CSRH-Y Water Cooled Chiller_R134a

20
NUMERICALLY SUPERIOR CSRH Water cooled chillers CSRH-D Chillers with partial heat recove ry  CSRH-R Chillers with t otal heat recovery  High Efficien t Water Cooled Chillers Water Cooled Chillers With Screw Compressors

Transcript of CSRH-Y Water Cooled Chiller_R134a

Page 1: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 1/20

NUMERICALLY SUPERIOR 

CSRH Water cooled chillers

CSRH-D Chillers with partial heat recovery 

CSRH-R Chillers with total heat recovery 

High Efficient Water Cooled ChillersWater Cooled Chillers With Screw Compressors

Page 2: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 2/20

Page 3: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 3/20

CSRH-Y High efficient chillers

1

Energy indices

Energy indices ESEER and IPLV

Increasingly closer attention is being paid towards the power consumption of air-conditioning

equipment. Indices have been introduced that also consider usage in part load conditions when the

external air temperature is lower than the rated value and when the separation stages of the cooling

compressors are used.

The valuation index adopted in the United States is called IPLV (Integrated Part Load Value) and is

defined in the regulations issued by ARI (American Refrigeration Institute).

IPLV ARI

= (1*EER100%

+ 42*EER75%

+ 45*EER50%

+ 12*EER25%

) /100ARI Standard

where:

EER100%

, EER75%

, EER50%

and EER25%

are the efficiencies of the chiller in the various load conditions (100% - 75% - 50% and

25% respectively), calculated in the external air temperature conditions shown below.The temperature of the water leaving the evaporator is considered constant at 6.7°C in all load conditions, with a delta of 

5°C in the full load condition.

The multipliers 1, 42, 45 and 12 are the cooling performance coefficients in various load conditions statistically calculated by

 ARI an the basis of surveys conducted, for various types of buildings and operating conditions, in 29 Amerian cities.

Evaporator temp. leaving 6,7°C costante

DeltaT full load 5°C

Load 100% 75% 50% 25%

Cond. water temp. 29,4°C 23,9°C 18,3°C 18,3°C

Page 4: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 4/20

CSRH-Y High efficient chillers

2

 Proposal EECCAC  ESEER = (3*EER100%

+ 33*EER75%

+ 41*EER50%

+ 23*EER25%

) /100

In Europe there is a proposal for EECCAC (Energy Efficiency and Certification of Central Air Conditioner)

Using the energy indices

Temperature changes on the condenser water inlet are a characteristic of use of cooling towers, an installation solution

widely used in big air conditioning systems. In any case the components must be designed against the maximum outdoor 

temperature.

 After establishing which index to use and estimating the total power required by the system in the summer mode (in kWh),

we can calculate seasonal electricity consumption (in kWh) using the following formula:

Power absorbed = Power requested / Index of efficiency

The real power calculation can be obtained more correctly in a “dynamic” form, that is, considering the load performance

curve at different external temperatures, the location and the reference number of operating hours.

These figures will allow plant consultants and designers to make their evaluations depending on the type of building, the

place of installation and the type of heat load. etc.. They can also determine the energy index using the method that best

reflects plant requirements and can make comparisons between similar or equivalent systems using the same reference

unit.

Evaporator temp. leaving 6,7°CDeltaT full load 5°C

Load 100% 75% 50% 25%

Cond. water temp. 30°C 26°C 22°C 18°C

Size IPLV

6. 186. 52

6. 51

6. 42

6. 62

6. 54

6. 70

6. 65

6. 73

6. 32

6. 81

6. 91

6. 86

6. 85

ESEER

5. 956. 33

6. 35

6. 19

6. 42

6. 32

6. 51

6. 52

6. 62

6. 22

6. 68

6. 79

6. 74

6. 75

04010501

0551

0651

0751

0802

0851

0951

1002

1102

1302

1502

1702

1902

Size IPLV ESEER

5. 067. 43

6. 48

7. 36

6. 78

7. 43

7. 00

7. 39

6. 81

7. 50

6. 95

7. 41

6. 76

7. 06

5. 117. 24

6. 26

7. 16

6. 54

7. 24

6. 89

7. 28

6. 69

7. 39

6. 84

7. 31

6. 63

6. 94

10011201

1301

1351

1601

1801

2002

2402

2602

2702

3202

3602

4202

4502

48025003

5203

5403

5414

5904

6404

6804

7204

7804

8404

9004

9604

7. 356. 68

7. 27

7. 23

7. 42

7. 07

6. 87

7. 39

7. 32

6. 98

6. 58

6. 92

7. 26

7. 246. 59

7. 19

7. 15

7. 33

7. 00

6. 82

7. 30

7. 24

6. 91

6. 53

6. 85

7. 17

Size IPLV ESEER

Page 5: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 5/20

CSRH-Y High efficient chillers

3

High efficiency series

This new series of units combines elevated efficiency rates (EER) with the use of R134a refrigerant.

The excellent level of performance was achieved thanks to the accurate sizing of all internal components in order to fully

exploit the characteristics of the ecological refrigerant used. Special attention was paid to all the heat exchange surfaces,

compressors and new asymmetrical evaporators with improved and more efficient refrigerant distribution both in the liquid

and steam phases.

The new screw compressors are specially designed for R134a refrigerant. The continual adjustment feature constantly

modulates the capacity of each compressor between 100% and 50% of its potential. This adjustment mode also allows the

exact power required by the system to be instantaneously delivered and precisely adapted to load variations. This in turn

reduces the number of start-ups and consequently improves reliability. The accompanying unit adjustment feature, based

on evaporator outlet water temperature control with Quick Mind adjustment logic, guarantees extremely small variations

compared with the set point (+/- 0.5 °C, probe precision limit) as well as considerably reducing the time required for the

system to become fully operative.

The advantages of the continual adjustment of individual compressors are enhanced with the use of electronic thermostat

valves.

Their precision and rapidity of response optimise load variations and allow stable conditions to be achieved in a very short

time, even when operating in the part load mode.

The accurate sizing of the system combined with this series of units offers considerable energy saving and consequently

significant reductions in running costs.

