Construction Details5. Construction Details
Construction Details
OV
ER
LA
P M
INIM
UM
2'-0
"
VERTICAL REINFORCEMENT (AMOUNT AND SAPCING PER STRUCTURAL DESIGN )
CONTEC AAC BLOCK WALL
MORTAR LEVELINGBED (TYPE M)
FINISH
CONTEC AAC O.BLOCKFILLED WITH GROUT
CONCRETE
EXTERIOR WALL TYPICAL DETAIL
MAS-01
BENT BAR
DPC (DAMP PROOF. COURSE)(IF REQUIRED)
GRADE8"
FOUNDATION
5-1
Co
nstru
ction
Details
VERTICAL REINFORCEMENT AT WALL INTERSECTION
MAS-11
REINFORCEMENT(CONTINUOUS)
(PER STRUCTURAL DESIGN)
SET #5 CONTINUOUS VERTICAL REINFORCEMENT,LAP 2' MIN. FILLED WITH 3000 psiCONCRETE.
CONTEC AAC O - BLOCK
CL
CL
COREFILLED WITH 3000 psiCONCRETE
5-2
Co
nstru
ction
Details
CONTEC AAC LINTEL
CONTEC AAC BLOCK WALL
CONTEC NAIL OR ANCHOR
EXTERIOR FINISH
CONTEC NAIL OR ANCHOR
WINDOW
WINDOW DETAIL
MAS-12
OPENING
CONTEC AACBLOCK WALL
ANCHOR AT 24" O.C. (MAXIMUM)MINIMUM TWO PER SIDE
5-3
Construction Details
CONTEC AAC BLOCK WALL
MORTAR LEVELINGBED TYPE M
FLOOR JOIST AT AAC BLOCK WALL
MAS-15
2x NAILER, J-BOLT
4" BEARING TYPEWOOD FLOOR JOIST OR TRUSS
PLYWOOD
CONTEC AAC BLOCK WALL
CUT AAC BLOCKFOR JOISTPOCKET
BOND BEAM/AAC U-BLOCKFILLED WITH 3000 psi CONCRETE,
REINFORCED WITH 2-#5 BARS
2 #5 BARS CONTAT BOND BEAM, TYP
1'-4"
2'-0"41/2"
4"
AAC BLOCK HEAD JOINT
WOOD FLOOR JOIST OR TRUSS
3/4"
FOUNDATION
5-4
Construction DetailsIS
OM
ET
RIC
VIE
W
MA
S-1
6
CO
NT
EC
AA
C O
-BLO
CK
SE
T #
5 C
ON
T V
ER
TIC
AL
RE
INF.
(PE
R S
TR
UC
TU
RA
L D
ES
IGN
)
CO
NT
EC
AA
C B
LOC
K W
ALL
CO
NC
RE
TE
RIN
G B
EA
MW
/ 2 #
4 H
OR
IZO
NTA
LB
AR
S C
ON
TIN
UO
US
#3 C
ON
T. B
AR
AT
GR
OU
T K
EY
US
E B
EN
T B
AR
WH
ER
EPA
NE
LS D
O N
OT
ALI
GN
CO
NT
INO
US
VE
RT
ICA
LR
EIN
FO
RC
EM
EN
T
#3 B
AR
CO
NT
JOIN
T R
EIN
F.
CO
NT
EC
AA
C F
LOO
R/
RO
OF
PA
NE
LSG
RO
UT
KE
Y F
ILLE
DW
ITH
MO
RTA
R
TY
PE
M
5-5
Co
nstru
ction
Details
CONNECTIONS FOR CONTEC BLOCK WALL
MAS-17
AAC BLOCK WALL AAC BLOCK WALL-CMU
AAC BLOCK WALL-DRY WALL
METAL STRIPS@ 16" OC. VERTICAL SPACING AAC BLOCK WALL
MORTARED JOINT
CONTEC AAC WALL
CMU BLOCKFILLED W/CONCRETE
CONTEC NAILAT 24" O.C.
