CSI Division 7 Guide Specification TIEMPO™+ 2000 TPO Mechanically Attached CSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY ATTACHED SYSTEMS PART 1 - GENERAL 1.01 Description A. Furnish and install mechanically attached TIEMPO™+ 2000 TPO membrane roofing system in accordance with drawings and specifications approved by Dow Roofing Systems (DRS). Special Conditions 1. Applications that involve severe exposures, ASCE Ground Roughness Category D, and those conditions outlined in secion 3.03 require review by Dow Roofing Systems Technical Review Department before any specification is valid (Reference Table 2, ASCE Exposure Classification Chart). Buildings operating with interior positive pressure at the deck require review by DRS Technical Review Department before any specification is valid. B. Related work: Metal work other than Dow Edge Metal Systems is not covered by DRS for Warranty. Metal work must be secured in a manner approved by DRS, SMACNA guidelines, and/or in compliance with ES-1 where applicable. All metal work that is part of the waterproofing envelope must be sealed, structurally sound, and appropriately anchored to prevent leakage. 1.02 Quality assurance A. Apply roofing system using a roofing applicator authorized by DRS. B. TIEMPO™+ 2000 TPO membrane is classified by Underwriters Laboratories as a Class A sheathing material for use in construction of Class A roofing assemblies. See UL’s Roofing Materials and Systems Directory for specific assemblies. Meets all test requirements for Factor Mutual Global (FMG) Class 1A fire and wind resistance (Reference Factory Mutual Global RoofNav Database). C. Inspection: Upon completion of the installation, an inspection will be performed by a representative of DRS to ascertain that the roofing system has been installed according to DRS approved specifications and details. Upon approval of the project, a warranty shall be written. D. Changes: Should there be deviations or changes from this specification without written approval from DRS, the project is not authorized for installation and is not eligible for warranty coverage. 1.03 Submittals A. Minimum job file submittal information for warranty coverage consideration shall be an accurately completed Request for Warranty form (www.dowrfw.com) and the information discussed in paragraph B following. B. Authorized Applicators must submit a roof drawing indicating which details will be employed in the project. These drawings shall be approved by DRS prior to the start of work, and must include: outline and size of the roof, location and type of penetrations, perimeter and penetration flashing detail references, and a copy of any non-DRS details to be used. Details which do not conform to Standard DR Detail Drawings must be submitted to DRS Technical Review for approval. C. Samples and data sheets of all materials not supplied or approved by DRS shall be submitted to DRS for written approval prior to the start of installation. D. For a Limited Membrane Material Only Warranty, the Request for Membrane Warranty form is the only submittal required. 1.04 Delivery and Storage A. All materials provided by DRS shall be delivered with appropriate packaging labels indicating warnings, storage conditions, lot numbers, and usage instructions. B. Materials shall be stored in their ®™ Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. T2000 MA.09.09. 1

Transcript of CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc ·...

Page 1: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

CSI Division 7 Guide SpecificationTIEMPO™+ 2000 TPO Mechanically Attached

CSI Division 7 Guide Specifications TIEMPO™+ 2000 TPO MEMBRANE MECHANICALLY ATTACHED SYSTEMSPART 1 - GENERAL 1.01 Description

A. Furnish and install mechanically attached TIEMPO™+ 2000 TPO membrane roofing system in accordance with drawings and specifications approved by Dow Roofing Systems (DRS).

Special Conditions 1. Applications that involve severe exposures, ASCE

Ground Roughness Category D, and those condi-tions outlined in secion 3.03 require review by Dow Roofing Systems Technical Review Department before any specification is valid (Reference Table 2, ASCE Exposure Classification Chart). Buildings operating with interior positive pressure at the deck require review by DRS Technical Review Depart-ment before any specification is valid.

B. Related work: Metal work other than Dow Edge Metal Systems is not covered by DRS for Warranty. Metal work must be secured in a manner approved by DRS, SMACNA guidelines, and/or in compliance with ES-1 where applicable. All metal work that is part of the waterproofing envelope must be sealed, structurally sound, and appropriately anchored to prevent leak-age.

1.02 Quality assurance A. Apply roofing system using a roofing applicator autho-

rized by DRS.

B. TIEMPO™+ 2000 TPO membrane is classified by Underwriters Laboratories as a Class A sheathing material for use in construction of Class A roofing assemblies. See UL’s Roofing Materials and Systems Directory for specific assemblies. Meets all test requirements for Factor Mutual Global (FMG) Class 1A fire and wind resistance (Reference Factory Mutual Global RoofNav Database).

C. Inspection: Upon completion of the installation, an in-spection will be performed by a representative of DRS to ascertain that the roofing system has been installed according to DRS approved specifications and details. Upon approval of the project, a warranty shall be writ-ten.

D. Changes: Should there be deviations or changes from this specification without written approval from DRS, the project is not authorized for installation and is not eligible for warranty coverage.

1.03 Submittals

A. Minimum job file submittal information for warranty coverage consideration shall be an accurately com-pleted Request for Warranty form (www.dowrfw.com) and the information discussed in paragraph B follow-ing.

B. Authorized Applicators must submit a roof drawing indicating which details will be employed in the project. These drawings shall be approved by DRS prior to the start of work, and must include: outline and size of the roof, location and type of penetrations, perimeter and penetration flashing detail references, and a copy of any non-DRS details to be used. Details which do not conform to Standard DR Detail Drawings must be submitted to DRS Technical Review for approval.

C. Samples and data sheets of all materials not supplied or approved by DRS shall be submitted to DRS for written approval prior to the start of installation.

D. For a Limited Membrane Material Only Warranty, the Request for Membrane Warranty form is the only sub-mittal required.

1.04 Delivery and Storage A. All materials provided by DRS shall be delivered with

appropriate packaging labels indicating warnings, stor-age conditions, lot numbers, and usage instructions.

B. Materials shall be stored in their original undamaged packaging and storage conditions shall be maintained in accordance with the manufacturer’s requirements.

1.05 Precautions A. Adhesives, solvents, and caulks as indicated are

potentially flammable and/or toxic. Follow precautions indicated on containers or packaging labels.

B. Surfaces to be bonded shall be dry, clean and free of debris. Suitable surfaces are usually considered to be smooth: solid masonry, wood, and metal, plus insula-tion board fastened per the specific manufacturer’s recommendations for receiving adhered roofing mem-branes and accepted by DRS for adhered applications of TIEMPO™+ 2000 TPO membrane.

C. All fasteners should be installed with a depth-sensing screw gun to prevent over driving or under driving.

D. Block off or shut down positive pressure building ventilation systems during application to prevent sheet from billowing during application

.

E. Consideration should be given in the project design to potential safety problems that can precipitate from the smooth surface characteristic of the TIEMPO™+ 2000

®™ Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. T2000 MA.09.09.1

Page 2: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

CSI Division 7 Guide SpecificationTIEMPO™+ 2000 TPO Mechanically Attached

TPO sheet. The membrane surface becomes slippery when wet. If access to roof is required, walk way surfaces are highly recommended. In northern climates, sliding snow could create a hazard below and adjacent to the perimeter if a retarding system is not installed on roofs with slopes greater than 2-in. per foot.

F. Job specification and retrofit preparation should always include provision to ensure positive drainage in all areas. Good roofing practice does not permit uncontrolled, uncollected drainage over the edge of a roof.

G. All rooftop mechanical units are to have their conden-sation lines piped to drains, or off the roof.

H. Grease shall not be allowed to accumulate on the roof. If rooftop grease units do not receive continual maintenance they are to have an approved grease containment system specified.

I. At the discretion of DRS, excessive patching as a re-sult of damage to the TIEMPO™+ 2000 membrane, or caused by faulty installation, may require total recover in those areas.

J. Buildings with canopies or large wall openings, e.g. hangar doors and truck docks or buildings that are otherwise subject to positive pressurization from wind or air handling systems, consult DRS suitability of application and possible design enhancement require-ments.

1.06 Warranty A. A DRS Technical Representative shall inspect the

installation for compliance with applicable DRS speci-fications upon completion of the roofing system.

B. Upon acceptance of the roofing system installation, a DRS Standard or Total System Warranty will be issued for a five (5), ten (10) or fifteen (15) year period that covers wind damage up to 60 mph.

(Refer to Appendix 3, Additional Requirements for DRS 20-year Warranty Systems.)