Water-to-water chillers

Water-to-water chillers. The unit is supplied with anti-freeze oil and refrigerant and has been factory tested. On-site installation

therefore just involves making connections to the mains power and water supplies.

Unit charged with R134a refrigerant.

STANDARD UNIT COMPOSITIONSupporting frame

Frame comprising supporting elements in polyester-painted thick hot-galvanised sheet steel. The self-supporting frame

containing the main components is designed to ensure maximum ease of access during servicing and maintenance operations.

The various components have been arranged to reduce the overall dimensions of the unit to a minimum.

Screw compressors

Semi-hermetic screw-compressors with 2 five and six-lobe rotors. The five-lobe rotor is directly splined onto the 2-pole

motor (2,950 rpm) without the use of overgears. Compression occurs five times every motor turn and the gas therefore

discharges continuously without the typical throbbing common to reciprocating compressors. Leading-edge numerical control

machines were used to make the rotors and machine the bearing seats. Compressor cooling power is continuously modulatedfrom 100 to 50%. In addition to the standard no-load starting feature, the motors are fitted with electric starting devices

which limit the power absorbed during the compressor starting phase. A check valve on the coolant delivery line prevents

the rotor from reversing after stopping. Special maintenance-free bearings allow very long work cycles. Lubrication is

forced, without the use of an oil pump. The high efficiency built-in oil separator ensures the constant presence of oil in the

compressor. The rotors are dynamically balanced to ensure that the vibrations common to reciprocating compressors do

not occur. The lack of vibrations and the absence of delicate intake and delivery valves, in addition to very fine manufacturing

tolerances, sophisticated quality controls during the production process and a limited number of moving parts, guarantee

quiet and highly reliable operation. Each compressor is fitted with manual-reset motor thermal protection, delivery gas

temperature control, an oil level float, an oil level sight-glass and an electric resistance for heating the oil when the compressor 

is stopped.

Page 6: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 6/20

CSRH-Y High efficient chillers

4

Water-refrigerant heat exchanger 

Direct expansion shell and tube exchanger with asymmetric refrigerant circuits for keeping the refrigerant at the correct

speed inside the tubes during the change from the liquid to the gaseous phase. The steel shell is insulated with a closed-cell

condensation proof lining in foamed elastomer. The copper pipes are internally grooved to improve heat exchange and are

mechanically expanded onto the tube plate ends.

Refrigerant-water heat exchanger 

Finned coil exchanger with steel shell and finned coil made from copper tubes with external fins, mechanically expanded

onto the tube plate ends. The heads can be removed to inspect the tubes. Water connections are fitted standard for water 

from towers; connectors for water from wells can be supplied on request.

Refrigerant circuit

Main components of the refrigerant circuit:

- compressor discharge check valve,

- compressor discharge shut-off valve,

- liquid line shut-off valve,

- liquid line solenoid valve,

- dryer filter with replaceable cartridge,

- refrigerant line sight glass with humidity indicator,

- externally equalised thermostatic valve,

- high pressure safety valve,

- low pressure safety valve,

- high and low pressure transducers

- high pressure switches,

- differential pressure switch for water 

Electric power and control panel

Electric power and control panel, built to EN 60204-1/EC

204-1 standards, complete with:

- control circuit transformer,

- general door lock isolator,

- power circuit with bar distribution system,

- fuses and contactors for compressors,

- terminals for cumulative alarm block (BCA),

- remote ON/OFF terminals,

- spring-type control circuit terminal board,

- electronic controller.

- phase sequence relay

Basic model

Unit without heat recovery.

Model with partial heat recovery (D)

Water cooled chiller with partial heat recovery. Compared with the basic configuration, this version features an additional

refrigerant/water heat exchanger on the gas delivery line. This heat exchanger, fitted in series before the traditional cooling

circuit condenser, is large enough to recover heat for the production of medium-to-high temperature water for domestic hot

water and the like. The heating capacity of the heat recovery circuit is approximately equal to the power input of the

compressor.

Model with total heat recovery (R)

Water cooled chiller with total heat recovery. This version features an oversized water/freon heat exchanger with a dual

water circuit comprising a dual shell and tube exchanger for heat condensation and total recovery, all enclosed in a single

steel shell with removable heads and externally lagged in closed-cell neoprene. This exchanger is large enough to recover 

condensation heat and produce hot water (secondary or recovery circuit). Hot water can be produced in the recovery circuit

for domestic hot water and the like. The heating capacity of this circuit is approximately equal to the cooling power plus the

power input of the compressor.

Page 7: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 7/20

CSRH-Y High efficient chillers

5

Accessories (Option)

 Acoustic box

Rubber isolators

Compressor suction valve

Increased evaporator insulation.Cu/Ni condensers

Flanges on evaporator (if not standard)

Evaporator water flow switch (supplied separately)

Pressure valve for water from wells (14/30°C)

W3000

Electronic control features

Microprocessor 

Multi- language menu

Phase sequency relay

Cumulative fault alarm

Alarms log function

Black- Box funct ion for alarm events

Programming of daily/ weekly program

Evaporator inlet/ outlet water temperature display

Condenser inlet water temperature display

Compressor/ circuit failure display

General unit alarms display

Quick Mind outlet adjustment

Pump- down when stopped

St arting compressors sequency contro l

Management of the compressors working hours

Remote keyboard

Par.

