Copper Development Association K Rating of Transformers supplying Harmonic Rich Loads .
-
Upload
william-cooper -
Category
Documents
-
view
222 -
download
4
Transcript of Copper Development Association K Rating of Transformers supplying Harmonic Rich Loads .
Copper Development Association
Copper Development Association
K Rating of Transformers supplying Harmonic Rich Loads
www.cda.org.uk
Copper Development Association
Losses in Transformers
No-load loss (‘iron loss’)
– energy consumed in eddy current and hysteresis loss
– present 100% of the time
Load losses
Resistive loss (‘copper loss’)
– dependent on square of load current
– important only during peak load periods
Eddy current loss
Copper Development Association
Distribution transformer efficiency standards HD 428 (538)
Source: CENELEC
Load Losses for Distribution Transformers No-Load Losses for Distribution Transformers
RATED
POWER
OIL-FILLED (HD428) UP TO 24kV2) DRY TYPE
(HD538)
OIL-FILLED (HD428) UP TO 24kV2) DRY TYPE
(HD538)
LIST A LIST B LIST C 12kV
PRIMARY 3)
LIST A’ LIST B’ LIST C’ 12kV
PRIMARY 3)
kVA W W W W W W W W
50 1,100 1,350 875 N/A 190 145 125 N/A
100 1,750 2,150 1,475 2,000 320 260 210 440
160 2,350 3,100 2,000 2,700 460 375 300 610
250 3,250 4,200 2,750 3,500 650 530 425 820
400 4,600 6,000 3,850 4,900 930 750 610 1,150
630 /4%1) 6,500 8,400 5,400 7,300 1,300 1,030 860 1,500
630 /6% 6,750 8,700 5,600 7,600 1,200 940 800 1,370
1000 10,500 13,000 9,500 10,000 1,700 1,400 1,100 2,000
1600 17,000 20,000 14,000 14,000 2,600 2,200 1,700 2,800
2500 26,500 32,000 22,000 21,000 3,800 3,200 2,500 4,300
Copper Development Association
Full load losses in a 100kVA C-C’ transformer
12%
88%
Winding
Magnetic
Total loss = 1685 W
Copper Development Association
Full load losses in a 100kVA C-C’ transformer
79%
9%
12% Resistance
Magnetic
Eddy Current
Total loss = 1685 W
Copper Development Association
Transformers supplying harmonic loads must be appropriately de-rated.
Harmonic currents, being of higher frequency, cause increased magnetic losses in the core and increased eddy current and skin effect losses in the windings.
Triple-n harmonic currents circulate in delta windings, increasing resistive losses, operating temperature and reducing effective load capacity.
Effect of harmonics on transformers
Copper Development Association
Typical harmonic profile - six-pulse controller
Six pulse bridge - harmonic current
0
5
10
15
20
25
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Harmonic number
%
Copper Development Association
Increased Eddy current losses in transformers
2hh
1h
2hefeh hIPP
max
where: Peh is the total eddy current loss
Pef is the eddy current loss at fundamental frequencyh is the harmonic orderIh is the RMS current at harmonic h as a percentage of rated fundamental current
Increase in eddy current loss can be calculated by:
Copper Development Association
K-Rating of Transformers
Two rating or de-rating systems for transformers:-
• American system, established by UL and manufacturers, specifies harmonic capability of transformer - known as K factor.
• European system, developed by IEC, defines de-rating factor for standard transformers - known as factor K.
Copper Development Association
K-Rating of Transformers - US System
2hh
1h
2hhIK
max
where: h is the harmonic order Ih is the RMS current at h in per unit of rated load current
First, calculate the K factor of the load according to:
Copper Development Association
For this typical PC load, the K factor is 11.6
(See IEE 1100-1992 for a worked example)
K-Rating of Transformers - US System
Copper Development Association
Full load losses in a 100kVA C-C’ transformer
41%53%
6%
Resistance
Magnetic
Eddy Current
Total loss = 3245 W
Copper Development Association
K-Rating of Transformers - US System
Next, select a transformer with a higher K rating: standard ratings are 4, 9, 13, 20, 30, 40 and 50.
NB - for non K-rated transformers:
The K factor describes the increase in eddy current losses, not total losses.
Eddy current losses at the fundamental are normally around 10 % of the resistive losses, so that a load K factor of 11.6 would require de-rating to 70 % load.
Copper Development Association
K-Rating of Transformers - European System
In Europe, the transformer de-rating factor is calculated according to the formulae in BS 7821 Part 4. The factor K is given by:
5.0
2
2
1
2
1
11
Nn
n
nq
I
In
I
I
e
eK
e is ratio of eddy current loss (50 Hz) to resistive loss
n is the harmonic order
q is dependent on winding type and frequency, typically 1.5 to 1.7
Copper Development Association
K-Rating of Transformers - European System
For the same PC load, the de-rating factor is 78%
Copper Development Association
K Factor
0
2
4
6
8
10
12
14
16
1 2 5 10 20 41
No of Units (pairs)
K F
acto
r
Harmonic Diversity - K Factor
Copper Development Association
Full load losses in a 100kVA C-C’ transformer
41%53%
6%
Resistance
Magnetic
Eddy Current
Total loss = 3245 W
Copper Development Association
CP
PttempWorking
f
k 17393.190
102t
TtimeLife
yearsTtimeLife
f
fk
P
PPt
13.02402 3.8
10
Effect of additional losses on life-time
where T is working temperature at rated fundamental power, Pf,, Pk is the total power and T is the rated life-time in years
Copper Development Association
80% load losses in a 100kVA C-C’ transformer
39%51%
10%
Resistance
Magnetic
Eddy Current
Total loss = 2156 W
Copper Development Association
CP
PttempWorking
f
k 11528.190
102t
TtimeLife
yearsTtimeLife
f
fk
P
PPt
72402 5.2
10
Effect of additional losses on life-time
where T is working temperature at rated fundamental power, Pf,, Pk is the total power and T is the rated life-time in years
Copper Development Association
Full load losses in a 100kVA C-C’ transformer
51%41%
8%
Resistance
Magnetic
Eddy Current
Total loss = 2605 W
Copper Development Association
CP
PttempWorking
f
k 13955.190
102t
TtimeLife
yearsTtimeLife
f
fk
P
PPt
34.12402 9.4
10
Effect of additional losses on life-time
where T is working temperature at rated fundamental power, Pf,, Pk is the total power and T is the rated life-time in years
Copper Development Association
K-Rating or De-rating?
‘K-rated’ transformers are designed to supply harmonic
loads by :
• using stranded conductors to reduce eddy current
losses
• bringing secondary winding star point connections
out separately to provide a 300% neutral rating
Copper Development Association
‘De-rating’ a standard transformer has some disadvantages:-
primary over-current protection may be too high to protect the secondary and too low to survive the in-rush current future increases in loading must take the de-rating fully into account
it is less efficient the neutral star point is likely to be rated at only 100% of the phase current
K-Rating or De-rating?
Copper Development Association
Transformers supplying harmonic loads must be appropriately de-rated.
Harmonic currents, being of higher frequency, cause increased magnetic losses in the core and increased eddy current and skin effect losses in the windings.
Triple-n harmonic currents circulate in delta windings, increasing resistive losses, operating temperature and reducing effective load capacity.
Effect of harmonics on transformers
Copper Development Association
Effect of triple-n harmonics in transformers
Triple-n harmonic currents circulate in delta windings - they do not propagate back onto the supply network.
- but the transformer must be specified and rated to cope with the additional losses.