Since its’ launch in 2003, the VoCALL Emergency Voice

Communication System (EVCS) has been used in some

of the world’s most prestigious sites, from Wimbledon

AELTCC and St Pancras stations in the UK to the

Marina Towers and Jumeirah Tunnel in the Middle East.

VoCALL suits all sizes of installation from one and two outstationsystems in small shops like Bon Marche, to massive 364 line dualnetwork system at Westfield shopping centre in London’s White City.

Allied to the fully compliant hardware, Cooper also offer softwarepackages such as VoCALL Site Installer, allowing global configurationof the system from any exchange on the network, and the VoCALLReCALL, system, a real time incident and fault logging system, whichnot only logs faults and the start and end of call incidents, it recordsthe conversation as well.

The VoCALL

Emergency

Voice

Communication

Systems

Standards ComplianceDesigned from the outset to comply with BS5839 Pt9.

Scalable SolutionOutstations are common across the range and can be used on both compact and network solution.

Cable SavingBy utilising a star topology for compact systems and a ring and star topology for the network solution, outstations can be cabled inlow cost 2 core fire rated cables.

Space SavingBy distributing the network solution, no dedicated ‘comms’ room is required, and the exchanges can be located in risers or utility cupboards.

Highly IntegratedBy allowing designers to choose the outstation type and mix any type on a system, including emergency assistance alarms, all EVCSand disabled calls can be managed from a single control location, orin the case of the network solution up to 8 points.

Site ProvenWith thousands of sites since the launch in 2003 you can be sure of the systems reliability and longevity, all the firmware is flash™ based, making site upgrades to the latest version simple to implement to add the latest software features. T

he

Benefit

s

Page 3: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

3

Fire Telephones

Fire telephones are hardwired full duplex communications systemswith monitoring and battery backup, and are required in buildingsover 4 stories in many countries in the world (in the UK this isgoverned by BS9999). These are provided as a backup to traditionalfireman’s radio systems, which can fail to operate in many high riseenvironments due to the large amount of steel in the building, andthe “corona” effect of fire on radio broadcasts.

Fire telephones are also required in fire fighting lift lobbies whenthese lifts are provided within a building. Fire telephones can also beused for fire wardens to call the control point during fire drills andprimary evacuation phases before the fire services arrive andassume control.

Disabled Refuge Systems

Disabled refuge systems are required in the UK in all non domesticpremises over 1 story or where an emergency exit is by stairs (for afull description see building regulations approved document B). Adisabled refuge is a relatively safe area within a building or exitstaircase where mobility impaired occupants can be placed (not justwheelchair users) while the main building occupancy is evacuated,allowing building management and emergency services to safelyassist these people from the building when stairwell crowding haseased. Mobility impairment is defined as not being able to walk200m continuously without aid, and includes arthritis sufferers,people with leg and back injuries and women over 6 months termpregnancy. A disabled refuge system is not just for use during a fire,and must be available at all times.

Emergency Assist Alarm

An emergency assist alarm is defined in Building RegulationsApproved Document M, and must be provided at all disabled toiletswithin a non domestic premises, if the toilet is in a non permanentlyoccupied space, remote indication must be provided at a centralcontrol or monitoring point. An emergency assist alarm can only bereset by attending the location of the call, so the reset point is withinthe cubical, also allowing accidental calls to be cancelled by thetoilet occupier. The VoCALLemergency assist alarmsystem is powered from thelocal exchange or compactunit, and is fully monitoredover and above thespecification described inBS8300.T

he

Ove

rvie

w

Page 4: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

Page 17Roaming Handset and Jack PlateCFVCRHS and CFVCRJP

Page 19VoCall Emergency Assist Alarm KitCFVCEA

4

Contents VoCALL - Emergency Voice Communication System

Page 7 Compact 9 Line MasterExchange UnitCFVCCM9

Page 9Network 8 Line Exchange UnitCFVCX8

Page 13Type A HandsetCFVCSHP, CFVCFHP andCFVCIPA

Page 15Type B HandsetCFVCSHF, CFVCSHFG andCFVCSHFSS

Page 11Network Master HandsetCFVCM and CFVCWM

Page 5Compact 5 Line Exchange UnitCFVCC5

Page 5: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

VoCALL - Emergency Voice Communication System

5

Compact 5 Line Exchange Unit

Overview

The VoCAll compact 5 line exchange unit

(CFVCC5) is ideal for the smaller installations

which require just a limited number of

outstations and emergency assist alarms.

This system comprises of the 5 line exchange

unit and up to 5 outstations (type A, type B,

emergency assist alarms or in Far East and

Middle East applications jack plates). It

requires no programming and is simple to

install.

This VoCALL Emergency Voice CommunicationSystem (EVCS) is designed to fully comply withBS5839 Pt9 (abb. Pt9) for use as a fire telephonesystem, disabled refuge call system or as acombined system when both fire telephones anddisabled refuge points are required. The standardstates that were both systems are fitted to abuilding these should form a single system.

An EVCS is a fixed, monitored and maintained,bi-directional, full duplex voice communicationsystem to assist the orderly evacuation ofdisabled or mobility impaired people andenhance fire fighters communication duringemergencies.

Features

• BS5839 Pt9 compliant• Monitored handset• Monitored supply and charger• Up to 5 outstations• 5 line keys, 1 fault accept• 15 status LED’s• Full duplex system• Wall mount case

Benefits

• Simple cabling, outstations connect directly into the master using 2 core radial fire rated enhanced cables.

• In addition to type A and type B outstation the CFVCC5 can also monitor emergency assist alarms (using a 2 core radial).

• No programming required, panel is fitted with end of line resistors which are discarded when an outstation or emergency assist alarm is connected.

CFVCC5 - Compact 5 Line Exchange Unit

Page 6: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

6

VoCALL Compact 5 Line Exchange Unit - CFVCC5

Code CFVCC5

Description Compact 5 Line Exchange Unit

Standards EMC: EN55103-1 & EN55103-2.

