Current & Voltage Transformer.pptx
Transcript of Current & Voltage Transformer.pptx
-
7/28/2019 Current & Voltage Transformer.pptx
1/43
Current &VoltageTransformer
M. M. Meraat
Spring 1392
-
7/28/2019 Current & Voltage Transformer.pptx
2/43
Instrument Transformer Standards
IEC 60044-1,6,8 CTs IEC 60044-2,5,7 VTs
BRITISH BS 3938:1973 CTs
BS 3941:1975 VTs
AMERICAN ANSI C51.13.1978 CTs and VTs
-
7/28/2019 Current & Voltage Transformer.pptx
3/43
Current transformer
The Current Transformers transform current fromsystem to other system
CT should produce Secondary current (Is) exactlyproportional to that flowing in the primary system
(Ip).CT should produce Secondary current (Is) exactly
in phase with the current flowing in the primarysystem (Ip).
A CT rated primary current value is indicated asIpn and is selected based on the current which ismaximum intended continuous current at which itsperformance is based
-
7/28/2019 Current & Voltage Transformer.pptx
4/43
Current transformer
-
7/28/2019 Current & Voltage Transformer.pptx
5/43
PrimaryConductor
Ring TypeCurrentTransformer
PrimaryInsulation
Core
SecondaryWinding
-
7/28/2019 Current & Voltage Transformer.pptx
6/43
RELAY
1A ?1000A ?
1000 turns sec. ?
Insulation covered wire,giving inter-turninsulation & secondaryto core insulation
Generator, orsystem voltagesource
Feeder or Bus-bar
forming 1 turn of primarycircuit
Insulation to stop flash-over
from HV primary to core &secondary circuit
Laminated strip wound steeltoroidal core
-
7/28/2019 Current & Voltage Transformer.pptx
7/43
Current transformer A CT rated secondary current (Isn), however, is fixed value
depending on the rated current of secondary device it feeds and isstandardized as 1A, 5A commonly to meet almost all applications
IEC 60044-1 defines the following standard rated currents:
IEEE C57-13 defines the following standard rated currents:
-
7/28/2019 Current & Voltage Transformer.pptx
8/43
Current transformer
rated continuous thermal current (Icth) the value of the current which can be permitted to
flow continuously in the primary winding, the
secondary winding being connected to the rated
burden, without the temperature rise exceeding
the values specified
-
7/28/2019 Current & Voltage Transformer.pptx
9/43
Current transformerAn Ideal CT can be defined as the CT which meets
the requirement of constant (non-changing) valueof k and zero phase displacement between the Ip& Is over the entire range of interest. It is possible toachieve this requirement to any imaginableaccuracy. But achieving higher and higher
accuracy requires more sophisticated designs andmost of the time is not feasible due to cost and sizeof such a CT.
A Practical CT is one which is designed to meet an
particular application maintaining a minimum levelof accuracy within the constraints of cost & size.Thus a Practical CT differs from an Ideal CT due toits accuracy in k (which we can also call as currentratio of a CT) and phase displacement from zero.
-
7/28/2019 Current & Voltage Transformer.pptx
10/43
Current transformer The error in the reproduction will appear both in
amplitude and phase. The error in amplitude iscalled current or ratio error and the error in phase iscalled phase error or phase displacement.
( = 1% = 1 centiradian = 34.4 minutes)
-
7/28/2019 Current & Voltage Transformer.pptx
11/43
Current Transformer Errors Phase Error Definition:
The displacement in phase between the primary and
secondary current vectors, the direction of the vectors
being chosen so the angle is zero for a perfect
transformer.
Phase Error is :
positive: When secondary current vector LEADS
the primary current vector. negative: When secondary current vector LAGS
the primary current vector.
-
7/28/2019 Current & Voltage Transformer.pptx
12/43
composite error under steady-state conditions, the r.m.s. value of
the difference between: a) the instantaneous values of the primary current,
and
b) the instantaneous values of the actual
secondary current multiplied by the rated transformation ratio
The composite errorc is generally expressed as apercentage of the r.m.s. values of the primarycurrent according to the formula
It includes amplitude (Ratio) and phase errors andalso the effects of any possible harmonics in theexciting current
-
7/28/2019 Current & Voltage Transformer.pptx
13/43
Current transformer
Two basic groups of C.T.
Measurement C.T.s
Limits well defined
Protection C.T.s
Operation over wide range of currents
Note : They have DIFFERENT characteristics
-
7/28/2019 Current & Voltage Transformer.pptx
14/43
DefinitionAccuracy Limit Factor ( A.L.F. ) or Saturation Factor
Ratio of Ip to Irated up to which the C.T. ratedaccuracy is maintained.
Marking: Accuracy limit factor is written after the
accuracy class.
E.g. 10 VA 5P10, 15 VA 10P10, 30 VA 5P20.
e.g. 200 / 1A C.T. with an A.L.F. = 5 will maintain itsaccuracy for Ip < 5 x 200 = 1000 Amps
-
7/28/2019 Current & Voltage Transformer.pptx
15/43
Current transformerMeasuring C.T.s
Require good accuracy upto approx 120% ratedcurrent.
