DAR Lecture
-
Upload
neelakandan-masilamani -
Category
Documents
-
view
224 -
download
0
Transcript of DAR Lecture
-
8/10/2019 DAR Lecture
1/57
Auto-Reclose onDistribution Networks
-
8/10/2019 DAR Lecture
2/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 2 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Agenda
1st topic Why Perform Auto-Reclose ? Page 3
2nd topic Where can we apply Auto-Reclose ? Page 7
3rd topic Terminology, Sequences & Settings Page 15
4th topic Check Synchronism Page 46
5th topic Conclusion Page 56
-
8/10/2019 DAR Lecture
3/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 3 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Why Perform Auto-Reclose ?
Auto-Reclose is the automatic closure
of a Circuit Breaker without theintervention of a person
It is a Control Technique
IEC61850 (parts -5 and 7-4) bothinclude autoreclose as a ProtectionRelated function, with a logical nodename of RREC
ANSI / IEEE C37.2 reference 79
IEC 60617 symbol:
What is Auto-Reclose
O I
PTOC
RREC
PTOC Fault
RREC
PTOC Fault
RREC
Pre-Fault
Trip
Reclose
Trip
Close
-
8/10/2019 DAR Lecture
4/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 4 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Why Perform Auto-Reclose ?
Continuity of Supply Restoration is Automatic, therefore quicker Shorter duration of Power Outages
Fewer Customer Minutes Lost
Reduced Asset Damage
Autoreclose permits use of faster, non-discriminative protection Some overtripping is deemed acceptable
Less chance of faults evolving to more damaging scenarios
Lower pre-heating of CB contacts May reduce maintenance requirements ?
What are the Benefits ?
-
8/10/2019 DAR Lecture
5/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 5 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Why Perform Auto-Reclose ?
Reduction in Operating Costs (OPEX) Reduced requirement for substation visits Reduction in damage of asset Increase in capital costs (CAPEX)
Higher price of switchgear capable of autoreclose duty Additional control relay (Autoreclose & Check Sync)
Improve System Stability Not traditionally considered at Distribution voltages
Traditionally the distribution network was/is radial in design
With modern networks (Embedded generation) a definiteconsideration
Part of the SMART Grid
What are the Benefits ?
-
8/10/2019 DAR Lecture
6/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 6 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Agenda
1st topic Why Perform Auto-Reclose ? Page 3
2nd topic Where can we apply Auto-Reclose ? Page 7
3rd topic Terminology, Sequences & Settings Page 15
4th topic Check Synchronism Page 46
5th topic Conclusion Page 56
-
8/10/2019 DAR Lecture
7/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 7 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Where Can We Apply Auto-Reclose ?
Type and relative quantities of Fault
Type of Plant
Circuit Breaker Capabilities
HUMAN SAFETY
On some areas of distribution networks, human safety will be theoverriding decision even when autoreclose seems applicable
Consider overhead line feeders in sparsely populated areas
What Dictates Application ?
-
8/10/2019 DAR Lecture
8/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 8 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Where Can We Apply Auto-Reclose ?
Permanent Faults
Require human intervention to resolve
Successive re-energisations of the system will extend the damage
Self Clearing Faults
No permanent damage to the power system
When cleared, the power system can be safely re-energised Further classification:
Transient: Cleared by immediate isolation of the fault when the CB is
opened
Semi-Permanent: Cleared after a short time of isolation of the fault,
when the cause of the fault has been burnt or blown away
Fault Types
-
8/10/2019 DAR Lecture
9/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 9 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Where Can We Apply Auto-Reclose ?
Transformers Most faults are PERMANENT and require investigation &
rectification
Machines (motors & generators)
Most faults on machines are PERMANENT and requireinvestigation & rectification
Underground Cables
Most faults are considered as PERMANENT, require investigation& rectification
Pecking faults may be self healing initially but consequential
weakening of the insulation requires intervention
Fault Types related to Plant Items
-
8/10/2019 DAR Lecture
10/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 10 ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Where Can We Apply Auto-Reclose ?
