -1 = 210, 2- -2 = 220, 2- -3 = 230, 2- -4 = 240, 2- -5 = 250, 2- -6 = 260, 2- -7 = 270, 2- -8 = 280, 2- -9 = 290, 3- -0 = 300

TABLE 8MPO SECURE TRUNK ASSEMBLY PART NUMBERS

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 9 of 24

Page 10: Data Center Cabling Specification

GenericData Center Specification

[MPO PARA-OPTIX Trunk Assembly]

[Data Center or SAN] data cable shall be AMP NETCONNECT 850nm laser-optimized 50/125µm XG PARA-OPTIX trunk cable(s). The trunk cables shall be comprised of a 72-fiber cable terminated with a single MPO-style connector on each end. Pulling socks shall protect the MPO style terminations during installation.

Trunk cable shall be connected between Pair-flipped AB/BA and Pair-straight AB/AB enclosures.

Trunk cable shall be factory pre-tested and ready for installation. Cable shall be plenum (OFNP) rated with an Aqua jacket color. PARA-OPTIX trunk assembly shall be AMP NETCONNECT part number 1919505-X (X denotes length in feet, see Table 9).

Description Fiber Type UL/NEC Rating Jacket Color Part Number

72 Fiber Trunk Assembly, Pair-Straight AB/AB

XG (850nm LO 50/125um) Plenum (OFNP) Aqua 1919505-X

X denotes length in feet: -1=10,-2=20,-3=30,-4=40,-5=50,-6=60,-7=70,-8=80,-9=90, 1--0=100,1--1=110, 1--2=120, 1--3=130, 1--4=140, 1--5=150, 1--6=160, 1--7=170, 1--8=180, 1--9=190, 2--0=200, 2--1=210, 2--2=220, 2--3=230, 2--4=240, 2--5=250

TABLE 9MPO PARA-OPTIX TRUNK CABLE PART NUMBERS

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 10 of 24

Page 11: Data Center Cabling Specification

GenericData Center Specification

3.5 OPTICAL FIBER CASSETTES

[AMPTRAC] MPO cassettes shall house [XG 50/125um, 50/125um, 62.5/125um, or single-mode] 12-fiber break out assemblies. Cassettes shall have [MT-RJ, MT-RJ SECURE, ST, LC, LC SECURE, or SC] connectors on the front and [one (12-fiber) or two (24-fiber)] [SECURE] MPO connections on the back. Cassette polarity shall be Pair-Flipped (AB/BA).

MPO cassettes shall meet the most recent revision of TIA/EIA-568-C.3 standard, and its published addenda.Optical fiber MPO cassettes shall be AMP NETCONNECT part number(s) [see Tables 10 and 11.]

Front Connector Type

Rear Connector Fiber Type Fiber

CountDuplex Port

CountPart

Number

MT-RJ MPO

50/125µm 12 6 6754286-124 12 6754288-1

XG (850nm LO 50/125µm) 12 6 1918777-124 12 1918778-1

62.5/125µm 12 6 6754285-124 12 6754287-1

Single-mode 12 6 1938996-124 12 6828819-1

MT-RJ SECURE MPO SECURE

50/125µm 12 6 6754286-X24 12 6754288-X

XG (850nm LO 50/125µm) 12 6 1918777-X24 12 1918778-X

62.5/125µm 12 6 6754285-X24 12 6754287-X

Single-mode 12 6 1938996-X24 12 6828819-X

SC Duplex MPO

50/125µm 12 6 6435181-2XG (850nm LO 50/125µm) 12 6 6754333-2

62.5/125µm 12 6 6435180-2Single-mode 12 6 6435069-2

ST-Style MPO 50/125µm 12 6 6435067-262.5/125µm 12 6 6278418-2

LC Duplex MPO

50/125µm 12 6 1918779-124 12 1918780-1

XG (850nm LO 50/125µm) 12 6 1918783-124 12 1918784-1

62.5/125µm 12 6 1918781-124 12 1918782-1

Single-mode 12 6 1938056-124 12 1918786-1

LC SECURE MPO SECURE

50/125µm 12 6 1918779-X24 12 1918780-X

XG (850nm LO 50/125µm) 12 6 1918783-X24 12 1918784-X

62.5/125µm 12 6 1918781-X24 12 1918782-X

Single-mode 12 6 1938056-X24 12 1938965-X

TABLE 10OPTICAL FIBER CASSETTE PART NUMBERS (CONTINUED)

