Appendix B - APOGEE BACnet PICS
PICS..................................................................................................................................................10-1 Product Description ......................................................................................................................................10-1
Object Types and Supported Properties ...........................................................................................10-5 Analog Input Object Type ............................................................................................................................10-5 Analog Output Object Type..........................................................................................................................10-6 Analog Value Object Type ...........................................................................................................................10-8 Binary Input Object Type .............................................................................................................................10-9 Binary Output Object Type.........................................................................................................................10-10 Binary Value Object Type ..........................................................................................................................10-11 Calendar Object Type .................................................................................................................................10-12 Command Object Type...............................................................................................................................10-12 Device Object Type ....................................................................................................................................10-12 File Object Type .........................................................................................................................................10-14 Multistate Output Object Type ...................................................................................................................10-14 Multistate Value Object Type.....................................................................................................................10-15 Notification Class Object Type...................................................................................................................10-16 Schedule Object Type.................................................................................................................................10-17 Trend Log Object Type ..............................................................................................................................10-18 Data Link Layer Options ............................................................................................................................10-19 Device Address Binding .............................................................................................................................10-19 Networking Options....................................................................................................................................10-19 Supported Character Sets............................................................................................................................10-19
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 1
PICS
Product Description Product Implementation Conformance Statement for APOGEE BACnet Over IP BLN
Devices (BPXCM) Document 149-487. The PXC Modular Series for BACnet
networks is a high-performance modular Direct Digital Control (DDC) supervisory
equipment controller, which is an integral part of the APOGEE Automation System. It
is classified as a BACnet Building Controller
(B-BC) and supports BACnet/IP and BACnet MS/TP protocols.
The PXC Modular operates stand-alone or networked to perform complex control,
monitoring, and energy management functions without relying on a higher-level
processor.
Up to 1000 modular field panels communicate on a peer-to-peer network.
With the addition of TX-I/O modules and a TX-I/O Power Supply on a self-
forming bus, the PXC Modular can directly control up to 500 points.
With the addition of an Exp Module, the PXCM also provides central monitoring
and control for distributed wireless or wired Field Level Network (FLN) devices.
This document has been modified for class purposes. Some sections of this PICS were intentionally deleted. The full version can be found at http://www.bacnetinternational.net/catalog/index.php?m=23&pr=2.
BACnet Standardized Device Profile (Annex L)BACnet Standardized Device Profile (Annex L)BACnet Standardized Device Profile (Annex L)BACnet Standardized Device Profile (Annex L)
Supported
SupportedSupported
Supported
Device Profile
Device ProfileDevice Profile
Device Profile
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Actuator (B-SA)
BACnet Smart Sensor (B-SS)
Supported BACnet Interoperability Building Block (BIBSupported BACnet Interoperability Building Block (BIBSupported BACnet Interoperability Building Block (BIBSupported BACnet Interoperability Building Block (BIBBs)Bs)Bs)Bs)
BIBB
BIBBBIBB
BIBB
Name
NameName
Name
Initiate
InitiateInitiate
Initiate
Execute