Product Family: BS5839 Pt9 & BS9999

Power Supply

Voltage 230V ac +/- 10% 50/60Hz

Internal Power Supply 14V dc

Supply and Battery Monitored, open, short, fuses

Protection Deep discharge, short, thermal

Battery Size and Type 1 x 12V 5Ah

Mains Fuse 240V 2A HRC

Battery Fuse 1A PTC

Charge Current 250mA (max)

Inputs

Number of lines 5

Remote Enable Short to use

End of Line 1 10kΩ

Outputs

Number 2 (fault & in-use)

Type Volt free relay

Contact 30V dc 1A

Controls

Buttons 5 zone keys, 1 acknowledge

Zone LEDs (x5) 1 line status,1 fault status

Fault LEDs 3 (ac, dc & general)

Outstation Cables

Type Enhanced

Cores 2 Core (1mm or 1.5mm)

Distance 500m

Physical

Construction Powder Coated Zintec

Dimensions (H x W x D) 300mm x 350mm x 90mm

Weight 6.5kg

Technical SpecificationFull System Architecture

Code Description

CFVCC5 Compact 5 Line Exchange Unit

Product Codes

Control and Design

The VoCALL compact 5 line exchange unit(CFVCC5) is a self contained enclosure housinga master handset, 5 line exchange, powersupply, and battery charger. It can be surface orsemi-flush mounted as standard.

The case is made from powder coated zintec,with a smoked perspex door covering thehandset.

20mm cable knockouts are provided for allnecessary cables as well as space for thebackup 12V SLA battery.

The unit is microprocessor controlled, butrequires no programming on site; the panel isfitted with end of line resistors which are simplydiscarded when an outstation is connected.

Page 7: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

VoCALL - Emergency Voice Communication System

7

Compact 9 Line Master Exchange Unit

Overview

The VoCALL compact 9 line master exchange

unit (CFVCCM9) is ideal for small to medium

sized installations which don’t require the

complexity of a full network solution.

This system comprises of the 9 line master

exchange unit and up to 9 outstations (type A,

type B, emergency assist alarms or in Far East

and Middle East applications jack plates).

Using the 10 line slave exchange unit

(CFVCCS10) this system can be easily

expanded to 19 lines.

This VoCALL Emergency Voice CommunicationSystem (EVCS) is designed to fully comply withBS5839 Pt9 (abb. Pt9) for use as a fire telephonesystem, disabled refuge call system or as acombined system when both fire telephones anddisabled refuge points are required. The standardstates that were both systems are fitted to abuilding these should form a single system.

An EVCS is a fixed, monitored and maintained,bi-directional, full duplex voice communicationsystem to assist the orderly evacuation ofdisabled or mobility impaired people andenhance fire fighters communication duringemergencies.

Features

• BS5839 Pt9 compliant• EN54 Pt4:A2 power supply and charger

• 4 navigation keys• 6 status LED’s• 4 line, 20 character LCD• Full duplex system• Simple menu programming• Wall mount case

Benefits

• Up to 19 outstations, using 10 line slave exchange unit (CFVCCS10) the 9 line master exchange unit can be expanded up to 19 lines.

• In addition to type A and type B outstation the CFVCCM9 can also monitor emergency assist alarms (using a 2 core radial).

• 4 core is fire rated enhancedcable used to connect exchange unit to the slave.

CFVCCM9 - Compact 9 Line Master Exchange Unit

Page 8: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

8

VoCALL Compact 9 Line Master Exchange Unit - CFVCCM9

Code CFVCCM9

Description Compact 9 Line Master Exchange Unit

Standards EMC: EN55103-1 & EN55103-2

LVD: EN60950

Product Family: BS5839 Pt9 & BS9999

Power Supply

AC Input 230V ac +/- 10% 50/60Hz

Internal Supply 14V dc

Supply and Battery Monitored open, short, fuses

Protection Deep discharge, short thermal, impedence

Battery Type 1 x 12V VRSLA (7Ah required)

Mains Fuse 240V 1A HRC

Battery Fuse 250mA PTC

Charge Current 250mA

Inputs

Number of Lines 9

Remote Enable Short to use

Outputs

Number 2 (fault & in-use)

Type Volt free relay

Contact 30V dc 1A

Controls

Buttons 4 navigation keys

Display 4 lines, 20 characters

Status LED’s 3 (in-use, healthy & energised)

Fault LED’s 3 (line, PSU & general)

Outstation Cables

Type Enhanced

Cores 2 Core (1mm or 1.5mm)

Distance 500m

Physical

Construction Powder Coated Zintec

Dimensions (H x W x D) 300mm x 350mm x 90mm

Weight 6.5kg

Technical Specification

Code Description

CFVCCM9 Compact 9 Line Master Exchange UnitCFVCCS10 10 Line Slave Exchange Unit

Product Codes

Full System Architecture

Control and Design

The VoCALL compact 9 line master exchangeunit (CFVCCM9) is a self contained enclosurehousing a master handset, 9 line exchange,power supply, and battery charger. It can besurface or semi-flush mounted as standard.

The case is made from powder coated zintec,with a smoked perspex door covering thehandset.

20mm cable knockouts are provided for allnecessary cables as well as space for thebackup 12V SLA battery.

The unit is microprocessor controlled, withsimple menus, including a call log, fault log andchange log, all accessible from the front panelnavigation keys.

10 Line Slave

Exchange Unit

The 10 line slave exchangeunit (CFVCCS10) adds 10additional lines to the compact9 line master exchange unitgiving a total of 19 linesavailable on a system.

Page 9: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

VoCALL - Emergency Voice Communication System

9

Network 8 Line Exchange Unit

Overview

The VoCALL network 8 line exchange unit

(CFCVX8) is a small wall mounted unit which

can be distributed throughout a site and being

concealed from view in convenient locations

such places as rises, stairwells and cupboards.

Using this system greatly reduces the cabling

requirement and equipment ‘on view’ in such

key places as reception areas, making the

system aesthetically pleasing to the customer

as well reducing the cost of installation.

