DAR Lecture

download DAR Lecture

of 57

Transcript of DAR Lecture

  • 8/10/2019 DAR Lecture

    1/57

    Auto-Reclose onDistribution Networks

  • 8/10/2019 DAR Lecture

    2/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 2 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Agenda

    1st topic Why Perform Auto-Reclose ? Page 3

    2nd topic Where can we apply Auto-Reclose ? Page 7

    3rd topic Terminology, Sequences & Settings Page 15

    4th topic Check Synchronism Page 46

    5th topic Conclusion Page 56

  • 8/10/2019 DAR Lecture

    3/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 3 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Why Perform Auto-Reclose ?

    Auto-Reclose is the automatic closure

    of a Circuit Breaker without theintervention of a person

    It is a Control Technique

    IEC61850 (parts -5 and 7-4) bothinclude autoreclose as a ProtectionRelated function, with a logical nodename of RREC

    ANSI / IEEE C37.2 reference 79

    IEC 60617 symbol:

    What is Auto-Reclose

    O I

    PTOC

    RREC

    PTOC Fault

    RREC

    PTOC Fault

    RREC

    Pre-Fault

    Trip

    Reclose

    Trip

    Close

  • 8/10/2019 DAR Lecture

    4/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 4 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Why Perform Auto-Reclose ?

    Continuity of Supply Restoration is Automatic, therefore quicker Shorter duration of Power Outages

    Fewer Customer Minutes Lost

    Reduced Asset Damage

    Autoreclose permits use of faster, non-discriminative protection Some overtripping is deemed acceptable

    Less chance of faults evolving to more damaging scenarios

    Lower pre-heating of CB contacts May reduce maintenance requirements ?

    What are the Benefits ?

  • 8/10/2019 DAR Lecture

    5/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 5 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Why Perform Auto-Reclose ?

    Reduction in Operating Costs (OPEX) Reduced requirement for substation visits Reduction in damage of asset Increase in capital costs (CAPEX)

    Higher price of switchgear capable of autoreclose duty Additional control relay (Autoreclose & Check Sync)

    Improve System Stability Not traditionally considered at Distribution voltages

    Traditionally the distribution network was/is radial in design

    With modern networks (Embedded generation) a definiteconsideration

    Part of the SMART Grid

    What are the Benefits ?

  • 8/10/2019 DAR Lecture

    6/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 6 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Agenda

    1st topic Why Perform Auto-Reclose ? Page 3

    2nd topic Where can we apply Auto-Reclose ? Page 7

    3rd topic Terminology, Sequences & Settings Page 15

    4th topic Check Synchronism Page 46

    5th topic Conclusion Page 56

  • 8/10/2019 DAR Lecture

    7/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 7 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Where Can We Apply Auto-Reclose ?

    Type and relative quantities of Fault

    Type of Plant

    Circuit Breaker Capabilities

    HUMAN SAFETY

    On some areas of distribution networks, human safety will be theoverriding decision even when autoreclose seems applicable

    Consider overhead line feeders in sparsely populated areas

    What Dictates Application ?

  • 8/10/2019 DAR Lecture

    8/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 8 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Where Can We Apply Auto-Reclose ?

    Permanent Faults

    Require human intervention to resolve

    Successive re-energisations of the system will extend the damage

    Self Clearing Faults

    No permanent damage to the power system

    When cleared, the power system can be safely re-energised Further classification:

    Transient: Cleared by immediate isolation of the fault when the CB is

    opened

    Semi-Permanent: Cleared after a short time of isolation of the fault,

    when the cause of the fault has been burnt or blown away

    Fault Types

  • 8/10/2019 DAR Lecture

    9/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 9 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Where Can We Apply Auto-Reclose ?

    Transformers Most faults are PERMANENT and require investigation &

    rectification

    Machines (motors & generators)

    Most faults on machines are PERMANENT and requireinvestigation & rectification

    Underground Cables

    Most faults are considered as PERMANENT, require investigation& rectification

    Pecking faults may be self healing initially but consequential

    weakening of the insulation requires intervention

    Fault Types related to Plant Items

  • 8/10/2019 DAR Lecture

    10/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 10 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Where Can We Apply Auto-Reclose ?