Overhead Lines Can have all fault types:
Permanent: Broken Conductors or Insulators
Transient: Insulator flashovers due to switching or lightning transient
overvoltages, conductor clashing (due to high winds or ice shedding)
Semi-Permanent: Phases bridged by animals or vegetation
Relative incidence depends upon the voltage level as this dictatesthe spacing between conductors
Typical figures are 80-85% transient, 5 to 10% semi-permanent and10% permanent
Statistically, 70-90% of all faults are -E faults at EHV
Fault Types related to Plant Items
-
8/10/2019 DAR Lecture
11/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 11
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Where Can We Apply Auto-Reclose ?
Auto-Reclose is generally applied to Overhead Lines only Auto-Reclose on Mesh Busbar arrangements although controlling
other CBs, only provides auto-reclose for line faults
Auto-Reclose is generally not applied to Underground Cables,Transformers or Machines
May be required for auto-reclose action on Mesh Busbararrangements
May be required for auto-reclose action on embedded generation
incomer circuits to restore connection to utility network (afternetwork faults)
Fault Types related to Plant Items
-
8/10/2019 DAR Lecture
12/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 12
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Where Can We Apply Auto-Reclose ?
In order for the system to be safe, it is considered that the CB must always becapable of achieving the open state safely ie tripping and breaking fault current
Circuit Breakers are required to declare an operating or duty cycle by ANSI/IEEEand IEC standards, typically of the form
O t CO t CO , where
t is the minimum time between initial tripping before reclosure can be attempted t is the minimum time between subsequent tripping and reclosure events
Not all current breaking devices are intended for auto-reclose application
The times t and t will affect the settings for the auto-reclose relay and hence
define whether auto-reclose can be effective
Circuit Breaker Capability
-
8/10/2019 DAR Lecture
13/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 13
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Where Can We Apply Auto-Reclose ?
Conventional OHL Application
Protection relay & auto-reclose relayoperate for OHL faults only Control of single CB only
Embedded Generation Application
Protection relay used to disconnectgeneration for network faults eginterconnection (G59) protection
Auto-reclose used to re-connectdistributed generation automaticallywhen network recovers
Mesh Corner Application
OHL protection relay triggers threeauto-reclose relays, including relay onLV side of transformer circuit
Auto-reclose relays operate to restoresupply for transient faults
Permanent (and transformer) faultscause auto-isolation prior to auto-reclose
Examples of Auto-Reclose Applications
PTOC
RREC
Simple OHL Application
G59
RREC
Public
Network
Public
Network
Embedded
Generation
OHL Circuit
Transformer Circuit
RREC
RRECRREC
PDIS
-
8/10/2019 DAR Lecture
14/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 14
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Agenda
1st topic Why Perform Auto-Reclose ? Page 3
2nd topic Where can we apply Auto-Reclose ? Page 7
3rd topic Terminology, Sequences & Settings Page 15
4th topic Check Synchronism Page 46
5th topic Conclusion Page 56
-
8/10/2019 DAR Lecture
15/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 15
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Successful Auto-Reclose for Transient Fault
PTOC Fault
RREC
Trip
Close
Time (non-linear)
Fault
Inception Trip
Contacts
Separate
End of
Sequence
Operating Time OperatedProtection Relay
Circuit Breaker
Opening
Time
Auto-Reclose Relay
Closing
Pulse
Closing
Time
Closing
Pulse
Contacts
Fully Closed
CB Reclaim Time
Reclaim Time
Auto-Reclose in Progress (ARIP)
Arc
Extinguished
Arcing
Time
CB Operating Time
Fault Clearance Time
Dead Time
Protection
Reset
Contacts
Fully Open
Reset Time
Dead Time
Contacts
Make
Recovery Time
Disturbance Time
System
-
8/10/2019 DAR Lecture
16/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 16
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Unsuccessful Auto-Reclose for Permanent Fault
PTOC Fault
RREC
Trip
Close
Time (non-linear)
Fault
Inception Trip
Contacts
Separate
End of
Sequence
Operating Time OperatedProtection Relay
Circuit Breaker
Opening
Time
Auto-Reclose Relay
Closing
