Comfort Systems USA (Arkansas), Inc. P.O. Box 16620 Little Rock, AR 72231 Phone 501-834-3320 Fax 501-834-5416 4806 Rixey Road No. Little Rock, AR 72117 Date: 10/28/2019 Return Request: 11/4/2019 Project: Lockheed Martin ATACMS PrSm Building Supplier: Woodbury Beach Manufacturer: Durafin Submittal: Steel Water Tube Boilers Submittal Number: 23 52 33.16-01 Spec Section: 23 52 33.16, 2.01-2.06 Drawing # and Installation: Mechanical Drawings ARCHITECT ENGINEER Cromwell Architects Engineers Cromwell Architects Engineers 1300 E. 6 th Street 1300 E. 6 th Street Little Rock, AR 72202 Little Rock, AR 72202 501-372-2900 501-372-2900 GENERAL CONTRACTOR MECHANICAL SUBCONTRACTOR Baldwin & Shell Construction Comfort Systems USA (Arkansas), Inc. 1000 W. Capitol Ave. 4806 Rixey Road Little Rock, AR 72201 North Little Rock, AR 72117 501-374-8677 501-834-3320 CSUSA PROJECT NO. 19-212 [email protected] *Lead times for this item will be 9-10 weeks; +/- weeks due to the Holidays, factories shut down process from the of November through the beginning of the new year.

Transcript of CSUSA PROJECT NO. 19-212 [email protected]/Matt/19-212 Lockheed Martin... ·...

Page 1: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

Comfort Systems USA (Arkansas), Inc. P.O. Box 16620

Little Rock, AR 72231 Phone 501-834-3320

Fax 501-834-5416

4806 Rixey Road No. Little Rock, AR 72117

Date: 10/28/2019 Return Request: 11/4/2019 Project: Lockheed Martin ATACMS PrSm Building Supplier: Woodbury Beach Manufacturer: Durafin Submittal: Steel Water Tube Boilers Submittal Number: 23 52 33.16-01 Spec Section: 23 52 33.16, 2.01-2.06 Drawing # and Installation: Mechanical Drawings

ARCHITECT ENGINEER Cromwell Architects Engineers Cromwell Architects Engineers 1300 E. 6th Street 1300 E. 6th Street Little Rock, AR 72202 Little Rock, AR 72202 501-372-2900 501-372-2900

GENERAL CONTRACTOR MECHANICAL SUBCONTRACTOR Baldwin & Shell Construction Comfort Systems USA (Arkansas), Inc. 1000 W. Capitol Ave. 4806 Rixey Road Little Rock, AR 72201 North Little Rock, AR 72117 501-374-8677 501-834-3320

CSUSA PROJECT NO. 19-212

[email protected]

*Lead times for this item will be 9-10 weeks; +/- weeks due to the Holidays, factories shut down processfrom the of November through the beginning of the new year.

Page 2: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

Hot Water Boiler Submittal B1, B2 & B3 SPEC 23 53 33 16

PROJECT: Lockheed Martin – ATACMS PrSM Building East Camden, Arkansas CONTRACTOR: Comfort Systems USA North Little Rock, Arkansas ENGINEER: Cromwell Firm Little Rock, Arkansas EQUIPMENT Three (3) Rite Model #D10000 Durafin atmospheric factory packaged steel watertube hot water boilers each rated at 10,000 MBH input and de-rated 6972 MBH output with Glycol additives firing natural gas. Boiler trim and accessories to include for each unit: - 160 psi ASME design pressure - Power Flame CR5-G-30HTD high turndown 10:1 low NOx burner full modulating burner with

UL gas train (7-14” wc gas pressure) - U.L./ASME CSD-1 control group/Arkansas State Code - Electrical: 460v/3/60 with 115v/1/60 control voltage - Flame safeguard controls - High limit controls, manual reset. Probe type low water cutoff. - High and low gas pressure switches - Alarm bell and silencer - Hinged headplates. - Durafin control panel with operating and failure indicating lights with relays for remote

alarms outputs for the following: Flame Failure, Low Water Cut-off, High Stack Temp, High Firebox Pressure, Boiler Condensing plus options of Low Gas Pressure, High Gas Pressure and High Limit

- Siemens RWF temperature controls for BACnet communication. - 6” 3-way valves with actuators, temp control and sensors for low temp protection shipped

loose for field piping between supply and return lines by Others. Controller allows input from BMS or stand-alone with supplied RTD.

- 22” flue outlet each (stack and cap by Others, vent supplier to spec flue size) - Weight at 16,500 lbs. each Drawings Included: Rite Engineering Data Sheets, Burner Data, Control Panel Detail, 3-Way Valve Data Submitted by: Dain Matthey Date: October 1, 2019

Woodbury-Beach Company 6329 Crystal Hill Road

No. Little Rock, AR 72118 Phone: 501-753-8323 Fax: 501-753-8350

Page 3: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever
Page 4: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever
Page 5: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

• DIMENSIONS ARE IN INCHES AND SUBJECT TO PRODUCTION TOLERANCES. WHENEVER TOLERANCES ARE CRITICAL, NOTIFY THE FACTORY BEFOREHAND.• WEATHERPROOF BOILERS WILL SLIGHTLY INCREASE IN WIDTH, LENGTH AND HEIGHT.• OIL FIRED BOILER DIMENSIONS WILL VARY - ESPECIALLY #4, #5 & #6 OIL.• RIGGING: MODELS D300 TO D5000 ARE DESIGNED TO BE FORKLIFTED FROM EITHER SIDE. TIE DOWN EYES (4) ARE 21/2” DIAMETER AND CAN BE USED FOR

HOISTING. MODELS D5500 AND LARGER HAVE LIFTING LUGS IN THE FRONT AND REAR HEADPLATES FOR OFFLOADING AND RIGGING.• HINGES AND ACCESS DOOR: THE BURNER (FIREBOX ACCESS) DOOR AND BOTH THE HEADPLATES ARE HINGED ON THE RIGHT HAND SIDE AS SHOWN

ABOVE (LEFT HAND AVAILABLE IF SPECIFIED). THE REAR HEADPLATE CAN BE SPECIFIED NON-HINGED IF SPACE DOES NOT PERMIT FULL OPENING.• ALL HINGE PINS ARE REMOVABLE FOR “ZERO” SWING REQUIREMENT. 24” SPACE IS RECOMMENDED AT THE REAR FOR TUBE MAINTENANCE.• ANCHORING: 4 ANCHORING PADS ARE PROVIDED. O.D. TO O.D. PAD LENGTH = BASE LENGTH “A” DIMENSION. PADS ARE 3/8” THICK. PREDRILLED

ANCHOR HOLES IN PADS ARE: 9/16” FOR D300-D1000, 11/16” FOR D1250-D5000 AND 13/16” FOR D5500-D10000.• “D” & “E” FLANGES ARE ANSI 150 LBS. RAISED FACE.• CALCULATED ACFM BASED ON NATURAL OR L.P. GAS @ 25 FEET-PER-SECOND STACK VELOCITY, 300º F STACK TEMPERATURE, 25% EXCESS AIR AND

SEA LEVEL ELEVATION.• “ZERO” TUBE PULL CLEARANCE REQUIRED. NATIONAL BOARD INSPECTION CODE I-3340 REQUIRES 36” CLEARANCE ON BOTH SIDES.