OPT

Microprocessor 

Local/ Remote supervision through browser and F WS

Communication protocol

Metasys J ohnson Contro ls communicat ion gateway

Modbus communication protocol

Bacnet c ommunicat ion protocol

Interface connection to LonWorks network

Siemens communication gateway

Remote on/ of f with external volt- free contact

Double set- point by external contact

Set- point regulation from external signal (4- 20 mA)

Continuous regulation of the compressors

Relay manage pump

Reduced load functioning from external contact

Connection to sequencier

W3000

OPT

OPT

OPT

OPT

OPT

OPT

OPT

OPT

OPT

OPT

OPT

OPT

  Standard 

OPT Available on request 

Par. Available modifying a value of the configuration parameters

 Automatic circuit breaker for compressors

Free voltage contacts for compr. operation signalling

Remote keyboard

Sequencer (supplied separately)Pump relay

Numbered wires

Electronic expansion valves (if not standard)

CSRH 2402 - D - EX - ST - LN - Y

Model Number Description

_Wpí~åÇ~êÇ==ikWiçï=kçáëÉ==piWpìéÉê=içï=kçáëÉ

råáí=çÑ=ÇçìÄäÉ=çéÉê~íáçå=ãçÇÉë

bÑÑáÅáÉåÅó=ÉåÜ~åÅÉÇ=ãçÇÉä

oÉÑêáÖÉê~åíWuWoQMTÅ==vWoNPQ~==wWoQNM~

oOO=áë=åçí=ã~êâÉÇ

`çÇÉ=çÑ=ìåáíë

eÉ~í=êÉÅçîÉêóW=aWm~êíá~ä==oWqçí~ä

t~íÉê=ÅççäÉÇ=ÅÜáääÉê=ïáíÜ=ëÅêÉï=ÅçãéêÉëëçê

Page 8: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 8/20

CSRH-Y High efficient chillers

6

General Technical Data

CSRH- Y(1)(2)

CSRH- D- Y(1)(2)(5)

CSRH- R- Y(1)(6)

kW

kW

m3/ h

kPa

m3/ h

kPa

kW

kW

kW

m3/ h

kPa

m3/ h

kPa

Performance

SIZE

Cooling capacity

Power input

Desuperheater heating capacit

Evaporator water f low

Evaporator water pressure drop

Desuperheater water f low

Desuperheater water pressureMicroprocessor

kW

kW

kW

m3/ h

kPa

m3/ h

kPa

W3000

W3000

W3000

Cooling capacity

Power input

Heat recovery capacity

Evaporator water f low

Evaporator water pressure drop

Heat recovery water f low

Heat recovery water pressure drop

Microprocessor

n

n

Compressors

Number of compressors

Number of circuits

Minimum resource step

CSRH- Y

CSRH- D- Y

CSRH- R- Y

kg

kg

kg

Operating weight

kg

kg

kg

kg

CSRH- Y

CSRH- D- Y

CSRH- R- Y

Oil

R134a

R134a

R134a

Charge

dB(A)

0401

99. 1

19. 8

17. 1

23. 0

20. 4

40. 7

102.9

19. 1

17. 7

17. 7

24. 8

3. 0

26. 4

88. 3

23. 7

110.6

15. 2

18. 2

19. 2

55. 4

1

1

800

830

850

19

19

20

9

91

74

0501

121.6

25. 2

20. 9

22. 8

25. 1

65. 8

126.1

24. 3

22. 5

21. 7

24. 5

3. 9

3. 0

108.6

30. 0

136.8

18. 7

18. 2

23. 7

42. 7

1

1

840

890

940

21

22

23

9

92

75

0551

148. 5

29. 1

25. 6

18. 4

30. 5

54. 4

154. 0

28. 1

26. 0

26. 5

19. 8

4. 6

2. 4

131. 7

35. 4

164. 9

22. 7

14. 4

28. 7

62. 1

1

1

1160

1210

1250

31

33

34

15

94

77

0651

168.0

33. 5

28. 9

23. 5

34. 5

55. 1

174.3

32. 4

29. 9

30. 0

25. 3

5. 2

3. 2

149.5

40. 2

187.2

25. 7

18. 6

32. 6

54. 2

1

1

1180

1230

1280

30

31

33

15

94

77

0751

187.6

37. 5

32. 3

29. 3

38. 6

55. 9

194.7

36. 2

33. 5

33. 5

31. 6

5. 8

2. 5

167.8

44. 7

209.9

28. 9

23. 5

36. 5

49. 2

1

1

1190

1240

1310

29

30

32

15

94

77

0802

202.4

40. 2

34. 8

22. 8

41. 7

64. 9

210.0

38. 9

36. 0

36. 1

24. 6

6. 2

27. 5

180.0

48. 2

225.3

31. 0

18. 0

39. 2

57. 5

2

2

1470

1530

1550

42

44

46

18

94

77

0851

225. 4

44. 1

38. 8

28. 3

46. 2

66. 1

233. 9

42. 6

39. 4

40. 3

30. 5

6. 8

3. 5

199. 8

52. 9

249. 5

34. 4

22. 2

43. 4

57. 5

1

1

1270

1330

1390

36

37

39

15

94

77

0951

252.1

50. 3

43. 4

53. 7

51. 8

48. 4

261.5

48. 6

44. 9

45. 0

57. 8

7. 8

2. 5

224.3

59. 9

280.6

38. 6

42. 5

48. 7

52. 1

1

1

1350

1410

1540

51

53

56

15

94

77

1002

247.4

49. 3

42. 6

51. 7

50. 9

67. 3

256.7

47. 6

44. 0

44. 2

55. 6

7. 6

3. 0

220.6

58. 8

275.9

38. 0

41. 1

47. 9

43. 4

2

2

1560

1660

1770

43

45

47

18

95

78

1102

285.8

57. 0

49. 2

69. 0

58. 8

50. 9

296.5

55. 0

50. 8

51. 1

74. 3

8. 9

2. 3

254.2

69. 4

319.4

43. 8

54. 6

55. 5

58. 2

2

2

2000

2100

2170

51

54

56

30

97

80

1302

339. 7

67. 3

58. 5

59. 8

69. 8

56. 5

352. 4

64. 9

60. 1

60. 7

64. 4

10. 5

3. 2

302. 0

80. 6

377. 8

52. 0

47. 3

65. 6

55. 2

2

2

2290

2390

2500

54

56

59

30

97

80dB(A)

Sound power level( 4)

Sound pressure level(3)

Cooling capacity

Power input

Evaporator water f low

Evaporater water pressure drop

Condenser water f low

Condenser water pressure drop

Microprocessor

50% 50% 50% 50% 50% 50% 50%25% 25% 25%25%

(1) Chilled water (in/out) 12/7 °C

(2) Condensing water (in/out) 30/35 °C

(3) At 1 metre (see "Full load sound level" section)

(4) According to ISO 3744 (see "Full load sound level" section)