C. For additional information see General Warranty section of the DRS Technical Manual or at www.dowroofingsystems.com.

PART 2 - PRODUCTS 2.01 General

A. DRS supplies a full line of accessory components to complete the construction of a DRS membrane roofing system. These parts shall be used when applicable in assemblies requiring a DRS Warranty. Materials for warranted systems are described or specified herein. Materials other than those supplied by DRS shall be submitted to the DRS Technical Review Department for review and approval prior to the start of work.

2.02 Membrane

A. Membrane for roof cover shall be 0.045-in., 0.060-in. or 0.080-in. (TIEMPO™+ 2000 TPO nominal thickness overall), scrim-reinforced, Ethylene propylene-based sheet in widths 5 ft, 8 ft, or 10 ft wide by appropriate length conforming to the physical properties in Table 1, Physical Properties Chart. TIEMPO™+ 2000 TPO membrane is available in white. Contact your DRS Representative for thickness options, minimums, and lead times. TIEMPO™+ 2000 Membranes meet the ASTM 6878-06 specification for TPO-based roofing material. Packaging to bear the UL label.

2.03 Related Materials A. Insulation/underlayment/recover board: DRS

supplies a wide range of insulations, underlayments and cover-boards to satisfy a broad spectrum of design conditions. Only Dow supplied insulation products can be used for warranty coverage. (Reference Appendix 2-M, DRS Approved Insulation List and Fastening Rates for Mechanically Attached Systems). 1. STYROFOAM™ Brand Extruded

PolystyreneFoam Insulation (XPS): Extruded polystyrene closed-cell foam panel with continuous skin on face and back surface that meets ASTM C-578, Standard Specification for Rigid Cellular Polystyrene Thermal Insulation. (Reference Dow Technical Data Sheets for additional information).

2. TERMICO™ Polyisocyanurate Insulation: Closed-cell HCFC FREE polyisocyanurate foam core manufactured and integrally laminated to heavy non-asphaltic, fiber-reinforced felt facers; Is available in 20 or 25 psi compressive strength. (Reference DRS Technical Data Sheets for additional information).

3. TERMICO™ Polyisocyanurate Insulation Tapered: Closed-cell HCFC FREE polyisocyanurate foam core manufactured and integrally laminated to a heavy non-asphaltic, fiber-reinforced felt facers; Is available in 20 or 25 psi compressive strength. (Reference DRS Technical Data Sheets for additional information).

4. TERMICO™ ISO 3000: Closed-cell HCFC FREE polyisocyanurate foam core manufactured and integrally laminated to a heavy coated-glass facers; Is available in 20 or 25 psi compressive strength. (Reference DRS Technical Data Sheets for additional information).

5. TERMICO™ HP-FR: Closed-cell polyisocyanurate foam core integrally laminated to heavy, durable and dimensionally stable inorganic coated-glass facers. CFC-, HCFC-, and HFC-free foam blowing technology with zero ozone depletion potential (ODP) and zero (negligible) global warming potential (GWP). Dow TERMICO™ HP-FR is available in 20 psi compressive strength. (Reference DRS Technical Data Sheets for additional information).

6. DensDeck® Roof Boards: (Reference Technical

®™ Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. T2000 MA.09.09.2

Page 3: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

CSI Division 7 Guide SpecificationTIEMPO™+ 2000 TPO Mechanically Attached

Data Sheets for additional information).

a. Georgia-Pacific Gypsum Corporation 1/4-in. DensDeck Roof Board, 1/2-in DensDeck Roof Board and 5/8-in.Type X Roof Board. Non-structural, glass mat faced gypsum panel with water-resistant core available in 4-ft.x8-ft. sizes and 4-ft.x4-ft.sizes.

b. Georgia-Pacific Gypsum Corporation 1/4-in. DensDeck Prime Roof Board, 1/2-in. DensDeck Prime Roof Board and 5/8-in. DensDeck Prime Roof Board (Type X). Glass mat faced gypsum with non-asphaltic, highly filled proprietary heat-cured coating on one side available in 4-ft.x8-ft. and 4-ft.x4-ft. sizes.

7. Expanded Polystyrene (EPS): ASTM C578-04a expanded polystyrene thermal rigid board insulation with a minimum density of 1.25 lbs./cu.ft. (ft3). (Reference DRS Technical Data Sheets for additional information).

B. Flashing Membrane: Flashing shall be 0.045-in. or 0.060-in, thick membrane for walls and curbs. Unsupported 0.060-in. thick, Ethylene propylene-based membrane shall be supplied for field-fabricated vent stacks, pipes, drains, and corners.

C. Adhesive, Primers, Caulks and Sealant: 1. Dow 2000 Membrane Adhesives: Are designed

for bonding all TIEMPO™+ 2000 TPO membranes to wood, metal, masonry, and approved roof insulation board surfaces.

a. Dow 2000 Membrane Adhesive (Solvent Based)

b. Dow 2000 Membrane Adhesive (Low-VOC)

2. Dow 2000 Multi-Purpose Sealant: Dow 2000 Multi-Purpose Sealant is designed to be used as a water cutoff mastic, sealant to top off pitch boxes as an exterior grade caulk for metal work.

3. Dow 2000 Edge Sealant: Dow 2000 Edge Sealant is a solvent-based sealant developed to seal exposed cut edges of reinforced membrane.

4. Dow 2000 Insulation Adhesive (2 Part urethane): Dow 2000 Insulation Adhesive (2 Part Urethane) is a two part, polyurethane low rise foam that is applied in ribbons with appropriate dispensing equipment.

5. INSTA STIK™ Quik Set Insulation Adhesive: INSTA STIK™ Quik Set Insulation Adhesive is a single component polyurethane insulation adhesive dispensed from a portable, disposable, pre-pressurized container requiring no external power source. Product must be installed as required by manufacturer.

DRS Insulation Adhesives are designed for bonding most insulation and recover boards to a wide range of substrates. Please consult the appropriate Technical Data Sheet or the DRS Technical Department for detailed information.

6. Dow 2000 Membrane Cleaner: Dow 2000

Membrane Cleaner is a surface cleaner for use with TIEMPO™+ 2000 TPO membranes that have become dirty or contaminated prior to heat welding.

D. Perimeter sheets: 1. Perimeter Sheet specification is defined as

TIEMPO™+ 2000 TPO membrane with a maximum sheet width of 5 ft. (60-in).

2. Perimeter sheet(s) shall be installed at all exterior building perimeter edges, and along the upper edge of adjoining roof levels when the difference between roof elevations is greater than 3-ft.

3. Perimeter area shall be defined as follows: the extent of perimeter and corner enhancement is based on the smaller value of either 40% of building elevation or 10% of the least horizontal dimension. Perimeter/corner enhancement can never be less than 4% of the least horizontal plan dimension, or 3-ft.

4. Guidelines addressing more severe exposures and special building conditions can be reference in Section 3.03.

DRS published fastening rates for perimeter enhancement may not comply with the requirements of FMG. For additional information contact DRS Technical Review Department

E. Mechanical fasteners: Shall be supplied by DRS.

1. Membrane:

a. Refer to Appendix 1, DRS Fastener Selection Guide and Table 4 System Options Specification Guide to select appropriate fastener and plate combination and approved fastening rates. Also, DRS Technical Data Sheets can be found on the DRS Technical Manual CD-Rom or at www.dowroofingsystems.com.

b. For gypsum, cementitious woodfiber decks (“Tectum”) and light-gauge metal panel roofs, fastener pull tests must be submitted to DRS Technical Review Department with the project Request for Warranty form (RFW).

2. Insulation:

a. Refer to Appendix 1, DRS Fastener Selection Guide and Approved 2-M Insulation List and Fastening Rates to select appropriate fastener/plate combination and approved fastening rates. Also, DRS Technical Data Sheets can be found on the DRS Technical Manual CD-Rom or at www.dowroofingsystems.com.

b. For gypsum, cementitious woodfiber decks (“Tectum”) and light-gauge metal panel roofs, fastener pull tests must be submitted to DRS Technical Review Department with the project Request for Warranty form (RFW).

®™ Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. T2000 MA.09.09.3 ® DensDeck is a registered Trademark of Georgia-Pacific.

Page 4: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

CSI Division 7 Guide SpecificationTIEMPO™+ 2000 TPO Mechanically Attached

F. Dow 2000 Aluminum Termination bar: Dow 2000 Aluminum Termination Bar fastened 6-in. o.c. is the only authorized product.

