CS 1000/3000 Operating Messages

190
Toc-1 IM 33S02H10-01E CONTENTS 15th Edition : Dec.10,2007-00 CS 1000/CS 3000 Operating Messages IM 33S02H10-01E 15th Edition 1. Overview ................................................................................................. 1-1 1.1 Message Types, Numbering System, and Output Destination ..................... 1-2 1.2 Operation Window Message Display Format ................................................ 1-3 1.3 Message Printout Format ............................................................................... 1-4 2. Message Output Details ......................................................................... 2-1 2.1 FCS Error Generation and Recovery Messages (Message Nos. 0001 to 0099) .......................................................................... 2-2 No.0001 Control station reset start .................................................................. 2-2 No.0003 Control station automatic reset start .................................................. 2-2 No.0005 Control station power on initialization cold start ................................. 2-3 No.0007 Control station power on restart ........................................................ 2-3 No.0009 Control station control right transfer .................................................. 2-3 No.0011 Control station failure information ...................................................... 2-4 No.0013 Control station AC power failure ........................................................ 2-6 No.0015 CPU internal clock self-diagnostic testing error ................................. 2-6 No.0017 CPU card ROM check sum error ....................................................... 2-7 No.0019 Control Station Task Error ................................................................. 2-7 No.0021 Control station task internal error ...................................................... 2-7 No.0023 Function block fatal error ................................................................... 2-8 No.0025 Function control word error ............................................................... 2-8 No.0027 Function block record information error ............................................. 2-9 No.0029 HIS station communication failure ..................................................... 2-9 No.0030 HIS station communication recovery ................................................. 2-9 No.0033 Online downloading abnormal end .................................................. 2-10 No.0035 General-purpose calculation block calculation error ........................ 2-12 No.0036 General-purpose calculation block calculation error recovery .......... 2-12 No.0037 Block one-shot start error ................................................................ 2-13 No.0038 Recovery from block one-shot starting error .................................... 2-13 No.0039 Process I/O error ............................................................................ 2-13 No.0040 Recovery from process I/O error ..................................................... 2-14 No.0041 Control Station Cabinet Fan Alarm .................................................. 2-14 No.0042 Control Station Cabinet Fan Alarm Recovery .................................. 2-14 No.0043 Control Station Cabinet Temperature Alarm .................................... 2-15 No.0044 Control Station Cabinet Temperature Alarm Recovery .................... 2-15

description

Operating Messages

Transcript of CS 1000/3000 Operating Messages

Page 1: CS 1000/3000 Operating Messages

Toc-1

IM 33S02H10-01E

CONTENTS

15th Edition : Dec.10,2007-00

CS 1000/CS 3000Operating Messages

IM 33S02H10-01E 15th Edition

1. Overview ................................................................................................. 1-11.1 Message Types, Numbering System, and Output Destination ..................... 1-2

1.2 Operation Window Message Display Format ................................................ 1-3

1.3 Message Printout Format ............................................................................... 1-4

2. Message Output Details ......................................................................... 2-12.1 FCS Error Generation and Recovery Messages

(Message Nos. 0001 to 0099) .......................................................................... 2-2

No.0001 Control station reset start .................................................................. 2-2

No.0003 Control station automatic reset start .................................................. 2-2

No.0005 Control station power on initialization cold start ................................. 2-3

No.0007 Control station power on restart ........................................................ 2-3

No.0009 Control station control right transfer .................................................. 2-3

No.0011 Control station failure information ...................................................... 2-4

No.0013 Control station AC power failure ........................................................ 2-6

No.0015 CPU internal clock self-diagnostic testing error ................................. 2-6

No.0017 CPU card ROM check sum error ....................................................... 2-7

No.0019 Control Station Task Error ................................................................. 2-7

No.0021 Control station task internal error ...................................................... 2-7

No.0023 Function block fatal error ................................................................... 2-8

No.0025 Function control word error ............................................................... 2-8

No.0027 Function block record information error ............................................. 2-9

No.0029 HIS station communication failure ..................................................... 2-9

No.0030 HIS station communication recovery ................................................. 2-9

No.0033 Online downloading abnormal end .................................................. 2-10

No.0035 General-purpose calculation block calculation error ........................ 2-12

No.0036 General-purpose calculation block calculation error recovery .......... 2-12

No.0037 Block one-shot start error ................................................................ 2-13

No.0038 Recovery from block one-shot starting error .................................... 2-13

No.0039 Process I/O error ............................................................................ 2-13

No.0040 Recovery from process I/O error ..................................................... 2-14

No.0041 Control Station Cabinet Fan Alarm .................................................. 2-14

No.0042 Control Station Cabinet Fan Alarm Recovery .................................. 2-14

No.0043 Control Station Cabinet Temperature Alarm .................................... 2-15

No.0044 Control Station Cabinet Temperature Alarm Recovery .................... 2-15

Page 2: CS 1000/3000 Operating Messages

IM 33S02H10-01E

Toc-2

13th Edition : Dec.26,2005-00

No.0045 Control station power supply unit alarm........................................... 2-16

No.0046 Control station power supply unit alarm recovery ............................ 2-16

No.0047 Control unit battery alarm ................................................................ 2-17

No.0048 Control unit battery alarm recovery ................................................. 2-17

No.0051 Control Station I/O Extension Cabinet Fan Alarm ............................ 2-17

No.0052 Control Station I/O Extension Cabinet Fan Alarm Recovery ............ 2-18

No.0053 Control Station I/O Extension Cabinet Temperature Alarm .............. 2-18

No.0054 Control Station I/O Extension Cabinet Temperature AlarmRecovery ........................................................................................ 2-18

No.0055 Online downloading communication same frame receivedinformation...................................................................................... 2-18

No.0057 Online downloading error information ............................................. 2-19

No.0059 Node Power Recovery Notice ......................................................... 2-19

No.0061 Control Unit RIO or IO Bus Interface Card Error .............................. 2-20

No.0063 RIO or ESB Bus Error ..................................................................... 2-20

No.0064 Recovery of RIO or ESB bus........................................................... 2-21

No.0065 Node RIO or IO Bus Interface Card Error ........................................ 2-22

No.0066 RIO or IO Bus Node Interface Card Recovery ................................. 2-22

No.0067 Node Power Supply Card Error ....................................................... 2-23

No.0068 Node Power Supply Card Recovery ................................................ 2-23

No.0069 Error before database downloading to I/O module .......................... 2-24

No.0073 Error in bus connected between I/O unit and CPU unit .................... 2-24

No.0074 Normal recovery of bus connecting I/O unit and CPU unit ............... 2-24

No.0075 I/O module error (for AAM/APM) ..................................................... 2-25

No.0076 I/O module normal recovery (for AAM/APM) ................................... 2-25

No.0077 I/O module database error (for AAM/APM) ...................................... 2-25

No.0079 I/O module communication error (for AAM/APM) ............................ 2-25

No.0080 I/O module communication error recovery (for AAM/APM) .............. 2-26

No.0081 I/O Module Error (ADM/AMM, FIO related) ..................................... 2-26

No.0082 I/O Module Recovery (ADM/AMM, FIO related) .............................. 2-28

No.0083 I/O Module Database Error (ADM/AMM, FIO related) ..................... 2-28

No.0085 I/O Module Communication Error (ADM/AMM, FIO related) ............ 2-29

No.0086 I/O Module Communication Recovery (ADM/AMM, FIO related) ..... 2-29

No.0087 Node Error ...................................................................................... 2-30

No.0088 Node Recovery ............................................................................... 2-30

No.0089 Subsystem Communication Error ................................................... 2-31

No.0090 Subsystem Communication Recovery ............................................ 2-33

No.0091 Failing Node Housekeeping Unit in the I/O Expansion Cabinet ....... 2-33

No.0092 Node Housekeeping Unit in the I/O Expansion Cabinet Recovery ... 2-33

No.0093 Control Unit Housekeeping Unit Error ............................................. 2-33

No.0094 Control Unit Housekeeping Unit Error Recovery ............................. 2-34

No.0098 System alarm normal recovery ....................................................... 2-34

No.0099 System alarm ................................................................................. 2-35

Page 3: CS 1000/3000 Operating Messages

Toc-3

IM 33S02H10-01E 13th Edition : Dec.26,2005-00

2.2 Control Station Messages of Other Systems(Message Nos. 0101 to 0198) ........................................................................ 2-36

No.0101 Control Station System Alarm ......................................................... 2-36

No.0103 Control Station System Alarm ......................................................... 2-36

No.0105 Upload Error ................................................................................... 2-36

No.0106 Upload Recovery ............................................................................ 2-36

No.0107 CI-Bus Failure ................................................................................. 2-37

No.0108 CI-Bus Recovery ............................................................................ 2-37

No.0109 Nest Common Card Error ............................................................... 2-37

No.0110 Nest Common Card Error Recovery ............................................... 2-37

No.0111 CI-Bus Error ................................................................................... 2-38

No.0113 BCU FC1 Failure ............................................................................ 2-38

No.0114 BCU FC1 Recovery ........................................................................ 2-38

No.0115 Control Station Duplex Control Section Error .................................. 2-38

No.0116 Control Station Duplex Control Section Error Recovery .................. 2-39

No.0117 Control Station Equalize Error ......................................................... 2-39

No.0118 Control Station Equalize Error Recovery ......................................... 2-39

No.0119 Control Station Self-diagnosis Error ................................................ 2-39

No.0120 Control Station Self-diagnosis Error Recovery ................................ 2-40

No.0121 Control Station SI-Bus Communication Card Error .......................... 2-40

No.0122 Control Station SI11 Communication Card Error Recovery ............. 2-40

No.0123 Control station Nest Common Card Error ........................................ 2-40

No.0124 Control Station Nest Common Card Error Recovery ....................... 2-40

No.0125 Control Station SI-Bus Error ............................................................ 2-41

No.0126 Control Station SI Bus Error Recovery ............................................ 2-41

No.0127 Control Station SI11 Communication Card Fuse Blow Out .............. 2-41

No.0128 Control Station SI11 Communication Card Fuse Recovery ............. 2-41

No.0129 Control Station Nest Common Card Fuse Blow Out ........................ 2-41

No.0130 Control Station Nest Common Card Fuse Recovery ....................... 2-42

No.0131 Control Station AC Power Failure .................................................... 2-42

No.0133 Control Station AC Power Failure .................................................... 2-42

No.0135 Control Station Task Abnormal Termination or Termination byException Interrupt ......................................................................... 2-42

No.0137 Control station Power ON. (Hot Start) ............................................. 2-42

No.0139 Control station Power ON. (Cold Start) ........................................... 2-43

No.0141 Control Station Reset Start ............................................................. 2-43

No.0143 EMCS/EMCD Reset Start ............................................................... 2-43

No.0151 Control Station I/O Card Error ......................................................... 2-43

No.0152 Control Station I/O Card Error Recovery ......................................... 2-44

No.0153 Control Station I/O Card Error ......................................................... 2-44

No.0154 Control Station I/O Card Error Recovery ......................................... 2-44

No.0155 Control Station I/O Nest Power Supply Card Error .......................... 2-44

No.0156 Control Station I/O Nest Power Supply Card Error Recovery .......... 2-45

Page 4: CS 1000/3000 Operating Messages

IM 33S02H10-01E

Toc-4

14th Edition : Dec.26,2006-00

No.0157 Control Station Power Supply Card Error ........................................ 2-45

No.0158 Control Station Power Supply Card Error Recovery ........................ 2-45

No.0161 Control Unit Self-diagnostic Error .................................................... 2-45

No.0162 Control Unit Self-diagnostic Error Recovery .................................... 2-45

No.0163 RL Bus Failure ................................................................................ 2-46

No.0164 RL Bus Recovery ............................................................................ 2-46

No.0165 �XL, EFUS/EFUD Fan Alarm ......................................................... 2-46

No.0166 �XL, EFUS/EFUD Fan Alarm Recovery .......................................... 2-46

No.0167 Abnormal Communication with Subsystem ..................................... 2-47

No.0168 Recovery of Communication with Subsystem ................................. 2-47

No.0171 Control Station/CFGW Station System Alarm ................................. 2-48

No.0173 Cabinet Environment Error ............................................................. 2-49

No.0174 Cabinet Environment Recovery ...................................................... 2-50

No.0175 Control Station CPU Card Memory Self-diagnostic Error ................ 2-50

No.0177 Control Station CPU Card Memory Self-diagnostic Error ................ 2-50

No.0179 Control Station CPU Card Realtime Clock Error .............................. 2-50

No.0181 Control Station Control Right Transfer ............................................. 2-51

No.0183 Error in Batch System ..................................................................... 2-51

No.0185 Duplexed Control Station Control Error ........................................... 2-51

No.0187 Duplexed Control Station Duplexity Control Section Power Error .... 2-51

No.0189 SEBOL Internal Error ...................................................................... 2-52

No.0191 SEBOL Error ................................................................................... 2-52

No.0195 Application System Alarm ............................................................... 2-52

No.0196 Application System Alarm Recovery ............................................... 2-52

No.0197 Application System Alarm ............................................................... 2-53

No.0198 Application System Alarm Recovery ............................................... 2-53

2.3 HIS System Status Messages (Message Nos. 0201 to 0251) ...................... 2-54

No.0201 Control bus interface card error ....................................................... 2-54

No.0203 Control bus communication circuit error .......................................... 2-54

No.0204 Control bus communication circuit recovery .................................... 2-54

No.0207 Program terminated in an abnormal state ....................................... 2-55

No.0209 Program execution error ................................................................. 2-55

No.0211 HIS temperature abnormal .............................................................. 2-55

No.0213 HIS temperature abnormality sustained .......................................... 2-55

No.0214 HIS temperature returned to normal ................................................ 2-56

No.0215 HIS fan abnormal ............................................................................ 2-56

No.0216 HIS fan recovered ........................................................................... 2-56

No.0217 Hard Disk Error Detected ................................................................ 2-57

No.0219 System error on Touch Panel function ............................................. 2-57

No.0225 UPS Diagnosis Error ....................................................................... 2-57

No.0227 UPS power supply failure ................................................................ 2-58

No.0228 HIS power supply recovered ........................................................... 2-58

Page 5: CS 1000/3000 Operating Messages

Toc-5

IM 33S02H10-01E 14th Edition : Dec.26,2006-00

No.0229 Run HIS Shutdown Sequence Due to Power Supply Failure ........... 2-58

No.0231 HIS shutdown ................................................................................. 2-58

No.0236 HIS start ......................................................................................... 2-58

No.0238 Virtual HIS test start ........................................................................ 2-58

No.0239 HIS temperature sensor fails ........................................................... 2-59

No.0240 HIS temperature sensor recovered ................................................. 2-59

No.0251 HIS system stop by WDT time up .................................................... 2-59

2.4 Communication Related Messages (Message Nos. 0301 to 0397) ............. 2-60

No.0301 V/VL net communication error ......................................................... 2-60

No.0303 Station failure .................................................................................. 2-63

No.0304 Station recovery .............................................................................. 2-63

No.0305 Control bus failure ........................................................................... 2-63

No.0306 Control bus recovery ....................................................................... 2-63

No.0307 Network communication error ......................................................... 2-63

No.0308 Network communication recovery ................................................... 2-64

No.0311 HIS communication error ................................................................ 2-64

No.0321 HF/RL Bus Communication Failure ................................................. 2-64

No.0322 HF/RL Bus Communication Recovery ............................................. 2-64

No.0323 HF/RL Bus Communication Error .................................................... 2-65

No.0324 Control Rights Switching of HF/RL Bus DuplexedCommunication Card ...................................................................... 2-67

No.0325 DataBase Downloading Error ......................................................... 2-67

No.0326 DataBase Download Completion .................................................... 2-68

No.0327 Error in Conventional Bus Duplexed Communication Card ............. 2-68

No.0328 Conventional Bus Duplexed Communication Card Stand-by ........... 2-68

No.0329 Other Error Occurred on Bus Converter .......................................... 2-68

No.0330 Time adjustment ............................................................................. 2-68

No.0331 Network time error .......................................................................... 2-69

No.0332 Time Setting Master Right Acquisition ............................................. 2-69

No.0334 Time Setting Master Right Release ................................................. 2-69

No.0340 Bus Converter Low-order V net in the Control State ........................ 2-69

No.0341 Bus Converter Communication Failure ........................................... 2-69

No.0342 Bus Converter Low-order V net in the Standby State ...................... 2-69

No.0343 Bus Converter Communications Card Fatal Error ........................... 2-70

No.0345 Bus Converter Communications LoopBack Card Error ................... 2-72

No.0346 Time adjustment between domain .................................................. 2-72

No.0350 Station Database Loaded by the Bus Converter .............................. 2-72

No.0352 The communication excessively is demanded ofthe ABC bus converter .................................................................... 2-72

No.0353 Start SIOS ...................................................................................... 2-73

No.0355 SIOS Starting Error ......................................................................... 2-73

No.0356 SIOS online downloading successfully complete ............................ 2-75

No.0357 SIOS online downloading ended with errors .................................... 2-75

Page 6: CS 1000/3000 Operating Messages

IM 33S02H10-01E

Toc-6

14th Edition : Dec.26,2006-00

No.0360 OPC Communication Recovered .................................................... 2-76

No.0361 OPC Communication Error ............................................................. 2-76

No.0363 SIOS Task Error .............................................................................. 2-76

No.0365 SIOS Task Warning......................................................................... 2-76

No.0367 SIOS Station FAIL........................................................................... 2-77

No.0390 Database equalization to the Exaopc station completed ................. 2-77

No.0391 Database equalization to the Exaopc station not completed ............ 2-77

No.0393 Restart request of the Exaopc station ............................................. 2-77

No.0394 Downloading database into the Exaopc station completed .............. 2-77

No.0395 Downloading database into the Exaopc station not completed ........ 2-78

No.0397 Excessive number of taglists in the Exaopc station ......................... 2-78

2.5 Control Station Status Change Related Messages(Message Nos. 0400 to 0491) ........................................................................ 2-79

No.0400 Duplexed Control Station Control Status ......................................... 2-79

No.0402 Duplexed Control Station Ready Status .......................................... 2-79

No.0406 Duplexed Control Station Duplexity Controller Power Recovery ...... 2-79

No.0408 CFCU2 Backup .............................................................................. 2-79

No.0410 CFCU2 Recovery ........................................................................... 2-80

No.0412 CIU Backup .................................................................................... 2-80

No.0414 CIU Recovery ................................................................................. 2-80

No.0416 CFCU2/UFCH MAC2/PAC Card Out-of-Service ............................. 2-80

No.0418 CFCU2/UFCH MAC2 Card In-Service ............................................ 2-80

No.0420 Control Station MAC2/PAC or CFCDE MAC3 Out-of-Service .......... 2-81

No.0422 Control Station MAC2/PAC or EFCE/CFCDE MAC3 In-Service ...... 2-81

No.0424 Duplexed Control Station Control Unit Standby State ...................... 2-81

No.0430 Control Station All Program Copy .................................................... 2-81

No.0450 Control station control side program database copy tostandby side ................................................................................... 2-82

No.0451 Control station control side ready .................................................... 2-82

No.0452 Control station standby side ready .................................................. 2-82

No.0453 RIO bus communication card or IO bus interface card is ready toControl ............................................................................................ 2-83

No.0454 The RIO bus communication card or IO bus interface card isready to Standby............................................................................. 2-83

No.0455 Node Maintenance Information ....................................................... 2-83

No.0456 Node Maintenance Release Information ......................................... 2-83

No.0457 I/O module service side notified (for AAM/APM) .............................. 2-83

No.0458 I/O module out service notified (for AAM/APM) ............................... 2-83

No.0459 The I/O Module Service Ready (ADM/AMM, FIO related) ............... 2-84

No.0460 The I/O Module Service Stopped (ADM/AMM, FIO related) ............ 2-84

No.0461 Node RIO Bus Communication Card Maintenance Information ....... 2-84

No.0462 Node RIO Bus Communication Card Maintenance Release ........... 2-85

No.0471 Online downloading normal end ...................................................... 2-85

No.0474 Tag list double-defined error notification .......................................... 2-85

Page 7: CS 1000/3000 Operating Messages

Toc-7

IM 33S02H10-01E 14th Edition : Dec.26,2006-00

No.0475 IOM Database Downloading Start ................................................... 2-86

No.0476 IOM Database Downloading Completed ......................................... 2-86

No.0477 IOM Database Downloading Aborted .............................................. 2-87

No.0478 Tuning parameters save normal end ............................................... 2-88

No.0479 Tuning parameters save abnormal end ........................................... 2-88

No.0480 Periodic processing overload .......................................................... 2-88

No.0482 Tuning parameters save start successful ........................................ 2-88

No.0483 Tuning parameters save abnormal start failed ................................. 2-89

No.0485 SFC block download error .............................................................. 2-89

No.0486 Recovery from FIO function error .................................................... 2-89

No.0487 FIO function error ............................................................................ 2-90

No.0490 FCS Batch Management Ready ..................................................... 2-91

No.0491 HART Device Status ....................................................................... 2-91

2.6 Operation Command and Operation Record Messages(Message Nos. 0501 to 0692) ........................................................................ 2-92

No.0501 Database equalize request ............................................................. 2-92

No.0502 Database equalization completed normally ..................................... 2-92

No.0503 Database equalization ended with error .......................................... 2-92

No.0505 HIS restart request .......................................................................... 2-92

No.0506 Delete Database file ....................................................................... 2-92

No.0507 Computer Reset Start Request ....................................................... 2-93

No.0509 System Configuration Warning ....................................................... 2-93

No.0510 Database download ........................................................................ 2-93

No.0511 Database download error ................................................................ 2-93

No.0513 DataBase of the project not relevant to the executing project .......... 2-94

No.0514 Operation and monitoring function database change ...................... 2-94

No.0515 Operation and monitoring function database change error .............. 2-94

No.0517 Number of Registered Tags Overflow.............................................. 2-94

No.0519 Duplication of tag names ................................................................ 2-94

No.0602 Control station all program copy operation ...................................... 2-95

No.0603 Control station system reserve operation ........................................ 2-95

No.0604 Control station system release operation ........................................ 2-95

No.0605 Control station stopped ................................................................... 2-95

No.0606 Control station started ..................................................................... 2-95

No.0607 Program loading to I/O module started ............................................ 2-95

No.0608 Control station tuning parameters save ........................................... 2-96

No.0609 Control station download ................................................................ 2-96

No.0626 Time Setting Changed .................................................................... 2-96

No.0630 System Alarm Acknowledgment ...................................................... 2-96

No.0634 Advanced Alarm Filter Setting Change............................................ 2-96

No.0635 Process alarm acquisition mode changed ....................................... 2-97

No.0636 Message acknowledgment method changed .................................. 2-97

No.0637 Referenced database changed ....................................................... 2-97

Page 8: CS 1000/3000 Operating Messages

IM 33S02H10-01E

Toc-8

14th Edition : Dec.26,2006-00

No.0638 User-defined function key changed ................................................. 2-97

No.0639 Operation mark changed ................................................................ 2-97

No.0640 Multimedia definition changed......................................................... 2-98

No.0641 Trend display pen assignment changed .......................................... 2-98

No.0642 Graphic instrument faceplate assignment changed ......................... 2-98

No.0644 Switching Mode .............................................................................. 2-98

No.0645 Switching User (User-In) ................................................................. 2-98

No.0646 Switching User (User out) ............................................................... 2-99

No.0647 User Password Changed ................................................................ 2-99

No.0648 Setting of message summary master HIS station ............................ 2-99

No.0649 Changing of watching Tag volume .................................................. 2-99

No.0650 Change trend acquisition pen assignment ...................................... 2-99

No.0653 HIS printer on ............................................................................... 2-100

No.0654 HIS printer off ................................................................................ 2-100

No.0655 HIS printer assignment change ..................................................... 2-100

No.0656 Buzzer sound output destination changed .................................... 2-100

No.0657 Window mode changed ................................................................ 2-100

No.0658 Enable/Disable Touch Panel Function ........................................... 2-101

No.0659 Calibration operation on touch panel ............................................. 2-101

No.0663 Equalization operation .................................................................. 2-101

No.0691 Authentication server connection error .......................................... 2-101

No.0692 Authentication server connection recovered ................................. 2-101

2.7 FCS Related Messages (Message Nos. 0721 to 0799) .............................. 2-102

No.0721 SEBOL error (Fatal error: SFC block) ............................................ 2-102

No.0723 SEBOL error (SFC block) .............................................................. 2-103

No.0725 Arbitary character string system alarm generation ........................ 2-103

No.0726 Arbitary character string system alarm recovery ............................ 2-103

No.0727 Block mode recovery error information .......................................... 2-104

No.0729 SFC block main program intermediate language downloadingerror information ........................................................................... 2-104

No.0731 Unit error (unit procedure) ............................................................. 2-105

No.0733 Unit error (SEBOL interpreter) ....................................................... 2-108

No.0735 Unit Error (batch execution management) ..................................... 2-108

No.0737 FCS Batch Execution Management Error ..................................... 2-109

No.0739 Unit Busy (batch execution management) ...................................... 2-110

No.0743 Self-diagnostic ENBUS Failure ...................................................... 2-111

No.0744 Self-diagnostic ENBUS Recovery .................................................. 2-111

No.0745 Mismatched Database ................................................................... 2-111

No.0747 Notification of Failure to Load SEBOL Functions ............................ 2-112

No.0749 Self-diagnosis Detected an I/O Error .............................................. 2-112

No.0750 I/O Recovery from the error detected by self-diagnosis .................. 2-113

No.0751 Time self-diagnostic testing error ................................................... 2-113

No.0753 Communication Overload .............................................................. 2-114

Page 9: CS 1000/3000 Operating Messages

Toc-9

IM 33S02H10-01E 15th Edition : Dec.10,2007-00

No.0755 Failed to download the user customizable algorism ....................... 2-114

No.0757 Cannot find the function of user customizable algorism .................. 2-114

No.0759 User customizable block terminated with error ............................... 2-115

No.0761 User customizable block aborted (exception handling) ................... 2-115

No.0763 User customizable block aborted (timeout) .................................... 2-115

No.0765 User customizable block aborted (timeout) .................................... 2-115

No.0767 ESB Bus Error (One-side SB301/CP401 Error) .............................. 2-116

No.0768 Single ESB Bus Recovery ............................................................. 2-116

No.0770 Node Temperature Recovery ......................................................... 2-117

No.0787 Self-diagnosis detected an I/O error ............................................... 2-117

No.0791 APCS or general-purpose subsystem gateway (GSGW)start error ....................................................................................... 2-118

No.0795 Inappropriate ID ............................................................................. 2-118

No.0796 UPS Diagnosis Error ...................................................................... 2-118

No.0797 PSU power failure .......................................................................... 2-119

No.0798 Power Supply Recovered .............................................................. 2-119

No.0799 APCS or GSGW starts shutdown due to main power supplyfailure ............................................................................................ 2-119

2.8 HIS Peripherals Messages (Message Nos. 0811 to 0892) ......................... 2-120

No.0811 FA-M3 Hardware error occurrence ................................................ 2-120

No.0813 FA-M3 Communication error occurrence ...................................... 2-120

No.0814 FA-M3 communication error recovery ........................................... 2-121

No.0821 Printer is unavailable .................................................................... 2-121

No.0823 Printer is offline ............................................................................. 2-121

No.0825 Printer out of paper ....................................................................... 2-121

No.0827 Printer error .................................................................................. 2-121

No.0829 Printer undefined .......................................................................... 2-122

No.0871 HIS Batch Manager Recipe Load Error ......................................... 2-122

No.0873 HIS Batch Manager Recipe Common Block Access Error ............. 2-124

No.0875 HIS Batch Manager Unit Recipe Dynamic Assignment Error ......... 2-124

No.0877 HIS Batch Manager Recipe Uploading Error ................................. 2-124

No.0879 Error of HIS schedule management interface ................................ 2-125

No.0885 Violation of Process Management License ................................... 2-127

No.0886 Process Management Configuration Error .................................... 2-127

No.0889 HIS Batch Management Recipe Set Up Error ............................... 2-128

No.0891 Package error ............................................................................... 2-128

No.0892 Package error recovery ................................................................ 2-129

2.9 Process Messages (Message Nos. 1101 to 1903)...................................... 2-130

No.1101 Input process alarm generation ..................................................... 2-130

No.1102 Input process alarm recovery ........................................................ 2-130

No.1103 Output process alarm generation .................................................. 2-131

No.1104 Output process alarm recovery ..................................................... 2-131

Page 10: CS 1000/3000 Operating Messages

IM 33S02H10-01E

Toc-10

14th Edition : Dec.26,2006-00

No.1106 Process alarm normal recovery .................................................... 2-131

No.1107 Process alarm continuation ........................................................... 2-131

No.1111 Unit alarm generation, task alarm generation ................................ 2-132

No.1112 Unit alarm recovery, task alarm recovery ...................................... 2-132

No.1201 Annunciator generation message ................................................. 2-132

No.1206 Annunciator recovery message .................................................... 2-132

No.1207 Annunciator generation continuation ............................................. 2-132

No.1221 Annunciator with Data Turned On ................................................. 2-133

No.1226 Annunciator with Data Turned Off (Recovered) ............................. 2-133

No.1227 Annunciator with Data Kept On ..................................................... 2-133

No.1303 Sequence message ...................................................................... 2-134

No.1305 History message ........................................................................... 2-134

No.1401 Block mode (loop status) .............................................................. 2-134

No.1403 Alarm off ....................................................................................... 2-134

No.1404 Alarm on ....................................................................................... 2-135

No.1405 Block status change information ................................................... 2-135

No.1407 Data item value change information .............................................. 2-135

No.1421 Recipe Execution Start ................................................................. 2-135

No.1422 Recipe Execution End .................................................................. 2-136

No.1423 Recipe Abortion ............................................................................ 2-136

No.1424 Recipe Status Change Notification................................................ 2-136

No.1425 Server Station Change Notification ............................................... 2-137

No.1426 Reservation Processing Completion Notification ........................... 2-137

No.1428 Recipe Setup Request .................................................................. 2-137

No.1431 Unit Recipe Execution Start .......................................................... 2-137

No.1432 Unit Recipe Execution End ........................................................... 2-138

No.1433 Unit Recipe Abortion ..................................................................... 2-138

No.1434 Unit Recipe Status Change Notification ........................................ 2-138

No.1435 Unit Recipe Download Request .................................................... 2-139

No.1436 Dynamic Unit Recipe Assignment Request ................................... 2-139

No.1501 Request for playing multimedia ..................................................... 2-139

No.1502 Request for playing multimedia denied (Unauthorized Station) ..... 2-139

No.1503 Request for playing multimedia denied(Multimedia File Undefined) .......................................................... 2-140

No.1601 Entry operation record .................................................................. 2-140

No.1602 Tag alarm acknowledgment .......................................................... 2-140

No.1603 Block mode change ...................................................................... 2-141

No.1604 Function block operation ............................................................... 2-141

No.1605 Alarm off ....................................................................................... 2-141

No.1606 Alarm on ....................................................................................... 2-141

No.1608 Switch Button Operation Record ................................................... 2-141

No.1612 Operation Guide Message Acknowledgment ................................ 2-142

No.1613 Function block operation ............................................................... 2-142

Page 11: CS 1000/3000 Operating Messages

Toc-11

IM 33S02H10-01E 14th Edition : Dec.26,2006-00

No.1617 Common Block Data Entry ............................................................ 2-142

No.1619 Recipe Status Operation ............................................................... 2-142

No.1621 Unit Recipe Status Operation ........................................................ 2-143

No.1623 Dynamic Unit Recipe Assignment ................................................. 2-143

No.1633 Server Station Change ................................................................. 2-143

No.1641 Operation mark assignment .......................................................... 2-143

No.1642 Operation mark reset .................................................................... 2-143

No.1643 Graphic window data group entry operation .................................. 2-144

No.1672 Operator Control recipe memo...................................................... 2-144

No.1681 Package operation ........................................................................ 2-144

No.1691 Save Trend Data ........................................................................... 2-145

No.1693 Trend recording start operation ..................................................... 2-145

No.1694 Trend recording stop operation ..................................................... 2-145

No.1695 Trend recording continuation operation ......................................... 2-145

No.1701 Operation guide message ............................................................. 2-145

No.1711 Dialogue message ........................................................................ 2-145

No.1712 Reinput type dialog message ........................................................ 2-146

No.1713 Dialogue cancel ............................................................................ 2-146

No.1714 Dialogue time-out cancel .............................................................. 2-146

No.1801 Sequence message request ......................................................... 2-146

No.1802 Sequence message request denied (Unauthorized Station) .......... 2-146

No.1803 Sequence message request denied (Undefined) .......................... 2-146

No.1902 Supervisory computer event message(for operation and monitoring function program, device address 3)received ........................................................................................ 2-147

No.1903 Supervisory computer event message(for computer program, device address 6) received ...................... 2-147

2.10 Fieldbus Messages (Message Nos. 3001 to 3282) ..................................... 2-148

No.3001 Fieldbus Device Failure ................................................................ 2-148

No.3002 Recovery of Fieldbus Device to Normal ........................................ 2-148

No.3011 ACF11 Self-Diagnosed Failure ...................................................... 2-149

No.3021 ACF11 Configuration Failure ......................................................... 2-150

No.3050 Occurrence of an Update Event in ACF11 ..................................... 2-152

No.3101 Occurrence of a Fieldbus Device Alarm ........................................ 2-152

No.3102 Recovery of Fieldbus Devices to Normal ....................................... 2-152

No.3111 Occurrence of process Alarm from Fieldbus Devices .................... 2-153

No.3112 Recovery of Fieldbus Devices from Process Alarm ....................... 2-153

No.3150 Update of Fieldbus Devices .......................................................... 2-153

No.3160 Change in Write Protection of Fieldbus Devices ............................ 2-154

No.3171 Fieldbus Device Abnormal ............................................................ 2-154

No.3172 Fieldbus Device Recovered to Normal .......................................... 2-154

No.3173 Fieldbus Device Detected a Process Alarm................................... 2-155

No.3174 The Process Alarm detected by the Fieldbus Device vanished ...... 2-155

Page 12: CS 1000/3000 Operating Messages

IM 33S02H10-01E

Toc-12

14th Edition : Dec.26,2006-00

No.3175 Fieldbus Device Update Event ...................................................... 2-155

No.3176 Enable/Disable Write Protection of Fieldbus Device ...................... 2-156

No.3181 Fieldbus Device Failure ................................................................ 2-156

No.3182 Fieldbus Device Recovery ............................................................ 2-156

No.3183 Error Detected by ALF111 Self-diagnosis ...................................... 2-157

No.3201 PROFIBUS-DP field device-common message: Master Lockoccurrence.................................................................................... 2-157

No.3202 PROFIBUS-DP field device-common message: recovery fromMaster Lock .................................................................................. 2-158

No.3203 PROFIBUS-DP field device-common message: ParameterFault occurrence ........................................................................... 2-158

No.3204 PROFIBUS-DP field device-common message: recovery fromParameter Fault ............................................................................ 2-158

No.3205 PROFIBUS-DP field device-common message: Invalid SlaveResponse occurrence ................................................................... 2-158

No.3206 PROFIBUS-DP field device-common message: recovery fromInvalid Slave Response ................................................................ 2-158

No.3207 PROFIBUS-DP field device-common message: Not Supportedoccurrence.................................................................................... 2-158

No.3208 PROFIBUS-DP field device-common message: recovery fromNot Supported .............................................................................. 2-159

No.3209 PROFIBUS-DP field device-common message: ConfigurationFault occurrence ........................................................................... 2-159

No.3210 PROFIBUS-DP field device-common message: recovery fromConfiguration Fault ....................................................................... 2-159

No.3211 PROFIBUS-DP field device-common message: Station NotReady occurrence ........................................................................ 2-159

No.3212 PROFIBUS-DP field device-common message: recovery fromStation Not Ready......................................................................... 2-159

No.3213 PROFIBUS-DP field device-common message: Station NonExistent occurrence ...................................................................... 2-159

No.3214 PROFIBUS-DP field device-common message: recovery fromStation Non Existent ..................................................................... 2-160

No.3215 PROFIBUS-DP field device-common message: Deactivatedoccurrence.................................................................................... 2-160

No.3216 PROFIBUS-DP field device-common message: recovery fromDeactivated .................................................................................. 2-160

No.3217 PROFIBUS-DP field device-common message: ParameterRequest occurrence ..................................................................... 2-160

No.3218 PROFIBUS-DP field device-common message: recovery fromParameter Request ...................................................................... 2-160

No.3219 PROFIBUS-DP field device-common message: Ext DiagOverflow occurrence ..................................................................... 2-160

No.3220 PROFIBUS-DP field device-common message: recovery fromExt Diag Overflow ......................................................................... 2-161

No.3231 PROFIBUS-DP field device-specific message: error occurrence ... 2-161

No.3232 PROFIBUS-DP field device-specific message: recovery fromerror .............................................................................................. 2-161

No.3241 PROFIBUS-DP field device module error occurrence ................... 2-161

No.3242 PROFIBUS-DP recovery from field device module error ............... 2-161

Page 13: CS 1000/3000 Operating Messages

Toc-13

IM 33S02H10-01E 14th Edition : Dec.26,2006-00

No.3251 PROFIBUS-DP field device channel error: short circuitoccurrence.................................................................................... 2-161

No.3253 PROFIBUS-DP field device channel error: undervoltageoccurrence.................................................................................... 2-162

No.3255 PROFIBUS-DP field device channel error: overvoltageoccurrence.................................................................................... 2-162

No.3257 PROFIBUS-DP field device channel error: overload occurrence ... 2-162

No.3259 PROFIBUS-DP field device channel error: overtemperatureoccurrence.................................................................................... 2-162

No.3261 PROFIBUS-DP field device channel error: link break occurrence .. 2-162

No.3263 PROFIBUS-DP field device channel error: upper limit valueexceeded ...................................................................................... 2-162

No.3265 PROFIBUS-DP field device channel error: lower limit valueexceeded ...................................................................................... 2-163

No.3267 PROFIBUS-DP field device channel error: error occurrence ......... 2-163

No.3269 PROFIBUS-DP field device channel error occurrence................... 2-163

No.3270 PROFIBUS-DP recovery from field device channel error ............... 2-163

No.3281 PROFIBUS communication stop ................................................... 2-163

No.3282 PROFIBUS communication resumption ........................................ 2-163

2.11 Control Station Related Messages (Message Nos. 4001 to 4036) ............ 2-164

No.4001 Fieldbus Device Error or Communication Error Due to ExternalCause of ALF111 .......................................................................... 2-164

No.4002 Fieldbus Device Recovery or External Cause of ALF111 Solved ... 2-164

No.4003 Occurrence of “Other” ................................................................... 2-165

No.4004 Recovery of “Other” ...................................................................... 2-165

No.4005 Occurrence of “Block Configuration Error” .................................... 2-165

No.4006 Recovery of “Block Configuration Error” ........................................ 2-165

No.4007 Occurrence of “Link Configuration Error” ....................................... 2-165

No.4008 Recovery of “Link Configuration Error” .......................................... 2-166

No.4009 Occurrence of “Device Needs Maintenance Soon” ........................ 2-166

No.4010 Recovery of “Device Needs Maintenance Soon” ........................... 2-166

No.4011 Occurrence of “Memory Failure” ................................................... 2-166

No.4012 Recovery of “Memory Failure” ....................................................... 2-166

No.4013 Occurrence of “Lost Static Data” ................................................... 2-167

No.4014 Recovery of “Lost Static Data” ...................................................... 2-167

No.4015 Occurrence of “Lost NV Data” ....................................................... 2-167

No.4016 Recovery of “Lost NV Data” .......................................................... 2-167

No.4017 Occurrence of “Readback Check Failed” ...................................... 2-167

No.4018 Recovery of “Readback Check Failed” .......................................... 2-168

No.4019 Occurrence of “Device Needs Maintenance Now” ......................... 2-168

No.4020 Recovery of “Device Needs Maintenance Now” ............................ 2-168

No.4021 Error When Write to Foundation Fieldbus Faceplate Block ........... 2-168

No.4023 Communication Error with Duplicate ALF111 ................................ 2-169

No.4024 Communication Error with Duplicate ALF111 Recovered .............. 2-169

No.4031 HART Device Error ....................................................................... 2-169

Page 14: CS 1000/3000 Operating Messages

IM 33S02H10-01E

Toc-14

14th Edition : Dec.26,2006-00

No.4032 HART Device Recovery ................................................................ 2-169

No.4033 HART Communication Error ......................................................... 2-169

No.4034 HART Communication Recovery .................................................. 2-170

No.4035 HART Communication Command Error ........................................ 2-170

No.4036 HART Communication Command Recover ................................... 2-170

2.12 ProSafe-RS Messages (Message Numbers 4101 to 4199) ........................ 2-171

Page 15: CS 1000/3000 Operating Messages

1-1

IM 33S02H10-01E

<1. Overview>

1. OverviewThe message processing function notifies the operator of system status changes,process operating status, and various events from the control station. It sendsmessages to the operator by a predefined method.

This manual describes the following messages:

• System alarm messages

• Process alarm messages

• Operation record messages related to the operation and monitoring functionThe following messages are output in easy to understand text, and are notdescribed in this manual:

• Error messages

• Reconfirmation messages

• Help messages

10th Edition : Dec.18,2003-00

Page 16: CS 1000/3000 Operating Messages

1-2<1. Overview>

IM 33S02H10-01E

1.1 Message Types, Numbering System, andOutput DestinationMessages are grouped for easy identification. The output destination (windowdisplay, LED, buzzer, printer, file, etc.) can be decided for each type.