Rev. 9/2007

A B C COA D E F G H J*

BASE LENGTH

OVERALLWIDTH

FLANGES &STACKHEIGHT

OVERALLHEIGHT

WATER RETURN (IN)

WATER SUPPLY (OUT)

C/L TO C/L SUPPLY &RETURN

ROUND VENT CONNECTOR

O.D.

POWERBURNER

HEADPLATE SWING

D1000 59 35 58 68 3 FL 3 FL 12 7 23 29 23 291 50

D1250 70 35 58 68 3 FL 3 FL 12 8 23 29 23 364 55

D1500 81 35 58 68 3 FL 3 FL 12 8 23 29 23 436 55

D1750 92 35 58 68 3 FL 3 FL 12 9 23 29 23 509 55

D2000 103 35 58 68 3 FL 3 FL 12 9 23 29 23 582 55

D2250 114 35 58 68 3 FL 3 FL 12 10 43 29 23 654 60

D2500 125 35 58 68 3 FL 3 FL 12 10 43 29 23 727 60

DA2000 73 49 58 68 4 FL 4 FL 20 9 23 44 37 582 55

DA2250 80 49 62 72 4 FL 4 FL 20 10 43 44 37 654 60

DA2500 86 49 62 72 4 FL 4 FL 20 10 43 44 37 727 60

D2750 93 49 62 72 4 FL 4 FL 20 12 43 44 37 800 60

D3000 99 49 62 72 4 FL 4 FL 20 12 43 44 37 873 65

D3500 112 49 62 72 4 FL 4 FL 20 12 46 44 37 1018 65

D4000 125 49 62 72 4 FL 4 FL 20 14 46 44 37 1163 70

D4500 138 49 62 72 4 FL 4 FL 20 14 46 44 37 1309 70

D5000 151 49 62 72 4 FL 4 FL 20 14 46 44 37 1454 70

D5500 122 67 65 75 6 FL 6 FL 23 16 46 63 56 1600 70

D6000 131 67 65 75 6 FL 6 FL 23 16 46 63 56 1745 75

D6500 140 67 65 75 6 FL 6 FL 23 16 53 63 56 1890 75

D7000 148 67 65 75 6 FL 6 FL 23 18 53 63 56 2036 75

D7500 157 67 65 75 6 FL 6 FL 23 18 53 63 56 2181 75

D8000 143 78 65 75 6 FL 6 FL 31 18 53 73 67 2327 80

D8500 150 78 65 75 6 FL 6 FL 31 18 53 73 67 2472 80

D9000 157 78 65 75 6 FL 6 FL 31 20 53 73 67 2618 80

D9500 164 78 65 75 6 FL 6 FL 31 20 53 73 67 2763 80

D10000 172 78 65 75 6 FL 6 FL 31 20 53 73 67 2908 80

SOUND LEVELS

(dBA)

ACFMSTACK

EXHAUST

TOTAL#

TUBES

BOILER

MODEL

Rite Durafin™ Boilers160 PSIG Models, Dimensions & Ratings

* HINGE PINS ARE REMOVABLE TO

ELIMINATE SWING CLEARANCE.

J*J*

ZERO INCHES REQUIRED FOR

TUBE REPLACEMENT

FORKLIFT UP TO D5000

GAS/OIL CONNECTIONS

D300 29 35 58 68 2 MNPT 2 MNPT 12 4 23 29 23 87 50

D500 37 35 58 68 2 MNPT 2 MNPT 12 5 23 29 23 145 50

D750 48 35 58 68 2 MNPT 2 MNPT 12 6 23 29 23 218 50

D10000 172 78 65 75 6 FL 6 FL 31 20 53 73 67 2908 80

Page 6: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

!"#$%"#$#&'!()*+,-+,-

.../01234052/647289*9:

;4/<+;=;>4.?@

ABCDEFGHIBCGCJKGLCKMDGN

1(1OPQ0R>1P8(05(352S

(O51Q0R>1P8(05(352S

T #'UVFWXDGNYKWBXLKZF[YLN\'"UXDGNYKWBXLK&"F[YLN\

T MDGN]DGDNF_C KaWDGWXWNLDKBGLWGbLLKKFCVFLYFGKCCVFCFG[\

T MDGWKKC]DGKCWCWVFLYc_WK]cKCN]CVWCFaCNKLK]c\

T dF]]BCD_NDGWLFWD_NYDaNLDLBNFGWF]DLFG[F[YLN\

T dXDGNYDaLYEKKVFG[C KL]K `BGF]DLFKGN d#efdJCD_EKCC KLNLDCLgNLKX AC_]KGLD]LNLKFGWF]DLBCGCKG AC_]KGLD]LNLKFGWF]DLBGN]YWBWhDDC iNYBLWKVG d FFL_LKD]]XLeLK#jFFD XC KLNF[GDVYGEFCFG[FNKWBDLFKG

T kYGXKVCNBXX_ClBFCWFNKCLYDL&#jfdJmDNLXWKVGLCDGNEKC CVFLYEBNXCKL]LFKGFNNLDGWDCW\

T YXKVWC]KDLWnFLBXDGNYDYFG[WFGLVKXD]NEKCD]]NNDGWNCaF]FG[\

odpAdnA qMrqpds

4.2/ ? 4/?(352

Q0701P/482? /2tO/R2u652 Q4.0/2 ?

(55v4/2(1 R?0104? ? 0R>0/2 ?

(0?O25 0541 ? Q4.0/245w

odpAdnA qMrqpds

5(72(05O/2 /07(/uQ4.(12/O1, vv 0R>(12//2PPO/2

Q4.(12/O1, vv 264?w(/uQ4.(12/O1, vv Q4.(12//2PPO/2

0R>1(6x27t2/(1O/2 Q4.(P/2PPO/2 Q4.(12/54.

0R>0/234)/2PPO/2 0R>(P/2PPO/2 (Py(582

0R>Q0701 0R>7302?14052/4?w2?P0?R=1/432Q0R>1@ O/?2/44/ t2? /(v1t055

;

*z;

-|

dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
dmatthey
Line
Page 7: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

MODEL CGMODEL CG HTDFORCED DRAFTBURNERS

GAS 98,000 -19,100,000BTU/HR.

The Power Flame Model CG gas burner presents optimum state-of-the-art design for maxi-mum combustion efficiency and operating dependability. These packaged combustion systems will fire natural gas and a full range of waste or other gaseous fuels. The Model CG HTD (High Turndown) will fire natural gas at turndowns up to 10 to 1. The flame retention firing head incorp-orates the nozzle mix multiport combustor and unique air sand-wich design to produce full range stable performance in both positive or negative combustion cham- ber environments. Operating system

adjustments have been minimized to provide trouble free start up and operating performance. The Model CG produces efficient combustion without the aid of refrac-tory or other costly flame support devices. Optional features include the premix and low gas pressure firing heads for limited size combus-tion chamber configurations or low gas pressure conditions. Modular design produces added flexibility for a wide range of optional fea-tures. All Power Flame packaged combustion systems are factory fire-tested to ensure cost effective installation and start up.