(5) Desuperheater water (in/out) 40/45 °C

(6) Recovery water (in/out) 40/45 °C

Page 9: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 9/20

CSRH-Y High efficient chillers

7

General Technical Data

Performance

SIZE

Cooling capacity

Power input

Desuperheater heating capacit

Evaporator water flow

Evaporator water pressure drop

Desuperheater water f low

Desuperheater water pressureMicroprocessor

W3000

W3000

W3000

Cooling capacity

Power input

Heat recovery capacity

Evaporator water flow

Evaporator water pressure drop

Heat recovery water f low

Heat recovery water pressure drop

Microprocessor

Compressors

Operating weight

R134a

R134a

R134a

Charge

1502

387.7

76. 5

66. 7

53. 9

79. 6

59. 5

402.3

73. 7

68. 2

69. 3

58. 0

11. 8

2. 6

346.0

91. 0

431.5

59. 6

42. 9

75. 0

52. 0

2

2

2330

2430

2560

56

59

62

30

97

80

1702

448.0

87.7

77.1

72.0

91.9

65.3

464.8

84.6

78.3

80.0

77.5

13.6

3. 5

397.1

105.1

496.0

68.4

56.6

86.1

56.8

2

2

2390

2500

2630

68

72

75

30

97

80

1902

509.6

101.5

87. 7

38. 5

104.8

49. 4

528.7

97. 9

90. 6

91. 0

41. 4

15. 7

2. 5

453.1

120.8

566.6

78. 0

30. 4

98. 5

53. 0

2

2

2790

2910

3170

105

110

116

30

97

80

1001

265.4

52. 4

45. 7

54. 9

54. 5

38. 3

275.3

50. 5

46. 7

47. 4

59. 1

8. 1

12. 2

245.4

64. 3

305.9

42. 3

47. 0

53. 2

72. 3

1

1

1590

1640

1670

44

46

48

15

94

77

1201

323.2

61. 9

55. 6

54. 2

66. 1

56. 3

335.3

59. 8

55. 3

57. 7

58. 3

9. 7

17. 2

289.8

75. 9

361.2

49. 9

43. 6

62. 7

70. 9

1

1

2010

2100

2120

47

49

52

22

97

80

1301

366.3

70. 7

63. 1

48. 1

75. 0

59. 0

380.0

68. 2

63. 1

65. 4

51. 8

11. 0

14. 9

326.4

83. 9

405.3

56. 2

38. 2

70. 5

73. 4

1

1

2030

2140

2170

50

52

55

22

97

80

1351

412.7

77.3

71.1

61.1

84.1

65.8

428.2

74.6

69.0

73.7

65.8

12.0

17.8

369.2

93.4

457.0

63.6

48.9

79.5

75.7

1

1

2050

2160

2200

49

51

53

22

97

80

1601

483.1

91. 8

83. 2

34. 6

98. 6

62. 3

501.2

88. 6

81. 9

86. 3

37. 2

14. 2

17. 5

429.7

110.0

533.1

74. 0

27. 4

92. 6

77. 2

1

1

2712

2860

3110

75

79

83

28

97

80

1801

546.2

105.9

94. 0

44. 2

111.8

66. 4

566.7

102.2

94. 5

97. 6

47. 6

16. 4

23. 3

489.8

129.8

611.9

84. 3

35. 6

106.3

89. 9

1

1

2720

2880

3140

73

77

81

28

97

80

2002

524.7

102.2

90. 3

37. 5

107.5

37. 3

544.4

98. 7

91. 3

93. 7

40. 4

15. 9

11. 7

466.6

121.4

580.7

80. 3

29. 7

100.9

65. 2

2

2

3140

3310

3420

94

99

103

30

97

80

Sound power level(4)

Sound pressure level(3)

Cooling capacity

Power input

Evaporator water f low

Evaporater water pressure drop

Condenser water f low

Condenser water pressure drop

Microprocessor

kW

kW

m3/ h

kPa

m3/ h

kPa

kW

kW

kW

m3/ h

kPa

m3/ h

kPa

kW

kW

kW

m3/ h

kPa

m3/ h

kPa

CSRH- Y

CSRH- D- Y

CSRH- R- Y

kg

kg

kg

kg

kg

kg

kg

CSRH- Y

CSRH- D- Y

CSRH- R- Y

Oil

dB(A)

dB(A)

CSRH- Y(1)(2)

CSRH- D- Y(1)(2)(5)

CSRH- R- Y(1)(6)

25% 25% 25% 25%50%50%50% 50%50%50%

Number of compressors

Number of circuits

Minimum resource step

n

n

(1) Chilled water (in/out) 12/7 °C

(2) Condensing water (in/out) 30/35 °C

(3) At 1 metre (see "Full load sound level" section)

(4) According to ISO 3744 (see "Full load sound level" section)

