MCD 3000 Soft Starter Overview

The perfect softener of rough startsAC motors often cause one or more serious problems during start-up

acceleration. These problems include:

• High starting current, often causing an unacceptable load on the

AC line.

• Shock load on gear and other transmission elements, causing

unnecessary wear on mechanical parts.

• Fast acceleration and deceleration, causing unstable process

conditions (e.g. in conveyors).

The Danfoss MCD 3000 Soft Starter is the optimum solution to all these

problems for AC motors ranging from 10-1,000 HP.

Page 3: DANFOSS - Soft Starters Linha MCD3000

Drives Solutionswww.danfossdrives.com tel. 800.432.6367 E 3

MC

D 3

00

0

E

2xTN

Torque

Speed

TN

Auto Transformer

DOLStar/Delta

Soft Starter

6xIN

Current

Speed

IN

Limitations of Traditional StartersTraditionally, star/delta and auto transformer starters have been seen as

solutions to these problems. However, both these options have

drawbacks and do not solve the problems caused by wear of the

transmission elements and unstable process conditions.

The Star/Delta Starter

• Reduces start current but introduces a damaging torque transient

when switching from star to delta connection

• Does not allow selection of the best start current level. This

sometimes means the load cannot accelerate to full speed in star

connection, thereby making the star/delta starter ineffective

• Does not control the way the motor stops, thus leaving the speed to

ramp down without control

The Auto Transformer

• Reduces start current but also allows some control over the level of

start current. Auto transformer starters do not, however, eliminate

the risk of a surge in torque when shifting voltage

The MCD 3000 Soft Starter SolutionUnlike traditional solutions the MCD 3000 Soft Starter offers a wide

range of benefits for motor and equipment operation as a whole,

including:

• Flexible control of starting current and torque

• Smooth control of current and voltage without any steps or

transients

• Frequent start/stop operation without mechanical damage

• Flexibility to changes in the start conditions, increasing flexibility

in the application

• Soft stop control for extending the motor deceleration time

• Braking control to reduce motor deceleration time

Page 4: DANFOSS - Soft Starters Linha MCD3000

www.danfossdrives.com tel. 800.432.6367 E 4

Pumps

• Minimized hydraulic shocks

in pipelines during start and

stop.

• Minimized mechanical stress

on motor shaft.

• Reduced starting current.

• Undercurrent protection

preventing damage from

blocked pipe or low water

situations.

• Automatic reset functionality

ensures continued operation

of unmanned pump stations.

• Phase rotation protection

prevents damage from reverse

pump rotation.

• Instantaneous overload

protection prevents damage

from debris drawn into the

pump.

MCD 3000 Soft Starter Overview

Ski Lifts

• Jerk-free acceleration

increases skiers’ comfort and

prevents swinging T-bars.

• Reduced starting current

allows starting of large

motors on a low power

supply.

• Smooth and gradual

acceleration whether the lift

is lightly or heavily loaded.

• Phase rotation protection

prevents operation in reverse

direction.

Centrifuges

• Smooth application of

torque, preventing

mechanical stress.

• Reduced starting times over

star/delta starting.

• Reduced stopping times

thanks to DC brake and soft

braking.

Conveyor Belts

• Controlled start without

mechanical shocks, (e.g.

bottles on a belt do not fall

over).

• Minimized belt stretch.

Reduced counter balance

stress.

• Controlled stop without

mechanical shocks.

• Optimum soft start

performance even with

varying starting loads, (e.g.

coal conveyors starting

loaded or unloaded).

• Extended mechanical

lifetime.

• No maintenance.

A Host of ApplicationsThe MCD 3000 Soft Starter is extremely versatile, offering benefits to

almost all motor starting applications. Here you will find some typical

examples:

Page 5: DANFOSS - Soft Starters Linha MCD3000

Drives Solutionswww.danfossdrives.com tel. 800.432.6367 E 5

MC

D 3

00

0

E

Compressors

• Reduced mechanical shocks

extend the life of the

compressor, couplings and

motor.

• Limited start current enables

large compressors to be

started even when maximum

power capacity is limited.

• Phase rotation protection

prevents operation in reverse

direction.

• Instantaneous overload

protection prevents possible

damage from liquid

ammonia entering the

compressor screw.

Crushers

• Maximum overload

capability available for ride-

through of operating

overloads. The MCD 3000

Soft Starter motor thermal

model accounts for the

connected motors actual

overload capability and will

trip only if absolutely

necessary.

• Maximum start capability

available for starting if

crusher stops while not

completely empty. The MCD

3000 Soft Starter motor

thermal model accounts for

the actual overload capability

of the connected motors and

will allow the motor to

provide start torque for the

longest time possible.