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 11 of 24

Page 12: Data Center Cabling Specification

GenericData Center Specification

Front Connector Type

Rear Connector Fiber Type Fiber

CountDuplex Port

CountPart

Number

LC SECURE MPO

50/125µm 12 6 1985798-X24 12 1938966-X

XG (850nm LO 50/125µm) 12 6 1985713-X24 12 1918785-X

62.5/125µm 12 6 1985799-X24 12 1938967-X

Single-mode 12 6 1985797-X24 12 1918786-X

X denotes LC SECURE connector color: -2=Red,-3=Green,-4=Blue,-5=Yellow, 6=Orange,-7=Brown,-8=Violet, -9=Rose, 1—0=Slate, 1—1=Aqua

Table 10: Optical Fiber Cassette Part Numbers

Front Connector Type

Rear Connector Fiber Type Fiber

CountDuplex Port

CountPart

Number

MT-RJ (AMPTRAC) MPOXG (850nm LO 50/125µm) 12 6 1435594-2

62.5/125µm 12 6 1435672-2Single-mode 12 6 1435673-2

SC Duplex (AMPTRAC) MPO

XG (850nm LO 50/125µm) 12 6 1435688-262.5/125µm 12 6 1435653-2Single-mode 12 6 1435689-2

LC Duplex (AMPTRAC) MPO

XG (850nm LO 50/125µm) 12 6 1499647-262.5/125µm 12 6 1499648-2Single-mode 12 6 1499649-2

Table 11: AMPTRAC Optical Fiber Cassette Part Numbers

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 12 of 24

Page 13: Data Center Cabling Specification

GenericData Center Specification

3.6 RACK MOUNT ENCLOSURES

Fiber optic rack mount Enclosures shall hold [two, three, four, eight, or twelve] cassettes. Fiber optic rack mount enclosures shall accept [distribution, armored or multiple trunk] cables, and mount to [19 or 23 (19 only for 1U enclosures)]-inch racks. Enclosures shall be [1U, 2U, 3U or 4U (1U or 4U for MT-RJ AMPTRAC Cassettes)] high and shall be constructed of metal with a black powder coat finish. Enclosures shall be AMP NETCONNECT part number [see Table 11].

Description Accepts For Cable Type Height (in) Part Number

1U Rack Mount Enclosure 3 Cassettes Armored or Multiple Trunk 1.75 1-1657014-7

1U Rack Mount Enclosure 3 Cassettes Armored or Multiple Trunk 1.75 1435555-1

2U Rack Mount Enclosure 4 Cassettes Standard Distribution 3.50 559542-2

2U Rack Mount Enclosure 4 Cassettes Armored or Multiple Trunk 3.50 1435556-1

3U Rack Mount Enclosure 8 Cassettes Standard Distribution 5.25 559614-2

3U Rack Mount Enclosure 8 Cassettes Armored or Multiple Trunk 5.25 1435557-1

4U Rack Mount Enclosure 12 Cassettes Standard Distribution 7.00 559552-2

4U Rack Mount Enclosure 12 Cassettes Armored or Multiple Trunk 7.00 1435558-1

1U AMPTRAC Rack Mount Enclosure

4 AMPTRAC MT-RJ Cassettes Standard Distribution 1.75 1435608-1

4U AMPTRAC Rack Mount Enclosure

12 AMPTRAC MT-RJ Cassettes Standard Distribution 7.00 1435593-2

Table 11: Rack Mount Fiber Optic Enclosures

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 13 of 24

Page 14: Data Center Cabling Specification

GenericData Center Specification

3.7 OPTICAL FIBER PATCH CORDS

[AMPTRAC optical fiber assemblies or Optical fiber assemblies] shall be provided to patch the equipment to the cassettes. Optical fiber cable assemblies shall be [Duplex LC, Duplex LC SECURE, MT-RJ, MT-RJ SECURE, or SC] to [MT-RJ, SC Duplex, ST duplex, or LC duplex] (depending upon the electronic interface) and [1, 2, 3, 5 or 10] meter[s] in length

Cable assemblies shall be factory-terminated using duplex [50/125µm, 62.5/125µm or XG (850nm LO 50/125µm) or single-mode] cable. Optical fiber patch cables assemblies shall be AMP NETCONNECT part number [see Table 14].