G. Dow 2000 Edge Metal Systems: Dow 2000 Edge Metal must be installed per standard DRS details. Dow 2000 Clad Metal may be used for gravel stops or drip edges.

H. Dow 2000 Walkway Roll: When roof traffic is indicated (for example to service rooftop units), a walkway over the membrane shall be made. DRS recommends Dow 2000 Walkway Rolls to heat welded to the membrane surface.

I. Dow 2000 TPO Pipe Boots/Vent Gloves: Are provided as an alternative to 0.060-in. unsupported flashing for vent stacks and pipes 1-in. to 6-in. diameter.

J. Dow 2000 TPO universal Inside/Outside Corners: Are provided as an alternative to 0.060-in. unsupported flashing for use at outside and inside corners.

K. Dow 2000 T-Joint Patch: Dow 2000 T-Joint Patches are made with TIEMPO™+ 2000 TPO Unsupported membrane and are used to cover T-joints in the membrane. Refer to Guide Specifications for installation requirements.

L. Dow 2000 Flashing Tape and Dow 2000 Tape Primer: 6-in. wide x 0.60-in. thick, packaged 100-ft. rolls. This product is made with unsupported membrane with a butyl tape backing (with a release paper) and is the preferred method for stripping-in non-Dow gravel stop and drip edge metal (not for use on Dow 2000 Clad Metal). Surfaces must be prepared with Dow 2000 Tape Primer prior to Dow 2000 Flashing Tape application.

PART 3 - EXECUTION 3.01 Substrate Preparation

A. The applicator is responsible for ensuring the suitability of the substrate surface to accept the TIEMPO™+ 2000 TPO membrane. In reroofing, test cuts shall be made by the roofing applicator to determine existing condition and deck suitability. All noticeably damp, wet or deteriorated materials must be removed and replaced. In all cases, prior to the start of work, the substrate shall be smooth and free of debris, sharp edges, and other surface irregularities that will be detrimental to the installation. Any unevenness or joint gaps greater than 1/4-in. in the membrane substrate can cause inconsistent membrane welds and must be avoided. When such conditions occur, fill with appropriate and properly secured insulation or material approved by DRS Technical Review Department.

B. Steel deck, wood plank and lightweight cementitious decks: Shall be covered with an approved insulation mechanically fastened or adhered to the deck with DRS approved products (Exception: Adhering to steel decks is not approved). (Reference Appendix 2-M, Approved Insulation List & Fastening Rates for Mechanically Attached

Systems). Certain insulation types may require a thermal barrier underlayment and/or cover board in order to meet building code, Factory Mutual or other agency requirements. Consult DRS Technical Department and/or applicable building code.

C. Concrete, plywood, or flat sheet-metal surface: Shall be dry, flat, clean, smooth, free of sharp edges, and suitable for acceptance of TIEMPO™+ 2000 membrane. Plywood must be exterior grade with an A or B finish side up and with no joints gapped greater than 1/4-inch. Consideration should be given to installing slip plates over all gapped or uneven joints where membrane seams will cross to minimize welding inconsistency. Thickness, structural grade, fastening, and fire resistance requirements should meet the requirements and recommendations of applicable building codes and the APA and are the responsibility of the owner and the installer. Concrete must be dry, cured, and prepared smooth with dust removed. The membrane shall have a fastened expansion joint detail (as per Standard DRS Detail Drawings) where deck joints exceed 1/4-in. or when crossing a building expansion joint.

D. Reroofing over existing roof: The specifier and/or applicator shall determine the condition of the existing roof. Deteriorated decking must be repaired or replaced, as appropriate. Wet materials (containing free moisture that would evaporate if exposed to atmosphere) must be found and replaced. Existing surface shall be dry, reasonably smooth and even, blisters cut, and loose aggregate removed prior to installation of approved insulation board.

E. Vapor retarder: Is not required for protection of Dow Roofing System membrane. As a guideline, the National Roofing Conctactors Association (NRCA) states, “... vapor retarders should be considered for use when both of two conditions are anticipated: (1) the outside mean, average January temperature is below 40oF (4.4oC), and (2) the expected winter, interior relative humidity is 45 percent or greater.” Consult design professional or building designer for determination of vapor retarder requirement.

NOTE: In all high humidity situations consult DRS Technical Review Department and the insulation manufacturer for specific application requirements.

F. Nailers: Pressure preservative treated wooden nailers shall be installed at gravel stops or drip edges.

1. Reroofing: Use #2 or better wood treated for rot resistance. Creosote and asphaltic preservatives are not acceptable.

2. New roofing: As specified by architect. A pressure preservative treated wood nailer is recommended. Effective perimeter attachment must be achieved per details.

3. All construction: Nailer shall be anchored with a suitable fastener for the application having a minimum withdrawal resistance of 100-lbs., staggered 6-in. o.c. within 8-ft. of an outside corner and 12-in. o.c. along other perimeter areas.

4. All construction: Nailer thickness shall be chosen to match the top surface of adjacent construction

®™ Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. T2000 MA.09.09.4

Page 5: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

CSI Division 7 Guide SpecificationTIEMPO™+ 2000 TPO Mechanically Attached

±1/4-in. This permissible variation shall not contribute to ponding.

5. Nailers: Nailers around skylights, curbs, expansion joints, etc., are not required. Use of DRS fasteners and plates anchored to deck 12-in. o.c. (except tall building applications, see 3.03.E) through membrane and insulation is acceptable.

G. Existing flashings: Must be removed and completely cleaned off wherever new Dow Roofing System terminations and water stops are to be installed. Existing flashings may be left in place up to DRS termination areas when in good structural condition and solidly attached to the substrate.

H. New construction or reroof with complete tearoff of flashings: The applicator is responsible for determining the suitability of the substrate for the TIEMPO™+ 2000 membrane. The substrate shall be smooth and free of sharp edges and other surface irregularities that prevent the flashing membrane from being 100% adhered.

3.02 Application Procedures NOTE: For insulation application and suitability, refer to Appendix 2-M, DRS Approved Insulation List & Fastening Rates.

A. Insulation or protection board: 1. Minimum thickness: Shall be approved in writing

by DRS. Since the insulation requirement for thermal value will vary for each project, the thickness of the insulation must be calculated for the desired results.

2. Compatibility: Certain polystyrene type insulations are not compatible with coal tar pitch. Contact insulation manufacturer for recommendations. (Reference Appendix 2-M, Approved Insulation List and Fastening Rates for Mechanically Attached Systems).

3. Manufacturers’ instructions: In regard to attachment, compatibility, and spanning metal flutes, the manufacturers’ specifications shall determine the suitability for an application, subject to acceptance by DRS.

4. Precautions: Be careful when handling insulation to avoid damaging or rupturing the facer and/or surface. All damaged areas must be cut out and replaced with structurally sound insulation that is properly secured in place.

5. Attachment: Insulation boards must be secured sufficiently to conform to the substrate surface geometry and this may necessitate additional securement beyond or in excess of the minimum published DRS requirement.

a. Mechanical attachment: All boards must be attached with DRS supplied insulation plates and appropriate fasteners. (Reference Appendix 2-M, Insulation List & Fastening Rates for Mechanically Attached System).

b. Adhered insulation with approved adhesive: As an alternative to mechanical attachment, DRS permits adhering insulation with DRS-supplied insulation adhesive as stated herein. (Reference Section 3.01). DRS Insulation Adhesives are the only products eligible for DRS warranty coverage. Insulation boards must be secured sufficiently to conform to the substrate surface geometry.

c. Adhered insulation with asphalt: As an alternative to mechanical attachment, DRS permits adhering insulation with hot steep asphalt (ASTM D-312 Type III or IV). The specific application must be approved in writing from the insulation board manufacturer and be approved by DRS Technical Review Department All temperature requirements and application procedures must be followed. Insulation boards must be secured sufficiently to conform to the substrate surface geometry.

6. Tapered insulation: Most tapered insulation systems taper down to a minimum 1/2-in. thickness only. Therefore, a tapered edge strip of high-density fiberboard should be used to provide a smooth transition to the flat areas.

7. Approved insulation boards shall be installed with the longest dimension perpendicular to the direction of the membrane seams whenever possible and installed with end joints staggered. Over steel decking install the longest board dimension parallel to deck corrugations. Boards will be butted as closely as possible with no gaps over 1/4-in. and secured as specified in 3.02.A.5.