ExecuteExecute
Execute
Data Sharing
Data SharingData Sharing
Data Sharing
DS-RP-A Data Sharing-ReadProperty-A
DS-RP-B Data Sharing-ReadProperty-B
DS-RPM-A Data Sharing-ReadPropertyMultiple-A
DS-RPM-B Data Sharing-ReadPropertyMultiple-B
DS-WP-A Data Sharing-WriteProperty-A
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10-2
BIBB
BIBBBIBB
BIBB
Name
NameName
Name
Initiate
InitiateInitiate
Initiate
Execute
ExecuteExecute
Execute
Data Sharing
Data SharingData Sharing
Data Sharing
DS-WP-B Data Sharing-WriteProperty-B
DS-WPM-B Data Sharing-WritePropertyMultiple-B
DS-COV-A Data Sharing-COV-A
DS-COV-B Data Sharing-COV-B
DS-COVU-A Data Sharing-COV-Unsolicited-A
DS-COVU-B Data Sharing-COV-Unsolicited-B
Scheduling
SchedulingScheduling
Scheduling
SCHED-I-B Scheduling-Internal-B
SCHED-E-B Scheduling-External-B
Alarm and Event Management
Alarm and Event ManagementAlarm and Event Management
Alarm and Event Management
AE-N-A Alarm and Event-Notification-A
AE-N-I-B Alarm and Event-Notification Internal-B
AE-N-E-B Alarm and Event-Notification External-B
AE-ACK-A Alarm and Event-ACK-A
AE-ACK-B Alarm and Event-ACK-B
AE-ASUM-B Alarm and Event-Alarm Summary-B
AE-ESUM-A Alarm and Event-Enrollment Summary-A
AE-ESUM-B Alarm and Event-Enrollment Summary-B
AE-INFO-A Alarm and Event-Information-A
AE-INFO-B Alarm and Event-Information-B
Trending
TrendingTrending
Trending
T-VMT-A Trending-Viewing and Modifying Trends-A
T-VMT-I-B Trending-Viewing and Modifying Trends-
Internal-B
T-VMT-E-B Trending-Viewing and Modifying Trends-
External-B
T-ATR-B Trending-Automated Trend Retrieval-B
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 3
Network Management
Network ManagementNetwork Management
Network Management
NM-CE-A Network Management-Connection
Establishment-A
Device Management
Device ManagementDevice Management
Device Management
DM-DDB-A Device Management-Dynamic Device Binding-A
DM-DDB-B Device Management-Dynamic Device Binding-B
DM-DOB-A Device Management-Dynamic Object Binding-A
DM-DOB-B Device Management-Dynamic Object Binding-B
DM-DDC-B Device Management-
DeviceCommunicationControl-B
DM-PT-A Device Management-Private Transfer-A
DM-PT-B Device Management-Private Transfer-B
DM-TM-A Device Management-Text Message-A
DM-TM-B Device Management-Text Message-B
DM-TS-B Device Management-TimeSynchronization-B
DM-RD-B Device Management-ReinitializeDevice-B
DM-BR-B Device Management-Backup and Restore-B
DM-LM-B Device Management-List Manipulation-B
DM-OCD-B Device Management-Object Creation and
Deletion-B
Standard Object Types SupportedStandard Object Types SupportedStandard Object Types SupportedStandard Object Types Supported
Name
NameName
Name
Creatable
CreatableCreatable
Creatable
Deletable
DeletableDeletable
Deletable
Analog Input
Analog Output
Analog Value
Binary Inpute
Binary Output
Binary Value
Calendar
Command
Device
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10-4
Name
NameName
Name
Creatable
CreatableCreatable
Creatable
Deletable
DeletableDeletable
Deletable
Event Enrollment
File
Multi-state Output
Multi-state Value
Notification Class
Schedule
Trend Log
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 5
Object AttributesObject AttributesObject AttributesObject Attributes O
OO
O indicates that the property is optional, per the BACnet standard.
R
RR
R indicates that the property is required to be present and readable using BACnet services.
Yes indicates that the property is
indicates that the property is indicates that the property is
indicates that the property is required to be present, readable, and writable using BACnet services.
to be present, readable, and writable using BACnet services. to be present, readable, and writable using BACnet services.
to be present, readable, and writable using BACnet services.
Object Types and Supported Properties
Analog Input Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component AI Present_Value Yes w REAL
Description Yes w Limited to 16 chars
Device_Type Yes Text corresponding to the Apogee LAI sensor type as follows: current voltage pneumatic 100k Thermistor 1K Platinum RTD LType custom
Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.
Event_State Yes If point is in alarm, then Event_State = OFFNORMAL, else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.
Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.
Out_Of_Service Yes w Must be set to override Present_Value
Units Yes Uses BACnet enumeration corresponding to fixed engineering units strings
Resolution Yes Slope
COV_Increment Yes w COV Limit
Time_Delay Alarm
Notification Class Alarm w
High_Limit Alarm w High Limit
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10-6
Property Identifier Support Access Notes
Low_Limit Alarm w Low Limit
Deadband Alarm w
Limit_Enable Alarm If alarming enabled, then low_limit and high_limit both enabled
Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE
Acked_Transitions Alarm
New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Notify_Type Alarm w
Event_Time_Stamps Alarm
New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Analog Output Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component AO Present_Value Yes w REAL
Description Yes w Limited to 16 chars
Device_Type Yes Associated Apogee Point type
Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name..
Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.
Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.
Out_Of_Service Yes Always FALSE
Units Yes Uses BACnet enumeration corresponding to fixed engineering units strings
Resolution Yes Slope
Priority_Array Yes For commanding the present value
Relinquish_default Yes For releasing the present value when the Priority Array is empty.
COV_Increment Yes w COV Limit
Analog Input Object Type, continued
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 7
Object Types and Supported Properties, continued
Analog Output Object Type, continued
Time_Delay Alarm
Notification Class Alarm w
High_Limit Alarm w High Limit
Low_Limit Alarm w Low Limit
Deadband Alarm w
Limit_Enable Alarm If alarming enabled, then low_limit and high_limit both enabled
Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE
Acked_Transitions Alarm
New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Notify_Type Alarm w
Event_Time_Stamps Alarm
New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10-8
Object Types and Supported Properties, continued
Analog Value Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component AV Present_Value Yes w REAL
Description Yes w Limited to 16 chars
Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.
Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.
Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.
Out_Of_Service Yes Always FALSE
Units Yes Uses BACnet enumeration corresponding to fixed engineering units strings
Priority_Array Yes For commanding the present value
Relinquish_default Yes For releasing the present value when the Priority Array is empty.
COV_Increment Yes w COV Limit
Time_Delay Alarm
Notification Class Alarm w
High_Limit Alarm w High Limit
Low_Limit Alarm w Low Limit
Deadband Alarm w
Limit_Enable Alarm If alarming enabled, then low_limit and high_limit both enabled
Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE
Acked_Transitions Alarm
New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Notify_Type Alarm w
Event_Time_Stamps Alarm
New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 9
Object Types and Supported Properties, continued
Binary Input Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component BI Present_Value Yes w Binary Value
Description Yes w Limited to 16 chars
Device_Type Yes Associated Apogee Point type
Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.
Event_State Yes If point is in alarm, then Event_State = OFFNORMAL, else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.
Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.
Out_Of_Service Yes w Must be set in order to override the Present_Value
Polarity Yes Normally Closed
Inactive_Text Yes Correspond with first entry in the points State Text Table
Active_Text Yes Correspond with second entry in the points State Text Table
Elapsed_Active_Time Yes w Totalization
Time_Of_ Active_Time_Reset
Yes Totalization_Reset_Time
Time_Delay Alarm
Notification Class Alarm w
Alarm_Value Alarm Specifies what the present_value is when the point is in Alarm.
Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE
Acked_Transitions Alarm
New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Notify_Type Alarm w
Event_Time_Stamps Alarm
New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10-10
Object Types and Supported Properties, continued
Binary Output Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component BO Present_Value Yes w Binary Value
Description Yes w Limited to 16 chars
Device_Type Yes Associated Apogee Point type
Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.
Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.
Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.
Out_Of_Service Yes Always FALSE
Polarity Yes Inverted
Inactive_Text Yes Correspond with first entry in the points State Text Table
Active_Text Yes Correspond with second entry in the points State Text Table
Elapsed_Active_Time Yes w Totalization
Time_Of_ Active_Time_Reset
Yes Totalization_Reset_Time
Priority_Array Yes For commanding the present value
Relinquish_default Yes For releasing the present value when the Priority Array is empty.
Time_Delay Alarm Proof Delay Notification Class Alarm w
Feedback_Value Alarm Current value of the proof point for Apogee proof points, set equal to the Present_Value for points without proofing.
Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE
Acked_Transitions Alarm
New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Notify_Type Alarm w
Event_Time_Stamps Alarm
New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 11
Object Types and Supported Properties, continued
Binary Value Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component BV Present_Value Yes w Binary Value
Description Yes w Limited to 16 chars
Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.
Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.
Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.
Out_Of_Service Yes Always FALSE
Inactive_Text Yes Correspond with first entry in the points State Text Table
Active_Text Yes Correspond with second entry in the points State Text Table
Elapsed_Active_Time Yes w Totalization
Time_Of_ Active_Time_Reset
Yes Totalization_Reset_Time
Priority_Array Yes For commanding the present value
Relinquish_default Yes For releasing the present value when the Priority Array is empty.