This VoCALL Emergency Voice CommunicationSystem (EVCS) is designed to fully comply withBS5839 Pt9 (abb. Pt9) for use as a fire telephonesystem, disabled refuge call system or as acombined system when both fire telephones anddisabled refuge points are required. The standardstates that were both systems are fitted to abuilding these should form a single system.

An EVCS is a fixed, monitored and maintained,bi-directional, full duplex voice communicationsystem to assist the orderly evacuation ofdisabled or mobility impaired people andenhance fire fighters communication duringemergencies.

Features

• Can control up to 8 independent monitored lines

• Built in monitored 1A charger for 12V SLA 5Ahbatteries

• 12 status LEDs• Dry contact for fault or ‘in-use’ indication

• Serial port for configuration or updates

• Dual network ports which provide power for the master handsets

• Full duplex system• Compact design

Benefits

• LED indication, for effective & easy fault finding.

• Fault or ‘in-use’ relay, can be connected to a fire panel or BMS.

• Global configuration, uploadinformation quickly via a PC using the serial port.

• Up to 32 distributed units onany network, no central exchange rack required.

CFVCX8 - Network 8 Line Exchange Unit

Page 10: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

10

VoCALL Network 8 Line Exchange Unit - CFVCX8

Code CFVCX8

Description Network 8 Line Exchange Unit

Standards EMC: EN55103-1 & EN55103-2

LVD: EN61000-3-2 & EN61000-3-3 & EN60950

Product Family: BS5839 Pt9 & BS9999 &

EN54 Pt4

Power Supply

Voltage 230V ac ± 20%

Current 11mA

Battery 12V SLA 5Ah

Charger 1A controlled impedance

Monitoring Open, short & high impedance cell

Outstation Cables

Grade Enhanced

Cable (per Leg) 1 off 2 core (twisted for MICC)

Distance (per Leg) 500M soft skin types, 300M MICC

Monitoring DC open, short & earth

Network Cables

Type Enhanced

Cores 1 off 4 pair (eg Draka 91-0245)

2 off 4 core 1mm CSA soft skin

4 off 1 pair MICC twisted

Distance 500M soft skin types, 300M MICC

Monitoring Data and phantom voltage

Indication & Controls

Fault LEDs 10 off yellow

(general, PSU, 8 lines)

Status LEDs 2 off green

(ac & dc)

Settings 8 way DIP switch

Physical

Construction Zintec, Texture Powder Coated, RAL 7032

Dimensions (H x W x D) 296mm x 210mm x 82mm

Weight 1.6kg

Technical Specification

Control and Operation

Each network 8 line exchange unit (CFVCX8) sitson a data highway and is locally powered, withinternal battery backup from a monitored,maintained sealed lead acid battery.

Up to 8 lines can be connected to eachdistributed exchange, and each line is fullymonitored for open, short or earth faults.

Up to 32 CFVCX8 exchange units can beattached to a VoCALL system giving a maximumsystem size of 256 independent lines.

The compact case is made from powder coatedzintec and is fitted with 20mm cable knockoutsfor all cables needed, and also provides spacefor the system backup 12V SLA battery.

Wiring

Using network communicationscombined with subscriber linetelephone techniques, aVoCALL provides large scalecable savings, while notrequiring a dedicated rackroom to house a centralexchange.

The network comprises a lineor ring of 8 cores, each leg canbe up to 500M depending oncable type.

A ring topology isrecommended by BS5839 Pt9.

Line cables consist of a single2 core enhanced cable, eithersoft skin types or MICC andonly 1mm CSA is required.

Code Description

CFVCX8 Network 8 Line Exchange UnitCFVCSI VoCALL Site Installer Software

Product Codes

Full System Architecture

VoCALL Site Installer Software

The VoCALL site installer software allows forglobal configuration of the system from anyexchange on the network.

Page 11: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

VoCALL - Emergency Voice Communication System

11

Network Master Handset

Overview

The VoCALL network master handset can be

either desk (CFVCM) or wall (CFVCWM)

mounted.

Each system can have up to 8 master handsets

which gives great flexibility to the larger

installations allowing all calls to be monitored

from various control points. As an example, an

installation may have security offices requiring

a master handset, reception and numerous

entrances that need to be monitored.

This VoCALL Emergency Voice CommunicationSystem (EVCS) is designed to fully comply withBS5839 Pt9 (abb. Pt9) for use as a fire telephonesystem, disabled refuge call system or as acombined system when both fire telephones anddisabled refuge points are required. Thestandard states that were both systems are fittedto a building these should form a single system.

An EVCS is a fixed, monitored and maintained,bi-directional, full duplex voice communicationsystem to assist the orderly evacuation ofdisabled or mobility impaired people andenhance fire fighters communication duringemergencies.

Features

• Up to 8 masters per system• Controls up to 256 Lines (32 CFVCX8 exchanges)

• Monitored handset• Large high contrast display (4 x 20 character)

• 12 key quick dial keypad• Full duplex system• Directory dial function• Full system event log (fault & configuration)

• 16 character unique name per line

• Dual network ports• Remote powered

Benefits

• Flexibility can be used as a fire telephone system, disabled refuge call system or as a combined system.

• Global configuration, wholesite can be configured fromthe master handset.

• Directory dialing, speed dial and conference calling

• All hail function makes testing the system simple.

CFVCWM - Network Master Handset, Wall Mounted

Page 12: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

12

VoCALL Network Master Handset - CFVCM / CFVCWM

Code CFVCM CFVCWM

Description Network Master handset, Desk Mount Network Master handset, Wall Mount

Standards EMC: EN55103-1 & EN55103-2 EMC: EN55103-1 & EN55103-2

Product Family: BS5839 Pt9 & BS9999 Product Family: BS5839 Pt9 & BS9999

Power Supply

Voltage 11V dc to 18V dc 11V dc to 18V dc

Current 88mA at 12V dc 88mA at 12V dc

Source Network port x 2 Network port x 2

Processing

Architecture AVR RISK AVR RISK

Clock 16MHz 16MHz

Memory 4K ram, 20K EEProm, 128K flash 4K ram, 20K EEProm, 128K flash

Monitoring 125mS asynchronous watchdog 125mS asynchronous watchdog

checksum on EEPROM & flash checksum on EEPROM & flash

Network Cables

Grade Enhanced Enhanced

Cable (per Leg) 1 off 4 pair (eg Draka 91-0245) 1 off 4 pair (eg Draka 91-0245)