    Overhead Lines Can have all fault types:

    Permanent: Broken Conductors or Insulators

    Transient: Insulator flashovers due to switching or lightning transient

    overvoltages, conductor clashing (due to high winds or ice shedding)

    Semi-Permanent: Phases bridged by animals or vegetation

    Relative incidence depends upon the voltage level as this dictatesthe spacing between conductors

    Typical figures are 80-85% transient, 5 to 10% semi-permanent and10% permanent

    Statistically, 70-90% of all faults are -E faults at EHV

    Fault Types related to Plant Items

  • 8/10/2019 DAR Lecture

    11/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 11

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Where Can We Apply Auto-Reclose ?

    Auto-Reclose is generally applied to Overhead Lines only Auto-Reclose on Mesh Busbar arrangements although controlling

    other CBs, only provides auto-reclose for line faults

    Auto-Reclose is generally not applied to Underground Cables,Transformers or Machines

    May be required for auto-reclose action on Mesh Busbararrangements

    May be required for auto-reclose action on embedded generation

    incomer circuits to restore connection to utility network (afternetwork faults)

    Fault Types related to Plant Items

  • 8/10/2019 DAR Lecture

    12/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 12

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Where Can We Apply Auto-Reclose ?

    In order for the system to be safe, it is considered that the CB must always becapable of achieving the open state safely ie tripping and breaking fault current

    Circuit Breakers are required to declare an operating or duty cycle by ANSI/IEEEand IEC standards, typically of the form

    O t CO t CO , where

    t is the minimum time between initial tripping before reclosure can be attempted t is the minimum time between subsequent tripping and reclosure events

    Not all current breaking devices are intended for auto-reclose application

    The times t and t will affect the settings for the auto-reclose relay and hence

    define whether auto-reclose can be effective

    Circuit Breaker Capability

  • 8/10/2019 DAR Lecture

    13/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 13

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Where Can We Apply Auto-Reclose ?

    Conventional OHL Application

    Protection relay & auto-reclose relayoperate for OHL faults only Control of single CB only

    Embedded Generation Application

    Protection relay used to disconnectgeneration for network faults eginterconnection (G59) protection

    Auto-reclose used to re-connectdistributed generation automaticallywhen network recovers

    Mesh Corner Application

    OHL protection relay triggers threeauto-reclose relays, including relay onLV side of transformer circuit

    Auto-reclose relays operate to restoresupply for transient faults

    Permanent (and transformer) faultscause auto-isolation prior to auto-reclose

    Examples of Auto-Reclose Applications

    PTOC

    RREC

    Simple OHL Application

    G59

    RREC

    Public

    Network

    Public

    Network

    Embedded

    Generation

    OHL Circuit

    Transformer Circuit

    RREC

    RRECRREC

    PDIS

  • 8/10/2019 DAR Lecture

    14/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 14

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Agenda

    1st topic Why Perform Auto-Reclose ? Page 3

    2nd topic Where can we apply Auto-Reclose ? Page 7

    3rd topic Terminology, Sequences & Settings Page 15

    4th topic Check Synchronism Page 46

    5th topic Conclusion Page 56

  • 8/10/2019 DAR Lecture

    15/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 15

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Successful Auto-Reclose for Transient Fault

    PTOC Fault

    RREC

    Trip

    Close

    Time (non-linear)

    Fault

    Inception Trip

    Contacts

    Separate

    End of

    Sequence

    Operating Time OperatedProtection Relay

    Circuit Breaker

    Opening

    Time

    Auto-Reclose Relay

    Closing

    Pulse

    Closing

    Time

    Closing

    Pulse

    Contacts

    Fully Closed

    CB Reclaim Time

    Reclaim Time

    Auto-Reclose in Progress (ARIP)

    Arc

    Extinguished

    Arcing

    Time

    CB Operating Time

    Fault Clearance Time

    Dead Time

    Protection

    Reset

    Contacts

    Fully Open

    Reset Time

    Dead Time

    Contacts

    Make

    Recovery Time

    Disturbance Time

    System

  • 8/10/2019 DAR Lecture

    16/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 16

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Unsuccessful Auto-Reclose for Permanent Fault