(5) Desuperheater water (in/out) 40/45 °C

(6) Recovery water (in/out) 40/45 °C

Page 10: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 10/20

CSRH-Y High efficient chillers

8

General Technical Data

Performance

SIZE

Cooling capacity

Power input

Desuperheater heating capacit

Evaporator water f low

Evaporator water pressure drop

Desuperheater water f lowDesuperheater water pressure

Microprocessor

W3000

W3000

W3000

Cooling capacity

Power input

Heat recovery capacity

Evaporator water f low

Evaporator water pressure drop

Heat recovery water f low

Heat recovery water pressure drop

Microprocessor

Compressors

Operating weight

R134a

R134a

R134a

Charge

2402

637.6

123.6

109.8

55. 4

130.6

55. 1

661.5

119.2

110.3

113.9

59. 7

19. 217. 1

572.3

151.6

714.9

98. 5

44. 7

124.2

69. 5

22

3440

3590

3950

94

99

103

44

99

81

2602

733. 3

141. 5

126. 2

39. 8

150. 0

59. 3

760. 8

136. 5

126. 3

131. 0

42. 9

22. 014. 9

653. 3

168. 0

811. 3

112. 5

31. 6

141. 0

73. 5

22

3720

3880

4220

103

108

113

44

99

81

2702

835.5

155.8

143.8

55. 9

170.2

67. 4

866.9

150.3

139.1

149.2

60. 1

24. 218. 1

746.7

188.3

923.7

128.6

44. 6

160.5

77. 3

22

3750

3900

4300

100

105

111

44

99

81

3202

941.9

182.7

162.1

71. 0

192.9

59. 6

977.2

176.3

163.1

168.2

76. 4

28. 317. 3

839.1

219.0

1044. 9

144.5

56. 3

181.6

74. 2

22

4550

4700

5230

100

105

111

44

99

81

3602

1086. 4

211.6

187.0

69. 3

222.7

66. 0

1127. 1

204.2

188.9

194.0

74. 5

32. 923. 3

974.6

259.6

1218. 6

167.8

55. 7

211.8

89. 3

22

5230

5380

5920

144

151

158

56

99

81

4202

1241. 4

241.0

213.7

61. 7

254.3

59. 8

1287. 9

232.5

215.1

221.7

66. 4

37. 423. 8

1107. 0

286.6

1376. 4

190.6

49. 0

239.2

79. 5

22

5540

5700

6240

213

224

235

56

99

81

4502

1314. 5

250.7

226.3

69. 1

268.6

59. 9

1363. 8

241.9

223.7

234.8

74. 4

38. 925. 8

1174. 4

300.9

1457. 2

202.2

55. 2

253.2

83. 3

22

6020

6180

6710

210

221

231

56

99

81

4802

1386. 4

260.5

238.7

76. 9

282.7

59. 9

1438. 4

251.4

232.5

247.6

82. 8

40. 427. 8

1241. 0

315.1

1537. 2

213.6

61. 6

267.1

87. 1

22

6490

6590

7120

210

221

231

56

99

81

5003

1462. 8

286.7

251.8

85. 6

300.2

60. 3

1517. 7

276.6

255.8

261.3

89. 0

44. 519. 0

1307. 6

346.7

1633. 5

225.1

68. 4

283.9

77. 4

33

6880

7115

7885

197

207

217

84

101

82

5203

1542. 0

300.7

265.5

67. 0

316.1

62. 9

1599. 9

290.2

268.4

275.4

72. 1

46. 720. 9

1381. 6

366.5

1726. 1

237.9

53. 7

300.0

82. 7

33

6910

7145

7925

203

213

223

84

101

82

Sound power level(4)

Sound pressure level(3)

Cooling capacity

Power input

Evaporator water f low

Evaporater water pressure drop

Condenser water f low

Condenser water pressure drop

Microprocessor

kW

kW

m3/ h

kPa

m3/ h

kPa

kW

kW

kW

m3/ h

kPa

m

3

/ hkPa

kW

kW

kW

m3/ h

kPa

m3/ h

kPa

CSRH- Y

CSRH- D- Y

CSRH- R- Y

kg

kg

kg

kg

kg

kg

kg

CSRH- Y

CSRH- D- Y

CSRH- R- Y

Oil

dB(A)

dB(A)

CSRH- Y(1)(2)

CSRH- D- Y(1)(2)(5)

CSRH- R- Y(1)(6)

nn

Number of compressorsNumber of circuits

Minimum resource step 25% 25% 25% 25%25% 25% 25% 25% 16. 6% 16. 6%

(1) Chilled water (in/out) 12/7 °C

(2) Condensing water (in/out) 30/35 °C

(3) At 1 metre (see "Full load sound level" section)

(4) According to ISO 3744 (see "Full load sound level" section)

(5) Desuperheater water (in/out) 40/45 °C

(6) Recovery water (in/out) 40/45 °C

Page 11: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 11/20

CSRH-Y High efficient chillers

9

General Technical Data

Performance

SIZE

Cooling capacity

Power input

Desuperheater heating capacit

Evaporator water f low

Evaporator water pressure drop

Desuperheater water f lowDesuperheater water pressure

Microprocessor

W3000

W3000

W3000

Cooling capacity

Power input

Heat recovery capacity

Evaporator water f low

Evaporator water pressure drop

Heat recovery water f low

Heat recovery water pressure drop

Microprocessor

Compressors

Operating weight

R134a

R134a

R134a

Charge

5403

1599. 9

313. 5

275. 4

72. 1

328. 2

63. 6

1659. 9

302. 5

279. 8

285. 8

77. 6

48. 622. 7

1436. 8

384. 6

1798. 4

247. 4

58. 1

312. 5

85. 9

33

6910

7175

7965

201

211

221

84

101

82

5414

1671. 1

311.7

287.7

55. 9

340.3

67. 2

1733. 7

300.8

278.2

298.5

60. 1

48. 318. 1

44

8070

8310

201

211

88

102

83

5904

1778. 6

336.3

306.2

63. 3

362.9

63. 2

1845. 3

324.6

300.2

317.7

68. 1

52. 117. 5

44

8820

9120

231

243

100

102

83

6404

1922. 7

367.0

331.0

54. 2

392.9

61. 8

1994. 8

354.1

327.6

343.4

58. 4

56. 917. 5

44

10340

10650

295

310

112

102

83

6804

2048. 8

394.7

352.7

61. 6

419.3

63. 3

2125. 6

380.8

352.3

365.9

66. 3

61. 220. 2

44

10400

10710

291

306

112

102

83

7204

2172. 7

423. 1

374. 0

69. 3

445. 4

65. 4

2254. 2

408. 4

377. 8

388. 1

74. 5

65. 623. 3

44

10470

10780

288

302

112

102

83

7804

2328. 6

452.1

400.9

80. 4

477.0

61. 4

2415. 9

436.2

403.5

415.9

86. 5

70. 223. 5

44

10690

11100

357

375

112

102

83

8404

2482. 7

482.1

427.4

61. 7

508.6

59. 5

2575. 8

465.2

430.3

443.4

66. 5

74. 823. 8

44

11060

11420

427

448

112

102

83

9004

2628. 9

501.4

452.6

69. 2

537.1

60. 6

2727. 5

483.8

447.5

469.6

74. 5

77. 725. 8

44

11920

12320

420

441

112

102

83

9604

2772. 7

521.0

477.3

77. 0

565.2

60. 7

2876. 7

502.8

465.1

495.2

82. 9

80. 827. 8

44

12740

13070

413

434

112

102

83

Sound power level( 4)