Chippers

• Reduced starting current.

• Instantaneous overload trip

prevents mechanical damage

from jammed loads.

• Reduced deceleration times

due to use of braking

function.

Band Saws

• Reduced time for saw band

replacements since the soft

braking function stops the

motor quickly.

• Extended saw band life

thanks to eliminated torque

shocks during start.

• Easier saw band alignment.

Slow acceleration allows saw

bands to be ‘tracked’ without

jogging.

• Maximum overload

capability available for ride-

through of operating

overloads. The MCD 3000

Soft Starter motor thermal

model accounts for the

actual overload capability of

the connected motors and

will trip only if absolutely

necessary.

Page 6: DANFOSS - Soft Starters Linha MCD3000

www.danfossdrives.com tel. 800.432.6367 E 6

MCD 3000 Features – Control

MCD 3000 electronic soft starters control motor current to provide a

smooth start. When is the MCD 3000 the correct fit for your application?

Anytime one or more of the following apply:

• High starting currents put an unacceptable load on the electrical

supply

• Rapid acceleration rates place stress on the driven equipment or slip

drive belts

• Utility regulations prohibit line-starting of motors

Adjustable Frequency Drives vs. Electronic Soft StartersJust like Danfoss adjustable frequency drives, the MCD 3000 provides the

latest in electronic, programmable, motor control.

The smooth, current-controlled acceleration provided by the soft

starter is the perfect fit for many applications. In more complex

applications, the soft starter may be used in conjunction with the

adjustable frequency drive’s bypass circuitry to provide smooth, reduced

current acceleration whenever the system is run in bypass.

Keypad Control and LED DisplayThe built-in local control panel and LED display allows setting of all

parameters, selection of local or remote operation, and monitoring of

motor current.

MCD 3000 is Fully Electronic and Fully controllableThe smooth, electronic, current-controlled starts provided by the MCD

3000 eliminate undesired torque pulsations and power line current

transients. The MCD 3000 provides smooth, controlled acceleration to a

degree not possible with wye/delta, auto transformer, or partial winding

motor starters.

The MCD 3000 uses three-phase, closed loop current control to

constantly monitor current. Current transducers continuously measure

the current supplied to the motor. A rugged, full-wave, fully-controlled

SCR bridge directly controls current to all three phases of the motor.

The fully interchangeable control card uses the current information

from the transducers to construct the ideal switching algorithms to

control the SCRs at all times, precisely maintaining the desired current,

controlling acceleration, and minimizing motor heating.

The user sets the desired acceleration current. The soft starter

smoothly accelerates the load to full speed. Current draw is minimized

and stress on the motor and driven equipment is reduced.

The MCD 3000 provides a wide range of control and protection

features, including:

• Overload protection for the motor

• Overload protection for the soft starter

• Adjustable calculated motor thermal protection

• Provision for a motor thermistor

• Overtemperature protection for the soft starter

• Phase imbalance protection

• Phase loss protection

• Phase rotation protection

• Undervoltage protection

• Selectable automatic or manual fault reset

• Line frequency monitoring to detect unstable operation of

emergency power generators

• A fault log for troubleshooting

Programmable Features• Three programmable relay outputs allow external indications of a

run command, presence of a fault, or of a broken belt (low current

warning)

• An auto restart time delay can be set

• Phase imbalance sensitivity can be set to eliminate nuisance faults

• Password protection locks the parameters from unauthorized

changes

Page 7: DANFOSS - Soft Starters Linha MCD3000

Drives Solutionswww.danfossdrives.com tel. 800.432.6367 E 7

MC

D 3

00

0

E

MCD 3000 Features – Control

Working PrincipleMotor voltage is controlled by means of a phase cut principle. Two

thyristors in each phase perform the power switching, enabling the

starter to handle high starting torque and frequent starts/stops. Current

transformers measure the motor current providing feedback for

constant current control of motor starting, and also for numerous

motor and application protection functions.

Cabling

• AC line, motor and bypass connectors: Bar type with thread for

fastening bolts for cable shoes.

• Control cable connections: Terminal block for 0.14 m~1.5 m 2/

26~16 AWG.

• Control card supply connection: Terminal block for 2.5~4 mm2/

14~12 AWG.

• The bottom plates are removable and include a drilling template for

cable entries.

Short circuit protection

For proper protection semiconductor fuses must be installed in front of

the starter.

Control inputs

• Start/stop. Can be configured for either two-wire and pulse (three-

wire) start/stop commands.

• Reset.

• Parameter set. For selection between two unique motor parameter

sets.

Signal outputs

Three relay outputs (programmable) for control of:

• Line, Bypass and DC brake contactors.

• Run, Trip, Output on, and High/low current indication.