Connector Type End A Connector Type End B Fiber Type AMPTRAC

EnabledPart

NumberMT-RJ MT-RJ 50/125µm - 6278128-XMT-RJ MT-RJ XG (850nm 50/125µm) - 6588572-XMT-RJ MT-RJ 62.5/125µm - 6278032-XMT-RJ MT-RJ Single-mode - 6278033-XMT-RJ SECURE Red MT-RJ 50/125µm - 6278873-XMT-RJ SECURE Red MT-RJ XG (850nm 50/125µm) - 6754406-XMT-RJ SECURE Red MT-RJ 62.5/125µm - 6278890-XMT-RJ SECURE Red MT-RJ Single-mode - 6918733-XMT-RJ SECURE Yellow MT-RJ 50/125µm - 6278874-XMT-RJ SECURE Yellow MT-RJ XG (850nm 50/125µm) - 6754407-XMT-RJ SECURE Yellow MT-RJ 62.5/125µm - 6278891-XMT-RJ SECURE Yellow MT-RJ Single-mode - 6918735-XMT-RJ SECURE Green MT-RJ 50/125µm - 6278875-XMT-RJ SECURE Green MT-RJ XG (850nm 50/125µm) - 6754408-XMT-RJ SECURE Green MT-RJ 62.5/125µm - 6278892-XMT-RJ SECURE Green MT-RJ Single-mode - 6918737-XMT-RJ SECURE Blue MT-RJ 50/125µm - 6278876-XMT-RJ SECURE Blue MT-RJ XG (850nm 50/125µm) - 6754409-XMT-RJ SECURE Blue MT-RJ 62.5/125µm - 6278893-XMT-RJ SECURE Blue MT-RJ Single-mode - 6918739-XMT-RJ Duplex SC 50/125µm - 6278126-XMT-RJ Duplex SC XG (850nm 50/125µm) - 1907429-XMT-RJ Duplex SC 62.5/125µm - 6278028-XMT-RJ Duplex SC Single-mode - 6278031-XMT-RJ SECURE Red Duplex SC 50/125µm - 6278877-XMT-RJ SECURE Red Duplex SC XG (850nm 50/125µm) - 6754410-XMT-RJ SECURE Red Duplex SC 62.5/125µm - 6278894-XMT-RJ SECURE Red Duplex SC Single-mode - 6918734-XMT-RJ SECURE Yellow Duplex SC 50/125µm - 6278878-XMT-RJ SECURE Yellow Duplex SC XG (850nm 50/125µm) - 6754411-XMT-RJ SECURE Yellow Duplex SC 62.5/125µm - 6278895-XMT-RJ SECURE Yellow Duplex SC Single-mode - 6918736-XMT-RJ SECURE Green Duplex SC 50/125µm - 6278879-XMT-RJ SECURE Green Duplex SC XG (850nm 50/125µm) - 6754412-XMT-RJ SECURE Green Duplex SC 62.5/125µm - 6278896-XMT-RJ SECURE Green Duplex SC Single-mode - 6918738-XMT-RJ SECURE Blue Duplex SC 50/125µm - 6278880-XMT-RJ SECURE Blue Duplex SC XG (850nm 50/125µm) - 6754413-XMT-RJ SECURE Blue Duplex SC 62.5/125µm - 6278897-XMT-RJ SECURE Blue Duplex SC Single-mode - 6918740-X