Pulse
Closing
Time
Closing
Pulse
Contacts
Fully Closed
CB Reclaim Time
Auto-Reclose in Progress (ARIP)
Arc
Extinguished
Arcing
Time
CB Operating Time
Fault Clearance Time
Dead Time
Protection
Reset
Contacts
Fully Open
Reset Time
Dead Time
Contacts
Make
onto
Fault
Recovery Time
System
Disturbance Time
Contacts
Separate
Operating Time Operated
Opening
Time
Arc
Extinguished
Arcing
Time
CB Operating Time
Protection
Reset
Contacts
Fully Open
Reset Time
Re-Trip
Auto-RecloseLockout
Reclaim Time
Fault Clearance Time
-
8/10/2019 DAR Lecture
17/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 17
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
For system stability, the System Disturbance Time should beminimised Fast (instantaneous) Protection Short Dead Times
High Speed Auto-Reclose (HSAR): Fault initiation to CB Closure is less than 1 second
Low Speed or Delayed Auto-Reclose (DAR): Fault initiation to CB Closure is greater than 1 second (but often
10s of seconds) Generally only applicable on highly interconnected systems (where
system synchronism is maintained) or on single sourced, radialsystems
Speed
-
8/10/2019 DAR Lecture
18/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 18
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Fast Protection is preferred to minimise system disturbance
At higher voltages, fast, discriminating protection is normal Eg Line Differential, Phase Comparison, Directional Comparison,
Distance (Z1 or Aided Schemes)
At lower voltages, fast, discriminating protection may not beavailable but auto-reclose allows: Fast, non-discriminating (overreaching) protection for the initial
trip cycle
Eg Instantaneous OC/EF, Distance (Z1 Extension)
Slower, discriminating protection for the final trip
Eg IDMT Overcurrent/Earth Fault
Protection
-
8/10/2019 DAR Lecture
19/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 19
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Fast (Non-discriminating) Z1X trip causes
initial trip to cover 100% of line length fromboth ends
Some possibility of tripping for adjacentlines
After reclosure, the Z1X element is inhibited, sothat discriminating distance protection is used
Advantage transient faults are cleared quickly
Example of Auto-Reclose Application (Distance Z1 Extension)Z3
Z3
Z2
Z2
Z1X
Z1X Z1
Z1
1
t3Z3
Trip
&
Z1 1
Z2
Z1X
A/R
t2Z2
Z1
Z1X
A/R
Trip 1
t3 Z3
Trip
&
Z11
Z2
Z1X
A/R
t2 Z2
Z1
Z1X
A/R
Trip
-
8/10/2019 DAR Lecture
20/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 20
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Sequence diagrams showed two Dead Times System Dead Time
Time when arc goes out, to when CB contacts touch Relay Dead Time
Typically from protection reset to start of close pulse
For stability, the System Dead time must be minimised
System Dead Time needs to consider:
Load Type
Protection Reset Time
Fault De-ionisation Time
Circuit Breaker Capabilities
Dead Time
-
8/10/2019 DAR Lecture
21/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 21
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Predominantly Motors
Induction machines will typically ride through 0.5s supply interruptions
Synchronous machines will lose synchronism quickly, typically in less than0.3s
Generally allow for 3-10s dead times (to allow UV isolation of machines)
Street Lighting For safety (traffic, theft, violence) outages should be minimised, typically
1-2 seconds
Domestic
Traditionally, could be long (measured in minutes)
Modern systems impose penalties due to outages, therefore minimised(according to local legislation)
Dead Time & Load Type
-
8/10/2019 DAR Lecture
22/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 22
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Embedded Generation Generally treated as a negative load Similar to motor considerations
Minimum dead time to allow safe disconnection of generation
Can be set much longer (minutes) to allow for system to stabiliseprior to reconnection
Future systems cannot follow this approach
Embedded generation will be required to stay on-line and ride
through system faults as much as possible Reconnection will need to occur as quickly as safely possible
Dead Time & Load Type
-
8/10/2019 DAR Lecture
23/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 23
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Usually the Auto-Reclose Dead time only starts when the
protection trip resets Check scheme some simple schemes start the Dead Time earlier!