AACBLOCK WALL
DRY WALL
CONTEC AAC BLOCK WALL
METAL STRIPS
METAL STRIPS@ 16" OC. VERTICAL SPACING
1/4"
JOINT
BACKER RODAND CAULKING
5-6
Construction Details
CONTEC AAC BLOCKWALL
CMU WALL(8" MINIMUM)
FOUNDATION
VERITCAL REINFORCEMENTFOR CMU FOUNDATION WALL
(PER STRUCTURAL CALCULATIONS)
BAR #5 AND AAC O-BLOCKREINFORCED WITH
FILL WITH CONCRETE 3000 psi
EXTERIOR WALL OVER CMU FOUNDATION
VENTILATED CRAWL SPACE
CONTEC AAC FLOOR PANEL
MINIMUM BEARING LENGTH (3")
MAS-02
CONTINUOUS RINGBEAM WITH 2 #4
MORTAR LEVELINGBED
DPC (DAMP PROF. COURSE)
CORE FILLED WITH CONCRETE
VERTICAL REINFORCEMENT (TIE-DOWNS)(AMOUNT AND SPACING PER STRUCTURALDESIGN
BENT BAR
#3 BENT BAR ATGROOVE - TONGUEFLOOR PANELS
5-7
Construction Details
EXPANSION JOINT BETWEEN AACBLOCK WALL WITH CONCRETE WALL
MAS-20
PLAN VIEW
SECTION A
CONTEC AACBLOCK WALL
CONCRETE WALL
CONCRETE WALL
CONTEC AACBLOCK WALL
A
1/2" PRE-MOLDEDJOINT FILLER
METAL STRIPSAT TWO BLOCK
COURSES
EXPANSION JOINTS
BACKER RODAND CAULKING
3/8" - 1/2"
TWO CONCRETENAILS OR SIMILAR
BENT METALSTRIP
1 1/
2"
5-8
Co
nstru
ction
Details
WALL SECTION AT ROOF EAVE
MAS-21
#5 VERTICAL BAR, PROVIDE90° BENT 8" LONG INTOBOND BEAM AT TOP OF WALL
CONTEC AAC O-BLOCK REINFORCEDWITH 1 # 5 BAR (SPACING AS
REQUIRED BY STRUCTURAL DESIGN)FILLED WITH 3000 psi CONCRETE
ROOF TRUSSSYSTEM
PLATE FOR CONNECT STRUSSES NAILER WITH ANCHOR BOLTS(SPACING AS REQUIRED BYSTRUCTURAL DESIGN)
CONTEC AAC U-BLOCKBOND BEAM FILLEDW/3000 psi CONCRETEREINFORCED WITH 2 #5
CONTEC AACBLOCK WALL
5-9
Co
nstru
ction
Details
SPANDREL AT GARAGE OPENING
MAS-22
BOND BEAM WITH 2 #5HORIZONTAL BARSFILLED W/ 3000 psi
CONCRETE
ROOF TRUSSSYSTEM
PLATE FOR CONNECT TRUSSESNAILER WITH ANCHOR BOLTS(SPACING AS REQUIRED BYSTRUCTURAL DESIGN)
CONTEC AAC U-BLOCK(AMOUNT AND DIMENSIONS OFREINFORCEMENT ACCORDINGTO STRUCTURAL DESIGN)
TOP OF WALL
5-1
0
Co
nstru
ction
Details
ROOF AT EXTERIOR WALL
MAS-23
BOND BEAM WITH 2 #5HORIZONTAL BARSFILLED W/ 3000 psi
CONCRETE, TYP
ROOF TRUSSSYSTEM
PLATE FOR CONNECT STRUSSES NAILER WITH ANCHOR BOLTS(SPACING AS REQUIRED BYSTRUCTURAL DESIGN)
CONTEC AAC U-BLOCK
CONTEC AAC LINTEL
TOP OF WALL
ADJUSTMENT BLOCK CONTEC AAC BLOCKWALL BEYOND OPENING
ADJUSTMENT BLOCK
2" M
IN.
2" M
IN.
