  • Appendix B - APOGEE BACnet PICS

    PICS..................................................................................................................................................10-1 Product Description ......................................................................................................................................10-1

    Object Types and Supported Properties ...........................................................................................10-5 Analog Input Object Type ............................................................................................................................10-5 Analog Output Object Type..........................................................................................................................10-6 Analog Value Object Type ...........................................................................................................................10-8 Binary Input Object Type .............................................................................................................................10-9 Binary Output Object Type.........................................................................................................................10-10 Binary Value Object Type ..........................................................................................................................10-11 Calendar Object Type .................................................................................................................................10-12 Command Object Type...............................................................................................................................10-12 Device Object Type ....................................................................................................................................10-12 File Object Type .........................................................................................................................................10-14 Multistate Output Object Type ...................................................................................................................10-14 Multistate Value Object Type.....................................................................................................................10-15 Notification Class Object Type...................................................................................................................10-16 Schedule Object Type.................................................................................................................................10-17 Trend Log Object Type ..............................................................................................................................10-18 Data Link Layer Options ............................................................................................................................10-19 Device Address Binding .............................................................................................................................10-19 Networking Options....................................................................................................................................10-19 Supported Character Sets............................................................................................................................10-19

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 1

    PICS

    Product Description Product Implementation Conformance Statement for APOGEE BACnet Over IP BLN

    Devices (BPXCM) Document 149-487. The PXC Modular Series for BACnet

    networks is a high-performance modular Direct Digital Control (DDC) supervisory

    equipment controller, which is an integral part of the APOGEE Automation System. It

    is classified as a BACnet Building Controller

    (B-BC) and supports BACnet/IP and BACnet MS/TP protocols.

    The PXC Modular operates stand-alone or networked to perform complex control,

    monitoring, and energy management functions without relying on a higher-level

    processor.

    Up to 1000 modular field panels communicate on a peer-to-peer network.

    With the addition of TX-I/O modules and a TX-I/O Power Supply on a self-

    forming bus, the PXC Modular can directly control up to 500 points.

    With the addition of an Exp Module, the PXCM also provides central monitoring

    and control for distributed wireless or wired Field Level Network (FLN) devices.

    This document has been modified for class purposes. Some sections of this PICS were intentionally deleted. The full version can be found at http://www.bacnetinternational.net/catalog/index.php?m=23&pr=2.

    BACnet Standardized Device Profile (Annex L)BACnet Standardized Device Profile (Annex L)BACnet Standardized Device Profile (Annex L)BACnet Standardized Device Profile (Annex L)

    Supported

    SupportedSupported

    Supported

    Device Profile

    Device ProfileDevice Profile

    Device Profile

    BACnet Operator Workstation (B-OWS)

    BACnet Building Controller (B-BC)

    BACnet Advanced Application Controller (B-AAC)

    BACnet Application Specific Controller (B-ASC)

    BACnet Smart Actuator (B-SA)

    BACnet Smart Sensor (B-SS)

    Supported BACnet Interoperability Building Block (BIBSupported BACnet Interoperability Building Block (BIBSupported BACnet Interoperability Building Block (BIBSupported BACnet Interoperability Building Block (BIBBs)Bs)Bs)Bs)