    PTOC Fault

    RREC

    Trip

    Close

    Time (non-linear)

    Fault

    Inception Trip

    Contacts

    Separate

    End of

    Sequence

    Operating Time OperatedProtection Relay

    Circuit Breaker

    Opening

    Time

    Auto-Reclose Relay

    Closing

    Pulse

    Closing

    Time

    Closing

    Pulse

    Contacts

    Fully Closed

    CB Reclaim Time

    Auto-Reclose in Progress (ARIP)

    Arc

    Extinguished

    Arcing

    Time

    CB Operating Time

    Fault Clearance Time

    Dead Time

    Protection

    Reset

    Contacts

    Fully Open

    Reset Time

    Dead Time

    Contacts

    Make

    onto

    Fault

    Recovery Time

    System

    Disturbance Time

    Contacts

    Separate

    Operating Time Operated

    Opening

    Time

    Arc

    Extinguished

    Arcing

    Time

    CB Operating Time

    Protection

    Reset

    Contacts

    Fully Open

    Reset Time

    Re-Trip

    Auto-RecloseLockout

    Reclaim Time

    Fault Clearance Time

  • 8/10/2019 DAR Lecture

    17/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 17

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    For system stability, the System Disturbance Time should beminimised Fast (instantaneous) Protection Short Dead Times

    High Speed Auto-Reclose (HSAR): Fault initiation to CB Closure is less than 1 second

    Low Speed or Delayed Auto-Reclose (DAR): Fault initiation to CB Closure is greater than 1 second (but often

    10s of seconds) Generally only applicable on highly interconnected systems (where

    system synchronism is maintained) or on single sourced, radialsystems

    Speed

  • 8/10/2019 DAR Lecture

    18/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 18

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Fast Protection is preferred to minimise system disturbance

    At higher voltages, fast, discriminating protection is normal Eg Line Differential, Phase Comparison, Directional Comparison,

    Distance (Z1 or Aided Schemes)

    At lower voltages, fast, discriminating protection may not beavailable but auto-reclose allows: Fast, non-discriminating (overreaching) protection for the initial

    trip cycle

    Eg Instantaneous OC/EF, Distance (Z1 Extension)

    Slower, discriminating protection for the final trip

    Eg IDMT Overcurrent/Earth Fault

    Protection

  • 8/10/2019 DAR Lecture

    19/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 19

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Fast (Non-discriminating) Z1X trip causes

    initial trip to cover 100% of line length fromboth ends

    Some possibility of tripping for adjacentlines

    After reclosure, the Z1X element is inhibited, sothat discriminating distance protection is used

    Advantage transient faults are cleared quickly

    Example of Auto-Reclose Application (Distance Z1 Extension)Z3

    Z3

    Z2

    Z2

    Z1X

    Z1X Z1

    Z1

    1

    t3Z3

    Trip

    &

    Z1 1

    Z2

    Z1X

    A/R

    t2Z2

    Z1

    Z1X

    A/R

    Trip 1

    t3 Z3

    Trip

    &

    Z11

    Z2

    Z1X

    A/R

    t2 Z2

    Z1

    Z1X

    A/R

    Trip

  • 8/10/2019 DAR Lecture

    20/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 20

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Sequence diagrams showed two Dead Times System Dead Time

    Time when arc goes out, to when CB contacts touch Relay Dead Time

    Typically from protection reset to start of close pulse

    For stability, the System Dead time must be minimised

    System Dead Time needs to consider:

    Load Type

    Protection Reset Time

    Fault De-ionisation Time

    Circuit Breaker Capabilities

    Dead Time

  • 8/10/2019 DAR Lecture

    21/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 21

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Predominantly Motors

    Induction machines will typically ride through 0.5s supply interruptions

    Synchronous machines will lose synchronism quickly, typically in less than0.3s

    Generally allow for 3-10s dead times (to allow UV isolation of machines)

    Street Lighting For safety (traffic, theft, violence) outages should be minimised, typically

    1-2 seconds

    Domestic

    Traditionally, could be long (measured in minutes)

    Modern systems impose penalties due to outages, therefore minimised(according to local legislation)

    Dead Time & Load Type

  • 8/10/2019 DAR Lecture

    22/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 22

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Embedded Generation Generally treated as a negative load Similar to motor considerations

    Minimum dead time to allow safe disconnection of generation

    Can be set much longer (minutes) to allow for system to stabiliseprior to reconnection

    Future systems cannot follow this approach

    Embedded generation will be required to stay on-line and ride

    through system faults as much as possible Reconnection will need to occur as quickly as safely possible

    Dead Time & Load Type

  • 8/10/2019 DAR Lecture

    23/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 23

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Usually the Auto-Reclose Dead time only starts when the

    protection trip resets Check scheme some simple schemes start the Dead Time earlier!