Bypass

If the soft starter is mounted in a cabinet without ventilation, a bypass

contactor should be applied to prevent heat dissipation during

operation. The starter has built in bars for connection of a bypass

contactor. This allows the MCD 3000 Soft Starter to measure motor

current and retain all motor protection functions even when the bypass

contactor is closed.

EMC

Compliant with the requirements in the product standard IEC 947-4-2,

AC semiconductor motor controllers and starters.

Power

• Supply voltage: 3x200-525 VAC Please specify voltage range at

ordering.

• Supply frequency: 50/60 Hz

• Control voltage: 110 V or 230 V (+10%/-15%)

• Other control voltages can be accommodated by fitting an optional

transformer within the starter.

• Ambient max temperature 60°C (for ambient temperature beyond

40°C — contact Danfoss)

Approvals:

• UL, CE cUL, C √

Thermistor input

• Trip level at >2.8 kOhm

Page 8: DANFOSS - Soft Starters Linha MCD3000

www.danfossdrives.com tel. 800.432.6367 E 8

START

START STOP RESET

REMOTE CONTROL INPUTS

PAR. SET

RUN TRIP REMOTE

AMPS

TEMP

CODE

START

MENU

CANCEL

CHANGE DATA

OK

STOP RESETLOCAL/

REMOTE

Numeric Display

Starter Status LEDs

Programming Buttons

Operational Buttons

Remote Control Input Status LEDs

MCD 3000 Features – Keypad and Parameter Functions

Programming the MCD 3000For simple applications the MCD 3000 needs only to be programmed

with the FLC (Full Load Current) of the connected motor.

To program the MCD 3000 with the motor FLC do the following:

1. Enter the programming mode by pressing the [Menu/Cancel]

button on the Local Control Panel. The display will show the

number of the first programming parameter, Par. 1 Motor FLC.

2. Press the [Change Data/OK] button to display the programmed

value. The setting may now be adjusted.

3. Using the [+/-] buttons adjust the setting to match the motor FLC.

4. When correct, store the Motor FLC setting by pressing the [Change

Data/OK] button. (Pressing the [Menu/Cancel] button returns you

to the parameter number without saving the new value).

5. Return the MCD 3000 to run mode by pressing the [Menu/Cancel]

button.

Remote ControlRemote circuits connected to the MCD 3000 control inputs can be used

to operate the starter when in remote control mode.

Serial CommunicationThe RS485 serial link can be used to control operation when the starter

is either local or remote modes.

Restart DelayRestart Delay sets a minimum time between the end of a stop and the

beginning of the next start. During this period the LED to the right of

the numeric display will flash, indicating the motor cannot be started.

Local Control PanelThe Local Control Panel can be used to operate the MCD 3000 when in

local control mode.

Numeric Display for Programming or Showing

• Current

• Motor temperature

• Fault code

Starter Status LED’s

• Start. Voltage has been applied to the motor

• Run. Full voltage has been applied to the motor

• Trip. The starter has tripped

• Remote. The motor is controlled via external control signals

Programming Buttons

Operational buttons

• For control of motor when in Local mode (can be selected by means

of the Local/Remote button)

Remote Control Input (digital) Status LED’s

• Start

• Run

• Trip

• Remote

Page 9: DANFOSS - Soft Starters Linha MCD3000

Drives Solutionswww.danfossdrives.com tel. 800.432.6367 E 9

MC

D 3

00

0

E

MCD 3000 Features – Programming

Secondary Parameter SetThe MCD 3000 has two motor parameter sets

• Primary Parameter Set: Par. 1 – 9

• Secondary Parameter Set: Par. 25 – 33

When the MCD 3000 is in the off state and is commanded to start, it

checks the Par. Set control input. If open circuit, the primary parameter

set is used. If closed circuit, the secondary parameter set is used.

Motor Thermal ModelThe MC 3000 motor overload protection is an advanced motor thermal

model. Motor temperature is continuously calculated by the

microprocessor that uses a sophisticated mathematical model to

accurately reflect motor heat generation and dissipation during all

stages of operation, e.g. Starting, Running, Stopping & Stopped.

Because it operates continuously, the motor thermal model

eliminates the need for protection systems such as: Excess Start Time,

Limited Starts per hour etc. The state of the motor thermal model can

be viewed on the numeric display while the MCD 3000 is not in

programming mode. Us the [+/-] keys to change the parameter shown

on the numeric display. Motor temperature is shown as a % of

maximum temperature. An overload trip occurs at 105%.

Pre-start TestsOn receiving a start command, MCD 3000 starters operate the Line

Contactor relay output (if programmed) and then perform a series of

tests before applying voltage to the motor terminals and operating the

Output On relay output (if programmed).