Table System Alarm Messages and Output Destination

No. Message type Window Buzzer LED lit key Printing File

00XX Control station alarm � � (*1) sys � �

02XX HIS alarm � � (*1) sys � �

03XX Other system alarms � � (*1)

(*2)

� (*1)

sys � �

04XX System status information � sys � �

05XX System operation command � sys � �

06XX System operation record � sys � �

07XX Control station alarm � � (*1)(*3) sys � �

08XX Others � � (*1) sys � �

� � (*1) sys � �40XX Control station alarm010101E.EPS

01XX Other system alarms � � (*1) sys � �

�: OutputBlank: Not outputsys: System status list display window call key*1: In principle, the buzzer output for messages is as follows:

• Odd numbered messages output with buzzers.• Even numbered messages output without buzzers.

*2: There are exceptions to buzzer output. The numbers, 0477, 0479, and 0485 are output.*3: There are exceptions to buzzer output. The numbers, 0723, 0753, 0755, and 0759 are not output. The number 0796 is

output.

Table Process Alarm Messages and Output Destination ( Included Fieldbus Message )

No. Message type Window Buzzer LED lit key Printing File

11XX Process alarm � � (*1)(*2) alarm � �

12XX Annunciation message � � (*1)(*2) alarm � �

13XX Print message � �

14XX Status change report � �

16XX Process operation record � �

17XX Operation guide message � � (*1)(*3) opeg � �

19XX Application startup message � �

010102E.EPS

18XX Message request � �

3XXX Fieldbus message �

�: OutputBlank: Not outputalarm: Process alarm window call keyopeg: Operation guide window call key*1: In principle, the buzzer output for messages is as follows:

• Odd numbered messages output with buzzers.• Even numbered messages output without buzzers.

*2: There are exceptions to buzzer output. The numbers, 1106 and 1206 both for “Non-Lock (Recovery Notification)” typefor Process Alarm High are output.

*3: There are exceptions to buzzer output. The number 1712 is output. The number 1713 is not output.

15th Edition : Dec.10,2007-00

Page 17: CS 1000/3000 Operating Messages

1-3

IM 33S02H10-01E

<1. Overview>

10th Edition : Dec.18,2003-00

1.2 Operation Window Message Display FormatThe operation and monitoring function displays the message generation conditions,cause, and other information on a window so that they can be easily understood bythe operator.

■ Message Display Format and PositionsThe message processing function displays in the message display area the most recentunacknowledged message from among the process alarm, annunciator, and system alarmmessages.

While an alarm is unacknowledged, the corresponding window call button (process alarm,system alarm button) flashes. When the operator clicks on the message history displaybutton, or message display area, the message processing function displays the five newestunacknowledged messages as a group.

010201E.EPS

03/12/18 PM 01:49

PIC100 System A inlet differential pressure LO

? NAME COPY

Message display area Message historydisplay button

Date and time display area

Process Alarm Message window call

System Alarm Message window call

Icon display area

Figure System Message Window Message Display Positions

■ Display Message DetailsThe message processing function displays messages in the following formats:

● Process Alarm Messages

Process alarm messages indicate generation of a process alarm or annunciator alarmmessage.

The process alarm window displays process alarm message details.

Example: ■FCS0101 Fail

● System Alarm Messages

System alarm messages indicate generation of a system alarm message.

The system alarm window displays system alarm message details.

Example: ◆0301 05.15 12:30:27 COM-E FCS0101 Error Code=0011

Page 18: CS 1000/3000 Operating Messages

1-4<1. Overview>

IM 33S02H10-01E

1.3 Message Printout FormatThis section describes the display format when printing generated messages on aprinter or similar device.

■ Message Printing FormatMessages are printed on a printer in the following format:

* * * 0303 05.18 13:50:54 FCS0201 Fail

Message

Date and time (month day hour minute second)

Message No.

Message identifier

(Note) The message identifier asterisks (***) are added at alarm generation to discriminate from recovery.

010301E.EPS

Figure Message Printing Format

■ Message Printing PositionsThe message printing positions can be set for each type of message by setting tabs. Thissetting is performed using the HIS Printer Builder of the system builders.

System alarm message

3 tabs Operation message

6 tabs Process alarm message 1

6 tabs Process alarm message 2

010302E.EPSNote: The number of characters/tab depends on the connected printer.

Figure Message Printing Positions

10th Edition : Dec.18,2003-00

Page 19: CS 1000/3000 Operating Messages

2-1

IM 33S02H10-01E

<2. Message Output Details>

2. Message Output DetailsThis chapter describes the output message in detail. The descriptions are made upthe items shown below for each message. The Meaning, Cause, Action, Note, andRemark items can be omitted, depending on the message.

IMPORTANT

This chapter includes the messages related to the functions not yet installed in the currentsystem.

Message name Name of the message.Example: Process I/O error

Printing example Printing or display example.Example: FCS0101 FIC1001 IN PI/O not ReadyIn this manual, spaces in messages and leading “00” of numbers may be different fromthe actual printing examples within the range over which understanding of the mes-sage is not impaired.

Meaning Defines the message.Example: Error generated in the connection destination process I/O of a function block.

Cause Describes the generation cause. This description may be omitted, depending on themessage.Example: Error in process I/O connected to I/O terminal of function block.

Action Describes the action to be taken. This description may be omitted, depending on themessage.Example: Reset the error process I/O.“Contact the service department.” means that user should contact the service depart-ment.

Note Comment or explanation. This item may be omitted, depending on the message.

Remark Annotation. This item may be omitted, depending on the message.

10th Edition : Dec.18,2003-00

Page 20: CS 1000/3000 Operating Messages

2-2<2. Message Output Details>

IM 33S02H10-01E

2.1 FCS Error Generation and Recovery Messages(Message Nos. 0001 to 0099)This section describes the messages sent from the CS 1000/CS 3000 control sta-tions and the messages sent from the ProSafe-RS safety control stations.

No. 0001Message name Control station reset start

Printing example FCS0101 RIGHT Manual Reset Start

Meaning Control station (station name=FCS0101) CPU card (right side in the example) wasreset started.

Cause Start operation from a HIS, or from the front of the CPU card.

• ProSafe-RS

Message name Reset start of safety control station

Printing example SCS0101 RIGHT Manual Reset Start

Meaning A CPU module (right side in the above example) of the safety control station (stationname = SCS0101) was reset and started.

Cause Start operation from the SENG or from the front switch of the CPU module

No. 0003Message name Control station automatic reset start

Printing example FCS0101 RIGHT Automatic Reset Start

Meaning An error in the displayed CPU card (right side in the example) of the control station(station name=FCS0101) caused the control station to be automatically reset started.

Cause CPU card is faulty.

• ProSafe-RS

Message name Safety control station automatic reset start

Printing example SCS0101 RIGHT Automatic Reset Start

Meaning An error in the displayed CPU module (right side in the example) of the safety con-trol station (station name=SCS0101) caused the safety control station to be automati-cally reset started.

Cause CPU module is faulty.

14th Edition : Dec.26,2006-00

Page 21: CS 1000/3000 Operating Messages

2-3

IM 33S02H10-01E

<2. Message Output Details>

No. 0005Message name Control station power on initialization cold start

Example FCS0101 Power On (Cold Start)

Meaning Control station (station name=FCS0101) was initialization cold started after the powerwas turned on.

Cause Recovery from power a failure.

• ProSafe-RS

Message name Power ON initial cold start of safety control station

Printing example SCS0101 Power ON (Cold Start)

Meaning The safety control station (station name = SCS0101) performed the initial cold startprocessing after it was powered ON.

Cause Recovery from power failure

Note The safety control station always performs the initial cold start processing after recov-ery from power failure.

No. 0007Message name Control station power on restart

Printing example FCS0101 Power ON (Hot Start)

Meaning Control station (station name=FCS0101) was restarted after the power was turned on.

Cause Recovery from a power failure.

No. 0009Message name Control station control right transfer

Printing example FCS0101 Control Transfer

Meaning Dual-redundant control station (station name=FCS0101) generated a control righttransfer.

Cause • One of the CPU cards stopped, or is abnormal.• Power supply unit stopped, or is abnormal.

Action Standby CPU unit starts automatically. If the standby CPU unit does not start, replacethe CPU card that stopped the station.

• ProSafe-RS

Message name Transfer of control right of safety control station

Printing example SCS0101 Control Transfer

Meaning A transfer of control right occurred in the redundant safety control station (station name= SCS0101).

Cause • The CPU module on one side was stopped.• An error occurred in the CPU module on one side.

Action The CPU module on the standby side takes over control. Replace the CPU modulethat was stopped.

13th Edition : Dec.26,2005-00

Page 22: CS 1000/3000 Operating Messages

2-4<2. Message Output Details>

IM 33S02H10-01E

No. 0011Message name Control station failure information

Printing example FCS0101 RIGHT Fail (xxxxxxxx Code= yyyy yyyy yyyy yyyy)

Meaning Control station (station name=FCS0101) CPU (right side in the example) failed.

Cause Indicated by Code. For a detailed description of Code, see the table below.

Action If the control station operates normally after automatic restart, continue operation.If the control station stops after automatic restart, replace the CPU card.

Table Message No. 0011 - Causes

Item xxxxxxxx Code (hex 16 digits)yyyy yyyy yyyy yyyy Description Auto (*1)

restart

CPU cardstopped

SW STOP

-

Stopped by CPU card front panel switch. -

V STOP Stop command via Control bus. -

DC FAIL Stopped by power failure. -

CPU DOWN

NSR3 (*2)Error generated in CPU card error check.NSR3, INTSTS, ERRSTS1, andERRSTS2 are the detailed error codes.

INTSTS (*2)

ERRSTS1 (*2)

ERRSTS2 (*2)

SELFSTOP

Codes that indicate the cause.(*2)

Stopped by detection of error by software. -

UNKNOWN Stopped by unknown cause. -

RESTART Restarted by detection of error bysoftware. Yes

Yes

001101E.EPS

*1: Auto restart: – (No)*2: When this error message is displayed, notify the service department of the contents of the Code display.

14th Edition : Dec.26,2006-00

Page 23: CS 1000/3000 Operating Messages

2-5

IM 33S02H10-01E

<2. Message Output Details>

• ProSafe-RS

Message name Fail information of safety control station

Printing example SCS0101 RIGHT Fail (xxxxxxxx Code= yyyy yyyy yyyy yyyy)

Meaning A CPU module (right side in the above example) of the safety control station (stationname = SCS0101) failed.

Cause The causes are indicated by “causes (xxxxxxxx)” and a code. For more information,see the table below.

Action If the safety control station operates normally after restarting automatically, continueoperation. If the safety control station stops after restarting automatically, replace theCPU module.

Table Message No. 0011 - Cause List

Itemcauses

xxxxxxxxCode (hex 16 digits)yyyy yyyy yyyy yyyy Description Auto (*1)

restart

SW STOP

-

Stop by operation of the front switch of the CPU module

Stop instruction via control bus

Stop due to power failure

Stop after software detected an error

Stop due to unknown cause

Restart after software detected an error

An error occurred during CPU module error check. NSR3, INTSTS, ERRSTS1 and ERRSTS2 are detailed error codes.

V STOP

-

DC STOP

CPU DOWN

SELFSTOP

UNKNOWN

RESTART

-

-

Yes

-

-

Yes

001102E.EPS

NSR3(*2)

INTSTS(*2)

ERRSTS1(*2)

ERRSTS2(*2)

(*3)

CPU module stop

*1: Auto restart: – (No)*2: If this error message is displayed, report the display contents of causes (xxxxxxxx) and code to Yokogawa’s service

department.*3: Refer to the following “Table Error Codes and Solutions”.

Table Error Codes and Solutions

Code (HEX; 16 Digits) Error Solution

0000 5090 yyyy yyyy Zero division occurred when running the application logic.

Check to see if the application logic contains zero division or not, and correct the application logic if it contains.

001103E.EPS

0000 5091 yyyy yyyy The application logic is trying to access an array datum beyond the scope of the array.

Check the application and find out which logic program is accessing the out-of-range array data and correct the error.

0000 50a9 yyyy yyyyThe database inconsistence is detected. It may be caused by restarting the SCS without releasing the brake point.

Run offline downloading.

4000 3BF1 0255 8082The firmware (Revision F4) in the CPU module is too old to support the system with Optical ESB Bus Repeater modules.

For a system that contains Optical ESB Bus Repeater modules, the firmware of CPU with the proper revision number should be used.

0000 5010 yyyy yyyy The CPU model and station model are inconsistent.

Match the CPU model and station model with each other.

FFFF 000B 0000 000F The calculation in a running application overflowed.

Check the application and find out what caused the calculation overflow and then modify it.

Other OtherIf this error message is displayed, report the display contents of causes (xxxxxxxx) and the code to Yokogawa's service department.

15th Edition : Dec.10,2007-00

Page 24: CS 1000/3000 Operating Messages

2-6<2. Message Output Details>

IM 33S02H10-01E

No. 0013Message name Control station AC power failure

Printing example FCS0101 AC Fail (Time 97.02.01 18:45)

Meaning Control station (station name=FCS0101) AC power failed, then recovered.TIME is the time the power failed. This message is output after the power recovers.

Cause AC power supply voltage drop, or power failure.

• ProSafe-RS

Message name AC power supply failure of safety control station

Printing example SCS0101 AC Fail (Time 05.02.01 18:45)

Meaning AC power of the safety control station (station name = SCS0101) failed and was thenrecovered. The date and time indicated are when the power failed. This message isoutput after the power is recovered.

Cause The voltage of AC power supply dropped, or a power failure occurred.

Note The SCS has been initialized and then started.

No. 0015Message name CPU internal clock self-diagnostic testing error

Printing example FCS0101 RTC Diagnose Error Code=0001

Meaning Control station (station name=FCS0101) internal clock self-diagnosis detected anerror.Code=0001: Check pattern mismatchCode=0002: Time value invalidCode=0003: Time not updated

Action Replace the CPU card.

• ProSafe-RS

Message name Self-diagnosis error of clock inside CPU module

Printing example SCS0101 RTC Diagnose Error Code=0001

Meaning An error was detected during self-diagnosis of the clock inside the safety control sta-tion (station name = SCS0101).Code=0001: Check pattern mismatchCode=0002: Inappropriate date/time valueCode=0003: Date/time not updated

Action Replace the CPU module.

13th Edition : Dec.26,2005-00

Page 25: CS 1000/3000 Operating Messages

2-7

IM 33S02H10-01E

<2. Message Output Details>

No. 0017Message name CPU card ROM check sum error

Printing example FCS0101 RIGHT ROM Sum Check Error

Meaning ROM check sum error was detected in the displayed CPU card (right side in the ex-ample) of the control station (station name=FCS0101).

Action Replace the CPU card.

• ProSafe-RS

Message name ROM checksum error of CPU module

Printing example SCS0101 RIGHT ROM Sum Check Error

Meaning A ROM checksum error was detected in the indicated CPU module (right side in theabove example) of the safety control station (station name = SCS0101).

Action Replace the CPU module.

No. 0019Message name Control Station Task Error

Printing example FCS0101 TASK=USERC Abort Code=xxxx

Meaning A task (USERC in the above example) in the control station (station name = FCS0101)was aborted. If the CPU card failed, this message is output when the CPU card isrestarted. The error code (Abort Code) shows the detailed internal information.

Action Report the message and the error code to the vendor’s technical service group.

No. 0021Message name Control station task internal error

Printing example FCS0101 Internal Error TASK=KAKA Code=100 Error=1000-E0F0

Meaning An abnormal state was detected during control station (station name=FCS0101) in-ternal task (KAKA in the example) execution. TASK, Code, and Error are the detailederror information.

Cause Software error.

Action Report the message and the error code to the vendor’s technical service group.

• ProSafe-RS

Message name Internal task error of safety control station

Printing example SCS0101 Internal Error TASK=TSK1 Code=100 Error=1000 - E0F0

Meaning An error state was detected during the execution of a task (TSK1 in the above ex-ample) in the safety control station (station name = SCS0101). “TASK,” “Code” and“Error” indicate detailed error information.

Cause This is a software problem.

Action Report the message content to Yokogawa’s service department.

12th Edition : Mar.31,2005-00

Page 26: CS 1000/3000 Operating Messages

2-8<2. Message Output Details>

IM 33S02H10-01E

No. 0023Message name Function block fatal error

Printing example FCS0101 Block FIC001 Return Error 8E04 and stop

Meaning An error that prevents farther execution was detected during control station (stationname=FCS0101) function block (FIC001 in the example) execution.

Cause Function block database error. Error is the detailed error information.

Action To recover, execute online downloading.

• ProSafe-RS

Message name Mapping block fatal error

Printing example SCS0101 Block TAG001 Return Error 8E04 and stop

Meaning An execution disabled error was detected during the execution of a mapping block(TAG001 in the above example) in the safety control station (station name =SCS0101).

Cause There is a problem in the integration DB. “Error” indicates detailed error information.

Action Report the message content to Yokogawa’s service department.

No. 0025Message name Function control word error

Printing example FCS0101 No Block Control Word for Block Type=1804

Meaning Internal program corresponding to the control station (station name=FCS0101) blocktype code was not found. Type is the detailed internal information.

Cause Task initialization error.

Action Execute offline downloading.

• ProSafe-RS

Message name Function control word error

Printing example SCS0101 No Block Control Word for Block Type=1804

Meaning The internal program that corresponds to the block type code of the safety controlstation (station name = SCS0101) does not exist. “Type” indicates detailed internalinformation.

Cause This is an internal error at task initialization.

Action Report the message content to Yokogawa’s service department.

13th Edition : Dec.26,2005-00

Page 27: CS 1000/3000 Operating Messages

2-9

IM 33S02H10-01E

<2. Message Output Details>

No. 0027Message name Function block record information error

Printing example FCS0101 FIC001 Block Bad Record No=3

Meaning Control station function block (FIC001 in the example) record error. No is the error datablock record No.

Cause Function block and record block No. don’t correspond.

Action Notify the service department of the type and No. display contents of the block thatgenerated the error.

Note Do not execute online downloading after this alarm is generated.

• ProSafe-RS

Message name Mapping block record information error

Printing example SCS0101 TAG001 Block Bad Record No = 3

Meaning There is a bad record in the mapping block (TAG001 in the above example) of thesafety control station. “No” indicates the bad record number in the database.

Cause The mapping block and the record block number do not match.

Action Report the block type and record number where an error occurred to Yokogawa’sservice department.

Note Do not perform on-line change download after this alarm occurred.

No. 0029Message name HIS station communication failure

Printing example FCS0101 Tag List Communication Error

Meaning An HIS that can execute control station (station name=FCS0101) tag list communi-cation was not found.

Cause An HIS that can execute tag list communication could not be found.

Action Set an HIS that can communicate by system view.

No. 0030Message name HIS station communication recovery

Printing example FCS0101 Tag List Communication Recover

Meaning An HIS that can execute tag list communication was found.

Cause An HIS that can execute tag list communication was found.

13th Edition : Dec.26,2005-00

Page 28: CS 1000/3000 Operating Messages

2-10<2. Message Output Details>

IM 33S02H10-01E

No. 0033Message name Online downloading abnormal end

Printing example1 FCS0101 Online Download Error Code=9402-0000

Printing example2 FCS0101 Online Download Error Area = 1 Code = 9402-0000

Meaning Control station (station name=FCS0101) internal online downloading was abnormallyended. Code is the detailed internal information.

Cause / Action See the table below.

Code Error contents Cause Action

8164 No specified block. Specified block not found. Notify the service department of the Codedisplay contents.

8222A423 Status change failure. Specified block did not accept status

change.

Check the maintenance target block modefrom on the HIS. If the block has modes,check if the O/S can change the blockmode.If the O/S can change the block mode,perform the following operations.If even one Online Complete system alarmis generated during the currently executingonline downloading, execute station offlinedownloading.If there is not even one Online Completesystem alarm, execute online downloadingagain.

8724A424 Status change failure.

Specified block cannot be changedfrom current status to specifiedstatus.

8EC5 No tag name. Specified tag name not found. Notify the service department of the Codedisplay contents.

8EC8 Station command tag list areainsufficient.

Station common part tag list area isinsufficient.

Station common part tag lists cannot beadded.(Increase the area.) Add station commonpart tag lists after executing offlinedownloading, or deleting unwanted taglists.

8EC9 Tag list area insufficient Tag lists cannot be added.(Increase the area.) Add tag lists afterexecuting offline downloading, or deletingunwanted tag lists.

9402Online downloading abnormal end.Common part online downloadingrequest.

FCS was reset started during stationcommon part online downloading.

If even one Online Complete system alarmis generated during the currently executingonline downloading, execute station offlinedownloading. If there is not even oneOnline Complete system alarm, executeonline downloading again.9403 Online downloading abnormal end.

Online download request.FCS was reset started during onlinedownloading.

If even one Online Complete system alarmwas generated during executing onlinedownloading, execute offline downloading.

9404 Online downloading abnormal end.Offline downloading request.

FCS was reset started during onlinedownloading.

9405 Online downloading abnormal end.Station offline loading request.

FCS was reset started during stationcommand part online downloading.

Shut down the station. Execute stationoffline downloading.

9408Common part intermediate wordreload request. Online downloading normally ended.

FCS was reset started during stationcommon part online downloading(during intermediate word loading).

Execute station offline downloading.

9409 Intermediate word reload request.Online downloading normally ended.

FCS was reset started during onlinedownloading (during intermediateword downloading).

If even one Online Complete system alarmis generated during the currently executingon-line downloading, execute stationoffline downloading.

003301E.EPS

13th Edition : Dec.26,2005-00

Page 29: CS 1000/3000 Operating Messages

2-11

IM 33S02H10-01E

<2. Message Output Details>

Code Error contents Cause Action

9430 Function block addition check failure. Function block addition check failed. Check the detailed error code anddecide what action to take. (*1)

9432 Tried to add an existing block. The previous online downloadingprobably failed.

Notify the service department of theCode display contents.

9437 Tried to delete a nonexistent block. Previous online downloading probablyfailed.

Notify the service department of theCode display contents.

9443 Block tag list addition check failure. Block tag list addition check failed. Check the detailed error code anddecide what action to take. (*1)

9444 Block tag list change check failure. Tag list change check failed. Check the detailed error code anddecide what action to take. (*1)

9445 Block tag list deletion check failure. Block tag list deletion check failed.Check the detailed error code anddecide what action to take. (*1)

9448Message tag list addition checkfailure.

Message tag list addition check failed. Check the detailed error code anddecide what action to take. (*1)

9449 Message tag list change check failure. Message tag list change check failed. Check the detailed error code anddecide what action to take. (*1)

944AMessage tag list deletion checkfailure.

Message tag list deletion check failed. Check the detailed error code anddecide what action to take. (*1)

9461Station common part tag list additioncheck failure.

Station common part tag list additioncheck failed.

Check the detailed error code anddecide what action to take. (*1)

9462 Station common part tag list changecheck failure.

Station common part tag list changecheck failed.

Check the detailed error code anddecide what action to take. (*1)

9463Station common part tag list deletioncheck failure.

Station common part tag list deletioncheck failed.

Check the detailed error code anddecide what action to take. (*1)

9484 Block area insufficient (fixed part). Block area (fixed part) is insufficient. Blocks cannot be added. (Increase thearea.) Add more blocks afterexecuting offline downloading, ordeleting unwanted blocks.

9485 Block area insufficient (variable part).Block area (variable part) isinsufficient.

94F8 Block mode change check failure.Maintenance target block mode couldnot be changed to O/S.

(1) Ensure that the block mode can bechanged to O/S. (Judge using thedetail code.)(2) If even one Online Completesystem alarm is generated during thecurrently executing onlinedownloading, execute station offlinedownloading. If there is not even oneOnline Complete system alarm,execute online downloading again.

9633 Buffer overflow. Amount of change data is too large.

If even one Online Complete systemalarm is generated during the currentlyexecuting online downloading,execute station offline downloading.If there is not even one OnlineComplete system alarm, reduce theamount of change data, then executeonline downloading.

C001 SEBOL block addition check failure. SEBOL block addition check failed.Check the detailed error code anddecide what action to take. (*1)

C007 SFC block addition check failure. SFC block addition check failed.Check the detailed error code anddecide what action to take. (*1)

003302E.EPS

*1: “Detailed error code” is another error code in the alarm message No. 0033 table displayed together with the relevanterror code.

12th Edition : Mar.31,2005-00

Page 30: CS 1000/3000 Operating Messages

2-12<2. Message Output Details>

IM 33S02H10-01E

• ProSafe-RS

Message name Online downloading abnormal end

Printing example SCS0101 Online Download Error Code=9402 - 0000

Meaning On-line change download of the safety control station (station name = SCS0101)ended with an error. “Error Code” indicates detailed internal information.

Cause/Action See the table below.

Table Message No. 0033 - Error Code List

Code Error Contents Cause Action

9402940394049405

On-line change downloading abnormal end

The SCS was reset and started during on-line change download. Execute off-line download.

Report the display content of the code to Yokogawa’s service department.

003303E.EPS

Others Internal error Internal error

No. 0035Message name General-purpose calculation block calculation error

Printing example FCS0101 FY001 Calculation Error Line=10 Code=123456-FFFF

Meaning A control station (station name=FCS0101) general-purpose calculation block (blockname=FY001, block type=CALCU or CALCU-C in the example) generated an error.This message also displays the error generation line No. (Line) and error code (Code).

Action Remove the cause of the error based on the error code.

SEE ALSO

For error code details, see the following:

D2.47.7, “Error Handling” in Reference (IM 33S01B30-01E)

No. 0036Message name General-purpose calculation block calculation error recovery

Printing example FCS0101 FY001 Normal from CERR

Meaning Recovered from a control station (station name=FCS0101) general-purpose calcu-lation block (block name=FY001, block type=CALCU or CALCU-C in the example)error.

Cause The cause of the calculation error was removed.

13th Edition : Dec.26,2005-00

Page 31: CS 1000/3000 Operating Messages

2-13

IM 33S02H10-01E

<2. Message Output Details>

No. 0037Message name Block one-shot start error

Printing example FCS0101 SEQ001 One-Shot Error CND 3-12 Code=FFFF

Meaning One-shot block starting by control station (station name=FCS0101) function block(SEQ001 in the example) sequence connection failed.• When this alarm message is generated by sequence table, the condition testing

(CND) or status action (ACT) generation sequence table extension No., conditionsignal or action signal No. , and error code (Code) are displayed.

• If this alarm was generated in other sequence connection, this message displaysthe error code (Code) only.

Code is the detailed internal information.

Error Code (HEX) Cause

9E12 The connection destination block is under online maintenance.

9E13 The connection destination block mode is out of service (O/S).

9E14 The nesting configuration, where a one-shot start block is to start another one-shot start block, executes multiple blocks.

9E16The nesting configuration, where a one-shot start block is to start another one-shot start block, has over seven levels including the execution source block.

003701E.EPS

Action Check the relevant part of the function block that generated the error and remove thecause of the error.

No. 0038Message name Recovery from block one-shot starting error

Printing example FCS0101 SEQ001 Normal from One-Shot Error

Meaning Recovered from one-shot block starting error by sequence connection of control sta-tion (station name=FCS0101) function block (SEQ001 in the example).

No. 0039Message name Process I/O error

Printing example FCS0101 FIC001 IN PI/O not Ready

Meaning Error generated in process I/O at connection destination of control station (stationname=FCS0101) function block (FIC001 in the example).

Cause Error in block primary input terminal, secondary input terminal, primary output termi-nal, or secondary output terminal connection destination process I/O.

Action Reset the error process I/O.

12th Edition : Mar.31,2005-00

Page 32: CS 1000/3000 Operating Messages

2-14<2. Message Output Details>

IM 33S02H10-01E

No. 0040Message name Recovery from process I/O error

Printing example FCS0101 FIC001 Normal from PI/O not Ready

Meaning Recovered from control station (station name=FCS0101) function block (FIC001 in theexample) connection destination process I/O error.

No. 0041Message name Control Station Cabinet Fan Alarm

Printing example FCS0101 Fan (DOOR D1) Alarm

Meaning This is an alarm message about the cooling fan in the cabinet of control station (sta-tion name = FCS0101). One of the following items is displayed in the Printing exampleparentheses ( ) :For the cooling fan on door : DOOR D1, DOOR D2, DOOR D3, DOOR D4For the cooling fan in control unit : FCU N1, FCU N2

Action Replace the Fan unit.

• ProSafe-RS

Message name Safety control station fan alarm

Printing example SCS0101 Fan (SCU N1) Alarm

Meaning A cooling fan of the safety control station (station name = SCS0101) is abnormal. Oneof the following items is displayed in the parentheses in the above example.SCU N1: Left side fanSCU N2: Right side fan

Cause The cooling fan stopped or its revolution is abnormal.

Action Replace the failed fan unit.

Remark HKU function

No. 0042Message name Control Station Cabinet Fan Alarm Recovery

Printing example FCS0101 Fan (DOOR D1) Recover

Meaning The fan in the cabinet of the control station (station name = FCS0101) has been re-stored to the normal status. The information displayed in the Printing example paren-theses ( ) is the same as that for No. 0041.

• ProSafe-RS

Message name Recovery from safety control station fan alarm

Printing example SCS0101 Fan(SCU N1) Recover

Meaning The cooling fan of the safety control station (station name = SCS0101) recovered. Thecontent in the parentheses in the above example is the same as message No. 0041.(This is a recovery message of No. 0041.)

Remark HKU function

13th Edition : Dec.26,2005-00

Page 33: CS 1000/3000 Operating Messages

2-15

IM 33S02H10-01E

<2. Message Output Details>

No. 0043Message name Control Station Cabinet Temperature Alarm

Printing example FCS0101 Temperature (RIGHT BATTERY) Alarm

Meaning This is an alarm message about the high temperature in the cabinet of control station(station name = FCS0101). One of the following items is displayed in the Printingexample parentheses ( ) :RIGHT BATTERY (Right power source)LEFT BATTERY (Left power source)AIR IN (Air intake)AIR OUT (Air outlet)

Action Check the operation status of cooling fans. If necessary, report the phenomenon tothe vendor’s technical service group.

• ProSafe-RS

Message name Safety control station temperature alarm

Printing example SCS0101 Temperature(RIGHT BATTERY) Alarm

Meaning This is a temperature rise alarm of the safety control station (station name =SCS0101). One of the following items is displayed in the parentheses in the aboveexample.RIGHT BATTERY: Battery of the right side CPU moduleLEFT BATTERY: Battery of the left side CPU moduleAIR IN: Air inletAIR OUT: Air outlet

Cause The CPU module temperature exceeded the specified value.

Action After checking the operation of the cooling fans, report to Yokogawa’s service depart-ment as necessary.

Remark HKU function

No. 0044Message name Control Station Cabinet Temperature Alarm Recovery

Printing example FCS0101 Temperature (RIGHT BATTERY) Recover

Meaning The abnormal temperature in the cabinet of the control station (station name =FCS0101) has been corrected. The information displayed in the Printing exampleparentheses ( ) is the same as that for No. 0043.

• ProSafe-RS

Message name Recovery from safety control station temperature alarm

Printing example SCS0101 Temperature(RIGHT BATTERY) Recover

Meaning The temperature of the safety control station (station name = SCS0101) recoverednormally. The content in the parentheses in the above example is the same as mes-sage No. 0043. (This is a recovery message of No. 0043.)

Remark HKU function

13th Edition : Dec.26,2005-00

Page 34: CS 1000/3000 Operating Messages

2-16<2. Message Output Details>

IM 33S02H10-01E

No. 0045Message name Control station power supply unit alarm

Printing example FCS0101 RIGHT PSU Alarm

Meaning Power supply unit of the internal control unit of control station (station name =FCS0101) (right side in the example) is faulty.

Action Replace the Power Supply unit.

• ProSafe-RS

Message name Power supply module alarm of safety control station

Printing example SCS0101 RIGHT PSU Alarm

Meaning The power supply module of a CPU node (right side in the above example) of thesafety control station (station name = SCS0101) is abnormal.

Cause Power supply module failure

Action Replace the applicable power supply module.

No. 0046Message name Control station power supply unit alarm recovery

Printing example FCS0101 RIGHT PSU Recover

Meaning Control station (station name=FCS0101) internal control unit power supply unit recov-ered to normal.

• ProSafe-RS

Message name Recovery from power supply module alarm of safety control station

Printing example SCS0101 RIGHT PSU Recover

Meaning The power supply module of a CPU node (right side in the above example) of thesafety control station (station name = SCS0101) recovered normally. (This is a recov-ery message of No. 0045.)

13th Edition : Dec.26,2005-00

Page 35: CS 1000/3000 Operating Messages

2-17

IM 33S02H10-01E

<2. Message Output Details>

No. 0047Message name Control unit battery alarm

Printing example FCS0101 RIGHT Battery Alarm

Meaning A control station (station name=FCS0101) battery (right side in the example) is faulty.

Action Check the switch position of the battery. If the error message occurs even when theswitch position is ON, replace the battery.

• ProSafe-RS

Message name Battery alarm of CPU module

Printing example SCS0101 RIGHT Battery Alarm

Meaning A battery of the CPU module (right side in the above example) of the safety controlstation (station name = SCS0101) is abnormal.

Cause The battery switch is OFF, or the battery is faulty.

Action Make sure that the switch of the applicable battery is ON. If the above message oc-curs even if the battery switch is ON, replace the battery.

Remark HKU function

No. 0048Message name Control unit battery alarm recovery

Printing example FCS0101 RIGHT Battery Recover

Meaning Control station (station name=FCS0101) battery (right side in the example) recoveredto normal.

• ProSafe-RS

Message name Recovery from battery alarm of CPU module

Printing example SCS0101 RIGHT Battery Recover

Meaning A battery of the CPU module (right side in the above example) of the safety controlstation (station name = SCS0101) recovered normally. (This is a recovery messageof No. 0047.)

Remark HKU function

No. 0051Message name Control Station I/O Extension Cabinet Fan Alarm

Printing example FCS0101 Fan Alarm RIO1 NODE 01 Fan (DOOR D1)

Meaning The door fan of the I/O extension cabinet containing Node 1 of RIO Bus 1 for the con-trol station (station name = FCS0101) is in abnormal state. One of the following itemsis displayed in the Printing example parentheses ( ) :DOOR D1, DOOR D2, DOOR D3, DOOR D4

Action Replace the Fan unit.

13th Edition : Dec.26,2005-00

Page 36: CS 1000/3000 Operating Messages

2-18<2. Message Output Details>

IM 33S02H10-01E

No. 0052Message name Control Station I/O Extension Cabinet Fan Alarm Recovery

Printing example FCS0101 Fan Recover RIO1 NODE 01 Fan (DOOR D1)

Meaning The door fan of the I/O extension cabinet for the control station has been restored tothe normal state. The information displayed in the Printing example parentheses ( )is the same as that for No. 0051.

No. 0053Message name Control Station I/O Extension Cabinet Temperature Alarm

Printing example FCS0101 Temperature Alarm RIO1 NODE 01 Temp (AIR IN)

Meaning The temperature in the I/O extension cabinet containing Node 1 of RIO Bus 1 for thecontrol station (station name = FCS0101) is abnormal. One of the following items isdisplayed in the Printing example parentheses ( ) :AIR IN (Air intake)AIR OUT (Air outlet)RBS (RIO bus interface card)

Action Check the operation status of cooling fans. If necessary, report the phenomenon tothe vendor’s technical service group.

No. 0054Message name Control Station I/O Extension Cabinet Temperature Alarm Recovery

Printing example FCS0101 Temperature Recover RIO1 NODE 01 Temp (AIR IN) Recover

Meaning The temperature in the I/O extension cabinet for the control station has been restoredto the normal state. The information displayed in the Printing example parentheses ( )is the same as that for No. 0053.

No. 0055Message name Online downloading communication same frame received information

Printing example1 FCS0101 Received Same Online Download Frame Code=1 Frame=3

Printing example2 FCS0101 Received Same Online Download Frame Area=1 Code = 1 Frame = 3

Meaning The same communication frame was received twice while online downloading, tun-ing parameters saving or offline loading was performed. Code and Frame indicate thedetailed internal information.

Action Execute the executed function from the start again.

• ProSafe-RS

Message name Information of same frame reception in on-line change download communication

Printing example SCS0101 Received Same Online Download Frame Code=1 Frame=3

Meaning The same communication frame was received twice during the execution of on-linechange download. “Code” and “Frame” indicate detailed internal information.

Action Execute on-line change download again.

13th Edition : Dec.26,2005-00

Page 37: CS 1000/3000 Operating Messages

2-19

IM 33S02H10-01E

<2. Message Output Details>

No. 0057Message name Online downloading error information

Printing example1 FCS0101 Online Download Error Call Code=9601-0000 Data=91, 0, 0, 0

Printing example2 FCS0101 Online Download Error Call Area= 1 Code= 9601-0000 Data = 91,0,0,0

Meaning An error was generated during control station (station name=FCS0101) online down-loading. Code and Data are the detailed internal information.

Cause The control station couldn’t save the error data.

Action What action to take must be decided according to the Code and Data information.Notify the service department of the Code and Data display contents.

Note After this alarm is generated, do not execute online downloading.

• ProSafe-RS

Message name Information of on-line change download error

Printing example SCS0101 Online Download Error Call Code=9601 - 0000 Data=91,0,0,0

Meaning An error occurred during the execution of on-line change download of the safety con-trol station (station name = SCS0101). “Code” and “Data” indicate detailed internalinformation.

Cause This error occurs if error data cannot be saved on the safety control station side.

Action It is necessary to determine an action to take based on the “Code” and “Data” infor-mation. Report the display contents of “Code” and “Data” to Yokogawa’s service de-partment.

Note Do not execute on-line change download after this alarm occurred.

No. 0059Message name Node Power Recovery Notice

Printing example1 FCS0101 RIO NODE Power On RIO1 NODE 01

Printing example2 FCS0101 FIO NODE Power On FIO1 NODE 01

Meaning Node 1 of RIO or FIO 1 of the control station(station name=FCS0101) recovered from the power failure.

• ProSafe-RS

Message name Information of recovery from node power failure

Printing example SCS0101 FIO NODE Power On FIO NODE 02

Meaning An I/O node (2 in the above example) of the safety control station (station name =SCS0101) recovered from power failure.

13th Edition : Dec.26,2005-00

Page 38: CS 1000/3000 Operating Messages

2-20<2. Message Output Details>

IM 33S02H10-01E

No. 0061Message name Control Unit RIO or IO Bus Interface Card Error

Printing example1 FCS0101 RIO Fail RIO1 RIGHT

Printing example2 FCS0101 FIO Fail FIO1 RIGHT

Meaning An error occurred in the right side communication card of RIO busor IO bus of RIO or FIO line 1of the control station (station name=FCS0101).

Action Replace RIO or IO bus communication card.

No. 0063Message name RIO or ESB Bus Error

Printing example1 FCS0101 RIO-BUS Fail RIO1 BUS No.1

Printing example2 FCS0101 IO-BUS Fail FIO1 BUS No.1

Meaning An error occurred in one side (No.1) of RIO or FIO1line of the control station (station name=FCS0101).No. shows the line (always 1 when the bus is single).

Action For the ESB bus, the failure of the coupler of SB401,SB301 (SB302) or ESB bus, orthe ESB bus itself may cause the abnormality.1) Confirm whether the ESB bus is correctly connected.Check the mis-connection with the bus, the defective connections and the termina-tors of the bus and so on.2) Confirm whether the SB401 card has caused the entire bus error with the follow-ing procedure. Pull out the T-shapeconnector of SB401 cards one by one connectedto a node on the bus node of the ESB bus. Wait for 2 or 3 seconds or more, and if “Re-cover” is not printed, insert the T-shape connector again and pull out the T-shape con-nector of the next node. If “Recover” is printed, the error must be in the SB401 cardwhere the T-shape connector was pulled out at that time.Replace the SB401.3) If the bus does not recover even after the check by pulling out the T-shape connec-tors of all nodes is ended, the coupler of the ESB bus on SB301 (or,SB302) may fail.Exchange the coupler of the ESB bus.If the bus does not recover even after this procedure, push the START/STOP switchon the front panel of the controlling CPU card twice, to pass the control to the standbyCPU card and restart. Then, replace SB301/SB302.4) If the bus does not recover even after the above operations, the error may occur inthe parts related to SI bus cable (T-shape connector, etc.)Exchange the doubted parts of the bus.

12th Edition : Mar.31,2005-00

Page 39: CS 1000/3000 Operating Messages

2-21

IM 33S02H10-01E

<2. Message Output Details>

• ProSafe-RS

Message name ESB bus error

Printing example SCS0101 FIO-BUS Fail FIO BUS No.1

Meaning An error occurred on one side (No. 1 in the above example) of the ESB buses of thesafety control station (station name = SCS0101).

Cause This is an ESB bus error on one side.