2 off 4 core 1mm CSA soft skin 2 off 4 core 1mm CSA soft skin

4 off 1 pair MICC twisted 4 off 1 pair MICC twisted

Distance (per leg) 500M soft skin types, 300M MICC 500M soft skin types, 300M MICC

Monitoring Data and phantom voltage Data and phantom voltage

Indication & Controls

Fault LEDs 4 off yellow 4 off yellow

(general, panel, supply & exchange) (general, panel, supply & exchange)

Status LEDs 4 off green 4 off green

(healthy, ac, dc & network) (healthy, ac, dc & network)

LCD High contrast blue/white LCD High contrast blue/white LCD

4 line 20 character, 5 x 8 pixel format 4 line 20 character, 5 x 8 pixel format

Keyboard 12 key telephone style 12 key telephone style

Navigation 3 keys (down/left, accept, up/right) 3 keys (down/left, accept, up/right)

Physical

Construction Base: Brushed Stainless Steel Base: Brushed Stainless Steel

Lid: Zintec, Black Powder Coated Lid: Zintec, Black Powder Coated

Sides: Aluminium, Black Powder Coated Sides: Aluminium, Black Powder Coated

Dimensions (H x W x D) 268mm x 275mm x 85mm 300mm x 350mm x 90mm

Weight 6.5kg 6.5kg

Technical SpecificationFull System Architecture

Control and Design

The network master handset has a clear 4 linebacklit display which shows the callingoutstation name in plain text, and calls can bemade to outstations by either dialling thenumber of the unit, or choosing the name froma text dialling directory.

The case is made from stainless steel withextruded aluminium rails. 20mm cableknockouts are provided for all necessarycables.

Wiring

Using network communicationscombined with subscriber linetelephone techniques, a VoCALLnetwork provides large scalecable savings, while not requiringa dedicated rack room to housea central exchange.

The network comprises a line orring of 8 cores, each leg can beup to 500M depending on cabletype.

A ring topology is recommendedby BS5839 Pt9. In line with therecommendations of BS5839 Pt9multiple master handsets can befitted to a VoCALL network (up to8) with lockouts operating whena multiple consoles are in use.

Code Description

CFVCM Network Master Handset, Desk Mount CFVCWM Network Master Handset, Wall Mount CFVCRM 19” 6u Rack Mount Kit for CFVCM onlyCFVCLOG VoCALL ReCALL Logging and Recording Software

Product Codes

VoCALL ReCALL Software

The VoCALL ReCALL software is a real timeincident and fault logging system, which recordsthe start and end of any call, logs faults and anyconversations fully.

Page 13: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

VoCALL - Emergency Voice Communication System

13

Type A Handset

Overview

The VoCALL type A handset is a compact unit

which offers easy access via a magnetic push

catch door. The flush (CFVCFHP) mountable

unit offers a unique front levelling system

allowing the back box to be mounted at a

slight angle whilst still retaining a true front

face and door. A surface (CFVCSHP)

mountable unit is also available.

The type A handset is compatible with all

VoCALL systems for use as a standard fire

telephone or disabled refuge call point.

This VoCALL Emergency Voice CommunicationSystem (EVCS) is designed to fully comply withBS5839 Pt9 (abb. Pt9) for use as a fire telephonesystem, disabled refuge call system or as acombined system when both fire telephones anddisabled refuge points are required. Thestandard states that were both systems are fittedto a building these should form a single system.

An EVCS is a fixed, monitored and maintained,bi-directional, full duplex voice communicationsystem to assist the orderly evacuation ofdisabled or mobility impaired people andenhance fire fighters communication duringemergencies.

Features

• Compact design• High volume ringer• Status LED• Telecoil for hearing impaired users

• Full duplex operation• Magnetic push catch• Stainless steel option

Benefits

• Versatility, the unit can be used on all VoCALL systems.

• Dual use, the type A handset can be used as a fire telephone or a disabled refuge call point.

• Magnetic push catch, for quick and easy access.

CFVCSHP - Type A Handset, Surface / CFVCFHP - Type A Handset, Flush

Page 14: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

14

VoCALL Type A Handset - CFVCSHP / CFVCFHP / CFVCIPA

Code CFVCSHP CFVCFHP CFVCIPA

Description Type A Handset, Surface Mount Type A Handset, Flush Mount Type A Handset, Lockable Surface Mount

Standards EMC: EN55103-1 & EN55103-2 EMC: EN55103-1 & EN55103-2 EMC: EN55103-1 & EN55103-2

LVD: EN60950 LVD: EN60950 LVD: EN60950

Product Family BS5839 Pt9 & BS9999 & EN60118-4 Product Family BS5839 Pt9 & BS9999 & EN60118-4 Product Family BS5839 Pt9 & BS9999 & EN60118-4

Outstation Cables

Grade Enhanced Enhanced Enhanced

Cores 2 core 1mm or 1.5mm 2 core 1mm or 1.5mm 2 core 1mm or 1.5mm

Distance 500m 500m 500m

Physical

Construction Zintec, Powder Coated Zintec, Powder Coated Zintec, Powder Coated

Dimensions (H x W x D) 300mm x 150mm x 75mm 320mm (bezel) x 150mm x 75mm 300mm x 200mm x 120mm

295mm (backbox) x 150mm x 75mm

Weight 1400g 1400g 2500g

Technical Specification

Suitability

All type A handsets are defined in BS5839 Pt9,and can be used as a fire telephone or disabledrefuge call point.

When choosing the outstation type for use withan EVCS we recommend reading section 11 ofBS5839 Pt9 2011 which deals with outstationtypes, and states as follows:

11.1.a Type A handsets should be used for evacuationor fire fighting use, and a type B handsetsshould only be used where a type A handsetsare impractical.

11.1.b For disabled refuges type A or type B handsetscan be used, however in locations (section11.6.k) type B handsets can only be used wherethe background noise is below 40dBA (thereforethere can be no sounder or voice alarmcoverage in the area).