B. Membrane installation procedures: 1. DRS perimeter and corner sheet(s): Perimeter

sheet(s) shall be installed at all exposed building perimeters. (Reference 2.03.D for perimeter sheet specifications). Corners shall be installed as shown in DRS Standard Detail Drawing DR-602. Appropriate DRS fastener and plate combination (Reference 2.03.E and Appendix 1, DRS Fastener Selection Guide) is installed along the edge of the membrane through the insulation (through existing roof in reroofing), and into the roof deck. (Reference DRS Technical Manual, standard DRS details and Table 4 Systems Options Specification Guide and Approved 2-M Insulation List and Fastening Rates). Adjacent rolls of TIEMPO™+ 2000 TPO membrane shall overlap the fastened edge of the installed membrane by 6-inches. (Reference DRS Technical Manual, Standard Detail Drawing DR-624.) At perimeters that are to receive a gravel stop or metal edging, TIEMPO™+ 2000 TPO membrane must be brought over the outside edge and terminated 12-in. o.c. unless otherwise stated in the appropriate detail.

2. Field sheets: TIEMPO™+ 2000 TPO membrane shall be unrolled on the area to be covered. Appropriate Dow 2000 Fastener and Plate combination (Reference section 2.03.E and

®™ Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. T2000 MA.09.09.5

Page 6: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

CSI Division 7 Guide SpecificationTIEMPO™+ 2000 TPO Mechanically Attached

Appendix 1, DRS Fastener Selection Guide) should be installed along the leading edge of the membrane, as illustrated in Standard Details Drawing DR-624, through the insulation (through existing roof in reroofing) and into the roof deck. Adjacent rolls of TIEMPO™+ 2000 TPO membrane shall overlap the fastened edge of the installed membrane by 6-inches.

C. Lap splice: Membrane shall be overlapped and hot-air welded without any contaminants (adhesive, dirt, debris, etc.) in the seam.

1. Hot-air welding: An automatic hot-air welder and hand-held welder which are functionally in top condition are a necessity for DRS applications. Small work and repairs can be completed efficiently with the hand-held welders, however, hand-held welders are not a recommended means of field seaming.

2. The entire lap edge must be probed with an approved seam probing tool (i.e. Sears cotter pin extractor) after it has cooled completely to verify seam consistency. Probing before the seam area has cooled will damage the membrane. In addition, destructive tests should be performed daily on a 3-in. wide area of seam weld to verify sufficient peel strength. A properly welded seam will have membrane delamination from scrim prior to weld failure. Destructive tests on welds should be conducted for the first seam of the day, the first seam after the robot welder has been allowed to cool down, and after any extreme changes in weather conditions. Cut edges shall be caulked by applying Dow 2000 Edge Sealant from a squeeze bottle.

3. T-Seams.

a. Definition: The point where two perpendicular lap seams intersect is called a “T-seam” and if T-seams are not properly welded, a seam void may result, which will require patching.

b. For 0.045-in. and 0.060-in. membrane, T-seams should be properly creased in at the step-off area, using a hand roller. For T-seam locations that have not been welded properly, a patch is required. Patches shall be a minimum of 4-in. in diameter and can be either 0.045-in. reinforced TIEMPO™+ 2000 membrane, 0.060-in. unsupported membrane, or Dow 2000 T-Joint Patch.

c. For TIEMPO™+ 2000 0.080-in. thick membrane, a patch is required on all T-seam locations.

4. Membrane Preparation: TIEMPO™+ 2000 membrane, as with any material after exposure, will require cleaning prior to seaming. The approved method for cleaning TIEMPO™+ 2000 membrane prior to hot-air welding is as follows:

a. Remove any visible dirt and debris with a clean rag and water. For heavily contaminated surfaces, scrubbing with a detergent cleaner

(i.e. Fantastik® or 409®) followed by a water rinse may be necessary.

b. With a clean scrub pad saturated with Dow 2000 Membrane Cleaner, aggressively agitate the seaming area. With a clean white rag, follow with a final one-swipe pass over the seaming area, without redepositing any contaminants.

c. Allow Dow 2000 Membrane Cleaner to completely flash off (i.e. membrane should be completely dry).

d. Follow the standard hot-air welding procedures with an approximate 20% reduction in speed.

e. Final weld strength may not be achieved for several days.

D. Perimeter fastening: Wood nailers are required for perimeter gravel stops or drip edges. Membrane may be fastened at other terminations using DRS Fasteners and Seam Plates.

1. Wooden nailers: See 3.01.F.

2. Base of parapet or curb: Membrane shall be mechanically fastened 12-in. o.c. (except as described in section 3.03.E) through insulation (and existing roof in reroofing) into deck. Fastening shall occur at parapet wall, curbs, skylights, expansion joints and any other roof penetrations that exceed 24-in. in any dimension (Reference specific DR Detail Drawings).

E. Flashing: Perimeters, curbs, vents, expansion joints, drains, and other details shall be flashed as shown in standard DRS Detail Drawings. Under no condition shall flashings cover weep holes or any form of through-wall drainage.

1. Apply Dow 2000 Membrane Adhesive (Solvent Based) or Dow 2000 Membrane Adhesive (Low- VOC) to both underside of flashing membrane and surface to which it is to be bonded at a rate of approximately one gallon per 60 square ft. of surface coverage (when applied to two surfaces).

NOTE: Adhesive shall not be applied to membrane surfaces that are to be hot-air welded. Hot-air welding shall be used throughout the system where DRS Membrane overlaps itself.

2. Dow 2000 Membrane Adhesive shall be allowed to dry until tacky and until it does not string or stick to a dry finger. Roll the flashing into the dry adhesive. Care must be taken to ensure that the flashing does not bridge where there is any elevation or directional change. Completely roll in the flashing membrane against the substrate using a hand roller, J-roller or similar device applying firm pressure to the entire surface area to promote full contact.

3. All flashing shall be terminated as shown in standard DR Detail Drawings.

4. Dow 2000 Clad Metal Flashing at perimeter shall be made and installed as per standard DR Detail

®™ Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. T2000 MA.09.09.6

®Fantastik is a registered Trademark of S.C. Johnson & Son, Inc.®409 is a registered Trademark of the Clorox Company.

Page 7: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

CSI Division 7 Guide SpecificationTIEMPO™+ 2000 TPO Mechanically Attached

Drawings.

5. Pipe flashings shall be installed in accordance with standard DR Detail Drawings. Remove existing flashings and sleeves. Do not flash to lead.

6. Expansion joints shall be installed according to standard DR Detail Drawings.

7. Roof drains shall be installed according to standard DR Detail Drawings. In reroofing, old drains must be cleaned or replaced as needed for clamping detail. All bolts must be properly secured to supply 100% continuous compression of the clamping ring. Remove old leads and packings. Field seams shall not be run through drains. Drain sleeves are not covered under warranty. Prefabricated sleeve insert with a clamping ring and backflow seal are recommended.

F. Metal work: Metal work other than Dow Edge Metal Systems is not covered by DRS Warranty.

1. Metal work shall be installed in a manner that prevents damage from buckling or wind.

2. All metal work must be sealed and waterproofed in an acceptable manner.

G. Overnight seal/temporary water stop: Shall be made by a sealant method approved by DRS. To protect the insulation from inclement weather at the end of a day’s work, the membrane is extended beyond the insulation and set into the approved overnight seal material. Roofing applicator shall coordinate installation to ensure the system is made watertight at the end of each workday.

H. Roof walkway: When regular roof traffic is indicated (for example, to service rooftop units), Dow 2000 Walkway Roll is recommended over the membrane. Installation:

For dirty and/or weathered membrane, start with #1 below. For clean fresh membrane, start with #4 below.

1. TIEMPO™+ 2000 membrane must be clean and dry. Remove any visible dirt and debris with a clean rag and water. For heavily contaminated surface, scrubbing with a detergent cleaner (i.e. Fantastik® or 409®) followed by a water rinse may be necessary.

2. With a clean scrub pad saturated with Dow 2000 Membrane Cleaner, aggressively agitate the seaming area of the roof membrane surface. With a clean white rag, follow with a final one-swipe pass without redepositing any contaminants.

3. Allow Dow 2000 Membrane Cleaner to completely flash off (i.e. membrane should be completely dry).

4. Position Walkway Roll and cut to desired length. In circumstances where drainage around the walkway is a concern, shorter walkway lengths spaced with a 2-in. gap may be desired.