Require low saturation levelto protect instruments, thususe nickel iron alloy core
with low exciting currentand knee point at low fluxdensity.
Protection C.T.s Accuracy not as important
as above.
Require accuracy up tomany times rated current,thus use grain orientatedsilicon steel with highsaturation flux density.
B
Protection C.T.
Measuring C.T.
H
-
7/28/2019 Current & Voltage Transformer.pptx
16/43
Measuring Class CTs: These CTs are intended for measurement which is
close to normal operating current values (load). InAC systems, thus are designed to provideaccuracy within a band close to normal ratedvalues of current at fundamental frequency of
primary system. This is also important when such a current is used
for revenue (billing) purposes. Thus specialapplication to meet load as low as 1% of rated at
specific accuracy becomes important. In IEC 60044-1 & IS standard, the following standard
accuracies for Metering class CTs are defined:
-
7/28/2019 Current & Voltage Transformer.pptx
17/43
Measuring Class CTs: IEC standard accuracy class of 0.1, 0.2, 0.5, 1 for Normal
Metering purpose (this value indicates percentage ratio errorat 100% & 120% of rated primary current).
IEC standard accuracy class of 0.2S & 0.5S for Tariff Metering
purpose (this value indicates percentage ratio error at 20%,
100% & 120% of rated primary current).
-
7/28/2019 Current & Voltage Transformer.pptx
18/43
Measuring Class CTs:
IEC standard accuracy class of 3 & 5 for roughDisplay reading meters (which is not required to bevery accurate) and this value indicatespercentage ratio error at 50% & 120% of rated
primary current.
-
7/28/2019 Current & Voltage Transformer.pptx
19/43
Protective class These CTs are intended for measurement which is usually
at rated values as well as at high currents encounteredduring system faults.
In AC systems, thus are designed to provide accuracy
within a band close to normal rated values of current at
fundamental frequency of primary system and accuracyat higher current expected at faults.
IEC Standard Protective CT Classes & IS Standard CT
classes:
IEC defines accuracy classes for Protective class CTs based on
steady state performance as well as on Transient performances.All CTs are indicated with letter P.
IEC standard classes for Protective CTs based on Steady Stateperformances: Classes defined: 5P, 10P, PX
IEC standard classes for Protective CTs based on Transient
performances: Classes defined: TPX, TPY, TPZ, TPS
-
7/28/2019 Current & Voltage Transformer.pptx
20/43
IEC Standard CTs for Steady State performances:
Protective class CTs in IEC standard for SteadyState performances are defined for meetingaccuracy based on fundamental component ofAC fault current.
Transient DC component performance is not
defined for these CTs.
These CTs are defined in three groups: without limiton remanence flux (5P, 10P), with 10% limit onremanence flux (5PR, 10PR) and a CT with 0.25%
limit turns error having low leakage reactancedesign (PX).
-
7/28/2019 Current & Voltage Transformer.pptx
21/43
Steady State performanceClass-5P & 10P CTs (No
limit defined for remanence flux & turns ratio error):
Steady State performance Class-PX CTs (turns error
limit defined & no limit defined for remanence flux): These CTs are also protective class CTs with letter P
but must be low leakage flux type. CT turns error shallnot exceed 0.25% and the knee-point of CT must bedeclared
IEC Standard CTs for Steady State performances:
-
7/28/2019 Current & Voltage Transformer.pptx
22/43
knee-point is the point on the secondary excitation
characteristics of CT at which 10% raise inrms secondary voltage results in 50% raisein the rms excitation current).
The Vk is also limited by practical design
and manufacturing consideration as:
Vk = Rated output in VA x ALFSecondary rated current
-
7/28/2019 Current & Voltage Transformer.pptx
23/43
Application of Class PX CTs: For sensitive application which compare phase or neutral (or
residual) currents from more than one CT such as highimpedance protection or sensitive differential protections, itis necessary to have CTs which are with low leakage flux andsecondary characteristics can be used to evaluateperformances of protection (e.g. to evaluate performancebased on differences in secondary current outputs,differences in time to saturate of CTs etc).
IEC Standard CTs for Steady State performances:
-
7/28/2019 Current & Voltage Transformer.pptx
24/43
IEC Standard CTs for Transient performances:
Four Protective class CTs are defined in IEC60044-6
standard based on the Transient Performances. LetterT is prefixed with letter P for these class CTs.
These are Class TPS, TPX, TPY & TPZ.
These CTs performances are defined for dc componentcurrent in addition to ac current. Flux in the core due to
dc current component is X/R times the flux due to accomponent.
Thus in applications which are fast and are requiringtransient performances like Distance Protection, theseCTs can be evaluated.
Steady state performance CTs can also be used for suchapplication as long as they are over dimensioned for dcflux based on evaluation of CT time to saturate, relayoperation time and relay design.