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 14 of 24

Page 15: Data Center Cabling Specification

GenericData Center Specification

MT-RJ Dual ST 50/125µm - 6278199-XMT-RJ Dual ST 62.5/125µm - 1907441-XMT-RJ Dual ST Single-mode - 6278298-XMT-RJ SECURE Red Dual ST 50/125µm - 6278881-XMT-RJ SECURE Red Dual ST 62.5/125µm - 6278898-XMT-RJ SECURE Yellow Dual ST 50/125µm - 6278882-XMT-RJ SECURE Yellow Dual ST 62.5/125µm - 6278899-XMT-RJ SECURE Green Dual ST 50/125µm - 6278883-XMT-RJ SECURE Green Dual ST 62.5/125µm - 6278900-XMT-RJ SECURE Blue Dual ST 50/125µm - 6278884-XMT-RJ SECURE Blue Dual ST 62.5/125µm - 6278901-XMT-RJ Duplex LC 50/125µm - 6374647-XMT-RJ Duplex LC XG (850nm LO 50/125µm) - 1907440-XMT-RJ Duplex LC 62.5/125µm - 6374646-XMT-RJ Duplex LC Single-mode - 6374645-XDuplex SC Duplex SC 50/125µm - 1907379-XDuplex SC Duplex SC XG (850nm 50/125µm) - 6828151-XDuplex SC Duplex SC 62.5/125µm - 1907434-XDuplex SC Duplex SC Single-mode - 1907435-XDuplex SC Dual ST 50/125µm - 5492591-XDuplex SC Dual ST XG (850nm 50/125µm) 1907339-XDuplex SC Dual ST 62.5/125µm - 1907385-XDuplex SC Dual ST Single-mode - 1907357-XDuplex SC Duplex LC 50/125µm - 1907380-XDuplex SC Duplex LC XG (850nm LO 50/125µm) - 1907438-XDuplex SC Duplex LC 62.5/125µm - 1906777-XDuplex SC Duplex LC Single-mode - 1906768-XDual ST Dual ST 50/125µm - 6278207-XDual ST Dual ST XG (850nm LO 50/125µm) - 1907557-XDual ST Dual ST 62.5/125µm - 1907436-XDual ST Dual ST Single-mode - 1907437-XDuplex LC Duplex LC 50/125µm - 1906866-XDuplex LC Duplex LC XG (850nm LO 50/125µm) - 6828317-XDuplex LC Duplex LC 62.5/125µm - 1906865-XDuplex LC Duplex LC Single-mode - 1906856-XMT-RJ MT-RJ 62.5µm X 1435351-XMT-RJ MT-RJ XG (850nm LO 50µm) X 1435352-XMT-RJ MT-RJ Single-mode X 1435353-XMT-RJ Duplex SC 62.5µm X 1435355-XMT-RJ Duplex SC XG (850nm LO 50µm) X 1435356-XMT-RJ Duplex SC Single-mode X 1435357-XMT-RJ Duplex LC 62.5µm X 1435792-XMT-RJ Duplex LC XG (850nm LO 50µm) X 1435793-XMT-RJ Duplex LC Single-mode X 1435794-XDuplex SC Duplex SC 62.5µm X 1435724-XDuplex SC Duplex SC XG (850nm LO 50µm) X 1435725-XDuplex SC Duplex SC Single-mode X 1435726-XDuplex SC Duplex LC 62.5µm X 1435795-XDuplex SC Duplex LC XG (850nm LO 50µm) X 1435796-XDuplex SC Duplex LC Single-mode X 1435797-XDuplex LC Duplex LC 62.5µm X 1435789-XDuplex LC Duplex LC XG (850nm LO 50µm) X 1435790-XDuplex LC Duplex LC Single-mode X 1435791-XX denotes length in meters: -1 = 1, -2 = 2, -3 = 3, -5 = 5, 1- -0 = 10

Table 14: Optical Fiber Patch Cable Assemblies AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 15 of 24

Page 16: Data Center Cabling Specification

GenericData Center Specification

[3.6 AMPTRAC SENSOR STRIPS]All Horizontal LAN electronic ports to be monitored by the AMPTRAC Connectivity Management System shall be fitted with an AMPTRAC sensor strip.

[3.7 AMPTRAC I/O CABLES]All AMPTRAC enabled patch panels and LAN electronics fitted with sensor strips shall utilize an AMPTRAC I/O cable assembly to connect the monitored device to the AMPTRAC analyzer.