Adjustable Premix Firing HeadProduces optimum fuel-airmixture within the premix combustion zone*

Circular Furnace OpeningNo special cutting of combustion chamber front plate

Low Gas Pressure Firing HeadAdded flexibility of application for low gas pressure conditions*

*Optional

Total Access PanelSwing out, easily removable top and front panels give total access to all internal panel-mounted components

Graphic Burner Management SystemDirector® graphic annunciation of critical burner functions* CG-1090 Rpt. 1211

Power Flame’sVersatile High PerformanceGas Burner

Characterized Fuel MeteringVaricam® provides adjustable and accurately repeatable fuel-air ratios throughout the firing range*

®

Alpha System™LED indicators, switches and operator annunciator. (Optional additional 6-light board shown on right.)

Page 8: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

Flame Safeguard with UV and intermittent pilotFlame Safeguard with UV and interrupted pilotOn-Off diaphragm gas valve with fixed air control manual adjustmentLow-Hi-Off motorized gas valve with automatic air controlLow-Hi-Low motorized gas valve with automatic air control

Modulation with automatic air control (Standard on all CG HTD)Dual gas safety valves AHigh and Low gas pressure switchesNova Low NOx systemsCustomized control systems and accessoriesMan/Auto switch - manual potentiometer-modulation units

STANDARD EQUIPMENT Alpha System™ LED (power, demand, main fuel, FSG alarm, selectable) and control switch Gas electric pilot and gas ignition transformer Leakage test cock, pilot cock and main gas cock Pilot and main gas pressure regulators Air safety switch

DIMENSIONS RATINGS & SPECIFICATIONS(Inches) Standard Models.CAPACITY1

© Copyright Power Flame Incorporated 2004 Printed in U.S.A.

®

Conforms to UL795

C1-G-10C1-G-12C2-G-15

C2-G-20A C2-G-20B C3-G-20C3-G-25C3-G-25B

C4-G-25 C4-G-30C5-G-30(B)

C6-G-30

C7-G-30C8-G-30

®

MODEL CR (For low centerline applications)

ADDED FEATURESX-Standard O-Optional NA-Not Available

Web Site: http://www.powerflame.comE-Mail: [email protected]

Phone 620-421-0480Fax 620-421-0948

2001 South 21st Street Parsons, KS 67357

MODEL C

5,000 MBH and below may be replaced by one (1) proof of closure valve; Above 5,000 MBH one (1) of the safety valves will include proof of closure feature.

Optional NOVA Low NOx systems: Induced Flue Gas Recirculation shown.

®

XOXOOOXOOOX

XO

NAXOOXOOOX

NAX

NAXOOXXOOX

NAX

NAXOOXXOOX

NAX

NAXOOXXOOX

NAX

NANANAXXXOOX

NAX

NANANAXXXOOX

A

BurnerModel

C1-G-10

C1-G-12C2-G-15C2-G-20AC2-G-20B

C3-G-20

C3-G-25C3-G-25BC4-G-25

C4-G-30C5-G-30(B)C6-G-30

C7-G-30C7-G-30BC8-G-30

A

341/8

341/8

391/8

391/8

391/8

44444450

5050

497/8

5111/16

5111/16

569/16

B

313/16

313/16

41/2

41/2

41/2

51/4

51/4

51/4

61/4

61/4

61/4

61/4

81/8

81/8

81/8

B(R)

59/16

59/16

61/8

61/8

61/8

77

775/16

75/16

75/16

75/16

101/8

101/8

101/8

C

141/2

141/2

147/8

147/8

147/8

165/8

165/8

165/8

187/8

187/8

187/8

187/8

245/16

245/16

271/8

C(R)

141/2

141/2

141414

151/4

151/4

151/4

1711/16

1711/16

1711/16

1711/16

223/8

223/8

275/8

D

45/8

45/8

51/4

51/4

51/4

66

67

77

73/4

83/4

83/4

83/4

E

121/4

121/4

141414

161616

181/2

181/2

181/2

197/8

18

1820

F**

202020

2020

223/8

223/8

223/8

28

28261/2

261/2

2113/16

2113/16

243/8

GStd.

31/4

31/4

444

41/2

41/2

41/2

6

665

47/8

47/8

31/4

G*Max.

43/4

43/4

63/4

63/4

63/4

8889

99

111/2

111/4

111/4

95/8

H

71/4

71/4

83/4

83/4

83/4

101/8

101/8

101/8

121/8

121/8

121/8

135/8

155/8

155/8

155/8

I

73/8

73/8

81/2

81/2

81/2

111/2

111/2

111/2

141/4

141/4

141/4

141/8

137/8

137/8

121/4

K

101/4

101/4

101/4

101/4

101/4

101/4

101/4

101/4

101/4

101/4

101/4

101/4

91/8

91/8

91/8

L

171/8

171/8

187/8

187/8

187/8

222222

265/8

265/8

265/8

261/2

261/2

261/2

247/8

S

125/8

125/8

133/8

133/8

133/8

151/2

151/2

151/2

191/8

191/8

191/8

19

1919

175/16

X

71/4

71/4

81/2

81/2

81/2

10101012

1212

131/2

131/2

131/2

131/2

Nat. GasMBH Max.

9801,3602,2002,5003,080

4,2004,7185,2506,300

7,84010,50014,215

17,00017,70019,100

NominalBoiler H.P.

Max.

23.532.352.360.073.5

100.0112.0125.0150.0

190.0250.0340.0

404.0421.0454.0

BlowerMotor H.P.

(3450RPM)1/3

1/3

1/2

3/4

1

11/2

11/2

33

571/2

10

152015

StandardGas TrainSize(In.)

111/4

11/2

22

221/2

21/2

21/2

333

333

Gas PressureRequired(In. W.C.)2

5.65.35.24.84.8

7.67.07.210.0

12.119.9,17.8

26.5

40.045.050.0

1. Capacities listed are based on 0.20” W.C. positive pressure, except for C5-G-30B, which is rated at +1.2” W.C. Refer to capacity curves for derates based upon combustion chamber pressure. 2. At inlet to main manual shutoff cock to obtain P/F certified ratings with standard U.L. gas train. Optional gas trains and combustion heads available for lower pressures. * This dimension may be increased. Consult factory. ** This dimension depicts space required to accomodate a standard gas train.

MODEL CR

C5-G-30(

NAX

NANANAXXXOOX

C5-G-30( 50 61//4 75/5/16 187/7/8 1711//16 7 181//2 261//2 6 9 121//8 141//4 101//4 265/5/8 191//8 12 10,500 250.0 71//2 3 19.9,17.8

Page 9: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

CC1N7865EMarch 28, 2000

Siemens Building TechnologiesLandis & Staefa Division

ISO9001

7865

Compact UniversalControllers

RWF40...

The RWF40... is a universal digital boiler temperature / pressure controller withfunctions designed specifically for the control of heat generating plant.

The RWF40... and this data sheet are intended for use by OEMs which integratethe controller in their products!

Mechanical design

The controller is supplied complete with a housing for flush panel mounting. TheRWF40... is matched to the controlled variable and the required setpoint range bymaking parameter settings. The control parameters can be set and optimized while theburner is running. All settings are made with four buttons located on the unit front andare directly displayed.