    Protection should fully reset during dead time

    Ensures that a fully discriminative trip can occur on reclosure

    Technology considerations

    Electromechanical (Induction Disc) relays had long resets(seconds)

    Static relays designed with Instantaneous Reset (

  • 8/10/2019 DAR Lecture

    24/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 24

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Must allow for the ionised air at the fault point to disperse Ionised air constitutes a conduction path

    De-ionisation time depends upon:

    System Voltage Type of Fault

    Current Weather Conditions

    Fault Clearance Time

    Difficult to establish an exact time

    Approximate formula is (10.5+KV/34.5) cycles

    For 66kV: 250ms (@50Hz); 210ms (@60Hz)

    For 132kV: 290ms (@50Hz); 240ms (@60Hz)

    Usually considered on HV systems only distribution systems have CBoperating time criteria that are more onerous

    Dead Time & Fault De-ionisation

  • 8/10/2019 DAR Lecture

    25/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 25

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    In order for the system to be safe, it is considered that the CB must always becapable of achieving the open state safely ie tripping and breaking faultcurrent

    Circuit Breakers are required to declare an operating or duty cycle by

    ANSI/IEEE and IEC standards, typically of the form O t CO t CO , where

    t is the minimum time between initial tripping before reclosure can be

    attempted

    t is the minimum time between subsequent tripping and reclosure events

    t defines the CB mechanism reset

    t may be more significant (if longer) for multi-shot schemes

    Dead Time & CB Capability

  • 8/10/2019 DAR Lecture

    26/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 26

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Mechanism Reset + Closing Time imposes a minimum systemdead time

    Significant for HSAR to satisfy stability requirements

    Most CBs have a trip free mechanism

    Tripping is the priority and can interrupt the closing stroke After tripping the trip free mechanism must be reset before

    attempting closure

    Dead Time & CB Capability

  • 8/10/2019 DAR Lecture

    27/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 27

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Dead Time & CB Capability

    Time (non-linear)

    Fault

    Inception Trip

    Contacts

    Separate

    Circuit Breaker

    Opening

    Time

    Closing

    Pulse

    Closing

    Time

    Contacts

    Fully Closed

    Arc

    Extinguished

    Arcing

    Time

    CB Operating Time

    Fault Clearance Time

    Contacts

    Fully Open

    Dead Time

    Contacts

    Make

    Recovery Time

    Disturbance Time

    System

    4012020107020T2 (msec)

    70110300550280240Minimum Dead Time (msec)

    60806535048160Closing Time (msec)

    10302352002380T1 (msec)

    5070456053100Operating Time (msec)

    204035303860Opening Time (msec)

    SF6380kV

    SF6132kV

    Air380kV

    Oil132kV

    Vacuum15kV

    Oil11kV

    T1 T2

  • 8/10/2019 DAR Lecture

    28/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 28

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Needs to be of sufficient duration to release the closingmechanism eg spring

    Usually a fixed pulse duration to ensure mechanism is fullyoperated

    Can be terminated by the CB auxiliary contact

    Anti-pumping is required to prevent repetitive open/close inquick succession when both trip & close circuits are active

    Trip circuit is given priority !