Sound pressure level(3)

Cooling capacity

Power input

Evaporator water f low

Evaporater water pressure drop

Condenser water f low

Condenser water pressure drop

Microprocessor

kW

kW

m3/ h

kPa

m3/ h

kPa

kW

kW

kW

m3/ h

kPa

m

3

/ hkPa

kW

kW

kW

m3/ h

kPa

m3/ h

kPa

CSRH- Y

CSRH- D- Y

CSRH- R- Y

kg

kg

kg

kg

kg

kg

kg

CSRH- Y

CSRH- D- Y

CSRH- R- Y

Oil

dB(A)

dB(A)

CSRH- Y(1)(2)

CSRH- D- Y(1)(2)(5)

CSRH- R- Y(1)(6)

16. 6% 12. 5%12. 5%12. 5%12. 5% 12. 5%12. 5%12. 5%12. 5%12. 5%

Number of compressorsNumber of circuits

Minimum resource step

nn

(1) Chilled water (in/out) 12/7 °C

(2) Condensing water (in/out) 30/35 °C

(3) At 1 metre (see "Full load sound level" section)

(4) According to ISO 3744 (see "Full load sound level" section)

(5) Desuperheater water (in/out) 40/45 °C

(6) Recovery water (in/out) 40/45 °C

Page 12: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 12/20

CSRH-Y High efficient chillers

10

Evaor.

Exch. Water( in) (℃)

Exch. Water( in) (℃)

Exch. Water( in) (℃)

Desuperh. Heat. Rec.

Min Max Min Max Min Max

8 (1)

5 (1)(6)

3

23 (1)

15 (1)

8

18(2)

26(2)

4

10(2)

26(2)

4

51(2)

55(4)(5)

16

CSRH- Y CSRH- D- Y CSRH- R- Y

Water side

-

-

-

cP f cQ

cdp

0

0

11

1

- 10

20%

0,981,04

1,11

- 15

30%

0,9741,075

1, 18

- 20

35%

0, 971, 11

1, 22

- 25

40%

0,9651,14

1,24

- 30

45%

0,9641, 17

1, 27

- 35

50%

0, 961, 2

1, 3

- 5

12%

0,9851, 02

1, 07

Freezing point (℃)

Ethylene glycol percentage by weight

4,4 x 10- 5

0,86 x 10- 4

1,72 x 10- 4

(m2℃/ W)

(m2℃/ W)

(m2℃/ W)

f 1

1

0, 96

0, 93

f k1

1

0, 99

0, 98

fx1

1

0,99

0,98

f 2

0, 99

0, 98

0, 95

f k2

1, 03

1, 04

1, 06

f x2

1, 03

1, 04

1, 06

f3

0, 99

0, 98

0, 95

fk3

1, 03

1, 04

1, 06

f x3

1, 03

1, 04

1, 06

Fouling factors Evaporator Heat recovery Desuperheater

Limits to exchanger water temperature are valid within the minimum maximum water flow range indicated in the Hydraulic Data section.

(1) Condenser water temp. 30/35 °C

(2) Evaporator water (in/out) 12/7 °C

(3) With temperatures down to -8°C use anti-freeze mixtures. In case of lower temperatures, please contact our Sales Department.

(4) Values related only to total heat-recovery version.

(5) Valid for temperature of fluid the evaporator >= -3°C. In case of lower temperatures, please contact our Sales Department.

ETHYLENE GLYCOL MIXTURE

Ethylene glycol and water mixtures, used as a heat-conveying fluid, cause a variation in unit performance. For correct data, use

the factors indicated in the following table.

cPf cooling capacity correction factor 

cQ flow correction factor 

cdp pressure drop correction factor 

For data concerning other kind of anti-freeze solutions (e.g. propylene glycol) please contact our Sales Department.

FOULING FACTORS

Performances are based on clean condition of tubes (fouling factor =1). For different fouling values, performance should be

adjusted using the correction factors shown in the following table.

f1 - f2 - f3 capacity correction factors

fk1 - fk2 - fk3 compressor power input correction factors

fx1 - fx2 - fx3 total power input correction factors

OPERATING RANGE

Page 13: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 13/20

CSRH-Y High efficient chillers

11

K Q min

m3/ h

Q max

m3/ h

C.a./ W.c.

