CUSTOMER - New Mexico State University

5

Transcript of CUSTOMER - New Mexico State University

—›

—›

—›

—›

CUSTOMER

REFERENCE

PROJECT

SERVICE OF UNIT

MODEL

SURFACE PER UNIT NO. OF UNITS:

QUOTATION NO. :

DATE :

CONNECTED IN :

:

:

:

:

:

:

COLD SIDE HOT SIDE

CONSTRUCTION OF SINGLE UNIT

CONNECTIONSCOLD SIDE

pos. pos.

HOT SIDE

type type

FLUID CIRCULATED

TOTAL FLUID ENTERING

volume

mass

FLUID TYPE

DENSITY

SPECIFIC HEAT

THERMAL CONDUCTIVITY

DYNAMIC VISCOSITY

LATENT HEAT

TEMPERATURE IN / SAT.

TEMPERATURE OUT

OPERATING PRESSURE

NO. OF PASSES / PLATE ARR.

PRESSURE DROP

EXCESS SURFACE / FOULING

HEAT EXCHANGED

LMTD / U-VALUE

DESIGN PRESSURE

TEST PRESSURE

DESIGN TEMPERATURE

PLATE MATERIAL

NO. OF PLATES

PLATE THICKNESS (mm)

FRONT/REAR MATERIAL:

GASKET MATERIAL:

GASKET TYPE:

TIE RODS:

SHROUD:

empty / flooded (H20)

CODE REQUIREMENTS:

NOTES:

Tap Water

30.0 gpm

14,908.4 lb/h

Liquid

61.96

0.999

0.364

0.664

Gas

35.0

170.0

1 / 1 x 7 SH

1.60 PSI

in A 2" Male NPT 316LSS

out B 2" Male NPT 316LSS

Steam

4.8 gpm

2,218.5 lb/h

Liquid

57.13

1.031

0.394

0.18

Gas

0.17

0.553

0.018

0.014

906.8

305.6

305.6

1 / 1 x 7 SW

7.18 PSI

in C 2" Male NPT 316LSS

out D 2" Male NPT 316LSS

2.40 /

2,011,714.0

195.4 / 631.28

150.0

195.0

305.6

AISI 316L

15

0.50

Carbon Steel

EPDM

Mechanically Fixed

Zinc Plated

Aluminum

276 | 284

.45 / .45

New Mexico State University

Brewery Research Facility

Water Heater

SX13-350-15

16.7 ft²

LMH-16-29144

24-Mar-2016

Single

PERFORMANCE OF UNIT

The unit is designed under balanced pressure conditions.

lb/ft³

Btu/lb·°F

Btu/h·ft·°F

cP

Btu/lb

°F

°F

PSI

FLOODED VOLUME (gal)

Btu/h

°F / Btu/ft²·h·°F

PSI

PSI

°F

weight (lb):

TSS Version: FULL 31.2.0 - I -BP

Plate Heat Exchanger

DA

CB

31

.0

Pre

ssu

re P

late

28

.73

14.0

5.0

23

.25

5.31

A,D

B,C

1.95 min.2.07 nom.

1.0 typ

19.13

2.0

0.3

8

4.63

4.63

11

.5

1.5

2.88

(2) Ø.563

3.25

1.5

NOTES: Dimensions shown in InchesTOLERANCE: Nozzle centerline & face: ±0.125" Frame foundation & bolt hole locations: ±0.25"

ConnectionsFluid Port Size Type MaterialHot (in) C 2 Male NPT 316LSSHot (out) D 2 Male NPT 316LSSCold (in) A 2 Male NPT 316LSSCold (out) B 2 Male NPT 316LSS

Nozzle Arrangement

Job No. -101Part No. SX13-350-15 Rev. 0Made Mar 24, 2016 By Lindsey HallCheck Mar 24, 2016 By Lindsey Hall

Construction Frame Size 350Plate Arr't 1 x 7 SH 1 x 7 SWNo. of Plates 15Plate Mtl. 316L SS / 0.5 mmMax No. of Plates 30Gasket Mtl. EPDM - Clip

Design ConditionsHot Cold

Design Pres. (PSIG) 150 150Test Pres. (PSIG) 195 195Design Temp. (F) 305.6 305.6Min. Temp. (F) 32 32Weight Dry/Filled (lb) 276 284

Version: FULL 31.2.0 Model: Sigma X13

—›

—›

—›

—›

CUSTOMER

REFERENCE

PROJECT

SERVICE OF UNIT

MODEL

SURFACE PER UNIT NO. OF UNITS:

QUOTATION NO. :

DATE :

CONNECTED IN :

:

:

:

:

:

:

COLD SIDE HOT SIDE

CONSTRUCTION OF SINGLE UNIT

CONNECTIONSCOLD SIDE

pos. pos.

HOT SIDE

type type

FLUID CIRCULATED

TOTAL FLUID ENTERING

volume

mass

FLUID TYPE

DENSITY

SPECIFIC HEAT

THERMAL CONDUCTIVITY

DYNAMIC VISCOSITY

LATENT HEAT

TEMPERATURE IN / SAT.

TEMPERATURE OUT

OPERATING PRESSURE

NO. OF PASSES / PLATE ARR.

PRESSURE DROP

EXCESS SURFACE / FOULING

HEAT EXCHANGED

LMTD / U-VALUE

DESIGN PRESSURE

TEST PRESSURE

DESIGN TEMPERATURE

PLATE MATERIAL

NO. OF PLATES

PLATE THICKNESS (mm)

FRONT/REAR MATERIAL:

GASKET MATERIAL:

GASKET TYPE:

TIE RODS:

SHROUD:

empty / flooded (H20)

CODE REQUIREMENTS:

NOTES:

Tap Water

30.0 gpm

14,762.1 lb/h

Liquid

61.35

0.999

0.378

0.461

Gas

90.0

193.0

1 / 1 x 7 SH

1.51 PSI

in A 2" Male NPT 316LSS

out B 2" Male NPT 316LSS

Steam

3.6 gpm

1,676.3 lb/h

Liquid

57.13

1.031

0.394

0.18

Gas

0.17

0.553

0.018

0.014

906.8

305.6

305.6

1 / 1 x 7 SW

4.31 PSI

in C 2" Male NPT 316LSS

out D 2" Male NPT 316LSS

17.60 /

1,520,000.0

158.6 / 674.89

150.0

195.0

305.6

AISI 316L

15

0.50

Carbon Steel

EPDM

Mechanically Fixed

Zinc Plated

Aluminum

276 | 284

.45 / .45

New Mexico State University

Brewery Research Facility

Summer Conditions

Water Heater

SX13-350-15

16.7 ft²

LMH-16-29144

24-Mar-2016

Single

PERFORMANCE OF UNIT

The unit is designed under balanced pressure conditions.

lb/ft³

Btu/lb·°F

Btu/h·ft·°F

cP

Btu/lb

°F

°F

PSI

FLOODED VOLUME (gal)

Btu/h

°F / Btu/ft²·h·°F

PSI

PSI

°F

weight (lb):

TSS Version: FULL 31.2.0 - I -BP

Plate Heat Exchanger