Protection should fully reset during dead time
Ensures that a fully discriminative trip can occur on reclosure
Technology considerations
Electromechanical (Induction Disc) relays had long resets(seconds)
Static relays designed with Instantaneous Reset (
-
8/10/2019 DAR Lecture
24/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 24
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Must allow for the ionised air at the fault point to disperse Ionised air constitutes a conduction path
De-ionisation time depends upon:
System Voltage Type of Fault
Current Weather Conditions
Fault Clearance Time
Difficult to establish an exact time
Approximate formula is (10.5+KV/34.5) cycles
For 66kV: 250ms (@50Hz); 210ms (@60Hz)
For 132kV: 290ms (@50Hz); 240ms (@60Hz)
Usually considered on HV systems only distribution systems have CBoperating time criteria that are more onerous
Dead Time & Fault De-ionisation
-
8/10/2019 DAR Lecture
25/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 25
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
In order for the system to be safe, it is considered that the CB must always becapable of achieving the open state safely ie tripping and breaking faultcurrent
Circuit Breakers are required to declare an operating or duty cycle by
ANSI/IEEE and IEC standards, typically of the form O t CO t CO , where
t is the minimum time between initial tripping before reclosure can be
attempted
t is the minimum time between subsequent tripping and reclosure events
t defines the CB mechanism reset
t may be more significant (if longer) for multi-shot schemes
Dead Time & CB Capability
-
8/10/2019 DAR Lecture
26/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 26
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Mechanism Reset + Closing Time imposes a minimum systemdead time
Significant for HSAR to satisfy stability requirements
Most CBs have a trip free mechanism
Tripping is the priority and can interrupt the closing stroke After tripping the trip free mechanism must be reset before
attempting closure
Dead Time & CB Capability
-
8/10/2019 DAR Lecture
27/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 27
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Dead Time & CB Capability
Time (non-linear)
Fault
Inception Trip
Contacts
Separate
Circuit Breaker
Opening
Time
Closing
Pulse
Closing
Time
Contacts
Fully Closed
Arc
Extinguished
Arcing
Time
CB Operating Time
Fault Clearance Time
Contacts
Fully Open
Dead Time
Contacts
Make
Recovery Time
Disturbance Time
System
4012020107020T2 (msec)
70110300550280240Minimum Dead Time (msec)
60806535048160Closing Time (msec)
10302352002380T1 (msec)
5070456053100Operating Time (msec)
204035303860Opening Time (msec)
SF6380kV
SF6132kV
Air380kV
Oil132kV
Vacuum15kV
Oil11kV
T1 T2
-
8/10/2019 DAR Lecture
28/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 28
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Needs to be of sufficient duration to release the closingmechanism eg spring
Usually a fixed pulse duration to ensure mechanism is fullyoperated
Can be terminated by the CB auxiliary contact
Anti-pumping is required to prevent repetitive open/close inquick succession when both trip & close circuits are active
Trip circuit is given priority !