Operation after Power LossWhen control and supply voltage is applied to the MCD 3000 it will enter

either the local or remote mode according to the state it was in when

voltage was removed.

If in remote mode, the condition of the remote control inputs is

checked and if a start command is present the motor will be started.

If in local mode, the motor will not be restarted until the [Start]

push button is activated.

Page 10: DANFOSS - Soft Starters Linha MCD3000

www.danfossdrives.com tel. 800.432.6367 E 10

MCD 3000 Features – Protection and Easy Handling

The MCD 3000 Soft Starter is second-to-none when it comes to

compensating for the drawbacks of starting and stopping of AC motors.

In addition it offers the most comprehensive motor and application

protection on the market, including:

Motor ProtectionContinuous monitoring of motor load for calculating motor

temperature. The value is shown in the display as percentage of

maximum temperature, and the function is active even when the power

section is bypassed.

Phase Rotation ProtectionMany applications are sensitive to the direction of rotation of the motor.

With a standard motor starter, a change in phase rotation of the power

applied to the starter will cause the driven motor to reverse direction.

The MCD 3000 can be programmed to detect the phase rotation of the

applied three-phase power. If the phase rotation is changed, the MCD

3000 can trip and indicate a fault.

Application Protection• Undercurrent protection. Particularly useful for ensuring that

pumps do not run dry.

• Shear pin protection. Ensures detection of foreign bodies blocking

operation.

• Phase sequence protection. Prevents machinery from running in

reverse.

• Phase imbalance protection.

Completing the picture Danfoss has added a range of user-friendly

benefits to the MCD 3000 Soft Starter. Among them are:

Easy installation• MCD 3000 Soft Starter is wall mountable, offering ample space for

glanding and terminating the cables.

• Side-by-side mounting without clearance (larger sizes only require

4 inches of clearance).

• No optional equipment required to perform any tasks.

Easy operation• Only one parameter to adjust for basic operation.

• Only a few parameters to adjust for high level control and

protection.

• No need for field calibration to ensure correct operation. The MCD

3000 Soft Starter has a factory accuracy of +5% for current

measurement.

• Built-in local control panel with display.

• Quick set-up.

Bypass OperationThe soft-starter may be bypassed once the motor has reached rated

speed. The MCD 3000 will close an optional externally-mounted

contactor, transferring the motor to the line, reducing the heat

generated by the MCD 3000, maximizing system efficiency, and

minimizing electrical noise generation. The contactor wires run

through the MCD 3000 so that current is monitored and complete

motor overload protection is provided even when bypassed.

Page 11: DANFOSS - Soft Starters Linha MCD3000

Drives Solutionswww.danfossdrives.com tel. 800.432.6367 E 11

MC

D 3

00

0

E

MCD 3000 Soft Starter SelectionMotor horsepower ratings are given for reference only. Soft starters must

always be sized for the full load current rating of the connected load.

Nominal current ratings given are the continuous full load current that

the soft starter can deliver.

The typical starter current ratings are based on:

• Max Operating Temperature 40° C

• Max Elevation 3000 Feet

• Max Number Of Starts Per Hour 10

• Minimum On Load Duty Cycle 50%

Example of starts per hour and on load duty cycle:

The starter starts 10 times an hour or once every 6 minutes. During that

6 minutes the starter runs at least 3 or more of those minutes, or at least

50% of the cycle time.

Many applications will not require as high of a cycle rate. If the

cycle rate were greater or the on load duty cycle shorter, the starter may

have to be oversized to handle the application.

The list at right shows the typical multipliers assigned to the full

load current requirements of various applications. Based on experience

the required start current ratings are given. For high inertia or heavy

load applications consult the factory for sizing assistance. Consult the

Operating Instructions manual for more application information.

Sizing software is also available on our web site:

http://danfossdrives.com/WinStart/passform.htm

This software provides you with the ability to enter application

information such as, starts per hour, load information, ramp time

required and environmental information. Once the information is

entered the software will automatically select the correct starter size.

MCD 3000 Features – Selection Overview

Application Typical Start Current

General and Water

Agitator 4.0 X FLA

Centrifugal Pump 3.5 X FLA

Conveyor 4.0 X FLA

Fan w/Damper Control 3.5 X FLA

Fan w/o Damper Control 4.5 X FLA

Positive Displacement Pump 4.0 X FLA

Metals and Mining

Hammer Mill 4.5 X FLA

Roller Mill 4.5 X FLA

Grinder 3.0 X FLA

Food Processing

Bottle Washer 3.0 X FLA

Centrifuge 4.0 X FLA

Palletizer 4.5 X FLA

Petrochemical

Ball Mill 4.5 X FLA

Extruder 5.0 X FLA

Screw Conveyor 4.0 X FLA

Transport and Machine Tool

Ball Mill 4.5 X FLA

Press 3.5 X FLA

Rotary Table 4.0 X FLA

Lumber and Wood

Bandsaw 4.5 X FLA

Chipper 4.5 X FLA

Planer 3.5 X FLA

Sander 4.0 X FLA

The soft starter decreases the starting current by reducing, but

controlling the starting voltage. In doing so the available starting

torque available from the motor is also reduced. Typical starting torque

reductions are approximately the square of the current reduction

obtained from soft start control.

