CSRH-Y Water Cooled Chiller_R134a
Transcript of CSRH-Y Water Cooled Chiller_R134a
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 1/20
NUMERICALLY SUPERIOR
CSRH Water cooled chillers
CSRH-D Chillers with partial heat recovery
CSRH-R Chillers with total heat recovery
High Efficient Water Cooled ChillersWater Cooled Chillers With Screw Compressors
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 2/20
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 3/20
CSRH-Y High efficient chillers
1
Energy indices
Energy indices ESEER and IPLV
Increasingly closer attention is being paid towards the power consumption of air-conditioning
equipment. Indices have been introduced that also consider usage in part load conditions when the
external air temperature is lower than the rated value and when the separation stages of the cooling
compressors are used.
The valuation index adopted in the United States is called IPLV (Integrated Part Load Value) and is
defined in the regulations issued by ARI (American Refrigeration Institute).
IPLV ARI
= (1*EER100%
+ 42*EER75%
+ 45*EER50%
+ 12*EER25%
) /100ARI Standard
where:
EER100%
, EER75%
, EER50%
and EER25%
are the efficiencies of the chiller in the various load conditions (100% - 75% - 50% and
25% respectively), calculated in the external air temperature conditions shown below.The temperature of the water leaving the evaporator is considered constant at 6.7°C in all load conditions, with a delta of
5°C in the full load condition.
The multipliers 1, 42, 45 and 12 are the cooling performance coefficients in various load conditions statistically calculated by
ARI an the basis of surveys conducted, for various types of buildings and operating conditions, in 29 Amerian cities.
Evaporator temp. leaving 6,7°C costante
DeltaT full load 5°C
Load 100% 75% 50% 25%
Cond. water temp. 29,4°C 23,9°C 18,3°C 18,3°C
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 4/20
CSRH-Y High efficient chillers
2
Proposal EECCAC ESEER = (3*EER100%
+ 33*EER75%
+ 41*EER50%
+ 23*EER25%
) /100
In Europe there is a proposal for EECCAC (Energy Efficiency and Certification of Central Air Conditioner)
Using the energy indices
Temperature changes on the condenser water inlet are a characteristic of use of cooling towers, an installation solution
widely used in big air conditioning systems. In any case the components must be designed against the maximum outdoor
temperature.
After establishing which index to use and estimating the total power required by the system in the summer mode (in kWh),
we can calculate seasonal electricity consumption (in kWh) using the following formula:
Power absorbed = Power requested / Index of efficiency
The real power calculation can be obtained more correctly in a “dynamic” form, that is, considering the load performance
curve at different external temperatures, the location and the reference number of operating hours.
These figures will allow plant consultants and designers to make their evaluations depending on the type of building, the
place of installation and the type of heat load. etc.. They can also determine the energy index using the method that best
reflects plant requirements and can make comparisons between similar or equivalent systems using the same reference
unit.
Evaporator temp. leaving 6,7°CDeltaT full load 5°C
Load 100% 75% 50% 25%
Cond. water temp. 30°C 26°C 22°C 18°C
Size IPLV
6. 186. 52
6. 51
6. 42
6. 62
6. 54
6. 70
6. 65
6. 73
6. 32
6. 81
6. 91
6. 86
6. 85
ESEER
5. 956. 33
6. 35
6. 19
6. 42
6. 32
6. 51
6. 52
6. 62
6. 22
6. 68
6. 79
6. 74
6. 75
04010501
0551
0651
0751
0802
0851
0951
1002
1102
1302
1502
1702
1902
Size IPLV ESEER
5. 067. 43
6. 48
7. 36
6. 78
7. 43
7. 00
7. 39
6. 81
7. 50
6. 95
7. 41
6. 76
7. 06
5. 117. 24
6. 26
7. 16
6. 54
7. 24
6. 89
7. 28
6. 69
7. 39
6. 84
7. 31
6. 63
6. 94
10011201
1301
1351
1601
1801
2002
2402
2602
2702
3202
3602
4202
4502
48025003
5203
5403
5414
5904
6404
6804
7204
7804
8404
9004
9604
7. 356. 68
7. 27
7. 23
7. 42
7. 07
6. 87
7. 39
7. 32
6. 98
6. 58
6. 92
7. 26
7. 246. 59
7. 19
7. 15
7. 33
7. 00
6. 82
7. 30
7. 24
6. 91
6. 53
6. 85
7. 17
Size IPLV ESEER
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 5/20
CSRH-Y High efficient chillers
3
High efficiency series
This new series of units combines elevated efficiency rates (EER) with the use of R134a refrigerant.
The excellent level of performance was achieved thanks to the accurate sizing of all internal components in order to fully
exploit the characteristics of the ecological refrigerant used. Special attention was paid to all the heat exchange surfaces,
compressors and new asymmetrical evaporators with improved and more efficient refrigerant distribution both in the liquid
and steam phases.
The new screw compressors are specially designed for R134a refrigerant. The continual adjustment feature constantly
modulates the capacity of each compressor between 100% and 50% of its potential. This adjustment mode also allows the
exact power required by the system to be instantaneously delivered and precisely adapted to load variations. This in turn
reduces the number of start-ups and consequently improves reliability. The accompanying unit adjustment feature, based
on evaporator outlet water temperature control with Quick Mind adjustment logic, guarantees extremely small variations
compared with the set point (+/- 0.5 °C, probe precision limit) as well as considerably reducing the time required for the
system to become fully operative.
The advantages of the continual adjustment of individual compressors are enhanced with the use of electronic thermostat
valves.
Their precision and rapidity of response optimise load variations and allow stable conditions to be achieved in a very short
time, even when operating in the part load mode.
The accurate sizing of the system combined with this series of units offers considerable energy saving and consequently
significant reductions in running costs.
Water-to-water chillers
Water-to-water chillers. The unit is supplied with anti-freeze oil and refrigerant and has been factory tested. On-site installation
therefore just involves making connections to the mains power and water supplies.
Unit charged with R134a refrigerant.