Whenever possible, walkway shall not cover seams. When installed adjacent to a seam, the walkway should be kept a minimum of 2-in. from the edge of the seam on the bottom sheet of the

completed lap and a minimum of 6-in. from the edge of the seam when located on the top sheet of a completed lap.

When covering seams is unavoidable, the lap seam should be completed per DRS Specifications and thoroughly probed with any deficiencies repaired prior to walkway installation.

5. Fully weld perimeter of walkway to the membrane following standard welding procedures.

3.03 Fastening Requirements NOTE: Attachment recommendations are for DRS Warranty Issuance only and may not comply with all Factory Mutual Global (FMG) system enhancement requirements for perimeter and corner areas. Refer to applicable FMG Loss Prevention Data Sheets or contact DRS Technical Review Department.

A. Membrane Fastening Requirements 1. Field Sheet Attachment - follow procedure below:

a. Determine Basic Wind Speed for specific project location using diagrams in current versions of: ASCE-7, Factory Mutual Global LPDS 1-28 (Reference the RoofNav Database at www.roofnav.com), or similar approved wind guidelines.

b. Consult Table 2-ASCE Exposure Classification to determine appropriate exposure category for specific project location.

c. Use Table 3-System Options Specification Guide to determine acceptable attachment option.

d. Table 4 - System Options Attachment Guide provides a detailed securement recommendation for approved fastening combinations. Note: These attachment options are applicable for Field areas only.

2. Perimeter Sheet Attachment:

a. Perimeter sheet(s) shall be installed as indicated in Section 2.03 D. Exception: System Option H-1 requires a maximum 3-ft. perimeter sheet width.

b. Perimeter sheet fastener spacing within the 6-in. seam overlap shall be the same as for the approved Field area System Option.

3. Corner Sheet Attachment Options:

a. All corner sheets shall be installed as shown in Standard DR Detail Drawing DR-602.

b. Reduce the lap seam fastener spacing of the corner sheets to one-half that of the approved perimeter sheet fastener spacing for those sheets that fall within the designated corner area. If the resultant fastener spacing is less

®™ Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. T2000 MA.09.09.7

Page 8: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

CSI Division 7 Guide SpecificationTIEMPO™+ 2000 TPO Mechanically Attached

than 6-in. on-center, this method can’t be used and option “c” should be used.

c. Reduce the row spacing of corner sheets to one-half that of the perimeter sheet row spacing by installing a row of fasteners and plates (at the prescribed fastener spacing) along the centerline of those perimeter sheets that fall within the designated corner areas. Cover fastener row with a minimum 9” wide reinforced membrane strip, hot-air welded in-place per DRS Specifications.

B. Severe Exposure and Special Building Conditions 1. For buildings over 110-ft. high fasten around all

projections over 12-in. in length or diameter at 9-in. o.c.

2. Buildings situated on a high elevation relative to the surrounding area (Reference Table 2, ASCE Ground Roughness) are subject to different fastening patterns (Contact DRS Technical Review Department)

3. Changes in parapet wall heights, fire walls, adjacent roof areas, and roof geometry affect wind exposure. Ensure that all such pertinent information is submitted to DRS for review before committing to a fastening specification.

C. Special Conditions: Any one of or combination of the below conditions is a valid reason to consider increased perimeter and field fastening. DRS may require enhanced system design in the absence of significant compensating factors. DRS should be consulted before committing to a design and/or cost. Typical considerations: 1. ASCE Exposure D.

2. Buildings over 350-ft.

3. Buildings with positive pressure.

4. Canopies.

5. Hangar facilities and other buildings with side wall openings greater than 10% of a side wall area.

®™ Trademark of The Dow Chemical Company (“Dow”) or an affiliated company of Dow. T2000 MA.09.09.8

Page 9: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

Table 1 - Physical Properties - TIEMPO™+ 2000 TPO Membrane

Physical Propetery Test MethodTypical Values

45 mil (1.14 mm)

Typical Values60 mil (1.52 mm)

ASTM 6878Minimum 80 mil

(2.03 mm)

Breaking Strength ASTM D-751MD 339.94 lbf. (1.5

kN), 335.73 lbf. (1.4 kN)

325.83 lbf, (1.45 kN), 335.73 lbf, (1.5 kN)

220 lbf, (0.98 kN) XMD (Grab Method)XMD

Tear StrengthASTM D-751 Procedure B,

(8”x8” sample)

MD 77.6 lbf. (0.35 kN),163 lbf. (0.73 kN)

89.8 lbf. (0.34 kN),184.6 lbf. (0.82 kN) 55 lbf. (0.25 kN) min.

XMD

Ozone Resistance ASTM D-1149 (70 hrs. @ 100˚F/37.8˚C) 0 Rating 0 Rating No visible cracks

Puncture Resistance

Static D 5602 44 lbf. (20 kg) 44 lbf. (20 kg)N/A

Dynamic D 5635 25 Joules 25 JoulesElongation at

Reinforcement Break

ASTM D-751MD 34.29% 42.41%

15%XMD 33.88% 34.93%

Brittleness ASTM D-2137 @-49°F/-45°C Pass Pass PassWater Apsorption

(max. % weight change)

ASTM D-6878 D-471, (158°F/70°C for 7 Days)

Testing only one side section± 3.0% ± 3.0% ± 3.0%

Heating Age (D 751) (80 mil Test

MethodD 573)

Breaking Strength

MD 365.92 lbf. (1.63 kN) 328.14 lbf. (1.46 kN) 90 % Retention of

Breaking Strength and Elongation at

BreakXMD 319.26 lbf. (1.42

kN) 334.16 lbf, (1.49 kN)

Elongation at Reinforcement

Break

MD 40.68% 39.10%

XMD 30.71% 35.14%60.0% Retention of Tearing Strength at

BreakTearing Strength

MD 150.30 lbf. (0.67 kN) 77.10 lbf. (0.34 kN)

XMD 203.75 lbf. (0.91 kN) 245.0 lbf. (1.09 kN)

Weight Change < 0.1% < 0.1% ± 1.0%Linear Dimension Change (% max.) ASTM D-1204 < 0.1% < 0.1% ± 1.0%

Solar Reflectance (initial) ASTM C-1549 78.4% 80.78% Greater than or

Equal to 0.65

Thermal Emittance ASTM C1371 0.88% 0.86% Greater than or Equal to 0.75

*Thickness (nominal) per ASTM D-751 Test method. MD= Machine Direction XMD= Cross Machine Direction

Page 10: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

Table 2 - ASCE Exposure Classification

ASCE Exposure Classifications Defined American Society of Civil Engineers (ASCE) has defined the roughness of the terrain into four “ground roughness” categories, or “exposures”.

Exposure A This classification applies to large city centers with at least 50 percent of the buildings hav-ing a height in excess of 70 ft. (21.3 m). Use of this exposure category shall be limited to those areas for which representative terrain prevails in the upwind direction for a distance of at least one-half mile (0.8 km) or 10 times the height of the building or structure, whichever is greater. Possible channeling effects or increased velocity pressures due to the building or structure being located in the wake of adjacent buildings shall be taken into account.

Exposure B Urban and suburban areas, wooded areas, or other terrain with numerous closely spaced obstructions having the size of a single-family dwelling or larger. Use of this exposure cat-egory shall be limited to those areas for which representative terrain prevails in an upwind direction for a distance of at least 1,500 ft. (460 m) or 10 times the height of the building or structure, whichever is greater.

Exposure C Open terrain with scattered obstructions having heights generally less than 30 ft. (9.1 m). This category includes flat, open country and grasslands..

Exposure D Flat, unobstructed areas exposed to wind flowing over open water for a distance of at least one mile (1.61 km). This exposure shall apply only to those buildings and other structures exposed to the wind coming from over the water. Exposure D extends inland from the shoreline a distance of 1,500 ft. (460 m) or 10 times the height of the building or structure, whichever is greater.

Page 11: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

Table 3 - System Options Specification Guide • Reference Guide Specification Section 3.03 for additional information on the use of this table. • For building applications not described here, Contact DRS Technical Review Department for assistance.

ASCE EXPOSURE CATEGORY - A & B

Building Height (ft.)

Basic Wind Speed (ASCE- 7) 85 mph 90 mph 100 mph 110 mph 120 mph 130 mph 140 mph

15 A A A A B B C

25 A A A A B B C35 A A A A B B C50 A A A A B C D60 A A A B B C D70 A A A B C D E

ASCE EXPOSURE CATEGORY - C

Building Height (ft.)