VoCALL handsets are designed for use by multi-disability users, having high contrast signage inline with RNIB guidelines and an induction loopcoil (to BSEN60118-4) in the handset.

It is recommend that a type A handset is used inmost locations, otherwise you may have toconsider acoustic hoods or 2 outstations in eachlocation for compliance with the otherassociated standards and laws, includingBS8300 and the Equality Act 2010.

Mounting The Unit

All type A handsets should be mounted at a heightof either 1200mm from the floor, or on a 1400mmcentre line to comply with the requirements ofBuilding Regulations Document M (Access for theDisabled).

CFVCSHP / CFVCIPA

The back box has 4 indented feet to allowmounting on uneven walls.

CFVCFHP

A cut out of 300mm x 160mm is recommended,the front bezel has adjustments to level the backbox on the wall.

If the units are to be used as a refuge pointsuitable space must be allowed to the side of theunit to allow a wheelchair to be parked for usingthe system.

Code Description

CFVCSHP Type A Handset, Surface Mount (Red)CFVCSHPSS Type A Handset, Surface Mount (Stainless Steel)CFVCFHP Type A Handset, Flush Mount (Red)CFVCFHPSS Type A Handset, Flush Mount (Stainless Steel)CFVCIPA Type A Handset, Lockable Surface Mount (Red)CFVCIPASS Type A Handset, Lockable Surface Mount (Stainless Steel)CFVCHFS Type A Handset, Uncased (for retro fit integration in to equipment)

Product Codes

75mm

150mm

300mm

1400mm*

75mm

155mm

295mm

1400mm*

180mm

320mm

Surface Mount

Flush Mount

* Unit mounting height from floor level.

Page 15: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

VoCALL - Emergency Voice Communication System

15

Type B Handset

Overview

The VoCALL type B handset is designed to be

versatile, compact and easy to use refuge call

point.

This unit can either be surface or flush mounted

using a simple to install bezel (CFVCFHB).

This VoCALL Emergency Voice CommunicationSystem (EVCS) is designed to fully comply withBS5839 Pt9 (abb. Pt9) for use as a fire telephonesystem, disabled refuge call system or as acombined system when both fire telephones anddisabled refuge points are required. The standardstates that were both systems are fitted to abuilding these should form a single system.

An EVCS is a fixed, monitored and maintained,bi-directional, full duplex voice communicationsystem to assist the orderly evacuation ofdisabled or mobility impaired people andenhance fire fighters communication duringemergencies.

Features

• Compact design• High volume ringer• Status LED• 20mm cable glands• Loop output for hearing impaired users

• Tactile braille signage• Full duplex operation• Flush bezel available• Stainless steel option

Benefits

• Versatility, the unit can be used on all the VoCALL systems.

• Full duplex operation, allowing 2 way voice communication.

• Tactile braille signage to assist partially sighted people to easily operate refuge point.

CFVCSHF / CFVCSHFG / CFVCSHFSS - Type B Handset

Page 16: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

16

VoCALL Type B Handset - CFVCSHF / CFVCSHFG / CFVCSHFSS

Technical Specification

Suitability

All type B handsets are defined in BS5839 Pt9,and can be used as a fire telephone or disabledrefuge call point.

When choosing the outstation type for use withan EVCS we recommend reading section 11 ofBS5839 Pt9 2011 which deals with outstationtypes, and states as follows:

11.1.a Type A handsets should be used for evacuationor fire fighting use, and a type B handsetsshould only be used where a type A handsetsare impractical.

11.1.b For disabled refuges type A or type B handsetscan be used, however in locations (section11.6.k) type B handsets can only be used wherethe background noise is below 40dBA (thereforethere can be no sounder or voice alarmcoverage in the area).

VoCALL type B handsets are designed for useby multi-disability users, having high contrastsignage in line with RNIB guidelines and asocket for an external induction loop amplifier ifrequired.

Mounting The Unit

All type B handsets should be mounted at a heightof either 1200mm from the floor, or on a 1400mmcentre line to comply with the requirements ofBuilding Regulations Document M (access for thedisabled).

The back box has 4 indented feet to allowmounting on uneven walls.

Type B handsets can be flush mounted by cuttinga hole 133mm x 133mm and 45mm deep, andusing the stainless steel bezel (CFVCFHB) to finishthe surround.

Code Description

CFVCSHF Type B Handset, Surface Mount (Red)CFVCSHFG Type B Handset, Surface Mount (Green)CFVCSHFSS Type B Handset, Surface Mount (Stainless Steel)CFVCFHB Flush Mounting Bezel (Stainless Steel)

Product Codes

45mm

133mm

133mm

1400mm*

Code CFVCSHFG CFVCSHF CFVCSHFSS

Description Type B Handset, Surface Mount Type B Handset, Surface Mount Type B Handset, Surface Mount

Standards EMC: EN55103-1 & EN55103-2 LVD: EN60950 EMC: EN55103-1 & EN55103-2 LVD: EN60950 EMC: EN55103-1 & EN55103-2 LVD: EN60950

Product Family BS5839 Pt9 & BS9999 & EN60118-4 Product Family BS5839 Pt9 & BS9999 & EN60118-4 Product Family BS5839 Pt9 & BS9999 & EN60118-4

Outstation Cables

Grade Enhanced Enhanced Enhanced

Cores 2 core 1mm or 1.5mm 2 core 1mm or 1.5mm 2 core 1mm or 1.5mm

Distance 500m 500m 500m

Indications & Controls

Status LEDs 2 off red (ashes location lights, solid in use) 2 off red (ashes location lights, solid in use) 2 off red (ashes location lights, solid in use)

Call Press to call button Press to call button Press to call button

Cancel Press to cancel button Press to cancel button Press to cancel button

Physical

Construction Zintec, Powder Coated Zintec, Powder Coated Zintec, Powder Coated

Colour Option Green Red Stainless Steel

Dimensions (H x W x D) 133mm x 133mm x 45mm 133mm x 133mm x 45mm 133mm x 133mm x 45mm

Weight 1105g 1105g 1105g

* Unit mounting height from floor level.