Time_Delay Alarm Proof Delay Notification Class Alarm w
Alarm_Value Alarm Specifies what the present_value is when the point is in Alarm.
Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE
Acked_Transitions Alarm
New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Notify_Type Alarm w
Event_Time_Stamps Alarm
New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10-12
Object Types and Supported Properties, continued
Calendar Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component CA Description Yes w Limited to 16 chars
Present_Value Yes Binary Value, True if today is in the calendar.
Date_List Yes w Single Dates, Date Ranges, and WeekNDays
Command Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component CO Description Yes w Limited to 16 chars
Present_Value Yes w Unsigned value, similar to a mode point, triggers one of many action lists
In_Process Yes True during the time the action list is being executed
All_Writes_Successful Yes True if all commands in last action list run were executed without error
Action Yes w The array of Action Lists
Action _Text Yes w The array of Names for the Action Lists
Device Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Configured in IP Settings Object_Name Yes Field Panel Name, limited to 30 chars, Configured in IP
Settings
Object_Type Yes Encoded name component BACDev System_Status Yes OPERATIONAL status used to set Ready status
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 13
Object Types and Supported Properties, continued
Device Object Type, continued
Vendor_Name Yes "Siemens BAU"
Vendor_Identifier Yes All Siemens ISA devices = 7
Model_Name Yes "Siemens BACnet EMEC"
Firmware_Revision Yes Firmware Rev String for example, "BCE V3.0 Apogee
Application_Software_Version Yes Firmware Rev String for example, "BCE3001
Location Yes limited to 40 chars, Configured in IP Settings
Description Yes limited to 40 chars, Configured in IP Settings
Protocol_Version Yes 1
Protocol_Revision Yes 4
Protocol_Services_Supported Yes See section 7.3.2 for list of services supported
Protocol_Object_Types _Supported
Yes See section 7.1.1 for list of objects supported
Object_List Yes List of object Ids for all points in this field panel ! Max_APDU_Length_Accepted Yes 1497
Segmentation_Supported Yes BACNET_SEGMENTATION_TYPE_BOTH
Max_Segments_Supported Yes 32
Local_Time Yes Field Panel Time
Local_Date Yes Field Panel Date
Daylight_Savings_Status Yes
APDU_Segment_Timeout Yes 3000
APDU_Timeout Yes 3000
Number_Of_APDU_Retries Yes 3
Device_Address_Binding Yes
Database_Revision Yes Logical revision number for the database, incremented when objects are created and/or deleted, an object's name is changed, or a database restore is performed.
Configuration_Files Yes List of files to be backed up. Valid only during the backup procedure.
Last_Restore_Time Yes Time of last file download. Applies only to BACnet file transfer services.
Backup_Failure_Timeout Yes w How long to wait before aborting a backup or restore operation.
Active_COV_Subscriptions Yes A list of active subscriptions. Applies to the server side.
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10-14
Object Types and Supported Properties, continued
File Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component FI Description Yes Limited to 16 chars
File_Type Yes
File_Size Yes w
Modification_Date Yes
Archive Yes w
Read_only Yes
File_Access_Method Yes
Multistate Output Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component MO Present_Value Yes w Unsigned
Description Yes w Limited to 16 chars
Device_Type Yes Associated Apogee Point type
Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.
Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.
Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.
Out_Of_Service Yes w
Number_Of_States Yes Correspond to size of State Text Table
State_Text Yes Corresponds with State Text Table
Priority_Array Yes For commanding the present value
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 15
Object Types and Supported Properties, continued
Multistate Output Object Type, continued
Property Identifier Support Access Notes Relinquish_default Yes For releasing the present value when the Priority Array is empty.
Time_Delay Alarm Proof Delay Notification Class Alarm w
Feedback_Value Alarm Current value of the proof point for Apogee proof points, set equal to the Present_Value for points without proofing.
Event_Enable Alarm w If alarming enabled, then to-offnormal, to-fault, and to-normal all set to TRUE
Acked_Transitions Alarm
New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Notify_Type Alarm Always = Alarm
Event_Time_Stamps Alarm
New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Multistate Value Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component MV Present_Value Yes w Unsigned
Description Yes w Limited to 16 chars
Status_Flags Yes IN_ALARM = true if point is in alarm, else false. FAULT = true if point is failed, else false. OVERRIDDEN = true if point is in hand mode, else false. OUT_OF_SERVICE = reflects the value of the property by the same name.