LEDs on the front indicate the following operational statuses:- Control «ON / OFF»- Positioning pulses «ON» or «OFF» for driving the burner´s air damper when using

modulating burner control, or «Stage I / stage II» when using two-stage burnercontrol

- «Two-stage» operating mode- Position of the configurable contact «K6»- Manual control «ON / OFF»

During operation, the digital displays above the LEDs show the setpoint (green), theactual value (red) and – when making parameter settings – the relevant parameters.

RWF40... complete with housing

Page 10: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

2/7

Siemens Building Technologies CC1N7865ELandis & Staefa Division 28.03.2000

Warning notesTo avoid injury to persons, damage to property or the environment, the followingwarning notes should be observed!It is not permitted to open, interfere with or modify the controller!

• When selecting the cables, when making the installation and the electrical connec-tions, observe the regulations of VDE 0100 «Erection of power installations withrated voltages below AC 1000 V» and the relevant national regulations

• The electrical connections may only be made by authorized staff• Provide double-pole isolation of the controller from the mains supply if there is a

risk of touching live parts while work is carried out

Installation notesPlease observe the notes given in the user documentation CC1B7865E.

Service notes• For service purposes, the controller can be removed from is housing with no need

for tools• The electrical connections are made via the screw terminals located at the rear of

the housing

Type summaryController with RWF40.000A97- three-position output- housing- fixing material and seal

Controller with RWF40.001A97- three-position output- analog output- housing- fixing material and seal

Controller with RWF40.002A97- three-position output- analog output- RS-485 port- housing- fixing material and seal

Packaging variants RWF40.010A97RWF40.011A97RWF40.012A97

Adapter frame for replacing the RWF32... ARG40

Bracket ARG41For mounting the RWF40... on 35 mm DIN rails to DIN 46277

Dummy cover AVA10.200/109For covering a panel cutout for the RWF40...

Accessories

Page 11: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

3/7

Siemens Building Technologies CC1N7865ELandis & Staefa Division 28.03.2000

Technical data

Mains voltage AC 100...240 V ±10 %

Mains frequency 50...60 Hz

Safety class II to DIN 0631

Mounting orientation optional

Terminals for 2 x 1.5 mm² or 1 x 2.5 mm²

Power consumption approx. 8 VA

Safety extra low voltage DC 24 V

Contact rating of the control outputs (relays«K1...K3»)- Up to 2 x 105 switching cycles- Up to 107 switching cycles

max. 2 A; AC 24...240 Vmax. 0.1 A; AC 24...240 V

Weight complete with housing approx. 760 g

Recommended actuator running time 15...60 s

Degree of protection of housing- Front- Base

IP 65, EN 60529IP 20, EN 60529

TransportTemperature range -40...+70 °C

Humidity < 75 % r.h.

OperationTemperature range -20...+50 °C

Humidity < 75 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

CE conformityAccording to the directives of the European Union

Electromagnetic compatibility EMCaccording to NAMUR recommendation

NE 21, EN 50 081 Part 1 andEN 50 082 Part 2

General controller data

Environmentalconditions

Page 12: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

4/7

Siemens Building Technologies CC1N7865ELandis & Staefa Division 28.03.2000

Function

The RWF40... provides the following functions:- One digital PID controller with a three-position or analog output (optional)- To control two-stage burners, the RWF40... can be switched over to provide two-

position control- Automatic thermostat (or pressurestat) function in low-fire operation- One shift controller for weather-dependent setpoint shifting- One minimum limiter and one maximum limiter for the boiler temperature or the

boiler pressure- One limit thermostat to DIN 3440- One potential-free configurable contact- Manual operating mode- Communication via serial port (option)- Self-setting function

Ω

AC 100 ...240 V ±10 %,48...63 Hz

3 analog inputs

2 binary inputs

Power supplySerial port (optional)

Release of burner

3-position output

Limit comparator

Modulating output (optional)

Power supply measuring transducerRW

F40.

..

7865f01e/0400

Input 1:Actual valuefor Pt100, Ni100, Pt1000,Ni1000 thermocouples orstandard signals

Input 2:External setpoint,setpoint shiftingfor 0...1 k resistoror linearized standardsignals

Input 3:Outside temperaturefor Pt1000, Ni1000

For potential-free contacts

Input 1:Operating modechangeover

Input 2:Setpoint shifting /changeover

Output 1:- Relay (N.O. contact)

Output 2:-Relay (regulating unit open)

Output 3:- Relay (regulating unit closed)

Output 4:- Relay (N.O. contact)

DC 24 V, 30 mA(short-circuit-proof)

Output 5:

DC 0...10 V, DC 0...20 mADC 4...20 mA

RS-485MOD bus protocolBaud rate 9600

Block structure

Page 13: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

5/7

Siemens Building Technologies CC1N7865ELandis & Staefa Division 28.03.2000

Function of the controller when used for burner controlIn low-fire operation, the RWF40... operates like a control thermostat or pressurestat.This means that it operates as a two-position controller maintaining the required set-point by switching the burner on and off. The switching differential for two-position op-eration can be adjusted within a wide range. If the demand for heat increases, the con-troller switches to high-fire operation only when an adjustable limit is exceeded. Thisfunction is aimed at optimizing the burner´s switching ratio.

In that case, the RWF40... operates as a two-position controller with adjustable switch-ing thresholds. Using the relays of the three-position output, the RWF40... drives theactuator to the 1st and 2nd output stage. In this operating mode, the optional analogoutput switches between the minimum signal for the 1st stage and the maximum outputsignal for the 2nd stage.

In that case, the RWF40... operates as a PID / PI controller with a three-position outputwithout position feedback signals or, optionally, with a modulating output. By makinguse of its self-setting facility, the RWF40... is able to determine the PID / PI controlparameters, or the parameters can be set manually.

Using a potential-free contact, the RWF40... can be switched from the modulatingmode to two-stage operation.

In the case setpoint shifting is configured, the current setpoint is shifted by an adjust-able amount. Configuration of setpoint changeover provides changeover between twosetpoints adjusted on the RWF40... If analog input 2 is configured for an external set-point, changeover is provided between the setpoint adjusted on the RWF40... and anexternal setpoint.

Potential-free contact «K6» can be assigned a number of functions.Example: limit value supervision

Four buttons on the unit front are used to operate and program the RWF40... . Duringoperation and programming, the seven-segment displays show the parameter valuesand parameter names.

The controller´s standard configuration ex works is such that when connecting aQAC22 outside sensor, automatic changeover to weather-dependent setpoint shiftingtakes place.

The signal delivered by the QAC2... outside sensor may not be fed parallel to sev-eral RWF40...!

To acquire the actual value, a number of sensors can be connected to the RWF40...

Measurement range

Pt100 / IEC 751 -200...+850 °CPt1000 / IEC 751 -200...+850 °CNi100 / DIN 43760 -60...+230 °CNi1000 / DIN 43760 -60...+230 °C

Two-or three-wire resis-tance sensors

L&S-Ni1000 -50...+160 °C

NiCr-Ni / type «K» -200...+1372 °CCu-Cu-Ni / type «U» -200...+400 °CNiCroSil-NiSil / type «N» -100...+1300 °C

Thermocouples

FeCuNi / type «J» -200...+1000 °C

0...20 mA Scaleable -1999...+99994...20 mA Scaleable -1999...+9999DC 0...10 V Scaleable -1999...+9999

Linearized standardsignals

DC 0...1 V Scaleable -1999...+9999

To power provided for the measuring transducers is DC 24 V / 30 mA.