    BIBB

    BIBBBIBB

    BIBB

    Name

    NameName

    Name

    Initiate

    InitiateInitiate

    Initiate

    Execute

    ExecuteExecute

    Execute

    Data Sharing

    Data SharingData Sharing

    Data Sharing

    DS-RP-A Data Sharing-ReadProperty-A

    DS-RP-B Data Sharing-ReadProperty-B

    DS-RPM-A Data Sharing-ReadPropertyMultiple-A

    DS-RPM-B Data Sharing-ReadPropertyMultiple-B

    DS-WP-A Data Sharing-WriteProperty-A

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10-2

    BIBB

    BIBBBIBB

    BIBB

    Name

    NameName

    Name

    Initiate

    InitiateInitiate

    Initiate

    Execute

    ExecuteExecute

    Execute

    Data Sharing

    Data SharingData Sharing

    Data Sharing

    DS-WP-B Data Sharing-WriteProperty-B

    DS-WPM-B Data Sharing-WritePropertyMultiple-B

    DS-COV-A Data Sharing-COV-A

    DS-COV-B Data Sharing-COV-B

    DS-COVU-A Data Sharing-COV-Unsolicited-A

    DS-COVU-B Data Sharing-COV-Unsolicited-B

    Scheduling

    SchedulingScheduling

    Scheduling

    SCHED-I-B Scheduling-Internal-B

    SCHED-E-B Scheduling-External-B

    Alarm and Event Management

    Alarm and Event ManagementAlarm and Event Management

    Alarm and Event Management

    AE-N-A Alarm and Event-Notification-A

    AE-N-I-B Alarm and Event-Notification Internal-B

    AE-N-E-B Alarm and Event-Notification External-B

    AE-ACK-A Alarm and Event-ACK-A

    AE-ACK-B Alarm and Event-ACK-B

    AE-ASUM-B Alarm and Event-Alarm Summary-B

    AE-ESUM-A Alarm and Event-Enrollment Summary-A

    AE-ESUM-B Alarm and Event-Enrollment Summary-B

    AE-INFO-A Alarm and Event-Information-A

    AE-INFO-B Alarm and Event-Information-B

    Trending

    TrendingTrending

    Trending

    T-VMT-A Trending-Viewing and Modifying Trends-A

    T-VMT-I-B Trending-Viewing and Modifying Trends-

    Internal-B

    T-VMT-E-B Trending-Viewing and Modifying Trends-

    External-B

    T-ATR-B Trending-Automated Trend Retrieval-B

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 3

    Network Management

    Network ManagementNetwork Management

    Network Management

    NM-CE-A Network Management-Connection

    Establishment-A

    Device Management

    Device ManagementDevice Management

    Device Management

    DM-DDB-A Device Management-Dynamic Device Binding-A

    DM-DDB-B Device Management-Dynamic Device Binding-B

    DM-DOB-A Device Management-Dynamic Object Binding-A

    DM-DOB-B Device Management-Dynamic Object Binding-B

    DM-DDC-B Device Management-

    DeviceCommunicationControl-B

    DM-PT-A Device Management-Private Transfer-A

    DM-PT-B Device Management-Private Transfer-B

    DM-TM-A Device Management-Text Message-A

    DM-TM-B Device Management-Text Message-B

    DM-TS-B Device Management-TimeSynchronization-B

    DM-RD-B Device Management-ReinitializeDevice-B

    DM-BR-B Device Management-Backup and Restore-B

    DM-LM-B Device Management-List Manipulation-B

    DM-OCD-B Device Management-Object Creation and

    Deletion-B

    Standard Object Types SupportedStandard Object Types SupportedStandard Object Types SupportedStandard Object Types Supported

    Name

    NameName

    Name

    Creatable

    CreatableCreatable

    Creatable

    Deletable

    DeletableDeletable

    Deletable

    Analog Input

    Analog Output

    Analog Value

    Binary Inpute

    Binary Output

    Binary Value

    Calendar

    Command

    Device

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10-4

    Name

    NameName

    Name

    Creatable

    CreatableCreatable

    Creatable

    Deletable

    DeletableDeletable

    Deletable

    Event Enrollment

    File

    Multi-state Output

    Multi-state Value

    Notification Class

    Schedule

    Trend Log

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 5

    Object AttributesObject AttributesObject AttributesObject Attributes O

    OO

    O indicates that the property is optional, per the BACnet standard.

    R

    RR

    R indicates that the property is required to be present and readable using BACnet services.

    Yes indicates that the property is

    indicates that the property is indicates that the property is

    indicates that the property is required to be present, readable, and writable using BACnet services.

    to be present, readable, and writable using BACnet services. to be present, readable, and writable using BACnet services.

    to be present, readable, and writable using BACnet services.

    Object Types and Supported Properties

    Analog Input Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component AI Present_Value Yes w REAL

    Description Yes w Limited to 16 chars

    Device_Type Yes Text corresponding to the Apogee LAI sensor type as follows: current voltage pneumatic 100k Thermistor 1K Platinum RTD LType custom

    Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.

    Event_State Yes If point is in alarm, then Event_State = OFFNORMAL, else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.

    Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.