Action SSB401, SEC401 or ESB bus failure may be considered as an error cause. Takeappropriate action in the followings:• Check to see if the ESB bus cables are connected correctly. Check for incorrect con-

nection or bad connection of the cables, or check the terminators of the bus.• Check to see if one SSB401 is causing a bus error of the entire buses according to

the following procedure. Pull out the ESB bus connector of each SSB401 that con-nects to the corresponding bus, one by one, from the node.Wait for two to threeseconds, and if “Recover” is not printed, insert the ESB bus connector again, andpull the bus connector of the next node.If “Recover” is printed, the bus connector ofthe SSB401 that was pull out at that time is faulty, so replace the SSB401.

• If no recovery was made even after the bus connectors of all nodes were pulled out,the SEC401 may be faulty. In such a case, replace the SEC401.

• If no recovery was still made, press the START/STOP button on the CPU module’sfront panel on the control side twice, and switch the control right of the CPU mod-ule. Replace the CPU module after restarting.

If no recovery was still made after the above actions, it may be an ESB bus cablefailure (such as a bus connector). Replace the applicable bus.

Note This message will be notified if all the I/O nodes, excluding the CPU node, becomeabnormal.However, if a system contains Optical ESB Bus Repeater module, when all the I/Onodes directly connected to/from SEC401 (i.e., the I/O nodes not connected via Op-tical ESB Bus Repeater module), become abnormal, but the I/O nodes connected viathe Optical ESB Bus Repeater module are normal, this message will not be notified.

No. 0064Message name Recovery of RIO or ESB bus

Printing example1 FCS0101 RIO-BUS Recover RIO1 BUS No.1

Printing example2 FCS0101 IO-BUS Recover FIO1 BUS No.1

Meaning Displayed RIO or ESB bus recovered to normal.No. shows the line (always 1 when the bus is single) of the RIO bus.

• ProSafe-RS

Message name Normal recovery of ESB bus

Printing example SCS0101 FIO-BUS Recover FIO BUS No.1

Meaning The ESB bus indicated in the message recovered normally. (This is a recovery mes-sage of No. 0063.)

14th Edition : Dec.26,2006-00

Page 40: CS 1000/3000 Operating Messages

2-22<2. Message Output Details>

IM 33S02H10-01E

No. 0065Message name Node RIO or IO Bus Interface Card Error

Printing example1 FCS0101 RBS Fail RIO1 NODE 01 RBS RIGHT

Printing example2 FCS0101 SBS Fail FIO1 NODE 01 SBS RIGHT

Meaning An error occurred in the right side communication card of RIO bus (RBS) or the IO bus(SBS) of RIO or FIO line 1 of the control station (station name=FCS0101).

Action For the ESB bus, if there is no error message for the extension SB bus, the error mayhave occurred the IO bus interface card.Replace the IO bus interface card.

• ProSafe-RS

Message name Failure of ESB Bus Interface module (SSB401) of node

Printing example SCS0101 SBS Fail FIO NODE 02 SBS RIGHT

Meaning An error occurred in an ESB Bus Interface module (right side in the above example)of an I/O node (2 in the above example) of the safety control station (station name =SCS0101).

Cause One of the following causes may be considered.• ESB Bus Interface module becomes abnormal.• Connection route to the ESB Bus Interface module becomes abnormal.• For the I/O nodes that connected via Optical ESB Bus Repeater module, the Opti-

cal ESB Bus Repeater module related hardware such as module or Fiber-opticcable may have problem.

Action If an ESB bus error message has not been output, a failure of the ESB Bus Interfacemodule may be the cause. Replace the applicable ESB Bus Interface module.If an I/O node routed through the Optical ESB Bus Repeater related devices becomesabnormal, the erroneous device can be identified according to the content of themessages or the LED status so as to replace the damaged device. If all the I/O nodesrouted through the Optical ESB Bus Repeater related devices become abnormal, theerror may have occurred in the Optical ESB Bus Repeater module related hardwaresuch as module or Fiber-optic cable. Moreover, if the Optical ESB Bus Repeater mod-ules are mounted in the SNT10D, unit for Optical Bus Repeater modules, the errormay be caused by the failure of a power supply module of SNT10D unit.

No. 0066Message name RIO or IO Bus Node Interface Card Recovery

Printing example1 FCS0101 RBS Recover RIO1 NODE 01 RBS RIGHT

Printing example2 FCS0101 SBS Recover FIO1 NODE 01 SBS RIGHT

Meaning Displayed RIO or IO Bus Interface Card recovered to normal.

• ProSafe-RS

Message name Normal recovery of ESB Bus Interface module (SSB401) of node

Printing example SCS0101 SBS Recover FIO NODE 02 SBS RIGHT

Meaning An ESB Bus Interface module (right side in the above example) of an I/O node (2 inthe above example) of the safety control station (station name = SCS0101) recoverednormally. (This is a recovery message of No. 0065.)

15th Edition : Dec.10,2007-00

Page 41: CS 1000/3000 Operating Messages

2-23

IM 33S02H10-01E

<2. Message Output Details>

No. 0067Message name Node Power Supply Card Error

Printing example1 FCS0101 PSU Fail RIO1 NODE 01 PSU RIGHT

Printing example2 FCS0101 PSU Fail FIO1 NODE 01 PSU RIGHT

Meaning The right power supply card of the node No.1 of RIO or FIO line 1 of the control sta-tion (station name = FCS0101) is abnormal.

Action The problem may be caused by node error or 24 V DC power supply error. (If 24 V DCis abnormal, the node status dialog box in status display window shows [PSU] and[DC] texts in red.) If the power unit is an 80 W unit, replace the unit.

• ProSafe-RS

Message name Failure of power supply module of node

Printing example SCS0101 PSU Fail FIO NODE 02 PSU RIGHT

Meaning An error occurred in a power supply module (right side in the above example) of anI/O node (2 in the above example) of the safety control station (station name =SCS0101).

Cause Failure of a power supply module of an I/O node

Action Replace the power supply module of the applicable node.

Note When the message shows node 1, it indicates that an error occurred in a PSU for theCPU node.

No. 0068Message name Node Power Supply Card Recovery

Printing example1 FCS0101 PSU Recover RIO1 NODE 01 PSU RIGHT

Printing example2 FCS0101 PSU Recover FIO1 NODE 01 PSU RIGHT

Meaning The power supply card of the displayed node recovered to normal.

• ProSafe-RS

Message name Normal recovery of power supply module of node

Printing example SCS0101 PSU Recover FIO NODE 02 PSU RIGHT

Meaning The power supply module of the I/O node indicated in the message (2 in the aboveexample) recovered normally. (This is a recovery message of No. 0067.)

15th Edition : Dec.10,2007-00

Page 42: CS 1000/3000 Operating Messages

2-24<2. Message Output Details>

IM 33S02H10-01E

No. 0069Message name Error before database downloading to I/O module

Printing example FCS0101 IOM Download Error=A701

Meaning Downloading of I/O module database cannot start.Error=A701 is generated when database downloading to one I/O module was ex-ecuted during another database downloading to execute to the same I/O module.

Action When the contents of Error are A701, execute database downloading again after da-tabase downloading to I/O module normal end (No. 476) is output.If the Error contents are a value other than A701, notify the service department of theError display contents.

• ProSafe-RS

Message name Error before database download to I/O module

Printing example SCS0101 IOM Download Error=A701

Meaning Database download to the I/O module (IOM) can not be started.

Cause/Action The cause and action vary depending on the content of the error.• A701

This message occurs when start downloading to an IOM while downloading toanother IOM is running. Only one task for downloading to IOM can be performedat one time so that the downloading to the IOM can only be started after the down-loading to the other IOM is completed.

• 5135This message occurs when start downloading to an I/O module while the moduleis running normally.

• OthersReport the error display content to Yokogawa’s service department.

No. 0073Message name Error in bus connected between I/O unit and CPU unit

Printing example1 FCS0101 IOM-BUS Error UNIT 01 BUS No.01 RIGHT

Printing example2 FCS0101 IOM-BUS Error RIO1 NODE 01 UNIT 01 BUS No.01 RIGHT

Meaning There is an error in the internal bus connecting the control station (stationname=FCS0101) I/O unit (No. 1 unit in the example) and the CPU unit. The internalbus (FIO internal bus) is the right side or the left side. (Right side in the example.)

Action Report the message and the error code to the vendor’s technical service group.

No. 0074Message name Normal recovery of bus connecting I/O unit and CPU unit

Printing example1 FCS0101 IOM-BUS Recover UNIT 01 BUS No.01 RIGHT

Printing example2 FCS0101 IOM-BUS Recover RIO1 NODE 01 UNIT 01 BUS No.01 RIGHT

Meaning Internal bus (FIO internal bus) connecting control station (station name=FCS0101)I/O unit (No. 1 unit in the example) and CPU unit has recovered to normal.

15th Edition : Dec.10,2007-00

Page 43: CS 1000/3000 Operating Messages

2-25

IM 33S02H10-01E

<2. Message Output Details>

No. 0075Message name I/O module error (for AAM/APM)

Printing example1 FCS0101 IOM Fail UNIT 01 SLOT 01 IOM 01

Printing example2 FCS0101 IOM Fail RIO1 NODE 01 UNIT 01 SLOT 01 IOM 01

Meaning An error was generated in I/O module No. 1 mounted in slot No. 1 of unit No. 1 of thecontrol station (control station name=FCS0101).

Action Replace the I/O module.

No. 0076Message name I/O module normal recovery (for AAM/APM)

Printing example1 FCS0101 IOM Recover UNIT 01 SLOT 01 IOM 01

Printing example2 FCS0101 IOM Recover RIO1 NODE 01 UNIT 01 SLOT 01 IOM 01

Meaning I/O module No. 1 mounted in slot No. 1 of unit No. 1 of the control station (stationname=FCS0101) has recovered to normal.

No. 0077Message name I/O module database error (for AAM/APM)

Printing example1 FCS0101 IOM Configuration Error UNIT 01 SLOT 01 IOM 01

Printing example2 FCS0101 IOM Configuration Error RIO1 NODE 01 UNIT 01 SLOT 01 IOM 01

Meaning An error was generated in the database for I/O module No. 1 mounted in slot No. 1 ofunit No. 1 of the control station (station name=FCS0101).

Action When discrepancy of an I/O module and the I/O module information in FCS databaseis detected, this alarm occurs.If this alarm occurs when starting an I/O module after installation of the I/O module,the information in FCS database may not be properly downloaded to the I/O module.In this case, run IOM download.If this alarm occurs when an I/O module is running, the I/O module becomes malfunc-tion. In this case, replace the I/O module.

No. 0079Message name I/O module communication error (for AAM/APM)

Printing example1 FCS0101 IOM Communication Error UNIT 01 SLOT 01 IOM 01 RIGHT

Printing example2 FCS0101 IOM Communication Error RIO1 NODE 01 UNIT 01 SLOT 01 IOM 01RIGHT

Meaning An error was generated when accessing the I/O module No. 1 mounted in slot No. 1of unit No. 1 of the control station (station name=FCS0101).

Action Report this message to vendor’s technical service group.

13th Edition : Dec.26,2005-00

Page 44: CS 1000/3000 Operating Messages

2-26<2. Message Output Details>

IM 33S02H10-01E

No. 0080Message name I/O module communication error recovery (for AAM/APM)

Printing example1 FCS0101 IOM Communication Recover UNIT 01 SLOT 01 IOM RIGHT

Printing example2 FCS0101 IOM Communication Recover RIO1 NODE 01 UNIT 01 SLOT 01 IOM 01RIGHT

Meaning Communication with the relevant IOM 1 mounted in slot No.1 of unit No.1 of the con-trol station (station name = FCS0101) recovered to normal.

No. 0081Message name I/O Module Error (ADM/AMM, FIO related)

Printing example1 FCS0101 IOM Fail UNIT 01 SLOT 01

Printing example2 FCS0101 IOM Fail RIO1 NODE 01 UNIT 01 SLOT 01

Printing example3 FCS0101 IOM Fail FIO1 NODE 01 SLOT 01

Meaning An error occurred in the I/O module mounted in slot No.1 of unit No.1 of the controlstation (station name = FCS0101).

Action Replace the I/O module.

• ProSafe-RS

Message name Failure of I/O module

Printing example SCS0101 IOM Fail FIO NODE 01 SLOT 01 Code=5101

Meaning An error occurred in the I/O module mounted in slot 1 of node 1 (CPU node) of thesafety control station (station name = SCS0101).

Cause For more information about error codes, see the table below.

Action Replace the applicable I/O module.

Table Error Details of Message No.0081 - Errors of Analog Input Modules and Contact I/OModules

Error code Description of error

5101

5102

5103

5104

5105

5106

5107

5114, 5115

5116, 5117

5118

5111, 5112,5113

The communication between CPU and I/O modules encounters a no-response error. This error is caused either by the I/O module abnormality or by the communication route abnormality.

The type of the I/O module defined on the SENG and the type of the I/O module mounted do not match. Check the type of the I/O module.

The setting information defined on the SENG and the I/O module setting information do not match. Execute IOM download.

A setting error of the I/O module. Check detailed error causes in the IOM report (field side connector disconnection, field power supply/wiring problem, etc.)

The error that actuated the output shutoff switch occurred. Check detailed error causes in the IOM report. When this error occurred, start the I/O module after recovering from the error.

A communication data check error was detected between the CPU and the I/O module. A failure of the I/O module or a problem of the communication path up to the I/O module may be the cause.

A hardware error of the I/O module was detected. Check detailed error causes in the IOM report.

The I/O module recovered from an error state. Check detailed error causes in the IOM report.

An error was detected in the redundant control part of the I/O module. Replace the I/O module.

An I/O module error was detected. Replace the I/O module.

An SCS internal error (SCS database error) was detected.008101E.EPS

13th Edition : Dec.26,2005-00

Page 45: CS 1000/3000 Operating Messages

2-27

IM 33S02H10-01E

<2. Message Output Details>

Table Error Details of Message No.0081 - ALR111/ALR121 Modbus Slave

Error code Cause/Action

C580

C581

C582

C583

The communication between CPU and I/O modules encounters a no-response error. This error may be caused by the I/O module abnormality, communication route abnormality or an abnormality other than C581 to C583 depicted.

The communication program is not downloaded to the communication module. Run IOM download.

The communication program in the communication module is not the program for Modbus slave communication. Run IOM download.

The physically installed communication module shows a different model name from the communication module defined in SENG. Check the model of the communication module.

008102E.EPS

Table Error Details of Message No.0081 - ALR111/ALR121 Subsystem Communication

Error code Cause/Action

A33D

A33E

C581

C582

C583

C585

C598

C59A

C5C1

C5C6

C599

No response from the communication module due to communication module abnormality. Change the communication module.

Error occurred in the communication route between CPU and node.

The communication program is not downloaded to the communication module. Run IOM download.

The physically installed communication module shows a different model name from the communication module defined in SENG. Check the model of the communication module.

The communication module is reset due to on-line change download or the IOM downloading.

Downloading to database. This error code will be displayed only in IOM report.

The communication program in the communication module is not the program for the communication defined in SENG. Run IOM download.

Error is found by self-diagnosis. Change the communication module.

Downloading communication program. This error code will be displayed only in IOM report.

Error found after resetting the communication module. Change the communication module.

Failed to download the communication program. Waiting time for shifting to downloading communication program mode became timeout. Run IOM download again.

C5C7 Failed to download the communication program. Processing time for downloading communication program became timeout. Run IOM download again.

C5E2 Communication module encountered an error and stopped. Change the communication module.008103E.EPS

13th Edition : Dec.26,2005-00

Page 46: CS 1000/3000 Operating Messages

2-28<2. Message Output Details>

IM 33S02H10-01E

No. 0082Message name I/O Module Recovery (ADM/AMM, FIO related)

Printing example1 FCS0101 IOM Recover UNIT 01 SLOT 01

Printing example2 FCS0101 IOM Recover RIO1 NODE 01 UNIT 01 SLOT 01

Printing example3 FCS0101 IOM Recover FIO1 NODE 01 SLOT 01

Meaning The displayed I/O module mounted in slot No.1 of unit No.1 of the control station (sta-tion name = FCS0101) recovered to normal.

• ProSafe-RS

Message name Normal recovery of I/O module

Printing example SCS0101 IOM Recover FIO NODE 01 SLOT 01

Meaning The I/O module mounted in slot 1 of node 1 in the safety control station (station name= SCS0101) recovered normally. (This is a recovery message of No. 0081.)

No. 0083Message name I/O Module Database Error (ADM/AMM, FIO related)

Printing example1 FCS0101 IOM Configuration Error UNIT 01 SLOT 01

Printing example2 FCS0101 IOM Configuration Error RIO1 NODE 01 UNIT 01 SLOT 01

Printing example3 FCS0101 IOM Configuration Error FIO1 NODE 01 SLOT 01

Meaning An error occurred in database of the I/O module mounted in slot No.1 of unit No.1 ofthe control station (station name = FCS0101).

Action This error occurs when the database in IOM does not agree with that in FCS. Thereis a possibility that the database is not downloaded in the input-output module for er-rors such as after exchanging the module and on starting. Execute the IOM loading.There is a possibility of the error of the I/O module if this error occurred while the I/Omodule is working. Replace the I/O module.

• ProSafe-RS

Message name I/O module database error occurred

Printing example SCS0101 IOM Configuration Error FIO NODE 01 SLOT 01

Meaning An error occurred in the database on the I/O module mounted in slot 1 of node 1 inthe safety control station (station name = SCS0101).

Cause The database on the I/O module and the database on the SCS do not match. Thefollowing causes may be considered.• IOM download has not been executed.• IOM failure

Action If this error occurred after replacing a module or at startup, the database might nothave been downloaded to the I/O module. Execute IOM download.If this error occurred during I/O module operation, the I/O module may be faulty. Re-place the I/O module.

13th Edition : Dec.26,2005-00

Page 47: CS 1000/3000 Operating Messages

2-29

IM 33S02H10-01E

<2. Message Output Details>

No. 0085Message name I/O Module Communication Error (ADM/AMM, FIO related)

Printing example1 FCS0101 IOM Communication Error UNIT 01 SLOT 01 RIGHT

Printing example2 FCS0101 IOM Communication Error RIO1 NODE 01 UNIT 01 SLOT 01 RIGHT

Printing example3 FCS0101 IOM Communication Error FIO1 NODE 01 SLOT 01

Meaning An error occurred when accessing the I/O module mounted in slot No.1 of unit No.1of the control station (station name = FCS0101).In case of FIO, if all modules in the same node have communication errors, the nodebackboard bus may fail. In case of local node, the ESB bus or SB401 card may haveabnormality or disconnection.

Action Report this message to vendor’s technical service group.

• ProSafe-RS

Message name I/O module communication error occurred

Printing example SCS0101 IOM Communication Error FIO NODE 01 SLOT 01 RIGHT

Meaning An error occurred in one of the SB buses (right side in the above example). An erroroccurred when accessing the I/O module mounted in slot 1 of node 1 in the safety con-trol station (station name = SCS0101).

Cause If this error occurred on all input modules within the same node, an I/O module maybe faulty, or the backboard bus of the node may be faulty. Or, an ESB bus or anSSB401 may be faulty, or they may not be connected properly.

Action Report to Yokogawa’s service department.

No. 0086Message name I/O Module Communication Recovery (ADM/AMM, FIO related)

Printing example1 FCS0101 IOM Communication Recover UNIT 01 SLOT 01 RIGHT

Printing example2 FCS0101 IOM Communication Recover RIO1 NODE 01 UNIT 01 SLOT 01 RIGHT

Printing example3 FCS0101 IOM Communication Recover FIO1 NODE 01 SLOT 01

Meaning The communication with the I/O module mounted in the slot 1 of unit No.1 in the controlstation (station name = FCS0101) recovered.

• ProSafe-RS

Message name Recovery from I/O module communication error

Printing example SCS0101 IOM Communication Recover FIO NODE 01 SLOT 01 RIGHT

Meaning A communication error with the I/O module mounted in slot 1 of node 1 in the safetycontrol station (station name = SCS0101) recovered. (This is a recovery message ofNo. 0085.)

13th Edition : Dec.26,2005-00

Page 48: CS 1000/3000 Operating Messages

2-30<2. Message Output Details>

IM 33S02H10-01E

No. 0087Message name Node Error

Printing example1 FCS0101 NODE Fail RIO1 NODE 01

Printing example2 FCS0101 NODE Fail FIO1 NODE 01

Meaning An error occurred in the node No.1 of RIO or FIO line 1 of the control station (stationname=FCS0101).

Cause The node power failure; Both control and backup RIO and IO bus cards fail, or bothcontrol and backup RB401 and SB401 cards fail.

• ProSafe-RS

Message name Node error occurred

Printing example SCS0101 NODE Fail FIO NODE 02

Meaning An error occurred in node 2 of the safety control station (station name = SCS0101).

Cause One of the following causes may be considered.• A power failure occurred in the node, or both of the two ESB buses are abnormal.• Both SSB401 are abnormal.• For the I/O nodes that connected via Optical ESB Bus Repeater module, the Opti-

cal ESB Bus Repeater module related hardware such as module or Fiber-opticcable may have problem.

Action Report to Yokogawa’s service department.

No. 0088Message name Node Recovery

Printing example1 FCS0101 NODE Recover RIO1 NODE 01

Printing example2 FCS0101 NODE Recover FIO1 NODE 01

Meaning The displayed node returned to normal.

• ProSafe-RS

Message name Normal recovery of node

Printing example SCS0101 NODE Recover FIO NODE 02

Meaning The node indicated in the message recovered normally. (This is a recovery messageof No. 0087.)

14th Edition : Dec.26,2006-00

Page 49: CS 1000/3000 Operating Messages

2-31

IM 33S02H10-01E

<2. Message Output Details>

No. 0089Message name Subsystem Communication Error

Printing example1 FCS0101 SS-COM Error UNIT 01 SLOT 02 STN002 Code= A3B0

Printing example2 FCS0101 SS-COM Error RIO1 NODE 03 UNIT 01 SLOT 02 STN002 Code= A3B0

Printing example3 FCS0101 SS-COM Error FIO1 NODE 01 SLOT 01 PORT 01 STN001 Code= A3B0

Meaning The displayed card or module encountered an error when communicating with theconnected subsystems.

Action The error details can be found in the instruction manuals of the connected subsystem.See the manuals for error details.

SEE ALSO

For more information about the error code details, see the followings:

FIO Related:

K2.2, “System Alarm Messages”

K3.8, “System Alarm Messages Specific to FA-M3”

K4.8, “System Alarm Messages Specific to MELSEC-A”

K5.9, “System Alarm Messages Specific to Modbus PLC”

K6.6, “System Alarm Messages Specific to YS Instruments”

K7.8, “System Alarm Messages Specific to FA-M3”

K8.9, “System Alarm Messages Specific to MELSEC”

K9.8, “System Alarm Messages Specific to PLC-5/SLC 500”

K10.8, “System Alarm Messages Specific to PLC-5”

K11.7, “System Alarm Messages Specific to SLC 500”

K12.9, “System Alarm Messages Specific to Modbus/TCP PLC”

K13.6, “System Alarm Messages Specific to YS Instruments”

RIO Related:

J2.3, “System Alarm Messages Specific to the Communication Module”

J2.4, “System Alarm Messages Specific to Ethernet Communication”

J3.7, “System Alarm Messages Specific to FA-M3”

J4.8, “System Alarm Messages Specific to FA-M3”

J5.8, “System Alarm Messages Specific to DARWIN”

J6.7, “System Alarm Messages Specific to Gas Chromatography”

J7.6, “System Alarm Messages Specific to YS Instruments”

J8.8, “System Alarm Messages Specific to MELSEC-A”

J9.9, “System Alarm Messages Specific to MELSEC-A”

J10.10, “System Alarm Messages Specific to Modbus PLC”

J11.8, “System Alarm Messages Specific to PLC-5”

J12.8, “System Alarm Messages Specific to SYSMAC”

J13.8, “System Alarm Messages Specific to SIMATIC S5”

J14.10, “System Alarm Messages Specific to DARWIN/DAQSTATION”

J15.7, “System Alarm Messages Specific to SLC 500”

J16.8, “System Alarm Messages Specific to PLC-5/SLC 500”

J17.9, “System Alarm Messages Specific to Modbus/TCP PLC”

13th Edition : Dec.26,2005-00

Page 50: CS 1000/3000 Operating Messages

2-32<2. Message Output Details>

IM 33S02H10-01E

• ProSafe-RS

Message name Subsystem communication error

Printing example SCS0101 SS-COM Error FIO NODE 01 SLOT 01 PORT 01 STN001 Code=A3B0

Meaning A communication error occurred between the indicated communication module andthe subsystem.

Cause/Action The error details can be found in the instruction manuals of the connected subsystem.See the manuals for error details.The error codes that irrelevant to the connected subsystems are shown below:

Remark Subsystem communication

Table Error Details of Message No.0089 - Errors that irrelevant to subsystems

Code Errors Cause/Action

A391

A392

A393

A394

A395

A397

A398

A39A

A39B

A39C

A399

Occurs when sending or receiving.

This message occurs when carrier detection fails due to the CD line is energized within the transmission enable monitoring time.

This message occurs when clear to send fails due to the CS line is not energized within the transmission enable monitoring time, or when data ready fails due to the DR line is not energized within the transmission enable monitoring time. (*1)

This message occurs when the interval of characters exceeds the specified time.

A39D

A39F

A3B0 to A3FF

Driver Busy

Communication Line Busy

Communication Line Not Ready

Data size is too large for sending.

The port for sending is not declared.

Underrun

Interval of characters became timeout

Reception parity error

Reception overrun

Reception frame error

Reception buffer overflow

Number of characters beyond range

Other errors

Reserved for subsystems For more information, see the instruction manuals of subsystems.008901E.EPS

*1: The transmission-watching timer monitors the waiting time of the transmission line become ready for transmission.When RS is sent, and the waiting time for transmission exceeds the specified time period, the transmission becomeserror.The transmission waiting time is normally set to 1000 ms.The conditions for transmission are as follows:• CD line off (When CD check is enabled)• CS (CTS) line on• DR line on (When DR check is enabled)

15th Edition : Dec.10,2007-00

Page 51: CS 1000/3000 Operating Messages

2-33

IM 33S02H10-01E

<2. Message Output Details>

No. 0090Message name Subsystem Communication Recovery

Printing example1 FCS0101 SS-COM Recover UNIT 01 SLOT 02 STN002

Printing example2 FCS0101 SS-COM Recover RIO1 NODE 03 UNIT 01 SLOT 02 STN002

Printing example3 FCS0101 SS-COM Recover FIO1 NODE 01 SLOT 01 PORT 01 STN001

Meaning The communication between the displayed communication module (ACM/ALR/ALE)and the connected subsystems recovered.

• ProSafe-RS

Message name Subsystem communication recovered

Printing example SCS0101 SS-COM Recover FIO NODE 01 SLOT 01 PORT 01 STN001

Meaning The communication between the indicated communication module and the subsystemrecovered from the error.

Remark Subsystem communication

No. 0091Message name Failing Node Housekeeping Unit in the I/O Expansion Cabinet

Printing example FCS0101 RIO HKU Error RIO1 Node 01 Code=0001

Meaning The housekeeping unit in the I/O expansion cabinet in which node 1 of RIO bus 1 inthe control station (station name = FCS0101) has failed. The error code (Code) pro-vides detailed internal information.

Action Report this message to vendor’s technical service group.

No. 0092Message name Node Housekeeping Unit in the I/O Expansion Cabinet Recovery

Printing example FCS0101 RIO HKU Recover RIO1 Node 01 Code=0001

Meaning The housekeeping unit in the I/O expansion cabinet has been restored to the normalstate.

No. 0093Message name Control Unit Housekeeping Unit Error

Printing example FCS0101 RIGHT HKU Error Code=0001

Meaning An error occurred in the right housekeeping unit of the intelligence section (control unit)for the control station (station name = FCS0101). The Code shows detailed internalinformation.

Action Report this message to vendor’s technical service group.

13th Edition : Dec.26,2005-00

Page 52: CS 1000/3000 Operating Messages

2-34<2. Message Output Details>

IM 33S02H10-01E

• ProSafe-RS

Message name CPU node’s housekeeping unit error

Printing example SCS0101 RIGHT HKU Error Code=0001

Meaning The CPU node’s housekeeping unit of the safety control station (station name =SCS0101) is faulty. “Code” indicates detailed internal information.

Action Report to Yokogawa’s service department.

Remark HKU function

No. 0094Message name Control Unit Housekeeping Unit Error Recovery

Printing example FCS0101 RIGHT HKU Recover Code=0001

Meaning The housekeeping unit of the control unit has been restored to the normal state.

• ProSafe-RS

Message name Normal recovery of CPU node’s housekeeping unit

Printing example SCS0101 RIGHT HKU Recover Code=0001

Meaning The CPU node’s housekeeping unit of the safety control station (station name =SCS0101) recovered normally. (This is a recovery message of No. 0093.)

Remark HKU function

No. 0098Message name System alarm normal recovery

Printing example FCS0101 arbitrary character string

Meaning User-defined system alarm recovered to normal.

• In case of GSGW

Message name OPC communication recovered

Printing example GSGW0101 OPC-PLC Communication Recover OPCFGW1 WW1024

Meaning The communication of the 1024th word specified on subsystem communication I/Omodule (Program = OPCFGW1) recovered.

13th Edition : Dec.26,2005-00

Page 53: CS 1000/3000 Operating Messages

2-35

IM 33S02H10-01E

<2. Message Output Details>

No. 0099Message name System alarm

Printing example FCS0101 arbitrary character string

Meaning User-defined system alarm was generated.

• In case of GSGW

Message name OPC Communication Error

Printing example GSGW0101 OPC-PLC Communication Error OPCFGW1 WW1024 CODE=A334-C0040007

Meaning The communication of the 1024th word specified on subsystem communication I/Omodule (Program = OPCFGW1) encountered an error. Error category code: 0xA334;Error detail code: 0xC0040007.OPCFGW1 – OPCFGW4:Program name can be specified on subsystem communication I/O module

WW0000 – WW3998:The first communication word assigned for communication I/O

Error Code:A combination of four-digit error category code and eight-digit error detail code

SEE ALSO

For more information about error category code and error detail code, see the following:

Q4.1, “System Alarm Messages”

13th Edition : Dec.26,2005-00

Page 54: CS 1000/3000 Operating Messages

2-36<2. Message Output Details>

IM 33S02H10-01E

2.2 Control Station Messages of Other Systems(Message Nos. 0101 to 0198)This section explains the messages output from the control stations (FCSes) of thesystem other than CENTUM CS , CS 1000 and CS 3000.

No. 0101Message name Control Station System Alarm

Printing example STN1701 Power ON Start

Cause The control station of CENTUM-XL or �XL has been powered on and started or re-set and started, or the control right has been switched in a duplexed FCS.

No. 0103Message name Control Station System Alarm

Printing example STN1701 Power ON Start

Cause A control station other than CENTUM-XL or �XL has been powered on and startedor reset and started, or the control right has been switched in a duplexed FCS.

No. 0105Message name Upload Error

Printing example STN1701 Upload Error

Meaning A communication error occurred when the backup controller BCU of CFBS2 wasuploading the contents of the memory of CFCU2. Since this is a temporary error, itdoes not inhibit the implementation of the next uploading.

Cause/Action NM1 error in CFCU2 (Memory No Response has occurred.):Replace the defective card.

NC1 error in BCU: Replace the defective card.NC1 error in CFCU2: Replace the defective card.

Note: If a CI-Bus error occurs during the uploading, this message is not output becauseanother CI-Bus is used automatically. The CI-Bus error of No. 0111 is reported.

No. 0106Message name Upload Recovery

Printing example STN1701 Upload Recover

Meaning Upload could be performed correctly after an error (Message No. 0105).

13th Edition : Dec.26,2005-00

Page 55: CS 1000/3000 Operating Messages

2-37

IM 33S02H10-01E

<2. Message Output Details>

No. 0107Message name CI-Bus Failure

Printing example STN1701 CI-BUS 2 Fail

Meaning An error occurred in the CI-Bus, which is an internal bus of CFBS2. The error wasdetected as a result of the CIU19.CI-Bus check (every second).

Cause CI-Bus errorNC1 error in BCU (*1)NC1 error in all CFCU2s (*1)

*1: No. 0109 is also output at the same time.

Action Replace the NC1 card or connecting coaxial cable.

No. 0108Message name CI-Bus Recovery

Printing example STN1701 CI-BUS 2 Recover

Meaning The CI-Bus of CFBS2 has been restored to the normal state.

No. 0109Message name Nest Common Card Error

Printing example STN1701 NCM 2 Fail

Meaning An error occurred on the nest common card of CFBS2. The error was detected as aresult of the check by CIU (every second).

Cause CI-Bus errorNC1 error in BCU (*1)NC1 error in all CFCU2s (*1)

*1: If the NC1 in the CIU is defective, this alarm occurs in both CFCU2 and BCU.

Action Replace the NC1 card or connecting coaxial cable.

No. 0110Message name Nest Common Card Error Recovery

Printing example STN1701 NCM 2 Recover

Meaning The nest common card of CFBS2 has been restored to the normal state.

13th Edition : Dec.26,2005-00

Page 56: CS 1000/3000 Operating Messages

2-38<2. Message Output Details>

IM 33S02H10-01E

No. 0111Message name CI-Bus Error

Printing example STN1701 Cl-Bus 2 Error 15 TO 7 Code=21

Meaning A CI-Bus error was detected in the CIU or BCU of CFBS2. This is a communicationerror that may occur during the uploading of data by BCU or monitoring of CFCU2 byCIU.

Cause/Action See the table below.

Code Name Meaning Cause/Operator action/Explanation

0021 CI-Bus No Response No CI-Bus response

• Power has failed at the equipment to which theCI-Bus is connected.

• NC1 failure• Disconnected NC-Bus

0022 CI-Bus Frame ErrorA CRC check error at the receptionside of the command frame has beendetected.

• Send NC1 failure• Receive NC1 failure• CI-Bus failure

0023 CI-Bus Transmission FailA communication request from NC1 cannot be issued.

• No data have been output on the line after sending a communications request.

• NC1 failure

0028 Line Busy The CI-Bus is busy. BCU’s or CIU’s NC1 error

002B Micro Check A CI-Bus micro diagnostic error hasbeen detected.

A micro-diagnostic error has been issued from the send or receive circuit.

011100E.EPS

No. 0113Message name BCU FC1 Failure

Printing example STN1701 BCU-FC1 Fail

Meaning During the self-diagnosis of BCU or periodical communication from CIU to BCU, anerror was detected from the FC1 of BCU (No Response or Frame Error).

Cause BCU FC1 or coupler error

No. 0114Message name BCU FC1 Recovery

Printing example STN1701 BCU FC1 Recover

Meaning The FC1 of BCU has been restored to the normal state.

No. 0115Message name Control Station Duplex Control Section Error

Printing example STN1701 Duplex Controller Fail

Meaning The duplex control section does not work.

Cause An error was detected by the self-diagnosis of the duplex control section.

Action Report this message to vendor’s technical service group.

13th Edition : Dec.26,2005-00

Page 57: CS 1000/3000 Operating Messages

2-39

IM 33S02H10-01E

<2. Message Output Details>

No. 0116Message name Control Station Duplex Control Section Error Recovery

Printing example STN1701 Duplex Controller Recover

Meaning The duplex control section has been restored to the normal state.

No. 0117Message name Control Station Equalize Error

Printing example STN1701 Equalize Error

Meaning An error occurred in the equalization of the data between control side and standbyside.

Cause/Action • For CFCD2, CFCDE, and CFSD :The error was probably caused by the failure of DXS2 or standby memory (it mayhave been caused by the failure of the CTL2 or FCA4 card also). Replace DXS2first, and if the error is not corrected, replace the memory card on the standby side.

• For EFCD and EFCE :The error was probably caused by the failure of DX11 or standby memory (it mayhave been caused by the failure of the CP11 or FC11 card also). Replace DX11 first,and if the error is not corrected, replace the memory card on the standby side.

• For MFCD :The error was probably caused by the failure of the NP card on the standby side.Replace the NP card on the standby side first, and if the error is not corrected, re-place that on the control side.

No. 0118Message name Control Station Equalize Error Recovery

Printing example STN1701 Equalize Recover

Meaning The equalization function of the duplex control section has been normalized.

No. 0119Message name Control Station Self-diagnosis Error

Printing example STN1701 F-Diagnose Error

Meaning An error occurred in the check communication from the control side to the standbyside.

Cause/Action • For CFCD2, CFCDE, and CFSD :The error was probably caused by the failure of the FCA4 card on the standby side.Replace the FCA4 card on the standby side first, and if the error is not corrected,replace the FCA4 card on the control side.

• For EFCD and EFCE :The error was probably caused by the failure of the FC11 card on the standby side.Replace the FC11 card on the standby side first, and if the error is not corrected, re-place the FC11 card on the control side.

15th Edition : Dec.10,2007-00

Page 58: CS 1000/3000 Operating Messages

2-40<2. Message Output Details>

IM 33S02H10-01E

No. 0120Message name Control Station Self-diagnosis Error Recovery

Printing example STN1701 F-Diagnose Recover

Meaning The check communication from control side to standby side has been restored to thenormal state.

No. 0121Message name Control Station SI-Bus Communication Card Error

Printing example STN1701 SI-BUS Controller Fail

Meaning A No Response error occurred in the access to a register in the SI11 communicationcard. Or data unmatch was detected by CKR when reading/writing the check data.

Cause The SI11 communication card is defective. Replace the SI11 card.

No. 0122Message name Control Station SI11 Communication Card Error Recovery

Printing example STN1701 SI-BUS Controller Recover

Meaning The SI11 card has been restored to the normal state.

No. 0123Message name Control station Nest Common Card Error

Printing example STN1701 NCM Fail NEST1 NCM1

Meaning A No Response error occurred when reading a register on the nest common card (thiserror also occurs even when the nest common card maintenance switch is set to theMAINT position).If the nest common card is duplexed, the No Response error occurred in one of theSI-Buses used for the access of the I/O card (this means that a failure occurred in Bus1 of the nest common card).

Action Set the maintenance switch of the nest common card to the NORM position. If theerror is not corrected yet, replace the nest common card.

No. 0124Message name Control Station Nest Common Card Error Recovery

Printing example STN1701 NCM Recover NEST1 NCM1

Meaning The nest common card has been restored to the normal state (Bus 1 of the nest com-mon card has recovered).

13th Edition : Dec.26,2005-00

Page 59: CS 1000/3000 Operating Messages

2-41

IM 33S02H10-01E

<2. Message Output Details>

No. 0125Message name Control Station SI-Bus Error

Printing example STN1701 SI-Bus1 Fail

Meaning An error occurred in the parts related to the SI-Bus.

Cause SI11 card, the bus connector of SI11 or nest common card may be defective.

Action Take the following actions.1.The nest common cards connected to the error bus should be extracted from the

I/O nest one by one. After extracting one card, wait for at least 1 second, and if RE-COVER is not printed out, insert that card into the nest and extract the next card.If RECOVER is printed out, the card just extracted is defective and it must be re-placed.

2. If the error is not corrected after all the nest common cards have been checked, itmay be due to the SI communication card. Replace the SI communication card aftertransferring the control right by the Mode switch.

3. If the error still persists after the above measures, it may be due to the failure of SIbus cable. Replace the relevant bus cable.

No. 0126Message name Control Station SI Bus Error Recovery

Printing example STN1701 SI-Bus1 Recover

Meaning The SI bus has been restored to the normal state.

No. 0127Message name Control Station SI11 Communication Card Fuse Blow Out

Printing example STN1701 VTT FUSE1 Blow SI-Bus Controller

Meaning The VTT fuse in the SI communication card has blown out.

Action Replace the SI communication card.

No. 0128Message name Control Station SI11 Communication Card Fuse Recovery

Printing example STN1701 VTT FUSE1 Recover SI-Bus Controller

Meaning The VTT fuse in the SI11 communication card has been restored to the normal state.

No. 0129Message name Control Station Nest Common Card Fuse Blow Out

Printing example STN1701 VTT FUSE Blow NEST1 NCM1

Meaning The VTT fuse in the nest common card has blown out.

Action Replace the nest common card.

13th Edition : Dec.26,2005-00

Page 60: CS 1000/3000 Operating Messages

2-42<2. Message Output Details>

IM 33S02H10-01E

No. 0130Message name Control Station Nest Common Card Fuse Recovery

Printing example STN1701 VTT FUSE Recover NEST1 NCM1

Meaning The VTT fuse in the nest common card has been restored to the normal state.

No. 0131Message name Control Station AC Power Failure

Printing example STN1701 AC Fail

Meaning The AC power for the control station failed, but recovered before it affects the inter-nal DC power supply.

Note: This message is output after the power has recovered.

No. 0133Message name Control Station AC Power Failure

Printing example STN1701 AC Fail (TIME 93.10.09 18:45)

Meaning The AC power for the station failed.Note: This message is output after the power has recovered. For EFCS-H2, EFCD-H2,

and EFCE-H2, the value of TIME becomes effective if the time and date are setby the EOPS operator station.

No. 0135Message name Control Station Task Abnormal Termination or Termination by Exception Interrupt

Printing example STN1701 TASK=ABCD Abort Code=8010

Meaning This message is output for the EMCS/EMCD master control station. The displayedabort code is the abort code generated when the task was terminated.

Action Report this message to vendor’s technical service group.

No. 0137Message name Control station Power ON. (Hot Start)

Printing example STN1701 Power ON (Hot Start)

Meaning The control station has been powered on and started (hot start).Related Models: EFCS/D-H2, EFCS/D-H4, EFCE-H2, EMCS/D, EMCS/D-H4,

ECGW2.