Feeding a signal to analog input 2, the controller´s setpoint can be influenced. Theinfluence can be scaled.

The following signals can be used:- Input signals DC 0...1 V, DC 0...10 V, 0...20 mA, 4...20 mA- 1 kΩ potentiometer in a two-wire circuit

Low-fire operation

High-fire operation, two-stage control

High-fire operation,modulating control

Binary input 1(changeover of operat-ing mode)

Binary input 2 (setpointshifting or setpointchangeover)

Limit comparator

Operation

Weather-dependentsetpoint shifting

Analog input 1 (actualvalue sensor)

Analog input 2 (externalsetpoint shift or externalsetpoint)

Page 14: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

6/7

Siemens Building Technologies CC1N7865ELandis & Staefa Division 28.03.2000

Connection diagram (basic diagram)

Temperature and pressure control on a dual-fuel burner.Burner control and supervision are provided by burner control type LAL... or LFL...

DC 24 V at terminals «G+» and «G-» is used for powering the QBE620... pressuresensor!

N

0

I

QAE...

B

RWF40...L N G1+ M1B9 M9 XB6 M6 Q14 Y1 Y2 D1Q

L

M B M

QAC...M R

FZA...

LAL..., LFL...

4 5ST

GAS

BS

1 0 2

BV1

N

RV

LK

18 19

BV1

BV2

9 11 10 20

v a

Mz m

MIN.

SQ...

OIL

~

7865a01/0799

GND

int. ext.

D2

S1

Q13

N

0

I

QBE620...

B

RWF40...L N G+ M1 XU6 M6 Q14 Y1 Y2 D1Q

L

M

0...10 V

FZA...

LAL..., LFL...

4 5ST

GAS

BS

1 0 2

BV1

N

RV

LK

18 19

BV1

BV2

9 11 10 20

v a

Mz m

MIN.

SQ...

OIL

~

7865a02/0799

G

U1- G- GND

int. ext.

D2

S1

Q13

a Limit switch for air damper position «OPEN» QAE... Immersion temperature sensor

BS Operation selector QBE... Pressure sensor

1 = «gas» RV Gas control damper

(modulating burner control) S1 Internal / external setpoint switch (E)

2 = «oil» SQ... Actuator of burner´s air damper and gas

(two-stage burner control) control damper

BV... Fuel valve ST Connections for burner control´s start

FZA... Remote setpoint adjuster (active when control loop

«S1» is closed) v Auxiliary switch for the release of the

L... Burner control 2nd fuel valve depending on the air damper

LK Burner´s air damper position

m (MIN) Auxiliary switch for controlling low-fire z Limit switch for the fully «CLOSED»

operation position of the air damper

QAC... Outside sensor for weather-dependent

setpoint shifting

Note

Legend

Page 15: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

7/7

Siemens Building Technologies CC1N7865ELandis & Staefa Division 28.03.2000

Dimensions

Dimensions in mm48

96

91,5K6

PGM EXIT

RWF40

112

Panel cutout to DIN 43 700

45

92

+0,6

+0,

8

43,5

127,

5

15,5

7865

m0

1e/0

300

7865m02/0799

ARG40 adapter frame

© 2000 Landis & Staefa Produktion GmbH

Page 16: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

GB-12.6.03.02-B3-way Control Valves type G3FM-TM (AB-Middle)

Nodular cast iron, DN 65 - 600 mmCharacteristics• Nominal pressure

DN65 - 125 mm: PN 25, max. 100°C DN150 - 300 mm: PN 16,max. 100 °C

DN350 - 600 mm: PN 10,max. 100 °C• Slide in Nodular cast iron

ApplicationsControl valve type G3FM-TM is a three-way control valve with a slide for quarter turn operation designed for regulating of fresh water, lubricating oil and other liquid media.

The valves are designed for use in con-junction with industrial processes, district heating and marine installations with large water or lubricating oil volumes:

• Engine Jacket Cooling Water System• Lubricating Oil Cooling• Central Cooling Water System, etc.

The valves are designed for use in con-junction with valve motor type CAR with handle for manual operation or for use in conjunction with a pneumatic actuator.

DimensioningFor sizing of control valves the following equation can be used:

⎟⎟⎠

⎞⎜⎜⎝

⎛=Δ

Δ=

DesignThe valve body and the valve slide are made of nodular cast iron. The valve flanges are drilled according to EN 1092-2 (JIS B 2210 option).

Quality assuranceAll valves are manufactured under an ISO 9001 certification, and are pressure and leakage tested before shipment.For marine applications the valves can be supplied with relevant test certificates from recognized classification societies.

FunctionThe slide is firmly connected with the motor spindle. When the slide is in the one outer position by turning the spindle, connection A-AB is fully open and connection B-AB is fully closed. In the other outer position connection A-AB is fully closed and connection B-AB is fully open. In the intermediate positions the opening degrees change proportionally.The valve has a small tolerance between body and slide. To minimize the leakage an O-ring is mounted in a groove on the slide.

Technical dataMaterials:- Valve body, slide Nodular cast iron

EN-GJS-400-15- O-ring NBR 70AValve characteristic Almost linearLeakage Max. 0.5% Temperature range Max. 100°C Mounting See page 2Flanges EN 1092-2

PN 10/16/25- option JIS B 2210 5K Counter flanges (suggested for EN 1092-2) DIN 2632 – PN 10

DIN 2633 – PN 16 DIN 2634 – PN 25Max. pressure pL, against which the valve can close:

- DN 65 - 125 25 Bar- DN 150 - 300 16 Bar- DN 300 - 600 10 Bar

A

AB

B

Subject to change without notice.

Port numbering

Specifications

TypeFlange

connectionDN in mm

kvs-value 1)

Mixing valvem3/h

kvs-value 1)

Diverting valvem3/h

TorqueNm

Weightkg

65 G3FM-TM 65 95 120 61 2980 G3FM-TM 80 122 154 64 31

100 G3FM-TM 100 175 220 118 45125 G3FM-TM 125 245 330 224 63150 G3FM-TM 150 395 425 237 83200 G3FM-TM 200 800 1100 412 129250 G3FM-TM 250 1500 2100 568 177300 G3FM-TM 300 2000 2650 865 241350 G3FM-TM 350 2530 3380 1156 310400 G3FM-TM 400 3050 3950 1565 401450 G3FM-TM 450 3680 4480 1728 483500 G3FM-TM 500 4150 5250 2280 627600 G3FM-TM 600 4800 6050 2580 830

1) kvs-value for port A and B 50% open.