STANDARD UNIT COMPOSITIONSupporting frame
Frame comprising supporting elements in polyester-painted thick hot-galvanised sheet steel. The self-supporting frame
containing the main components is designed to ensure maximum ease of access during servicing and maintenance operations.
The various components have been arranged to reduce the overall dimensions of the unit to a minimum.
Screw compressors
Semi-hermetic screw-compressors with 2 five and six-lobe rotors. The five-lobe rotor is directly splined onto the 2-pole
motor (2,950 rpm) without the use of overgears. Compression occurs five times every motor turn and the gas therefore
discharges continuously without the typical throbbing common to reciprocating compressors. Leading-edge numerical control
machines were used to make the rotors and machine the bearing seats. Compressor cooling power is continuously modulatedfrom 100 to 50%. In addition to the standard no-load starting feature, the motors are fitted with electric starting devices
which limit the power absorbed during the compressor starting phase. A check valve on the coolant delivery line prevents
the rotor from reversing after stopping. Special maintenance-free bearings allow very long work cycles. Lubrication is
forced, without the use of an oil pump. The high efficiency built-in oil separator ensures the constant presence of oil in the
compressor. The rotors are dynamically balanced to ensure that the vibrations common to reciprocating compressors do
not occur. The lack of vibrations and the absence of delicate intake and delivery valves, in addition to very fine manufacturing
tolerances, sophisticated quality controls during the production process and a limited number of moving parts, guarantee
quiet and highly reliable operation. Each compressor is fitted with manual-reset motor thermal protection, delivery gas
temperature control, an oil level float, an oil level sight-glass and an electric resistance for heating the oil when the compressor
is stopped.
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 6/20
CSRH-Y High efficient chillers
4
Water-refrigerant heat exchanger
Direct expansion shell and tube exchanger with asymmetric refrigerant circuits for keeping the refrigerant at the correct
speed inside the tubes during the change from the liquid to the gaseous phase. The steel shell is insulated with a closed-cell
condensation proof lining in foamed elastomer. The copper pipes are internally grooved to improve heat exchange and are
mechanically expanded onto the tube plate ends.
Refrigerant-water heat exchanger
Finned coil exchanger with steel shell and finned coil made from copper tubes with external fins, mechanically expanded
onto the tube plate ends. The heads can be removed to inspect the tubes. Water connections are fitted standard for water
from towers; connectors for water from wells can be supplied on request.
Refrigerant circuit
Main components of the refrigerant circuit:
- compressor discharge check valve,
- compressor discharge shut-off valve,
- liquid line shut-off valve,
- liquid line solenoid valve,
- dryer filter with replaceable cartridge,
- refrigerant line sight glass with humidity indicator,
- externally equalised thermostatic valve,
- high pressure safety valve,
- low pressure safety valve,
- high and low pressure transducers
- high pressure switches,
- differential pressure switch for water
Electric power and control panel
Electric power and control panel, built to EN 60204-1/EC
204-1 standards, complete with:
- control circuit transformer,
- general door lock isolator,
- power circuit with bar distribution system,
- fuses and contactors for compressors,
- terminals for cumulative alarm block (BCA),
- remote ON/OFF terminals,
- spring-type control circuit terminal board,
- electronic controller.
- phase sequence relay
Basic model
Unit without heat recovery.
Model with partial heat recovery (D)
Water cooled chiller with partial heat recovery. Compared with the basic configuration, this version features an additional
refrigerant/water heat exchanger on the gas delivery line. This heat exchanger, fitted in series before the traditional cooling
circuit condenser, is large enough to recover heat for the production of medium-to-high temperature water for domestic hot
water and the like. The heating capacity of the heat recovery circuit is approximately equal to the power input of the
compressor.
Model with total heat recovery (R)
Water cooled chiller with total heat recovery. This version features an oversized water/freon heat exchanger with a dual
water circuit comprising a dual shell and tube exchanger for heat condensation and total recovery, all enclosed in a single
steel shell with removable heads and externally lagged in closed-cell neoprene. This exchanger is large enough to recover
condensation heat and produce hot water (secondary or recovery circuit). Hot water can be produced in the recovery circuit
for domestic hot water and the like. The heating capacity of this circuit is approximately equal to the cooling power plus the
power input of the compressor.
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 7/20
CSRH-Y High efficient chillers
5
Accessories (Option)
Acoustic box
Rubber isolators
Compressor suction valve
Increased evaporator insulation.Cu/Ni condensers
Flanges on evaporator (if not standard)
Evaporator water flow switch (supplied separately)
Pressure valve for water from wells (14/30°C)
W3000
Electronic control features
Microprocessor
Multi- language menu
Phase sequency relay
Cumulative fault alarm
Alarms log function
Black- Box funct ion for alarm events
Programming of daily/ weekly program
Evaporator inlet/ outlet water temperature display
Condenser inlet water temperature display
Compressor/ circuit failure display
General unit alarms display
Quick Mind outlet adjustment
Pump- down when stopped
St arting compressors sequency contro l
Management of the compressors working hours
Remote keyboard
√
√
√
√
√
Par.