5-11
Co
nstru
ction
Details
WALL SECTION AT CONTEC ROOF PANELS
MAS-24
ROOF TRUSSSYSTEM
CONTEC AAC BLOCK WALL
CONTEC AACROOF PANEL
INSULATION
#3 REBAR REINFORCEDAT GROUT KEY
WOOD PLATE &ANCHOR BOLTS
RING BEAM WITH 2 #4 BARS
FILLED WITH CONCRETE3000 psi
PLYWOOD
AAC U-BLOCKBOND BEAM
BEARING LENGTHMIN. 3"
5-1
2
Co
nstru
ction
Details
CONTEC AAC BLOCK AT GABLE END
MAS-25
OPENING
CONTEC AAC U-BLOCKLINTEL
USE SHALL BE DEFINITEDPER STRUCTURAL DESIGNER
CONTEC AAC U-BLOCKBOND BEAM W/ 2#5USE SHALL BE DEFINITEDPER STRUCTURAL DESIGNER
CONTEC AAC "U" BLOCKBOND BEAM W/ 2 #5USE SHALL BE DEFINITEDPER DESIGNER
CONTEC AACBLOCK WALL
2'-0"OVER LAP
CONTEC AACO-BLOCKREINFORCED WITH1 BAR #4 OR 5(USE SHALL BE DEFINITEDPER DESIGNER)
5-1
3
Co
nstru
ction
Details
CONTEC WALL-CANOPY CONSTRUCTION
MAS-26
SPACING & SIZE(ACCORDING TO STRUCTURALDESIGN)
FASTENEREXTERIOR FINISH
ROOFING ONPLYWOOD SHEATHING
2x FRAMING
4x8 WOOD BEAM
FASCIA
FINISHMIN. 1/4"
THICKNESSCONTEC AACBLOCK WALL
FLASHING & SEALANT
CONTEC AAC U-BLOCKREINFORCEMENT 2 #5 ANDFILLED W/ CONCRETE 3000 psi
WOOD PLATE
5-1
4
Co
nstru
ction
Details
CONTEC AAC BLOCK WALL AT ROOF
MAS-27
CONTEC AACBLOCK WALL
BRICK METAL TIE
BRICK VENEER
CONTEC AACU- BLOCKBOND BEAM
METAL JOIST(BY STRUCTURAL DESIGNER)
GALVANIZED VENTEDMETAL DECK
INSULATING CONCRETEBUILT-UP ROOFINGGRAVEL
STOP
WOOD NAILERS
STEELPLATE
1 1/
2"D
RY
PA
CK
5-1
5
Co
nstru
ction
Details
CONTEC AAC WALL-STEEL JOIST CONNECTION
MAS-28
BRICK VENEER(CONNECTIONS SHALL
SATISFIED STRUCTURALDESIGN CRITERIAS)
FLASHING W/ NAILER
BRICK METALTIES
CONTEC AAC BLOCK WALL
STEEL JOISTS WELDEDTO METAL PLATE ASREQUIRED BY STRUCTURAL DESIGN
EMBEDDED STEEL PLATE
WATERPROOFING
WELD PER ENGINEER REQUIREMENT
STEEL DECKAND CONCRETE
BOLT CONNECTORWELDED TO
PLATE
BOND BEAM WITHAAC U-BLOCK
REINFORCED WITH2 #5 AND FILLED
WITH 3000 psi CONCRETE
1 1/
2"D
RY
PA
CK
5-1
6
Co
nstru
ction
Details
CONTEC AAC BLOCK AT FOUNDATION WITH BRICK VENEER
MAS-29
AIR SPACEAIR SPACE
CONTEC AAC BLOCK WALL
CONTEC AAC WALL BLOCK
MORTAR LEVELING BED(TYPE M)
GRADE
MORTAR LEVELING BED(TYPE M)
BRICK TIE
BRICK VENEER
BRICK VENEER
BRICK TIE
FLASHING
STEEL ANGLEWITH ANCHOR
(PER STRUCTURALDESIGN)
WEEP HOLE WEEP HOLE
FLASHING
SPACING VERTICAL AT 16" O.C.
SPACING HORIZONTAL AT 24" O.C.
USE CONTECADHESIVE MORTAR
USE CONTEC ADHESIVEMORTAR
SPACING VERTICAL AT 16" O.C.