Closing Pulse
-
8/10/2019 DAR Lecture
29/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 29
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
The Auto-Reclose device should not reset before the Protectionhas had time to operate, to ensure that permanent and semi-permanent faults are seen as part of the same Auto-Reclosesequence
Set Reclaim Time > Maximum Protection Operating Time
Set shorter reclaim time and inhibit its timing if a fault is detectedby use of a protection start signal
Reclaim Timer settings need to consider:
Supply Continuity
Fault Incidence/Past Experience Switchgear Capability & Maintenance requirements
Reclaim Time
-
8/10/2019 DAR Lecture
30/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 30
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Supply Continuity Setting a long reclaim time risks that separate fault events will be
seen as the same fault and cause inadvertent lockout of the auto-reclose cycle
Setting a short reclaim time imposes a risk that a permanent faultisnt detected
The appropriate setting is largely dictated by knowledge of pastnetwork events
Reclaim Time
-
8/10/2019 DAR Lecture
31/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 31
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Advantages
Correctly identifies thepermanent fault condition &trips to lockout on thediscriminative (IDMT) trip
Minimises CB duty
Disadvantages
Incorrectly identifies twosuccessive independent
transient faults as a permanentfault condition
Leads to unwanted lockout &unplanned outages
Example of Long Reclaim Time Settings
PIOC & PTOC Permanent
FaultRREC
Trip
Close
PIOC & PTOC F1
RREC
Trip
Trip
Close
F2
Time (non-linear)
Fault
Inception
PIOC
Trip
CB Contacts
Make onto Fault
Arc
Extinguished
Arc
Extinguished
PTOC
Trip &
Lockout
Reclaim Time >30s
Maximum PTOC
Time =30s
Time (non-linear)
Fault F1Inception PIOC
Trip CB Contacts
Make
Arc
Extinguished
Arc
Extinguished
PTOC
Trip &
Lockout
Reclaim Time >30s
Maximum PTOC
Time =30s
Fault F2Inception
-
8/10/2019 DAR Lecture
32/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 32
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Advantages
Correctly identifies thepermanent fault condition &trips to lockout on thediscriminative (IDMT) trip
Correctly identifies twosuccessive independenttransient faults & recloses foreach
Disadvantages
Increased switchgear duty,
especially in areas of frequentlightning
May require remote Auto-Reclose Control
Example of Short Reclaim Time Settings
PIOC & PTOC Permanent
FaultRREC
Trip
Close
PIOC & PTOC F1
RREC
Trip
Trip
Close
F2
Time (non-linear)
Fault
Inception
PIOC
Trip
CB Contacts
Make onto Fault
Arc
Extinguished
Arc
Extinguished
PTOC
Trip &
Lockout
Reclaim Time Setting = 10s
Maximum PTOC
Time =30s
Time (non-linear)
Fault F1Inception PIOC
Trip CB Contacts
Make
Arc
Extinguished
Arc
Extinguished
PIOC
Trip
Reclaim Time = 10s
Fault F2Inception
PTOC
Start
Reclaim Time Extended by Start signaloperation to allow Trip & Lockout
CB Contacts
Make
Reclaim Time = 10s
-
8/10/2019 DAR Lecture
33/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 33
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
In order for the system to be safe, it is considered that the CB must always becapable of achieving the open state safely ie tripping and breaking faultcurrent
Circuit Breakers are required to declare an operating or duty cycle byANSI/IEEE and IEC standards, typically of the form
O t CO t CO , where t is the minimum time between initial tripping before reclosure can beattempted
t is the minimum time between subsequent tripping and reclosure events
t effectively imposes a minimum reclaim time as this is the taken to re-
energise the breaker (spring winding, establish air pressure, etc) Usually a contact is made available to the auto-reclose device to indicate
when the CB is ready for operation (Springs Charged) Used to inhibit reclosure until safe
Reclaim Time & CB Capability
-
8/10/2019 DAR Lecture
34/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 34
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Theoretically, the Reclaim Time can be set
-
8/10/2019 DAR Lecture
35/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 35
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
In auto-reclose, every attempted reclosure of the CB is termed aShot
Single shot schemes predominate at higher voltage levels
Increased risk of plant damage for multiple shots
Increased system disturbance and risk of stability issues
Increased plant maintenance requirements
At lower voltages (distribution), multi-shot schemes can be