√
√
√
√
√
√
√
√
OPT
Microprocessor
Local/ Remote supervision through browser and F WS
Communication protocol
Metasys J ohnson Contro ls communicat ion gateway
Modbus communication protocol
Bacnet c ommunicat ion protocol
Interface connection to LonWorks network
Siemens communication gateway
Remote on/ of f with external volt- free contact
Double set- point by external contact
Set- point regulation from external signal (4- 20 mA)
Continuous regulation of the compressors
Relay manage pump
Reduced load functioning from external contact
Connection to sequencier
W3000
OPT
OPT
OPT
OPT
OPT
OPT
OPT
√
OPT
OPT
√
OPT
OPT
OPT
Standard
OPT Available on request
Par. Available modifying a value of the configuration parameters
Automatic circuit breaker for compressors
Free voltage contacts for compr. operation signalling
Remote keyboard
Sequencer (supplied separately)Pump relay
Numbered wires
Electronic expansion valves (if not standard)
CSRH 2402 - D - EX - ST - LN - Y
Model Number Description
_Wpí~åÇ~êÇ==ikWiçï=kçáëÉ==piWpìéÉê=içï=kçáëÉ
råáí=çÑ=ÇçìÄäÉ=çéÉê~íáçå=ãçÇÉë
bÑÑáÅáÉåÅó=ÉåÜ~åÅÉÇ=ãçÇÉä
oÉÑêáÖÉê~åíWuWoQMTÅ==vWoNPQ~==wWoQNM~
oOO=áë=åçí=ã~êâÉÇ
`çÇÉ=çÑ=ìåáíë
eÉ~í=êÉÅçîÉêóW=aWm~êíá~ä==oWqçí~ä
t~íÉê=ÅççäÉÇ=ÅÜáääÉê=ïáíÜ=ëÅêÉï=ÅçãéêÉëëçê
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 8/20
CSRH-Y High efficient chillers
6
General Technical Data
CSRH- Y(1)(2)
CSRH- D- Y(1)(2)(5)
CSRH- R- Y(1)(6)
kW
kW
m3/ h
kPa
m3/ h
kPa
kW
kW
kW
m3/ h
kPa
m3/ h
kPa
Performance
SIZE
Cooling capacity
Power input
Desuperheater heating capacit
Evaporator water f low
Evaporator water pressure drop
Desuperheater water f low
Desuperheater water pressureMicroprocessor
kW
kW
kW
m3/ h
kPa
m3/ h
kPa
W3000
W3000
W3000
Cooling capacity
Power input
Heat recovery capacity
Evaporator water f low
Evaporator water pressure drop
Heat recovery water f low
Heat recovery water pressure drop
Microprocessor
n
n
Compressors
Number of compressors
Number of circuits
Minimum resource step
CSRH- Y
CSRH- D- Y
CSRH- R- Y
kg
kg
kg
Operating weight
kg
kg
kg
kg
CSRH- Y
CSRH- D- Y
CSRH- R- Y
Oil
R134a
R134a
R134a
Charge
dB(A)
0401
99. 1
19. 8
17. 1
23. 0
20. 4
40. 7
102.9
19. 1
17. 7
17. 7
24. 8
3. 0
26. 4
88. 3
23. 7
110.6
15. 2
18. 2
19. 2
55. 4
1
1
800
830
850
19
19
20
9
91
74
0501
121.6
25. 2
20. 9
22. 8
25. 1
65. 8
126.1
24. 3
22. 5
21. 7
24. 5
3. 9
3. 0
108.6
30. 0
136.8
18. 7
18. 2
23. 7
42. 7
1
1
840
890
940
21
22
23
9
92
75
0551
148. 5
29. 1
25. 6
18. 4
30. 5
54. 4
154. 0
28. 1
26. 0
26. 5
19. 8
4. 6
2. 4
131. 7
35. 4
164. 9
22. 7
14. 4
28. 7
62. 1
1
1
1160
1210
1250
31
33
34
15
94
77
0651
168.0
33. 5
28. 9
23. 5
34. 5
55. 1
174.3
32. 4
29. 9
30. 0
25. 3
5. 2
3. 2
149.5
40. 2
187.2
25. 7
18. 6
32. 6
54. 2
1
1
1180
1230
1280
30
31
33
15
94
77
0751
187.6
37. 5
32. 3
29. 3
38. 6
55. 9
194.7
36. 2
33. 5
33. 5
31. 6
5. 8
2. 5
167.8
44. 7
209.9
28. 9
23. 5
36. 5
49. 2
1
1
1190
1240
1310
29
30
32
15
94
77
0802
202.4
40. 2
34. 8
22. 8
41. 7
64. 9
210.0
38. 9
36. 0
36. 1
24. 6
6. 2
27. 5
180.0
48. 2
225.3
31. 0
18. 0
39. 2
57. 5
2
2
1470
1530
1550
42
44
46
18
94
77
0851
225. 4
44. 1
38. 8
28. 3
46. 2
66. 1
233. 9
42. 6
39. 4
40. 3
30. 5
6. 8
3. 5
199. 8
52. 9
249. 5
34. 4
22. 2
43. 4
57. 5
1
1
1270
1330
1390
36
37
39
15
94
77
0951
252.1
50. 3
43. 4
53. 7
51. 8
48. 4
261.5
48. 6
44. 9
45. 0
57. 8
7. 8
2. 5
224.3
59. 9
280.6
38. 6
42. 5
48. 7
52. 1
1
1
1350
1410
1540
51
53
56
15
94
77
1002
247.4
49. 3
42. 6
51. 7
50. 9
67. 3
256.7
47. 6
44. 0
44. 2
55. 6
7. 6
3. 0
220.6
58. 8
275.9
38. 0
41. 1
47. 9
43. 4
2
2
1560
1660
1770
43
45
47
18
95
78
1102
285.8
57. 0
49. 2
69. 0
58. 8
50. 9
296.5
55. 0
50. 8
51. 1
74. 3
8. 9
2. 3
254.2
69. 4
319.4
43. 8
54. 6
55. 5
58. 2
2
2
2000
2100
2170
51
54
56
30
97
80
1302
339. 7
67. 3
58. 5
59. 8
69. 8
56. 5
352. 4
64. 9
60. 1
60. 7
64. 4
10. 5
3. 2
302. 0
80. 6
377. 8
52. 0
47. 3
65. 6
55. 2
2
2
2290
2390
2500
54
56
59
30
97
80dB(A)
Sound power level( 4)
Sound pressure level(3)
Cooling capacity
Power input
Evaporator water f low
Evaporater water pressure drop
Condenser water f low
Condenser water pressure drop
Microprocessor
50% 50% 50% 50% 50% 50% 50%25% 25% 25%25%
(1) Chilled water (in/out) 12/7 °C
(2) Condensing water (in/out) 30/35 °C
(3) At 1 metre (see "Full load sound level" section)
(4) According to ISO 3744 (see "Full load sound level" section)
(5) Desuperheater water (in/out) 40/45 °C
(6) Recovery water (in/out) 40/45 °C