Event_State Yes If point is in alarm, then Event_State = OFFNORMAL , else if point is failed, then Event_State = FAULT, else Event_State = NORMAL.
Reliability Yes if point is failed, then Reliability = UNRELIABLE_OTHER, else Reliability = NO_FAULT_DETECTED.
Out_Of_Service Yes w
Number_Of_States Yes Correspond to size of State Text Table
State_Text Yes Corresponds with State Text Table
Priority_Array Yes For commanding the present value
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10-16
Object Types and Supported Properties, continued
Multistate Value Object Type, continued
Property Identifier Support Access Notes Relinquish_default Yes For releasing the present value when the Priority Array is
empty.
Time_Delay Alarm
Notification Class Alarm w
Alarm_Values Alarm
Fault_Values Alarm
Event_Enable Alarm w
Acked_Transitions Alarm
New. Indicates which of the transitions have been acknowledged, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Notify_Type Alarm w Always = Alarm
Event_Time_Stamps Alarm
New. Timestamps of the following event transitions, TO_OFFNORMAL, TO_FAULT, TO_NORMAL.
Notification Class Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component NC Description Yes w Limited to 16 chars
Notification_Class Yes Range is 0 to 4 meg, Automatically assigned, same as Object_Id
Priority Yes w
Ack_Required Yes w
Recipient_List Yes w
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 17
Object Types and Supported Properties, continued
Schedule Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component SC Present_Value Yes w REAL, Unsigned, Enum and BOOL
Description Yes w Limited to 16 chars
Effective_Period Yes w
Weekly_Schedule Yes w
Exception_Schedule Yes w
Schedule_Default Yes w
List_Of_Object_ Property_References
Yes w
Priority_For_Writing Yes w
Status_Flags Yes
Reliability Yes
Out_Of_Service Yes w
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10-18
Object Types and Supported Properties, continued
Trend Log Object Type
Property Identifier Support Access Notes
Object_Identifier Yes Range is 0 to 4 meg, Automatically assigned by default Object_Name Yes System Name, limited to 30 chars Object_Type Yes Encoded name component TL Description Yes w Limited to 16 chars
Log_Enable Yes w BOOL
Start_Time Yes w New BACnet only feature
Stop_Time Yes w New BACnet only feature
Log_DeviceObjectProperty Yes Always the Present Value property of a Point Log_Interval Yes Nonzero for byTime, Zero for by COV
Client_COV_Interval Yes
Stop_When_Full Yes w New BACnet only feature
Buffer_Size Yes
Log_Buffer Yes Accessed by Read Range service only
Record_Count Yes w
Total_Record_Count Yes
Notification_Threshold Alarm w Intrinsic reporting used to notify Insight that buffer is full.
Records_Since_Notification Alarm Intrinsic reporting used to notify Insight that buffer is full.
Last_Notify_Record Alarm Intrinsic reporting used to notify Insight that buffer is full.
Event_State Yes
Notification_Class Alarm w
Event_Enable Alarm
Acked_Transitions Alarm
Notify_Type Alarm w Always set to Event
Event_Time_Stamps Alarm
-
Siemens Industry, Inc. Building Technologies
Appendix B For Internal Use Only
10 - 19
Object Types and Supported Properties, continued
Data Link Layer Options
BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____________
MS/TP master (Clause 9), baud rate(s): MS/TP slave (Clause 9), baud rate(s): Point-To-Point, EIA 232 (Clause 10), baud rate(s): _________________ Point-To-Point, modem, (Clause 10), baud rate(s): _________________ LonTalk, (Clause 11), medium: _________________________________ Other: _____________________________________________________
Device Address Binding
Is Static Device Binding supported? Yes
Networking Options
Router, Clause 6 Annex H.3, BACnet Tunneling Router over UDP/IP
BACnet/IP Broadcast Management Device (BBMD) Yes Does the BBMD support registrations by Foreign Devices?
Supported Character Sets
ANSI X3.4 ISO 10646 (UCS-2) IBM/Microsoft DBCS ISO 10646 (ICS-4) ISO 8859-1 JIS C 6226