13th Edition : Dec.26,2005-00

Page 61: CS 1000/3000 Operating Messages

2-43

IM 33S02H10-01E

<2. Message Output Details>

No. 0139Message name Control station Power ON. (Cold Start)

Printing example STN1701 Power ON (Cold Start)

Meaning The control station has been powered on and started (initial cold start).Related Models: EFCS/D-H2, EFCS/D-H4, EFCE-H2, EMCS/D, EMCS/D-H4,

ECGW2.

No. 0141Message name Control Station Reset Start

Printing example STN1701 Reset Start

Meaning The control station has been reset and started.Related Models: EFCS/D-H2, EFCS/D-H4, EFCE-H2, EMCS/D-H4, ECGW2.

No. 0143Message name EMCS/EMCD Reset Start

Printing example STN1701 Reset Start

Meaning The EMCS/EMCD master control station has been reset and started.

No. 0151Message name Control Station I/O Card Error

Printing example1 STN1701 Nest Error NEST1 CARD01 CH.00

Printing example2 STN1701 Nest Error NEST1 CARD01 CH.02

Meaning • For Printing example1, A No Response error was detected when making access tothe indicated card in the control station.

• For Printing Printing example2, An IOP error occurred on either the in-service sideor the standby side of MAC2 card (CARD01, CH.02) (the service right is not trans-ferred), or the IOP status on the in-service side is different from that on the standbyside.

• When FA500 is connected :Error in the access to RS4 card if the channel number is 0. Error in the communi-cation with FA500 if the channel number is other than 0. (The channel number is thestation number of the relevant FA500.)

Cause/Action • The card is not mounted.Mount the card.

• The slot in which the card is actually mounted is different from the I/O card slotspecified by the builder function.Mount the card in the slot specified by the builder function.

• Failure of the card itself.Replace the card.

• The value of the voltage supplied to the card is below the rated value.Check the power supply. Replace the I/O card.

• Backboard connector or PC board failureReplace the nest.

13th Edition : Dec.26,2005-00

Page 62: CS 1000/3000 Operating Messages

2-44<2. Message Output Details>

IM 33S02H10-01E

No. 0152Message name Control Station I/O Card Error Recovery

Printing example1 STN1701 Nest Normal NEST1 CARD01 CH.00

Printing example2 STN1701 Nest Normal NEST1 CARD01 CH.02

Meaning • For Printing example1, The indicated card has been restored to the normal state af-ter the output of Message 0151 (I/O Card Error). Detection of the recovery takes 2to 8 seconds.

• For Printing example2, Both the in-service side and standby side of the MAC2 card(CARD01, CH.02) are free from IOP error, or the difference in IOP status betweenthe in-service side and standby side has disappeared.

• When FA500 is connected :Recovery of access to RS4 card if the channel number is 00. The recovery messageis output when the RS4 is accessed correctly and the communication from the RS4to FA500 is restored to the normal state. Recovery of communication with FA500if the channel number is other than 00. (The channel number is the station numberof the relevant FA500.)

No. 0153Message name Control Station I/O Card Error

Printing example STN1701 Nest Error CARD01 CH.00

Meaning A No Response error was detected when making access to the indicated card.

Cause/Action • The card is not mounted.Mount the card.

• The slot in which the card is actually mounted is different from the I/O card slotspecified by the builder function.Mount the card in the slot specified by the builder function.

• Failure of the card itself.Replace the card.

• The value of the voltage supplied to the card is below the rated value.Check the power supply.

• Backboard connector or PC board failure.Replace the nest.

No. 0154Message name Control Station I/O Card Error Recovery

Printing example STN1701 Nest Normal CARD01 CH.00

Meaning The indicated card has been restored to the normal state after the output of Message0153 (I/O Card Error). Detection of the restoration takes 1 or 2 seconds.

No. 0155Message name Control Station I/O Nest Power Supply Card Error

Printing example STN1701 PSU Fail NEST1 PSU2

Meaning A power supply error occurred in the indicated I/O nest power card of the indicatedstation. The error was detected by the PSU diagnosis.

Action Replace the power supply card of the I/O nest.

13th Edition : Dec.26,2005-00

Page 63: CS 1000/3000 Operating Messages

2-45

IM 33S02H10-01E

<2. Message Output Details>

No. 0156Message name Control Station I/O Nest Power Supply Card Error Recovery

Printing example STN1701 PSU Recover NEST1 PSU2

Meaning The power supply card in the I/O Nest of the indicated station has been restored tothe normal state.

No. 0157Message name Control Station Power Supply Card Error

Printing example STN1701 PSU Fail PSU2

Meaning A power supply error occurred in the indicated PSU of the indicated station. The er-ror was detected by the PSU diagnosis (for CFCU2, UFCH, and UFMH).

Cause Failure detected by NPU

No. 0158Message name Control Station Power Supply Card Error Recovery

Printing example STN1701 PSU Recover PSU2

Meaning The PSU of the indicated station has been restored to the normal state.

No. 0161Message name Control Unit Self-diagnostic Error

Printing example STN1701 RL Diagnose Error

Meaning An error occurred in the check communication from the control side to the standby sideof the �XL control unit.

Cause/Action The error was probably caused by the failure of the NP card on the standby side.Replace the NP card on the standby side first, and if the error is not corrected, replacethe NP card on the control side.

No. 0162Message name Control Unit Self-diagnostic Error Recovery

Printing example STN1701 RL Diagnose Recover

Meaning The error in the check communication from the control side to the stand by side of the�XL control unit has been corrected.

15th Edition : Dec.10,2007-00

Page 64: CS 1000/3000 Operating Messages

2-46<2. Message Output Details>

IM 33S02H10-01E

No. 0163Message name RL Bus Failure

Printing example STN1701 RL BUS Fail No.1

Meaning An RL-Bus failure was detected during communication between the printed stations.

Cause/Action Bus or coupler failure: Replace the bus or coupler.System start (Note): Since this condition is not a bus failure, issue a recovery

command.Note: The message is not always output at the time of system start. Usually, it is not

output.Note: When the RL-Bus failure is reported on a bus, that bus is put out of service. It is

diagnosed periodically, and if it is considered to be normal as a result of the di-agnosis, it returns to service automatically.

Explanation • When the RL-Bus is duplexed, which bus is to be used is determined by the inter-face card, not by software.

• The interface card performs the error retry only once on each bus. If one of thebuses does not operate correctly while the other does, the former bus is consideredto have failed. When one of the buses is considered to have failed, the other busis retried three times.

No. 0164Message name RL Bus Recovery

Printing example STN1701 RL Bus Recover No.1

Meaning RL-Bus 1 has been restored to the normal state.

No. 0165Message name �XL, EFUS/EFUD Fan Alarm

Printing example STN1701 Fan Fail

Meaning The fan does not operate correctly.

Cause/Action Check if the power is supplied to the fan and if the fan is rotating. If the fan is defec-tive, replace it.

No. 0166Message name �XL, EFUS/EFUD Fan Alarm Recovery

Printing example STN1701 Fan Recover

Meaning The fan has been restored to the normal state.

13th Edition : Dec.26,2005-00

Page 65: CS 1000/3000 Operating Messages

2-47

IM 33S02H10-01E

<2. Message Output Details>

No. 0167Message name Abnormal Communication with Subsystem

Printing example STN1701 SS-COM Error NEST2 CARD2 STN001 Code=000F

Meaning An error occurred in the communication with a subsystem.

Cause/Action The details of the errors are explained in the instruction manuals on the communica-tion functions of individual subsystems. Refer to the instruction manual of the relevantsubsystem.

Table Errors irrelevant to connected subsystem type

Code Explanation

$0B70 The subsystem name is not defined. The subsystem program does not exist.

$0B81 Invalid sub ID

$0B82 Invalid call from supervisor

$0B83 The communication target task does not exist.

$0B84 The queue of the event communication target task is full.

$0B91 The communication driver is busy.

$0B92 The communication line is busy.

$0B93 The communication line is not ready.

$0B94 The communication block size is too large.

$0B95 The use of communication port is not declared.

$0B97 Under-run error

$0B98 Inter-character time out for receive

$0B99 Receive buffer overflow

$0B9A Receive data parity error 1

$0B9B Receive overrun error

$0B9C Receive framing error

$0B9D Unallowable number of receive characters

$0B9E Transmission is disabled because FIFO buffer is full.

$0B9F Internal error

016700E.EPS

No. 0168Message name Recovery of Communication with Subsystem

Printing example STN1701 SS-COM Normal NEST2 CARD2 STN0001 Code=0000

Meaning The abnormal communication with a subsystem has been corrected. (The value ofCode is always 0.)

Cause This message is output when all the errors are corrected.

13th Edition : Dec.26,2005-00

Page 66: CS 1000/3000 Operating Messages

2-48<2. Message Output Details>

IM 33S02H10-01E

No. 0171Message name Control Station/CFGW Station System Alarm

Printing example STN1701 System Error Code=XXXX

Meaning A control station system error occurred.

Table Cause and Action for Detail Code

Code Cause Software action Operator action Type

1. MS�� card failure or bus error

(1) Not mounted.

(2) Writing into ROM area

(3) Parity error in access tomemory

(4) Voltage drop in card

2. ALU4, CTL4, or PNL4 cardfailure

(1) Microprogram does not run.

(2) WDT time-out

(3) Voltage drop in card

1. CP11 card failureParity error

2. NP61 card failureParity error

3. NP5� card failureParity error

Execution of undefined instruction

ALU4, CTL4, PNL4, MI��, orFCA4 card failure, or illegal program operation

Occurrence of test interrupt duringprogram debugging

1. When vector number is 2(bus error):

(1) Not mounted.

(2) Writing into ROM area

(3) Parity error

2. When vector number is 3 (address error):

Illegal program operation

Vector numbers 4 to 11

00020004

0004

0007

0005

0008

0004

0007

The task being executed is aborted.

The next processing is executed.

Save the system for causeanalysis.

After replacing MS�� cardor ALU4, CTL4, or PNL4card, reload the program.

• Save the system for causeanalysis.

• Replace the processor card.

Replace the ALU4, CTL4,PNL4, MI��, or FCA4 card.

The task being executed is aborted.

The next task is processed fromits beginning.

If the alarm is output more thanonce in one minute, system downoccurs.

Same as above (Code 0004)

Save the system for causeanalysis.

Reload

Same as above (Code 0004)

*1

*2

*3

*4

*1

*5

*6

*6

017100E.EPS

Type: Object station*1: CFCS2/CFSS/CFCD2/CFSD/CFCDE*2: EFCS/EFCD/EFCE*3: EFUS/EFUD*4: MFCD/MFCU/MFCN/MFMU*5: Unused*6: CFGW

13th Edition : Dec.26,2005-00

Page 67: CS 1000/3000 Operating Messages

2-49

IM 33S02H10-01E

<2. Message Output Details>

No. 0173Message name Cabinet Environment Error

Printing example STN1701 Cabinet Error ADDR=ll-mm Code=nnnn

Table Meaning of Printing example

AlarmCabinet address Code

ll mm nnnn

TEMP alarm 01 to 04 00 0001

01 ROOF FAN02 NEST FAN03 SC FAN

FAN alarm 01 to 04 0002

01 FRONT RIGHT02 FRONT LEFT11 REAR RIGHT12 REAR LEFT

PS40 alarm 01 to 04 0003

HK-BUS communication alarm 01 to 04 00 See the table below

017301E.EPS

Meaning An error occurred on the environment in the control station.

Table HK-Bus Related Alarms

Abnormal stateError name

Code(00XX) Explanation

$80$81$82

$90

$91

$92

$93

$A0

$A1

$B0

$B1

$C0

$C1

$D0

$FF

$FC

SDHARD

SDSOFT1

SDSOFT2

SDSOFT3

SDSOFT4

SCI1(Invalid Carrier Detect)

SC12(Transmission Fail)

RDHARD1(Framing Error)

RDHARD2(Framing Error)

RDSOFT1

RDSOFT2

NORSP

NOTRDY

SI11 ER

Other than above

HKBSDR hardware may be defective.

LENGTH of HKBSD does not match the number of data items.

Invalid address for accessing SI11 (not 0).

Value of LENGTH is greater than the HK bus standard.

Attempt was made to access HK bus by the standby SI11.

Data transmission to HK bus is disabled. (HK bus is busyor SCI has error.)

The data sent to HK bus cannot be read back.

A FRAMING or OVERRUN error was detected in the response data from HK bus.

A BCC error was detected in the response data from HK bus.

The frame length of the response data from HK bus is longer than 64.

ADRS, CTL, or LENGTH of the response data from HKbus does not correspond to the bus specifications.

No response from HK bus

No response from SI11

SI11 HKU interface error

Undefined

0

*1

3

017302E.EPS

*1: Number of retry times before error code is returned

Action Replace the fan or the power supply unit, or report this to vendor’s technical servicegroup.

13th Edition : Dec.26,2005-00

Page 68: CS 1000/3000 Operating Messages

2-50<2. Message Output Details>

IM 33S02H10-01E

No. 0174Message name Cabinet Environment Recovery

Printing example STN1701 Cabinet Recover ADDR=01-00 Code=0001

Meaning The cabinet environment error described in No. 0173 has been restored to the nor-mal state.

No. 0175Message name Control Station CPU Card Memory Self-diagnostic Error

Printing example STN1701 SEC Counter Overflow

Meaning SEC (Single Error Correction: Memory bit error correction) occurred many times.Related Models: EFCS/D-H2, EFCS/D-H4, EFCE-H2, EMCS/D-H4.

Cause The error may have been caused by the memory (RAM) failure or ECC function er-ror.

Action Replace the CPU card.

No. 0177Message name Control Station CPU Card Memory Self-diagnostic Error

Printing example STN1701 ECC Diagnose Error

Meaning An error was detected by the self-diagnosis of the ECC (Error Correction Code) func-tion.

Cause The error may have been caused by the failure of the ECC function of the CPU card.

Action Replace the CPU card.

No. 0179Message name Control Station CPU Card Realtime Clock Error

Printing example STN1701 Real Time Clock Error

Meaning An error was detected by the self-diagnosis of the realtime clock.

Cause The error may have been caused by the failure of the realtime clock on the CPU card.

13th Edition : Dec.26,2005-00

Page 69: CS 1000/3000 Operating Messages

2-51

IM 33S02H10-01E

<2. Message Output Details>

No. 0181Message name Control Station Control Right Transfer

Printing example STN1701 Baton Transfer

Meaning The control right has been transferred in the duplexed control station.

Cause The causes of the phenomenon are as follows.• An error is detected in the CP card, SI11 card or FC11 card on control side.• An error is detected on control side by system self-diagnosis.• Control side stops by system software malfunction.• Control right is switched by the switch in front of DX11 card.

Action Report this to vendor’s technical service group unless the phenomenon is caused byswitching the switch on DX11 card.

No. 0183Message name Error in Batch System

Printing example STN1701 System Warning Code = 0025

Meaning Error in database of batch system.

Action Re-Download database for Batch control from ENGS.

No. 0185Message name Duplexed Control Station Control Error

Printing example STN1701 L Fail

Meaning The left controller has failed.

Cause An abnormal signal was output from the controller monitored by the duplexity controlsection.

Action Replace the CPU card.

No. 0187Message name Duplexed Control Station Duplexity Control Section Power Error

Printing example STN1701 Duplex Controller Fail

Meaning For CFCD2, CFCDE, CFSD, the 5V DC power supplied to the duplexity control sec-tion from power supply card is abnormal.

15th Edition : Dec.10,2007-00

Page 70: CS 1000/3000 Operating Messages

2-52<2. Message Output Details>

IM 33S02H10-01E

No. 0189Message name SEBOL Internal Error

Printing example VESSEL1 REACTOR FUNC L=10 Code=20400-0000

Meaning An error of error classification code 20000 to 29999 or an internal error of error clas-sification code 30000 to 32767 has occurred in a SEBOL program of CENTUM-XL.

SEE ALSO

For the meanings of the error classification code and error detail code, refer to the appendix of SequenceLanguage SEBOL Instruction Manual (IM 34A1B51-21E).

No. 0191Message name SEBOL Error

Printing example VESSEL1 REACTOR FUNC L=10 Code=4-0000

Meaning An error of error classification code 1 to 19999 has occurred in a SEBOL program ofCENTUM-XL.

SEE ALSO

For the meanings of the error classification code and error detail code, refer to Appendix C of SequenceLanguage SEBOL Instruction Manual (IM 34A1B51-21E).

No. 0195Message name Application System Alarm

Printing example STN1701 (SYSTEM) Task Abort

Meaning System alarm from ECMP or ECGW3

Action Report this message to vendor’s technical service group.

No. 0196Message name Application System Alarm Recovery

Printing example STN1701 (SYSTEM) Printer No1 Recover

Meaning System alarm from ECMP or ECGW3 recovered.

15th Edition : Dec.10,2007-00

Page 71: CS 1000/3000 Operating Messages

2-53

IM 33S02H10-01E

<2. Message Output Details>

No. 0197Message name Application System Alarm

Printing example STN1701 MCS AP_Task Alarm

Meaning When an error is detected in an application program on the control station, the appli-cation program issues this system alarm message. Up to 79 characters can be out-put as this message. (This is an alarm message from a BASIC program on �XL FieldControl Unit.)

Action Check the BASIC applications.

No. 0198Message name Application System Alarm Recovery

Printing example STN1701 MCS AP_Task Recover

Meaning When an error is corrected in an application program on the control station, the ap-plication program issues this system alarm recovery message. Up to 79 characterscan be output as this message. (This is an alarm recovery message from a BASICprogram on �XL Field Control Unit.)

13th Edition : Dec.26,2005-00

Page 72: CS 1000/3000 Operating Messages

2-54<2. Message Output Details>

IM 33S02H10-01E

2.3 HIS System Status Messages(Message Nos. 0201 to 0251)This section describes the system messages generated by a Human Interface Sta-tion (HIS).

No. 0201Message name Control bus interface card error

Printing example V/VL net Card Error Code=0100-00010900

Meaning An error was generated in the Control bus interface card internal hardware or in theControl bus interface card connection bus.The following lists some typical error codes( xx is unspecified)

0100-000109xx:Another station of the same address was detected.

0100-00010Axx:Discrepancy was detected in the bus connection.

0100-00010Bxx:A parity error occurred when DIP-SW station number was read.

0100-00010Cxx:A parity error occurred when DIP-SW domain number was read.

0100-000127xx:A media error occurred in the individual loopback.

0500-00050001:Control bus monitoring daemon ended with error.

Action • Restart PICS• Recheck Control bus interface card setup and bus connection status• Replace the defective hardware

No. 0203Message name Control bus communication circuit error

Printing example V/VL net communication Fail

Meaning An error was generated in the Control bus communication circuit in CPU card.

Action Check the settings of control bus interface card and the connection of the control bus.

No. 0204Message name Control bus communication circuit recovery

Printing example V/VL net communication Recover

Meaning Control bus communication circuit in CPU card has recovered to normal state.

13th Edition : Dec.26,2005-00

Page 73: CS 1000/3000 Operating Messages

2-55

IM 33S02H10-01E

<2. Message Output Details>

No. 0207Message name Program terminated in an abnormal state

Printing example Process Abort xxxxxx Code=yyyyyyyy

Meaning Program (program name xxxxx) terminated in an abnormal state.

Action Notify the service department of the contents of the Code display.

No. 0209Message name Program execution error

Printing example Program can’t start xxxxxx Code=yyyyyyyy

Meaning Program file (file name=xxxxxx) failed to start

Cause • The selected file doesn’t exist in the designated path.• Security rejected to execute the program.

Action Notify the service department of the contents of the Code display.

No. 0211Message name HIS temperature abnormal

Printing example xxxx High Temperature

Meaning Temperature inside the HIS cabinet is too high.xxxx indicates the location where the temperature alarm is generated.AIR-IN : Temperature of air-in (Console, inside)AIR-OUT : Temperature of air-out (Console, inside)No Indication : CPU card ambient temperature

Action Lower the ambient temperature. Check or exchange the fan. If it is AIR-IN or AIR-OUTalarm, clean or exchange the air filters.

Note This alarm message is only generated in the HIS with RAS card.

No. 0213Message name HIS temperature abnormality sustained

Printing example xxxx High Temperature Sustained

Meaning Temperature alarm has continued for more than 15 minutes.xxxx indicates the location where the temperature alarm is generated.AIR-IN : Temperature of air-in (Console, inside)AIR-OUT : Temperature of air-out (Console, inside)No Indication : CPU card ambient temperature

Action Lower the ambient temperature. Check or exchange the fan. If it is AIR-IN or AIR-OUTalarm, clean or exchange the air filters.

Note This alarm message is only generated in the HIS with RAS card.

13th Edition : Dec.26,2005-00

Page 74: CS 1000/3000 Operating Messages

2-56<2. Message Output Details>

IM 33S02H10-01E

No. 0214Message name HIS temperature returned to normal

Printing example xxxx High Temperature Recovery

Meaning HIS temperature has recovered to normal.xxxx indicates the location where the temperature alarm is generated.

Note This message is only generated in the HIS with RAS card.

No. 0215Message name HIS fan abnormal

Printing example xxx Fan Fail

Meaning A fan inside the HIS has failed.xxxx indicates the location where the alarm is generated.DOOR(D1) : left fan of door (Console, inside)DOOR(D2) : center fan of door (Console, inside)DOOR(D3) : right fan of door (Console, inside)Power :power supply for fans (PC, inside)Front : front fan (PC, inside)

Action Replace the fan with a new one.

Note This alarm message is only generated in the HIS with RAS card.

No. 0216Message name HIS fan recovered

Printing example xxx Fan Recover

Meaning Fan has recovered.xxxx indicates the location where the alarm is generated.DOOR(D1) : left fan of door (Console, inside)DOOR(D2) : center fan of door (Console, inside)DOOR(D3) : right fan of door (Console, inside)Power :power supply for fans (PC, inside)Front : front fan (PC, inside)

Note This message is only generated in the HIS with RAS card.

13th Edition : Dec.26,2005-00

Page 75: CS 1000/3000 Operating Messages

2-57

IM 33S02H10-01E

<2. Message Output Details>

No. 0217Message name Hard Disk Error Detected

Printing example xxxx Hard Disk Error

Meaning An alarm or RAID failure is detected by Self Monitoring Analysis and Reporting Tech-nology (SMART).The details of xxxx and their indications are as followsDRIVE(1) : Primary controller master driveDRIVE(2) : Primary controller slave driveDRIVE(3) : Secondary controller master driveRAID: One of the disks in the RAID-1 (Disk mirroring) system

Action Backup the hard disk immediately. After that, solve the problem. Replace the disk, ifnecessary.

Note The message with DRIVE (1), DRIVE (2), or DRIVE (3) in place of XXXX is raised onlyon a console-type HIS with an interface expansion card (Model name: AIP261) con-nected.The message with RAID in place of XXXX is raised on a HIS which is a componentof the RAID-1 (Mirroring) system.This message is valid only with specific PCs. See the hardware requirements of PC.

No. 0219Message name System error on Touch Panel function

Printing example Touch Panel System Error xxxx

Meaning An error in Touch Panel function is detected.Touch Panel can not be recognized by the system. There might be a breakage incables or power supply, or an error in touch panel itself.The details of xxxx and their indications are as followsNOTREADY: The touch panel can not be recognized and connected.NOTREADY(RETRY): There might be a breakage in cables or power supply, oran error in touch panel itself.DISCONNECTED: The touch panel is not connected (cables or power supply are

broken).DISCONNECTED(RETRY): The touch panel is not connected (cables or power

supply are broken).

Action Unless the breakage is for the test purpose, replace the cable or power supply, orreplace the failed touch panel.

Note This message may be generated only in the Console type HIS with touch panel func-tion.

No. 0225Message name UPS Diagnosis Error

Printing example UPS Diagnose Error

Meaning Abnormality is detected in the UPS for supplying power to HIS.

Action Refer to the User’s Manual of the UPS.

14th Edition : Dec.26,2006-00

Page 76: CS 1000/3000 Operating Messages

2-58<2. Message Output Details>

IM 33S02H10-01E

No. 0227Message name UPS power supply failure

Printing example AC Fail

Meaning A power supply error is detected in the UPS for supplying power to HIS.

Action Ensure the power supply to UPS is normal, otherwise HIS shutdown sequence willstart automatically within 10 seconds.

No. 0228Message name HIS power supply recovered

Printing example AC Recover

Meaning HIS power supply has recovered.

No. 0229Message name Run HIS Shutdown Sequence Due to Power Supply Failure

Printing example AC Fail shutdown

Meaning HIS shutdown sequence started automatically when the power supply abnormalitysustained for 10 seconds (emergency shutdown).In case of normal shutdown, HIS shutdown message (message No. 231) appears.

No. 0231Message name HIS shutdown

Printing example HIS Shutdown

Meaning HIS shuts down due to one of the causes as follows:• Log-off operation by user• Shutdown operation by computer• Switch operation to virtual test function• Automatic shutdown caused by prolonged AC fail status

No. 0236Message name HIS start

Printing example HIS Start

Meaning HIS function started and monitoring and operation function started.

No. 0238Message name Virtual HIS test start

Printing example HIS Start (Virtual)

Meaning HIS operation and monitoring functions are started using the virtual test function.

14th Edition : Dec.26,2006-00

Page 77: CS 1000/3000 Operating Messages

2-59

IM 33S02H10-01E

<2. Message Output Details>

No. 0239Message name HIS temperature sensor fails

Printing example xxxx Temperature Sensor Fails

Meaning A temperature sensor inside the HIS cabinet has failed.xxxx indicates the location where the alarm is generated.AIR-IN : Temperature of air-in (Console, inside)AIR-OUT : Temperature of air-out (Console, inside)

Action Change the temperature sensor.

Note This message is generated only in the HIS with RAS card.

No. 0240Message name HIS temperature sensor recovered

Printing example xxxx Temperature Sensor Recover

Meaning Temperature sensor has recovered.xxxx indicates the location where the alarm is generated.AIR-IN : Temperature of air-in (Console, inside)AIR-OUT : Temperature of air-out (Console, inside)

Note This message is generated only in the HIS with RAS card.

No. 0251Message name HIS system stop by WDT time up

Printing example WDT Time Up

Meaning System was stopped due to WDT time up.

Action Report this message to vendor’s technical service group.

13th Edition : Dec.26,2005-00

Page 78: CS 1000/3000 Operating Messages

2-60<2. Message Output Details>

IM 33S02H10-01E

2.4 Communication Related Messages(Message Nos. 0301 to 0397)This section describes the Control bus status information messages.

No. 0301Message name V/VL net communication error

Printing example Communication Error HIS0101 to FCS0101 Code=xxxx

Meaning A communication error was generated between the Control bus stations (HIS0101 toFCS0101) indicated by the printing contents.

Cause/ActionTable Message No.0301 - Detail Error List (1/3)

Code Errors Cause/Action

0001 Send request: Target station address error

The request parameters are probably invalid. Check the parameters.

0002 Send request: Type error

0003 Send request: AP data word length error

0004Send request: Buffer size, AP data wordlength unsuitable

0006 Send request: AP command code error

0010 Target: No response

There is probably an target station error, or communication path error.Check each path and each station along the path from the sendingstation to the target station.

0011 Target: Busy response

0012 Target: Not ready

0013 Response wait time over

0014 Received AP command not registeredThere is probably an target station receive application error.Check the target station receive application.

0015 Receive data check sum error

(1) Since the possibility of coupler trouble is high, replace the coupler.If this error is reproduced after the coupler was replaced, the CPU cardis probably faulty. Replace the CPU card.(2) The bus connection may be incorrect, or both busses for stationconnection are disconnected.Recheck the bus connection and if the bus status is normal, restart theCPU card.If this error is generated in the normal state, there is probably troublein the hardware. Replace the CPU card.

0016 Receive frame memory busyPresent station memory resource is insufficient. Reduce thecommunication volume so that the memory resource is sufficient, orincrease the memory resource.

0017 ACK timer over

There is probably an address station error, or communication patherror.Check each bus and each station along the path from the sendingstation to the address station.

0018 Transmit buffer busyPresent station transmission capacity was exceeded.Reduce the transmission volume.

030101E.EPS

13th Edition : Dec.26,2005-00

Page 79: CS 1000/3000 Operating Messages

2-61

IM 33S02H10-01E

<2. Message Output Details>

Table Message No.0301 - Detail Error List (2/3)

Code Errors Cause/Action

0021 HAP: Bus request time-out

Since the possibility of hardware trouble is high, replace the CPU card.0022 HAP: Parity error

0023 HAP: Bus error

0024 HAP: Format error

(1) Since the possibility of hardware trouble is high, replace the CPU card.(2) The request parameters are probably unsuitable.Check the parameters.

0030VEHICLE transmit error:Transmit frame format error, transmission right error (Standby station transmission)

Since the possibility of hardware trouble is high, replace the CPU card.0031VEHICLE transmit error:Transmit memory access abnormal (underrun)

0032 VEHICLE transmit error: Serial signal error

0033Network down (error occurred before initialization)

0040 Bus status: BUS1 Fail occurred The bus connection may be incorrect, or both busses for station connection may be disconnected.Recheck the bus connection and if the bus status is normal, restart the CPU card.If this error was generated in the normal state, the trouble is probably in the hardware. Replace the CPU card.

0041 Bus status: BUS2 Fail occurred

0042 Bus status: BUS Fail Recover information

0043Bus status: Timeout occurred while waiting for token

0070 Present station domain No. Identification errorThe setting of the CPU card station address DIP-SW is incorrect.Set the station address DIP-SW correctly and restart the CPU card.If the DIP-SW setting is correct, the trouble is probably in the hardware. Replace the CPU card.0071 Present station No. Identification error

0081 Local RAM parity errorSince the possibility of hardware trouble is high, replace the CPU hard.

0082 Local RAM read/write check error

0087 Memory mark check error

The hardware or software generated an error. Executecrash dump, then replace the CPU card.If this error is reproduced even after the CPU card was replaced, the software may be unsuitable.

0088 Multimaster error Since the possibility of hardware trouble is high, replace the CPU card.

0089 Duplicate address error

CPU card station address DIP-SW setting is incorrect.Set the DIP-SW correctly and restart the CPU card.If the DIS-SW setting is correct, the trouble is probably in the hardware. Replace the CPU card.

008A Bus configuration error (Bus connection reversed)

This error may be generated when the bus connection is incorrect, or both busses for station connection are disconnected.Recheck the bus connection and check if the bus status is normal, then restart the CPU card.If this error is generated in the normal state, the trouble is probably in the hardware. Replace the CPU card.

008B DIP-SW station No. parity error The CPU card station address DIP.SW setting is incorrect.Set the DIP-SW correctly and restart the CPU card.If the setting is correct, the trouble is probably in the hardware. Replace the CPU card.

008C DIP-SW domain No. parity error.

008D DIP-SW station address setting error.

008E DIP-SW address mismatch.Since the possibility of hardware trouble is high, replace the CPU card.

008F ALU error030102E.EPS

13th Edition : Dec.26,2005-00

Page 80: CS 1000/3000 Operating Messages

2-62<2. Message Output Details>

IM 33S02H10-01E

Table Message No.0301 - Detail Error List (3/3)

Code Errors Cause/Action

0090 BUS1 VEHICLE internal loopback error

Since the possibility of hardware trouble is high, replace the CPU card.

0091 BUS2 VEHICLE internal loopback error

0092 BUS1 VEHICLE ENDEC loopback error

0093 BUS2 VEHICLE ENDEC loopback error

0094 BUS1 VEHICLE modem loopback error

0095 BUS2 VEHICLE modem loopback error

0096 BUS1 host internal loopback error

0097 BUS2 host internal loopback error

0098 BUS1 host ENDEC loopback error

0099 BUS2 host ENDEC loopback error

009A BUS1 host modem loopback error

009B BUS2 host modem loopback error

00A0 Collision flag error

00A1 Diagnostic error during single bus Enable Since the possibility of hardware trouble is high, replace the coupler. Ifthis error is reproduced even after coupler replacement, the trouble isprobably in the CPU card. Replace the CPU card.00A2 Diagnostic test error for single operation

00A3 Token return error

Since the possibility of hardware trouble is high, replace the CPU card.00A4 DMA test error

00A6 DMA error during descriptor updating

00A7 Media error

This error may be generated when the bus connection is incorrect orboth busses for station connection are disconnected.Recheck the bus connections and check the bus status, then restart theCPU card.If this error was generated in the normal state, the trouble is probablyin the hardware. Replace the CPU card.

00B0 Timer 0 error

Since the possibility of hardware trouble is high, replace the CPU card.

00B1 Timer 1 error

00B2 Timer 2 error

00B3 Timer 3 error

00B4 Timer 4 error

00B5 Timer 5 error

00B6 Timer 6 error

00B7 Timer 7 error

00F0 VEHICLE live list interrupt time-out error

The hardware or software generated an error. Execute crash dump, thenreplace the CPU card.If the error is reproduced even after CPU card replacement, thesoftware may be unsuitable.

00F1 VEHICLE micromemory errorSince the possibility of hardware trouble is high, replace the CPU card.

00F2 VEHICLE WDT time-out error

00F3 Send buffer size check error The hardware or software generated an error. Execute crash dump, thenreplace the CPU card.If the error is reproduced even after CPU card replacement, thesoftware may be unsuitable.00F5 Receive buffer mark check error

00FF HAP communication error

(1) There is probably an addressed station error, or communicationpath error.Check each bus and each station along the path from the sendingstation to the addressed station.(2) Request parameters are probably unsuitable.Check the parameters.

030103E.EPS

15th Edition : Dec.10,2007-00

Page 81: CS 1000/3000 Operating Messages

2-63

IM 33S02H10-01E

<2. Message Output Details>

No. 0303Message name Station failure

Printing example FCS0101 Fail

Meaning A station (station name=FCS0101) on the network stopped operating.Or a network error caused communication breakdown.

No. 0304Message name Station recovery

Printing example FCS0101 Recover

Meaning The stopped station (station name=FCS0101) on the network recovered to normal.Or a network error recovered and communication recovered to normal state.

No. 0305Message name Control bus failure

Printing example V net/VL net No.1 Fail (Domain No.1)

Meaning One of the dual-redundant Control bus of the domain (Domain No. 1) indicated by theprinted contents failed.

No. 0306Message name Control bus recovery

Printing example V net/VL net No. 1 Recover (Domain No.1)

Meaning The failed Control bus of the dual-redundant Control bus of the domain (Domain No.1)indicated by the printing contents recovered to normal.

No. 0307Message name Network communication error

Printing example Communication Fail (Domain No.2 )

Meaning The communication error occurs due to failure of the communication card or Controlbus of this HIS. The communication to other domain (such as domain 2) fails due toabnormality in bus converter (ABC).

13th Edition : Dec.26,2005-00

Page 82: CS 1000/3000 Operating Messages

2-64<2. Message Output Details>

IM 33S02H10-01E

No. 0308Message name Network communication recovery

Printing example Communication Recover (Domain No.2 )

Meaning Network communication recovered to normal.

No. 0311Message name HIS communication error

Printing contents Communication Error Code=xxxx

Meaning The HIS internal communication function generated an error.

Cause/Action For the error codes, see the table of alarm message No. 0301.

No. 0321Message name HF/RL Bus Communication Failure

Printing example BCVL0108 HF/RL Bus No.02 Fail (Domain No.3 STN 03 to STN 09)

Meaning One of the control buses connected to the bus converter (station name = BCV0108)has failed. HF/RL Bus is connected to the opposite side of the bus converter. The sta-tion numbers indicated in the message are the numbers of the stations on the bus onthis side.

No. 0322Message name HF/RL Bus Communication Recovery

Printing example BCVL0108 HF/RL Bus No.02 Fail (Domain No.3)

Meaning The HF/RL bus connected to the bus converter (station name = BCVL0108) has beenrestored to normal state.

13th Edition : Dec.26,2005-00

Page 83: CS 1000/3000 Operating Messages

2-65

IM 33S02H10-01E

<2. Message Output Details>

No. 0323Message name HF/RL Bus Communication Error

Printing example BCVL0108 HF/RL Bus Communication Error to 02 Code=xxxx

Meaning An error occurred in the HF/RL bus connected to the bus converter (station name =BCVL0108).

Table Detail Code for Control Bus Error (1/2)

0002

0003

0004

0005

0006

0007

0008

0009

000A

000E

000F

0011

0012

0013

0014

001A

0021

0022

Invalid Command

Memory Protect Violation

Format Error

Table Not Ready

Entry Buffer Busy

Key Code Check Error

CPU Not Ready

Application Disconnect

Disconnect

Event Buffer Overflow

Backed Up

Memory No Response

Parity Error

Channel No Responce

Memory Sequence Error

Machine Check

CI-Bus No Response

CI-Bus Frame Error • Send NC1 failure• Receive NC1 failure• CI-bus failure

• A power failure occurred at the equipment to which the CI-bus is connected.

• NC1 may be defective.• NC-bus disconnected

FC� failure may be detected during communications.

Error messages 11 to 13 are not issued.

• M-bus clamped.• FC� /NC1 failure• Other M-bus cards may be defective.

Memory not initialized. Or a memory error occurred.

Addresses not in use may be read. Or a memory error occurred. Write to RAM.

WDT time-up may occur in the FC� .Do STOP/RUN operations.

Same as Code 05.

Start/stop instructions need keywords, but these words are invalid.

If data exceeding the maximum data processing capacity of CFCU2 are entered, a data entry buffer overflow occurs. Allocate temporary loading, and the NC1 or FC� to NP1.

Communications tables are linked when the CFCU2 is in STOP/RUN. If they do not revert to the normal state following STOP/RUN operations, replace the NC1 or FC� card.

Frame: Data format to form a communications unit on the bus.

The memory protect switch on the NC1 card remains on.

An error occurred during the CRC checking at the receive side of the command frame.

The CI-bus does not respond.

The send FC� is defective.

While in memory Read/Write in non-contiguous addresses, errors 11 to 13 occurred in all addresses.

The FC� /NC1 cannot obtain the memory access right.

The destination memory cannot be read.

The destination memory cannot be read.

A reserve request has been issued to the back-up bus converter.

The receive buffer is overflowing.

The FC� has logically been disconnected from its specific program.

Not all of the AP command tables on the control station are linked to the communications requirements.

A keyword error occurred in the start/stop instructions.

If DDC/SEQ data are entered, Not Ready in the destination station is detected.

The control station’s data entry buffer is overflowing.

A specific AP command table on the control station is not linked to the communications requirements.

A write request has been issued to CFCU2 memory that was memory-protected.

The AP frame format is illegal.

Undefined application (AP) commands have been requested to the FC� .

Code Name Meaning Cause / Operator Action / Explanation

032301E.EPS

13th Edition : Dec.26,2005-00

Page 84: CS 1000/3000 Operating Messages

2-66<2. Message Output Details>

IM 33S02H10-01E

Table Detail Code for Control Bus Error (2/2)

0023

0028

002B

0031

0032

0033

0034

003A

003B

0040

0041

0042

0043

0080

0081

0082

0083

0036

CI-Bus Transmission Fail

Line Busy

Micro Check

F-Bus No Response

F-Bus Frame Error

F-Bus Transmission Fail

Buffer Busy

Invalid Command

P-Timer Overflow

Micro Check

FCA Not Ready

C-Timer Over

A-Timer Over

Move Error

L-M Timer Over

L-A Timer Over

NCM

NCM Not Ready

After a communications request is sent, no data are output through the line. The FCA4 or couplers may be defective.

• Temporarily overloaded communications data• FC� failure

The sending/receiving FC� may be defective.The stations on the HF-bus are communicating using

a baton (communications control right) periodically. The code 003A means that this baton is being used repeatedly, and that it is not handled as an error.

A request has been sent while the FC� is being initialized.

After sending a request to the FC� , the communications software monitors the communications status for 2 seconds with “Move End Timer.”• FC� failure• Temporary overload• FC� WDT time up

This message always appears if an error occurs on the CI-bus.

• Invalid format in the created frame• Memory cannot be read correctly.

M-Timer Over on the CI-bus.This message is output with instructions from the BCU or CIU.

A-Timer Over on the CI-bus.This message is output with instructions from the BCU or CIU.

• Send FC� failure• Receive FC� failure• HF-bus failure

• Power failure occurred at the equipment to which the HF-bus is connected.

• FC� may be defective.• The HF-bus may be disconnected.

Micro-diagnostic errors detected through the sending and receiving circuits.

NC1 error in the BCU or CIU.

After a communications request is sent, no data are output through the line. NC1 may be defective.

FC� cannot issue a communications request.

An error occurred while CRC checking at the receive side of the command frame.

The HF-bus does not respond.

A CI-bus micro-diagnostic error has been issued.

The CI-bus is busy.

NC1 cannot issue a communications request.

Code Name Meaning Cause / Operator Action / Explanation

The frame buffer in the FC� at the receive side is busy.

The HF-bus has paused for a certain period of time.

A HF-bus micro-diagnostic error has been issued.

The FC� status is not ready.

An interrupt from the FC� was not accepted within the specified time.

After a communications request, a response from the destination station was not sent back within 2 to 8 seconds.

The created frame in the main memory was not read correctly from the FC� .

NCM does not start.