AMPTRAC I/O cable system shall include AMP NETCONNECT part number(s) [see Table 15].

Analyzer End A Connector Type End B Application Conductors Part

NumberDB 25 HD22 MRJ21 Patch Panels 24 1499507-YDB 25

2.0 mm AMPMODU

PCB Sensor Strips (LAN Electronics)

24 1435845-Y

2.0 mm AMPMODU

16 1499686-Y12 1499687-Y8 1499688Y6 1499689-Y

RJ11 MTRJ and LC Fiber Cassettes 6 1499684-Y

MTE SC Adapter Plates and Cassettes 6 1499685-Y

2.0 mm AMPMODU

PCB Sensor Strips (LAN Electronics) 2 1499690-Y

Analyzer Adapter, DB25 to 2.0mm - 1499641-1

Y denotes length in feet : -4=4,-7=7,1-0=10,1-4=14,2-5=25,5-0=50,7-5=75,9-9=100

Table 15: AMPTRAC I/O Cable System

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 16 of 24

Page 17: Data Center Cabling Specification

GenericData Center Specification

[3.8 AMPTRAC ANALYZER]AMPTRAC Connectivity Management System shall include AMTRAC [336 port or 168 port] Analyzer(s). Analyzers shall contain AMPTRAC IM software.

Analyzer(s) shall be AMP NETCONNECT part number [3-1591306-1 (336 port) or 4-1591306-1 (168 port).

4.0 INSTALLATION

4.1 TRUNK CABLE INSTALLATION

The cable installation shall comply with the following guidelines. Cable shall be installed in accordance with manufacturer’s recommendations and best industry

practices. Cable raceways shall not be filled greater than the NEC maximum fill for the particular raceway

type. Connector protective devices (pulling “socks”) shall not be removed prior to cable placement

and shall remain in place until ready to be mated in the adapter. The cable’s minimum bend radius and maximum pulling tension shall not be exceeded. If a J-hook or trapeze system is used to support cable bundles, all cables shall be supported at

a maximum of four-foot intervals Cables shall not rest on acoustic ceiling grids or panels. Cables shall be installed above fire-sprinkler and related fire systems and shall not be attached

to the system or any ancillary equipment or hardware. The cabling system and support hardware shall be installed so that it does not obscure any valves, fire alarm conduit, boxes, or other control devices.

Any cable damaged or exceeding recommended installation limits during installation shall be replaced by the Contractor prior to final acceptance at no cost to the Owner.

Cables shall be identified by a self-adhesive label in accordance with the System Documentation Section of this specification.

Observe all regulations set forth by federal, state, and local authorities. This may include, but is not limited to, bonding, grounding, fire codes, and fire stopping.

Fiber cable slack shall be neatly coiled. Each cable shall be clearly labeled at both ends. Cables labeled within the bundle shall not be

acceptable. Dust caps shall be installed on all connectors and couplings at all times unless physically

connected.

[4.2 AMPTRAC SYSTEM]

AMPTRAC components shall be installed per the latest revision of the AMPTRAC Hardware Manual found on www.ampnetconnect.com.

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 17 of 24

Page 18: Data Center Cabling Specification

GenericData Center Specification

5.0 TELECOMMUNICATIONS SPACES

The telecommunication closets shall house racks, voice termination fields and required cable routing hardware. Racks shall be placed in a manner that will allow a minimum of 3 feet of clearance from the front and rear mounting surfaces and on one side. If one mounting rail of the rack is placed against a wall, the mounting rail shall be no closer than 6” to the wall to allow room for vertical management. Where there is more than one rack, the racks shall be ganged with vertical management hardware to provide interbay management. Ganged rack frames will be placed in a manner that will allow a minimum of 3 feet of clearance from the front and rear mounting surfaces and on one side of the ganged assembly.