    Closing Pulse

  • 8/10/2019 DAR Lecture

    29/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 29

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    The Auto-Reclose device should not reset before the Protectionhas had time to operate, to ensure that permanent and semi-permanent faults are seen as part of the same Auto-Reclosesequence

    Set Reclaim Time > Maximum Protection Operating Time

    Set shorter reclaim time and inhibit its timing if a fault is detectedby use of a protection start signal

    Reclaim Timer settings need to consider:

    Supply Continuity

    Fault Incidence/Past Experience Switchgear Capability & Maintenance requirements

    Reclaim Time

  • 8/10/2019 DAR Lecture

    30/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 30

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Supply Continuity Setting a long reclaim time risks that separate fault events will be

    seen as the same fault and cause inadvertent lockout of the auto-reclose cycle

    Setting a short reclaim time imposes a risk that a permanent faultisnt detected

    The appropriate setting is largely dictated by knowledge of pastnetwork events

    Reclaim Time

  • 8/10/2019 DAR Lecture

    31/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 31

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Advantages

    Correctly identifies thepermanent fault condition &trips to lockout on thediscriminative (IDMT) trip

    Minimises CB duty

    Disadvantages

    Incorrectly identifies twosuccessive independent

    transient faults as a permanentfault condition

    Leads to unwanted lockout &unplanned outages

    Example of Long Reclaim Time Settings

    PIOC & PTOC Permanent

    FaultRREC

    Trip

    Close

    PIOC & PTOC F1

    RREC

    Trip

    Trip

    Close

    F2

    Time (non-linear)

    Fault

    Inception

    PIOC

    Trip

    CB Contacts

    Make onto Fault

    Arc

    Extinguished

    Arc

    Extinguished

    PTOC

    Trip &

    Lockout

    Reclaim Time >30s

    Maximum PTOC

    Time =30s

    Time (non-linear)

    Fault F1Inception PIOC

    Trip CB Contacts

    Make

    Arc

    Extinguished

    Arc

    Extinguished

    PTOC

    Trip &

    Lockout

    Reclaim Time >30s

    Maximum PTOC

    Time =30s

    Fault F2Inception

  • 8/10/2019 DAR Lecture

    32/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 32

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Advantages

    Correctly identifies thepermanent fault condition &trips to lockout on thediscriminative (IDMT) trip

    Correctly identifies twosuccessive independenttransient faults & recloses foreach

    Disadvantages

    Increased switchgear duty,

    especially in areas of frequentlightning

    May require remote Auto-Reclose Control

    Example of Short Reclaim Time Settings

    PIOC & PTOC Permanent

    FaultRREC

    Trip

    Close

    PIOC & PTOC F1

    RREC

    Trip

    Trip

    Close

    F2

    Time (non-linear)

    Fault

    Inception

    PIOC

    Trip

    CB Contacts

    Make onto Fault

    Arc

    Extinguished

    Arc

    Extinguished

    PTOC

    Trip &

    Lockout

    Reclaim Time Setting = 10s

    Maximum PTOC

    Time =30s

    Time (non-linear)

    Fault F1Inception PIOC

    Trip CB Contacts

    Make

    Arc

    Extinguished

    Arc

    Extinguished

    PIOC

    Trip

    Reclaim Time = 10s

    Fault F2Inception

    PTOC

    Start

    Reclaim Time Extended by Start signaloperation to allow Trip & Lockout

    CB Contacts

    Make

    Reclaim Time = 10s

  • 8/10/2019 DAR Lecture

    33/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 33

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    In order for the system to be safe, it is considered that the CB must always becapable of achieving the open state safely ie tripping and breaking faultcurrent

    Circuit Breakers are required to declare an operating or duty cycle byANSI/IEEE and IEC standards, typically of the form

    O t CO t CO , where t is the minimum time between initial tripping before reclosure can beattempted

    t is the minimum time between subsequent tripping and reclosure events

    t effectively imposes a minimum reclaim time as this is the taken to re-

    energise the breaker (spring winding, establish air pressure, etc) Usually a contact is made available to the auto-reclose device to indicate

    when the CB is ready for operation (Springs Charged) Used to inhibit reclosure until safe

    Reclaim Time & CB Capability

  • 8/10/2019 DAR Lecture

    34/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 34

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Theoretically, the Reclaim Time can be set

  • 8/10/2019 DAR Lecture

    35/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 35

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    In auto-reclose, every attempted reclosure of the CB is termed aShot