032302E.EPS

13th Edition : Dec.26,2005-00

Page 85: CS 1000/3000 Operating Messages

2-67

IM 33S02H10-01E

<2. Message Output Details>

No. 0324Message name Control Rights Switching of HF/RL Bus Duplexed Communication Card

Printing example BCVL0108 HF/RL Bus Card RIGHT Control

Meaning The control right has been taken by the right side of the conventional bus communi-cation card connected to the Bus Converter (station name = BCVL0108).

No. 0325Message name DataBase Downloading Error

Printing example BCVL0108 DataBase Download Error STN1701 Code=xxxx

Meaning The bus converter (station name = BCVL0108) has failed in reading the data base ofthe target station (station name = STN1701) on the control bus.

Cause/Action 20xx: A File management error in the tag list file (refer to the next table for xx).2F04: The number of tags for an equalization request is greater than the maximum

number of elements for an equalization request.2F05: The total number of tags exceeds 16000.2F06: The number of phase names used in the list is greater than the maximum

number (128) allowed in the phase name list.2F08: The number of phase names used in the list is greater than the maximum

number (128) allowed in the phase name list.2F10: Tags for SEQ. elements have been added.2F11: The number of tags for an equalization request for the batch status indica

tor is greater than the maximum number of the batch status indicators for each station.

50xx: A File management error for the sequence file with data (refer to the next table for xx).

List of file management error codes01: File address syntax error02: Project does not exist.03: File directory does not exist.04: File ID does not exist.05: Local file access error06: Communications error07: No right to read08: No right to write09: Lock-freeze not engaged.0A: Lock-freeze engaged.0B: Lock-freeze mismatched.0C: RCS not in use.0D: File directory with lock-freeze not engaged.0E: Memory allocation error0F: Engineering file access error10: Undergoing shut-down processing11: Unrecoverable error12: Illegal combination of from and to13: Not a project user14: Backup disabled.15: Undergoing backup processing16: Back-end restart error

Action Report this message to vendor’s technical service group.

13th Edition : Dec.26,2005-00

Page 86: CS 1000/3000 Operating Messages

2-68<2. Message Output Details>

IM 33S02H10-01E

No. 0326Message name DataBase Download Completion

Printing example BCVL0108 DataBase Download Complete

Meaning The bus converter (station name = BCVL0108) has succeeded in reading the database of a station (registered in the bus converter) on the control bus.

No. 0327Message name Error in Conventional Bus Duplexed Communication Card

Printing example BCVL0108 FC31 Card LEFT not Ready

Meaning An error occurred on the left side of the conventional bus communication card con-nected to the Bus Converter (station name = BCVL0108).

Action Replace the card.

No. 0328Message name Conventional Bus Duplexed Communication Card Stand-by

Printing example BCVL0108 FC31 Bus Card RIGHT Stand-by

Meaning Right side of the conventional bus communication card connected to the bus converteris in stand-by.

No. 0329Message Name Other Error Occurred on Bus Converter

Printing example BCVL0108 RIGHT Other Error = xxxxxxxx

Meaning An other error occurred to the CPU card (such as RIGHT card) of the bus converter(Station name=BCVL0108) with error code of xxxxxxxx (Error Code=xxxxxxxx).

Table Message No.0329 - Error Details

Code(xxxxxxxx)

Errors Cause/Action

00000001CPU card encountered an error interruption from FC31 card, and reset FC31 card.

It may be caused by hardware malfunction. FC31 card needs to be changed.

00000002CPU card encountered an error interruption from VF31 card, and reset VF31 card.

It may be caused by hardware malfunction. VF31 card needs to be changed.

032901E.EPS

No. 0330Message name Time adjustment

Printing example HIS0124 Time Adjust (old Time 97. 07. 20 19: 20: 58)

Meaning HIS time was adjusted according to the time change information from HIS0124.The old time is shown in the message.

14th Edition : Dec.26,2006-00

Page 87: CS 1000/3000 Operating Messages

2-69

IM 33S02H10-01E

<2. Message Output Details>

No. 0331Message name Network time error

Printing example HIS0124 Network Time Out of Range (Network Time 96. 07. 20 10: 20: 58)

Meaning Time data of the time change information from HIS0124 is out of the effective range.

Cause This alarm message is generated when a control station volatilizing a real time clockstarted an HIS with a time master.

Action Set the correct time using the Set Time dialogue (switching from operation and moni-toring function system status overview window or FCS status display window).

No. 0332Message name Time Setting Master Right Acquisition

Printing example Turn on Date/Time Master

Meaning The HIS has acquired the right to set the time of other stations.

No. 0334Message name Time Setting Master Right Release

Printing example Release Date/Time Master

Meaning The HIS has resigned the right to set the time of other stations.

No. 0340Message name Bus Converter Low-order V net in the Control State

Printing example BCVV0109 VF31 Card RIGHT Control

Meaning The low-order V net (right-side net) of the ABC bus converter (station name =BCVV0109) has control.

No. 0341Message name Bus Converter Communication Failure

Printing example BCVV0109 VF31 Card LEFT not Ready

Meaning The low-order V net (left-side net) of the ABC bus converter (station name =BCVV0109) is in the communication disabled state, or the low-order V net commu-nications card (VF31) in the bus converter is out of position, or the VF31 card is faulty.

No. 0342Message name Bus Converter Low-order V net in the Standby State

Printing example BCVV0109 VF31 Card RIGHT Stand-by

Meaning The low-order V net (right-side net) of the ABC bus converter (station name =BCVV0109) has entered the standby state.

13th Edition : Dec.26,2005-00

Page 88: CS 1000/3000 Operating Messages

2-70<2. Message Output Details>

IM 33S02H10-01E

No. 0343Message name Bus Converter Communications Card Fatal Error

Printing example BCVV0109 VF31 Card RIGHT Fatal Error = xxxxxxxx

Meaning An error occurred in the low-order V net communications card (VF31) (right-side net)in the ABC bus converter (station name = BCVV0109).

Table Detail Fatal Error (1/2)

Code Errors Cause/Action

Local RAM parity error

Local RAM read/write check error

Memory mark check error

Multi-master error

Dual-address error

Bus structure error (bus connected improperly)

DIP.SW. and station number parity error

DIP.SW. and domain number parity error

DIP.SW. and station address setting error

DIP.SW. address error (mismatched)

ALU error

BUS1 VEHICLE internal loopback error

BUS2 VEHICLE internal loopback error

BUS1 VEHICLE ENDEC loopback error

BUS2 VEHICLE ENDEC loopback error

BUS1 VEHICLE modem loopback error

BUS2 VEHICLE modem loopback error

BUS2 host internal loopback error

BUS1 host internal loopback error

BUS1 host ENDEC loopback error

BUS2 host ENDEC loopback error

BUS1 host modem loopback error

BUS2 host modem loopback error

Collision flag error

00010100

00010200

00010700

00010800

00010900

00010A00

00010B00

00010C00

00010D00

00010E00

00010F00

00011000

00011100

00011200

00011300

00011400

00011500

00011600

00011700

00011900

00011800

00011A00

00011B00

00012000

Hardware may be defective. Replace the VF31 card.

This error occurs if the hardware or software is defective. After completing a crash dump, replace the VR31 card. After replacement, if the same error occurs, the software may not be appropriate.

Hardware may be defective. Replace the VF31 card.

The DIP switch on the VF31 card may be set incorrectly. Set it correctlyThen restart the VF31 card. If this error occurs though the switch setting is correct, the hardware may be defective. Replace the VF31 card.

Bus connections may be improper. Or buses may be disconnected while connecting the station. Check for improper bus connections and then restart the VF31 card. If this problem develops during normal operation, the hardware may be defective.Replace the VF31 card.

The DIP switch on the VF31 card may be set incorrectly. Set it correctly. Then restart the VF31 card. If this error occurs though the switch setting is correct, the hardware may be defective. Replace the VF31 card.

The hardware may be defective. Replace the VF31 card.

034301E.EPS

13th Edition : Dec.26,2005-00

Page 89: CS 1000/3000 Operating Messages

2-71

IM 33S02H10-01E

<2. Message Output Details>

Table Detail Fatal Error (2/2)

Code Errors Cause/Action

Diagnostic error when the one-way bus is enabled.

Self-diagnostic error

Token reply error

DMA test error

DMA error when updating the descriptor

Media error

00012100

00012200

00012300

00012400

00012600

00012700

Timer 0 error00013000

Timer 1 error00013100

Timer 2 error00013200

Timer 3 error00013300

Timer 4 error00013400

Timer 5 error00013500

Timer 6 error00013600

Timer 7 error00013700

VEHICLE micro-memory error00020001

VEHICLE WDT timeout error00020002

VEHICLE library list interrupt timeout error00020011

Receive buffer mark check error00020012

Station address setting error00020013

Control and standby station addressesmismatched 00020014

C-Over00020015

The coupler may be defective. Replace the coupler. After replacement, if the same error occurs, the VF31 card may be defective. Replace the VF31 card.

The hardware may be defective. Replace the VF31 card.

The hardware may be defective. Replace the VF31 card.

The hardware may be defective. Replace the VF31 card.

This error occurs if the hardware or software is defective. After completing a crash dump, replace the VR31 card. After replacement, if the same error occurs,the software may not be appropriate.

The DIP switch on the VF31 card may be set incorrectly. Set it correctly.Then restart the VF31 card. If this error occurs though the switch setting is correct, the hardware may be defective. Replace the VF31 card.

Bus connections may be improper. Or buses may be disconnected while connecting the station. Check for improper bus connections and then restart the VF31 card. If this problem develops during normal operation, the hardware may be defective. Replace the VF31 card.

Bus connections may be improper. Or the buses may be disconnected while connecting the station. Check for improper bus connections and then restart the VF31 card. If this problem develops during normal operation, the hardware may be defective. Replace the VF31 card.

034302E.EPS

Action Review the bus converter communication parameters. If the error recurs, replace theVF31 card. Please inform us of the error description.

15th Edition : Dec.10,2007-00

Page 90: CS 1000/3000 Operating Messages

2-72<2. Message Output Details>

IM 33S02H10-01E

No. 0345Message name Bus Converter Communications LoopBack Card Error

Printing example BCVV0109 VF31 Card RIGHT LoopBack Error = xxxxxxxx

Meaning A communication loopback error occurred in the low-order V net communications card(VF31) (right-side net) in the ABC bus converter (station name = BCVV0109).0000: Normal0009: VEHICLE internal loopback error000C: Host remote loopback error000E: Modem Disable SW. on0010: Driver detection error

Action Replace the VF31 card. Please inform us of the error description.

No. 0346Message name Time adjustment between domain

Printing example BCVV0109 Time Adjust ( Domain No.3, old Time 95.05.23 12:30:00 )

Meaning Time on Domain No.3 has been adjusted by the ABC bus converter (station name =BCVV0109), because the shift of time between the CP31 side domain and the VF31side domain occurred. Time on Domain No.3 before the time adjustment is displayedalso. (to which side of CP31 or VF31 each of Domain No. 3 and Domain No. X be-comes depends on the specification of the builder).

No. 0350Message name Station Database Loaded by the Bus Converter

Printing example BCVL0108 DataBase (STN1701, TFDATA) Download Complete

Meaning The ABC bus converter (station name = BCVL0108) has read a data base about thestation (station name = STN1701) on the low-order bus. Two types of files can be readTFDATA (tag list file)PRDATA (sequence message file with data)

No. 0352Message name The communication excessively is demanded of the ABC bus converter

Printing example BCVL0108 ABC Communication Busy

Meaning The communication excessively is demanded of the ABC bus converter. There is apossibility that the communication error due to the communication congestion occurs.The same message occurs by one minute period when the communication conges-tion situation continues. This message stops and at the time of ease the communica-tion congestion.

Action Please control the communication require quantity to ABC by decreasing the numberof display window.

15th Edition : Dec.10,2007-00

Page 91: CS 1000/3000 Operating Messages

2-73

IM 33S02H10-01E

<2. Message Output Details>

No. 0353Message name Start SIOS

Printing example BCVO0102 Start

Meaning SIOS Started.

No. 0355Message name SIOS Starting Error

Printing example BCVO0102 BcvOpc-A 10.0.90.63 Start Error Code=XXXX-YYYYYYYY

Meaning SIOS (Station=BcvOpc-A, IP Address=10.0.90.63) Start Failure. Code stands for theerror code.Error Code: Consists of the Category Code=0xXXXX and Detailed ErrorCode=0xYYYYYYYY

Action Run offline downloading. If it does not recover after offline downloading, write downthe displayed messages and contact with Yokogawa service agents.

13th Edition : Dec.26,2005-00

Page 92: CS 1000/3000 Operating Messages

2-74<2. Message Output Details>

IM 33S02H10-01E

Table Message No. 0355 – Category Code List (1/2)

Error Code Description

035501E.EPS

Incorrect SUB-ID

Incorrect code

Incorrect function

Incorrect number of requested parameters (Should not grater than 62)

Reserved for requested parameters

Error getting SIOS system configuration

Error reading SIOS system configuration file

Error inspecting SIOS system configuration file

Error reading OPC DA server configuration file

Error inspecting OPC DA server configuration file

Error reading OPC A&E server configuration file

Error inspecting OPC A&E server configuration file

Error reading the online-load desscrepancy file

Error reading the offline-load desscrepancy file

Error inspecting SIOS system configuration

Duplication Error

Cannot find the configuration file

Error reading BCV.1 file

Reserved configuration file error codes

Failed to access process data

Diagnostic error of accessing process data

Message Manager failed

Message Manager diagnostic error

DA Client Failed

DA Client diagnostic error

A&E Client Failed

A&E Client diagnostic error

Internal error of SIOS Management service

Internal error for accessing process data

Internal error of message management service

DA Client internal error

A&E Client internal error

Reserved internal error codes

OPC server connection error

OPC server disconnection error

Error adding a group

Error deleting a group

Error changing group properties

Error adding an item

Error deleting an item

Error writing an item

OPC server shutdown

Communication error to the PC of OPC server

A&E filter setting error

0xEF01

0xEF02

0xEF03

0xEF04

0xEF05 to 0F

0xEF10

0xEF11

0xEF12

0xEF13

0xEF14

0xEF15

0xEF16

0xEF17

0xEF18

0xEF19

0xEF1A

0xEF1B

0xEF1C

0xEF1D to 1F

0xEF20

0xEF21

0xEF22

0xEF23

0xEF24

0xEF25

0xEF26

0xEF27

0xEF28

0xEF29

0xEF2A

0xEF2B

0xEF2C

0xEF2D to 2F

0xEF30

0xEF31

0xEF32

0xEF33

0xEF34

0xEF35

0xEF36

0xEF37

0xEF38

0xEF39

0xEF3A

13th Edition : Dec.26,2005-00

Page 93: CS 1000/3000 Operating Messages

2-75

IM 33S02H10-01E

<2. Message Output Details>

Table Message No. 0355 – Category Code List (2/2)

Error Code Description

035502E.EPS

Error reading the item

Reserved OPC communication error codes

Cannot find the specified CENTUM tag name

Cannot find the specified CENTUM data item

Data conversion error

The data type is inconsitent to the load file

The status of the string is BAD

Cache size is changing for online downloading

Reserved conversion error codes

Socket error

Load communication error

Process data online-loading error

A&E client online-loading error

Reserved load communication error codes

Status monitoring communication error

APC sending error

Reserved communication redundancy error codes

A SIOS stop request is sent from ENG

Management service stopped by PC shutdown

Failed to start the station

Failed to resume online-load

Reserved station start/stop error codes

0xEF3B

0xEF3C to 3F

0xEF40

0xEF41

0xEF42

0xEF43

0xEF44

0xEF45

0xEF46 to 4F

0xEF50

0xEF51

0xEF52

0xEF53

0xEF54 to 5F

0xEF60

0xEF61

0xEF62 to 6F

0xEF70

0xEF71

0xEF72

0xEF73

0xEF74 to 7F

No. 0356Message name SIOS online downloading successfully complete

Printing example BCVO0102 Online Download Complete

Meaning SIOS online downloading successfully complete.

No. 0357Message name SIOS online downloading ended with errors

Printing example BCVO0102 Online Download Error Code=XXXX-YYYYYYYY

Meaning SIOS online downloading abnormal end. Code stands for the error code.Error Code: Consists of the Category Code=0xXXXX and Detailed ErrorCode=0xYYYYYYYY

Action Run online downloading again. If it does not recover after online downloading, writedown the displayed messages and contact with Yokogawa service agents.The error code contents are the same as the error code in the message No. 0355.

13th Edition : Dec.26,2005-00

Page 94: CS 1000/3000 Operating Messages

2-76<2. Message Output Details>

IM 33S02H10-01E

No. 0360Message name OPC Communication Recovered

Printing example BCVO0102 OPC Communication Recover OPCSDAnn

Meaning OPC server nn communication recovered.

No. 0361Message name OPC Communication Error

Printing example BCVO0102 OPC Communication Error OPCSDAnn Code=XXXX-YYYYYYYY

Meaning OPC Server nn communication error occurred. Code stands for the error code.Error Code: Consists of the Category Code=0xXXXX and Detailed ErrorCode=0xYYYYYYYY

Action Resolve the cause of the error according to the error code.The error code contents are the same as the error code in the message No. 0355. Thedetailed error code is a Windows error code.

No. 0363Message name SIOS Task Error

Printing example BCVO0102 BcvOpc-A 10.0.90.63 Internal Error Task = DACLIENT Code=ZZZZZZZZError=XXXX-YYYYYYYY

Meaning An unrecoverable task error (task name=DACLIENT) was found in SIOS(Station=BcvOpc-A, IP Address=10.0.90.63).ZZZZZZZZ indicates the whereabouts of the error.Error stands for the error code.Error Code: Consists of the Category Code=0xXXXX and Detailed ErrorCode=0xYYYYYYYY

Action Run offline downloading. If it does not recover after offline downloading, write downthe displayed messages and contact with Yokogawa service agents.The error code contents are the same as the error code in the message No. 0355.

No. 0365Message name SIOS Task Warning

Printing example BCVO0102 BcvOpc-A 10.0.90.63 Task Warning Task = DACLIENT Code=ZZZZZZZZError=XXXX-YYYYYYYY

Meaning A task warning error (task name=DACLIENT) was found in SIOS (Station=BcvOpc-A, IP Address=10.0.90.63).ZZZZZZZZ indicates the whereabouts of the error.Error stands for the error code.Error Code: Consists of the Category Code=0xXXXX and Detailed ErrorCode=0xYYYYYYYY

Action Run offline downloading. If it does not recover after offline downloading, write downthe displayed messages and contact with Yokogawa service agents.The error code contents are the same as the error code in the message No. 0355.

13th Edition : Dec.26,2005-00

Page 95: CS 1000/3000 Operating Messages

2-77

IM 33S02H10-01E

<2. Message Output Details>

No. 0367Message name SIOS Station FAIL

Printing example BCVO0102 BcvOpc-A 10.0.90.63 Fail Code=XXXX-YYYYYYYY

Meaning SIOS (Station=BcvOpc-A, IP Address=10.0.90.63) Failed.Code stands for the error code.Error Code: Consists of the Category Code=0xXXXX and Detailed ErrorCode=0xYYYYYYYY

Action Run offline downloading. If it does not recover after offline downloading, write downthe displayed messages and contact with Yokogawa service agents.The error code contents are the same as the error code in the message No. 0355.

No. 0390Message name Database equalization to the Exaopc station completed

Printing example STN0121 DataBase Equalize Complete

Meaning Data has been equalized properly by downloading the database to the Exaopc sta-tion (STN0121).

No. 0391Message name Database equalization to the Exaopc station not completed

Printing example STN0121 DataBase Equalize not Complete

Meaning Data has not been equalized by downloading the database to the Exaopc station(STN0121).

Action Run database download again. If fails, contact to vendor’s technical service group.

No. 0393Message name Restart request of the Exaopc station

Printing example STN0121 Power OFF/ON Request

Meaning The Exaopc station (STN0121) must be restarted when a change is made on hard-ware such as the control bus interface card.Shut down the Exaopc station, turn OFF the power and turn it ON again.

No. 0394Message name Downloading database into the Exaopc station completed

Printing example STN0121 Data Base Download from HIS0124 File = TFFCS0101.odb

Meaning Database was normally downloaded from the database master station to the Exaopcstation (STN0121).

13th Edition : Dec.26,2005-00

Page 96: CS 1000/3000 Operating Messages

2-78<2. Message Output Details>

IM 33S02H10-01E

No. 0395Message name Downloading database into the Exaopc station not completed

Printing example STN0121 Data Base Download Error from HIS0124 File = TFFCS0101.od

Meaning Database was not properly downloaded from the database master station to theExaopc station (STN0121).

Action Run database download again. If fails, contact to vendor’s technical service group.

No. 0397Message name Excessive number of taglists in the Exaopc station

Printing example STN0121 Tag Volume Overflow

Meaning The number of taglists exceeds the limit in the Exaopc station (STN0121). Inacces-sible tags are found.

Action Reduce the number of tags in the System Generation Function and download it to thestation.

13th Edition : Dec.26,2005-00

Page 97: CS 1000/3000 Operating Messages

2-79

IM 33S02H10-01E

<2. Message Output Details>

2.5 Control Station Status Change RelatedMessages (Message Nos. 0400 to 0491)This section describes the messages related to status changes from the controlstations for CS 1000/CS 3000 and the safety control stations.

No. 0400Message name Duplexed Control Station Control Status

Printing example STN1701 L Control

Meaning The left control unit is used as the controller.

Cause • The entire control station has been powered on.• The controller has been reset and started.• The control right has been transferred by Mode switch (not supported by �XL MFCD

and MFSD).• The control right has been transferred because the current controller has failed.

No. 0402Message name Duplexed Control Station Ready Status

Printing example STN1701 L Ready

Meaning The left control unit has become the standby unit.

Cause • The entire duplexed control station has been powered on.• The current controller or the standby unit has been reset and started.• The control right has been transferred by Mode switch (not supported by �XL MFCD

and MFSD).

No. 0406Message name Duplexed Control Station Duplexity Controller Power Recovery

Printing example STN1701 Duplex Controller Recover

Meaning For CFCD2, CFCDE, and CFSD;The 5V DC power for DXS2 on the power supply card has recovered.

No. 0408Message name CFCU2 Backup

Printing example STN1701 Backup

Meaning The BCU performs the functions of the indicated CFCU2. The BCU has detected anerror (ex. WDT timeout) in CFCU2 and started to perform the functions of the CFCU2on the basis of the memory data uploaded previously.

Cause NM1 or NP1 error in the indicated CFCU2

13th Edition : Dec.26,2005-00

Page 98: CS 1000/3000 Operating Messages

2-80<2. Message Output Details>

IM 33S02H10-01E

No. 0410Message name CFCU2 Recovery

Printing example STN1701 Recover

Meaning The functions of the indicated CFCU2 have been restored to normal state.

No. 0412Message name CIU Backup

Printing example STN1701 CIU Back up

Meaning The BCU performs the functions of the indicated CIU.

Cause FC1, NP1, or NM3 error in CIU or PS11 or PS12 error. The FC1 error is detected bythe cross-checking between CIU and BCU.

No. 0414Message name CIU Recovery

Printing example STN1701 CIU Recover

Meaning The functions of the indicated CIU have been restored to normal state.

No. 0416Message name CFCU2/UFCH MAC2/PAC Card Out-of-Service

Printing example STN1701 MAC/PAC Out Service NEST1 CARD2

Meaning The MAC2/PAC of the specified number in the specified station is not used for I/Ooperation.Example.• The MAC2/PAC was set to the standby state when the station was powered on.• The MAC2/PAC failed when it was running (Not Ready). Message 0153 may be

output at the same time.

Cause MAC2/PAC does not operate correctly.When MAC2/PAC is duplexed, IOP was detected in one card only.

Action Replace the MAC2/PAC card.

No. 0418Message name CFCU2/UFCH MAC2 Card In-Service

Printing example STN1701 MAC/PAC In Service CARD1

Meaning The MAC2/PAC of the specified number in the specified station is used for I/O opera-tion.

Cause • The MAC2/PAC was set in service when the station was powered on.• The MAC2/PAC has been switched from the standby state.

13th Edition : Dec.26,2005-00

Page 99: CS 1000/3000 Operating Messages

2-81

IM 33S02H10-01E

<2. Message Output Details>

No. 0420Message name Control Station MAC2/PAC or CFCDE MAC3 Out-of-Service

Printing example STN1701 MAC/PAC Out Service NEST1 CARD1

Meaning The MACn/PAC of the specified number in the specified station is not used for I/Ooperation.

Cause The MACn/PAC was set to the standby state when the station was powered on.MACn/PAC does not operate correctly.When MACn/PAC is duplexed, IOP was detected in one card only.

n: number

Action Case for operating incorrectly, replace the MACn/PAC card.

No. 0422Message name Control Station MAC2/PAC or EFCE/CFCDE MAC3 In-Service

Printing example STN1701 MAC/PAC In-Service NEST1 CARD2

Meaning The MACn/PAC of the specified number in the specified station is used for I/O opera-tion.

Cause • The MACn/PAC was set in service when the station was powered on.• The MACn/PAC has been switched from the standby state.

No. 0424Message name Duplexed Control Station Control Unit Standby State

Printing example STN1701 R Stand by

Meaning One of the CPUs in duplexed control station has been set in standby state.This message is output if the standby side is normal after all program copy.

No. 0430Message name Control Station All Program Copy

Printing example STN1701 All Program Copy

Meaning In the duplexed control station, ALL PROGRAM COPY was executed by the controlCPU to the standby CPU.When the ALL PROGRAM COPY execution is completed, the status of the standbyCPU is indicated by message.

15th Edition : Dec.10,2007-00

Page 100: CS 1000/3000 Operating Messages

2-82<2. Message Output Details>

IM 33S02H10-01E

No. 0450Message name Control station control side program database copy to standby side

Printing example FCS0101 Copy

Cause This message is generated when a control station (station name=FCS0101) standbyside CPU card was started.

• ProSafe-RS

Message name Copy program and database on control side of safety control station to standby side

Printing example SCS0101 Copy

Meaning The copying of the program and database on the control side of the safety control sta-tion to the standby side has been started.

Cause This message is displayed when the CPU module on the standby side of the safetycontrol station (station name = SCS0101) was started.

No. 0451Message name Control station control side ready

Printing example FCS0101 RIGHT Control

Meaning Control station (station name=FCS0101) right side or left side (right side in the ex-ample) CPU card become ready to control.

Cause CPU of either right or left side of the control station started normally.

• ProSafe-RS

Message name Information of switching of control side of safety control station

Printing example SCS0101 RIGHT Control

Meaning The CPU module on the right or left side (right side in the above example) of the safetycontrol station (station name = SCS0101) has been set to the control side.

No. 0452Message name Control station standby side ready

FCS0101 RIGHT Stand-By

Meaning Control station (station name=FCS0101) right side or left side (right side in the ex-ample) CPU card has become the standby side.

Cause CPU card of the standby side started operation normally.

• ProSafe-RS

Message name Information of switching of standby side of safety control station

Printing example SCS0101 LEFT Stand - By

Meaning The CPU module on the right or left side (left side in the above example) of the safetycontrol station (station name = SCS0101) has been set to the standby side.

13th Edition : Dec.26,2005-00

Page 101: CS 1000/3000 Operating Messages

2-83

IM 33S02H10-01E

<2. Message Output Details>

No. 0453Message name RIO bus communication card or IO bus interface card is ready to Control

Printing example1 FCS0101 RIO1 Control RIGHT

Printing example2 FCS0101 FIO1 Control RIGHT

Meaning The displayed RIO bus communication card or IO bus interface card is ready to Con-trol.

No. 0454Message name The RIO bus communication card or IO bus interface card is ready to Standby

Printing example1 FCS0101 RIO1 Stand-By RIGHT

Printing example2 FCS0101 FIO1 Stand-By RIGHT

Meaning The RIO bus communication card or IO bus interface card is ready to Standby.

No. 0455Message name Node Maintenance Information

Printing example FCS0101 NODE Maintenance RIO1 NODE 01

Meaning The indicated node is under maintenance.

No. 0456Message name Node Maintenance Release Information

Printing example FCS0101 NODE Maintenance Release RIO1 NODE 01

Meaning The indicated node has been released from maintenance state.

No. 0457Message name I/O module service side notified (for AAM/APM)

Printing example1 FCS0101 IOM In Service UNIT 01 SLOT 01 CH01

Printing example2 FCS0101 IOM In Service RIO1 NODE 01 UNIT 01 SLOT 01 CH01

Meaning A dual-redundant I/O module has entered the output ready state.

No. 0458Message name I/O module out service notified (for AAM/APM)

Printing example1 FCS0101 IOM Out Service UNIT 01 SLOT 01 CH01

Printing example2 FCS0101 IOM Out Service RIO1 NODE 01 UNIT 01 SLOT 01 CH01

Meaning A dual-redundant I/O module has entered the output wait state.

13th Edition : Dec.26,2005-00

Page 102: CS 1000/3000 Operating Messages

2-84<2. Message Output Details>

IM 33S02H10-01E

No. 0459Message name The I/O Module Service Ready (ADM/AMM, FIO related)

Printing example1 FCS0101 IOM In Service UNIT 01 SLOT 01

Printing example2 FCS0101 IOM In Service RIO1 NODE 01 UNIT 01 SLOT 01

Printing example3 FCS0101 IOM In Service FIO1 NODE 01 SLOT 01

Meaning One of the I/O modules in dual-redundant configuration starts running.

• ProSafe-RS

Message name Information on I/O module service side

Printing example SCS0101 IOM In Service FIO NODE 01 SLOT 01

Meaning One side (slot 1 of node 1 in the above example) of a redundant I/O module has gainedcontrol right.

No. 0460Message name The I/O Module Service Stopped (ADM/AMM, FIO related)

Printing example1 FCS0101 IOM Out Service UNIT 01 SLOT 01

Printing example2 FCS0101 IOM Out Service RIO1 NODE 01 UNIT 01 SLOT 01

Printing example3 FCS0101 IOM Out Service FIO1 NODE 01 SLOT01

Meaning One of the I/O modules in dual-redundant configuration stopped service.

• ProSafe-RS

Message name Information of I/O module out service

Printing example SCS0101 IOM Out Service FIO NODE 01 SLOT 01

Meaning An I/O module (slot 1 of node 1 in the above example) has been set to standby orstopped.

No. 0461Message name Node RIO Bus Communication Card Maintenance Information

Printing example FCS0101 RBS Maintenance RIO1 NODE 01 RBS RIGHT

Meaning The right or left RIO bus communication card in the indicated node is in the mainte-nance state.

Cause The front switch of the indicated RIO bus communication card is set to the MAINTposition.

Action Set the front switch of the indicated RIO bus communication card to the ENBL posi-tion.

13th Edition : Dec.26,2005-00

Page 103: CS 1000/3000 Operating Messages

2-85

IM 33S02H10-01E

<2. Message Output Details>

No. 0462Message name Node RIO Bus Communication Card Maintenance Release

Printing example FCS0101 RBS Maintenance Release RIO1 NODE 01 RBS RIGHT

Meaning The RIO bus communication card in the indicated node has been released from themaintenance state.

Cause The front switch of the indicated RIO bus communication card has been set from theMAINT position to the ENBL position if you release the maintenance state.

No. 0471Message name Online downloading normal end

Printing example1 FCS0101 Online Download Complete

Printing example2 FCS0101 Online Download Complete Area = 1

Meaning Downloading of the control station ended normally.

• ProSafe-RS

Message name Normal completion of on-line change download

Printing example SCS0101 Online Download (Integration Database) Complete

Meaning On-line change download to the safety control station has normally been completed.

No. 0474Message name Tag list double-defined error notification

Printing example1 FCS0101 Tag Duplication Error Tag=FIC100

Printing example2 FCS0101 Tag Duplication Error Master-Area= 2 Duplicate-Area= 1 Tag=FIC100

Meaning This message is generated when there is a tag list of the same name in the samecontrol station.

Action Report to Yokogawa’s service department.

• ProSafe-RS

Message name Information of tag list duplicate error

Printing example SCS0101 Tag Duplication Error Tag = TAG001

Meaning A duplicate tag list name exists in the same safety control station.

Action Report to Yokogawa’s service department.

15th Edition : Dec.10,2007-00

Page 104: CS 1000/3000 Operating Messages

2-86<2. Message Output Details>

IM 33S02H10-01E

No. 0475Message name IOM Database Downloading Start

Printing example1 FCS0101 IOM Download Start UNIT 01 SLOT 02 IOM 01

Printing example2 FCS0101 IOM Download RIO1 NODE 03 UNIT 01 SLOT 02 IOM 01

Printing example3 FCS0101 IOM Download FIO1 NODE 01 SLOT 01

Meaning Downloading of database to the displayed I/O module has started.

• ProSafe-RS

Message name Start of database download to I/O module

Printing example SCS0101 IOM Download Start FIO NODE 01 SLOT 01

Meaning Database download to the I/O module indicated in the message has been started.

No. 0476Message name IOM Database Downloading Completed

Printing example1 FCS0101 IOM Download Complete UNIT 01 SLOT 02 IOM 01

Printing example2 FCS0101 IOM Download Complete RIO1 NODE 03 UNIT 01 SLOT 02 IOM 01

Printing example3 FCS0101 IOM Download Complete FIO1 NODE 01 SLOT 01

Meaning Downloading of database to the displayed I/O module completed successfully.

• ProSafe-RS

Message name Normal completion of database download to I/O module

Printing example SCS0101 IOM Download Complete FIO NODE 01 SLOT 01

Meaning Database download to the I/O module indicated in the message has normally beencompleted.

13th Edition : Dec.26,2005-00

Page 105: CS 1000/3000 Operating Messages

2-87

IM 33S02H10-01E

<2. Message Output Details>

No. 0477Message name IOM Database Downloading Aborted

Printing example1 FCS0101 IOM Download Error UNIT 01 SLOT 02 IOM 01 Error= 00F8

Printing example2 FCS0101 IOM Download Error RIO1 NODE 03 UNIT 01 SLOT 02 IOM 01 Error=00F8

Printing example3 FCS0101 IOM Download Error FIO1 NODE 01 SLOT 01 Error= 252B

Meaning An error occurred when downloading database to the displayed IOM.

Cause/Action Find out the cause of error and resolve it, then download to the IOM again. If the dif-ferent errors occurred again after downloading, refer to the detailed error codes andcontact to Yokogawa Service department.

RIO Error codedetails 252B : Can not communicate to the I/O module

252C : I/O Module type is not correctA701 : The designated I/O module is undergoing downloading. Another download-

ing to the module can be performed after the message No.0476 appears indi-cating the current downloading is ended.

A70D : Downloading is completed, but the contents contain errors.A33D : Can not communicate to ACMA33E : Communication route between FCU and ACM is abnormal (Node error, etc.)A33F : The I/O is disconnected

FIO Error CodeDetails A701 : The designated I/O module is undergoing downloading.

3B1B : Both control and backup cards of SB301 or SB302 are abnormal.3B1C : I/O module abnormal, or node abnormalCFxx : An error returnedCF10 : I/O Module type is not correct

ALR1x1 ErrorCode Details A33D : Can not communicate to ALR

A33E : Communication route between FCU and ALR is abnormal (Node error, etc.)A33F : The I/O is disconnected

• ProSafe-RS

Message name Database download error to I/O module

Printing example SCS0101 IOM Download Error FIO NODE 01 SLOT 01 Error=xxxx

Meaning An error occurred during database download to the I/O module indicated in the mes-sage. “xxxx” indicates an error code.

Cause/Action The following lists error codes. If an error occurs, remove the cause, and execute IOMdownload again.If an error other than the following occurred, replace the I/O module and execute IOMdownload again. If other error occurred again, report details to Yokogawa’s servicedepartment.• IOM error codes other than ALR111 and ALR121

A701: This I/O module is currently executing download.3B1B: The I/O module is faulty.CFxx: An error was replied from the I/O module.CF10: The type of the I/O module is not correct.

• Error codes of ALR111 and ALR121A33D: Communication cannot be performed with the ALR1x1.A33E: The communication path between the CPU module and the ALR1x1

is abnormal (node failure, etc.)

15th Edition : Dec.10,2007-00

Page 106: CS 1000/3000 Operating Messages

2-88<2. Message Output Details>

IM 33S02H10-01E

No. 0478Message type Tuning parameters save normal end

Printing example1 FCS0101 Parameter Save Complete

Printing example2 FCS0101 Parameter Save Complete Area=1

Meaning Saving of tuning parameters of the control station ended normally.

No. 0479Message name Tuning parameters save abnormal end

Printing example1 FCS0101 Parameter Save Error Code=961B-0000

Printing example2 FCS0101 Parameter Save Error Area=1 Code= 02A1-0032

Meaning An error was generated during tuning parameters save of the control station.

Error code details 961B: Time-out generated during communication

Cause/Action • System generation function - control station communication failure1. Remove the cause of the communication failure.2. Save the tuning parameters again.

• OthersCheck the system generation function side messages and contact the service de-partment.

No. 0480Message name Periodic processing overload

Printing example FCS0101 Too Heavy Load

Meaning Control station basic scan processing did not end even through a time of 4 times itsperiod had elapsed.

Action Modify the application programs to reduce the CPU load.

• ProSafe-RS

Message name Heavy load on periodical processing

Printing example SCS0101 Too Heavy Load

Meaning The processing of external connection function of the safety control station did not endeven if four times the scan period of the external connection function has elapsed.

Cause The load on the safety control station is too heavy.

Action Correct the application and reduce the load on the safety control station.

No. 0482Message name Tuning parameters save start successful

Printing example1 FCS0101 Parameter Save Start

Printing example2 FCS0101 Parameter Save Start Area=1

Meaning Tuning parameters save has started.

13th Edition : Dec.26,2005-00

Page 107: CS 1000/3000 Operating Messages

2-89

IM 33S02H10-01E

<2. Message Output Details>

No. 0483Message name Tuning parameters save abnormal start failed

Printing example1 FCS0101 Parameter Save Start Error Code=9621-0000

Printing example2 FCS0101 Parameter Save Start Error Area=1 Code=9601-0000

Meaning Tuning parameters save was executed in an state in which tuning parameters savecannot be started.Code shows the detailed error information.

Error code details

9621: Cannot start during online downloading.Online downloading is executing for the same station.Execute tuning parameters save again after the end of the executing online download-ing.

9622: Cannot start while tuning parameters save is executing.Tuning parameters save is executing for the same station.Execute tuning parameters save again after the end of the executing tuning param-eters save.

9623: Cannot start during offline downloading.Offline downloading is executing for the same station.Execute tuning parameters save again after the end of the executing offline download-ing.

9624, 9625: Cannot start during mode change.Offline downloading is probably executing for the same station.Execute tuning parameters save again after the end of the executing offline download-ing.

962C: Cannot save during initialization processing.FCS has not completed started.Wait awhile, then execute tuning parameters save again.

No. 0485Message name SFC block download error

Printing example1 FCS0101 SFC Sequence Download Error Name=SFC001 Code=9601-0000

Printing example2 FCS0101 SFC Sequence Download Error Area=0 Name=SFC001 Code=9601-0000

Meaning Online downloading of SFC block failed.Name is the name of the SFC block that failed to load.Code is the detailed internal information.

Action Modify SFC block and execute downloading again.

No. 0486Message name Recovery from FIO function error

Print Example STN01 FIO Function Recover FIO01 01-02-01

Meaning The Cause of an internal processing error which occurred in ACM71 mounted into thefirst slot of the second unit of the first node of one line of the control station (stationname = STN01) was removed.

13th Edition : Dec.26,2005-00

Page 108: CS 1000/3000 Operating Messages

2-90<2. Message Output Details>

IM 33S02H10-01E

No. 0487Message name FIO function error

Print Example STN01 FIO Function Error FIO01 01-02-01 Code=9D07 Error=xxxx-yyyy

Meaning The internal processing in ACM71 mounted into the first slot of the second unit of thefirst node of one line of the control station (station name = STN01) caused an error.Code and Error show detailed internal information.

Cause/Action Remove the cause of the error based on error code.

Code Error Meaning

9D07 Failures of ACM71.

048701E.EPS

Error Code (=xxxx) Cause

1000 Network interface UP error

1100 Network interface DOWN error

20zz Routing addition error. zz: routing information (1 to 8)

21zz Routing deletion error. zz: routing information (1 to 8)

048702E.EPS

Table Code Table for ACM71 Failures (Code=9D07)

Error(=yyyy) Error Meaning

2965 It is in the state that data cannot input/output.

2966 In Connection operation.

2967 As for Connection, now in Disconnect.

296A The message is too long.

296F The specified operation is not supported in socket.

2971 The specified address family is not supported.

2972 The specified address has already been used.

2973 The specified address cannot be used.

2974 The network has downed.

2975 It is not possible to reach the network.

2977 The connection was aborted.

2978 The connection was reset.

2979 There is no space for buffer.

297A Socket has already been connected.

297B Socket is not connected.

297C After Socket is shutdown, the transmission data cannot be sent.

297E The time-out was generated by TCP.

297F The Connection demand was refused by the other party.

296B296C296D

Protocol type error

048703E.EPS

15th Edition : Dec.10,2007-00

Page 109: CS 1000/3000 Operating Messages

2-91

IM 33S02H10-01E

<2. Message Output Details>

No. 0490Message name FCS Batch Management Ready

Printing example FCS0101 Batch Manager Ready

Meaning Initialization of the FCS process control package was completed normally. The mes-sage is notified upon starting initialization of the FCS.