min m3K 

Q min

m3/ h

Q max

m3/ hK 

Q min

m3/ h

Q max

m3/ h

Evaporator Rec. (1) - Cond (2) Desuperheater

0401

0501

0551

0651

0751

0802

0851

0951

1002

1102

1302

1502

1702

1902

1001

1201

1301

1351

1601

1801

2002

2402

2602

2702

3202

3602

4202

4502

4802

5003

5203

54035414

5904

6404

6804

7204

7804

8404

9004

9604

79

52

28. 1

28. 1

28. 1

18. 8

18. 8

28. 5

28. 5

28. 5

17. 5

12. 1

12. 1

5

26. 3

17. 5

12. 1

12. 1

5

5

4. 6

4. 6

2. 5

2. 7

2. 7

2

1. 4

1. 4

1. 4

1. 4

1

10. 7

0. 7

0. 5

0. 5

0. 5

0. 5

0. 3

0. 3

0. 3

10

11. 1

15. 9

15. 9

15. 9

17. 6

17. 6

17. 6

17. 6

17. 6

28

28

28

42

21. 4

28

28

28

42

42

42

42

55. 8

55. 8

55. 8

102

117

124

131

138

145

151112

112

181

193

205

220

234

248

262

45. 1

50. 9

73. 7

73. 7

73. 7

81. 7

81. 7

81. 7

81. 7

81. 7

108

114

114

162

74. 5

108

114

114

162

162

171

171

201

210

221

300

313

330

330

330

330

330421

448

600

600

600

600

625

660

660

0. 8

1

1. 2

1. 3

1. 5

1. 3

1. 8

2

1. 6

1. 8

2. 1

2. 4

2. 8

3. 2

2. 1

2. 5

2. 9

3. 2

3. 8

4. 3

3. 3

4

4. 6

5. 3

5. 9

6. 8

7. 8

8. 3

8. 7

9. 2

9. 7

10. 110. 5

11. 2

12. 1

12. 9

13. 7

14. 7

15. 6

16. 5

17. 4

98

104

58. 6

46. 2

37. 5

37. 5

30. 9

18

26

14. 7

11. 6

9. 4

7. 7

4. 5

12. 9

12. 9

10. 5

9. 3

6. 4

5. 3

3. 2

3. 2

2. 6

2. 3

1. 6

1. 3

0. 9

0. 8

0. 8

0. 7

0. 6

0. 60. 6

0. 5

0. 4

0. 4

0. 3

0. 3

0. 2

0. 2

0. 2

5. 6

6. 9

8. 4

9. 5

10. 7

11. 5

12. 8

14. 4

14. 2

16. 3

19. 4

22. 1

25. 5

29. 2

14. 7

14. 7

16. 3

17. 3

20. 8

22. 8

29. 4

29. 4

32. 5

34. 5

41. 5

45. 5

54

57

60

64. 3

66. 3

68. 369

76

83

87

91

99. 5

108

114

120

26. 3

28. 2

35

39. 4

43. 8

46. 5

51. 6

61. 3

57. 1

69. 9

78. 7

88. 9

103.1

122.1

73. 8

73. 8

83. 7

93. 6

110.1

125.1

147.1

147.1

167.1

189.1

215.1

248.1

283.1

299.1

315.1

334.1

352.1

366.1378.1

404.1

437.1

467.1

496.1

531.1

566.1

598.1

629.1

2813

203

116

116

74. 4

703

74. 4

40. 1

50. 8

28. 9

28. 9

18. 6

18. 6

10

186

186

124

124

86. 4

86. 4

46. 5

46. 5

31

31

21. 6

21. 6

17

17

17

9. 6

9. 6

9. 67. 7

6. 4

5. 4

5. 4

5. 4

4. 7

4. 2

4. 2

4. 2

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

00

0

0

0

0

0

0

0

0

3. 8

4. 8

5. 6

6. 4

7. 2

7. 7

8. 3

9. 7

9. 6

11

12. 9

14. 5

16. 6

19. 4

9. 9

11. 7

13. 4

14. 5

17. 2

19. 9

19. 2

23. 2

26. 6

28. 9

34. 2

39. 7

45. 2

47

48. 9

54

56. 6

59. 457. 6

63

68. 7

74

79. 2

84. 7

90. 4

93. 9

97. 6

SIZE

WATER FLOW AND PRESSURE DROP

Water flow in the heat exchangers is given by:

Q=Px 0,86/Dt

Q: water flow (m3/h)

Dt: difference between inlet and outlet water temp. (°

C)P: heat exchanger capacity (kW)

Pressure drop is given by:

Dp=K x Q2 /1000

Q: water flow (m3/h)

Dp: pressure drop (kPa)K: unit size ratio

Q min: minimum water flow admitted to the heat exchanger.

Q max: maximum water flow admitted to the heat exchanger.

W.c min.: minimum water content admitted in the plant.

(1) Rec. = Heat Recovery. For units with total heat recovery.

(2) Cond. = Condenser. For water to water type units. In units with heatrecovery ,

this data is valid for both the condensing and the heatrecovery exchangers.

Page 14: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 14/20

CSRH-Y High efficient chillers

12

Compressor Total unit

F.L.A.

(A)

L.R.A.

(A)

F.L.I.

(kW)

F.L.A.

(A)

S.A.

(kW)

F.L.I.