Page 17: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

17

VoCALL - Emergency Voice Communication System

Roaming Handset and Jack Plate

Overview

The roaming handset (CFVCRHS) is used along

with the jack plate (CFVCRJP) for emergency

voice communication system installations in

countries whose fire codes allow for roaming

handsets (these units are not suitable for

installation in the UK under BS5839 Pt9).

When used together the roaming handset and

jack plate form a type A handset which is

compatible with all VoCALL systems

This VoCALL Emergency Voice CommunicationSystem (EVCS) is designed to fully comply withBS5839 Pt9 (abb. Pt9) for use as a fire telephonesystem, disabled refuge call system or as acombined system when both fire telephones anddisabled refuge points are required. The standardstates that were both systems are fitted to abuilding these should form a single system.

An EVCS is a fixed, monitored and maintained,bi-directional, full duplex voice communicationsystem to assist the orderly evacuation ofdisabled or mobility impaired people andenhance fire fighters communication duringemergencies.

Features

• Flexible roaming phone• Low noise high quality telephone jack

• Telecoil for hearing impaired users

• Full duplex operation• Stainless steel jack plate

Benefits

• The jack plate can be surface or flush mounted.

• Full duplex operation, allowing 2 way voice communication.

CFVCRHS - Roaming Handset / CFVCRJP - Jack Plate

Page 18: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

18

VoCALL Roaming Handset and Jack Plate - CFVCRHS / CFVCRJP

Code CFVCRHS

Description Roaming Handset

Standards EMC: EN55103-1 & EN55103-2

LVD: EN60950

Controls

Call Automatic “Off Hook” dialing

Connection

Jack 1/4” mono neutrik heavy duty

Physical

Construction ABS UL90V1

Dimensions (H x W x D) 210mm x 66mm x 45mm

Weight 700g

Technical Specification

Suitability

The roaming handset (CFVCRHS) and jack plate(CFVCRJP) are suitable for EVCS installations incountries whose fire codes allow for roaminghandsets, this is not suitable for installation inthe UK under BS5839 Pt9.

Code Description

CFVCRJP Jack PlateCFVCRHS Roaming Handset

Product Codes

Mounting The Unit

The jack plate (CFVCRJP) should be mounted ata height of either 1200mm from the floor, or on a1400mm centre line to comply with therequirements of Building Regulations DocumentM (access for the disabled).

The jack plate fits on to a standard MK styleback box (not supplied) and can be flush orsurface mounted.

25mm

86mm

86mm

1400mm*

Code CFVCRJP

Description Jack Plate

Cables

Grade Enhanced

Cores 2 core 1mm or 1.5mm

Distance 500M

Monitoring dc open, short and earth

End Of Line 10K 1/4 W

Physical

Construction Brushed Stainless Steal

Dimensions (H x W x D) 86mm x 86mm x 25mm

Weight 140g

Technical Specification

Jack Plate

Roaming Handset

Jack Plate

* Unit mounting height from floor level.

Page 19: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

VoCALL - Emergency Voice Communication System

19

VoCALL Emergency Assist Alarm Kit

Overview

It has now become very common for the

disabled toilet to be specified as part of the

refuge system.

The CFVCEA has been specifically designed to

integrate disabled call functions into the

VoCALL network or VoCALL compact ranges

providing the perfect solution for conformity

with the Building Regulations Document M and

Equality Act 2010.

Disabled toilet alarms are required by BuildingRegulation Document M, and by integrating itwith the Emergency Voice CommunicationSystem all calls relating to disabledcommunications can be displayed in a singlepoint.

The CFVCEA solution is fully monitored andbattery backed by the VoCALL system, savinglocal power supplies and giving confidence inthe system integrity.

The CFVCEA shows up as a call on the VoCALLsystem, but has no speech path so aconversation cannot be had with the occupant,use of the type B outstations would allow this.

Features

• Monitored to BS5839 Pt9• Remote powered from VoCALL exchange

• Dual loop pull cord• High contrast labels• Braille on cancel plate• Blue indication

Benefits

• Saving power, no PSU is required remote powered by VoCALL system.

• One install saves running 2 separate systems.

• One location all calls from disabled toilets and refuge points monitored from one location.

• Tactile braille signage to assist partially sighted people to easily operate thecancel plate.

CFVCEA - VoCALL Emergency Assist Alarm Kit

Coming soon2012

Page 20: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

20

VoCALL Emergency Assist Alarm Kit - CFVCEA

Code Description

CFVCEA VoCALL Emergency Assist Alarm Kit(1x Over Door Indicator, 1x Cancel Button, 1x Pull Cord Unit, 1x Disabled Sticker)

CFEAPULLKIT Emergency Assist Alarm, Stand Alone Kit(1x Power Supply Unit, 1x Over Door Indicator, 1x Cancel Button,1x Pull Cord Unit, 1x Disabled Sticker)*

Product Codes

Over Door Indicator

Cancel Button

Pull Cord Unit

+-

+-

VoCallExchange

12V +-

+-

+-+

-

Over DoorIndicator

CancelUnit

Pull Cord Unit

OUT IN

VoCALL Exchange Over Door IndicatorOver Door Indicator Cancel UnitCancel Unit Pull Cord Unit

Wiring Guide Using 2 Core Cable

Code CFEAODI

Description Over Door Indicator

Specification

Operating Voltage 12V dc (nominal)

Physical

Construction PC

Dimensions (mm) H 87 x W 87 x D 31.5

Technical Specification

Code CFEARSP

Description Cancel Button

Specification

Operating Voltage 12V dc (nominal)

Physical

Construction PC

Dimensions (mm) H 87 x W 87 x D 25

Technical Specification

Code CFEAPULL

Description Pull Cord Unit

Specification

Operating Voltage 12V dc (nominal)

Physical

Construction PC

Dimensions (mm) H 87 x W 87 x D 30.5 (+cord)

Technical Specification

VoCALL Emergency Assist Alarm Kit

Also available

* For further information see www.cooperfire.com

Page 21: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

Emergency Assist Alarm

21

Emergency Assist Alarm, Stand Alone Kit

Overview

The emergency assist alarm, stand alone kit

(CFEAPULLKIT) provides the perfect solution

for conformity with the Building Regulations

Document M and Equality Act 2010.