-
7/28/2019 Current & Voltage Transformer.pptx
25/43
Transient performance Class-TPS (No limit definedfor remanence flux, but turns ratio error shall be lessthan 0.25%):
These CTs are also protective class CTs with letter TP
but must be low leakage flux type. CT turns error shall
not exceed 0.25% and the knee-point of CT must bedeclared (knee-point is point on the secondary
excitation characteristics of CT at which 10% raise in
rms secondary voltage results in 100% raise in the peak
excitation current.
These CTs are with Iron core without air-gap.
IEC Standard CTs for Transient performances:
-
7/28/2019 Current & Voltage Transformer.pptx
26/43
Transient performance Class-TPX (No limit definedfor remanence flux & turns ratio error):
These CTs shall be assigned duty cycle like auto-
reclose attempts. These CTs are with Iron core without
air-gap.
IEC Standard CTs for Transient performances:
-
7/28/2019 Current & Voltage Transformer.pptx
27/43
Transient performance Class-TPY (10% defined forremanence flux & no limit on turns ratio error):
These CTs shall be assigned duty cycle like auto-
reclose attempts. These CTs may have small air-gaps.
Auto reclose duty may have to be considered.
Transient performance Class-TPZ (remanence fluxnegligibly small & no limit on turns ratio error):
These CTs shall be assigned duty cycle like auto-recloseattempts. These CTs may have large air-gaps.
IEC Standard CTs for Transient performances:
-
7/28/2019 Current & Voltage Transformer.pptx
28/43
Accuracy limits defined for TPX, TPY & TPZ class CTs:
IEC Standard CTs for Transient performances:
-
7/28/2019 Current & Voltage Transformer.pptx
29/43
AUTO-RECLOSE DUTY CYCLES: As applied to TPX &TPY class CTs:
IEC Standard CTs for Transient performances:
-
7/28/2019 Current & Voltage Transformer.pptx
30/43
Optical CT Technology
-
7/28/2019 Current & Voltage Transformer.pptx
31/43
Voltage transformer
Similar to a CT an ideal VT is a VT which introducesno ratio errors and no phase displacement when ittransforms Voltage from Primary system to thesecondary system.
Ratio error or Voltage error is expressed as:
-
7/28/2019 Current & Voltage Transformer.pptx
32/43
Standard values for VTs as defined in IEC60044-2 for VTs are:
-
7/28/2019 Current & Voltage Transformer.pptx
33/43
Standard values for VTs as defined in IEC60044-2 for VTs are:
-
7/28/2019 Current & Voltage Transformer.pptx
34/43
Voltage Transformer
ACCURACY CLASSES: IEC 60044-2 defined accuracy classes for Measuring
class VTs are:
-
7/28/2019 Current & Voltage Transformer.pptx
35/43
Voltage Transformer
ACCURACY CLASSES: IEC 60044-2 defined accuracy classes for Protective
class VTs are:
-
7/28/2019 Current & Voltage Transformer.pptx
36/43
Capacitive voltage transformer
-
7/28/2019 Current & Voltage Transformer.pptx
37/43
Capacitive voltage transformer
O ti l VT T h l
-
7/28/2019 Current & Voltage Transformer.pptx
38/43
Optical VT Technology
F
-
7/28/2019 Current & Voltage Transformer.pptx
39/43
Ferroresonance:
Resonance:
In a resonant circuit, inductive and capacitive
reactances of the circuit are equal to eachother
The only opposition to current is the circuit
resistance,
This resonance effect presents one stable
operation state, and its effects are mitigated
by the system frequencies control or by the
introduction of pure resistances.
-
7/28/2019 Current & Voltage Transformer.pptx
40/43
Ferroresonance:
Ferroresonance is a resonance situation with
nonlinear inductance, so the inductivereactance not only depends on frequency, but
also on the magnetic flux density of an iron
core coil (e.g. transformer iron core).
Theoretically, this nonlinear inductance could
be represented by two inductive reactances,according to the situation on thesaturation
curve.
Linear zone fl XLlinear= Llinear
Saturation zone fl XLsat
= Lsat
Example:
-
7/28/2019 Current & Voltage Transformer.pptx
41/43
Ferroresonance: Operation point 1: It is a non-ferroresonant stable
operation point. This is an inductive situation ( XLlinear >XC fl E = VLVC).
Operation point 2: It is a ferroresonant stable operationpoint. This is a capacitive situation ( XLsat < XC fl E = VC VL).
Operation point 3: It is an unstable operating point.
-
7/28/2019 Current & Voltage Transformer.pptx
42/43
Ferroresonance: Damping of ferroresonance A ferroresonance
oscillation, which is not
damped out efficiently, isdangerous for thetransformer. Under suchcircumstances the core ofthe intermediate voltagetransformer works at fullsaturation and the exciting
current might be large, sothat there is a risk of afailure. A dampingarrangement that dampsany resonance oscillationseffectively is thus anecessity. The standards
specify certainrequirements on thedamping and these testsshould be performed inorder to verify that theseare fulfilled.
-
7/28/2019 Current & Voltage Transformer.pptx
43/43
Ferroresonance:
Damping of ferroresonance