No. 0491Message name HART Device Status

Printing example FCS0101 FIO01 NODE01 SLOT01 CH01 HART Device Status=XX

Meaning Status notification of the HART device connected to channel 1 (Digital PV channel)of the module in slot 1, node 1, FIO 1 in field control station FCS0101.

13th Edition : Dec.26,2005-00

Page 110: CS 1000/3000 Operating Messages

2-92

IM 33S02H10-01E

<2. Message Output Details>

2.6 Operation Command and Operation RecordMessages (Message Nos. 0501 to 0692)This section describes the operation command and operation record messagesoutput by an HIS.

No. 0501Message name Database equalize request

Printing example Equalize Request (Displayed in message display area.)

Meaning When an HIS starts, the date of the database of another HIS or PC installed in sys-tem generation function is checked, and if the date of the database in the HIS is older,an equalize request is output.

Action If necessary, execute equalization.

No. 0502Message name Database equalization completed normally

Printing example DataBase Equalize Complete

Meaning A new database was loaded into HIS function normally after database downloading.

No. 0503Message name Database equalization ended with error

Printing example Database Equalize not Complete

Meaning HIS function failed to load the database after database downloading.

Action Run database download again.

No. 0505Message name HIS restart request

Printing example HIS Reset Start Request (Equalize)

Meaning Shows that the HIS must be reset started because the amount of changes of thedownloaded database exceeded the memory allowable range.

Action Restart HIS function (log-off).

No. 0506Message name Delete Database file

Print Example Data Base File Deleted from STN02 File = xxxxxxxx

Meaning It is shown to have deleted the database by the instruction from the database mas-ter station.Database master station name (STN02 in this example) and database name(File=xxxxxxx) are displayed.

13th Edition : Dec.26,2005-00

Page 111: CS 1000/3000 Operating Messages

2-93

IM 33S02H10-01E

<2. Message Output Details>

No. 0507Message name Computer Reset Start Request

Printing example Computer Reset Start Request (Shutdown & Power ON/OFF)

Meaning Any change in the hardware was made (such as Control bus interface card definition),it’s necessary to restart the computer.

Action Restart the computer after shutdown and power ON/OFF.

No. 0509Message name System Configuration Warning

Printing example HIS System Configuration Warning

Meaning There is unmatching among station configuration, Control bus interface card setup andcomputer name. There is possibility of an error occurring in database downloading.

Cause • An error in Control bus interface card’s station numbering• Use of an incorrect computer name• Execution of database downloading of the wrong project

No. 0510Message name Database download

Printing example Data Base Download From HIS0102 File=yyyyyyyyyyyyyyyy: Database file name

Meaning The database was downloaded normally from another HIS or PC installed in systemgeneration function. Displays the download source station name (HIS0102 in thisexample) and database name.

No. 0511Message name Database download error

Printing example DataBase Download Error From xxxxxxxx File=yyyyyyyyxxxxxxxx: PC name installed in system generation function.yyyyyyyy: Database file name

Meaning File transfer failed.

Cause System generation function side causes• Incorrect file address.• Project not found.• Transfer source file not found.• File ID not defined.• Access transfer destination file cannot be accessed.• Do no have the target file Read right.

Operation and monitoring function side causes• Do not have the folder/file Write right.• File system is full. (Disk FULL)

13th Edition : Dec.26,2005-00

Page 112: CS 1000/3000 Operating Messages

2-94

IM 33S02H10-01E

<2. Message Output Details>

No. 0513Message name DataBase of the project not relevant to the executing project

Printing example Different Project PROJ03 DataBase from HIS0102 File=yyyyyyyyyyyyyyyy: Database file name

Meaning Equalization notice from HIS0102 was received, but the database was not for theexecuting project.In this case, the equalization isn’t performed.

No. 0514Message name Operation and monitoring function database change

Printing example Data Base Change File=yyyyyyyyyyyyyyyy: Filename

Meaning Database change wasn’t proceeded normally in the setup window.

No. 0515Message name Operation and monitoring function database change error

Printing example Data Base Change Error File=yyyyyyyyyyyyyyyy: Filename

Meaning Database was changed and an error was generated from the HIS setup window.

Action • Download all files in COMMON folder of the project.• Check the setting for Referenced Database on HIS setup window.

No. 0517Message name Number of Registered Tags Overflow

Printing example Tag Volume Overflow

Meaning It indicates that the number of tags and windows has exceeded the limit of HIS moni-toring capacity. The windows and tags that exceeding the limit cannot be monitoredon HIS.

Action To increase HIS monitoring capacity on HIS setting window, or to reduce the numberof tags or windows for monitoring.

No. 0519Message name Duplication of tag names

Print Example Tag Duplication Error

Meaning The same tag names are defined in several projects or the tag name is too long, sothat the project name cannot be added to the tag name.

Cause On the Equalize tab of the HIS Setup window, click the button to display the result ofchecking for duplicate tag names. Any duplicate tag names or tag names of over 13characters are displayed. Change the displayed tag names to resolve the problems.

15th Edition : Dec.10,2007-00

Page 113: CS 1000/3000 Operating Messages

2-95

IM 33S02H10-01E

<2. Message Output Details>

No. 0602Message name Control station all program copy operation

Printing example FCS0101 All Program Copy Operation ONUSER@HIS0124

Meaning All Program Copy was operated on the system status overview display window fromthe control side CPU to the standby side CPU in the dual-redundant control station.

No. 0603Message name Control station system reserve operation

Printing example FCS0101 System Reserve Operation ONUSER@HIS0124

Meaning The system status overview display window shows that control station’s status has be-come “Reserve.”

No. 0604Message name Control station system release operation

Printing example FCS0101 System Release Operation ONUSER@HIS0124

Meaning The system status overview display window shows that control station’s status hasbeen changed from “Reserve” to “Release.”

No. 0605Message name Control station stopped

Printing example FCS0101 System Stop Operation ONUSER@HIS0124

Meaning Control station (FCS0101) was stopped from a HIS.

No. 0606Message name Control station started

Printing example FCS0101 System Start Operation ONUSER@HIS0124

Meaning Control station (FCS0101) was started from a HIS.

No. 0607Message name Program loading to I/O module started

Printing example FCS0101 I/O Module Download Start Operation (%Z010011) ONUSER@HIS0124

Meaning Downloading of program to control station (station name=FCS0101) I/O module(%Z010011) was started by operation from a HIS.

13th Edition : Dec.26,2005-00

Page 114: CS 1000/3000 Operating Messages

2-96

IM 33S02H10-01E

<2. Message Output Details>

No. 0608Message name Control station tuning parameters save

Printing example FCS0101 Parameter Save Operation ONUSER@HIS0124

Meaning Control station (FCS0101) tuning parameters were saved by operation from a HIS.

No. 0609Message name Control station download

Printing example FCS0101 Download Operation ONUSER@HIS0124

Meaning Control station (FCS0101) downloading was started from a HIS.

No. 0626Message Name Time Setting Changed

Printing example Date/Time Set 02.12.16 13:30:00 old=02.12.16 13:28:03

Meaning System clock has been changed from the HIS. With the Time Adjustment, the time ofall HISs and FCSs on the same domain has been adjusted at the same time. With theBus Converter, the time of HISs and FCSs on other domains can be set.

No. 0630Message name System Alarm Acknowledgment

Printing example FCS0101 No.0303 (2002/12/16 10:20:45) ACK ENGUSER@HIS0124

Meaning The system alarm message is acknowledged on the HIS.FCS0101: The station that initiated the acknowledged system alarm.No.0303: The message number of the acknowledged system alarm.2002/12/16 10:20:45: Date and time at which the system alarm occurred.

Remark The above message does not display in system alarm window.

No. 0634Message name Advanced Alarm Filter Setting Change

Printing example Alarm Filter = AF03 {TAG:FIC* & AL:HI} ENGUSER@HIS0214Alarm Filter = Filter Off ENGUSER@HIS0214Alarm Filter = Sum:ON AL:ON OG:OFF Keep:OFF ENGUSER@HIS0124

Meaning1 Settings of Advanced Alarm Filter is changed on Alarm Filter windowAF03: Filter Name{TAG:FIC* & AL:HI}:Filter RuleFilter Off: Filter Disabled

Meaning2 Settings of Advanced Alarm Filter is changed on HIS setup windowSum: Number of Process AlarmsAL: Filtering Process AlarmOG: Filtering Operation Guide MessagesKeep: Keep the Filter-Out Messages

Note This message is not displayed on system alarm window.

13th Edition : Dec.26,2005-00

Page 115: CS 1000/3000 Operating Messages

2-97

IM 33S02H10-01E

<2. Message Output Details>

No. 0635Message name Process alarm acquisition mode changed

Printing example Process Alarm Collection = ALL ONUSER@HIS0124

Meaning The process alarm acquisition mode was changed in the HIS setup window.There are the following acquisition modes:All: AllTag: Tag representative alarmsHigh Priority: High-priority alarms onlyMedium Priority: Medium-priority alarms

Remark This message is not displayed on the System alarm window.

No. 0636Message name Message acknowledgment method changed

Printing example Message Ack Method = ALL ONUSER@HIS0124

Meaning The message acknowledgment method was changed in the HIS setup window.There are the following acknowledgment methods:Group: Group acknowledgmentIndividual: Individual acknowledgment

Remark This message is not displayed on the System alarm window.

No. 0637Message name Referenced database changed

Printing example Database Master = HIS0123 ONUSER@HIS0124

Meaning The referenced database computer was changed in the HIS setup window.

Remark This message is not displayed on the System alarm window.

No. 0638Message name User-defined function key changed

Printing example Function Key No.13 = O .AL FCS0101 LED=.AL FCS0101 ONUSER@HIS0124

Meaning A function key setting was changed in the HIS setup window.

Remark This message is not displayed on the System alarm window.

No. 0639Message name Operation mark changed

Printing example Operation Mark No.13 = Operation Disabled Color = Red ONUSER@HIS0124

Meaning An operation mark was changed in the HIS setup window.

Remark This message is not displayed on the System alarm window.

13th Edition : Dec.26,2005-00

Page 116: CS 1000/3000 Operating Messages

2-98

IM 33S02H10-01E

<2. Message Output Details>

No. 0640Message name Multimedia definition changed

Printing example MultiMedia No.002 = canyon.mid Station=(ALL) ONUSER@HIS0124

Meaning The multimedia definition was changed in the HIS setup window.

Remark This message is not displayed on the System alarm window.

No. 0641Message name Trend display pen assignment changed

Printing example Trend TG0024 Pen No.1 = FIC001-1.PV 0.0 100.0 ONUSER@HIS0124

Meaning A trend display assignment was changed in the pen assignment dialog. The assignedtag name, data item name, range LO and range HI are displayed.

Remark This message is not displayed on the System alarm window.

No. 0642Message name Graphic instrument faceplate assignment changed

Printing example Graphic CONTROL1 Faceplate No.3 = FIC001-1 ONUSER@HIS0124

Meaning An instrument faceplate assignment was changed in the instrument faceplate assign-ment dialog for graphics.

Remark This message is not displayed on the System alarm window.

No. 0644Message name Switching Mode

Printing example OPKB Key Position Change to ENG ENGUSER@HIS0124

Meaning The Mode Selection Key is switched to ENG position.

Remark This message is not displayed on the System Alarm window.

No. 0645Message name Switching User (User-In)

Printing example ENGUSER UserIn from OFFUSER ENGUSER@HIS0124

Meaning ENGUSER logged in on USER-IN dialog box.

Remark This message is not displayed on the System Alarm window.

13th Edition : Dec.26,2005-00

Page 117: CS 1000/3000 Operating Messages

2-99

IM 33S02H10-01E

<2. Message Output Details>

No. 0646Message name Switching User (User out)

Printing example ENGUSER UserOut ENGUSER@HIS0124

Meaning ENGUSER logged out on USER-IN dialog box.

Remark This message is not displayed on the System Alarm window.

No. 0647Message name User Password Changed

Printing example ENGUSER Change Password ENGUSER@HIS0124

Meaning The password of ENGUSER is changed on USER-IN dialog box.

Remark This message is not displayed on the System Alarm window.

No. 0648Message name Setting of message summary master HIS station

Printing example Message Summary Master=HIS0123

Meaning Definition HIS0123 is set as a message summary master station.HIS0123 will hold message summary at next reboot.

Remark This message is not displayed on the system alarm window.

No. 0649Message name Changing of watching Tag volume

Printing example Tag Watch Size=LARGE

Meaning Definition The volume of Tag is changed to large.When you increase size of watching tag, memory has to be increased.

Remark This message is not displayed on the system alarm window.

No. 0650Message name Change trend acquisition pen assignment

Printing example 1 Trend Block=3 Group=12 Pen=7 SAVE ADD FIC001-1.PV Type=1 ONUSER@HIS0124

Printing example 2 Trend Block=3 Group=12 Pen=7 SAVE ADD FIC001-1.PV Type=1 HI=100.0 LO=0.0ONUSER@HIS0124

Meaning The trend acquisition pen assignment is changed on the trend acquisition pen assign-ment builder called from a trend window on HIS.The message shows Trend block number, Trend group, Trend acquisition pen num-ber, store method (SAVE: Overwritten; LOAD: Downloaded), action (ADD: Added;MOD: Modified; DEL: Deleted), Acquisition data set on the builder, and Data typenumber in that order.If the data axis of the trend is changed on the builder, the span of the data axis set onthe builder will be displayed with high limit (HI) and low limit (LO).

Remark This message is not displayed on the system alarm window.

14th Edition : Dec.26,2006-00

Page 118: CS 1000/3000 Operating Messages

2-100

IM 33S02H10-01E

<2. Message Output Details>

No. 0653Message name HIS printer on

Printing example Printer MSG1 ON ONUSER@HIS0124

Meaning A HIS printer was activated in the HIS setup window

Remark This message is not displayed on the System alarm window.

No. 0654Message name HIS printer off

Printing example Printer MSG1 OFF ONUSER@HIS0124

Meaning A HIS printer was deactivated in the HIS setup window.

Remark This message is not displayed on the System alarm window.

No. 0655Message name HIS printer assignment change

Printing example Printer HDCP =\\HIS0124\lp0124

Meaning Assignments of HIS and NT printers were changed in the HIS setup window.

Remark This message is not displayed on the System alarm window.

No. 0656Message name Buzzer sound output destination changed

Printing example Buzzer Device = OPKB ONUSER@HIS0124

Meaning The output destination device for buzzer sound was changed in the HIS setup window.There are the following three devices:BEEP: Computer beepOPKB: Optional operator keyboardSOUND: Sound processor

Remark This message is not displayed on the System alarm window.

No. 0657Message name Window mode changed

Printing example Window Mode = FULL SCREEN ONUSER@HIS0124

Meaning The HIS window mode was changed in the HIS setup window.FULL SCREEN: Full screen modeWINDOW: Window mode

Remark This message is not displayed on the System alarm window.

13th Edition : Dec.26,2005-00

Page 119: CS 1000/3000 Operating Messages

2-101

IM 33S02H10-01E

<2. Message Output Details>

No. 0658Message name Enable/Disable Touch Panel Function

Printing example CRT1 Touch Panel Status Change to xxxx

Meaning The touch panel function is switched ON or OFF.The details of xxxx and their indications are as follows;When the function is switched ON : EnableWhen the function is switched OFF: DisableUsually, when cleaning the CRT, the touch panel is temporarily switched OFF.

Note This message may be generated only in the Console type HIS with touch panel func-tion.

No. 0659Message name Calibration operation on touch panel

Printing example CRT1 Touch Panel Calibrated

Meaning The touch position of the touch panel was calibrated.

Note This message may be generated only in the Console type HIS with touch panel func-tion.

No. 0663Message name Equalization operation

Printing example Data Base Equalize Start ONUSER@HIS0124

Meaning Equalization operation was executed in system maintenance window.

No. 0691Message name Authentication server connection error

Printing example Can not Connect to the Authentication Server [ONUSER@HIS0124]

Meaning Connection to authentication server encountered an error.

Action Check the operation status of the authentication server PC and its network status.

Remark This message does not display in system alarm window.

No. 0692Message name Authentication server connection recovered

Printing example Connection with the Authentication Server Established [ONUSER@HIS0124]

Meaning Connection to authentication server recovered.

Remark This message does not display in system alarm window.

15th Edition : Dec.10,2007-00

Page 120: CS 1000/3000 Operating Messages

2-102

IM 33S02H10-01E

<2. Message Output Details>

2.7 FCS Related Messages(Message Nos. 0721 to 0799)This section describes the messages generated in the CS 1000/CS 3000 field controlstations and the messages generated in the ProSafe-RS safety control stations.

No. 0721Message name SEBOL error (Fatal error: SFC block)

Printing example FCS0101 SFC001 PROGNAME FUNCNAME S=10(0) L=1500 20411-0000FCS0101: Station nameSFC001: Tag namePROGNAME: SFC sequence nameFUNCNAME: Function name10: Step No.0: Plane No.1500: Error line No.20411-0000: Error code

PROGNAME L=10 FNNAME1 L=10 - - - - FUNCNAME L=1500PROGNAME: Main program name10: Line number that called FNNAME1.FNNAME1: FNNAME1 function name10: Line number that called FNNAME2.FUNCNAME: Currently executing function name1500: Line No.

Meaning A fatal error (SEBOL error) was detected during SFC block execution.If the error was detected by transition condition, <line number> becomes -1 to -8.The leftmost transition condition is -1, the next is -2, -3, ...-8 and so on.The second and subsequent lines are the user function calling path when executinga user function. During main program execution, the second and subsequent lines arenot output.

Action Remove the cause of the error based on the step No., line No., and error code.

SEE ALSO

For the error codes, see the following:

H1.13, “Error Handling” in the Reference (IM 33S01B30-01E)

15th Edition : Dec.10,2007-00

Page 121: CS 1000/3000 Operating Messages

2-103

IM 33S02H10-01E

<2. Message Output Details>

No. 0723Message name SEBOL error (SFC block)

Printing example FCS0101 SEBOL001 PROGNAME FUNCNAME S=10(0) L=1200 300-B030FCS0101: Station nameSEBOL001: Tag namePROGNAME: SFC sequence nameFUNCNAME: Function name10: Step No.0: Plane No.1200: Error line No.300-B030: Error code

PROGNAME L=10 FNNAME1 L=10 - - - - FUNCNAME L=1200PROGNAME: Main program name10: Line number that called FNNAME1.FNNAME1: FNNAME1 function name10: Line number that called FNNAME2.FUNCNAME: Currently executing function name1200: Line No.

Meaning An non-fatal error (SEBOL error) was detected during SFC block execution.When the error was detected by transition condition, <line number> is -1 to -8.The leftmost transition condition is -1, the next is -2, -3, ...-8 and so forth.The second and subsequent lines are the user function calling path when executinga user function. During main program execution, these lines are not output.

Action Remove the cause of the error based on the step No., line No., and error code.

SEE ALSO

For the error codes, see the following:

H1.13, “Error Handling” in the Reference (IM 33S01B30-01E)

No. 0725Message name Arbitary character string system alarm generation

Printing example FCS0101 (arbitrary character string)

Meaning An arbitrary character string system alarm is generated by SEBOL sysalarm state-ment, etc.

No. 0726Message name Arbitary character string system alarm recovery

Printing example FCS0101 (arbitrary character string)

Meaning An arbitrary character string system alarm is recovered by SEBOL sysalarm recoverstatement, etc.

15th Edition : Dec.10,2007-00

Page 122: CS 1000/3000 Operating Messages

2-104

IM 33S02H10-01E

<2. Message Output Details>

No. 0727Message name Block mode recovery error information

Printing example1 FCS0101 Block Mode Change Error Block=PID001Code=9601-0000

Printing example2 FCS0101 Block Mode Change Error Area=1 Block=PID001 Code=9601-0000FCS0101: Station namePID001: Tag name9601-0000: Error code

Meaning Block mode recovery failed at end of downloading.

Action Reset the block mode that failed to recover from a HIS.

• ProSafe-RS

Message name Block mode recovery error information

Printing example SCS0101 Block Mode Change Error Block=TAG001 Code=9601-0000TAG001: Tag name9601-0000: Error code

Meaning Block mode recovery failed at end of downloading.

Action Report the error code to Yokogawa’s Service department.

No. 0729Message name SFC block main program intermediate language downloading error information

Printing example1 FCS0101 SFC Program Download Error Block=SFC001 Code=9601-0000

Printing example2 FCS0101 SEBOL Program Download Error Area=1 Block=SEBOL001 Code=9601-0000FCS0101: Station nameSFC001: Tag name9601-0000: Error code

Meaning SFC block main program intermediate language downloading failed.

Action Provide a differential at the SFC block main program that failed to download and ex-ecute online downloading.

13th Edition : Dec.26,2005-00

Page 123: CS 1000/3000 Operating Messages

2-105

IM 33S02H10-01E

<2. Message Output Details>

No. 0731Message name Unit error (unit procedure)

Printing example FCS0101 UNITNAME UNIT TAGNAME OPEID STEPNO CONDNO AD01-0000FCS0101: Station nameUNITNAME: Unit nameTAGNAME: Operation tag nameOPEID: Operation IDSTEPNO: Step No.CONDNO: Transition condition No.AD01-0000: Error code

Meaning A fatal error was detected during unit procedure execution.

Cause A unit procedure execution error was detected during unit procedure execution.

Action Remove the cause of the error based on the error code.

Decimal Hexadecimal Description

073101E.EPS

44305 $AD11 State transition is disabled.

44306 $AD12 Initialization operation is in progress.

44307 $AD13 Invalid data item name

44308 $AD14 Interrupt processing is running.

44309 $AD15 Non-existing generic name is used, or non-existing operation generic name is used.

44310 $AD16 Invalid tag name specified in an operation name.

44311 $AD17 Unmatched left- and right-side data types in a transition condition.

44312 $AD18 Cannot change the block status in O/S block mode.

44313 $AD19 Constant is used on the left side member of a transition condition.

44314 $AD1A Invalid tag name used as a step transition condition.

44315 $AD1B Invalid tag name used as a parallel transition condition.

44317 $AD1D Cannot run a unit because it is under online maintenance.

44338 $AD32 Cannot run an operation.

44339 $AD33 Cannot execute pre-status change processing for an operation.

44340 $AD34 Cannot execute post-status change processing for an operation.

44341 $AD35 Cannot send a signal to an operation.

44343 $AD37 Cannot convert an operation generic name to a tag name.

44344 $AD38 Simultaneous step start ups exceed the limits.

44345 $AD39 Simultaneous parallel execution exceed the limits.

44346 $AD3A The number of parallel maximum steps is exceeded within the parallel.

44347 $AD3B Cannot obtain the dynamic management area.

44348 $AD3C Cannot obtain a state transition matrix, or transition destination is not defined.

44349 $AD3D Cannot obtain a unit procedure

13th Edition : Dec.26,2005-00

Page 124: CS 1000/3000 Operating Messages

2-106

IM 33S02H10-01E

<2. Message Output Details>

Decimal Hexadecimal Description

Decimal Hexadecimal Description073102E.EPS

44354 $AD42 EXECERR action is not defined for a state transition matrix.

44357 $AD45 Unit recipe start up was requested for a fixed procedure unit.

44418 $AD82 State transition matrix does not exist.

44421 $AD85 Unit status name is not defined in the builder.

44423 $AD87 Status change command name is not defined in the builder.

44426 $AD8A Target status name is not defined in the builder.

44427 $AD8B The corresponding state transition is prohibited in the state transition matrix.

44430 $AD8E Unit procedure is under online maintenance.

44431 $AD8F Unit procedure does not exist.

44434 $AD92 Unit procedure is not specified.

44435 $AD93Unit allocation dynamic area is not allocated. (Average number of parallelexecution units defined by station or the number of unit instruments is "0.")

44437 $AD95 Available unit dynamic work area falls below 5 %.

44438 $AD96 No unit dynamic work area is available.

44451 $ADA3 Unit is already active.

44452 $ADA4 Unit is already inactive.

44467 $ADB3 Process alarm character string is not defined by the builder.

44469 $ADB5 Non-existing generic name is used.

44470 $ADB6 Array subscript for the generic name is out of range, or error in the array dimension.

44471 $ADB7 Null character string is assigned to a tag name assigned to the generic name.

44512 $ADE0 The unit does not allocate valve pattern monitor.

44513 $ADE1 Cannot allocate the valve pattern monitor because the block status of the unitis END.

44514 $ADE2 Cannot allocate the valve pattern monitor because the block status of the unitis ABORTED.

44515 $ADE3 The unit has already allocated another valve pattern monitor.

44543 $ADFF Unsupported function is used.

13th Edition : Dec.26,2005-00

Page 125: CS 1000/3000 Operating Messages

2-107

IM 33S02H10-01E

<2. Message Output Details>

Decimal Hexadecimal Description073103E.EPS

45321 $B109 Signals with a return signal cannot be transferred because interrupt signal reception processing hasalready been defined to the corresponding signal at the signal recipient SFC block.

45322 $B10A Signals cannot be received because the number of signal parameters exceeds the maximum number of signal parameters.

45323 $B10B Signals cannot be received because the maximum receiving number of signals are queued.

45324 $B10C Signals cannot be received because the maximum receiving number of signals are queued. (including those in return signal processing)

45325 $B10D "wait for qsignal" was executed in a program other than a main program.

45326 $B10E Maximum number of queuing signals that can be received is "0."

45360 $B130 Internal error occurred at the signal destination.

45320 $B108 Illegal operation for an interrupt signal was made.

45569 $B201 Function permitted only in an operation

45571 $B203 Has not been run from a unit

45572 $B204 SFC blocks do not exist at all.

45573 $B205 Starting up of blocks other than operation from the unit was attempted.

45574 $B206 Block status cannot be changed because the block mode of an operation is in O/S.

45575 $B207 Being run from another unit

45576 $B208 Block status cannot be changed because the pre-status change processing is in progress.

45577 $B209 Block status cannot be changed because the post-status change processing is in progress.

45578 $B20A Database associated with the SFC sequence name is not found.

45579 $B20B SFC sequence main program is under online maintenance.

45580 $B20C Pre-status change processing judged the status change invalid.

45581 $B20D Error was detected during the pre-status change processing.

45582 $B20E Pre-status change processing exceeded the maximum number of lines that can be run.

45583 $B20F SFC sequence main program does not exist.

45584 $B210 Online maintenance of the SFC sequence main program is incomplete.

45585 $B211 SEBOL area database does not exist.

45586 $B212 Cannot run an operation because no dynamically reserved area is available.

45587 $B213 Cannot change the block status because the operation termination processing is in progress.

45616 $B230 Internal error occurred in an operation.

Decimal Hexadecimal Description

45314 $B102 Signal destination is other than SFC block, operation, or unit.

45315 $B103 Signaling operation illegal for a unit was sent.

45316 $B104 Destination block is halted due to a database error.

45317 $B105 Destination block is not running.

45318 $B106 Signal processing with the specified signal name is not defined at the signal recipient SFC block.

45319 $B107 Neither signal processing with the specified signal name nor queued signal processing is not definedat the signal recipient SFC block.

13th Edition : Dec.26,2005-00

Page 126: CS 1000/3000 Operating Messages

2-108

IM 33S02H10-01E

<2. Message Output Details>

No. 0733Message name Unit error (SEBOL interpreter)

Printing example FCS0101 UNITNAME OPER TAGNAME OPEID SEBOLID STEPNO CONDNOAD01-0000FCS0101: Station nameUNITNAME: Unit nameTAGNAME: Operation tag nameOPEID: Operation IDSEBOLID: SEBOL IDSTEPNO: Step No.CONDNO: Condition No.AD01-0000: Error code

Meaning An error was detected in operation control during unit procedure execution.

Cause An operation error was detected during unit procedure execution.

Action Remove the cause of the error based on the error code of No.0731.

SEE ALSO

For the error codes, see the following:

H1.13, “Error Handling” in the Reference (IM 33S01B30-01E)

No. 0735Message name Unit Error (batch execution management)

Printing example FCS0101 UNITNAME BATCH BATCHID RCPGR PARTNO AD01-0000FCS0101: Station nameUNITNAME: Assign unit nameBATCHID: Batch IDRCPGR: Recipe group numberPARTNO: Unit recipe numberAD01-0000: Error code

Meaning A batch execution management error is detected during SEBOL block execution.

Cause A batch execution management error is detected during unit procedure execution.

Action Eliminate the cause of the error based on the error code of No.0731.

13th Edition : Dec.26,2005-00

Page 127: CS 1000/3000 Operating Messages

2-109

IM 33S02H10-01E

<2. Message Output Details>

No. 0737Message name FCS Batch Execution Management Error

Printing example FCS0101 BATCHID RECIPENAME Gr.02 No.01 Code=xxxx-0000-yyyyFCS0101: Station nameBATCHID: Batch IDRECIPENAME: Recipe name02: Recipe group number01: Unit recipe numberCode: Error code (xxxx : error code, yyyy : detail error code)

Meaning A critical batch execution management error is detected during execution.

Action Eliminate the cause of the error based on the error code and error detail code.

xxxx (Hex) Explanation

AE02 Batch ID defined in duplicate

AE03 Recipe or unit recipe not supported by the FCS

AE04 Recipe status error

AE05 Unit recipe status error

AE06 Illegal status change request

AE07 Invalid unit recipe number

AE08 Unit recipe number 1 specified

AE09 Invalid common block name

AE0A Invalid data item name

AE0E Invalid management data base address

AE0F Abnormal recipe data base area pointer

AE10 Download station error

AE13 Illegal download request

AE14 Communication error

AE16 Non-ACTIVE recipe status

AE30 Inadequate total block size unavailable

AE31 Free amount of consecutive space unavailable

AE32 Block not found

AE50 Wrong status073701E.EPS

13th Edition : Dec.26,2005-00

Page 128: CS 1000/3000 Operating Messages

2-110

IM 33S02H10-01E

<2. Message Output Details>

yyyy (Hex) Explanation

Upper two digits

10** Loader reception module

11** Unit end posting module

12** Periodic execution module

13** Mail reception module

14** Special data access handling module

15** Mail transmission module

16** Initialization module

17** Mail handling module

Lower two digits

**02 Batch ID already existing

**04 Common block access error

**05 Download station error

**06 Recipe or unit recipe not supported by the FCS

**07 Unit recipe execution start request error

**08 Command incompatible with the current unit recipe status

**09 Forced unit end inoperable

**0A Communication error

**0B Abnormal station-common table address

**0C Abnormal recipe link

**0D Abnormal unit recipe link

**0E Command incompatible with the current unit recipe status

**13 Unit recipe cancellation error

**14 Illegal download request

**15 Batch ID entry disabled

**16 Batch ID deletion disabled

**18 Non-ACTIVE recipe status

**01 Illegal request

073702E.EPS

No. 0739Message name Unit Busy (batch execution management)

Printing example FCS0101 BATCHID RECIPENAME Gr.02 No.01 Unit BusyFCS0101: Station nameBATCHID: Batch IDRECIPENAME: Recipe name02: Recipe group number01: Unit recipe number

Meaning The following error is detected: the equivalent unit is already in use, although a unitrecipe execution start has been requested.

13th Edition : Dec.26,2005-00

Page 129: CS 1000/3000 Operating Messages

2-111

IM 33S02H10-01E

<2. Message Output Details>

No. 0743Message name Self-diagnostic ENBUS Failure

Printing example FCS0101 EN-BUS Alarm EN-BUS No.1

Meaning The EN-BUS in question has failed.

Cause There is a failure in the backboard bus within the FCU nest or the card inserted there.

Action Replace the FCU nest or inserted card.

• ProSafe-RS

Message name Self-diagnostic SEN-BUS Failure

Printing example SCS0101 SEN-BUS Alarm SEN-BUS No.1

Meaning The SEN-BUS in question has failed.

Cause There is a failure in the SEN-BUS in the CPU node or the CPU module mounted.

Action Replace the CPU node or the CPU module mounted.

No. 0744Message name Self-diagnostic ENBUS Recovery

Printing example FCS0101 EN-BUS Recover EN-BUS No.1

Meaning The EN-BUS in question has returned to normal.

• ProSafe-RS

Message name Self-diagnostic SEN-BUS Recovery

Printing example SCS0101 SEN-BUS Recover SEN-BUS No.1

Meaning The SEN-BUS in question has returned to normal. (This is a recovery message of No.0743.)

No. 0745Message name Mismatched Database

Printing example FCS0101 Database Mismatched

Meaning The database for a duplexed system has been loaded to a CPU card for a single-con-figuration system.

Action Select the type of CPU and database so they match.

13th Edition : Dec.26,2005-00

Page 130: CS 1000/3000 Operating Messages

2-112

IM 33S02H10-01E

<2. Message Output Details>

No. 0747Message name Notification of Failure to Load SEBOL Functions

Printing example1 FCS0101 SEBOL Function Load Error Area=0 Name=FNC01 Code=9601-0000

Printing example2 FCS0101 SEBOL Function Download Error Area=0 Name=FNC01 Code=9601-0000

Meaning Failed to load SEBOL functions online.

Action Execute online Load by obtaining some differences with SEBOL User function pro-gram which failed to load.

No. 0749Message name Self-diagnosis Detected an I/O Error

Printing example1 FCS0101 FIO Self Diag Error CODE = 40000B4E DET = 00000000

Printing example2 FCS0101 RIO Self Diag Error RIO01 CODE = 40000B4E DET = 00000000

Printing example3 FCS0101 FIO Self Diag Error FIO01 CODE = 40002512 DET = 00000000

Meaning RIO or FIO self-diagnosis detected an error.

Cause RB301 self-diagnosis detected a communication error between control and standbycards.

Action Take proper action after inspecting the details of CODE and DET. Contact Yokogawaservice department with the contents of CODE and DET.The details of error codes are as follows.xxxx9D03 : Self-diagnosis detected an error in IOM busxxxx9D04 : Self-diagnosis detected an error in dual-redundant configuration of

AMC80xxxx9D05 : Self-diagnosis detected that AMC80 switched control rightxxxx9D06 : Self-diagnosis detected a BN bus errorxxxx9D08 : Self-diagnosis detected an IOM dual-configuration error

• ProSafe-RS

Message name Self-diagnosis detected an I/O Error

Printing example SCS0101 FIO Self Diag Error FIO CODE = 00005119 DET = 00000000

Meaning I/O error was detected during self-diagnosis.

Cause/Action The action varies depending on the Code and DET. Contact Yokogawa service de-partment with the contents of CODE and DET.The following describes the contents of CODE and DET.• CODE = 00005119

An error was detected in the redundant control unit. Switching is not performed evenif an error occurred on the control side. Replace the I/O module.

• DET = nnss0000 (Mounting position of the error generating module, nn: Node num-ber, ss: Slot No.)

13th Edition : Dec.26,2005-00

Page 131: CS 1000/3000 Operating Messages

2-113

IM 33S02H10-01E

<2. Message Output Details>

No. 0750Message name I/O Recovery from the error detected by self-diagnosis

Printing example1 FCS0101 FIO Self Diag Recover CODE = 00000000 DET = 00000000

Printing example2 FCS0101 RIO Self Diag Recover RIO01 CODE = 00000000 DET = 00000000

Printing example3 FCS0101 FIO Self Diag Recover FIO01 CODE = 00000000 DET = 00000000

Meaning Recovery from RIO or FIO error detected by self-diagnosis.

• ProSafe-RS

Message name I/O Recovery from the error detected by self-diagnosis

Printing example SCS0101 FIO Self Diag Recover FIO CODE = 00000000 DET = 00000000

Meaning Recovery from I/O error detected by self-diagnosis. (This is a recovery message ofNo. 0749.)

No. 0751Message name Time self-diagnostic testing error

Printing example FCS0101 RIGHT Time Self Diag Error Code=00030021

Meaning A time self-diagnostic testing error was detected during single execution.

Cause VEHICLE clock trouble, or RTC trouble.

Action Replace the CPU card.

• ProSafe-RS

Message name Time self-diagnostic testing error

Printing example SCS0101 RIGHT Time Self Diag Error Code=00030021

Meaning A clock error is detected by self-diagnosis while the CPU of either redundant or non-redundant is running.

Cause VEHICLE clock, RTC or GPS clock trouble

Action Replace the CPU module.

13th Edition : Dec.26,2005-00

Page 132: CS 1000/3000 Operating Messages

2-114

IM 33S02H10-01E

<2. Message Output Details>

No. 0753Message name Communication Overload

Printing example FCS0101 Communication Overload

Meaning Communication load to control station exceeded the limit.

Cause There were many communication demands from operation and monitoring function’swindow or application program to the control station.

Action Close the relevant window to the control station of the operation and monitoring func-tion side. Or, reduce the amount of the communication to the control station.

• ProSafe-RS

Message name Communication Overload

Printing example SCS0101 Communication Overload

Meaning Communication load to safety control station exceeded the limit.

Cause There were many communication demands from the operation and monitoring func-tion window or application programs to the safety control station.

Action If the windows for the indicated safety control station are displayed on the CS 3000HIS, the windows need to be closed. Or modifying the application programs may re-duce the communication load to the safety control station.

No. 0755Message name Failed to download the user customizable algorism

Printing example APCS0101 UTAG0001 failed loading PROG001 (0xXXXXXXXX)

Meaning An error occurred when downloading the user customizable algorism.

Action The error maybe caused by missing of the functions that the user customizablealgorism referenced or abnormality in the DLL file of the user customizable algorism.The error code is the Windows error code.

No. 0757Message name Cannot find the function of user customizable algorism

Printing example APCS0101 PROG001 can not find PERIODICAL, ONESHOT

Meaning A function of user customizable algorism is not defined.

Action Malfunction may occur to the user program due to this error. All the functions of theuser customizable algorism should be properly defined.

13th Edition : Dec.26,2005-00

Page 133: CS 1000/3000 Operating Messages

2-115

IM 33S02H10-01E

<2. Message Output Details>

No. 0759Message name User customizable block terminated with error

Printing example APCS0101 UTAG0001 PROG001 stopped with a user-detected error in PERIODICAL

Meaning The user customizable block mode is turned to O/S for checking the error in the user-defined function of the user customizable algorism.

Action Debug the user-defined program. This message is the return message forUCAERR_STOPME (terminated with error) of the user-defined program.

No. 0761Message name User customizable block aborted (exception handling)

Printing example APCS0101 UTAG0001 PROG001 caused an exception (0xC0000005) in PERIODI-CAL

Meaning The user customizable block mode is turned to O/S due to an unexpected error foundin the user-defined function of the user customizable algorism.

Action Malfunction may occur to the user program due to this error. Debug the user-definedprogram to correct the mistake. The error code is the Windows error code. More in-formation for parsing the errors is attached as messages.

No. 0763Message name User customizable block aborted (timeout)

Printing example APCS0101 UTAG0001 PROG001 exceeded the time limit in PERIODICAL

Meaning The user customizable block mode is turned to O/S due to running time of the user-defined function in the user customizable algorism exceeds the time limit.

Action Malfunction may occur to the user program due to this error. Debug the user-definedprogram to correct the mistake.

No. 0765Message name User customizable block aborted (timeout)

Printing example APCS0101 UTAG0001 PROG001 exceeded the time limit in ONESHOT, called byST003

Meaning The user customizable block mode is turned to O/S due to running time of the user-defined function in the user customizable algorism exceeds the time limit.

Action Malfunction may occur to the user program due to this error. Debug the user-definedprogram to correct the mistake.

13th Edition : Dec.26,2005-00

Page 134: CS 1000/3000 Operating Messages

2-116

IM 33S02H10-01E

<2. Message Output Details>

No. 0767Message name ESB Bus Error (One-side SB301/CP401 Error)

Printing example FCS0101 FIO-BUS Fail FIO1 RIGHT BUS No.1

Meaning A communication error occurred in right side interface (CP401 I/O controller/SB301)of the FIO line 1, bus 1 of the control station (station name=FCS0101). (The com-munication of all nodes on the bus 1 failed)

Action Since the error is detected in an I/O communication interface, so that the cause of thefailure may exist in the CP401 I/O controller or in the SB301 card.

• ProSafe-RS

Message name Faulty one ESB bus in CPU module

Printing example SCS0101 FIO-BUS Fail FIO RIGHT BUS No.1

Meaning A communication error (bus1 in the above example) occurred in standby side CPUmodule (right side in the above example) of the safety control station (station name= SCS0101). (Communication with all nodes on the bus1 side became abnormal.)

Cause The CPU module or the backboard of the CPU node may be faulty.

Action Replace the CPU module or the CPU node.

No. 0768Message name Single ESB Bus Recovery

Printing example FCS0101 FIO-BUS Recover FIO1 RIGHT BUS No.1

Meaning Right side bus interface card of bus 1, FIO line 1 of control station (stationname=FCS0101) recovered

• ProSafe-RS

Message name Single ESB bus in CPU module Recovery

Printing example SCS0101 FIO-BUS Recover FIO RIGHT BUS No.1

Meaning A communication error (bus1 in the above example) in standby side CPU module(right side in the above example) of the safety control station (station name =SCS0101) recovered. (This is a recovery message of No. 0767.)

15th Edition : Dec.10,2007-00

Page 135: CS 1000/3000 Operating Messages

2-117

IM 33S02H10-01E

<2. Message Output Details>

No. 0770Message name Node Temperature Recovery

Printing example FCS0101 Node Temperature Recover FIO1 NODE 01

Meaning Node 1 of FIO line 1 of the control station (station name=FCS0101) recovered fromthe temperature error.