    Single shot schemes predominate at higher voltage levels

    Increased risk of plant damage for multiple shots

    Increased system disturbance and risk of stability issues

    Increased plant maintenance requirements

    At lower voltages (distribution), multi-shot schemes can be

    considered Use very dependent upon knowledge of faults on the network

    Number of Shots

  • 8/10/2019 DAR Lecture

    36/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 36

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Successful Auto-Reclose for Semi-Permanent Fault

    PTOC Fault

    RREC

    Trip

    Close

    Time (non-linear)

    Fault

    Inception Trip

    Contacts

    Separate

    End of

    Sequence

    Op. Time OperatedProtection Relay

    Circuit Breaker

    Opening

    Time

    Auto-Reclose Relay

    Closing

    Pulse

    Closing

    Time

    Closing

    Pulse

    Contacts

    Fully Closed

    Auto-Reclose in Progress (ARIP)

    Arc

    Extinguished

    Arcing

    Time

    CB Operating Time

    Fault Clearance Time

    Dead Time 1

    Protection

    Reset

    Contacts

    Fully Open

    Reset

    Dead Time

    Contacts

    Make

    onto

    Fault

    Recovery Time

    System

    Disturbance Time

    Contacts

    Separate

    Operated

    Opening

    Time

    Arc

    Extinguished

    Arcing

    Time

    CB Operating Time

    Protection

    Reset

    Contacts

    Fully Open

    Reset

    Re-Trip

    Reclaim Time

    Fault Clearance Time

    Op. Time

    Closing

    Pulse

    Closing

    Time

    Closing

    Pulse

    Contacts

    Fully Closed

    Dead Time 2

    Dead Time

    Contacts

    Make

    Reclaim Time

  • 8/10/2019 DAR Lecture

    37/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 37

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Typical experience from areas of frequent thunderstorms 83.25% are successful 1st Shot reclosures Additional 10.05% are successful for 2nd Shot reclosures

    (Dead Time 15-45s)

    Additional 1.42% are successful for 3rd

    Shot reclosures(Dead Time 120s)

    This suggest that 1 or 2 shot schemes are the most successfulwith limited benefit from further attempts

    Almost imposes minimal additional duty on switchgear

    Number of Shots

  • 8/10/2019 DAR Lecture

    38/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 38

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Benefits of Multi-Shot Auto-Reclose Improved Supply Continuity Helps prevent lockout during thunderstorms Systems with relatively high levels of semi-permanent faults

    First shot may be unsuccessful

    Second shot allows for the bridging material (vegetation or animal) to

    burn itself clear and give successful re-closure

    Helps on systems with fused spurs

    Promotes fuse operation for low fault levels Saves fuses for some transient faults

    Number of Shots

  • 8/10/2019 DAR Lecture

    39/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 39

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    For Permanent Faults with low IF

    Fuse may not blow before PTOC

    If fault reapplied during auto-reclose, the fuse will be pre-heated and may eventually blowbefore the PTOC element

    Maintains supply to most

    customers

    For Transient Faults

    PIOC element may operatebefore fuse

    Maintains supply to allcustomers after a briefinterruption (No need to replacefuse)

    Example of Multi-shot schemes with Fused Tees

    PIOC & PTOC

    Permanent

    Fault (Low IF)

    RREC

    Trip

    Close

    PIOC & PTOC

    Transient

    Fault (Low IF)

    RREC

    Trip

    Close

  • 8/10/2019 DAR Lecture

    40/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 40

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    If auto-reclosure is unsuccessful the auto-reclose device willlockout and prevent further reclose attempts. Other causesinclude: Failure of the CB to open & clear the fault when protection has

    operated

    Lack of CB energy within an acceptable time period

    Lack of synchronism when attempting reclosure Too many CB operations (maintenance) Too many CB operations in a defined period (Excessive Fault

    Frequency)

    Operation of protection that doesnt initiate auto-reclose (BARinput)

    Eg Busbar protection, VT Buchholz, etc

    Lockout

  • 8/10/2019 DAR Lecture

    41/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 41

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Once Lockout is attained, reset mechanisms include: Manual reset (either locally or via telecontrol) After Manual CB closure (either local or via telecontrol) usually

    with a time delay and/or detection of healthy load state for a

    period Automatically timed reset after lockout occurrence

    In all cases, the condition(s) causing lockout needs to have beenresolved

    Reset from Lockout

  • 8/10/2019 DAR Lecture

    42/57

  • 8/10/2019 DAR Lecture

    43/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 43

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    On LV networks, it is impossible to have switching stations at all requiredlocations

    Fused spurs are used

    Pole Mounted Reclosers (PMR) are used

    Upstream auto-reclose relays should discriminate with the installed PMRs

    Co-ordinate the reclose cycles

    Carefully select the auto-reclose sequences on both PMRs and switching stationsto ensure that the PMRs lockout for downstream faults.