(kW)n

1

1

1

1

1

2

1

1

2

22

2

2

2

1

1

1

1

1

1

2

2

2

2

2

2

2

2

2

3

3

3

4

4

4

4

4

4

4

4

4

0401

0501

0551

0651

0751

0802

0851

0951

1002

11021302

1502

1702

1902

1001

1201

1301

1351

1601

1801

2002

2402

2602

2702

3202

3602

4202

4502

4802

5003

5203

5403

5414

5904

6404

6804

7204

7804

8404

9004

9604

32. 6

40. 5

48. 7

51. 7

64. 3

32. 6

70. 2

82. 1

40. 5

48. 751. 7

64. 3

70. 2

82. 1

82. 1

101

112

127

145

171

82. 1

101

112

127

145

171

191

191/ 217

217

145/ 171

145/ 171

171

127

127/ 145

145

145/ 171

171

171/ 191

191

191/ 217

217

55. 4

67. 1

80. 4

91. 7

105

55. 4

115

132

67. 1

80. 491. 7

105

115

132

132

165

184

208

235

272

132

165

184

208

235

272

310

310/ 351

351

235/ 272

235/ 272

272

208

208/ 235

235

235/ 272

272

272/ 310

310

310/ 351

351

153

169

206

267

290

153

350

423

169

206267

290

350

423

423

300

360

404

436

465

423

300

360

404

436

465

586

586/ 650

650

436/ 465

436/ 465

465

404

404/ 436

436

436/ 465

465

465/ 586

586

586/ 650

650

32. 6

40. 5

48. 7

51. 7

64. 3

65. 2

70. 2

82. 1

81

97. 4103

129

140

164

82

101

112

127

145

171

164

201

223

255

291

341

382

408

434

461

487

512

509

545

581

632

683

724

764

816

868

55. 4

67. 1

80. 4

91. 7

105

111

115

132

134

161183

210

230

264

132

165

184

208

235

272

263

329

367

416

470

544

620

661

702

742

779

816

832

886

940

1014

1088

1164

1240

1322

1404

153

169

206

267

290

208

350

423

236

286359

395

465

555

423

300

360

404

436

465

555

465

544

612

671

737

896

960

1001

935

972

1009

1028

1087

1141

1207

1281

1440

1516

1621

1703

Size

Maximum values

F.L.I. Power input

F.L.A. Current absorption

L.R.A. Locked rotor current for single compressor S.A. Starting current

(1)Safety values to be considered when cabling the unit for power supply and

line-protections

Voltage tolerance: 10%Maximum voltage unbalance: 3%

Electrical Data

Page 15: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 15/20

CSRH-Y High efficient chillers

13

0401

0501

0551

0651

0751

0802

0851

0951

1002

1102

1302

1502

1702

1902

1001

1201

1301

1351

1601

1801

2002

2402

26022702

3202

3602

4202

4502

4802

5003

5203

5403

5414

5904

64046804

7204

7804

8404

9004

9604

Octave band [Hz] at 1m

55

52

48

56

55

58

55

55

55

51

5958

58

58

55

53

63

67

55

50

58

54

6468

55

51

51

51

51

52

52

52

70

69

58

57

53

57

53

57

53

44

44

54

59

58

47

58

58

47

57

6261

61

61

58

51

55

57

74

70

61

52

5658

74

71

71

71

71

72

72

72

60

74

77

76

73

76

73

76

73

60

61

71

77

73

63

73

73

64

74

8076

76

76

73

70

71

80

77

82

76

71

7281

78

83

83

83

83

84

84

84

83

83

80

83

85

83

85

83

85

74

75

75

73

72

77

72

72

78

78

7675

75

75

72

79

74

76

75

77

75

80

7577

75

78

78

78

78

79

79

79

79

79

78

79

80

79

80

79

80

70

71

74

74

74

73

74

74

74

77

7777

77

77

74

77

79

78

78

76

77

78

8079

78

77

77

77

77

78

78

78

81

81

81

80

79

80

79

80

79

64

65

67

67

69

67

69

69

68

70

7072

72

72

69

68

70

68

69

70

72

69

7169

69

71

71

71

71

72

72

72

71

72

72

73

73

73

73

73

73

55

56

59

60

63

58

63

63

59

62

6366

66

66

63

55

57

52

63

62

66

56

5853

63

63

63

63

63

64

64

64

55

64

66

66

65

66

65

66

65

49

47

49

48

53

52

53

53

50

52

5156

56

56

53

44

45

40

51

52

56

45

4641

51

53

53

53

53

54

54

54

43

51

54

55

55

55

55

55

55

74

75

77

77

77

77

77

77

78

80

8080

80

80

77

80

80

80

80

80

80

81

8181

81

81

81

81

81

82

82

82

83

83

83

83

83

83

83

83

83

63 125 250 500 1000 2000 4000 8000 Total

Sound pressure level [dB]

Size

Working conditions:

evaporator water (in/out) 12/7 [°C]

condenser water (in/out) 30/35 [°C]

Sound pressure

Sound pressure level values in free-field conditions, at 1 m distance.

Full Load Sound Level

Page 16: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 16/20

CSRH-Y High efficient chillers

        8 7

       4

        3

       5        6

        2

       1

Eveaporatorwaterinlet

Evaporatorwateroutlet

Condenserwaterinlet

Condenserwateroutlet

Recuperatorwaterinlet

Recuperatorwateroutlet

Powerinlet

Mainisolator

1 2 3 4

5 6 7 8

     R     E     M     A     R     K     S     :

Forinstallationpurposes,pleaserefertothedocumentationsentafterthep

urchase-contract.Thistechnical

datashouldbeconsideredasindicative.CLIMAVENETAmaymodifythematanymoment.

Dime

nsionDrawing

14

Coolingtower

Wellwater

Condenserinterface

      ̀      p      o      e

      M      T      R      N

         N      V      M      O

   J      v

Page 17: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 17/20

CSRH-Y High efficient chillers

15

     R     E     M     A     R     K     S     :

Forinstallationpurposes,pleaserefertothedocumentationsentafterthep

urchase-contract.Thistechnical

datashouldbeconsideredasindicative.CLIMAVENETAmaymodifythematanymoment.

       4

        3

       1

        6

       5

        2

       7        8

Eveaporatorwaterinlet

Evaporatorwateroutlet

Condenserwaterinlet

Condenserwateroutlet

Recuperatorwaterinlet

Recuperatorwateroutlet

Powerinlet

Mainisolator

1 2 3 4

5 6 7 8

Dime

nsionDrawing

      ̀      p      o      e      N      M      M      N

         Q      U      M      O

   J      v

      ̀      p      o      e      R

      M      M      P

         R      Q      M      P

   J      v

      ̀      p      o      e      R      Q      N      Q

         V      S      M      Q

   J      v

Page 18: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 18/20

Page 19: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 19/20

CSRH-Y High efficient chillers

17

     I     N     S      T     R     U      C      T     I     O      N     S 

-Makesurethatallthepan

elsarefirmlyfixedinplacebeforemovingtheunit.

-Beforeliftingit,checktheweightontheCElabel.

-Useall,andonly,theliftingpointsprovided,

-Useslingsofequallength,

-Useaspread-bar(notincluded)

-Movetheunitcarefullyandavoidabruptmovements.

FreeSpaces-Lif

tingMode-Symbols

Page 20: CSRH-Y Water Cooled Chiller_R134a

7/27/2019 CSRH-Y Water Cooled Chiller_R134a

http://slidepdf.com/reader/full/csrh-y-water-cooled-chillerr134a 20/20

Climaveneta Italy:

36061 BASSANO DEL GRAPPA (VICENZA) ITALIA - VIA SARSON 57/c

TEL. +39 / 0424 509 500 (r.a.) - TELEFAX +39 / 0424 509 509

E-mail:[email protected] http://www.climaveneta.com

Climaveneta China:

No,88 Baiyun Road Xinghuo Developing Zone ,Shanghai,China Post Code:201419

TEL: +86-21-57505566 FAX: +86-21-57505797

E-mail:[email protected] http://www.climaveneta.com.cn

Climaveneta Hongkong:

Room 2003,CCT Telecom Building, 11 Wo Shing Street,Fotan,Shatin,N.T.,Hongkong

TEL: +85-2-26871755 FAX: +85-2-26873078

E-mail:[email protected] http://www.climaveneta.asia

Climaveneta Vietnam:

381A1 Cong Hoa Street Ward 13 Tan Binh District, HCM City, Vietnam

TEL: +84-8-38497529 FAX: +84-8-38124190

E-mail:[email protected] http://www.climaveneta.asia

All ifi ti d d t bj t t h ith t ti B212 CCU/01 12 2009EN SH