    Out_Of_Service Yes w Must be set to override Present_Value

    Units Yes Uses BACnet enumeration corresponding to fixed engineering units strings

    Resolution Yes Slope

    COV_Increment Yes w COV Limit

    Time_Delay Alarm

    Notification Class Alarm w

    High_Limit Alarm w High Limit

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10-6

    Property Identifier Support Access Notes

    Low_Limit Alarm w Low Limit

    Deadband Alarm w

    Limit_Enable Alarm If alarming enabled, then low_limit and high_limit both enabled

    Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE

    Acked_Transitions Alarm

    New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Notify_Type Alarm w

    Event_Time_Stamps Alarm

    New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Analog Output Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component AO Present_Value Yes w REAL

    Description Yes w Limited to 16 chars

    Device_Type Yes Associated Apogee Point type

    Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name..

    Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.

    Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.

    Out_Of_Service Yes Always FALSE

    Units Yes Uses BACnet enumeration corresponding to fixed engineering units strings

    Resolution Yes Slope

    Priority_Array Yes For commanding the present value

    Relinquish_default Yes For releasing the present value when the Priority Array is empty.

    COV_Increment Yes w COV Limit

    Analog Input Object Type, continued

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 7

    Object Types and Supported Properties, continued

    Analog Output Object Type, continued

    Time_Delay Alarm

    Notification Class Alarm w

    High_Limit Alarm w High Limit

    Low_Limit Alarm w Low Limit

    Deadband Alarm w

    Limit_Enable Alarm If alarming enabled, then low_limit and high_limit both enabled

    Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE

    Acked_Transitions Alarm

    New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Notify_Type Alarm w

    Event_Time_Stamps Alarm

    New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10-8

    Object Types and Supported Properties, continued

    Analog Value Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component AV Present_Value Yes w REAL

    Description Yes w Limited to 16 chars

    Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.

    Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.

    Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.

    Out_Of_Service Yes Always FALSE

    Units Yes Uses BACnet enumeration corresponding to fixed engineering units strings

    Priority_Array Yes For commanding the present value

    Relinquish_default Yes For releasing the present value when the Priority Array is empty.

    COV_Increment Yes w COV Limit

    Time_Delay Alarm

    Notification Class Alarm w

    High_Limit Alarm w High Limit

    Low_Limit Alarm w Low Limit

    Deadband Alarm w

    Limit_Enable Alarm If alarming enabled, then low_limit and high_limit both enabled

    Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE

    Acked_Transitions Alarm

    New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Notify_Type Alarm w

    Event_Time_Stamps Alarm

    New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 9

    Object Types and Supported Properties, continued

    Binary Input Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component BI Present_Value Yes w Binary Value

    Description Yes w Limited to 16 chars

    Device_Type Yes Associated Apogee Point type

    Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.

    Event_State Yes If point is in alarm, then Event_State = OFFNORMAL, else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.

    Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.

    Out_Of_Service Yes w Must be set in order to override the Present_Value

    Polarity Yes Normally Closed

    Inactive_Text Yes Correspond with first entry in the points State Text Table

    Active_Text Yes Correspond with second entry in the points State Text Table

    Elapsed_Active_Time Yes w Totalization

    Time_Of_ Active_Time_Reset

    Yes Totalization_Reset_Time

    Time_Delay Alarm

    Notification Class Alarm w

    Alarm_Value Alarm Specifies what the present_value is when the point is in Alarm.

    Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE

    Acked_Transitions Alarm

    New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Notify_Type Alarm w

    Event_Time_Stamps Alarm

    New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10-10

    Object Types and Supported Properties, continued

    Binary Output Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component BO Present_Value Yes w Binary Value

    Description Yes w Limited to 16 chars

    Device_Type Yes Associated Apogee Point type

    Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.

    Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.

    Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.

    Out_Of_Service Yes Always FALSE

    Polarity Yes Inverted

    Inactive_Text Yes Correspond with first entry in the points State Text Table

    Active_Text Yes Correspond with second entry in the points State Text Table

    Elapsed_Active_Time Yes w Totalization

    Time_Of_ Active_Time_Reset

    Yes Totalization_Reset_Time

    Priority_Array Yes For commanding the present value

    Relinquish_default Yes For releasing the present value when the Priority Array is empty.

    Time_Delay Alarm Proof Delay Notification Class Alarm w

    Feedback_Value Alarm Current value of the proof point for Apogee proof points, set equal to the Present_Value for points without proofing.

    Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE

    Acked_Transitions Alarm

    New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Notify_Type Alarm w

    Event_Time_Stamps Alarm

    New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 11

    Object Types and Supported Properties, continued

    Binary Value Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component BV Present_Value Yes w Binary Value

    Description Yes w Limited to 16 chars

    Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.

    Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.

    Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.

    Out_Of_Service Yes Always FALSE

    Inactive_Text Yes Correspond with first entry in the points State Text Table

    Active_Text Yes Correspond with second entry in the points State Text Table

    Elapsed_Active_Time Yes w Totalization

    Time_Of_ Active_Time_Reset

    Yes Totalization_Reset_Time

    Priority_Array Yes For commanding the present value

    Relinquish_default Yes For releasing the present value when the Priority Array is empty.

    Time_Delay Alarm Proof Delay Notification Class Alarm w

    Alarm_Value Alarm Specifies what the present_value is when the point is in Alarm.

    Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE

    Acked_Transitions Alarm

    New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Notify_Type Alarm w

    Event_Time_Stamps Alarm

    New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10-12

    Object Types and Supported Properties, continued

    Calendar Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component CA Description Yes w Limited to 16 chars

    Present_Value Yes Binary Value, True if today is in the calendar.

    Date_List Yes w Single Dates, Date Ranges, and WeekNDays

    Command Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component CO Description Yes w Limited to 16 chars

    Present_Value Yes w Unsigned value, similar to a mode point, triggers one of many action lists

    In_Process Yes True during the time the action list is being executed

    All_Writes_Successful Yes True if all commands in last action list run were executed without error

    Action Yes w The array of Action Lists

    Action _Text Yes w The array of Names for the Action Lists

    Device Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Configured in IP Settings Object_Name Yes Field Panel Name, limited to 30 chars, Configured in IP

    Settings

    Object_Type Yes Encoded name component BACDev System_Status Yes OPERATIONAL status used to set Ready status

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 13

    Object Types and Supported Properties, continued

    Device Object Type, continued

    Vendor_Name Yes "Siemens BAU"

    Vendor_Identifier Yes All Siemens ISA devices = 7

    Model_Name Yes "Siemens BACnet EMEC"

    Firmware_Revision Yes Firmware Rev String for example, "BCE V3.0 Apogee

    Application_Software_Version Yes Firmware Rev String for example, "BCE3001

    Location Yes limited to 40 chars, Configured in IP Settings

    Description Yes limited to 40 chars, Configured in IP Settings

    Protocol_Version Yes 1

    Protocol_Revision Yes 4

    Protocol_Services_Supported Yes See section 7.3.2 for list of services supported

    Protocol_Object_Types _Supported

    Yes See section 7.1.1 for list of objects supported

    Object_List Yes List of object Ids for all points in this field panel ! Max_APDU_Length_Accepted Yes 1497

    Segmentation_Supported Yes BACNET_SEGMENTATION_TYPE_BOTH

    Max_Segments_Supported Yes 32

    Local_Time Yes Field Panel Time

    Local_Date Yes Field Panel Date

    Daylight_Savings_Status Yes

    APDU_Segment_Timeout Yes 3000

    APDU_Timeout Yes 3000

    Number_Of_APDU_Retries Yes 3

    Device_Address_Binding Yes

    Database_Revision Yes Logical revision number for the database, incremented when objects are created and/or deleted, an object's name is changed, or a database restore is performed.

    Configuration_Files Yes List of files to be backed up. Valid only during the backup procedure.

    Last_Restore_Time Yes Time of last file download. Applies only to BACnet file transfer services.

    Backup_Failure_Timeout Yes w How long to wait before aborting a backup or restore operation.

    Active_COV_Subscriptions Yes A list of active subscriptions. Applies to the server side.

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10-14

    Object Types and Supported Properties, continued

    File Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component FI Description Yes Limited to 16 chars

    File_Type Yes

    File_Size Yes w

    Modification_Date Yes

    Archive Yes w

    Read_only Yes

    File_Access_Method Yes

    Multistate Output Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component MO Present_Value Yes w Unsigned

    Description Yes w Limited to 16 chars

    Device_Type Yes Associated Apogee Point type

    Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.

    Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.

    Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.

    Out_Of_Service Yes w

    Number_Of_States Yes Correspond to size of State Text Table

    State_Text Yes Corresponds with State Text Table

    Priority_Array Yes For commanding the present value

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 15

    Object Types and Supported Properties, continued

    Multistate Output Object Type, continued

    Property Identifier Support Access Notes Relinquish_default Yes For releasing the present value when the Priority Array is empty.