considered Use very dependent upon knowledge of faults on the network
Number of Shots
-
8/10/2019 DAR Lecture
36/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 36
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Successful Auto-Reclose for Semi-Permanent Fault
PTOC Fault
RREC
Trip
Close
Time (non-linear)
Fault
Inception Trip
Contacts
Separate
End of
Sequence
Op. Time OperatedProtection Relay
Circuit Breaker
Opening
Time
Auto-Reclose Relay
Closing
Pulse
Closing
Time
Closing
Pulse
Contacts
Fully Closed
Auto-Reclose in Progress (ARIP)
Arc
Extinguished
Arcing
Time
CB Operating Time
Fault Clearance Time
Dead Time 1
Protection
Reset
Contacts
Fully Open
Reset
Dead Time
Contacts
Make
onto
Fault
Recovery Time
System
Disturbance Time
Contacts
Separate
Operated
Opening
Time
Arc
Extinguished
Arcing
Time
CB Operating Time
Protection
Reset
Contacts
Fully Open
Reset
Re-Trip
Reclaim Time
Fault Clearance Time
Op. Time
Closing
Pulse
Closing
Time
Closing
Pulse
Contacts
Fully Closed
Dead Time 2
Dead Time
Contacts
Make
Reclaim Time
-
8/10/2019 DAR Lecture
37/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 37
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Typical experience from areas of frequent thunderstorms 83.25% are successful 1st Shot reclosures Additional 10.05% are successful for 2nd Shot reclosures
(Dead Time 15-45s)
Additional 1.42% are successful for 3rd
Shot reclosures(Dead Time 120s)
This suggest that 1 or 2 shot schemes are the most successfulwith limited benefit from further attempts
Almost imposes minimal additional duty on switchgear
Number of Shots
-
8/10/2019 DAR Lecture
38/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 38
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Benefits of Multi-Shot Auto-Reclose Improved Supply Continuity Helps prevent lockout during thunderstorms Systems with relatively high levels of semi-permanent faults
First shot may be unsuccessful
Second shot allows for the bridging material (vegetation or animal) to
burn itself clear and give successful re-closure
Helps on systems with fused spurs
Promotes fuse operation for low fault levels Saves fuses for some transient faults
Number of Shots
-
8/10/2019 DAR Lecture
39/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 39
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
For Permanent Faults with low IF
Fuse may not blow before PTOC
If fault reapplied during auto-reclose, the fuse will be pre-heated and may eventually blowbefore the PTOC element
Maintains supply to most
customers
For Transient Faults
PIOC element may operatebefore fuse
Maintains supply to allcustomers after a briefinterruption (No need to replacefuse)
Example of Multi-shot schemes with Fused Tees
PIOC & PTOC
Permanent
Fault (Low IF)
RREC
Trip
Close
PIOC & PTOC
Transient
Fault (Low IF)
RREC
Trip
Close
-
8/10/2019 DAR Lecture
40/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 40
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
If auto-reclosure is unsuccessful the auto-reclose device willlockout and prevent further reclose attempts. Other causesinclude: Failure of the CB to open & clear the fault when protection has
operated
Lack of CB energy within an acceptable time period
Lack of synchronism when attempting reclosure Too many CB operations (maintenance) Too many CB operations in a defined period (Excessive Fault
Frequency)
Operation of protection that doesnt initiate auto-reclose (BARinput)
Eg Busbar protection, VT Buchholz, etc
Lockout
-
8/10/2019 DAR Lecture
41/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 41
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Once Lockout is attained, reset mechanisms include: Manual reset (either locally or via telecontrol) After Manual CB closure (either local or via telecontrol) usually
with a time delay and/or detection of healthy load state for a
period Automatically timed reset after lockout occurrence
In all cases, the condition(s) causing lockout needs to have beenresolved
Reset from Lockout
-
8/10/2019 DAR Lecture
42/57
-
8/10/2019 DAR Lecture
43/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 43
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
On LV networks, it is impossible to have switching stations at all requiredlocations
Fused spurs are used
Pole Mounted Reclosers (PMR) are used
Upstream auto-reclose relays should discriminate with the installed PMRs
Co-ordinate the reclose cycles
Carefully select the auto-reclose sequences on both PMRs and switching stationsto ensure that the PMRs lockout for downstream faults.