In all closets the racks shall be on the opposite side of the room from the voice termination fields. Voice termination fields shall be mounted on 4’ x 8’ x .75” virgin fire retardant plywood, unless otherwise noted in drawings, and shall be on the opposite side of the room from the room entrance. Backbone termination fields shall be mounted to the left of the horizontal voice fields. Conduits with 4” minimum diameter shall be used in all closets. Conduits for data backbone shall be located adjacent to the racks and conduits for voice shall be located adjacent to the voice termination fields. The Contractor shall provide innerduct for all backbone fiber runs. Contractor shall provide required ladder and wall-mount management rings to properly support and dress cables from conduits to racks and frames.

5.1 INSTALLATION SPECIFICATIONS

Racks shall be installed in the following manner.

Racks shall be securely attached to the concrete floor using 3/8” hardware All racks shall be grounded to the telecommunications ground bus bar in accordance

with Section 9.0 of this document Rack mount screws (#12-24) not used for installing fiber panels and other hardware

shall be bagged and left with the rack upon completion of the installation Voice termination fields shall be mounted on 4’ x 8’ x .75” virgin plywood that is

mounted vertically at 12” A.F.F.

6.0 CABLING SYSTEM TESTING

All cables and termination hardware shall be 100% tested for defects in installation and to verify cable performance under installed conditions. All conductors and fibers of each installed cable shall be verified useable by the Contractor prior to system acceptance. Any defect in the cabling system installation including but not limited to cable, connectors, feed-through couplers, patch panels, and connector blocks shall be repaired or replaced in order to ensure 100% useable conductors in all installed cables.

All cables shall be tested in accordance with this document, the ND&I Contract agreement, and best industry practices. If any of these are in conflict, the Contractor shall be responsible to bring any discrepancies to the attention of the project team for clarification and/or resolution.

Written documentation of test results must be submitted to the manufacturer and a copy provided to the end user for their records.

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 18 of 24

Page 19: Data Center Cabling Specification

GenericData Center Specification

6.1 COPPER

6.1.1 PERFORMANCE VERIFICATION

All Enhanced Category 5 cable drops shall be tested in accordance with the field test specifications defined in ANSI/TIA-568-C.2. The test equipment shall comply with the accuracy levels defined in ANSI/TIA-568-C.0.

Test results shall be automatically evaluated by the equipment, using the most up-to-date criteria from the ANSI/TIA-568.C Standard, and the result shown as pass/fail. Test results shall be printed directly from the test unit or from a download file using an application from the test equipment manufacturer. The printed test results shall include all tests performed, the expected test result and the actual test result achieved.

The Pass or Fail condition for the cabling run under test is determined by the results of the required individual tests. Any Fail or Fail* result yields a Fail for the cabling run under test. In order to achieve an overall Pass condition, the results for each individual test parameter must be a Pass or Pass*.

6.2 FIBER OPTIC TESTING

6.2.1 PERFORMANCE VERIFICATION

Horizontal distribution multimode optical fiber attenuation shall be measured in one direction at either 850 nanometers (nm) or 1300 nm using an LED light source and power meter. This measurement is consistent with the loss which network equipment will see under normal installation and use. Backbone multimode fiber shall be tested at both 850 nm and 1300 nm in one direction. Test set-up and performance shall be conducted in accordance with ANSI/TIA/EIA-526-14 Standard, Method B. Test results evaluation for the panel to panel (backbone) or panel to outlet (horizontal) shall be based on the values set forth in ANSI/TIA-568-C.0.

Test results shall be automatically evaluated by the equipment, using the most up-to-date criteria from the ANSI/TIA-568.C Standard, and the result shown as pass/fail. Test results shall be printed directly from the test unit or from a download file using an application from the test equipment manufacturer. The printed test results shall include all tests performed, the expected test result and the actual test result achieved.

The Pass or Fail condition for the cabling run under test is determined by the results of the required individual tests. Any Fail or Fail* result yields a Fail for the cabling run under test. In order to achieve an overall Pass condition, the results for each individual test parameter must be a Pass or Pass*.

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 19 of 24

Page 20: Data Center Cabling Specification

GenericData Center Specification

7.0 SYSTEM DOCUMENTATION

The following section describes the installation, administration, testing, and as-built documentation required to be produced and/or maintained by the Contractor during the course of the installation.