    Time_Delay Alarm Proof Delay Notification Class Alarm w

    Feedback_Value Alarm Current value of the proof point for Apogee proof points, set equal to the Present_Value for points without proofing.

    Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE

    Acked_Transitions Alarm

    New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Notify_Type Alarm Always = Alarm

    Event_Time_Stamps Alarm

    New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Multistate Value Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component MV Present_Value Yes w Unsigned

    Description Yes w Limited to 16 chars

    Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.

    Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.

    Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.

    Out_Of_Service Yes w

    Number_Of_States Yes Correspond to size of State Text Table

    State_Text Yes Corresponds with State Text Table

    Priority_Array Yes For commanding the present value

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10-16

    Object Types and Supported Properties, continued

    Multistate Value Object Type, continued

    Property Identifier Support Access Notes Relinquish_default Yes For releasing the present value when the Priority Array is

    empty.

    Time_Delay Alarm

    Notification Class Alarm w

    Alarm_Values Alarm

    Fault_Values Alarm

    Event_Enable Alarm w

    Acked_Transitions Alarm

    New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Notify_Type Alarm w Always = Alarm

    Event_Time_Stamps Alarm

    New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.

    Notification Class Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component NC Description Yes w Limited to 16 chars

    Notification_Class Yes Range is 0 to 4 meg, Automatically assigned, same as Object_Id

    Priority Yes w

    Ack_Required Yes w

    Recipient_List Yes w

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 17

    Object Types and Supported Properties, continued

    Schedule Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component SC Present_Value Yes w REAL, Unsigned, Enum and BOOL

    Description Yes w Limited to 16 chars

    Effective_Period Yes w

    Weekly_Schedule Yes w

    Exception_Schedule Yes w

    Schedule_Default Yes w

    List_Of_Object_ Property_References

    Yes w

    Priority_For_Writing Yes w

    Status_Flags Yes

    Reliability Yes

    Out_Of_Service Yes w

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10-18

    Object Types and Supported Properties, continued

    Trend Log Object Type

    Property Identifier Support Access Notes

    Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component TL Description Yes w Limited to 16 chars

    Log_Enable Yes w BOOL

    Start_Time Yes w New BACnet only feature

    Stop_Time Yes w New BACnet only feature

    Log_DeviceObjectProperty Yes Always the Present Value property of a Point Log_Interval Yes Nonzero for byTime, Zero for by COV

    Client_COV_Interval Yes

    Stop_When_Full Yes w New BACnet only feature

    Buffer_Size Yes

    Log_Buffer Yes Accessed by Read Range service only

    Record_Count Yes w

    Total_Record_Count Yes

    Notification_Threshold Alarm w Intrinsic reporting used to notify Insight that buffer is full.

    Records_Since_Notification Alarm Intrinsic reporting used to notify Insight that buffer is full.

    Last_Notify_Record Alarm Intrinsic reporting used to notify Insight that buffer is full.

    Event_State Yes

    Notification_Class Alarm w

    Event_Enable Alarm

    Acked_Transitions Alarm

    Notify_Type Alarm w Always set to Event

    Event_Time_Stamps Alarm

  • Siemens Industry, Inc. Building Technologies

    Appendix B For Internal Use Only

    10 - 19

    Object Types and Supported Properties, continued

    Data Link Layer Options

    BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device

    ISO 8802-3, Ethernet (Clause 7)

    ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

    ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____________

    MS/TP master (Clause 9), baud rate(s): MS/TP slave (Clause 9), baud rate(s): Point-To-Point, EIA 232 (Clause 10), baud rate(s): _________________ Point-To-Point, modem, (Clause 10), baud rate(s): _________________ LonTalk, (Clause 11), medium: _________________________________ Other: _____________________________________________________

    Device Address Binding

    Is Static Device Binding supported? Yes

    Networking Options

    Router, Clause 6 Annex H.3, BACnet Tunneling Router over UDP/IP

    BACnet/IP Broadcast Management Device (BBMD) Yes Does the BBMD support registrations by Foreign Devices?

    Supported Character Sets

    ANSI X3.4 ISO 10646 (UCS-2) IBM/Microsoft DBCS ISO 10646 (ICS-4) ISO 8859-1 JIS C 6226