This is a simple 2 wire system that has beenspecifically designed to meet the needs ofdisabled service users and conforms to all therelevant requirements; Disability RightsCommission code of practice, English TourismCouncil Recommendations and RNIB signageguidelines.

The use of combined high output blue LEDindication and buzzer ensures a response to thecall.

The emergency assist alarm, stand alone kit(CFEAPULLKIT) comprises of all thecomponents needed to install a fully compliantsystem, with additional parts availableseparately.

Features

• Complies with regulations & recommendations

• Dual loop pull cord• High contrast labels• Blue indication

Benefits

• Quick and simple installation, with limited cabling requirements.

• High contrast printing for increased visibility.

• Tactile braille signage to assist partially sighted people to easily operate thecancel plate.

CFEAPULLKIT - Emergency Assist Alarm, Stand Alone Kit

Page 22: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

22

Emergency Assist Alarm, Stand Alone Kit - CFEAPULLKIT

Code Description

CFEAPULLKIT Emergency Assist Alarm, Stand Alone Kit(1x Power Supply Unit, 1x Over Door Indicator, 1x Cancel Button,1x Pull Cord Unit, 1x Disabled Sticker)

CFEAPSU Emergency Assist Alarm Power Supply UnitCFEAODI Emergency Assist Alarm Over Door IndicatorCFEARSP Emergency Assist Alarm Cancel ButtonCFEAPULL Emergency Assist Alarm Pull Cord UnitCFEACORD Emergency Assist Alarm Pull Cord Accessory PackCFEASDS Emergency Assist Alarm Disabled Sticker (pack of 5)

Product Codes

Code CFEAPSU

Description Power Supply Unit

Specification

Mains 230V ac +10% -15%

Output 12V dc (nominal)

Physical

Construction PC

Dimensions (mm) H 146 x W 86 x D 39

Technical Specification

Code CFEAODI

Description Over Door Indicator

Specification

Operating Voltage 12V dc (nominal)

Physical

Construction PC

Dimensions (mm) H 87 x W 87 x D 31.5

Technical Specification

Power Supply Unit

Over Door Indicator

Cancel Button

Code CFEARSP

Description Cancel Button

Specification

Operating Voltage 12V dc (nominal)

Physical

Construction PC

Dimensions (mm) H 87 x W 87 x D 25

Technical Specification

Pull Cord Unit

Code CFEAPULL

Description Pull Cord Unit

Specification

Operating Voltage 12V dc (nominal)

Physical

Construction PC

Dimensions (mm) H 87 x W 87 x D 30.5 (+cord)

Technical Specification

+-

+-

Power Supply

12V +-

+-

+-+

-

Over DoorIndicator

CancelUnit

Pull Cord Unit

OUT IN

PSU 12V supply Over Door IndicatorOver Door Indicator Cancel UnitCancel Unit Pull Cord Unit

Wiring Guide Using 2 Core CableVoCALL Emergency Assist Alarm Kit

Page 23: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

Emergency Assist Alarm

23

4 Way Splitter Unit

Overview

The 4 way splitter unit CFEASL4 allows up to 4

stand alone disabled toilets to be monitored in

one specific area.

Staff can then at the designated area such as areception or security desk react to an alarmswiftly and efficiently.

Features

• Designed to comply with allregulations and recommendations

• High visibility• More than one 4 way splitter can be used

• Small compact design

Benefits

• Up to 4 disabled toilets monitored in one area

• Uses blue LEDs to avoid confusion

• Visibility to remote staffed areas

• No mains or PSU required at each disabled toilet

CFEASL4 - 4 Way Splitter Unit

Page 24: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

24

4 Way Splitter Unit - CFEASL4

Code Description

CFEASL4 Emergency Assist Alarm 4 Way Splitter Unit

Product Codes

Wiring Guide Using 2 Core Cable

Power Supply

12V +-

+-

+-

+-

+-

Over DoorIndicator

CancelUnit+

-

Pull Cord Unit

4 WaySlave Unit

+-

+-

+-

+-

+-

Over DoorIndicator

CancelUnit+

-

Pull Cord Unit

+-

+-

+-

+-

Over DoorIndicator

CancelUnit+

-

Pull Cord Unit

+-

+-

+-

+-

Over DoorIndicator

CancelUnit+

-

Pull Cord Unit

Page 25: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

25

Part Code Description Page Number

CFEACORD Emergency Assist Alarm Pull Cord Accessory Pack 19/21

CFEAODI Emergency Assist Alarm Over Door Indicator 19/21

CFEAPSU Emergency Assist Alarm Power Supply Unit 19/21

CFEAPULL Emergency Assist Alarm Pull Cord Unit 19/21

CFEAPULLKIT Emergency Assist Alarm, Stand Alone Kit 21

CFEARSP Emergency Assist Alarm Cancel Button 19/21

CFEASDS Emergency Assist Alarm Disabled Sticker (pack of 5) 19/21

CFEASL4 Emergency Assist Alarm 4 Way Splitter Unit 23

CFVCC5 Compact 5 Line Exchange Unit 5

CFVCCM9 Compact 9 Line Master Exchange Unit 7

CFVCCS10 10 Line Slave Exchange Unit 7

CFVCEA VoCALL Emergency Assist Alarm Kit 19

CFVCFHB Flush Mounting Bezel (Stainless Steel) 15

CFVCFHP Type A Handset, Flush Mount (Red) 13

CFVCFHPSS Type A Handset, Flush Mount (Stainless Steel) 13

CFVCHFS Type A Handset, Uncased (for retro fit integration in to equipment) 13

CFVCIPA Type A Handset, Lockable Surface Mount (Red) 13

CFVCIPASS Type A Handset, Lockable Surface Mount (Stainless Steel) 13

CFVCLOG VoCALL ReCALL Logging and Recording Software 11

CFVCM Network Master Handset, Desk Mount 11

CFVCRHS Roaming Handset 17

CFVCRJP Jack Plate 17

CFVCRM 19” 6u Rack Mount Kit for CFVCM only 11

CFVCSHF Type B Handset, Surface Mount (Red) 15

CFVCSHFG Type B Handset, Surface Mount (Green) 15

CFVCSHFSS Type B Handset, Surface Mount (Stainless Steel) 15

CFVCSHP Type A Handset, Surface Mount (Red) 13

CFVCSHPSS Type A Handset, Surface Mount (Stainless Steel) 13

CFVCSI VoCALL Site Installer Software 9

CFVCWM Network Master Handset, Wall Mount 11

CFVCX8 Network 8 Line Exchange Unit 9

Index Emergency Voice Communication System

Page 26: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

26

Over the last 6 years Cooper VoCALL and voice alarm products have been installed on