Page 12: DANFOSS - Soft Starters Linha MCD3000

www.danfossdrives.com tel. 800.432.6367 E 12

MCD 3000 Mechanical and Electrical Specifications

Mechanical InstallationModels MCD 3007 – 3132 have a NEMA 1 (IP21) rating and can be

wall mounted or installed inside another enclosure. These models can

be mounted side by side with no clearance.

Minimum Clearance

100mm

Minimum Clearance

100mm

Minimum Clearance

100mm

Minimum Clearance

100mm

Minimum Clearance

100mm

Minimum Clearance

100mm

Minimum Clearance

200mm

Minimum Clearance

200mm

Minimum Clearance

200mm

Minimum Clearance

100mm

Minimum Clearance

200mm

Minimum Clearance 100mm

Minimum Clearance

100mm

Models MCD 3185 – 3800 have an IP20 rating and must be mounted in

another enclosure. These models must have a clearance of 100mm on

either side.

VentilationMCD 3000 cooling is by means of air circulation. Consequently, the air

needs to be able to move freely above and below the soft starter.

Soft starters dissipate approximately 4.5 watts per amp. When installing

a soft starter in a control panel or other enclosure, ensure there is

sufficient airflow through the enclosure to limit heat rise in the

enclosure.

F1K1M

Semiconductor Fuses (customer suppliedl)Line Contactor (optional)

Legend

+

-

ToMotor

Output A

Output B

Output C

RS485SerialInterface

GND06

05

28

MotorThermistors

ParameterSet

Reset

Stop

Start

400V+10-15

230V+10-15

or

27

26

25

18

17

16

15

A3

A2

A1

B3

L3

L2

B1

L1 T1

T2

T3

E

13

14

21

24

22

34

68

61

69

33

3PhaseSupply

F1(Optional)

K1M

The

rmis

tor

Inpu

tC

ontr

ol S

uppl

yV

olta

geR

emot

e C

ontr

ol In

puts

Ser

ial C

omm

.P

ort R

S48

5

Pro

gram

mab

le R

elay

Out

puts

Wiring Schematic

Page 13: DANFOSS - Soft Starters Linha MCD3000

Drives Solutions

MC

D 3

00

0

E

www.danfossdrives.com tel. 800.432.6367 E 13

MCD 3000 Control Wiring

The MCD 3000 can be controlled using the local push buttons, or via

remote control inputs. Switch between the local and remote modes

using the [Local/Remote] push button.

The MCD 3000 has four remote control inputs. Contacts used for

controlling these inputs should be low voltage, low current rated (Gold

flash or similar). The Stop and Reset circuits must be closed for the

MCD 3000 to run in remote control mode.

Push button control Example:

15

16

17

18

25

26

27

Start

Stop

Reset

Par. Set28

Two Wire control Example:

15

16

17

18

25

26

27

Start

Stop

Reset

Par. Set28

The Par. Set input determines which of the two MCD 3000 motor

parameter sets is operative. When a start is initiated the MCD 3000

checks the state of the Par. Set input. If there is an open circuit the

primary parameters (Par. 1 – 9) are operative. If there is a closed circuit

the secondary parameters (Par. 25 – 33) are operative.

The MCD 3000 provides three relay outputs.

13

14

21

22

24

33

34

Output ALine Contactor Run

Trip Output On High Current Flag Low Current Flag Line Contactor

Run D.C. Brake Contactor

Output B

Output C

All outputs are programmable. Refer Par. 30, 37 & 38

Start Signal

Output Voltage

Line Contactor

Relay Functions

Output On

Pre-Start Tests

Run

Page 14: DANFOSS - Soft Starters Linha MCD3000

www.danfossdrives.com tel. 800.432.6367 E 14

MCD 3000 Control Wiring Examples

Example 2. MCD 3000 installed with a line contactor and operated via a

remote two wire start circuit with reset push button. The MCD 3000

must be in remote mode to function with this circuit. Relay Output A

must be programmed for the Line contactor function.

