C3000 D5 50 Diesel Our energy working for you.™ 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full 39.3 68.3 97.8 128.7 35.6 63.5 90.5 118.9 178.73 310.90 445.07 585.80 162.07 289.10 411.70 541.10 Standby rating Combustion air, m 3 /min Prime kVA (kW) 2750 (2200) Standby kVA (kW) 3000 (2400) 2617 2304 15.5:1 190 1500 Overspeed limit, rpm BMEP at set rated load, kPa Regenerative power, kW Cummins Prime rating 170 QSK78 - G9 Cast Iron, 60° V18 cylinder Turbo Charged and Low Temperature After-cooled 2375 2539 Configuration Aspiration Bore, mm Gross engine power output, kWm Governor type Starting voltage Maximum fuel inlet temperature (°C) Maximum fuel inlet restriction, mm Hg 2225 193.00 Engine model Piston speed, m/s Compression ratio Maximum air cleaner restriction, kPa Fuel consumption 9.5 Ratings Stroke, mm Rated speed, rpm Load gph L/hr Engine Engine manufacturer Air Fuel flow 70 127 413 Electronic 24 Volts DC 1850 ±50 189 Lube oil capacity, L Maximum fuel flow, L/hr 186.00 ©2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others. 6.22 Model: Frequency: Fuel Type: » Generator set data sheet Transient data sheet: TD50-HHP DD50-OSHHP/DD50-CSHHP Spec sheet: Noise data sheet (Open/enclosed): Airflow data sheet: Derate data sheet (Open/enclosed): SS18-CPGK ND50-OSHHP/ND50-CSHHP AF50-HHP

description

Cummins C3000D5 generator set specification sheet.

Transcript of Cummins C3000D5

Page 1: Cummins C3000D5

C3000 D5

50

Diesel

Our energy working for you.™

1/4 1/2 3/4 Full 1/4 1/2 3/4 Full

39.3 68.3 97.8 128.7 35.6 63.5 90.5 118.9

178.73 310.90 445.07 585.80 162.07 289.10 411.70 541.10

Standby rating

Combustion air, m3/min

Prime

kVA (kW)

2750 (2200)

Standby

kVA (kW)

3000 (2400)

2617

2304

15.5:1

190

1500

Overspeed limit, rpm

BMEP at set rated load, kPa

Regenerative power, kW

Cummins

Prime rating

170

QSK78 - G9

Cast Iron, 60° V18 cylinder

Turbo Charged and Low Temperature After-cooled

2375

2539

Configuration

Aspiration

Bore, mm

Gross engine power output, kWm

Governor type

Starting voltage

Maximum fuel inlet temperature (°C)

Maximum fuel inlet restriction, mm Hg

2225

193.00

Engine model

Piston speed, m/s

Compression ratio

Maximum air cleaner restriction, kPa

Fuel consumption

9.5

Ratings

Stroke, mm

Rated speed, rpm

Load

gph

L/hr

EngineEngine manufacturer

Air

Fuel flow

70

127

413

Electronic

24 Volts DC

1850 ±50

189

Lube oil capacity, L

Maximum fuel flow, L/hr

186.00

©2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.

6.22

Model:Frequency:Fuel Type:

» Generator set data sheet

Transient data sheet: TD50-HHP

DD50-OSHHP/DD50-CSHHP

Spec sheet:

Noise data sheet (Open/enclosed):

Airflow data sheet:

Derate data sheet (Open/enclosed):

SS18-CPGK

ND50-OSHHP/ND50-CSHHP

AF50-HHP

Page 2: Cummins C3000D5

Standby

Prime

Open Enclosed

Dimensions

Enclosed set

Coolant capacity (with radiator), L

6.8

Genset outline

432Exhaust gas flow at set rated load, m3/min

Fan load, KWm

Cooling system air flow, m3/sec @ 12.7mmH2O

RTF

Exhaust

RTF

Note: Standard open genset options running at 400V, 150m above sea level. For enclosed product derates, please refer to datasheet - DD50-CSHHP.

RTF

45°C

Maximum exhaust back pressure, kPa

RTF

RTF2965 (2372)

422Exhaust gas temperature, °C

40°C

Ambient design, °C

Standard set-mounted radiator cooling

Maximum cooling air flow static restriction mmH2O

27°C

--

Width

* Weights represent a set with standard features. See outline drawing for weights of other configurations

Unit wet weight kgs

Unit dry weight kgs

427

HeightLength

19996

3000 (2400) 3000 (2400)

RTF

Open set derating factors kVA (kW)

3000 (2400)

Total heat rejection, BTU/min

For 380V product derates, please consult the factory for details.

50°C 55°C

Prime rating

RTF

415

RTF

RTF

Standby rating

2750 (2200)

--

Weights*

2670 (2136)2750 (2200)2750 (2200)

20616

Open set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

©2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.

Enclosed set standard dimensions

Standard open set dimensions 23002313

-- --

5668

--

Page 3: Cummins C3000D5

Feature code

-- -- -- --

Formulas for calculating full load currents:

Single phase outputThree phase output

Alternator data

Web: www.cumminspower.comE-Mail: [email protected]: +44 (0) 1843 255902Telephone: +44 (0) 1843 255000

Manston Park, Columbus AvenueManston, Ramsgate Kent CT12 5BF, UK

See your distributor for more information.

Duty2

Cummins Power Generation

©2010 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.

Wye, 3 Phase

Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.

Emergency Standby Power (ESP)

Limited-Time running Power (LTP):

Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528.

HVS1804S,T,W,XS/P/C HVS1804S,T,W,XS/P/C 6600V

Ratings definitions

3300V

VoltageAlternator

80-125C 11000V

Base Load (Continuous) Power (COP)

Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power (COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.

Prime Power (PRP)

Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528. Ten percent overload capability is available in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514.

S/P/C

Temp rise degrees C

MVS1804R,S,T,W380-440VS/P/C

Connection1

LVS1804S,T,W,XWye, 3 PhaseWye, 3 Phase

80-150CWye, 3 Phase

80-125C80-150C

73x0.8Voltagex1.

kWx1000

Voltage

x1000haseFactorkWxSingleP