Basic Wind Speed (ASCE- 7) 85 mph 90 mph 100 mph 110 mph 120 mph 130 mph 140 mph

15 A A A B B C D25 A A A B C D E35 A A B B C D E50 A A B C D E F

60 A A B C D E F

70 A A B C D E G

ASCE EXPOSURE CATEGORY - D

Building Height (ft.)

Basic Wind Speed (ASCE- 7) 85 mph 90 mph 100 mph 110 mph 120 mph 130 mph 140 mph

15 A A B C C E F25 A A B C D E F35 A A B C D F G50 A B C D E F H60 A B C D E F H70 A B C D E G H

System Options Attachment Guide (Table 4a - 4g) • Reference Guide Specification Section 3.03 for additional information on the use of this table. • See “Notes” Section of Table 4 for additional information.

Page 12: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

• For deck types other than those listed here (i.e. metal roof systems, cementitious woodfiber, gypsum): A fastener pull test is required before a fastening rate can be determined. Contact DRS Technical Review Department for assistance.

Table 4a - (Min.) 22 Gauge Steel Decks System Option

Steel Decking Gauge

Tiempo™+ 2000 Field Sheet

Width

Fastener Spacing

(on-center)

Fastener / Plate

CombinationMinimum Fastener Withdrawal (lbf.)

Field Zone Design Pressure Limitation

(Max. psf)

A-1 22 ga. 8 ft. 18-in. (457mm)

#21 Fastener 3-in. plate 675 (-) 30 psf

B-1 22 ga. 10 ft. 12-in. (305mm)

#15 Fastener 2 3/8-in plate 713 (-) 37.5 psf

C-1 22 ga. 8 ft. 12-in. (305mm)

#21 Fastener 3-in. plate 675 (-) 45 psf

C-2 22 ga. 10 ft. 6-in. (152mm) #15 Fastener 2 3/8-in plate 428 (-) 45 psf

C-3 22 ga. 10 ft. 12-in. (305mm)

#21 Fastener 3-in. plate 855 (-) 45 psf

D-1 22 ga. 10 ft. 6-in. (152mm) #21 Fastener 3-in. plate 499 (-) 52.5 psf

E-1 22 ga. 8 ft. 6-in. (152mm) #15 Fastener 2 3/8-in plate 450 (-) 60 psf

F-1, G-1, H-1 22 ga. 5 ft. 6-in. (152mm) #15 Fastener 2

3/8-in plate 371 (-) 82.5 psf

Table 4b - 24 Gauge Steel Decks

System Option

Steel Decking Gauge

Tiempo™+ 2000 Field Sheet

Width

Fastener Spacing

(on-center)

Fastener / Plate

CombinationMinimum Fastener Withdrawal (lbf.)

Field Zone Design Pressure Limitation

(Max. psf)

A-1 24 ga. 10 ft. 9-in. (229mm) #15 Fastener 2 3/8-in plate 428 (-) 30 psf

C-1 24 ga. 10 ft. 6-in. (152mm) #15 Fastener 2 3/8-in plate 428 (-) 45 psf

C-2 24 ga. 10 ft. 9-in. (229mm) #21 Fastener 3-in. plate 641 (-) 45 psf

A-1 24 ga. 8 ft. 12-in. (305mm)

#15 Fastener 2 3/8-in plate 450 (-) 30 psf

B-1 24 ga. 8 ft. 9-in. (229mm) #15 Fastener 2 3/8-in plate 422 (-) 37.5 psf

B-2 24 ga. 8 ft. 12-in. (305mm)

#21 Fastener 3-in. plate 563 (-) 37.5 psf

Page 13: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

Table 4c - 26 Gauge Steel Decks

System Option

Steel Decking Gauge

Tiempo™+ 2000 Field

Sheet Width

Fastener Spacing

(on-center)

Fastener / Plate

CombinationMinimum Fastener Withdrawal (lbf.)

Field Zone Design Pressure Limitation

(Max. psf)

A-1 26 ga. 8 ft. 9-in. (229mm) #15 Fastener 2 3/8-in plate 338 (-) 30 psf

B-1 26 ga. 8 ft. 6-in. (152mm) #15 Fastener 2 3/8-in plate 281 (-) 37.5 psf

B-2 26 ga. 8 ft. 12-in. (305mm)

#21 Fastener 3-in. plate 563 (-) 37.5 psf

B-3 26 ga. 5 ft. 12-in. (305mm)

#15 Fastener 2 3/8-in plate 338 (-) 37.5 psf

C-1 26 ga. 8 ft. 9-in. (229mm) #21 Fastener 3-in. plate 506.25 (-) 45 psf

Table 4d - Plywood Decks (1/2-in. and 5/8-in.)

System Option

Plywood Thickness

Tiempo™+ 2000 Field

Sheet Width

Fastener Spacing

(on-center)

Fastener / Plate

CombinationMinimum Fastener Withdrawal (lbf.)

Field Zone Design Pressure Limitation

(Max. psf)

A-1 1/2-in. 8 ft. 12-in. (305mm)

#15 Fastener 2 3/8-in plate 450 (-) 30 psf

B-1 1/2-in. 8 ft. 9-in. (152mm) #15 Fastener 2 3/8-in plate 422 (-) 37.5 psf

C-1 1/2-in. 5 ft. 12-in. (305mm)

#15 Fastener 2 3/8-in plate 405 (-) 45 psf

A-1 5/8-in. 8 ft. 12-in. (229mm)

#15 Fastener 2 3/8-in plate 450 (-) 30 psf

B-1 5/8-in. 8 ft. 9-in. (305mm) #15 Fastener 2 3/8-in plate 422 (-) 37.5 psf

C-1, D-1 5/8-in. 5 ft. 12-in. (229mm)

#15 Fastener 2 3/8-in plate 473 (-) 52.5 psf

Table 4e - Min. 3/4-in. Plywood or Wood Plank Decks

System Option

Plywood / Wood Plank Thickness

Tiempo™+ 2000 Field

Sheet Width

Fastener Spacing (on-

center)

Fastener / Plate

CombinationMinimum Fastener Withdrawal (lbf.)

Field Zone Design Pressure Limitation

(Max. psf)

A-1 3/4-in. 10 ft. 12-in. (305mm)

#15 Fastener 2 3/8-in plate 570 (-) 30 psf

B-1 3/4-in. 10 ft. 9-in. (229mm) #15 Fastener 2 3/8-in plate 534 (-) 37.5 psf

B-2 3/4-in. 8 ft. 12-in. (305mm)

#15 Fastener 2 3/8-in plate 563 (-) 37.5 psf

C-1 3/4-in. 8 ft. 9-in. (229mm) #15 Fastener 2 3/8-in plate 506 (-) 45 psf

D-1 3/4-in. 5 ft. 12-in. (229mm)

#15 Fastener 2 3/8-in plate 473 (-) 52.5 psf

Table 4f - Oriented Strand Board (OSB) Wood Decks

Page 14: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

System Option

OSB Panel Thickness

Tiempo™+ 2000 Field Sheet

Width

Fastener Spacing

(on-center)

Fastener / Plate

CombinationMinimum Fastener Withdrawal (lbf.)

Field Zone Design Pressure Limitation

(Max. psf)

A-1 7/16 - 5/8-in. 8 ft. 9-in. (152mm)

#15 Fastener 2 3/8-in plate 338 (-) 30 psf

B-1 7/16 - 5/8-in. 8 ft. 6-in. (152mm)

#15 Fastener 2 3/8-in plate 281 (-) 37.5 psf

B-2 7/16 - 5/8-in. 5 ft. 12-in. (229mm)

#15 Fastener 2 3/8-in plate 338 (-) 37.5 psf

A-1 3/4-in. 8 ft. 12-in. (305mm)

#15 Fastener 2 3/8-in plate 450 (-) 30 psf

B-1 3/4-in. 8 ft. 9-in. (152mm)

#15 Fastener 2 3/8-in plate 422 (-) 37.5 psf

C-1 3/4-in. 5 ft. 12-in. (229mm)

#15 Fastener 2 3/8-in plate 405 (-) 45 psf

Table 4g - Structural Concrete Decks • Fastener Options for Structural Concrete: CD-10 Masonry Anchor (use 7/32-in. pilot hole) or #14 Deck Screw (use 3/16-in. pilot hole)

System Option

Steel Decking Gauge

Tiempo™+ 2000 Field Sheet

Width

Fastener Spacing

(on-center)Seam Plate Diameter

Minimum Fastener Withdrawal (lbf.)