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 9/20
CSRH-Y High efficient chillers
7
General Technical Data
Performance
SIZE
Cooling capacity
Power input
Desuperheater heating capacit
Evaporator water flow
Evaporator water pressure drop
Desuperheater water f low
Desuperheater water pressureMicroprocessor
W3000
W3000
W3000
Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
Evaporator water pressure drop
Heat recovery water f low
Heat recovery water pressure drop
Microprocessor
Compressors
Operating weight
R134a
R134a
R134a
Charge
1502
387.7
76. 5
66. 7
53. 9
79. 6
59. 5
402.3
73. 7
68. 2
69. 3
58. 0
11. 8
2. 6
346.0
91. 0
431.5
59. 6
42. 9
75. 0
52. 0
2
2
2330
2430
2560
56
59
62
30
97
80
1702
448.0
87.7
77.1
72.0
91.9
65.3
464.8
84.6
78.3
80.0
77.5
13.6
3. 5
397.1
105.1
496.0
68.4
56.6
86.1
56.8
2
2
2390
2500
2630
68
72
75
30
97
80
1902
509.6
101.5
87. 7
38. 5
104.8
49. 4
528.7
97. 9
90. 6
91. 0
41. 4
15. 7
2. 5
453.1
120.8
566.6
78. 0
30. 4
98. 5
53. 0
2
2
2790
2910
3170
105
110
116
30
97
80
1001
265.4
52. 4
45. 7
54. 9
54. 5
38. 3
275.3
50. 5
46. 7
47. 4
59. 1
8. 1
12. 2
245.4
64. 3
305.9
42. 3
47. 0
53. 2
72. 3
1
1
1590
1640
1670
44
46
48
15
94
77
1201
323.2
61. 9
55. 6
54. 2
66. 1
56. 3
335.3
59. 8
55. 3
57. 7
58. 3
9. 7
17. 2
289.8
75. 9
361.2
49. 9
43. 6
62. 7
70. 9
1
1
2010
2100
2120
47
49
52
22
97
80
1301
366.3
70. 7
63. 1
48. 1
75. 0
59. 0
380.0
68. 2
63. 1
65. 4
51. 8
11. 0
14. 9
326.4
83. 9
405.3
56. 2
38. 2
70. 5
73. 4
1
1
2030
2140
2170
50
52
55
22
97
80
1351
412.7
77.3
71.1
61.1
84.1
65.8
428.2
74.6
69.0
73.7
65.8
12.0
17.8
369.2
93.4
457.0
63.6
48.9
79.5
75.7
1
1
2050
2160
2200
49
51
53
22
97
80
1601
483.1
91. 8
83. 2
34. 6
98. 6
62. 3
501.2
88. 6
81. 9
86. 3
37. 2
14. 2
17. 5
429.7
110.0
533.1
74. 0
27. 4
92. 6
77. 2
1
1
2712
2860
3110
75
79
83
28
97
80
1801
546.2
105.9
94. 0
44. 2
111.8
66. 4
566.7
102.2
94. 5
97. 6
47. 6
16. 4
23. 3
489.8
129.8
611.9
84. 3
35. 6
106.3
89. 9
1
1
2720
2880
3140
73
77
81
28
97
80
2002
524.7
102.2
90. 3
37. 5
107.5
37. 3
544.4
98. 7
91. 3
93. 7
40. 4
15. 9
11. 7
466.6
121.4
580.7
80. 3
29. 7
100.9
65. 2
2
2
3140
3310
3420
94
99
103
30
97
80
Sound power level(4)
Sound pressure level(3)
Cooling capacity
Power input
Evaporator water f low
Evaporater water pressure drop
Condenser water f low
Condenser water pressure drop
Microprocessor
kW
kW
m3/ h
kPa
m3/ h
kPa
kW
kW
kW
m3/ h
kPa
m3/ h
kPa
kW
kW
kW
m3/ h
kPa
m3/ h
kPa
CSRH- Y
CSRH- D- Y
CSRH- R- Y
kg
kg
kg
kg
kg
kg
kg
CSRH- Y
CSRH- D- Y
CSRH- R- Y
Oil
dB(A)
dB(A)
CSRH- Y(1)(2)
CSRH- D- Y(1)(2)(5)
CSRH- R- Y(1)(6)
25% 25% 25% 25%50%50%50% 50%50%50%
Number of compressors
Number of circuits
Minimum resource step
n
n
(1) Chilled water (in/out) 12/7 °C
(2) Condensing water (in/out) 30/35 °C
(3) At 1 metre (see "Full load sound level" section)
(4) According to ISO 3744 (see "Full load sound level" section)
(5) Desuperheater water (in/out) 40/45 °C
(6) Recovery water (in/out) 40/45 °C
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 10/20
CSRH-Y High efficient chillers
8
General Technical Data
Performance
SIZE
Cooling capacity
Power input
Desuperheater heating capacit
Evaporator water f low
Evaporator water pressure drop
Desuperheater water f lowDesuperheater water pressure
Microprocessor
W3000
W3000
W3000
Cooling capacity
Power input
Heat recovery capacity
Evaporator water f low
Evaporator water pressure drop
Heat recovery water f low
Heat recovery water pressure drop
Microprocessor
Compressors
Operating weight
R134a
R134a
R134a
Charge
2402
637.6
123.6
109.8
55. 4
130.6
55. 1
661.5
119.2
110.3
113.9
59. 7
19. 217. 1
572.3
151.6
714.9
98. 5
44. 7
124.2
69. 5
22
3440
3590
3950
94
99
103
44
99
81
2602
733. 3
141. 5
126. 2
39. 8
150. 0
59. 3
760. 8
136. 5
126. 3
131. 0
42. 9
22. 014. 9
653. 3
168. 0
811. 3
112. 5
31. 6
141. 0
73. 5
22
3720
3880
4220
103
108
113
44
99
81
2702
835.5
155.8
143.8
55. 9
170.2
67. 4
866.9
150.3
139.1
149.2
60. 1
24. 218. 1
746.7
188.3
923.7
128.6
44. 6
160.5
77. 3
22
3750
3900
4300
100
105
111
44
99
81
3202
941.9
182.7
162.1
71. 0
192.9
59. 6
977.2
176.3
163.1
168.2
76. 4
28. 317. 3
839.1
219.0
1044. 9
144.5
56. 3
181.6
74. 2
22
4550
4700
5230
100
105
111
44
99
81
3602
1086. 4
211.6
187.0
69. 3
222.7
66. 0
1127. 1
204.2
188.9
194.0
74. 5
32. 923. 3
974.6
259.6
1218. 6
167.8
55. 7
211.8
89. 3
22
5230
5380
5920
144
151
158
56
99
81
4202
1241. 4
241.0
213.7
61. 7
254.3
59. 8