100-10

10

200 250

PN 10DN 350-800 mm

300 oC

100-10

16

200 250

PN 16DN 150-300 mm

300 oC

10

6

Bar

Bar

Not to be used

Not to be used

Pressure/Temperature diagram

(option)

(option)

PN 16DN 150-300 mm

100-10

16

200 250

PN 16DN 150-300 mm

300 oC

10

Not to be used

Bar

-10

16

25 PN25 DN65-125 mm

(option)

Clorius Controls A/SKajakvej 4 · DK-2750 Ballerup · DenmarkTel.: +45 77 32 31 30 · Fax: +45 77 32 31 31E-mail: [email protected]: www.cloriuscontrols.com

dmatthey
Line
Page 17: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

GB-22.6.03.02-B3-way Control Valves type G3FM-TM (AB-Middle)

Nodular cast iron, DN 65 - 600 mmDefinition of kvs-valueThe kvs-value is identical to the IEC flow coefficient kv and defined as the water flow rate in m3/h through the fully open valve by a constant differential pressure,

pv, of 1 bar.

MountingThe valve connections are marked A, B and AB. The slide is operating between A and B.Check slide position before installation in the pipe. The slide position is marked on the top of the shaft.

The valves can be installed with vertical as well as horizontal spindles. The valves must be mounted in a way that the valve actuator will be exposed to a minimum of moisture and unnecessary vibrations.

Valves can also be supplied in AB-Right configuration (data sheet 2.6.02.01).

StrainerIt is recommended to use a strainer in front of the control valve if the liquid contains suspended particles.

Dimension sketch

LL1

CH

H1

k D

b

d

150 mm

Subject to change without notice.

DimensionsEN 1092-2 ANSI Class 150 JIS B 2210 5K JIS B 2210 10K

Type Lmm

L1mm

Hmm

H1mm

bmm

Cmm

D (dia.)mm

k (dia.)mm

d mm dia.

(number)

D (dia.)mm

k (dia.)mm

d mm dia.

(number)

D (dia.)mm

k (dia.)mm

d mm dia.

(number)

D (dia.)mm

k (dia.)mm

d mm dia.

(number)

65 G3FM-TM 292 146 135 90 20 273 185 145 19x(8) 180 140 19x(4) 155 130 15X(4) 175 140 19x(4)80 G3FM-TM 292 146 140 94 20 273 200 160 19x(8) 190 152 19x(4) 180 145 19x(4) 185 150 19x(8)

100 G3FM-TM 350 175 158 112 17 273 235 190 23x(8) 230 190,9 19x(8) 200 165 19x(8) 210 175 19x(8)125 G3FM-TM 400 200 179 123 17 273 270 220 28x(8) 255 216 22x(8) 235 200 19x(8) 250 210 23x(8)150 G3FM-TM 438 219 196 139 20 276 290 240 23x(8) 280 241 22x(8) 265 230 19x(8) 280 240 23x(8)200 G3FM-TM 530 270 236 175 21 361 340 295 23x(12) 343 299 23x(8) 320 280 23x(8) 320 290 23x(12)250 G3FM-TM 592 300 273 205 23 361 400 355 28x(12) 407 362 26x(12) 385 345 23x(12) 400 355 25x(12)300 G3FM-TM 649 330 305 230 25.5 361 455 410 28x(12) 483 432 26x(12) 430 390 23x(12) 445 400 25x(16)350 G3FM-TM 717 360 337 255 25.5 361 505 460 23x(16) 534 477 29x(12) 480 435 25x(12) 490 445 25x(16)400 G3FM-TM 770 385 375 285 26 361 565 515 28x(16) 597 540 29x(16) 540 495 25x(16) 560 510 27x(16)450 G3FM-TM 820 410 391 310 26.5 556 615 565 28x(20) 635 578 32x(16) 605 555 25x(16) 620 565 27x(20)500 G3FM-TM 900 455 425 340 27.5 556 670 620 28x(20) 699 635 32x(20) 655 605 25x(20) 675 620 27x(20)600 G3FM-TM 1000 505 470 393 31.0 556 780 725 31x(20) 813 750 35x(20) 770 715 25x(20) 795 730 33x(24)

Clorius Controls A/SKajakvej 4 · DK-2750 Ballerup · DenmarkTel.: +45 77 32 31 30 · Fax: +45 77 32 31 31E-mail: [email protected]: www.cloriuscontrols.com

dmatthey
Text Box
6" ANSI Flg.
Page 18: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

142 www.cloriuscontrols.com

Subject to change without notice.

3-way Control Valve type G3FM-TM (AB-Middle)Nodular cast iron, PN16, DN 80 - 250 mm / PN10, DN 300 - 450 mm

Control valve type G3FM-TM is a threeway control valve with a slide for quarter turn operation designed for regulating of fresh water, lubricating oil and other liquid media. The valves are designed for use in conjunction with industrial processes, district heating and marine installations with large water or lubricating oil volumes:

• Engine Jacket Cooling Water System• Lubricating Oil Cooling• Central Cooling Water System, etc.

The valves are designed for use in conjunction with valve motor type CAR with handle for manual operation or for use in conjunction with a pneumatic actuator.

The valve body and the valve slide are made of nodular cast iron.The valve fl anges are drilled according to EN 1092-2 (JIS B 2210 option).

APPLICATIONS

DESIGN

FUNCTION

FEATURES

TECHNICAL DATA

Materials:- Valve body, slide Nodular cast iron

EN-GJS-400-15- O-ring NBR 70A- U-ring PTFEFlow characteristic Almost linearLeakage rate Max. 0.5%Regulating capability Kvs/Kvr > 25

Flanges EN 1092-2 PN 10/16- Option JIS B 2210 5KCounter fl anges (suggested forEN 1092-2) DIN 2633 – PN 16Max. pressure ΔpL, against which thevalve can close: - DN 250 16 Bar- DN 450 10 BarNominal pressure- DN 250 mm PN 16, max. 100°C- DN 450 mm PN 10, max. 100 °CSlide in Nodular cast iron

The slide is firmly connected with the motor spindle. When the slide is in the one outer position by turning the spindle, connection A-AB is fully open and connection B-AB is fully closed. In the other outer position connection A-AB is fully closed and connection B-AB is fully open. In the intermediate positions the opening degrees change proportionally.The valve has a small tolerance between body and slide. To minimize the leakage an O-ring is mounted in a groove on the slide.

Simple design secures reliable controls and reduces costly downtime.Low leakage rate secures energy savings.Flexible choice of port placement

0-2.6.03.02-B Page 1 of 4

Page 19: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

143www.cloriuscontrols.com

PORT NUMBERING

Mixing

Diverting

PRESSURE/TEMPERATURE DIAGRAMAccording to DIN 2401

The valve connections are marked A, B and AB. The slide is operating between A and B. Check slide position before installation in the pipe. The slide position is marked on the top of the shaft. The valves can be installed with vertical as well as horizontal spindles. The valves must be mounted in a way that the valve actuator will be exposed to a minimum of moisture and unnecessary vibrations. Valves can also be supplied in AB-Right confi guration (data sheet 0.2.6.02.01) or AB-Left (data sheet 0.2.6.03).

MOUNTING

Page 2 of 4

1

Page 20: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

144 www.cloriuscontrols.com

DIMENSION SKETCH

EN 1092-2 ANSI Class 150 JIS B 2210 5K JIS B 2210 10K

TypeL

(mm)L1

(mm)H

(mm)H1

(mm)b

(mm)C

(mm)

D (dia.) (mm)

k (dia.) (mm)

d mm dia.