B3

L3

L2

B1

L1 T1

T2

T3

E

M13

PhaseSupply

F1K1M

MotorThermistors or

17

16

25

18

05

S1

K1A

26

13

K1M

Rel

ayO

utpu

t A*

14

06

15

A3

A2

A1

The

rmis

tor

Inpu

tC

ontr

ol S

uppl

yV

olta

geR

emot

e C

ontr

ol In

puts

400VControlSupply

ControlSupply

(Refer spec.section forrelay rating)

* Par. 36 = O (Line Contactor)

+10-15

230V+10-15

or

F1K1AK1M

S1

Semiconductor Fuses (customer supplied)Start/Stop Control RelayLine ContactorReset Pushbutton

Legend

Motor ThermistorsIf the motor is fitted with thermistors these may be connected directly to

the MCD 3000. A trip will occur if the thermistor circuit resistance is

above approximately 2.8 kΩ.

If thermistors are not connected to the MCD 3000 there must be a link

across the thermistor input terminals.

05

06Thermistor InputNo Motor Thermistors

05

06Thermistor InputMotor Thermistors

Example 1. A basic installation where motor operation is controlled

using the MCD 3000 Local Control Panel. The MCD 3000 must be in

local mode to function with this circuit.

F1

or

M1

MotorThermistors

ControlSupply

3 PhaseSupply

400V+10-15

230V+10-15

or

06

05

A3

A2

A1

The

rmis

tor

Inpu

tC

ontr

ol S

uppl

yV

olta

ge

B3

L3

L2

B1

L1 T1

T2

T3

F1 Semiconductor Fuses (customer supplied)

Legend

Page 15: DANFOSS - Soft Starters Linha MCD3000

Drives Solutions

MC

D 3

00

0

E

www.danfossdrives.com tel. 800.432.6367 E 15

MCD 3000 Control Wiring Examples

Example 4. MCD 3000 controlled by remote 3 wire push button circuit.

The MCD 3000 must be in remote mode to function with this circuit.

orMotorThermistors

F1

3 PhaseSupply

ControlSupply

400V+10-15

230V+10-15

or

T1

T2

T3

E

M1

17

16

25

18

05

S3

S1S2

K1A

K1AK1A

26

06

15

A3

A2

A1

The

rmis

tor

Inpu

tC

ontr

ol S

uppl

yV

olta

geR

emot

e C

ontr

ol In

puts

B3

L3

L2

B1

L1

F1K1A

S1S2S3

Semiconductor Fuses (customer supplied)Start/Stop Control RelayStart PushbuttonStop PushbuttonReset Pushbutton

Legend

Example 3. MCD 3000 installed with a bypass contactor and controlled

via a remote push button circuit. The MCD 3000 must be in remote

mode to function with this circuit. Relay Output C must be programmed

for the Run function.

M13

PhaseSupply

B3

L3

L2

B1

L1

K2M

T1

T2

T3

E

MotorThermistors or

17

16

25

18

05

S3

S2

S1

26

06

15

A3

A2

A1

The

rmis

tor

Inpu

tC

ontr

ol S

uppl

yV

olta

geR

emot

e C

ontr

ol In

puts

400VControlSupply

+10-15

230V+10-15

or

33

K2M

Rel

ayO

utpu

t C*

34ControlSupply

(Refer spec.section forrelay rating)

F1

F1K2M

S1S2S3

Semiconductor Fuses (customer supplied)Bypass ContactorStart PushbuttonStop PushbuttonReset Pushbutton

* Par. 38 = O (Run)

Legend

Page 16: DANFOSS - Soft Starters Linha MCD3000

www.danfossdrives.com tel. 800.432.6367 E 16

MCD 3000 General Specifications

Mains supply (L1, L2, L3):Supply voltage MCD 3000 – T5 ........................................................................................................................................................... 3 x 200 VAC – 525 VAC

Supply frequency (at start) ..................................................................................................................................................... 50Hz (+ 2Hz) / 60 Hz (+ 2Hz)

Supply frequency (during start) .................................................................................................................. >45Hz (50Hz supply) or >55Hz (60Hz supply)

Supply frequency (during run) ................................................................................................................... >48Hz (50Hz supply) or >58Hz (60Hz supply)

Electronics control voltage ....................................................................................................................... 230 VAC (+ 10%/-15%) or 400 VAC (+10%/-15%)

Control InputsStart (Terminals 15 & 16) ................................................................................................................................ Normally Open, Active 24 VDC, 8mA approx.

Stop (Terminals 17 & 18) ............................................................................................................................... Normally Closed, Active 24 VDC, 8mA approx.

Reset (Terminals 25 & 26) .............................................................................................................................. Normally Closed, Active 24 VDC, 8mA approx.