1287. 9
232.5
215.1
221.7
66. 4
37. 423. 8
1107. 0
286.6
1376. 4
190.6
49. 0
239.2
79. 5
22
5540
5700
6240
213
224
235
56
99
81
4502
1314. 5
250.7
226.3
69. 1
268.6
59. 9
1363. 8
241.9
223.7
234.8
74. 4
38. 925. 8
1174. 4
300.9
1457. 2
202.2
55. 2
253.2
83. 3
22
6020
6180
6710
210
221
231
56
99
81
4802
1386. 4
260.5
238.7
76. 9
282.7
59. 9
1438. 4
251.4
232.5
247.6
82. 8
40. 427. 8
1241. 0
315.1
1537. 2
213.6
61. 6
267.1
87. 1
22
6490
6590
7120
210
221
231
56
99
81
5003
1462. 8
286.7
251.8
85. 6
300.2
60. 3
1517. 7
276.6
255.8
261.3
89. 0
44. 519. 0
1307. 6
346.7
1633. 5
225.1
68. 4
283.9
77. 4
33
6880
7115
7885
197
207
217
84
101
82
5203
1542. 0
300.7
265.5
67. 0
316.1
62. 9
1599. 9
290.2
268.4
275.4
72. 1
46. 720. 9
1381. 6
366.5
1726. 1
237.9
53. 7
300.0
82. 7
33
6910
7145
7925
203
213
223
84
101
82
Sound power level(4)
Sound pressure level(3)
Cooling capacity
Power input
Evaporator water f low
Evaporater water pressure drop
Condenser water f low
Condenser water pressure drop
Microprocessor
kW
kW
m3/ h
kPa
m3/ h
kPa
kW
kW
kW
m3/ h
kPa
m
3
/ hkPa
kW
kW
kW
m3/ h
kPa
m3/ h
kPa
CSRH- Y
CSRH- D- Y
CSRH- R- Y
kg
kg
kg
kg
kg
kg
kg
CSRH- Y
CSRH- D- Y
CSRH- R- Y
Oil
dB(A)
dB(A)
CSRH- Y(1)(2)
CSRH- D- Y(1)(2)(5)
CSRH- R- Y(1)(6)
nn
Number of compressorsNumber of circuits
Minimum resource step 25% 25% 25% 25%25% 25% 25% 25% 16. 6% 16. 6%
(1) Chilled water (in/out) 12/7 °C
(2) Condensing water (in/out) 30/35 °C
(3) At 1 metre (see "Full load sound level" section)
(4) According to ISO 3744 (see "Full load sound level" section)
(5) Desuperheater water (in/out) 40/45 °C
(6) Recovery water (in/out) 40/45 °C
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 11/20
CSRH-Y High efficient chillers
9
General Technical Data
Performance
SIZE
Cooling capacity
Power input
Desuperheater heating capacit
Evaporator water f low
Evaporator water pressure drop
Desuperheater water f lowDesuperheater water pressure
Microprocessor
W3000
W3000
W3000
Cooling capacity
Power input
Heat recovery capacity
Evaporator water f low
Evaporator water pressure drop
Heat recovery water f low
Heat recovery water pressure drop
Microprocessor
Compressors
Operating weight
R134a
R134a
R134a
Charge
5403
1599. 9
313. 5
275. 4
72. 1
328. 2
63. 6
1659. 9
302. 5
279. 8
285. 8
77. 6
48. 622. 7
1436. 8
384. 6
1798. 4
247. 4
58. 1
312. 5
85. 9
33
6910
7175
7965
201
211
221
84
101
82
5414
1671. 1
311.7
287.7
55. 9
340.3
67. 2
1733. 7
300.8
278.2
298.5
60. 1
48. 318. 1
44
8070
8310
201
211
88
102
83
5904
1778. 6
336.3
306.2
63. 3
362.9
63. 2
1845. 3
324.6
300.2
317.7
68. 1
52. 117. 5
44
8820
9120
231
243
100
102
83
6404
1922. 7
367.0
331.0
54. 2
392.9
61. 8
1994. 8
354.1
327.6
343.4
58. 4
56. 917. 5
44
10340
10650
295
310
112
102
83
6804
2048. 8
394.7
352.7
61. 6
419.3
63. 3
2125. 6
380.8
352.3
365.9
66. 3
61. 220. 2
44
10400
10710
291
306
112
102
83
7204
2172. 7
423. 1
374. 0
69. 3
445. 4
65. 4
2254. 2
408. 4
377. 8
388. 1
74. 5
65. 623. 3
44
10470
10780
288
302
112
102
83
7804
2328. 6
452.1
400.9
80. 4
477.0
61. 4
2415. 9
436.2
403.5
415.9
86. 5
70. 223. 5
44
10690
11100
357
375
112
102
83
8404
2482. 7
482.1
427.4
61. 7
508.6
59. 5
2575. 8
465.2
430.3
443.4
66. 5
74. 823. 8
44
11060
11420
427
448
112
102
83
9004
2628. 9
501.4
452.6
69. 2
537.1
60. 6
2727. 5
483.8
447.5
469.6
74. 5
77. 725. 8
44
11920
12320
420
441
112
102
83
9604
2772. 7
521.0
477.3
77. 0
565.2
60. 7
2876. 7
502.8
465.1
495.2
82. 9
80. 827. 8
44
12740
13070
413
434
112
102
83
Sound power level( 4)
Sound pressure level(3)
Cooling capacity
Power input
Evaporator water f low
Evaporater water pressure drop
Condenser water f low
Condenser water pressure drop
Microprocessor
kW
kW
m3/ h
kPa
m3/ h
kPa
kW
kW
kW
m3/ h
kPa
m
3
/ hkPa
kW
kW
kW
m3/ h
kPa
m3/ h
kPa
CSRH- Y
CSRH- D- Y
CSRH- R- Y
kg
kg
kg
kg
kg
kg
kg
CSRH- Y
CSRH- D- Y
CSRH- R- Y
Oil
dB(A)
dB(A)
CSRH- Y(1)(2)
CSRH- D- Y(1)(2)(5)
CSRH- R- Y(1)(6)
16. 6% 12. 5%12. 5%12. 5%12. 5% 12. 5%12. 5%12. 5%12. 5%12. 5%
Number of compressorsNumber of circuits
Minimum resource step
nn
(1) Chilled water (in/out) 12/7 °C
(2) Condensing water (in/out) 30/35 °C
(3) At 1 metre (see "Full load sound level" section)
(4) According to ISO 3744 (see "Full load sound level" section)
(5) Desuperheater water (in/out) 40/45 °C
(6) Recovery water (in/out) 40/45 °C
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 12/20
CSRH-Y High efficient chillers
10
Evaor.