No. 0787Message name Self-diagnosis detected an I/O error

Printing example FCS0101 I/O Diagnosis Error IO 01 RIGHT CODE=02518000 00000000

Meaning A self-diagnosis error occurred in one FIO system of the control station (station name= FCS0101) with error code (CODE: representative error code and detail error code).As a general rule, this message is transmitted together with other I/O error messages(such as 0061) in order to notify the detailed error source.The details of error codes are as follows.

Table Message No. 0787 - Error Code Detail

078701E.EPS

Error code(Upper 8 digits)

Error detail(Lower 8 digits)

FactorCode (hexadecimal, 16 digits)

02518000

02548006

Other than above

00000000

nnnnmmmm

An error has occurred while accessing an SB301 or the FIO controller of a CP401.

This error occurs when the connection from one SB301 or the FIO controller of a CP401 to the SB buses at both ends has became abnormal. On the FFCS, the information on self-diagnostic results is displayed as error detail.

Self-diagnostic error of an SB301 or the FIO controller of a CP401

The error might have been caused by one of the following reasons; an SB301 is faulty, the FIO controller of a CP401 is faulty, or the FCU backboard bus is faulty.

The error might have been caused by either of the following reasons; an SB301 is faulty or the FIO controller of a CP401 is faulty.

The error might have been caused by one of the following reasons; an SB301 is disengaged, an SB301 is faulty, the FIO controller of a CP401 is faulty, or the FCU backboard bus is abnormal.

• ProSafe-RS

Message name Self-diagnosis detected I/O error in CPU module

Printing example SCS0101 I/O Diagnosis Error IO RIGHT CODE=02518000 00000000

Meaning A self-diagnosis error occurred in a CPU module (right side in the above example) ofthe safety control station (station name = SCS0101).

Table Message No. 0787 - Error Code Detail

078702E.EPS

Error code(Upper 8 digits)

Error detail(Lower 8 digits)

FactorCode (hexadecimal, 16 digits)

0251 8000

0255 8082

0000 0000

0000 0270

A CPU module error was detected.

This code indicates that the revision of the firmware (F4) in the CPU module is obsolete for the system configured with Optical ESB Bus Repeater modules.

If a system contains Optical ESB Bus Repeater module, the proper revision of CPU should be used.

Replace the CPU module.

14th Edition : Dec.26,2006-00

Page 136: CS 1000/3000 Operating Messages

2-118

IM 33S02H10-01E

<2. Message Output Details>

No. 0791Message name APCS or general-purpose subsystem gateway (GSGW) start error

Printing example 1 APCS0101 Start Error Code=0001-0000

Printing example 2 GSGW0101 Start Error Code=0001-0000

Meaning APCS or general purpose subsystem gateway (GSGW) cannot be started. A detailederror code is indicated.

Action Check the detailed error code and resolve the cause of the error.

Table Detailed Error Codes of APCS and General Purpose Subsystem Gateway (GSGW)

0001-0000

Code

0001-0001

Offline downloading the APCS or GSGW again from the system builders.

Restart Windows. If the error occurs again, APCS software (LFS1200) or GSGW software (LFS1250 or PFS1250) needs to be re-installed.

APCS or GSGW memory image file abnormal. Because of the PC is terminated with error and the control functions are aborted without proper shutdown processing.

Error occurred in operating system.

0002-0000

The error maybe caused due to theconnection with OPC server is not severed, or due to the OPC client is not completely stopped. Restart the GSGW after moment. If the same error occurs again, shutdown and restart the PC.

GSGW start failure due to OPC client is running.

079101E.EPS

Meaning Action

No. 0795Message name Inappropriate ID

Printing example 1 APCS0101 Inappropriate ID Number

Printing example 2 GSGW0101 Inappropriate ID Number

Meaning The ID number of the APCS or GSGW PC is inconsistent with the keycode in the setupFD.

Action Use a consistent keycode FD.

No. 0796Message name UPS Diagnosis Error

Printing example SIOS0131 UPS Diagnose Error

Meaning Abnormality is detected in the UPS for supplying power to SIOS.

Action Refer to the User's Manual of the UPS.

14th Edition : Dec.26,2006-00

Page 137: CS 1000/3000 Operating Messages

2-119

IM 33S02H10-01E

<2. Message Output Details>

No. 0797Message name PSU power failure

Printing example 1 APCS0101 AC Fail

Printing example 2 GSGW0101 AC Fail

Printing example 3 SIOS0131 AC Fail

Meaning The PSU for APCS, GSGW, or SIOS is losing power and the UPS voltage is slopingdown.

Action Restore the power supply to the PSU as soon as possible; otherwise, the APCS,GSGW, or SIOS will start shutdown procedure in a few minutes.

No. 0798Message name Power Supply Recovered

Printing example 1 APCS0101 AC Recover

Printing example 2 GSGW0101 AC Recover

Printing example 3 SIOS0131 AC Recover

Meaning The power supply to APCS, GSGW, or SIOS recovered from main power supply fail-ure.

No. 0799Message name APCS or GSGW starts shutdown due to main power supply failure

Printing example 1 APCS0101 AC Fail Shutdown Execute

Printing example 2 GSGW0101 AC Fail Shutdown Execute

Meaning APCS or GSGW starts shutdown procedure (Emergency Shutdown Procedure) dueto main power supply failure.

14th Edition : Dec.26,2006-00

Page 138: CS 1000/3000 Operating Messages

2-120

IM 33S02H10-01E

<2. Message Output Details>

2.8 HIS Peripherals Messages(Message Nos. 0811 to 0892)This section describes the HIS peripherals messages.

No. 0811Message name FA-M3 Hardware error occurrence

Printing example FA-M3 Hardware Error ( XXX )

Meaning FA-M3 Hardware error occurred. As for XXX, one of the following characters are dis-played.CPU *** : CPU error

One of the following is displayed in “***”.Self Test : Self-diagnostic is abnormal.Program : Program is abnormal.Communication : Communication between CPUs is abnormal.Device Access : Device access is abnormal.Internal : Internal system is abnormal.Not Ready : CPU is not ready.

Device Slot** : Input/Output module error.Device Not Ready Slot** : The Input/Output module is not mounted or fails.

The slot number of module with an error is displayed in “**”.

Action Confirm the status of LED displayed in each module of FA-M3, and solve the prob-lem according to IM of FA-M3.

No. 0813Message name FA-M3 Communication error occurrence

Printing example FA-M3 Communication Error (XXX)

Meaning A communication error occurred in FA-M3. As for XXX, one of the following charac-ters are displayed.Serial Port : Cannot open the serial port.No Response : The hardware does not respond.Timeout : Detected the time-out between received characters in FA-M3.Framing : Detected a framing error in FA-M3.Overrun : Detected an overrun error in FA-M3.Parity : Detected a parity error in FA-M3.Framing, Overrun, and Parity might be generated at the same time.In this case, output the error messages by delimiting with “/” like Framing/Parity.

Action Confirm the serial port connection and the serial port setting of HIS setting. Moreover,confirm the status of LED displayed in each module of FA-M3, and solve the problemaccording to IM of FA-M3.

13th Edition : Dec.26,2005-00

Page 139: CS 1000/3000 Operating Messages

2-121

IM 33S02H10-01E

<2. Message Output Details>

No. 0814Message name FA-M3 communication error recovery

Printing example FA-M3 Communication Recovered

Meaning FA-M3 recovered from the communication error.

No. 0821Message name Printer is unavailable

Printing example Printer prt01 Unavailable

Meaning Printer cannot be used. The prt01 is the printer name.

Action Check if printer server has stopped.

No. 0823Message name Printer is offline

Printing example Printer prt01 Offline

Meaning Printer is in the offline state. The prt01 is the printer name.

Action Check the printer operation panel.

No. 0825Message name Printer out of paper

Printing example Printer prt01 Paper Out

Meaning Printer is out of paper. The prt01 is the printer name.

Action Replenish the printer paper.

No. 0827Message name Printer error

Printing example Printer prt01 Error

Meaning Printer is in an error state. The prt01 is the printer name.

Action Check the printer connection cable, printer power supply, and printer operation panel.

13th Edition : Dec.26,2005-00

Page 140: CS 1000/3000 Operating Messages

2-122

IM 33S02H10-01E

<2. Message Output Details>

No. 0829Message name Printer undefined

Printing example Printer prt01 Not Found

Meaning Printer is not defined. The prt01 is the printer name.

Action Print using a different printer.

No. 0871Message name HIS Batch Manager Recipe Load Error

Printing example Batch AUT Download Error Gr.01 BATCH-ID0001 No.00 Code = 5412

Meaning Tried but failed to load recipe in AUT mode. Not only AUT mode; also occurs in TIMEmode, as a result of message request.

Action Check error code and remove cause of error.

Table Common Detail Error Code (1/2)

Error code Description

5372 Can't operate this command.

5374 Can't acquire data in current status.

5376 No such recipe name.

5377 Different recipe group.

5379 No such unit name.

5382 Error occurred in communications with batch management station.

5386 Can't use that command in current status.

5387 No more space to save changes.

5394 Too many items scheduled. Delete some.

5397 Undefined command.

5401 Can't assign that recipe to that line. Please check master recipe .

5402 Invalid Batch ID entered. please check.

5403 That Batch ID already exist. Please enter a new Batch ID, or delete existing item.

5404 That line name not found. Please check.

5405 That path name not found. Please check.

5406 Recipe set up error.

5407 No space left for down-load to control station. Wait until current batch ends and retry.

5408 Recipe is loading, so that operation is not permitted now.

5409 No recipe or unit recipe exist. Please down-load.

5410 Unit recipe now executing. Wait until all unit recipes end, and then retry.

5411 Unit is in use. Wait until it finishes, then retry.

087101E.EPS

13th Edition : Dec.26,2005-00

Page 141: CS 1000/3000 Operating Messages

2-123

IM 33S02H10-01E

<2. Message Output Details>

Table Common Detail Error Code (2/2)

Error code Description

Error code Description

5412 No unit recipes executing, so can't do that.

5413 Not in recipe group.

5414 No server station. Switch server.

5415 Specified Batch ID does not exist.

5416 Already loaded.

5417 Specified unit is not assigned.

5418 Specified unit recipe No. does not exist.

5419 Unit recipe is now executing, so dynamic assignment is not possible.

5420 Can't execute that command in current status. Check status of current recipe or unit recipe.

5421 Currently assigning, can't accept commands.

5422 Error occurred during file transfer.

5423 Timeout occurred during communication with server ICS.

5424 Recipe load error occurred during FCS batch manager.

5425 FCS recipe loader is busy.

5426 Recipe name inappropriate.

5427 Error occurred in communications with FCS recipe loader.

5428 File access error occurred during loading.

5429 Loader process aborted.

5430 Error while accessing control recipe file.

5431 Error occurred in communications with FCS batch manager.

5432 Assigned process aborted due to abnormality.

5433 Server switching possible only for containing recipe group server.

5514 The common block specified in master recipe is not defined.

5515 Unit name of unit recipe1 is uncertain.

5517 Unit is not defined. Can not find the unit. It is not nonresident unit.

5521 Error occurs when accessing internal database.

5523 The number of assigned unit differs from the number of existing unit.

5601 Can not find the designated common block.

5602 Can not find the designated data item.

5603 The designated array element number of the data item is beyond range.

5604 Common block data, recipe group number or unit recipe number is beyond range.

5605 Data type of common block data is abnormal.

5606 Overflow occurred when converting data.

5614 The common block name designated in master recipe is not defined.

087102E.EPS

13th Edition : Dec.26,2005-00

Page 142: CS 1000/3000 Operating Messages

2-124

IM 33S02H10-01E

<2. Message Output Details>

No. 0873Message name HIS Batch Manager Recipe Common Block Access Error

Printing example Batch AUT Start Error Gr.01 BATCH-ID0001 No.01 Code = 5412

Meaning AUT mode, attempted to change recipe common block data but failed. Not only AUTmode; also occurs in TIME mode, as a result of message request. The error codedetails for this message is the same as the code table attached for message No.0871.

No. 0875Message name HIS Batch Manager Unit Recipe Dynamic Assignment Error

Printing example Batch Dynamic Assign Error Gr.01 BATCH-ID0001 No.01 Code = 5412

Meaning Attempted to perform dynamic unit assignment, in response to request from SEBOL,but failed. The error code details for this message is the same as the code table at-tached for message No.0871.

No. 0877Message name HIS Batch Manager Recipe Uploading Error

Printing example Batch Upload Error Gr.01 BATCH-ID0001 Code = 5412

Meaning Although recipe status is LOG, tried to up-load and failed. The error code details forthis message is the same as the code table attached for message No.0871.

13th Edition : Dec.26,2005-00

Page 143: CS 1000/3000 Operating Messages

2-125

IM 33S02H10-01E

<2. Message Output Details>

No. 0879Message name Error of HIS schedule management interface

Print Example Batch Scheduling Error Gr.01 BATCHID Code=2001-1030

Meaning The error was detected with the HIS schedule management interface.The details of high order four digits error code are listed in the following table.The details of low order four digits error code are listed in the table “Common DetailError Code” for message No.0871.

Action Remove the cause of the error by referring the error code details.

Table Error Code (High Order Four Digits)

Error code Content

0x2001 Error occurred when acquiring recipe group server information.

0x2002 Server status error

0x2003 Recipe assignment starting time error

0x2004 Recipe assignment end time error

0x2005 Unit recipe assignment starting time error

0x2006 Unit recipe assignment end time error

0x2007 Reschedule requested for already started batch

0x2008 Error occurred when deleting control recipe file.

0x2009 Error occurred when acquiring a new Batch ID.

0x200a Error occurred when creating requested parameter file.

0x200b Error occurred when checking the existence of recipe/train names.

0x200c Recipe setup error.

0x200d Error occurred when acquiring unit recipe information.

0x200e Recipe assignment starting time change error

0x200f Recipe assignment starting time, schedule quantity setting error

0x2010 Unit recipe assignment starting time change error

0x2011 Unit recipe assignment starting time, schedule quantity setting error

0x2012 Error occurred when acquiring recipe management information.

0x2013 Error occurred when assigning a dynamic unit.

0x2014 Formula data setting value error.

0x2015 Requested station name not found.

087901E.EPS

0x2016 Defined schedule file convention error

0x2017 Error - Identical Batch ID

13th Edition : Dec.26,2005-00

Page 144: CS 1000/3000 Operating Messages

2-126

IM 33S02H10-01E

<2. Message Output Details>

Table Error Code (Low Order Four Digits) (1/2)

Error code Content

Error code Content

087902E.EPS

0x1001 Defined schedule file deleted.

0x1002 Configuration file identifier error

0x1003 Activity management function open declaration error

0x1004 Error in declaration of opening recipe database.

0x1005 Activity management function close declaration error

0x1006 Error in declaration of closing recipe database.

0x1007 Defined schedule file open error

0x1008 Error occurred when reading defined schedule file.

0x1009 Defined schedule file identifier error

0x100a Control code error

0x100b Working defined schedule file open error

0x100c Separate defined schedule file open error

0x100d Defined schedule file convention error

0x100e Master management station information read error

0x100f Server status error

0x1010 Control recipe delete error

0x1011 Control recipe assign error

0x1012 Reschedule requested for already started batch.

0x1013 Requested parameter file name get error

0x1014 Recipe name get error

0x1015 Common block data read error

0x1016 Dynamic unit assign error

0x1017 Assigned time change error

0x1018 Common block data write error

0x1019 Control recipe information read error

0x101a Time assign error

0x101b Environmental variable name get error

0x101c Requested parameter file open error

0x101d Error occurred when writing to file.

0x101e GMT time conversion error

0x101f Batch progress log file create error

0x1020 Error occurred when searching in the file.

0x1021 Error occurred when acquiring file size.

0x1023 Error occurred when reading the file.

0x1029 Error occurred when searching in the file.

13th Edition : Dec.26,2005-00

Page 145: CS 1000/3000 Operating Messages

2-127

IM 33S02H10-01E

<2. Message Output Details>

Table Error Code (Low Order Four Digits) (2/2)

Error code Content

087903E.EPS

0x1030 Error occurred when acquiring file information.

0x1031 Error occurred when creating directory.

0x1032 Error occurred when changing current directory.

0x1033 No. of set parameters exceeded the maximum allowable limit.

0x1034 Unit name menu list get error

0x1035 Polling error.

0x1036 Error occurred when acquiring common block data.

0x1037 Error in declaration of opening common database.

0x1038 Error occurred when acquiring station information.

0x1039 Error in declaration of closing common database.

0x103a Server status undefined.

0x103b Server status fall

0x103c Server status being backed up.

0x103d Requested station name not found.

0x103c Server status being backed up.

0x103d Requested station name not found.

0x103e Recipe number get error

0x103f Configuration file convention error

0x102a Error occurred when creating Error file.

0x102b Environment parameters setting error.

0x102c Error occurred when opening Error file.

0x102d Error occurred when converting data.

0x102e Error occurred when acquiring unit recipe information.

0x102f Error occurred when creating scheduler management file.

No. 0885Message Name Violation of Process Management License

Printing example Batch Out of License Gr.01 BATCHID

Meaning The Process Management has been used beyond the scope of the keycode ID.

Action Read the license and remove the cause of the trouble.

No. 0886Message Name Process Management Configuration Error

Printing example Batch Configuration Error

Meaning The Process Management Configuration File does not exist. Therefore, the ProcessManagement Function does not run.

Action Download the file in the Process Management Configuration Builder.The computer needs to be restarted (shut down, or the power OFF/ON) after thedownload.

13th Edition : Dec.26,2005-00

Page 146: CS 1000/3000 Operating Messages

2-128

IM 33S02H10-01E

<2. Message Output Details>

No. 0889Message name HIS Batch Management Recipe Set Up Error

Printing example Batch SEBOL Recipe Set Up Error Gr.01 RECIPE Code=0001

Meaning Attempted but failed to set up recipe from SEBOL.

Action Check error codes and eliminate the cause of the error.

SEE ALSO

For more information about the details of the error code, see the table of Common Detail Error Code forthe message No.0871.

No. 0891Message name Package error

Printing example PackageName Error_Information

Meaning A package error occurred.The name of a package in which an error occurred is displayed in place of“PackageName” in the printing example.Refer to the User’s Manual of the package.

• Consolidated Historical Message Viewer Package

Message name 1 Fails to save the historical message to the server

Printing example 1 HIS0124 Historical file upload Error

Meaning 1 Error occurred when putting the message to historical message server.HIS0124: Station name

• Access Administrator Package

Message name 2 Illegal access detected

Printing example 2 HIS0124 Illegal Access detected User=xxxxxxxx

Meaning 2 The number of logon attempts denied by authentication reaches limit. Illegal accessmay have occurred.HIS0124: Station name or computer name at which the authentication fails.xxxxxxxx: User name of the last logon attempt that denied by authentication.

• Access Administrator Package

Message name 3 Illegal access detected

Printing example 3 HIS0124 Illegal Access detected User=xxxxxxxx (ENG)HIS0124 Illegal Access detected User=xxxxxxxx (RCP)HIS0124 Illegal Access detected User=xxxxxxxx (RPT)

Meaning 3 The number of logon attempts denied by authentication reaches limit of system builder(ENG), recipe builder (RCP) and report package (RPT). Illegal access may have oc-curred.HIS0124: Station name or computer name at which the authentication fails.xxxxxxxx: Engineer name (user name) of the last logon attempt that denied by

authentication.

15th Edition : Dec.10,2007-00

Page 147: CS 1000/3000 Operating Messages

2-129

IM 33S02H10-01E

<2. Message Output Details>

• Access Administrator Package

Message name 4 Insufficient disk space for Report and Audit Trail database.

Printing example 4 HIS0124 Insufficient DISK space for Audit Trail Database

Meaning 4 HIS0124 does not have sufficient disk space for Audit Trail database.HIS0124: Computer name

• Access Administrator Package

Message name 5 Fails to save the modified data to Report and Audit Trail database.

Printing example 5 HIS0124 Report file upload error, xxxxxxxx

Meaning 5 HIS0124 fails to update the changed data to Report and Audit Trail databases.HIS0124: Computer namexxxxxxxx: Report name

No. 0892Message name Package error recovery

Printing example PackageName Recover_Information

Meaning A package error has been recovered.The name of a package that recovered from an error is displayed in place of“PackageName” in the printing example.Refer to the Instruction Manual of the package.

13th Edition : Dec.26,2005-00

Page 148: CS 1000/3000 Operating Messages

2-130

IM 33S02H10-01E

<2. Message Output Details>

2.9 Process Messages (Message Nos. 1101 to 1903)This section describes the messages that notify the operator of the process statusand operation record.

No. 1101Message name Input process alarm generation

Printing example A0101A comment PV=0.0 KNM3/H LOA0101A: Tag namecomment: Tag comment0.0: PV valueKNM3/H: Engineering units symbolLO: Alarm status

Meaning A process alarm was generated by the function block indicated by the printing con-tents.(NR, IOP, IOP-, HH, LL, HI, LO, DV+, DV-, VEL+, VEL-, MHI, MLO, CNF, others)

SEE ALSO

For a description of alarm processing during AOF, see the following:

C5.14, “Alarm Inhibition (Alarm OFF)” in the Reference (IM 33S01B30-01E)

Cause • Process side error, or card misoperation.For IOP, there may be an open wire or I/O card error.For card misoperation, replace the card.

• Limit value change or CAL specificationAction is unnecessary.

Note When input process alarm generation/recovery occur in a very short time, only thegeneration or recovery message may be printed.

No. 1102Message name Input process alarm recovery

Printing example A0101A comment PV=4.8 KNM3/H LO RecoverA0101A: Tag namecomment: Tag comment4.8: PV valueKNM3/H: Engineering units symbolLO: Alarm status

Meaning Recovery from function block alarm state indicated by the printing contents.(NR, IOP, IOP-, HH, LL, HI, LO, DV+, DV-, VEL+, VEL-, MHI, MLO, CNF, others)

Note When input process alarm generation/recovery occur in a very short time, only thegeneration or recovery message may be printed.

13th Edition : Dec.26,2005-00

Page 149: CS 1000/3000 Operating Messages

2-131

IM 33S02H10-01E

<2. Message Output Details>

No. 1103Message name Output process alarm generation

Printing example A0101A comment MV=0.0 % OOPA0101A: Tag namecomment: Tag comment0.0: PV value%: Engineering units symbolOOP: Alarm status

Meaning The function block indicated by the printing contents generated a process alarm (MHI,MLO, or OOP). This message is not printed while the relevant function block is AOF.

Cause • MHI, MLO messageOutput limit was applied by output upper/lower limit value.

• OOP messageThere is an open in the output card. (for MAC2)If the card is faulty, replace the card.

Note When generation/recovery occur in a very short time, only the generation or recov-ery message may be printed.

No. 1104Message name Output process alarm recovery

Printing example A0101A comment MV=1.4 % MLO RecoverA0101A: Tag namecomment: Tag comment1.4: MV value%: Engineering units symbolMLO: Alarm status

Meaning Function block indicated by the printed contents recovered from the alarm state. (MHI,MLO, or OOP)

Note When generation/recovery occur in a very short time, only the generation or recov-ery message may be printed.

No. 1106Message name Process alarm normal recovery

Printing example FIC100A comment NR

Meaning All the alarms of the displayed tag name (FIC100A in the example) recovered to nor-mal. This message also displays the tag comment.

No. 1107Message name Process alarm continuation

Printing example FIC100A comment PV = 12.34 KNM3/H LO Still

Meaning Recovery operation was not performed and the alarm status of the displayed tag name(FIC100A in the example) was ignored for a specified time, or longer. (The functionblock definition builder specifies the time.)

Action Perform the recovery operation.

13th Edition : Dec.26,2005-00

Page 150: CS 1000/3000 Operating Messages

2-132

IM 33S02H10-01E

<2. Message Output Details>

No. 1111Message name Unit alarm generation, task alarm generation

Printing example VESSEL1 reactor2 OOPVESSEL1: Unit namereactor2: Unit comment (task comment)OOP: Alarm status

Meaning The SEBOL block of the relevant unit (for subsystem support language: task) ex-ecuted a prcsalarm statement.The alarm status is the character string specified in the prcsalarm statement.

No. 1112Message name Unit alarm recovery, task alarm recovery

Printing example VESSEL1 reactor2 Normal form OOPVESSEL1: Unit namereactor2: Unit comment (task comment)OOP: Alarm status

Meaning SEBOL program of relevant unit (task for subsystem support language) executed aprcsalarm recover statement.The alarm status is the character string specified in the prcsalarm statement that gen-erated the unit alarm (task alarm).

No. 1201Message name Annunciator generation message

Printing example %AN xxxxsyyyyyy A-23 error ALM

Meaning The control station annunciator switch was turned on.

Note When annunciator generation/recovery occurs generated in a very short time, onlythe generation or recovery message may be printed.

No. 1206Message name Annunciator recovery message

Printing example %AN xxxxsyyyyyy A-23 error NR

Meaning The control station annunciator switch was turned off.

No. 1207Message name Annunciator generation continuation

Printing example A-23 error ALM Still

Meaning The control station annunciator switch was left on for a specified time, or longer.

13th Edition : Dec.26,2005-00

Page 151: CS 1000/3000 Operating Messages

2-133

IM 33S02H10-01E

<2. Message Output Details>

14th Edition : Dec.26,2006-00

No. 1221Message name Annunciator with Data Turned On

Printing example Storage tank1 inlet flow 202.1KL/H error ALM

Meaning The switch on the control station for Annunciator with Data went on.

Note If the Annunciator goes on and off too quickly, there are cases where only the ‘turnedon’ or ‘turned off (recovered)’ message is shown on the window, not both. The char-acter string in the historical message contains “ALM”, but the character string dis-played in the Process Alarm window does not contain “ALM.”

No. 1226Message name Annunciator with Data Turned Off (Recovered)

Printing example Storage tank1 inlet flow 180.0KL/H error NR

Meaning The switch on the control station for Annunciator with Data went off.

Note The character string in the historical message contains “NR”, but the character stringdisplayed in the Process Alarm window does not contain “NR.”

No. 1227Message name Annunciator with Data Kept On

Printing example Storage tank1 inlet flow 202.1KL/H error ALM Still

Meaning The switch on the control station for Annunciator with Data keeps on for a certainperiod of time.

Note The character string in the historical message contains “Still”, but the character stringdisplayed in the Process Alarm window does not contain “Still.”

Page 152: CS 1000/3000 Operating Messages

2-134

IM 33S02H10-01E

<2. Message Output Details>

No. 1303Message name Sequence message

Printing example Storage tank1 inlet flow A 202.1KL/H B 235.7KL/H C 137.1KL/H

Meaning A control station sequence message is generated by the sequence table, etc.

Explanation The system generation functions defines the sequence messages.

No. 1305Message name History message

Printing example A pause command was received. (Arbitrary message)

Meaning An arbitrary character string is stored in the history file.

Remark This message is not printed.

No. 1401Message name Block mode (loop status)

Printing example A0101A comment MANA0101A: Tag namecomment: Tag commentMAN: Block mode

Meaning This is an operation record of block mode (loop status) changes by HIS operation orsequence control.

No. 1403Message name Alarm off

Printing example A0101A comment Alarm OFFA0101A: Tag namecomment: Tag comment

Meaning The alarm reporting function (Nos. 1101, 1102, 1103, 1104) of the relevant functionblock entered the alarm suppression state.

SEE ALSO

For a description of alarm processing during AOF, see the following:

C5.14, “Alarm Inhibition (Alarm OFF)” in the Reference (IM 33S01B30-01E)

Cause AOF was specified by tuning window, or sequence table execution.

14th Edition : Dec.26,2006-00

Page 153: CS 1000/3000 Operating Messages

2-135

IM 33S02H10-01E

<2. Message Output Details>

No. 1404Message name Alarm on

Printing example A0101A comment Alarm ON

Meaning The alarm reporting function (No. 1101, 1102, 1103, 1104) of the relevant functionblock was turned on.

Cause Alarm on (AON) was specified by tuning window, or sequence table execution.

No. 1405Message name Block status change information

Printing example FIC001-1 tank level-A ENDFIC001-1: Tag nametank level-A: Tag commentEND: Block status

Meaning The block status changed.

No. 1407Message name Data item value change information

Printing example FIC001-1 tank level-A UAID=20FIC001-1: Tag nametank level-A: Tag commentUAID: Data item20: Change value

Meaning The value of a data item (UAID) of the relevant function block changed.

Cause The operator, SEBOL, etc. changed the display item. Only data item UAID is reported.

Remark This message is not printed.

No. 1421Message name Recipe Execution Start

Printing example Gr.01 BATCH-001 ER102 StartGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe name

Meaning Execution of the related recipe was started.

Cause Execution of the recipe was started by a command from the HIS or by specificationof the batch mode.

14th Edition : Dec.26,2006-00

Page 154: CS 1000/3000 Operating Messages

2-136

IM 33S02H10-01E

<2. Message Output Details>

No. 1422Message name Recipe Execution End

Printing example Gr.01 BATCH-001 ER102 EndGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe name

Meaning Execution of the related recipe has ended.

Cause Execution of all unit recipes which are used for the related recipe has ended normally.

No. 1423Message name Recipe Abortion

Printing example Gr.01 BATCH-001 ER102 Abort code=0000-0000Gr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe name0000-0000: Code 1, Code 2

Meaning Execution of the related recipe was aborted.

Cause Execution of the related recipe was forcibly aborted.

No. 1424Message name Recipe Status Change Notification

Printing example Gr.01 BATCH-001 ER102 COMPLETE old=LOGGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameCOMPLETE: Recipe statusLOG: Recipe status before change

Meaning The recipe status of the related recipe was changed.

Cause The recipe status was changed by an operation command from the ICS. The follow-ing recipe statuses are providedRESERVED: reservation has already been madeREADY: downloading is already doneACTIVE: execution is in progressLOG: data have been acquiredCOMPLETE: execution is completedABORTED: execution is aborted

Remark This message is not printed out.

14th Edition : Dec.26,2006-00

Page 155: CS 1000/3000 Operating Messages

2-137

IM 33S02H10-01E

<2. Message Output Details>

No. 1425Message name Server Station Change Notification

Printing example Gr.01 Server Control ON FCS0101Gr.01: Recipe group numberON: ON/OFFFCS0101: Station name

Meaning The server station of the related recipe group was changed.

Cause The server HIS was changed on the server change panel. This message is not printedout.

Remark This message is not printed out.

No. 1426Message name Reservation Processing Completion Notification

Printing example Gr.01 BATCH-001 ER102 RESERVEDGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe name

Meaning The related recipe was set up.

Cause An execution recipe was created by the recipe setup command from the HIS.

Remark This message is not printed out.

No. 1428Message name Recipe Setup Request

Printing example Gr.01 BATCH-001 ER102 Recipe Setup TRAIN-AGr.01: New recipe group numberBATCH-001: New batch IDER102: New recipe nameTRAIN-A: New train name

Meaning SEBOL has made a recipe setup request for the relevant basic recipe.

Note If the Batch ID or Train name is not specified in SEBOL, the strings of “Gr.01,” “BATCH-001,” “ER102” and “TRAIN-A” will be shown with space characters.

Remark This message is not printed out. The message is output from the relevant HIS.

No. 1431Message name Unit Recipe Execution Start

Printing example Gr.01 BATCH-001 ER102 No.01 StartGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameNo.01: Unit recipe number

Meaning Execution of the related recipe was started.

Cause Execution of the recipe was started by a command from the HIS or by specificationof the batch mode.

Remark This message is not printed out.

15th Edition : Dec.10,2007-00

Page 156: CS 1000/3000 Operating Messages

2-138

IM 33S02H10-01E

<2. Message Output Details>

No. 1432Message name Unit Recipe Execution End

Printing example Gr.01 BATCH-001 ER102 No.01 EndGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameNo.01: Unit recipe number

Meaning Execution of the related recipe ended.

Cause Execution of the related recipe ended normally.

Remark This message is not printed out.

No. 1433Message name Unit Recipe Abortion

Printing example Gr.01 BATCH-001 ER102 No.01 Abort code=0000-0000Gr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameNo.01: Unit recipe number0000-0000: Code 1, Code 2

Meaning Execution of the related recipe was aborted.

Cause Execution of the related recipe was aborted.

Remark This message is not printed out.

No. 1434Message name Unit Recipe Status Change Notification

Printing example Gr.01 BATCH-001 ER102 No.01 COMPLETE old=LOGGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameNo.01: Unit recipe numberCOMPLETE: Unit recipe statusLOG: Unit recipe status before change

Meaning The unit recipe status of the related recipe was changed.

Cause The unit recipe status was changed by an operation command from the HIS. The fol-lowing unit recipe statuses are providedASSIGNED: unit recipe assignment is already madeNOASSIGN: unit recipe assignment is not yet madeREADY: downloading is already doneACTIVE: execution is in progressLOG: data have been acquiredCOMPLETE: execution is completedABORTED: execution is aborted

Remark This message is not printed out.

15th Edition : Dec.10,2007-00

Page 157: CS 1000/3000 Operating Messages

2-139

IM 33S02H10-01E

<2. Message Output Details>

No. 1435Message name Unit Recipe Download Request

Printing example Gr.01 BATCH-001 ER102 No.01 Down LoadGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameNo.01: Unit recipe number

Meaning Download of the related unit recipe was requested from SEBOL.

Remark This message is not printed out.

No. 1436Message name Dynamic Unit Recipe Assignment Request

Printing example Gr.01 BATCH-001 ER102 No.01 Unit Assign UNIT001Gr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameNo.01: Unit recipe numberUNIT001: Number of assigned unit recipe

Meaning Dynamic assignment of the related unit recipe was made from SEBOL.

Remark This message is not printed out.

No. 1501Message name Request for playing multimedia

Printing example FCS0101 %VM0001 comment

Meaning A request for playing multimedia is sent from the field control station (StationName=FCS0101).

Remark This message is not output to printer.

No. 1502Message name Request for playing multimedia denied (Unauthorized Station)

Printing example FCS0101 %VM0001 out of Limits

Meaning The request for playing multimedia sent from the field control station (StationName=FCS0101) is denied since the field control station is not authorized for therequest.

Remark This message is not output to printer.

14th Edition : Dec.26,2006-00

Page 158: CS 1000/3000 Operating Messages

2-140

IM 33S02H10-01E

<2. Message Output Details>

No. 1503Message name Request for playing multimedia denied (Multimedia File Undefined)

Printing example FCS0101 %VM0001 not Defined

Meaning The request for playing multimedia sent from the field control station (StationName=FCS0101) is denied since no multimedia file is defined to the request.

Remark This message is not output to printer.

No. 1601Message name Entry operation record

Printing example0500-006 Comment SV=41.7 CM Old=50.0

0500-017 Comment MV=77.0 % Old=60.0

Engineering units symbolNew dataTag commentTag name

.TM0001 (05-00) PH= Old=21

.SN0111 (05-00) PV= Old=0

New dataStation No.Tag name

.TM0001 (05-00) CONT Old=PAUSE

201

(05-00).TM0001 (05-00) START Old=STOP(05-00)

.TM0001 (05-00) STOP Old=START(05-00)

.TM0001 (05-00) PAUSE Old=CONT(05-00)

Station No.STARTSTOPPAUSECONTTimer/counter No.

.TM : Timer

.CT : Counter

Timer only

160100E.EPS

Meaning Entry operation on HIS. Old= is the data before the entry operation.

No. 1602Message name Tag alarm acknowledgment

Printing example FIC001-1 distillation column1 inlet flow AckedFIC001-1: Tag namedistillation column1 inlet flow: Tag comment

Meaning Alarm acknowledgment operation was performed.

14th Edition : Dec.26,2006-00

Page 159: CS 1000/3000 Operating Messages

2-141

IM 33S02H10-01E

<2. Message Output Details>

No. 1603Message name Block mode change

Printing example FIC001-1 distillation column1 inlet flow MAN Old=AUT ONUSER@HIS0124FIC001-1: Tag namedistillation column1 inlet flow: Tag commentMAN: New block mode

Meaning Block mode was changed from a HIS. Old= is the status before the change.

No. 1604Message name Function block operation

Printing example TM0001S0101 block1 timer STOP ONUSER@HIS0124TM0001S0101: Tag nameblock1 timer: Tag commentSTOP: Operation contents

Meaning A function block operation was performed from a HIS.

Cause This message is output when an operation provided on the tuning window tool bar wasperformed.

No. 1605Message name Alarm off

Printing example TIC101 reactorA top temperature Alarm OFF ONUSER@HIS0124TIC101: Tag namereactorA top temperature: Tag comment

Meaning Alarm was turned off from a HIS.

No. 1606Message name Alarm on

Printing example TIC101 reactorA top temperature Alarm ON ONUSER@HIS0124TIC101: Tag namereactorA top temperature :Tag comment

Meaning Alarm was turned on (alarm off reset) from a HIS.

No. 1608Message name Switch Button Operation Record

Printing example0500-017 Comment MV=ON Old=OFF ONUSER@HIS0124

New Switch button operation

Tag comment

Tag name160800E.EPS

Meaning Switch button operation on HIS. Old= shows the data indicating the previous opera-tion.

14th Edition : Dec.26,2006-00

Page 160: CS 1000/3000 Operating Messages

2-142

IM 33S02H10-01E

<2. Message Output Details>

No.1612Message name Operation Guide Message Acknowledgment

Printing example FCS0101 %OG0001 (2001/11/29 10:34:19) ACK (a message) ONUSER@HIS0124

Meaning The system alarm message is acknowledged on the HIS.FCS0101: The station that initiated the acknowledged message.%OG0001: The Operation Guide Message number.2001/11/29 10:34:19: Date and time at which the acknowledged message

occurred.A message: The acknowledged message text.

No. 1613Message name Function block operation

Printing example VESSEL3 reactor2 Dialogue catalyst input=10 ONUSER@HIS0124VESSEL3: Unit name (tag name)reactor2: Unit comment (task comment)catalyst input: Dialogue name10: Entry data

Meaning Data entry type message, or acknowledgment type message input/acknowledgmentwas performed from a HIS.

No. 1617Message name Common Block Data Entry

Printing example Gr.01 BATCH-001 ER102 COMMON.ITEM [1, 1] =10 old=0Gr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameCOMMON.ITEM [1, 1] =10: Entered data

COMMON.ITEM: Common block name, data item name.[1, 1]: 1st- and 2nd-order elements.

old=0: Data before entry

Meaning Common block data of the related recipe were entered from the HIS.

No. 1619Message name Recipe Status Operation

Printing example Gr.01 BATCH-001 ER102 STARTGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameSTART: Instruction

Meaning Recipe status operation of the related recipe was done.

14th Edition : Dec.26,2006-00

Page 161: CS 1000/3000 Operating Messages

2-143

IM 33S02H10-01E

<2. Message Output Details>

No. 1621Message name Unit Recipe Status Operation

Printing example Gr.01 BATCH-001 ER102 No.01 STARTGr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameNo.01: Unit recipe numberSTART: Instruction

Meaning Unit recipe status operation of the related recipe was done.

No. 1623Message name Dynamic Unit Recipe Assignment

Printing example Gr.01 BATCH-001 ER102 No.01 Unit Assign UNIT001Gr.01: Recipe group numberBATCH-001: Batch IDER102: Recipe nameNo.01: Unit recipe numberUNIT001: Number of the assigned unit recipe

Meaning Dynamic unit recipe assignment of the related recipe was done.

No. 1633Message name Server Station Change

Printing example Gr.01 HIS0124 ServerGr.01: Recipe group numberHIS0124: Server station name

Meaning The server station was changed in the related recipe group.

No. 1641Message name Operation mark assignment

Printing example FIC001-1 tank level-A Ope-Mark=04 operation level3 ONUSER@HIS0124FIC001-1: Tag nametank level-A: Tag comment04: Operation mark No.

Meaning Operation mark was assigned, or changed, at the relevant function block.

No. 1642Message name Operation mark reset

Printing example FIC001-1 tank level-A Ope-Mark Reset ONUSER@HIS0124FIC001-1: Tag nametank level-A: Tag comment

Meaning Assignment of operation mark assigned to the relevant function block was reset.

14th Edition : Dec.26,2006-00

Page 162: CS 1000/3000 Operating Messages

2-144

IM 33S02H10-01E

<2. Message Output Details>

No. 1643Message name Graphic window data group entry operation

Printing example Group Data Set (8 data) ONUSER@HIS0124

Meaning Indicates that graphic window data group entry operation was performed. Outputs thenumber of data in parentheses. The entry contents of each are output immediatelybefore this message.

No. 1672Message name Operator Control recipe memo

Printing example Gr.01 BATCH001 It was paused because of unusual event.

Meaning This is the operator’s memo at control recipe.Operator can make a note at memo dialog called at recipe windows.

No. 1681Message name Package operation

Printing example PackageName Operation_Information

Meaning Operations are performed by the package.In the printing example, the Package_Name stands for the package that runs theoperations.For more information see the User’s Manual of the package.An example of the message from a main package is shown as follows.

• Consolidated Historical Message Viewer

Message name 1 Upload all archived historical message files

Printing example 1 All historical file upload ENGUSER@HIS0124

Meaning 1 Upload of all archived historical message files completes.