several very high profile projects, the following is a small sample of these.

Major Projects

Wimbledon AELTCC

Supplied and commissioned a sitewide fire telephone and disabledrefuge system with over 130 points,complete with audio recording andlogging software so the police canreview any incidents.

55 Broadway and Albany

House, London

Supplied and commissioned a touchscreen voice alarm and fire telephonesystem for the buildings which houseLondon Underground’s Headquartersand British Transport Police HQ.

Dublin Airport Terminal 2

Supplied a fully distributed fibre opticvoice alarm system, the disabledrefuge and fire telephone system andthe various disabled toilet alarmsystem.

3 and 4 More London

Supplied and commissioned the voicealarm and the fire telephone systemsfor More 3 and 4 buildings which arepart of the More London Estate,beside the Mayors building on theSouth Bank of the Thames.

WimbledonAELTCC

Albany House,London

Page 27: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

27

St Pancras Station, London

Supplied Ashford, Stratford andEbbsfleet stations, with disabled refugesystems for the Channel TunnelExtension. Following the installationNetwork Rail Approval was granted.

Westfield Shopping Centre,

White City, London

Supplied and commissioned twonetworks of disabled refuge and firetelephones with over 300 points withmaster controls in both the fire andsecurity control rooms.

Nuclear Power Station,

Hartlepool

Supplied and commissioned a dual ringfibre optic linked voice alarm systemcovering the whole site, additional dualredundancy features were added withspecial microphones for the SimulatorTraining Suite.

Jumeirah Road Tunnel, ME

Linking the Palm Islands to mainlandDubai, Cooper VoCALL productssupplied the emergency telephonesystem in special stainless steel IP66enclosures.

Centre Parcs, Elveden

Supplied and commissioned thenetworked voice alarm system for thevillage centre, following its reconstructionafter fire destroyed the original building. Westfield Shopping

Centre, White City

St Pancras Station

Page 28: Cooper Fire · PDF filewith monitoring and battery backup, and are required in buildings over 4 stories in many countries in the world ... VoCALL - Emergency Voice Communication System

The trade names and brand names contained herein are valuable trademarks of Cooper Industries in the U.S. and other countries. You are not permitted to use theCooper Trademarks without the prior written consent of Cooper Industries.

Cooper Industries plc600 Travis, Suite 5600Houston, TX 77002 - 1001T: 713 - 209 - 8400www.cooperindustries.com

Sales

T: +44 (0)1302 303 999F: +44 (0)1302 303 333E: [email protected]

Technical and Quotations

T: +44 (0)1302 303 350F: +44 (0)1302 303 332E: [email protected]

Service

T: +44 (0)1302 303 352F: +44 (0)1302 303 332E: [email protected]

Export

T: +44 (0)1302 303 344F: +44 (0)1302 303 345E: [email protected]

Cooper Safety Fire Systems

Cooper Lighting and Safety LtdWheatley Hall RoadDoncasterSouth YorkshireDN2 4NBUnited Kingdom

www.cooperfire.com

Conditions of sale

All goods supplied are subject to the company’s general conditions of sale which are available on request.

Trade Descriptions

All descriptions represent only particulars of the goods to which they apply and do not form part of any contract. Thecompany reserves the right to change specification without prior notification or public announcement.

®2011 Cooper Lighting and SafetyAll rights reserved.

Publication reference: CFS0044-C-EVCSRevision reference: R1

Abu Dhabi

P.O. Box 53234, KaramaVilla 4 opp. Govt. Dept. SportsAssociation, Sector 2-17Street 6 (off Delma St No. 13)Abu Dhabi UAET: +971 2 446 6840F: +971 2 446 6841

Dubai

PO Box 30861Suite 302, Building 49Dubai Healthcare CityDubaiUnited Arab EmiratesT: +971 4427 2500F: +971 4429 8521

Egypt

1169, Ministries SquareSheraton Helipolis AreaBuilding 1, CairoEgyptT: +202 2269 1134F: +202 2269 1135

Qatar

Office No. 237, 2nd Floor Building No. 81, 'D' Ring RoadOld Airport AreaP.O. Box 55582DohaQatarT: +974 5515 9948

Saudi Arabia

P.O. Box 63153rd Floor Kaki Centre, Office 203Tahlia Street (opposite IKEA)21442 JeddahKSAT: +966 2668 7703F: +966 2663 6552

Australia

Cooper Industries AustraliaP.O. Box 2577205 – 209 Woodpark RoadSmithfield, N.S.W. 2164AustraliaT: +02 8787 2777F: +02 9609 2342

China

Cooper Electric (Shanghai) Co, Ltd.3F, 9th Building, No. 6101Longdong AvenueEast Area of ZhangjiangHigh Tech Park, PudongShanghaiChina 201201T: + 86 21 6891 9988

India

Cooper India Pvt. Ltd.DLF Cyber CityBuilding 10A, Ground FloorSector 25, Gurgaon – 122002IndiaT: +91 124 468 3888

Vietnam

Cooper Industries VietnamF4.1, 39 NguyenThi Dieu St, ward 6Dist. 03, Ho Chi Minh CityVietnamT: +848 6290 9639F: +848 6290 6549

Cooper Middle East