Exch. Water( in) (℃)
Exch. Water( in) (℃)
Exch. Water( in) (℃)
Desuperh. Heat. Rec.
Min Max Min Max Min Max
8 (1)
5 (1)(6)
3
23 (1)
15 (1)
8
18(2)
26(2)
4
10(2)
26(2)
4
51(2)
55(4)(5)
16
CSRH- Y CSRH- D- Y CSRH- R- Y
Water side
-
-
-
cP f cQ
cdp
0
0
11
1
- 10
20%
0,981,04
1,11
- 15
30%
0,9741,075
1, 18
- 20
35%
0, 971, 11
1, 22
- 25
40%
0,9651,14
1,24
- 30
45%
0,9641, 17
1, 27
- 35
50%
0, 961, 2
1, 3
- 5
12%
0,9851, 02
1, 07
Freezing point (℃)
Ethylene glycol percentage by weight
4,4 x 10- 5
0,86 x 10- 4
1,72 x 10- 4
(m2℃/ W)
(m2℃/ W)
(m2℃/ W)
f 1
1
0, 96
0, 93
f k1
1
0, 99
0, 98
fx1
1
0,99
0,98
f 2
0, 99
0, 98
0, 95
f k2
1, 03
1, 04
1, 06
f x2
1, 03
1, 04
1, 06
f3
0, 99
0, 98
0, 95
fk3
1, 03
1, 04
1, 06
f x3
1, 03
1, 04
1, 06
Fouling factors Evaporator Heat recovery Desuperheater
Limits to exchanger water temperature are valid within the minimum maximum water flow range indicated in the Hydraulic Data section.
(1) Condenser water temp. 30/35 °C
(2) Evaporator water (in/out) 12/7 °C
(3) With temperatures down to -8°C use anti-freeze mixtures. In case of lower temperatures, please contact our Sales Department.
(4) Values related only to total heat-recovery version.
(5) Valid for temperature of fluid the evaporator >= -3°C. In case of lower temperatures, please contact our Sales Department.
ETHYLENE GLYCOL MIXTURE
Ethylene glycol and water mixtures, used as a heat-conveying fluid, cause a variation in unit performance. For correct data, use
the factors indicated in the following table.
cPf cooling capacity correction factor
cQ flow correction factor
cdp pressure drop correction factor
For data concerning other kind of anti-freeze solutions (e.g. propylene glycol) please contact our Sales Department.
FOULING FACTORS
Performances are based on clean condition of tubes (fouling factor =1). For different fouling values, performance should be
adjusted using the correction factors shown in the following table.
f1 - f2 - f3 capacity correction factors
fk1 - fk2 - fk3 compressor power input correction factors
fx1 - fx2 - fx3 total power input correction factors
OPERATING RANGE
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 13/20
CSRH-Y High efficient chillers
11
K Q min
m3/ h
Q max
m3/ h
C.a./ W.c.