Utilise sequence co-ordination
This ensures that the upstream auto-reclose device monitors but doesnt trip for
downstream events which are controlled by the PMRs
Upstream protection and auto-reclose only trips when PMR sequences have
completed but without the need for additional reclose attempts
Sequence Co-ordination
-
8/10/2019 DAR Lecture
44/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 44
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Terminology, Sequences & Settings
Most schemes will have simple Auto-Reclose In/Out selection If remote selection, is possible then care should be taken
Any local selection should override the remote selection
Eg if a local user switches DAR out of service for testing purposes, to remainsafe it is necessary to ensure that the DAR can not be switched back intoservice remotely
With Auto-Reclose switched out of service, non-discriminating protectionshould be blocked
Eg Instantaneous elements, Distance Z1X
If Live Line working is permitted Auto-Reclose should be switched out of service Auto-Reclose mode selection by telecontrol should be disabled All instantaneous (including non-discriminating) elements should be
enabled
Auto-Reclose Mode Selection
-
8/10/2019 DAR Lecture
45/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 45
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Agenda
1st topic Why Perform Auto-Reclose ? Page 3
2nd topic Where can we apply Auto-Reclose ? Page 7
3rd topic Terminology, Sequences & Settings Page 15
4th topic Check Synchronism Page 46
5th topic Conclusion Page 56
-
8/10/2019 DAR Lecture
46/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 46
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Check Synchronism
Check Sync refers to the check of voltages either side of a CB that is to bereclosed, either manually or during an auto-reclose cycle. It monitors
Angle Difference the difference in phase angle between the voltages
Slip Frequency the difference in frequency between the voltages Voltage Magnitude the absolute value of the voltage Voltage Difference the difference in magnitude between the voltages
Combinations of these measurements are used to ascertain if it is safe to close theCB
Check synchronism is usually measured on a single phase
A Check Synchronism device only checks the status it doesnt issue control pulses
to bring systems into synchronism Synchronising controls are issued from a Auto-Synchroniser, or manually
Terminology
h k h i
-
8/10/2019 DAR Lecture
47/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 47
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Check Synchronism
Line Voltage is the voltage measured on the protected circuit Measured from a circuit VT
Bus Voltage is the voltage measured behind the protected circuit
Measured from a busbar VT, or from a suitable circuit VT via a
voltage selection scheme
Generally we consider the Bus Voltage as the reference with the
Line Voltage rotating relative to it
Terminology
Ch k S h i
-
8/10/2019 DAR Lecture
48/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 48
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Check Synchronism
Dead Voltage is when the measurementindicates a de-energised state
Live Voltage is when the measurementindicates an energised state
Voltages between the Dead and Livevoltage bands are undefined
For In Sync or System Splitmeasurement both voltages must be Live
In Synchronism is when the voltages areless than X apart
System Split is when the voltages are
180 apart On System Split detection the
criteria for permitting closure maychange
Terminology
NominalVolts
Live Volts
Dead Volts
VBUS
VLINE
0
180
In Sync
Region
System
Split
Region
Ch k S h i
-
8/10/2019 DAR Lecture
49/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 49
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Check Synchronism
To permit CB closure during an auto-reclose cycle it will often be necessary toconfirm that the voltages either side of the breaker are suitable
The Check Synchronism device performs this task. Suitable states for closureare one or more of the following:
In Sync - when both voltages are Live and within X apart Dead Line Charging when the Bus voltage is live and the Line voltage
is dead Dead Bus Charging when the Line voltage is live and the Bus voltage
is dead
When the Line and Bus voltages are both dead (less common) For the In Sync condition, the dead time may be shortened or even ignored
