Instrument Transformer Accuracy ND INSTRUMENT TRANSFORMER ACCURACY NOV 2007.DOC © Northern Design (Electronics) Ltd 8 December 2007 Page 1 of 1 Northern Desi g n (Electronics) Ltd, Bolton Road, BRADFORD BD3 0QW, UK Tel: +44 (0) 1274 750 620 Fax: +44 (0) 1274 721 074 E-mail: [email protected] www.ndmeter.co.uk Instrument transformer accuracy is normally specified in terms of 'Class' values. These are defined in the relevant Standards, BS EN 60044-4 for Current Transformers and BS EN 60044-2 for Voltage (or Potential) Transformers. The figures quoted below are based on extracts from the standards. Current Transformers Accuracy Class Ratio Error % Reading Phase Error Minutes Worst Case kW Error % Reading 100% FLC 20% FLC 5% FLC 1% FLC 100% FLC 20% FLC 5% FLC 1% FLC 5% FLC PF = 0.5 5 5 N/A 3 3 N/A 1 1 1.5 3 60 90 180 11.9 0.5 0.5 .75 1.5 30 45 90 6.0 0.5S 0.5 0.5 0.75 1.5 30 30 45 90 3.01 0.2 0.2 0.35 0.75 10 15 30 2.25 0.2S 0.2 0.2 0.35 0.75 10 10 15 30 1.10 0.1 0.1 0.2 0.4 5 8 15 1.15 NOTE Class 5 and Class 3 CTs are only specified for Ratio Error, at 120% FLC and 50% FLC. Class 0.5S and Class 0.2S, which are mainly designed for precision CT operated Meters, are only defined for a 5 Amp nominal output, have an operating range of 50mA to 6 Amp. For Class 0.1, 0.2, 0.5 and 1 CTs, the current errors and phase displacements shewn above are the maximum permissible when the secondary burden is any value between 25% and 100% of the rated burden, and operation is at rated frequency. The present standard does not allow rated burdens of less than 1 VA. Voltage Transformers Class Percentage Voltage (ratio) error % Reading Phase Displacement - Minutes Worse Case kW Error PF = 0.5 0.1± ± 0.1% 5 ± 0.35% 0.2 ± 0.2% 10 ± 0.70% 0.5 ± 0.5% 20 ± 1.5% 1.0 ± 1.0% 40 ± 3.0% 3.0 ± 3.0% Not Specified Not Specified NOTE A Class 3 VT is specified only for Ratio Error. For all the above VTs, the voltage errors and phase displacements shewn are the maximum permissible at any voltage between 80% and 120% of rated voltage, when the secondary burden is any value between 25% to 100% of the rated burden, the burden Power Factor is 0.8 lagging, and operation is at rated frequency Usage of Transformers For general kW and kWh measurement Class 1 For kW and kWh measurement at poor Power Factors Class 0.5 High Accuracy Measurements Class 0.5 or better Laboratory or Standards Room use Class 0.2 or better

Transcript of CT VT Accuracy

Page 1: CT VT Accuracy

Instrument Transformer Accuracy

ND INSTRUMENT TRANSFORMER ACCURACY NOV 2007.DOC © Northern Design (Electronics) Ltd 8 December 2007 Page 1 of 1

N o r t h e r n D e s i g n ( E l e c t r o n i c s ) L t d , B o l t o n R o a d , B R A D F O R D B D 3 0 Q W , U K T e l : +4 4 ( 0) 12 7 4 7 50 62 0 Fa x : +4 4 ( 0 ) 12 7 4 7 2 1 0 7 4 E -ma i l : s a l e s@ n d me t er . co . u k www. nd me te r . co . u k

Instrument transformer accuracy is normally specified in terms of 'Class' values. These are defined in the relevant Standards, BS EN 60044-4 for Current Transformers and BS EN 60044-2 for Voltage (or Potential) Transformers. The figures quoted below are based on extracts from the standards.

Current Transformers

Accuracy Class

Ratio Error % Reading

Phase Error Minutes

Worst Case kW Error

% Reading 100%

FLC 20% FLC

5% FLC

1% FLC

100% FLC

20% FLC

5% FLC

1% FLC

5% FLC PF = 0.5

5 5 N/A 3 3 N/A 1 1 1.5 3 60 90 180 11.9

0.5 0.5 .75 1.5 30 45 90 6.0 0.5S 0.5 0.5 0.75 1.5 30 30 45 90 3.01 0.2 0.2 0.35 0.75 10 15 30 2.25

0.2S 0.2 0.2 0.35 0.75 10 10 15 30 1.10 0.1 0.1 0.2 0.4 5 8 15 1.15

NOTE Class 5 and Class 3 CTs are only specified for Ratio Error, at 120% FLC and 50% FLC. Class 0.5S and Class 0.2S, which are mainly designed for precision CT operated Meters, are only defined for a 5 Amp nominal output, have an operating range of 50mA to 6 Amp. For Class 0.1, 0.2, 0.5 and 1 CTs, the current errors and phase displacements shewn above are the maximum permissible when the secondary burden is any value between 25% and 100% of the rated burden, and operation is at rated frequency. The present standard does not allow rated burdens of less than 1 VA.

Voltage Transformers

Class Percentage

Voltage (ratio) error

% Reading

Phase Displacement

- Minutes

Worse Case kW Error PF = 0.5

0.1± ± 0.1% 5 ± 0.35% 0.2 ± 0.2% 10 ± 0.70% 0.5 ± 0.5% 20 ± 1.5% 1.0 ± 1.0% 40 ± 3.0%

3.0 ± 3.0% Not Specified

Not Specified

NOTE A Class 3 VT is specified only for Ratio Error. For all the above VTs, the voltage errors and phase displacements shewn are the maximum permissible at any voltage between 80% and 120% of rated voltage, when the secondary burden is any value between 25% to 100% of the rated burden, the burden Power Factor is 0.8 lagging, and operation is at rated frequency

Usage of Transformers For general kW and kWh measurement Class 1 For kW and kWh measurement at poor Power Factors Class 0.5 High Accuracy Measurements Class 0.5 or better Laboratory or Standards Room use Class 0.2 or better