min m3K
Q min
m3/ h
Q max
m3/ hK
Q min
m3/ h
Q max
m3/ h
Evaporator Rec. (1) - Cond (2) Desuperheater
0401
0501
0551
0651
0751
0802
0851
0951
1002
1102
1302
1502
1702
1902
1001
1201
1301
1351
1601
1801
2002
2402
2602
2702
3202
3602
4202
4502
4802
5003
5203
54035414
5904
6404
6804
7204
7804
8404
9004
9604
79
52
28. 1
28. 1
28. 1
18. 8
18. 8
28. 5
28. 5
28. 5
17. 5
12. 1
12. 1
5
26. 3
17. 5
12. 1
12. 1
5
5
4. 6
4. 6
2. 5
2. 7
2. 7
2
1. 4
1. 4
1. 4
1. 4
1
10. 7
0. 7
0. 5
0. 5
0. 5
0. 5
0. 3
0. 3
0. 3
10
11. 1
15. 9
15. 9
15. 9
17. 6
17. 6
17. 6
17. 6
17. 6
28
28
28
42
21. 4
28
28
28
42
42
42
42
55. 8
55. 8
55. 8
102
117
124
131
138
145
151112
112
181
193
205
220
234
248
262
45. 1
50. 9
73. 7
73. 7
73. 7
81. 7
81. 7
81. 7
81. 7
81. 7
108
114
114
162
74. 5
108
114
114
162
162
171
171
201
210
221
300
313
330
330
330
330
330421
448
600
600
600
600
625
660
660
0. 8
1
1. 2
1. 3
1. 5
1. 3
1. 8
2
1. 6
1. 8
2. 1
2. 4
2. 8
3. 2
2. 1
2. 5
2. 9
3. 2
3. 8
4. 3
3. 3
4
4. 6
5. 3
5. 9
6. 8
7. 8
8. 3
8. 7
9. 2
9. 7
10. 110. 5
11. 2
12. 1
12. 9
13. 7
14. 7
15. 6
16. 5
17. 4
98
104
58. 6
46. 2
37. 5
37. 5
30. 9
18
26
14. 7
11. 6
9. 4
7. 7
4. 5
12. 9
12. 9
10. 5
9. 3
6. 4
5. 3
3. 2
3. 2
2. 6
2. 3
1. 6
1. 3
0. 9
0. 8
0. 8
0. 7
0. 6
0. 60. 6
0. 5
0. 4
0. 4
0. 3
0. 3
0. 2
0. 2
0. 2
5. 6
6. 9
8. 4
9. 5
10. 7
11. 5
12. 8
14. 4
14. 2
16. 3
19. 4
22. 1
25. 5
29. 2
14. 7
14. 7
16. 3
17. 3
20. 8
22. 8
29. 4
29. 4
32. 5
34. 5
41. 5
45. 5
54
57
60
64. 3
66. 3
68. 369
76
83
87
91
99. 5
108
114
120
26. 3
28. 2
35
39. 4
43. 8
46. 5
51. 6
61. 3
57. 1
69. 9
78. 7
88. 9
103.1
122.1
73. 8
73. 8
83. 7
93. 6
110.1
125.1
147.1
147.1
167.1
189.1
215.1
248.1
283.1
299.1
315.1
334.1
352.1
366.1378.1
404.1
437.1
467.1
496.1
531.1
566.1
598.1
629.1
2813
203
116
116
74. 4
703
74. 4
40. 1
50. 8
28. 9
28. 9
18. 6
18. 6
10
186
186
124
124
86. 4
86. 4
46. 5
46. 5
31
31
21. 6
21. 6
17
17
17
9. 6
9. 6
9. 67. 7
6. 4
5. 4
5. 4
5. 4
4. 7
4. 2
4. 2
4. 2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
00
0
0
0
0
0
0
0
0
3. 8
4. 8
5. 6
6. 4
7. 2
7. 7
8. 3
9. 7
9. 6
11
12. 9
14. 5
16. 6
19. 4
9. 9
11. 7
13. 4
14. 5
17. 2
19. 9
19. 2
23. 2
26. 6
28. 9
34. 2
39. 7
45. 2
47
48. 9
54
56. 6
59. 457. 6
63
68. 7
74
79. 2
84. 7
90. 4
93. 9
97. 6
SIZE
WATER FLOW AND PRESSURE DROP
Water flow in the heat exchangers is given by:
Q=Px 0,86/Dt
Q: water flow (m3/h)
Dt: difference between inlet and outlet water temp. (°
C)P: heat exchanger capacity (kW)
Pressure drop is given by:
Dp=K x Q2 /1000
Q: water flow (m3/h)
Dp: pressure drop (kPa)K: unit size ratio
Q min: minimum water flow admitted to the heat exchanger.
Q max: maximum water flow admitted to the heat exchanger.
W.c min.: minimum water content admitted in the plant.
(1) Rec. = Heat Recovery. For units with total heat recovery.
(2) Cond. = Condenser. For water to water type units. In units with heatrecovery ,
this data is valid for both the condensing and the heatrecovery exchangers.
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 14/20
CSRH-Y High efficient chillers
12
Compressor Total unit
F.L.A.
(A)
L.R.A.
(A)
F.L.I.
(kW)
F.L.A.
(A)
S.A.
(kW)
F.L.I.
(kW)n
1
1
1
1
1
2
1
1
2
22
2
2
2
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
3
3
3
4
4
4
4
4
4
4
4
4
0401
0501
0551
0651
0751
0802
0851
0951
1002
11021302
1502
1702
1902
1001
1201
1301
1351
1601
1801
2002
2402
2602
2702
3202
3602
4202
4502
4802
5003
5203
5403
5414
5904
6404
6804
7204
7804
8404
9004
9604
32. 6
40. 5
48. 7
51. 7
64. 3
32. 6
70. 2
82. 1
40. 5
48. 751. 7
64. 3
70. 2
82. 1
82. 1
101
112
127
145
171
82. 1
101
112
127
145
171
191
191/ 217
217
145/ 171
145/ 171
171
127
127/ 145
145
145/ 171
171
171/ 191
191
191/ 217
217
55. 4
67. 1
80. 4
91. 7
105
55. 4
115
132
67. 1
80. 491. 7
105
115
132
132
165
184
208
235
272
132
165
184
208
235
272
310
310/ 351
351
235/ 272
235/ 272
272
208
208/ 235
235
235/ 272
272
272/ 310
310
310/ 351
351
153
169
206
267
290
153
350
423
169
206267
290
350
423
423
300
360
404
436
465
423
300
360
404
436
465
586
586/ 650
650
436/ 465
436/ 465
465
404
404/ 436
436
436/ 465
465
465/ 586
586
586/ 650
650
32. 6
40. 5
48. 7
51. 7
64. 3
65. 2
70. 2
82. 1
81
97. 4103
129
140
164
82
101
112
127
145
171
164
201
223
255
291
341
382
408
434
461
487
512
509
545
581
632
683
724
764
816
868
55. 4
67. 1
80. 4
91. 7
105
111
115
132
134
161183
210
230
264
132
165
184
208
235
272
263
329
367
416
470
544
620
661
702
742
779
816
832
886
940
1014
1088
1164
1240
1322
1404
153
169
206
267
290
208
350
423
236
286359
395
465
555
423
300
360
404
436
465
555
465
544
612
671
737
896
960
1001
935
972