    Utilise sequence co-ordination

    This ensures that the upstream auto-reclose device monitors but doesnt trip for

    downstream events which are controlled by the PMRs

    Upstream protection and auto-reclose only trips when PMR sequences have

    completed but without the need for additional reclose attempts

    Sequence Co-ordination

  • 8/10/2019 DAR Lecture

    44/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 44

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Terminology, Sequences & Settings

    Most schemes will have simple Auto-Reclose In/Out selection If remote selection, is possible then care should be taken

    Any local selection should override the remote selection

    Eg if a local user switches DAR out of service for testing purposes, to remainsafe it is necessary to ensure that the DAR can not be switched back intoservice remotely

    With Auto-Reclose switched out of service, non-discriminating protectionshould be blocked

    Eg Instantaneous elements, Distance Z1X

    If Live Line working is permitted Auto-Reclose should be switched out of service Auto-Reclose mode selection by telecontrol should be disabled All instantaneous (including non-discriminating) elements should be

    enabled

    Auto-Reclose Mode Selection

  • 8/10/2019 DAR Lecture

    45/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 45

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Agenda

    1st topic Why Perform Auto-Reclose ? Page 3

    2nd topic Where can we apply Auto-Reclose ? Page 7

    3rd topic Terminology, Sequences & Settings Page 15

    4th topic Check Synchronism Page 46

    5th topic Conclusion Page 56

  • 8/10/2019 DAR Lecture

    46/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 46

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Check Synchronism

    Check Sync refers to the check of voltages either side of a CB that is to bereclosed, either manually or during an auto-reclose cycle. It monitors

    Angle Difference the difference in phase angle between the voltages

    Slip Frequency the difference in frequency between the voltages Voltage Magnitude the absolute value of the voltage Voltage Difference the difference in magnitude between the voltages

    Combinations of these measurements are used to ascertain if it is safe to close theCB

    Check synchronism is usually measured on a single phase

    A Check Synchronism device only checks the status it doesnt issue control pulses

    to bring systems into synchronism Synchronising controls are issued from a Auto-Synchroniser, or manually

    Terminology

    h k h i

  • 8/10/2019 DAR Lecture

    47/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 47

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Check Synchronism

    Line Voltage is the voltage measured on the protected circuit Measured from a circuit VT

    Bus Voltage is the voltage measured behind the protected circuit

    Measured from a busbar VT, or from a suitable circuit VT via a

    voltage selection scheme

    Generally we consider the Bus Voltage as the reference with the

    Line Voltage rotating relative to it

    Terminology

    Ch k S h i

  • 8/10/2019 DAR Lecture

    48/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 48

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Check Synchronism

    Dead Voltage is when the measurementindicates a de-energised state

    Live Voltage is when the measurementindicates an energised state

    Voltages between the Dead and Livevoltage bands are undefined

    For In Sync or System Splitmeasurement both voltages must be Live

    In Synchronism is when the voltages areless than X apart

    System Split is when the voltages are

    180 apart On System Split detection the

    criteria for permitting closure maychange

    Terminology

    NominalVolts

    Live Volts

    Dead Volts

    VBUS

    VLINE

    0

    180

    In Sync

    Region

    System

    Split

    Region

    Ch k S h i

  • 8/10/2019 DAR Lecture

    49/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 49

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Check Synchronism

    To permit CB closure during an auto-reclose cycle it will often be necessary toconfirm that the voltages either side of the breaker are suitable

    The Check Synchronism device performs this task. Suitable states for closureare one or more of the following:

    In Sync - when both voltages are Live and within X apart Dead Line Charging when the Bus voltage is live and the Line voltage

    is dead Dead Bus Charging when the Line voltage is live and the Bus voltage

    is dead

    When the Line and Bus voltages are both dead (less common) For the In Sync condition, the dead time may be shortened or even ignored

    Check Synchronism & Auto-Reclose

    Ch k S h i

  • 8/10/2019 DAR Lecture

    50/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 50

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Check Synchronism

    IEC61850 (parts -5 and 7-4) both include

    Check Synchronising as a Protection Related

    function, with a logical node name of RSYN

    End X attempts to reclose first after 5 seconds,

    to charge the dead line

    If reclose is successful, End Y will

    immediately reclose assuming an In

    Sync condition is measured If reclose is unsuccessful, End Y will

    reclose after a further 10s, to charge the

    dead line

    End X is the permitted to reclose

    assuming an In Sync condition is

    measured Typical Dead Line Charge settings are in the

    range of 5s to 60s

    Revertive Dead Line Charging

    PIOC & PTOC

    RREC

    Trip

    Close

    PIOC & PTOC

    RREC

    Trip

    Close

    RSYNRSYN

    End X End Y

    Dead Line Charge

    Time = 5s

    Dead Line Charge

    Time = 15s

    Check Synchronism

  • 8/10/2019 DAR Lecture

    51/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 51

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Check Synchronism

    With the voltage in the In Sync region,contact closure of the breaker can occur with

    some phase angle difference

    Some Check Synchronism elements have aPredictive Closure facility

    Monitors the frequency of rotation ofthe vectors

    With knowledge of the CB closingtime, it predicts when to issue theclosing pulse such that contact closureoccurs when the phase angledifference is virtually 0

    This places less stress on the CB andthe system but may delay the overalltime to closure

    Predictive Closure

    NominalVolts

    Live Volts

    Dead Volts

    VBUS

    VLINE

    0

    180

    In Sync

    Region

    System

    Split

    Region

    Predictive Closure

    Region. Close pulse

    issued to promote

    closure at top dead

    centre

    Check Synchronism

  • 8/10/2019 DAR Lecture

    52/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 52

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Check Synchronism

    At some point, two vectors rotating at different frequencies will have little orno phase angle

    Some customers perceive a risk that the check synchronism could be defeatedat Manual Closure by maintaining the close command and waiting for the insynchronism signal . Risk is overcome by:-

    Use of Slip Frequency measurement & blocking, and/or

    Use of Guard Relays

    An additional perceived risk, is that the output contacts of the check syncrelay could be damaged and hence give erroneous in synchronism signals

    Risk overcome by use of additional logic that prevents the output being

    used if it is present before the request to close

    With modern numeric relays and Programmable Scheme Logic, thesefacilities can all be mimicked and the risk negated

    Concerns with Check Synchronism

    Check Synchronism

  • 8/10/2019 DAR Lecture

    53/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 53

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Check Synchronism

    Concerns of Damaged Check Synch Relay

    Check Synchronism

  • 8/10/2019 DAR Lecture

    54/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 54

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Check Synchronism

    Implementation in Modern Numeric Relay

    Agenda

  • 8/10/2019 DAR Lecture

    55/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 55

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Agenda

    1st topic Why Perform Auto-Reclose ? Page 3

    2nd topic Where can we apply Auto-Reclose ? Page 7

    3rd topic Terminology, Sequences & Settings Page 15

    4th topic Check Synchronism Page 46

    5th topic Conclusion Page 56

    Auto-Reclose on Distribution Networks

  • 8/10/2019 DAR Lecture

    56/57

    Auto-Reclose on Distribution Networks MStockton 2012 - P 56

    ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

    Auto Reclose on Distribution Networks

    Traditionally this has been limited to Delayed Auto-Reclose withlittle or no concern for synchronism check or stability

    Modern networks are pushing for more efficient use of thenetwork, with fewer and shorter supply interruptions

    Increase requirement for Check Synchronism

    Use of faster protection, shorter dead times and reclaim times

    Scheme settings are largely dependent upon network faulthistory

    CB Capability and understanding has a large impact on possibleauto-reclose scheme selection & settings

    Conclusions

  • 8/10/2019 DAR Lecture

    57/57

    www.alstom.com