Parameter Set (Terminals 27 & 28) ................................................................................................................. Normally Open, Active 24 VDC, 8mA approx.

Relay OutputsProgrammable Output A(1) (Terminals 13 & 14) ............................................................. Normally Open, 5 A @ 250 VAC/360 VA, 5 A @ 30 VDC resistive

Programmable Output B(2) (Terminals 21, 22 & 24) ............................................................. Changeover, 5 A @ 250 VAC/360 VA, 5 A @ 30 VDC resistive

Output C(3) (Terminals 33 & 34) .......................................................................................... Changeover, 5 A @ 250 VAC/360 VA, 5 A @ 30 VDC resistive(1) Programmable functions: Line contactor, Run(2) Programmable functions: Tripped, output on, High current flag, Low current flag, Line contactor(3)Programmable functions: Run, D.C.Brake Contactor Control, Off

EnvironmentalDegree of protection MCD 3007 to MCD 3132 ................................................................................................................................................................... IP21

Degree of protection MCD 3185 to MCD 3800 ................................................................................................................................................................... IP20

Rated short-circuit current (with semi-conductor fuses) .............................................................................................................................................. 100kA

Rated insulation voltage (Surges) .................................................................................................................................... 2 kV line to earth, 1 kV line to line

Rated impulse withstand voltage (Fast transients) ........................................................................................................................................................... 2 kV

Pollution Degree .......................................................................................................................................................................................... Pollution Degree 3

Electro static discharge .......................................................................................................................................... 4 kV contact discharge, 8 kV air discharge

Equipment class (EMC) .................................................................................................................................................................................................. Class A

Radio-frequency electromagnetic field ........................................................................................ 0.15 MHz – 80 MHz; 140dBµV; 80 MHz – 1 GHz; 10 V/m

This product has been designed for Class A equipment. Use of the product in domestic environments may cause radio interference, in which case the

user may be required to employ additional mitigation methods.

Standards ApprovalsC√ .............................................................................................................................................................................................................................. CISPR-11

UL ....................................................................................................................................................................................................................................UL508

CSA .................................................................................................................................................................................................................... CSA 22.2 No. 14

CE ...................................................................................................................................................................................................................... IEC 60947-4-2

Page 17: DANFOSS - Soft Starters Linha MCD3000

Drives Solutions

MC

D 3

00

0

E

www.danfossdrives.com tel. 800.432.6367 E 17

MCD 3000 Current Ratings

Continuous Ratings (Not bypassed) 40°C Ambient Temperature, <1000 meters30 x FLC 40 x FLC 45 x FLC

Model AC53a 3.0-30: 50-10 AC53a 4.0-20: 50-10 AC53a 4.5-30: 50-10

MCD 3007 20A 16A 14A

MCD 3015 34A 28A 25A

MCD 3018 39A 33A 29A

MCD 3022 47A 40A 35A

MCD 3030 68A 54A 48A

MCD 3037 86A 70A 61A

MCD 3045 93A 76A 65A

MCD 3055 121A 100A 86A

MCD 3075 138A 110A 97A

MCD 3000 106A 150A 138A

MCD 3110 231A 188A 163A

MCD 3132 247A 198A 174A

MCD 3185 364A 299A 255A

MCD 3220 430A 353A 302A

MCD 3300 546A 455A 383A

MCD 3315 630A 530A 442A

MCD 3400 775A 666A 545A

MCD 3500 897A 782A 632A

MCD 3600 1153A 958A 826A

MCD 3700 1403A 1186A 1013A

MCD 3800 1564A 1348A 1139A

Page 18: DANFOSS - Soft Starters Linha MCD3000

www.danfossdrives.com tel. 800.432.6367 E 18

Bypassed Ratings, 40°C Ambient Temperature, <1000 metersModel 30 x FLC 40 x FLC 45 x FLC

AC53b 3.0-30: 330 AC53b 4.0-20: 340 AC53b 4.5-30: 330

MCD 3007 21 18A 15A

MCD 3015 35 32A 27A

MCD 3018 41 39A 33A

MCD 3022 50 49A 40A

MCD 3030 69 57A 49A

MCD 3037 88 73A 63A

MCD 3045 96 81A 69A

MCD 3055 125 107A 91A

MCD 3075 141 115A 100A

MCD 3090 202 168A 144A

MCD 3110 238 199A 171A

MCD 3132 254 206A 179A

MCD 3185 364 307A 201A

MCD 3220 430 362A 307A

MCD 3300 546 470A 392A

MCD 3315 630 551A 455A

MCD 3400 775 702A 566A

MCD 3500 897 833A 661A

MCD 3600 1153 1049A 887A

MCD 3700 1403 1328A 1106A

MCD 3800 1570 1534A 1257A

MCD 3000 Current Ratings

Page 19: DANFOSS - Soft Starters Linha MCD3000

Drives Solutions

MC

D 3

00

0

E

www.danfossdrives.com tel. 800.432.6367 E 19

Ø0.39 (10)