1009
1028
1087
1141
1207
1281
1440
1516
1621
1703
Size
Maximum values
F.L.I. Power input
F.L.A. Current absorption
L.R.A. Locked rotor current for single compressor S.A. Starting current
(1)Safety values to be considered when cabling the unit for power supply and
line-protections
Voltage tolerance: 10%Maximum voltage unbalance: 3%
Electrical Data
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 15/20
CSRH-Y High efficient chillers
13
0401
0501
0551
0651
0751
0802
0851
0951
1002
1102
1302
1502
1702
1902
1001
1201
1301
1351
1601
1801
2002
2402
26022702
3202
3602
4202
4502
4802
5003
5203
5403
5414
5904
64046804
7204
7804
8404
9004
9604
Octave band [Hz] at 1m
55
52
48
56
55
58
55
55
55
51
5958
58
58
55
53
63
67
55
50
58
54
6468
55
51
51
51
51
52
52
52
70
69
58
57
53
57
53
57
53
44
44
54
59
58
47
58
58
47
57
6261
61
61
58
51
55
57
74
70
61
52
5658
74
71
71
71
71
72
72
72
60
74
77
76
73
76
73
76
73
60
61
71
77
73
63
73
73
64
74
8076
76
76
73
70
71
80
77
82
76
71
7281
78
83
83
83
83
84
84
84
83
83
80
83
85
83
85
83
85
74
75
75
73
72
77
72
72
78
78
7675
75
75
72
79
74
76
75
77
75
80
7577
75
78
78
78
78
79
79
79
79
79
78
79
80
79
80
79
80
70
71
74
74
74
73
74
74
74
77
7777
77
77
74
77
79
78
78
76
77
78
8079
78
77
77
77
77
78
78
78
81
81
81
80
79
80
79
80
79
64
65
67
67
69
67
69
69
68
70
7072
72
72
69
68
70
68
69
70
72
69
7169
69
71
71
71
71
72
72
72
71
72
72
73
73
73
73
73
73
55
56
59
60
63
58
63
63
59
62
6366
66
66
63
55
57
52
63
62
66
56
5853
63
63
63
63
63
64
64
64
55
64
66
66
65
66
65
66
65
49
47
49
48
53
52
53
53
50
52
5156
56
56
53
44
45
40
51
52
56
45
4641
51
53
53
53
53
54
54
54
43
51
54
55
55
55
55
55
55
74
75
77
77
77
77
77
77
78
80
8080
80
80
77
80
80
80
80
80
80
81
8181
81
81
81
81
81
82
82
82
83
83
83
83
83
83
83
83
83
63 125 250 500 1000 2000 4000 8000 Total
Sound pressure level [dB]
Size
Working conditions:
evaporator water (in/out) 12/7 [°C]
condenser water (in/out) 30/35 [°C]
Sound pressure
Sound pressure level values in free-field conditions, at 1 m distance.
Full Load Sound Level
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 16/20
CSRH-Y High efficient chillers
8 7
4
3
5 6
2
1
Eveaporatorwaterinlet
Evaporatorwateroutlet
Condenserwaterinlet
Condenserwateroutlet
Recuperatorwaterinlet
Recuperatorwateroutlet
Powerinlet
Mainisolator
1 2 3 4
5 6 7 8
R E M A R K S :
Forinstallationpurposes,pleaserefertothedocumentationsentafterthep
urchase-contract.Thistechnical
datashouldbeconsideredasindicative.CLIMAVENETAmaymodifythematanymoment.
Dime
nsionDrawing
14
Coolingtower
Wellwater
Condenserinterface
̀ p o e
M T R N
N V M O
J v
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 17/20
CSRH-Y High efficient chillers
15
R E M A R K S :
Forinstallationpurposes,pleaserefertothedocumentationsentafterthep
urchase-contract.Thistechnical
datashouldbeconsideredasindicative.CLIMAVENETAmaymodifythematanymoment.
4
3
1
6
5
2
7 8
Eveaporatorwaterinlet
Evaporatorwateroutlet
Condenserwaterinlet
Condenserwateroutlet
Recuperatorwaterinlet
Recuperatorwateroutlet
Powerinlet
Mainisolator
1 2 3 4
5 6 7 8
Dime
nsionDrawing
̀ p o e N M M N
Q U M O
J v
̀ p o e R
M M P
R Q M P
J v
̀ p o e R Q N Q
V S M Q
J v
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 18/20
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 19/20
CSRH-Y High efficient chillers
17
I N S T R U C T I O N S
-Makesurethatallthepan
elsarefirmlyfixedinplacebeforemovingtheunit.
-Beforeliftingit,checktheweightontheCElabel.
-Useall,andonly,theliftingpointsprovided,
-Useslingsofequallength,
-Useaspread-bar(notincluded)
-Movetheunitcarefullyandavoidabruptmovements.
FreeSpaces-Lif
tingMode-Symbols
7/27/2019 CSRH-Y Water Cooled Chiller_R134a
http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 20/20
Climaveneta Italy:
36061 BASSANO DEL GRAPPA (VICENZA) ITALIA - VIA SARSON 57/c
TEL. +39 / 0424 509 500 (r.a.) - TELEFAX +39 / 0424 509 509
E-mail:[email protected] http://www.climaveneta.com
Climaveneta China:
No,88 Baiyun Road Xinghuo Developing Zone ,Shanghai,China Post Code:201419
TEL: +86-21-57505566 FAX: +86-21-57505797
E-mail:[email protected] http://www.climaveneta.com.cn
Climaveneta Hongkong:
Room 2003,CCT Telecom Building, 11 Wo Shing Street,Fotan,Shatin,N.T.,Hongkong
TEL: +85-2-26871755 FAX: +85-2-26873078
E-mail:[email protected] http://www.climaveneta.asia
Climaveneta Vietnam:
381A1 Cong Hoa Street Ward 13 Tan Binh District, HCM City, Vietnam
TEL: +84-8-38497529 FAX: +84-8-38124190
E-mail:[email protected] http://www.climaveneta.asia
All ifi ti d d t bj t t h ith t ti B212 CCU/01 12 2009EN SH