Field Zone Design Pressure Limitation

(Max. psf)

A-1 Min. 2500 psi [17.2 MPa] 8 ft. 18-in.

(457mm) 2 3/8-in. 675 (-) 30 psf

B-1 Min. 2500 psi [17.2 MPa] 10 ft. 12-in.

(305mm) 2 3/8-in. 713 (-) 37.5 psf

C-1 Min. 2500 psi [17.2 MPa] 10 ft. 6-in.

(152mm) 2 3/8-in. 428 (-) 45 psf

Notes (Table 4a - 4g): 1. It is acceptable to use any System Option with a higher Design Pressure Limitation than the minimum

recomended design from Table 3 - System Options Specification Guide. (Example: System Option B may be used in lieu of a System Option A).

2. Seam overlap shall be 6-in. (Reference DRS Detail Drawing DR-624.)

3. Perimeter and Corner zones: Install as described in DRS Guide Specification Section 3.03 Fastening Requirements.

4. Dow 2000 Fastener #21 should be sized to project through steel decking 1-in. (25mm). Dow 2000 Fastener #15 should be sized to project through steel decking 3/4-in. (19 mm) and 1/2-in. (13mm) for wood decking less than 1-in. (25 mm) thickness. Fasteners should penetrate structural concrete 1-1/4-in. (32mm) for a pointed screw and 1-in. (25mm) for the CD-10 anchor.

5. Attachment recommendations are for DRS Warranty Issuance only and may not comply with all Factory Mutual Global (FMG) requirements. Refer to applicable FMG Loss Prevention Data Sheets, FMG approvals database and/or contact DRS Technical Review Dept.

[End]

Page 15: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

Appendix 1 (page 1 of 2)

DOW ROOFING SYSTEMS FASTENER SELECTION GUIDETIEMPO™+ 2000 Product Line

QuickTime™ and aTIFF (Uncompressed) decompressorare needed to see this picture. QuickTime™ and aTIFF (Uncompressed) decompressorare needed to see this picture. QuickTime™ and aTIFF (Uncompressed) decompressorare needed to see this picture. QuickTime™ and aTIFF (Uncompressed) decompressorare needed to see this picture.

PRODUCT DESCRIPTION PRODUCT DESCRIPTION PRODUCT DESCRIPTION PRODUCT DESCRIPTIONDow 2000 Fastener #14 Dow 2000 Fastener # 12 Dow 2000 Fastener #21 Dow 2000 Fastener #15

Dow 2000 Fastener #14is for insulation attachment.Use with Dow 2000Insulation Plate 3-inch(76.2-mm).

Dow 2000 Fastener #12is for insulation attachment.Use with Dow 2000Insulation Plate 3-inch(76.2-mm).

Dow 2000 Fastener #21 isfor membrane attachmentfeaturing a drill point, anda deep buttress single leadthread. Use with Dow 2000Metal Seam Plate 3-in.(76.2-mm).

Dow 2000 Fastener #15 isfor membrane attachment.Use with Dow 2000 MetalSeam Plate 2 3/8-in (60-mm).

SIZE AVAILABLE: SIZE AVAILABLE: SIZE AVAILABLE: SIZE AVAILABLE:11/2, 2, 3, 4, 5 - 8 -in.(38, 50, 75, 100, 125 - 200- mm) in 1-inch (25-mm)increments

1 5/8, 21/4, 2 7/8, 31/4, 33/4,41/2, (41, 57, 73, 85, 95,114- mm) 5 - 8-inch (125- 200 -mm) in 1-inch (25-mm) increments

2 - 8-inch (50 - 200-mm) in1-inch (25-mm) increments

1¼, 2 - 9, 10, 12, 14 and 16 -inch (30, 50 - 229, 250, 300, 355 and 406-mm)

DECK TYPE: DECK TYPE: DECK TYPE: DECK TYPE:

Wood and 18 to 26 (0.30 - 0.55 mm) gauge steel.

Wood and 18 to 26 (1.3 - 0.55-mm) gauge steel

FM approved minimum 22 gauge steel* [*Test drill to check for installability on 18 and 20 (1.3 - 2.5-mm) gauge steel decks prior to committing to a project].

18-12 (1.3 - 2.5-mm) gauge steel

PACKAGING: PACKAGING: PACKAGING: PACKAGING:

1¼ - 6 -inch (30 - 150- mm): 1000/bucket 7, 8 – inch(175, 200- mm): 500/bucket

1 5/8 - 4½ and 5 - 8 inch (41 - 114 and 125-200 - mm): 1000/bucket

2 and 3-inch (50 and 75- mm): 1000/bucket 4 - 6-inch (100 - 150-mm): 500/bucket 7 and 8-inch (175 and 200- mm): 250/bucket

1¼ (30-mm) 2 -5 -inch (50- 125mm): 1000/box 6, 7, 8 , 9, 10, 12, 14-inch (150, 175, 200, 229, 250, 300, 355-mm): 500/box and 16-inch (406-mm)250/box

PRODUCT DESCRIPTION PRODUCT DESCRIPTION PRODUCT DESCRIPTION

Dow 2000 Insulation Plate 3-in. Dow 2000 Metal Seam Plate 3-in. Dow 2000 Metal Seam Plate 2 3/8-in.

Dow 2000 Insulation Plate 3-in. is a Galvalume-coated, metal insulation plate for use with Dow 2000 Insulation Fastener #12, Dow 2000 Fastener #14 or Dow 2000 Concrete Deck Fastener.

Dow 2000 Metal Seam Plate 3-in. for membrane attachment. Use with a Dow 2000 Fastener #21.

Dow 2000 Metal Seam Plate 2 3/8-in. (60 mm) features a patented “Eye Hook” design. Can be used with Dow 2000 Fastener #15 or the Dow 2000 Concrete Fastener.

SIZE AVAILABLE: SIZE AVAILABLE: SIZE AVAILABLE:

3-inch (76-mm) diameter 3-inch (76-mm) diameter 2 3/8-inch (60-mm) diameter

PACKAGING PACKAGING PACKAGING

1,000/box 500/bucket 1,000/bucket

Page 16: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

Appendix 1 (page 2 of 2)

DOW ROOFING SYSTEMS FASTENER SELECTION GUIDE TIEMPO™+ 2000 Product Line

PRODUCT DESCRIPTION PRODUCT DESCRIPTIONDow 2000

Insulation Fastener (PIF)Dow 2000

Fastener #15

Dow 2000 Preassembled Insulation Fastener (PIF) is for insulation attachment and it is comprised of a #12 fastener with a 3-inch (75-mm) polymer locking plate.

Dow 2000 Preassembled Fastener #15 is for membrane attachment and is comprised of a Dow 2000 Fastener #15 and a Dow 2000 Metal Seam Plate 2 3/8-in.

SIZE AVAILABLE: SIZE AVAILABLE: 21/4, 2 7/8, 3, 31/4, 4 - 10 -inch (57, 73, 76, 83, 102 - 254 mm) in 1-inch (25 mm) increments

2 - 8-inch (50 - 200 mm) in 1-inch (25 mm) increments

DECK TYPE: DECK TYPE: Wood and 18 to 26 (1.3 - 0.55 -mm) gauge steel. Structural concrete (pre-drilling required), wood and 18 to

26 gauge (1.3 - 0.55-mm) steel. PACKAGING: PACKAGING:

21/4 - 8-inch (57 - 200-mm): 500/box 9, 10-inch (229- 254-mm): 250/box

2-inch (50 mm): 500/box 3 - 8-inch (76 - 200-mm): 250/box

PRODUCT DESCRIPTION PRODUCT DESCRIPTION PRODUCT DESCRIPTION

Dow 2000 Concrete Fastener Dow 2000 Masonry Anchor Dow 2000 Aluminum Termination Bar

Non-threaded hammer-in fastener for membrane and insulation attachment.

Hammer-in-type expansion fastener for securing termination bar.

Aluminum bar for use in membrane termination. Refer to specific DRS details.

