Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

58
Cycle Stop Valves 1” through 16” 1 GPM to 10,000 GPM

Transcript of Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Page 1: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Cycle Stop Valves

1” through 16”1 GPM to 10,000 GPM

Page 2: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Using a Cycle Stop Valve, the flow rate from this pump will exactly match 1 or 100 sprinklers so,

an 86 gallon tank can replace 10,000 gallon tank

Page 3: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Questions about Pump Control Valves

• Resting Pumps and Motors? Pumps are made for continuous duty, they never need to rest.

• Soft Start Equipment? CSV has a mechanical soft start and stop but, soft starter can be used to

reduce end rush.

• Back Pressure? Back Pressure does not hurt pumps. Pumps only think they are in a

deeper well.

• Minimum Flow? Pumps need very little flow to remain cool. Derated motors also need very

little cooling.

• Cavitation? Recirculation not cavitation happens at low flow. Good impellers with high

tensile strength will resist wear from recirculation.

Page 4: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Operating and Maintenance Concerns using

Cycle Stop Valves

• Cannot have trash in your water

• Do not allow to freeze

• Maximum differential pressure 125 PSI

Page 5: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Differential Pressure

Pump dead head or shut off pressure – static water level – valve set pressure

<= 125 PSI

Page 6: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Example; Back Pressure & Differential Pressure

Pump Dead Head in PSI = 250 PSIStatic Water Level 150’ = 65 PSI

250 – 65 = 185 PSI Max inlet pressure or back pressure

All pipe and fittings before the CSV will see 185 PSI

If you have 185 PSI coming into the CSV and the CSV is set at 60 PSI then

185 – 60 = 125 PSI differential pressure through the CSV.

Differential Pressure must always be less than 125 PSI

Page 7: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

If differential pressure is more than 125 PSI, use two or more valves to stair step the pressure down to the required pressure.

Example; Differential Pressure is 200 PSI, max inlet pressure is 250 PSI and

system requires only 50 PSI.

First valve sees 250 PSI and is set for 150 PSI. Second valve sees 150 PSI and is set for 50 PSI. This gives 100 PSI differential through

each valve.

Page 8: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Requirements for submersible pumps and

motors using Cycle Stop Valves.

• Minimum cooling flow for de-rated motors is required.

Page 9: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Choking back on pumps with centrifugal impellers Reduces Horse Power, RPM doesn’t

need to change.(note constant 3450 RPM and Power required

still changes from 10 HP at 200 gpm to 4 HP at 50 gpm)

Page 10: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

66

Submersible motor companies cooling chart only good f or motors at

f ull service f actor load

• Using Constant Pressure Valves at low flow the load on the motor is much less than f ull load. At low amperage these motors can handle hot water. So this chart is no longer valid. (see hot water next)

Page 11: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

67

•I f a Sub motor can handle hot water when de-rated as below, then it will take very little cool water to keep the motor f rom overheating? De-rated motors need much less cooling than motors at f ull service f actor load (Choking back a pump with a Constant Pressure Valve de-rates the motor load)

Page 12: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Choose a pump for your

application

Page 13: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Required Flow in GPM ________Required Pressure at use ________Depth to pumping level ________Elevation from pump to use ________Friction loss in pipe and valves_______ Pump Dead Head ________

Static Water level _______

Page 14: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Example;

Required Flow in GPM 180

Required Pressure at use 50Depth to pumping level 0Elevation from pump to use 0Friction loss in pipe and valves 10Total pressure from pump 60

Pump Dead Head 80 Static Water level 0

Page 15: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Pick a pump that will deliver the head and flow required. 60 PSI = 138’ at

180 GPM

Page 16: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Pick a pump with a good drop in brake horse power.

Page 17: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Pump Dead Head Pressure 80 PSIPressure Switch Shut Off 60 PSI

Cycle Stop Valve 50 PSIPressure Switch On 45 PSI

Page 18: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Make sure pump dead head pressure is at least 10 PSI higher than pressure switch shut off pressure

Page 19: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Make sure pump dead head pressure is no more than 125 PSI higher than

Cycle Stop Valve setting.

Page 20: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Choose a Cycle Stop Valve to match the pump.

Use Easy Selection Chart to match pump flow rate

to valve flow rate.

Page 21: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Easy selection chart

is good rule of thumb.

Pump Max Flow is 180 GPM.

3” CSV3B is good from 5 to 300 GPM.

Page 22: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Confirm Max Pressure, Max Differential Pressure,

Adjustment Range, and Actual Friction Loss

Valve Sizing ChartKeep Less than 5 PSI

Page 23: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Friction Loss for CSV3B is 14 PSI.

When there is less than 100 PSI differential pressure, the cover spring can be removed

which decreases friction loss to 7 PSI.