(number)

D (dia.) (mm)

k (dia.) (mm)

d mmdia.

(number)

D (dia.) (mm)

k (dia.) (mm)

d mmdia.

(number)

D (dia.) (mm)

k (dia.) (mm)

d mmdia.

(number)

80 G3FM-TM 292 146 140 94 20 273 200 160 19x(8) 190 190.8 19x(8) 180 145 19x(4) 185 150 19x(8)

100 G3FM-TM 350 175 158 112 17 273 235 190 23x(8) 230 190.9 19x(8) 200 165 19x(8) 210 175 19x(8)

125 G3FM-TM 400 200 179 123 17 273 270 220 28x(8) 255 216 22x(8) 235 200 19x(8) 250 210 23x(8)

150 G3FM-TM 438 219 196 139 20 276 290 240 23x(8) 280 241 22x(8) 265 230 19x(8) 280 240 23x(8)

200 G3FM-TM 530 270 236 175 21 361 340 295 23x(12) 343 299 23x(8) 320 280 23x(8) 320 290 23x(12)

250 G3FM-TM 592 300 273 205 23 361 400 355 28x(12) 407 362 26x(12) 385 345 23x(12) 400 355 25x(12)

300 G3FM-TM 649 330 305 230 25.5 361 455 410 28x(12) 483 432 26x(12) 430 390 23x(12) 445 400 25x(16)

350 G3FM-TM 717 360 337 255 25.5 361 505 460 23x(16) 534 477 29x(12) 480 435 25x(12) 490 445 25x(16)

400 G3FM-TM 770 385 375 285 26 361 565 515 28x(16) 597 540 29x(16) 540 495 25x(16) 560 510 27x(16)

450 G3FM-TM 820 410 391 310 26.5 556 615 565 28x(20) 635 578 32x(16) 605 555 25x(16) 620 565 27x(20)

3-way Control Valve type G3FM-TM (AB-Middle)Nodular cast iron, PN16, DN 80 - 250 mm / PN10, DN 300 - 450 mm

0-2.6.03.02-B Page 3 of 4

Page 21: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

145www.cloriuscontrols.com

SPECIFICATIONS

Page 4 of 4

TypeFlange

connection DN in mm

kvs-value(1) Mixing valve

m3/h

kvs-value(1) Diverting valve

m3/h

Torque Nm

Weight kg

80 G3FM-TM 80 122 154 100 29

100 G3FM-TM 100 220 248 120 41

125 G3FM-TM 125 369 437 220 58

150 G3FM-TM 150 510 600 235 71

200 G3FM-TM 200 807 1100 420 114

250 G3FM-TM 250 1500 2100 590 159

300 G3FM-TM 300 2000 2650 590 207

350 G3FM-TM 350 2530 3380 1200 278

400 G3FM-TM 400 3050 3950 TBC 346

450 G3FM-TM 450 3680 4480 1750 433

1)kvs-value for port A and B 50% open.

1

Page 22: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

180 www.cloriuscontrols.com

.

ELECTRIC VALVE ACTUATOR TYPE CAR

S3FM-T.

APPLICATION S

MOUNTING

SERVICE

SPECIFICATIONS

TECHNICAL DATA

Casing: Ambient temp.: Power Supply:

Torque switches: Limit switches:

Stall protection:

Travel angle: Indicator: Manual override:

Worm gear:

Mechanical stops: Space heater:

Cabeling: Lubrication: Materials: External coating: Duty Cycle:

TypeMax.

torque Nm

Operating time

Weight

kg

No. of handle turns

Current draw

max. A

Current draw

max. A

Current draw

max. A

Current draw

max. A

CAR 009 90 17/14 11 8.5 1.2 0.6 0.18 2.2

CAR 019 186 17/20 13 10 1.5 0.7 0.28

CAR 028 274 24/20 17 12.5 2 0.7 0.3 7

CAR 060 588 29/24 22 14.5 3.1 1.18 0.5

CAR 100 981 29/24 25 14.5 4.5 2 0.87

CAR 150 1471 87/72 68 43.5 3.1 1.18 0.5

CAR 200 1962 87/72 70 43.5 4.5 1.8 0.8

FEATURES

0-4.11.08-H

dmatthey
Line
Page 23: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

181www.cloriuscontrols.com

DIMENSION SKETCH

Type CAR 009 CAR 019 CAR 028 CAR 060 CAR 100 CAR 150 CAR 200

Flange F07 F07, F10 F12, F10 F14, F12 F16, F14*C1 102 125 140 165C2 82 70 102 125 140*A1 M10 M12 M16 M14*/M16*A2 M8 M8 M10 M12 M20B 12 15 18 22 30

D(Max**) 22 22 32 42 75E 55 57 75 85 100F 43 43 52 59 126G 2 2 2 2 7H 60 60 70 78 78I 113 139 159 191 191J 213 213 250 283 283K 195L 102 120 145 175 266M 56 77 83 99 99N 175 184 202 226 226O 102 102 125 170 170P 16R 108 108 130 178 178T 68 85 99 116 116U 388

318W 556X 231 261 285 325 325Y 181 224 258 307 307Z 273 273 320 361 361

Flange

ISO 5211

CAR 009 - 100 CAR 150-200

3

dmatthey
Oval
dmatthey
Oval
Page 24: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

Page 1 of 2

182 www.cloriuscontrols.com

ELECTRIC VALVE ACTUATOR TYPE CAR

ACCESSORIES

CAR 009-200CAR PROPORTIONAL CONTROL UNIT PCU PB90

CAR 009-200

CAR CURRENTPOSITIONTRANSMITTER CPT

• • •

Command signal input

Analogue feedback signal

Fuse

Resolution

Conversion

0-4.11.08-H

Page 25: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

Page 2 of 2

183www.cloriuscontrols.com

ACCESSORIES

CAR 009-200CAR POTENTIOMETER PIU

• • • • -

• • • • •

RECOMMENDED ACTUATOR TYPES FOR G2/G3FM-TR and G2/G3FM-TL VALVES

Valve size

Actuator type CAR

DN 65 009 009 009 009

DN 80 009 009 009 009

DN 100 009 019 019 019

DN 125 019 019 028 028

DN 150 019 028 028 -

DN 200 060 060 060 -

DN 250 060 060 100 -

DN 300 100 100 100 -

DN 350 100 200 - -

DN 450 200 250 - -

Valve size

Actuator type CAR

DN 65 009 009 009 009

DN 80 009 009 009 009

DN 100 009 009 019 019

DN 125 019 019 028 028

DN 150 019 028 028 -

DN 200 028 060 060 -

DN 250 060 060 060 -

DN 300 060 100 100 -

DN 350 100 200 - -

DN 400 100 200 - -

DN 450 200 200 - -

DN 500 DN 550

200 250 - -

DN 600 200 300 - -

DN 800 - - - -

RECOMMENDED ACTUATOR TYPES FOR G3FM-TM VALVES

3

Page 26: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

194 www.cloriuscontrols.com

Subject to change without notice.