Check Synchronism & Auto-Reclose
Ch k S h i
-
8/10/2019 DAR Lecture
50/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 50
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Check Synchronism
IEC61850 (parts -5 and 7-4) both include
Check Synchronising as a Protection Related
function, with a logical node name of RSYN
End X attempts to reclose first after 5 seconds,
to charge the dead line
If reclose is successful, End Y will
immediately reclose assuming an In
Sync condition is measured If reclose is unsuccessful, End Y will
reclose after a further 10s, to charge the
dead line
End X is the permitted to reclose
assuming an In Sync condition is
measured Typical Dead Line Charge settings are in the
range of 5s to 60s
Revertive Dead Line Charging
PIOC & PTOC
RREC
Trip
Close
PIOC & PTOC
RREC
Trip
Close
RSYNRSYN
End X End Y
Dead Line Charge
Time = 5s
Dead Line Charge
Time = 15s
Check Synchronism
-
8/10/2019 DAR Lecture
51/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 51
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Check Synchronism
With the voltage in the In Sync region,contact closure of the breaker can occur with
some phase angle difference
Some Check Synchronism elements have aPredictive Closure facility
Monitors the frequency of rotation ofthe vectors
With knowledge of the CB closingtime, it predicts when to issue theclosing pulse such that contact closureoccurs when the phase angledifference is virtually 0
This places less stress on the CB andthe system but may delay the overalltime to closure
Predictive Closure
NominalVolts
Live Volts
Dead Volts
VBUS
VLINE
0
180
In Sync
Region
System
Split
Region
Predictive Closure
Region. Close pulse
issued to promote
closure at top dead
centre
Check Synchronism
-
8/10/2019 DAR Lecture
52/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 52
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Check Synchronism
At some point, two vectors rotating at different frequencies will have little orno phase angle
Some customers perceive a risk that the check synchronism could be defeatedat Manual Closure by maintaining the close command and waiting for the insynchronism signal . Risk is overcome by:-
Use of Slip Frequency measurement & blocking, and/or
Use of Guard Relays
An additional perceived risk, is that the output contacts of the check syncrelay could be damaged and hence give erroneous in synchronism signals
Risk overcome by use of additional logic that prevents the output being
used if it is present before the request to close
With modern numeric relays and Programmable Scheme Logic, thesefacilities can all be mimicked and the risk negated
Concerns with Check Synchronism
Check Synchronism
-
8/10/2019 DAR Lecture
53/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 53
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Check Synchronism
Concerns of Damaged Check Synch Relay
Check Synchronism
-
8/10/2019 DAR Lecture
54/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 54
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Check Synchronism
Implementation in Modern Numeric Relay
Agenda
-
8/10/2019 DAR Lecture
55/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 55
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Agenda
1st topic Why Perform Auto-Reclose ? Page 3
2nd topic Where can we apply Auto-Reclose ? Page 7
3rd topic Terminology, Sequences & Settings Page 15
4th topic Check Synchronism Page 46
5th topic Conclusion Page 56
Auto-Reclose on Distribution Networks
-
8/10/2019 DAR Lecture
56/57
Auto-Reclose on Distribution Networks MStockton 2012 - P 56
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subjectto change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particularpurpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
Auto Reclose on Distribution Networks
Traditionally this has been limited to Delayed Auto-Reclose withlittle or no concern for synchronism check or stability
Modern networks are pushing for more efficient use of thenetwork, with fewer and shorter supply interruptions
Increase requirement for Check Synchronism
Use of faster protection, shorter dead times and reclaim times
Scheme settings are largely dependent upon network faulthistory
CB Capability and understanding has a large impact on possibleauto-reclose scheme selection & settings
Conclusions
-
8/10/2019 DAR Lecture
57/57
www.alstom.com