SIZE AVAILABLE: SIZE AVAILABLE: SIZE AVAILABLE:

21/4, 2 7/8, 31/4, 3 3/4 -inch (57, 73, 83, 95mm), 4 - 10-inch (100-250-mm) in 1-inch (25-mm) increments

1/4-inch (6-mm) diameter x 11/4-inch (30-mm) length

1-inch (25-mm) wide, 10-ft. (3-m) long 6-inch (150-mm )o/c slotted, punched

DECK TYPE: FOR USE IN: FOR USE IN:

Structural concrete Concrete and masonry Membrane Terminations

PACKAGING PACKAGING PACKAGING

21/4 - 8-inch (57 - 200-mm): 500/box 9, 10-inch (228,254 -mm): 250/box

1,000/box 500-ft. (152-m)/tube 50 pcs,10-ft. (3-m) long

Appendix 2-M(Page 1 of 2)

Page 17: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

Approved Insulation List and Fastening Rates for Mechanically Attached, Ballasted and VRS Systems

Introduction

This is a listing of insulation and cover board products acceptable for use with DRS Mechanically Attached, Ballasted and VRS Roofing Systems. Each listing shows specific manufacturer and product names, indicates which products are approved for retrofit applications and which are eligible for DRS warranty coverage. In addition, fastening recommendations for each product type are shown. Please note the variations in required insulation pre-securement and/or cover board requirements as it relates to insulation type and thickness.

Note: It is not within the scope of this chart to provide information relating to building code compliance, or specific Factory Mutual Global (FMG) or Underwriters Laboratories (UL), Inc. approvals. FMG, UL and/or building code requirements for insula-tion type, thermal barrier requirements, minimum/maximum insulation thickness and product pre-securement rates may differ from the DRS requirements shown herein. Refer to the current edition of the FMG Approval Guide, the UL Roofing Materials and Systems Directory and/or the UL Fire Resistance Directory for complete information, or contact the DRS Technical Review Department DRS recommends that the building Department be consulted to ensure compliance with local requirements.

General Recommendations

1. Refer to the product manufacturer’s literature to confirm minimum allowable thickness required to span steel deck flutes, etc.

2. Adjacent insulation/cover boards shall be installed as closely as possible with no gaps or offsets greater than 1/4 inch.

3. Since many insulation systems provide taper to 1/2 inch thickness only, a tapered edging of DRS-approved insulation is recommended to be installed at all such transitions.

4. Approved insulation products shall be installed with the longest dimension of the board perpendicular to the direction of mechanically secured membrane lap seams whenever possible. Insulation end joints shall be staggered.

5. Insulation pre-securement fasteners/plates shall be installed at the rates shown herein and located on each board as shown in DRS Detail Drawing DR-622.

6. For applicable substrates (structural concrete, gypsum, cementitious woodfiber) DRS permits insulation boards to be adhered using a DRS-supplied insulation adhesive or hot steep asphalt (ASTM D312, type III and IV). The insulation manufacturer, adhesive manufacturer and DRS Technical Services must specifically approve such applications. When using insulation adhesives/asphalt to secure insulation, the insulation board size can not exceed 4-ft. X 4-ft.

7. Consult the DRS Technical Review Department at (877)788-8324 if the insulation manufacturer’s current installation/ securement instructions conflict with information published herein.

Rev: 091509

Appendix 2-M (page 2 of 2)

Page 18: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

Approved Insulation List and Fastening Ratesfor Mechanically Attached, Ballasted and VRS Systems

Insulation Type

ApprovedManufacturers

ApprovedProduct

Approved forRetrofit

Applications

Approved for DRS

“Total System” Warranty

TIEMPO™+ 2000TPO

Extruded Polystyrene

(XPS)

TheDow Chemical

Company

STYROFOAM™ Yes(See Note 1) Yes

4 per 4’ x 8’ bd.4 per 2’ x 8’ bd.

RECOVERMATE™ CR(fanfold)

Recover Only(See Note 1)

15 per 4’ x 50’ area

Gypsum-Board

Georgia-Pacific Corp.

1/4” DensDeck® (See Note 3)Yes 5 per 4’ x 8’ bd.

1/2” DensDeck® Yes

USG Corp.1/4” Securock® (See Note 3)

Yes 5 per 4’ x 8’ bd.1/2” Securock® Yes

PolyisocyanurateDow

Roofing Systems

TERMICO™Polyisocyanurate

Yes Yes 5 per 4’ x 8’ bd.4 per 4’ x 4’ bd.TERMICO™ Iso 3000

TERMICO™ HP-FR

Wood Fiberboard

Georgia-Pacific Corp. High Density Roof Fiberboard

N/A N/A 6 per 4’ x 8’ bd.4 per 4’ x 4’ bd.

IKOHigh DensitySheathing /

Roofboard Panels

Temple-Inland FiberBase®HD1, HD6

Expanded Polystyrene

(EPS)

Premier Industries

(Insulfoam)

Type VIII (1.25 pcf) Yes(See Note 1)

Yes

OverlaymentRequired

(See Note 2)Type VIII (1.25 pcf) with

“Secure-Ply” overlay 6 per 4’ x 8’ bd.

Type II (1.50 pcf) Recover Only(See Note 1)

6 per 4’ x 8’ bd.R-TECH (fanfold) 1/2-in., Type

VIII (1.25 pcf)15 per 4’ x 50’

area

NOTES:

1. A separation sheet/layer may be required when using a polystyrene product directly over coal tar pitch B.U.R. based roof systems. Consult the insulation manufacturer for specific requirements.

2. Due to the lower compressive strength of Type VIII (1.25 pcf nominal density) expanded polystyrene (EPS), DRS requires this product to be overlaid with an approved polyisocyanurate insulation or cover board (i.e. DensDeck® or Securock® for Mechanically Attached, Fully Adhered, GardenTopTM and some VRS Roofing Systems. Type I (1.0 pcf nominal density) EPS is acceptable for use under stone/paver ballasted systems only.

3. This product is not approved as a recovery layer directly over gravel-surfaced B.U.R. roof systems. It is approved for use over existing single-ply and smooth or mineral surfaced roof systems.

Rev: 091509

®DensDeck is a registered trademark of Georga-Pacific.®Securock is a registered trademark of USG Corporation.

®FiberBase is a registered trademark of Temple-Inland.

Appendix - 3(Rev. 091809)

Additional Requirements for

Page 19: CSI Division 7 Specification - Sweetssweets.construction.com/swts_content_files/2414/389315.doc · Web viewCSI Division 7 Guide Specifications TIEMPO + 2000 TPO MEMBRANE MECHANICALLY

20-year Warranty Systems

General

The information presented here is to be used in conjunction with published Dow Roofing System Guide Specifications. Twenty(20) year Labor and Material and Total System warranty types (with or without the “NDL” option) are available from DRS forinstallations that meet the criteria shown below. Consult the DRS Technical Review Department prior to committing to such anapplication to ensure warranty eligibility.

1. Membrane: 60-mil (minimum thickness) TIEMPO™+ 2000 TPO Roofing membranes.

2. System Types: Mechanically Attached, Fully Adhered, GardenTop™ and certain ballasted systems. Note that the Vented Roofing System (VRS) is not eligible for 20-year coverage.

3. Construction Type: New construction and complete tear-offs are eligible for a 20-year warranty. Some partial tear-offs and re-cover systems may also be eligible, however, it is required to consult the Dow Technical Review Department for approval prior to committing to such an application. A moisture survey will be required for re-cover systems and in all cases, any wet existing insulation must be removed and replaced.

4. Approved Deck Types: 22 gauge steel (or heavier), structural concrete or wood (plank or plywood) 3/4-in. min. thickness.

5. Acceptable Insulation/Substrate: Must be DRS-supplied (purchased through DRS) and installed per the appropriate DRS Guide Specification.

6. Positive Slope: Drainage system must effectively prevent ponding water as defined by the NRCA (48-hr. ponding guideline).

7. Warranty Request: Request for Warranty forms must be submitted and approved by Dow Technical Services prior to job start.

8. Applicator Qualifications: First-time applicators must arrange for job start-up assistance from their Dow Field Technical Representative (a minimum two week lead time is required for scheduling).

9. Warranty Issuance: 20-year warranty systems are not eligible for “Early Warranty” release and must be inspected by a Dow Field Technical Representative prior to issuance.

10. Reinspection: 20-year warranty projects which are rated as “good” (or lower) at job completion will be automatically re-inspected at 18 months.

Please contact the DRS Technical Services Department at (877) 788-8324 with any questions.