• Consolidated Historical Message Viewer

Message name 2 Configure historical server

Printing example 2 Setup historical server definition ENGUSER@HIS0124

Meaning 2 Configuration of historical server completes

• Consolidated Historical Message Viewer

Message name 3 Remove configuration of historical server

Printing example 3 Release historical server definition ENGUSER@HIS0124

Meaning 3 Removal of historical server configuration completes.

15th Edition : Dec.10,2007-00

Page 163: CS 1000/3000 Operating Messages

2-145

IM 33S02H10-01E

<2. Message Output Details>

No.1691Message name Save Trend Data

Printing example Trend Save TG0101 Block:01 Group:01 ONUSER@HIS0124

Meaning The data of designated trend group are saved.TG0101: Window nameBlock: Trend block numberGroup: Trend group number

No. 1693Message name Trend recording start operation

Printing example Trend Start ONUSER@HIS0124

Meaning Trend recording of the specified group was started.

No. 1694Message name Trend recording stop operation

Printing example Trend Stop ONUSER@HIS0124

Meaning Trend recording of the specified group was stopped.

No. 1695Message name Trend recording continuation operation

Printing example Trend Continue ONUSER@HIS0124

Meaning Trend recording of the specified group was continued.

No. 1701Message name Operation guide message

Printing example Input catalyst. (Arbitrary message)

Meaning An operation guide message was output from a SEBOL opeguide statement, or a se-quence table.

Explanation When an operation guide message is output from a sequence table, or message No.specification opeguide statement, the message character string created by the sys-tem generation function is used. For an arbitrary character string specificationopeguide statement, the specified character string becomes the message characterstring.

No. 1711Message name Dialogue message

Printing example Charging process. Input the charge again. (Arbitrary message)

Meaning SEBOL dialogue statement output a dialogue message.

15th Edition : Dec.10,2007-00

Page 164: CS 1000/3000 Operating Messages

2-146

IM 33S02H10-01E

<2. Message Output Details>

No. 1712Message name Reinput type dialog message

Printing example Charging process. Reinput. (Arbitrary message)

Meaning SEBOL dialogue statement output a reinput type dialogue message.

No. 1713Message name Dialogue cancel

Printing example Charging process. Cancel

Meaning Dialogue was canceled because the SFC/SEBOL block that executed the dialoguestatement ended before operator input.

No. 1714Message name Dialogue time-out cancel

Printing example Charging process. Time Out Cancel

Meaning Since the operator did not perform the input operation within the number of secondsspecified by the time parameter in the SEBOL dialogue statement, the dialogue wascanceled.

No. 1801Message name Sequence message request

Printing example FCS0101 %RQ0001 message request contents

Meaning A sequence message request sent from the field control station (StationName=FCS0101) received.

Remark This message is not output to printer.

No. 1802Message name Sequence message request denied (Unauthorized Station)

Printing example FCS0101 %RQ0001 out of Limits

Meaning The sequence message request sent from the field control station (StationName=FCS0101) is denied since the field control station is not authorized for therequest.

Remark This message is not output to printer.

No. 1803Message name Sequence message request denied (Undefined)

Printing example FCS0101 %RQ0001 not Defined

Meaning The sequence message request sent from the field control station (StationName=FCS0101) is denied since no function is defined to the request.

Remark This message is not output to printer.

14th Edition : Dec.26,2006-00

Page 165: CS 1000/3000 Operating Messages

2-147

IM 33S02H10-01E

<2. Message Output Details>

No. 1902Message name Supervisory computer event message (for operation and monitoring function

program, device address 3) received

Printing example FCS0101 %M3nnnn

Meaning Supervisory computer event message (message No.=nnnn and device address 3) forPICOT was received from control station (station name=FCS0101).

No. 1903Message name Supervisory computer event message (for computer program, device address 6)

received

Printing example FCS0101 %CPnnnn

Meaning Supervisory computer event message (message No.=nnnn and device address 6)was received from control station (station name=FCS0101)

14th Edition : Dec.26,2006-00

Page 166: CS 1000/3000 Operating Messages

2-148

IM 33S02H10-01E

<2. Message Output Details>

2.10 Fieldbus Messages(Message Nos. 3001 to 3282)This section explains the process messages related to fieldbus device. Thesemessages are displayed on the Historical Report window of the HIS. They informyou of failures in fieldbus devices detected by the ACF11 fieldbus communicationmodule and failures self-diagnosed by the ACF11 module, as well as alarm eventsoccurring in fieldbus devices.

IMPORTANT

The “detail” field in the printout examples of messages 3101, 3102, 3111, 3112, 3150 and3160, contains detailed information on field-device alerts. The HIS represents the “detail”field as a hexadecimal number. If you use the SSS6700 Device Management Tool forFieldbus—a PC-based tool, you can show the information in the field as a string of charac-ters.

No. 3001Message name Fieldbus Device Failure

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 Device Error Device=FIC001

Meaning An error was detected in the fieldbus device (tag name = FIC001) connected to thefieldbus of the I/O module installed in slot 1 of unit 1 of node 1 in RIO bus system 1of the field control station (name = FCS0101); or the HIS cannot communicate withthat fieldbus device.

Action Check if the fieldbus device is properly connected to the fieldbus, and make sure thatthe device is firmly connected to the fieldbus.Check if the fieldbus is terminated on both ends, and make sure that the terminatorsare connected to both ends of the fieldbus.Check if the filedbus device is provided with power, and make sure that the powersupply is working properly for the device.

No. 3002Message name Recovery of Fieldbus Device to Normal

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 Device Recover Device=FIC001

Meaning The indicated fieldbus device has recovered to normal.

14th Edition : Dec.26,2006-00

Page 167: CS 1000/3000 Operating Messages

2-149

IM 33S02H10-01E

<2. Message Output Details>

No. 3011Message name ACF11 Self-Diagnosed Failure

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 ACF Error Detected Type=00Code=xxxx

Meaning A self-diagnosed error was detected in the I/O module installed in slot 1 of unit 1 ofnode 1 in RIO bus system 1 of the field control station (name = FCS0101).

Table Error Code

Code Interpretation

0201 Invalid database of DCS definitions (not yet loaded or EEPROM failure)

0202 Invalid communication parameter for fieldbus definition (not yet loaded or EEPROM failure)

0203 Invalid VCR for fieldbus definition (not yet loaded or EEPROM failure)

0204 Invalid SMIB for fieldbus definition (not yet loaded or EEPROM failure)

0205 Invalid LAS for fieldbus definition (not yet loaded or EEPROM failure)

0211 Advance notice of critical limit of writing to EEPROM (warning)

0212 Excessive writing to EEPROM (alarm)

0213 Failure to write to EEPROM (alarm)301100E.EPS

Action Run IOM download.If the problem persists, replace the ACF11 module then run IOM download again.

14th Edition : Dec.26,2006-00

Page 168: CS 1000/3000 Operating Messages

2-150

IM 33S02H10-01E

<2. Message Output Details>

No. 3021Message name ACF11 Configuration Failure

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 Configuration Error Type=00Code=xxxx

Meaning An inconsistency was detected in the database of the I/O module installed in slot 1 ofunit 1 of node 1 in RIO bus system 1 of the field control station (name = FCS0101).

Action Generation on engineering tool is required. This problem maybe caused by lacking ofthis procedure. Run generation on engineering tool then run IOM download.If the problem persists, report this message to vendor's technical service group.

Table Error Code (1/2)

CodeInterpretation

SubcategoryMain Category

0101

0102

0103

0104

0105

0106

0110

0111

0112

0113

0114

0115

0116

0117

0118

0119

011A

011B

011C

011D

011E

011F

0120

0121

0122

0123

0124

0125

0126

0127

Node address of LAS

VCR number

VCR type and type_and_role

Line buffer attribute and type_and_role

Device address

VCR type and FMS service support

Invalid DCS type (out of range)

Invalid number of devices

Invalid number of blocks

Invalid number of VCRs

Invalid number of line buffers

Invalid total sum of blocks

Invalid logical block number

Invalid number of blocks in device configuration definitions

Invalid line buffer attribute and VCR type

Invalid VCR numbers in line buffers and VCR configuration definitions

Invalid data type based sub-index (MODE/ALRM)

Invalid line buffer attribute

Invalid node address (out-of-range)

Duplicate definition of node address

Duplicate definition of block number

Invalid index in block configuration definitions (out-of-range)

Duplicate definition of VCR number

Invalid index in line buffers (out-of-range)

Invalid sub-index in line buffers (out-of-range)

Invalid index attribute in line buffers (out-of-range)

Invalid data type in line buffers (out-of-range)

Invalid VCR number in line buffers (out-of-range)

Invalid device number

Inconsistent line buffer attribute

Disagreement in database

DCS definitions

302101E.EPS

14th Edition : Dec.26,2006-00

Page 169: CS 1000/3000 Operating Messages

2-151

IM 33S02H10-01E

<2. Message Output Details>

Table Error Code (2/2)

CodeInterpretation

SubcategoryMain Category

0130

0131

0132

0133

0134

0135

0136

0137

0138

0139

013A

013B

013C

013D

013E

013F

0140

0141

0142

0143

0144

0145

0146

0147

0148

0149

014A

014B

014C

014D

Invalid type_and_role (out-of-range)

Invalid local_time_diff

Invalid ap_clock_sync_interval

Invalid primary_time_publisher

Invalid macrocycle_duration

Invalid t1

Invalid t2

Invalid t3

Invalid fas_dll_priority

Invalid fas_dll_local_addr

Invalid fas_dll_configured_remote_addr

Invalid fas_dll_max_cnf_delay_for_conn

Invalid fas_dll_max_cnf_delay_for_data

Invalid fas_dll_size

Invalid fas_dll_authentification

Invalid fas_dll_delivery

Invalid scheduling

Invalid fms_vfd_id

Invalid max_scc

Invalid max_rcc

Invalid resid_acr_supp

Invalid SUB number

Invalid N_SUB in LAS definition

Invalid SUB_SCHEDULE size in LAS definition

Invalid SEQ number

Invalid N_SEQ in LAS definition

Invalid SCHED_SEQUENCE size in LAS definition

Invalid DLCEP number

Invalid DLCEP in LAS definition

Disagreement between piro and fas_dll_priority in LAS definition

014E Invalid macrocycle_time in LAS definition

014F Detection of duplicate VCR definition

0181 Invalid logical device number

0182 Invalid device configuration definition

0183 Invalid VCR number

0184 Invalid VCR configuration definition number

0185 Invalid line buffer number

01C1 The data type in the device does not match the one in the line buffer definition in the DCS definitions.

01C2 index in the device does not match the one in the line buffer definition in the DCS definitions.

01C3 subindex in the device does not match the one in the line buffer definition in the DCS definitions.

Fieldbus definition

DCS definition

302102E.EPS

14th Edition : Dec.26,2006-00

Page 170: CS 1000/3000 Operating Messages

2-152

IM 33S02H10-01E

<2. Message Output Details>

No. 3050Message name Occurrence of an Update Event in ACF11

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 ACF Updata Event Type=00 Rev=0000

Meaning A change was made to the fieldbus definitions of the I/O module installed in slot 1 ofunit 1 of node 1 in RIO bus system 1 of the field control station (name = FCS0101).

No. 3101Message name Occurrence of a Fieldbus Device Alarm

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 Device Alarm Type=08 Code=0007Device=FIC100 Block=FIC100 Detail=

Meaning An alarm (input failure) was received from the fieldbus device (tag name = FIC100)connected to the I/O module installed in slot 1 of unit 1 of node 1 in RIO bus system1 of the field control station (name = FCS0101).The details of error codes are as follows.0000: Other0001: Block Configuration Error0002: Link Configuration Error0003: Simulate Active0004: Local Override0005: Device Fault State Set0006: Device Needs Maintenance Soon0007: Input Failure / process variable has BAD status0008: Output Failure0009: Memory Failure000A: Lost Static Data000B: Lost NV Data000C: Read-back Check Failed000D: Device Needs Maintenance Now000E: Power-up000F: Out-of-Service

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

No. 3102Message name Recovery of Fieldbus Devices to Normal

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 Device Recover Device=FIC100Block=FIC100 Detail=

Meaning A recovery-to-normal alarm was received from the indicated fieldbus device.

15th Edition : Dec.10,2007-00

Page 171: CS 1000/3000 Operating Messages

2-153

IM 33S02H10-01E

<2. Message Output Details>

No. 3111Message name Occurrence of process Alarm from Fieldbus Devices

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 Process Alarm Occur Type=02Device=FIC100 Block=FI-100 Detail=

Meaning An alarm (HI alarm) for a process failure in the fieldbus block (tag name = FI-100) wasreceived from the fieldbus device (tag name = FIC100) connected to the I/O moduleinstalled in slot 1 of unit 1 of node 1 in RIO bus system 1 of the field control station(name = FCS0101).

Table Interpretation of Types

Type Interpretation

01 LO : Low limit

02 HI : High limit

03 LO LO : Critical low limit

04 HI HI : Critical high limit

05 DV LO : Deviation low

06 DV HI : Deviation high

07 DISC : Discrete311100E.EPS

No. 3112Message name Recovery of Fieldbus Devices from Process Alarm

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 Process Alarm Clear Device=FIC100Block=FI-100 Detail=

Meaning An event informing that the indicated fieldbus block has recovered from an alarm state,was received from the indicated fieldbus device.

No. 3150Message name Update of Fieldbus Devices

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 Updata Event Type=09 Rev=0002Device=FIC100 Block=FI-100 Detail=

Meaning A parameter update event (static data update) in the fieldbus block (tag name = FI-100) was received from the fieldbus device (tag name = FIC100) connected to the I/O module installed in slot 1 of unit 1 of node 1 in RIO bus system 1 of the field con-trol station (name = FCS0101).

Table Interpretation of Types

Type Interpretation

09 UPDATE-Static data update

0B UPDATE-Link associated with function block

0C UPDATE-Trend associated with block315001E.EPS

Table Interpretation of Rev

Rev Interpretation

0000 to FFFF Number of updates315002E.EPS

14th Edition : Dec.26,2006-00

Page 172: CS 1000/3000 Operating Messages

2-154

IM 33S02H10-01E

<2. Message Output Details>

No. 3160Message name Change in Write Protection of Fieldbus Devices

Printout example FCS0101 FB RIO1 NODE01 UNIT01 SLOT01 Write Protect Changed Type=0ADevice=FIC100 Block=FI-100 Detail=

Meaning A change event for the write protection of the fieldbus block (tag name = FI-100) wasreceived from the fieldbus device (tag name = FIC100) connected to the I/O moduleinstalled in slot 1 of unit 1 of node 1 in RIO bus system 1 of the field control station(name = FCS0101).

No. 3171Message Name Fieldbus Device Abnormal

Printout example FCS0101 FB FIO1 NODE01 SLOT01 PORT01 Device Alarm Type=08 Code=0007Device=FIC100 Block=FI-100 Detail=

Meaning An alarm message (Input Failure) is received from the Fieldbus device (Device Tag:FIC100) connected on Filed Control Station (Station Name:FCS0101), FIO bus train1, Node 1, Slot 1, Port 1.The details of error codes are as follows.0000: Other0001: Block Configuration Error0002: Link Configuration Error0003: Simulate Active0004: Local Override0005: Device Fault State Set0006: Device Needs Maintenance Soon0007: Input Failure / process variable has BAD status0008: Output Failure0009: Memory Failure000A: Lost Static Data000B: Lost NV Data000C: Read-back Check Failed000D: Device Needs Maintenance Now000E: Power-up000F: Out-of-Service

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

No. 3172Message Name Fieldbus Device Recovered to Normal

Printout example FCS0101 FB FIO1 NODE01 SLOT01 PORT01 Device Recover Device=FIC100Block=FIC100 Detail=

Meaning A message is received. It indicates that the Fieldbus device has recovered from ab-normality.

14th Edition : Dec.26,2006-00

Page 173: CS 1000/3000 Operating Messages

2-155

IM 33S02H10-01E

<2. Message Output Details>

No. 3173Message name Fieldbus Device Detected a Process Alarm

Printout example FCS0101 FB FIO1 NODE01 SLOT01 PORT01 Process Alarm Occur Type=02Device=FIC001 Block=FI-100 Detail=

Meaning A process HI abnormality (High alarm) is detected by Fieldbus function block (FB Tag:FI-100) in Fieldbus device (Device Tag: FIC001) connected on Filed Control Station(Station Name:FCS0101), FIO bus train 1, Node 1, Slot 1, Port 1.The details of the codes corresponding to the process alarm types are as follows.01: LO (Low limit)02: HI (High limit)03: LO LO (Critical low limit)04: HI HI (Critical high limit)05: DV LO (Deviation low)06: DV HI (Deviation high)07: DISC (Discrete)

No. 3174Message name The Process Alarm detected by the Fieldbus Device vanished

Printout example FCS0101 FB FIO1 NODE01 SLOT01 PORT01 Process Alarm Clear Device=FIC100Block=FI-100 Detail=

Meaning A message is received. It indicates that the process alarm detected by the functionblock of the displayed Fieldbus device has vanished.

No. 3175Message name Fieldbus Device Update Event

Printout example FCS0101 FB FIO1 NODE01 SLOT01 PORT01 Update Event Type=09 Rev=0002Device=FIC100 Block=FI-100 Detail=

Meaning An event message “Static data update” is received. It indicates that the parametershave been updated for Fieldbus function block (FB Tag: FI-100) in Fieldbus device(Device Tag: FIC100) connected on Filed Control Station (Station Name:FCS0101),RIO bus train 1, Node 1, Slot 1, Port 1.The details of the codes corresponding to the event types are as follows.09: UPDATE - Static data update0B: UPDATE - Link associated with function block0C: UPDATE - Trend associated with blockThe details of the codes corresponding to [rev] are as follows.0000 - FFFF : Total number of updates

15th Edition : Dec.10,2007-00

Page 174: CS 1000/3000 Operating Messages

2-156

IM 33S02H10-01E

<2. Message Output Details>

No. 3176Message name Enable/Disable Write Protection of Fieldbus Device

Printout example FCS0101 FB FIO1 NODE01 SLOT01 PORT01 Write Protect Changed Type=0ADevice=FIC100 Block=FI-100 Detail=

Meaning An event message is received. It indicates that the write protection setting for Field-bus function block (FB Tag: FI-100) in Fieldbus device (Device Tag: FIC100) con-nected on Filed Control Station (Station Name:FCS0101), RIO bus train 1, Node 1,Slot 1, Port 1.

No. 3181Message name Fieldbus Device Failure

Example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Device Error Device=FIC001

Meaning An error was detected in the fieldbus device (tag name = FIC001) connected to thefieldbus I/O module installed in port 1 of slot 1 of node 1 in FIO bus system 1 of thefield control station (name = FCS0101); or the HIS cannot communicate with that field-bus device.

No. 3182Message name Fieldbus Device Recovery

Example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Device Recover Device=FIC001

Meaning The indicated fieldbus device has recovered to normal

15th Edition : Dec.10,2007-00

Page 175: CS 1000/3000 Operating Messages

2-157

IM 33S02H10-01E

<2. Message Output Details>

No. 3183Message name Error Detected by ALF111 Self-diagnosis

Example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 ALF Error Detected Type=00Code=xxxx

Meaning Port 1 error is detected by the self-diagnosis of the module mounted in slot 1 of node1 of the control station (station name = FCS0101).Description of Code:0x0213: Flash Write Error (Alarm)0x0214: Hardware Error (Memory)0x0215: Hardware Error (Flash)0x0216: Hardware Error (ASIC)0x0221: Fieldbus Communication Setting Error (Communication parameter)

(Alarm)0x0222: Fieldbus Communication Setting Error (SM parameter) (Alarm)0x0223: Fieldbus Communication Setting Error (VCR) (Alarm)0x0224: Fieldbus Communication Setting Error (LAS schedule) (Alarm)0x0231: Port Hardware Error (ASIC)0x0232: Port Hardware Error (Send/Receive Circuit)0x0233: Port Communication Error

Action If the ALF111 is duplicated and the error is raised on both the modules, check theenvironment of the Fieldbus communication, isolate the cause, and solve it. If the erroris raised on one of the ALF111 modules, the possible cause is the failure of the mod-ule itself. If so, replace the module.

Remark The following error codes may appear if the ALF111 firmware version R11 or later isused.0x02140x02150x02160x02310x02320x0233In case that the ALF111 firmware version R11 or later is used together with FCS sys-tem revision R3.08 or later, the operation of the ALF111 defer depending on the sys-tem configuration when the error is detected.If the ALF111 is duplicated and both the modules are in operation, when the ALF111on the control side detects the port communication error, the control right is transferredto the standby side.If non-redundant ALF111 is used, one of the duplex ALF111 modules is in operation,or the ALF111 on the standby side detects the port communication error, the ALF111continues to operate.

No. 3201Message name PROFIBUS-DP field device-common message: Master Lock occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234 Master_Lock (Mas-ter STN099)

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas been locked by the other master device (address: 099).

14th Edition : Dec.26,2006-00

Page 176: CS 1000/3000 Operating Messages

2-158

IM 33S02H10-01E

<2. Message Output Details>

No. 3202Message name PROFIBUS-DP field device-common message: recovery from Master Lock

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234 Master_Lock

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas been released by the other master device.

No. 3203Message name PROFIBUS-DP field device-common message: Parameter Fault occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234 Parm_Fault

Meaning Parameter setting for the field device (address: 002, ID No.: 0x1234) connected to thedisplayed ACP card has failed.

No. 3204Message name PROFIBUS-DP field device-common message: recovery from Parameter Fault

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234 Parm_Fault

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from the Parameter Fault state.

No. 3205Message name PROFIBUS-DP field device-common message: Invalid Slave Response occur-

rence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234Invalid_Slave_Responce

Meaning An invalid communication frame has been received from the field device (address:002, ID No.: 0x1234) connected to the displayed ACP card.

No. 3206Message name PROFIBUS-DP field device-common message: recovery from Invalid Slave Re-

sponse

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234Invalid_Slave_Responce

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from the Invalid Slave Response state.

No. 3207Message name PROFIBUS-DP field device-common message: Not Supported occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234 Not_Supported

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas received a request for an unsupported function.

14th Edition : Dec.26,2006-00

Page 177: CS 1000/3000 Operating Messages

2-159

IM 33S02H10-01E

<2. Message Output Details>

No. 3208Message name PROFIBUS-DP field device-common message: recovery from Not Supported

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234 Not_Supported

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from the Not Supported state.

No. 3209Message name PROFIBUS-DP field device-common message: Configuration Fault occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234 Cfg_Fault

Meaning The configuration of the master device does not match that of the field device (address:002, ID No.: 0x1234) connected to the displayed ACP card.

No. 3210Message name PROFIBUS-DP field device-common message: recovery from Configuration Fault

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234 Cfg_Fault

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from the Configuration Fault state.

No. 3211Message name PROFIBUS-DP field device-common message: Station Not Ready occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234Station_Not_Ready

Meaning Data cannot be transferred to/from the field device (address: 002, ID No.: 0x1234)connected to the displayed ACP card.

No. 3212Message name PROFIBUS-DP field device-common message: recovery from Station Not Ready

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234Station_Not_Ready

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from the Station Not Ready state.

No. 3213Message name PROFIBUS-DP field device-common message: Station Non Existent occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234Station_Non_Existent

Meaning Communication with the field device (address: 002, ID No.: 0x1234) connected to thedisplayed ACP card is disabled.

14th Edition : Dec.26,2006-00

Page 178: CS 1000/3000 Operating Messages

2-160

IM 33S02H10-01E

<2. Message Output Details>

No. 3214Message name PROFIBUS-DP field device-common message: recovery from Station Non Existent

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234Station_Non_Existent

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from the Station Non Existent state.

No. 3215Message name PROFIBUS-DP field device-common message: Deactivated occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234 Deactivated

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas been removed from the cyclic transmission list.

No. 3216Message name PROFIBUS-DP field device-common message: recovery from Deactivated

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234 Deactivated

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from the Deactivated state.

No. 3217Message name PROFIBUS-DP field device-common message: Parameter Request occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234 Parm_Req

Meaning Parameter setting or configuration check is being performed for the field device (ad-dress: 002, ID No.: 0x1234) connected to the displayed ACP card.

No. 3218Message name PROFIBUS-DP field device-common message: recovery from Parameter Request

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234 Parm_Req

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from the Parameter Request state.

No. 3219Message name PROFIBUS-DP field device-common message: Ext Diag Overflow occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Alarm STN002 ID 0x1234 Ext_Diag_Overflow

Meaning The extension area has overflowed for diagnostic information received from the fielddevice (address: 002, ID No.: 0x1234) connected to the displayed ACP card.

14th Edition : Dec.26,2006-00

Page 179: CS 1000/3000 Operating Messages

2-161

IM 33S02H10-01E

<2. Message Output Details>

No. 3220Message name PROFIBUS-DP field device-common message: recovery from Ext Diag Overflow

Printing example FCS0101 PB UNIT 01 SLOT 01 Station Recover STN002 ID 0x1234Ext_Diag_Overflow

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from the Ext Diag Overflow state.

No. 3231Message name PROFIBUS-DP field device-specific message: error occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Device Related Alarm STN002 ID 0x1234

Meaning An error specific to the field device (address: 002, ID No.: 0x1234) connected to thedisplayed ACP card has occurred.CODE=XXXXXXXX refers to “Device related” in “Slave Diagnostic Information.”See the field device manual for more information.

No. 3232Message name PROFIBUS-DP field device-specific message: recovery from error

Printing example FCS0101 PB UNIT 01 SLOT 01 Device Related Recover STN002 ID 0x1234

Meaning The field device (address: 002, ID No.: 0x1234) connected to the displayed ACP cardhas recovered from its own specific error.

No. 3241Message name PROFIBUS-DP field device module error occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Module Alarm STN002 ID 0x1234 MODULE 01

Meaning An error has occurred in module 1 of the field device (address: 002, IDNo.: 0x1234)connected to the displayed ACP card.

No. 3242Message name PROFIBUS-DP recovery from field device module error

Printing example FCS0101 PB UNIT 01 SLOT 01 Module Recover STN002 ID 0x1234 MODULE 01

Meaning Module 1 of the field device (address: 002, ID No.: 0x1234) connected to the displayedACP card has recovered from the error.

No. 3251Message name PROFIBUS-DP field device channel error: short circuit occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 short circuit

Meaning Channel 1 has short-circuited in module 1 of the field device (address: 002, ID No.:0x1234) connected to the displayed ACP card.

14th Edition : Dec.26,2006-00

Page 180: CS 1000/3000 Operating Messages

2-162

IM 33S02H10-01E

<2. Message Output Details>

No. 3253Message name PROFIBUS-DP field device channel error: undervoltage occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 undervoltage

Meaning Undervoltage has occurred in channel 1 in module 1 of the field device (address: 002,ID No.: 0x1234) connected to the displayed ACP card.

No. 3255Message name PROFIBUS-DP field device channel error: overvoltage occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 overvoltage

Meaning Overvoltage has occurred in channel 1 in module 1 of the field device (address: 002,ID No.: 0x1234) connected to the displayed ACP card.

No. 3257Message name PROFIBUS-DP field device channel error: overload occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 overload

Meaning Channel 1 has been overloaded in module 1 of the field device (address:002, ID No.:0x1234) connected to the displayed ACP card.

No. 3259Message name PROFIBUS-DP field device channel error: overtemperature occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 overtempeature

Meaning The temperature is out of the acceptable range in channel 1 in module 1 of the fielddevice (address: 002, ID No.: 0x1234) connected to the displayed ACP card.

No. 3261Message name PROFIBUS-DP field device channel error: link break occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 link break

Meaning The link has broken in channel 1 in module 1 of the field device (address:002, ID No.:0x1234) connected to the displayed ACP card.

No. 3263Message name PROFIBUS-DP field device channel error: upper limit value exceeded

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 upper limit value exceeded

Meaning Channel 1 in module 1 of the field device (address: 002, ID No.: 0x1234) connectedto the displayed ACP card has exceeded the upper limit value.

14th Edition : Dec.26,2006-00

Page 181: CS 1000/3000 Operating Messages

2-163

IM 33S02H10-01E

<2. Message Output Details>

No. 3265Message name PROFIBUS-DP field device channel error: lower limit value exceeded

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 lower limit value exceeded

Meaning Channel 1 in module 1 of the field device (address: 002, ID No.: 0x1234) connectedto the displayed ACP card has exceeded the lower limit value.

No. 3267Message name PROFIBUS-DP field device channel error: error occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 error

Meaning An error has occurred in channel 1 in module 1 of the field device (address: 002, IDNo.: 0x1234) connected to the displayed ACP card.

No. 3269Message name PROFIBUS-DP field device channel error occurrence

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Alarm STN002 ID 0x1234 MODULE 01CHANNEL 01 Error Type = 20

Meaning Error type 20 has occurred in channel 1 in module 1 of the field device (address: 002,ID No.: 0x1234) connected to the displayed ACP card.See the field device manual for more information on the error type.

No. 3270Message name PROFIBUS-DP recovery from field device channel error

Printing example FCS0101 PB UNIT 01 SLOT 01 Channel Recover STN002 ID 0x1234 MODULE 01CHANNEL 01

Meaning Channel 1 in module 1 of the field device (address: 002, ID No.: 0x1234) connectedto the displayed ACP card has recovered from the error.

No. 3281Message name PROFIBUS communication stop

Printing example FCS0101 PB UNIT 01 SLOT 01 Communication Stop

Meaning The PROFIBUS communication of the displayed ACP card has stopped.

No. 3282Message name PROFIBUS communication resumption

Printing example FCS0101 PB UNIT 01 SLOT 01 Communication Recover

Meaning The PROFIBUS communication of the displayed ACP card has resumed.

14th Edition : Dec.26,2006-00

Page 182: CS 1000/3000 Operating Messages

2-164

IM 33S02H10-01E

<2. Message Output Details>

2.11 Control Station Related Messages(Message Nos. 4001 to 4036)In this chapter, the messages in regarding to CS1000/CS3000 field control stationsare explained.

No. 4001Message Name Fieldbus Device Error or Communication Error Due to External Cause of ALF111

Printing example 1 FCS0101 FB PIO01 NODE01 SLOT01 PORT01 Device Error Device=FIC001

Printing example 2 FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Device Error Device=@FBPS

Meaning An error was detected in one of the devices below. The devices are connected to Port1 on the I/O module connected to the Slot 1 on the Node 1 on the FIO Bus 1 systemon the control station (Station name: FCS0101).Device=FIC001: Fieldbus device (Device tag name: FIC001) has an error,

or communication cannot be established with the deviceon the Fieldbus.

Device=@FBPS: Power supply to the device on the Fieldbus is cut off, orALF111 power supply diagnostic circuit has an error. (De-vice tag = @FBPS)

Device=@FBCN(*1): Fieldbus cable (Device tag name: @ FBCN) may be disconnected or unplugged.

*1: Valid in ALF111 R11 or later. In the ALF111 before release R11, “@FBPS” isshown instead of @FBCN.

Note Only when the command script for detecting power failure is entered in the commandline field (ALF111 properties sheet on System View), the message can be triggeredby Fieldbus power failure, ALF111 power supply diagnostic circuit error and Fieldbusconnector disconnection.Depending on the disconnected status of the Fieldbus cable, the message No.3183,“Error Detected by ALF111 Self-diagnosis” may be output.

Action Check if the fieldbus is terminated on both ends, and make sure that the terminatorsare connected to both ends of the fieldbus.Using a tester to check if the power supply is properly provided to the fieldbus device.

No. 4002Message Name Fieldbus Device Recovery or External Cause of ALF111 Solved

Printing example 1 FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Device Recover Device=FIC001

Printing example 2 FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Device Recover Device=@FBPS

Meaning The shown Fieldbus device (Device tag name: FIC001), Power supply to the deviceon the Fieldbus (Device tag name: @FBPS), or Fieldbus cable (Device tag name: @FBCN) has been recovered.

14th Edition : Dec.26,2006-00

Page 183: CS 1000/3000 Operating Messages

2-165

IM 33S02H10-01E

<2. Message Output Details>

No. 4003Message name Occurrence of “Other”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Other Device=FIC001Block=FI-100

Meaning A field device manufacturer specified alarm has occurred in the fieldbus device (De-vice Tag: FIC001) connected to port 1 of slot 1 of node 1 in FIO bus system 1 of thefield control station (name = FCS0101).

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

No. 4004Message name Recovery of “Other”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Other RecoverDevice=FIC001 Block=FIC100

Meaning The indicated fieldbus device has recovered from a field device manufacturer speci-fied alarm.

No. 4005Message name Occurrence of “Block Configuration Error”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Block ConfigurationError Device=FIC001 Block=FIC100

Meaning “Block Configuration Error” has occurred in the fieldbus device (Device Tag: FIC001)function block (Block Tag:FIC100) connected to port 1 of slot 1 of node 1 in FIO bussystem 1 of the field control station (name = FCS0101).

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

No. 4006Message name Recovery of “Block Configuration Error”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Block ConfigurationError Recover Device=FIC001 Block=FIC100

Meaning The indicated fieldbus device has recovered from “Block Configuration Error”.

No. 4007Message name Occurrence of “Link Configuration Error”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Link ConfigurationError Device=FIC001 Block=FIC100

Meaning “Link Configuration Error” has occurred in the fieldbus device (Device Tag: FIC001)function block (Block Tag:FIC100) connected to port 1 of slot 1 of node 1 in FIO bussystem 1 of the field control station (name = FCS0101).

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

14th Edition : Dec.26,2006-00

Page 184: CS 1000/3000 Operating Messages

2-166

IM 33S02H10-01E

<2. Message Output Details>

No. 4008Message name Recovery of “Link Configuration Error”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Link ConfigurationError Recover Device=FIC001 Block=FIC100

Meaning The indicated fieldbus device has recovered from “Link Configuration Error”.

No. 4009Message name Occurrence of “Device Needs Maintenance Soon”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Device Needs Main-tenance Soon Device=FIC001 Block=FIC100

Meaning “Device Needs Maintenance Soon” has occurred in the fieldbus device (Device Tag:FIC001) function block (Block Tag:FIC100) connected to port 1 of slot 1 of node 1 inFIO bus system 1 of the field control station (name = FCS0101).

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

No. 4010Message name Recovery of “Device Needs Maintenance Soon”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Device Needs Main-tenance Soon Recover Device=FIC001 Block=FIC100

Meaning The indicated fieldbus device has recovered from “Device Needs Maintenance Soon”.

No. 4011Message name Occurrence of “Memory Failure”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Memory FailureDevice=FIC001 Block=FIC100

Meaning “Memory Failure” has occurred in the fieldbus device (Device Tag: FIC001) functionblock (Block Tag:FIC100) connected to in port 1 of slot 1 of node 1 in FIO bus system1 of the field control station (name = FCS0101).

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

No. 4012Message name Recovery of “Memory Failure”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Memory Failure Re-cover Device=FIC001 Block=FIC100

Meaning The indicated fieldbus device has recovered from “Memory Failure”.

14th Edition : Dec.26,2006-00

Page 185: CS 1000/3000 Operating Messages

2-167

IM 33S02H10-01E

<2. Message Output Details>

No. 4013Message name Occurrence of “Lost Static Data”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Lost Static DataDevice=FIC001 Block=FIC100

Meaning “Lost Static Data” has occurred in the fieldbus device (Device Tag: FIC001) functionblock (Block Tag:FIC100) connected to port 1 of slot 1 of node 1 in FIO bus system 1of the field control station (name = FCS0101).

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

No. 4014Message name Recovery of “Lost Static Data”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Lost Static Data Re-cover Device=FIC001 Block=FIC100

Meaning The indicated fieldbus device has recovered from “Lost Static Data”.

No. 4015Message name Occurrence of “Lost NV Data”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Lost NV DataDevice=FIC001 Block=FIC100

Meaning “Lost NV Data” has occurred in the fieldbus device (Device Tag: FIC001) function block(Block Tag:FIC100) connected to port 1 of slot 1 of node 1 in FIO bus system 1 of thefield control station (name = FCS0101).

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

No. 4016Message name Recovery of “Lost NV Data”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Lost NV Data RecoverDevice=FIC001 Block=FIC100

Meaning The indicated fieldbus device has recovered from “Lost NV Data”.

No. 4017Message name Occurrence of “Readback Check Failed”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Readback CheckFailed Device=FIC001 Block=FIC100

Meaning “Readback Check Failed” has occurred in the fieldbus device (Device Tag: FIC001)function block (Block Tag:FIC100) connected to port 1 of slot 1 of node 1in FIO bussystem 1 of the field control station (name = FCS0101).

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

14th Edition : Dec.26,2006-00

Page 186: CS 1000/3000 Operating Messages

2-168

IM 33S02H10-01E

<2. Message Output Details>

No. 4018Message name Recovery of “Readback Check Failed”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Readback CheckFailed Recover Device=FIC001 Block=FIC100

Meaning The indicated fieldbus device has recovered from “Readback Check Failed”.

No. 4019Message name Occurrence of “Device Needs Maintenance Now”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Device Needs Main-tenance Now Device=FIC001 Block=FIC100

Meaning “Device Needs Maintenance Now” has occurred in the fieldbus device (Device Tag:FIC001) function block (Block Tag:FIC100) connected to port 1 of slot 1 of node 1 inFIO bus system 1 of the field control station (name = FCS0101).

Action See the fieldbus device manual for detailed information about BLOCK Alarm andBLOCK_ERROR.

No. 4020Message name Recovery of “Device Needs Maintenance Now”

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 Block Alarm - Device Needs Main-tenance Now Recover Device=FIC001 Block=FIC100

Meaning The indicated fieldbus device has recovered from “Device Needs Maintenance Now”.

No. 4021Message name Error When Write to Foundation Fieldbus Faceplate Block

Printing example FCS0101 FB FIO01 NODE01 SLOT01 PORT01 WRITE Error Block=FIC100

Meaning Data entry to the Foundation Fieldbus faceplate block (block tag name = FIC100) ofthe control station (station name = FCS0101) could not be transmitted to the Fieldbusfunction block in port 1 of slot 1 of node 1 in FIO bus system 1. The error may becaused by frequently data entry or overload of Fieldbus.

15th Edition : Dec.10,2007-00

Page 187: CS 1000/3000 Operating Messages

2-169

IM 33S02H10-01E

<2. Message Output Details>

No. 4023Message name Communication Error with Duplicate ALF111

Printing example FCS0101 NODE 01 SLOT 01 PORT 01 FF-H1 Device Connection Error Address=0xF6(246)

Meaning This message appears if the ALF111 is duplicated and both the modules are in opera-tion.Communication error occurred between the ALF111 module and the Fieldbus device(Device address: 0xF6) connected to Port 1 on the I/O module connected to the Slot1 on the Node 1 on the control station (Station name: FCS0101). If this message israised on all the devices connected to one specific port, ALF111 module failure, wrongwiring, or connector failure is the possible cause. This is shown as a message froma failed module, either the Control side or Standby side.

Action If the communication error occurs on the Control side, the Standby ALF111 moduleis switched to Control according to the Builder setting.If the communication error occurs on the Standby side, isolate the cause, and solveit.

No. 4024Message name Communication Error with Duplicate ALF111 Recovered

Printing example FCS0101 NODE 01 SLOT 01 PORT 01 FF-H1 Device Connection Recover Address=0xF6(246)

Meaning Communication between the ALF111 module and the Fieldbus device resumed.

No. 4031Message name HART Device Error

Printing example FCS0101 FIO01 NODE01 SLOT01 CH01 HART Device Error

Meaning A HART device in control station FCS0101, FIO segment01, node 01, slot 01, chan-nel 01 has an error.

No. 4032Message name HART Device Recovery

Printing example FCS0101 FIO01 NODE01 SLOT01 CH01 HART Device Recover

Meaning The HART device recovered from error.

No. 4033Message name HART Communication Error

Printing example FCS0101 FIO01 NODE01 SLOT01 CH01 HART Communication Error=XX

Meaning A HART device in control station FCS0101, FIO segment 01, node 01, slot 01, channel01 has a communication error.

15th Edition : Dec.10,2007-00

Page 188: CS 1000/3000 Operating Messages

2-170

IM 33S02H10-01E

<2. Message Output Details>

No. 4034Message name HART Communication Recovery

Printing example FCS0101 FIO01 NODE01 SLOT01 CH01 HART Communication Recover

Meaning The HART device and related I/O module recovered from a communication error.

No. 4035Message name HART Communication Command Error

Printing example FCS0101 FIO01 NODE01 SLOT01 CH01 HART Communication CommandError=XX

Meaning A HART device in control station FCS0101, FIO segment 01, node 01, slot 01, channel01 has a communication command error.

No. 4036Message name HART Communication Command Recover

Printing example FCS0101 FIO01 NODE01 SLOT01 CH01 HART Communication Command Recover

Meaning The HART device and related I/O module recovered from a communication commanderror.

15th Edition : Dec.10,2007-00

Page 189: CS 1000/3000 Operating Messages

2-171

IM 33S02H10-01E

<2. Message Output Details>

2.12 ProSafe-RS Messages(Message Numbers 4101 to 4199)This section describes the ProSafe-RS system messages.

SEE ALSO

For more information about ProSafe-RS system messages, see the following:

2. “Details of Output Messages Specific to the SCS” in Messages (IM 32S02B10-01E).

14th Edition : Dec.26,2006-00

Page 190: CS 1000/3000 Operating Messages