7 PSI friction loss means the pump must deliver 57 PSI to get 50 PSI at max flow

rate.

Friction loss with Cycle Stop Valves only applies at maximum flow rate.

Page 24: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Specifications Page

gives Pressure Range, Flow Range, Friction Loss, and

Dimensions for the different valves

available.

Page 25: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

PressuresFlow Rate

Dimensions

Friction Loss

Retainer Dimensions

Page 26: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Minimum Friction Loss

Page 27: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Valve Sizing ChartKeep Less than 6 PSI

Page 28: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

CSV1 and CSV3 Valve are Constant Pressure Valves

CSV1W, CSV1Z, and CSV2W have Reduced Pressure Fall

Off

Page 29: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Reduced Pressure Fall Off means that you will see 11 PSI less when using 20 GPM than when using 1

GPM.

Page 30: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Reduced Pressure Fall Off has nothing to do with Friction Loss

Just means the CSV must be set at 61 PSI while using 1 GPM,

to get 50 PSI for a 20 GPM sprinkler zone

Page 31: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Max Differential Pressure

Min Friction Loss

Reduced Pressure Drop

Page 32: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Pressures

Reduced Pressure Fall Off

Page 33: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Pressures

Reduced Pressure Falloff

Page 34: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Determining Tank Size with Cycle Stop Valves

• No tank is needed when used with a pump start relay and a pressure relief valve

• Pressure switch systems can use tank sizes from 5-30 gallons of drawdown

• Water towers, large hydro tanks, and racks of bladder tanks can still be used if present or required.

• Larger systems with a continuous use of 5 gpm or more can use smaller tanks than other systems with intermittent use.

Page 35: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Only when required system flow is less than minimum for CSV will pump be allowed to

cycle.

Example; CSV3 has 5 GPM minimum and the system has

a 2 GPM leak.

Tank size is very important.

Page 36: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Minimum run time calculator on

www.cyclestopvalves.com

helps size tank for worst case scenarios.

Page 37: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Worst case cycles per day with a 2 GPM leak.

Page 38: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

If worst case cycles per day are more than allowed

by motor manufacturer, use larger or additional

tanks.

Page 39: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

119 gallon tank causes

95 cycles per day,

then two 119 gallon tanks

reduces cycles to 47

per day.

Page 40: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

When required system flow is greater than minimum flow for CSV, the

pump will run continuously.

I.E. CSV1 has 1 GPM minimum CSV3 has 5 GPM minimum

System never gets below 7 GPM

usage. Tank size is not important as pump will run

continuously.

Page 41: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Install CSV in the well or before the

pressure tank

Page 42: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

With 2” and larger valvesinstall pressure tank within 10’ of

CSV

Page 43: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Multiple Pumps work together by simply staggering pressure

settings.

Pump #1) 5 HP SubOn at 70 off at 80 PSI

Pump #2) 50 HP TurbineOn at 60 off at 70 PSI

Pump #3) 75 HP TurbineOn at 50 off at 60 PSI

Page 44: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Never Tee before the Cycle Stop Valve.

All Water must go through the CSV before going to

the use or the tank.

Page 45: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Pressure Switch placement is very important.

Switch must be as close to the tank as possible.

No elbows or tees between the switch and the pressure

tank.

Page 46: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Water line going to the tank should never be

larger than the tank inlet connection.

I.E. 1.25” elbow under tank means no larger than 1.25” pipe from main line

to tank.

Page 47: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Some tanks have 1.25” elbow with ¾” hole going

into tank.

These type tanks will not work properly.

Use tanks with full port inlet.

Page 48: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

In the well pressure tank with Cycle Stop Valve

and pitless adapter

Page 49: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

In well pressure tank only holds 3/4 of a gallon.

These tanks work great like any other small tank as long as there are no

leaks in the water system.

Page 50: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

If there are leaks in the system, add an additional

or larger tank.

This keeps the pump from having to start every time ¾ of a gallon has leaked

out.See Tank Calculator on our web page.

Page 51: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Dry Run &Rapid Cycle

Protection

Page 52: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Other Dry Run relays will not

work with Cycle Stop Valves

Page 53: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Other brands see low

amperage from CSV as Dry Run and shut down when they should not

Page 54: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Cycle Sensor has adjustable

underload, knows the difference

between low amps and Dry

Run

Page 55: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

Shuts pump off from Rapid Cycle

Can see bad tank, broken check valve,

bad pressure switch, or malfunction with CSV

Page 56: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

1/3 to 2HPWires like standard

pressure switch

3- 15 HP single phase

wires to deluxe control box

Page 57: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.

1 to 500 HP Three Phase

Wires to Magnetic Starter

Page 58: Cycle Stop Valves 1 ” through 16 ” 1 GPM to 10,000 GPM.