7.1 CABLING SYSTEM LABELING

The Contractor shall develop and submit for approval a labeling scheme for the cable installation. Customer will negotiate an appropriate labeling scheme with the successful Contractor. At a minimum, the labeling system shall clearly identify all components of the system: racks, cables, panels and cassettes. The labeling system shall designate the cable origin and destination and a unique identifier for each cable within the system. Racks and patch panels shall be labeled to identify the location within the cabling system infrastructure. All labeling information shall be recorded on the as-built drawings and all test documents shall reflect the appropriate labeling scheme.

7.1.1 PRODUCT SPECIFICATIONS

The labeling shall be machine-generated and affixed to the cable, faceplate, patch panel, rack or other hardware.

7.1.1.1 LABELING SOFTWARE

Labeling software shall be easily useable and run on Microsoft Windows® 95, 98, ME, NT, 2000 and XP operating systems. Labeling software shall be compliant with TIA/EIA-606-A and shall be able to produce complex unique identifiers of up to 12 independent segments. Labeling software shall be capable of inserting symbols as well as use any standard True Type Font as well as capable of saving individual build information and of fine tuning print adjustments. Labeling software shall be compatible with AMP NETCONNECT products and shall be [Microsoft Word®, Microsoft Excel® or purchased directly from Silver Fox, Ltd. at: http://www.silfox.com/eshop/viewproduct.php?id=149].

7.1.1.2 CABLE LABELS

Cable labels shall be self-adhesive, self-laminating, pre-cut and laser-printer compatible. Labels shall be used with [4-pair horizontal UTP cable and/or 25-Pair backbone UTP], be [0.984” x 1.496” (4-Pair) and/or 0.984” x 2.480” (25-Pair)] in size and be divided [48 (4-Pair) and/or 24 (25-Pair)] labels per sheet with each sheet being 8.5” x 11”. Cable labels shall be AMP NETCONNECT part number [1479002-X and/or 1479003-X (X denotes packaging, see Table-16)].

Description Labels per Sheet

Sheets per Pack

Labels per Pack Part Number

Card Stock 18 5 90 1479002-1100 1800 5-1479002-1

Self-adhesive Polyester 18 5 90 1479003-1

100 1800 5-1479003-1

Table 16: Labels

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 20 of 24

Page 21: Data Center Cabling Specification

GenericData Center Specification

7.2 AS-BUILT DRAWINGS

The installation Contractor will be provided with 2 sets of D or E-size drawings at the start of the project. One set will be designated as the central location to document all as-built information as it occurs throughout the project. The central set will be maintained by the Contractor’s foreman on a daily basis, and will be available to the technical representative upon request during the course of the project. Anticipated variations from the build-to drawings may include such things as cable routing and actual outlet placement. No variations will be allowed to the planned termination positions of horizontal and backbone cables or grounding conductors unless approved in writing by the Owner.

The Contractor shall provide the central drawing set to the Owner at the conclusion of the project. The marked up drawing set will accurately depict the as-built status of the system including termination locations, cable routing, and all administration labeling for the cabling system. In addition, a narrative will be provided that describes any areas of difficulty encountered during the installation that could potentially cause problems to the telecommunications system.

8.0 Test Documentation

Test documentation shall be provided in a three-ring binder(s) within three weeks after the completion of the project. The binder(s) shall be clearly marked on the outside front cover and spine with the words “Test Results”, the project name, and the date of completion (month and year). Each major heading shall be further sectioned by test type. Test data within each section shall be presented in the sequence listed in the administration records. The test equipment name, manufacturer, model number and last calibration date will also be provided at the end of the document. The test document shall detail the test method used and the specific settings of the equipment during the test.

Scanner tests shall be printed on 8-1/2” x 11” paper. Hand written test results (attenuation results and green light results) shall be documented on the attached test form (Appendix C). OTDR test results shall be printed or attached and copied on 8-1/2” x 11” paper for inclusion in the test documentation binder.

When repairs and re-tests are performed, the problem and corrective action taken shall be noted, and both the failed and passed test data shall be collocated in the binder.

9.0 WARRANTY AND SERVICES

Provide a system warranty covering the installed cabling system against defects in workmanship, components, and performance, and covering follow-on support after project completion.