Ø0.217 (5.5)

0.39 (10.0)

0.31 (8.0)b

C

B

aA

0.39 (10.0)

Ø0.217 (5.5)

b

C

B

aA

0.39 (10.0)

Ø0.59 (15)

Ø0.335 (8.5)

0.335 (8.5)

0.47 (12.0)

Ø0.335 (8.5)

NEMA 1 (IP 21)

Weight

MCD Model A B C a b lbs (kg)

3007-3022 20.87 (530) 5.20 (132) 10.63 (270) 20.16 (512) 3.54 (90) 25 (11)

3030-3055 20.87 (530) 5.20 (132) 10.63 (270) 20.16 (512) 3.54 (90) 26 (11.5)

3075-3110 20.87 (530) 10.40 (264) 10.63 (270) 20.16 (512) 8.74 (222) 43 (19.5)

3132 20.87 (530) 15.60 (396) 10.63 (270) 20.16 (512) 13.94 (354) 60 (27)

Chassis (IP 20)

Weight

MCD Model A B C a b lbs (kg)

3185-3500 33.46 (850) 16.93 (430) 11.02 (280) 32.59 (828) 14.57 (370) 109 (49.5)

3600-3800 39.37 (1000) 22.05 (560) 12.40 (315) 38.49 (978) 19.69 (500) 232 (105)

NEMA 1 (IP 21)MCD 3007 - MCD 3132

in (mm)

IP20 Mechanical Dimensions

Chassis (IP 20)MCD 3185 - MCD 3800

in (mm)

Page 20: DANFOSS - Soft Starters Linha MCD3000

www.danfossdrives.com tel. 800.432.6367 E 20

Ordering Normal Duty Rating(2) Heavy Duty Rating(2)

Model Number 3.0 X FLA starting current 4.5 X FLA starting current

230 VAC 460 VAC 230 VAC 460 VAC

MCD 3007 175G5000 5 HP 10 HP 3 HP 10 HP

MCD 3015 175G5004 10 HP 20 HP 7.5 HP 15 HP

MCD 3018 175G5008 25 HP 10 HP 20 HP

MCD 3022 175G5012 15 HP 30 HP 25 HP

MCD 3030 175G5016 20 HP 40 HP 15 HP 30 HP

MCD 3037 175G5020 25 HP 50 HP 20 HP 40 HP

MCD 3045 175G5024 30 HP 60 HP 25 HP 50 HP

MCD 3055 175G5028 40 HP 75 HP 30 HP 60 HP

MCD 3075 175G5032 50 HP 100 HP 40 HP 75 HP

MCD 3090 175G5036 60 HP 125 HP 50 HP 100 HP

MCD 3110 175G5040 75 HP 150 HP 60 HP 125 HP

MCD 3132 175G5044 100 HP 200 HP 75 HP

MCD 3185 175G5048 125 HP 300 HP 100 HP 150 HP

MCD 3220 175G5052 150 HP 350 HP 125 HP 250 HP

MCD 3300 175G5056 200 HP 450 HP 150 HP 300 HP

MCD 3315 175G5060 500 HP 350 HP

MCD 3400 175G5064 700 HP 200 HP 450 HP

MCD 3500 175G5068 800 HP 500 HP

MCD 3600 175G5072 900 HP 700 HP

MCD 3700(1) 175G5076 1000 HP 800 HP

MCD3800 (1) 175G5080 1250 HP 1000 HPNote:(1) Not UL Recognized(2) Consult next page for more detailed sizing information

MCD 3000 Features – Selection Overview

MCD Soft Starter Selection Guide and OrderingInformationWhen ordering, use the ordering number that corresponds to the

appropriate MCD 3000 model number.

Models MCD 3007 – 3132 are IP21 (NEMA 1) rated and have a local

control panel that includes start, stop & reset push buttons. They are

suitable for wall mounting or installation in a switchboard.

Models MCD 3185 – 3800 have an IP20 rating and must be installed in

a control panel or other enclosure. The MCD 3000 Soft Starters are

complete and require no optional modules to add functionality.

Automatic detection and calibration for supply voltage and frequency

eliminates the need for special models. MCD 3000 Soft Starters are

available with two maximum voltage ratings.

• 200 VAC – 525 VAC

• 200 VAC – 690 VAC

The power circuit uses reverse parallel connected thyristors to provide

full wave control on all three phases. The MCD 3000 can be used with

or, if local regulations permit, without a line contactor.