TECHNICAL DATA

Line voltage 230 V AC 115 V AC* -15 % /+10 %, 50 / 60 Hz 24 V AC* *- optional (please specify)

Power consumption approx. 7 VAWeight approx. 1 kg

Permissible ambient temperature- Operation 0 to 50°C- Transport and storage -25 to + 65°C

Degree of protection- Front: IP 65 according to DIN 40050- Terminals: IP00Design For control panel installation

96 x 96 x 135 mm (W x H x D)panel cut out 92 x 92 mm

Installation position arbitraryInput Pt100, 0°C to 300°C

Connection in three - wire systemOption: 4-20 mA

Output 2- or 3-pointOption: 4-20 mA

Measuring accuracy 0.1% of the measuring rangeDisplays Two 4 - digit 7 segment displays,

LED, red,character height = 13 mm

Alarm Type A, B, C;working contact normally

closed circuit principleRelay Switching capacity: 250 V AC/3A

Spark quenching elementData protection Semi - conductor memory

The ER 2000 controller is used for constant temperature control. It is suitable for all heating and cooling control systems. The controller is primarily intended for marine installations and other industrial applications - such as cooling water and lubricating oil installations, flow temperature control etc.

Microprocessor-based Controller type ER 2000For Electronic Temperature Control

The ER 2000 controller is designed for panel mounting. For easy start-up it has optimization for automatic determination of favourable control parameters. The optimization starts when changing the set point or when switching over from manual mode to automatic control. The optimization can be disregarded. For easy operation it has three keys - two for scrolling or changing values and an enter key. Two digital displays show the process variable and the set point. 3 LEDs indicate actuator opens, actuator closes and alarm.The controller can be switched from auto mode to manual mode. In manual mode the actuator can be opened, closed or stopped in a certain position.Three different alarm settings are possible: A: Alarm at a deviation from the set point SPB: Alarm at a fixed limit valueC: Alarm at leaving a band around the set point SP.It can operate either as a three position or as a two position controller or analogue (4-20 mA) controller and has adjustable proportional band, integral action time and derivative action time.

APPLICATIONS

DESIGN

FUNCTION

COMMUNICATION

FEATURES

PI and PID performanceEasy operationFor heating and cooling systems in maritime and industrial installationsManual- / automatic changeoverRobust self-optimizationAlarm indicating a deviation from set point, positive or negativeOnly one sensor element Pt 100 required for control and temperature indicationUser-defined operation level2 or 3 positional output for controlling the actuator

The temperature input comes via a Pt 100 sensor with a single sensing element. The measured value of the controlled variable is compared with the set point value and adjusted via a PI or a PID control structure. The ER 2000 can act as either a heating controller, the actuator closes at rising temperature, or as a cooling controller, the actuator opens at rising temperature. The ER 2000 permits direct reading ofthe actual temperature value (PV) and it is secured from failure in the measuring circuit, i.e. the controller can be set to give either a closing, an opening or remain in current position command in case of sensor short circuit or sensor break. The error message Err appears in the LED display PV.

The controller is equipped with a RS 485 communication module.

Page 1 of 20-4.6.01-H

Page 27: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

195www.cloriuscontrols.com

WIRING DIAGRAM

ELECTRICAL CONNECTIONS - OPTIONAL EXTERNAL UNITS

DIMENSIONS IN MM

Page 2 of 2

* AVM321/322/321S/322S and AVM234: Please refer to instruction depending on the type

4

Cooling: Remember to set controller into cooling mode

Lay power lines and signal lines separately

ALARM1 - Shown contact position = alarm condition (dropped relay)

Page 28: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

244 www.cloriuscontrols.com

Subject to change without notice.

Temperature sensorsType FF12-2, FF12-R, FF15-2, FF15-R and FF12 / 4-20mA for electronic temperature regulation

The temperature sensors are used for registration of temperatures in tubes, tanks and piping. The output signal of the sensor is used asreference for our ER2000 and ER3000 regulators. Type FF 12-2 / 4-20 mA is equipped with a built-in 2-wire transmitter with 4-20 mA output signals. Due to small installation dimensions and internationally widespread measuring element the sensor is especially fitted for marine purposes, just as the applications on land are innumerable.

The sensor consists of a pocket, a connection head and a measuring insert. The pocket is constructed of acid proof steel and can stand temperature/pressure as stated in the diagram. The connection head is made of light-alloy metal and complies with IP 65. The measuring insert contains one or two measuring windings and are exchangeable. The supply lines of the measuring insert are insulated from each other and from the insert tube with a ceramic insulator. Exchangeable measuring insert is mounted in the connection head by means of two spring loaded screws. This means that the measuring insert is always pressed towards the bottom of the pocket, and vibrations from the surroundings will not be transferred to the measuring insert, just like different heat evolutions of pocket and measuring insert are adjusted. Our standard types are shown in the below diagram.

APPLICATIONS

DESIGN

STANDARD TYPES

FEATURES

Resistance sensor Pt 100 Ω/0°C.Standardized design according to DIN 43765.Robust and reliable sensor for use in gaseous and liquid media, For medium temperature up to 200°C.For pressures up to 50 bar.Internationally recognized for marine purposesTo be used together with ER regulators type ER2000 See data sheet no. 0.4.6.01

TECHNICAL DATA

DATA FOR POCKETS According to DIN 43673Material X10CrNiMoTi1810 W. No. 1.4571corresponding to AISI 316 TiConnection: G½BPermissible torque moment: 50 NmPermissible flow velocities:-Air: 25 m/s-Hot steam: 25 m/s-Water: 3 m/sReaction times at liquid velocity:-0.4 m/sec: t 1/2: 7,5s t 9/10: 21s t = total temperature stepMax. pressure: 50 barMax. temperature: 200°CWeight incl. insert: 1 kg

DATA FOR MEASURING INSERT

According to DIN 43762The basic value of the measuringresistance corresponds to DIN 43760.Measuring range: -50°C to + 200°CMeasuring resistance: 1 x Pt 100 Ω or 2 x Pt 100 ΩMax. temperature: 200°CInsulation resistance between measuring resistance and insert tube is over 1000 MΩ at room temperature. The insert is made of stainless steel.Spring travel: 8 mmTwo-core couplingResistance of inner cables for supply andreturn line of the measuring insert: < 0.07 Ω/mWeight of loose insert: 0.06 kg

DATA FOR CONNECTION HEAD

According to DIN 43729, form BMaterial: Light-alloy metalSeal: IP 65Ambient temperature: max. 100°C

Type Measuring Comments

FF 12-21 x Pt 100

With exchangeable measuring insert

FF 12-R Measuring insert for FF 12-2

FF 15-22 x Pt 100

With exchangeable measuring insert

FF 15-R Measuring insert for FF 15-2

FF 12-2 / 4-20 mA 4-20 mA With exchangeable measuring insert

Page 1 of 20-4.7.01-H

Page 29: CSUSA PROJECT NO. 19-212 tad@comfortarcsdocs.comfortar.com/Matt/19-212 Lockheed Martin... · 2019-10-28 · • dimensions are in inches and subject to production tolerances. whenever

245www.cloriuscontrols.com

200 1)

Ø 11

G½B

50 85

15

50

M20x1.5

1) Alternative lengths are available on request: 100 mm, 150 mm, 200 mm, 250 mm

DIMENSION SKETCH - type FF12-2 (mm)

EXAMPLES OF MOUNTING

Page 2 of 2

9