9.1 INSTALLATION WARRANTY

The Contractor shall warrant the cabling system against defects in workmanship for a period of one year from the date of system acceptance. The warranty shall cover all labor and materials necessary to correct a failed portion of the system and to demonstrate performance within the original installation specifications after repairs are accomplished. This warranty shall be provided at no additional cost to the Owner.

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 21 of 24

Page 22: Data Center Cabling Specification

GenericData Center Specification

9.2 CABLING SYSTEM WARRANTY

The Contractor shall facilitate a 25-year system performance warranty between the Manufacturer and the Owner. An extended component warranty shall be provided which warrants functionality of components used in the system for 25 years from the date of acceptance. Fiber optic and copper links shall be warranted to the link and segment performance minimum expected results defined in ANSI/TIA/EIA-568-C. [AMPTRAC sensor strips shall have a 5 year component warranty, and AMPTRAC I/O cables shall have a 25 year component warranty. AMPTRAC analyzers shall have a 1 year basic warranty.]

9.3 POST INSTALLATION MAINTENANCE

The Contractor shall furnish an hourly rate with the proposal submittal, which shall be valid for a period of one year from the date of acceptance. This rate will be used when cabling support is required to affect moves, adds, and changes (MACs) to the system. MACs shall not void the Contractor’s nor Manufacturer’s warranty.

10.0 Project Management / General

The Contractor shall establish a single point of contact (POC) with the Customer who will be responsible for reporting progress and updating the Customer’s technical representative with issues that the Owner must address to facilitate the cabling system installation. The Contractor’s POC shall provide [daily, weekly] written reports to the Customer’s technical representative detailing progress. Requests for access to limited access or restricted areas shall be made [number of days] prior to the required access. Information critical to the completion of the task or project shall be communicated to the Customer’s technical representative as the requirement becomes known. Casual information shall be passed during the scheduled progress report.

The Contractor shall maintain the Customer’s facility in a neat and orderly manner during the installation of the communications cabling system. The Customer’s facilities shall be maintained in broom clean condition at the completion of work each day. At the completion of work in each area, the Contractor will perform a final cleaning of debris prior to moving the installation crew to the next work area.

11.0 CABLING SYSTEM ACCEPTANCE

The Customer’s technical representative will make periodic inspection of the project in progress. One inspection will be performed at the conclusion of cable pulling, prior to closing of the false ceiling, to inspect the method of cable routing and support, and the firestopping of penetrations. A second inspection will be performed at completion of cable termination to validate that cables were dressed and terminated in accordance with ANSI/TIA-568-C specifications for jacket removal and pair untwist, compliance with Manufacturer’s minimum bend radius, and that cable ends are dressed neatly and orderly.

11.1 FINAL INSPECTION

Upon completion of the project, the Customer’s technical representative will perform a final inspection of the installed cabling system with the Contractor’s project foreman. The final inspection will be performed to validate that all horizontal and backbone cables were installed as defined in the drawing package, and that the installation meets the aesthetic expectations of the Customer.

11.2 TEST VERIFICATIONAMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 22 of 24

Page 23: Data Center Cabling Specification

GenericData Center Specification

Upon receipt of the test documentation, the Customer reserves the right to perform spot testing of a representative sample of the cabling system to validate test results provided in the test document. Customer testing will use the same method employed by the Contractor, and minor variations will be allowed to account for differences in test equipment and test variability. If significant discrepancies are found, the Contractor will be notified for resolution.

11.3 SYSTEM PERFORMANCE

During the three-week period between final inspection and delivery of the test and as-built documentation, the Customer will activate the cabling system. The Customer will validate operation of the cabling system during this period.

11.4 FINAL ACCEPTANCECompletion of the installation, in-progress and final inspections, receipt of the test, receipt of the as-built documentation, and successful performance of the system for a two-week period will constitute acceptance of the system.

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 23 of 24

Page 24: Data Center Cabling Specification

GenericData Center Specification

AMP NETCONNECT, Tyco Electronics, AMPTRAC, MPO SECURE, MRJ21, and MT-RJ SECURE are trademarks. 24 of 24