SPACING HORIZONTAL AT 24" O.C.
5-1
7
Construction Details
INTERIOR WALL TYPICAL DETAIL
MAS-03
CONTEC AAC BLOCK WALL
MORTAR LEVELING BED
FOUNDATION
(PER STRUCTURAL DESIGN)
(TYPE M)
USE CONTECADHESIVE MORTAR
5-18
Construction Details
WINDOW DETAILS
MAS-30
NOTE: ADDITIONAL FLASHING DETAILS MAY BE REQUIRED REFER TO BIA AND PROJECT DOCUMENTS FOR FURTHER DETAILS
HEAD
JAMB
SILL
WEEP HOLES
BRICK VENEER
SEALANTCONTEC AAC SILLFIELD OUT
WOOD FRAME
CONTEC NAILFLASHING CONTEC NAIL
WOOD FRAME
CONTEC NAIL
WOOD FRAME
WOOD FRAME
CONTEC NAIL
CONTEC NAILBRICK VENEER
WEEP HOLES
FLASHING ANCHOR BOLT
CONTEC NAIL OR ANCHOR
CONTEC AAC BLOCK WALL
JAM
HEAD
SILL
5-19
Construction Details
CONTEC AAC BLOCK WITH WOOD SIDING
MAS-31
CONTEC AACBLOCK WALL
WOOD CLAPBOARDSOR CEDAR SHINGLES
FIX WITH SCREWS(DRYWALL SCREWS)
SCREWAT 1'-0" O.C.
5-20
Construction Details
CONTEC AAC BLOCK NON-LOADBEARING WALL
MAS-32
MORTAR LEVELING BED(TYPE M)SLAB ON GRADE
1/2" GAPE
CONTEC AAC BLOCK WALL
WITHOUT/ DROP CEILING
W/ DROP CEILING
3/8"-5/8" GAPE
FLOOR/ROOF SYSTEM
DROP CEILING
FILL WITH(BACKER ROD AND CAULKING)
FLOOR/ROOF SYSTEM
3/4"
(M
INIM
UM
)
BOND BEAM(WITH U-BLOCK)
BOND BEAM(WITH U-BLOCK)
5-21
Construction Details
IN LOAD-BEARING WALL
MAS-33
FLO
OR
HE
IGH
T
8" TYP 8" TYP
CLEAR OPENING
(REF. STANDARD CONTEC LINTELSFOR OPENING SIZE AND LOAD)
CONTEC LINTEL
A
MINIMUM 3"BEARINGRING BEAM
SECTION A-A
CONTEC AAC LINTEL
FLOOR/ROOF SYSTEM
CONTEC AACBLOCK WALL
CONTEC WALL UNITS AND CONTEC LINTEL
FLOOR/ROOF SYSTEM
ADJUSTMENT BLOCK
2"M
INIM
UM
5-22
Construction Details
CONTEC AAC U-BLOCK LINTEL
MAS-34
NOTE: CONTEC AAC U-BLOCK AS A BOND BEAMSHALL BE DESIGNED IN ACCORDANCE WITH
H: H
eigh
t
B: Width
H-2
"2"
2" B-4" 2"FILLED W/3000psi CONCRETE
2 #5 BARSREINFORCEMENT
< 6'-0"
STRUCTURAL DESIGN CRITERIA
1'-0"
BEARING LENGHT
CONTEC AACBLOCK WALL
CLIP #2AT 8 IN.
5-23
Construction Details
BLOCK "O" DETAIL
MAS-39
FILL WITHCONCRETE3000 psi
8"
CONTROL JOINT
1 #5
3/8"
SEAL WITH BACKER RODAND CAULKING
3000 psi STRAIGTH
1 3/
8"5
1/8"
1 3/
8"
8"
CONCRETEFILL WITH
(SHALL BE REVIEW BYSTRUCTURAL DESIGNER)
1 #5
8"
CORNER
FILL WITHCONCRETE3000 psi
1 3/8" 1 3/8"5 1/8" (SHALL BE REVIEW BY1 #5
STRUCTURAL DESIGNER)
METAL STRIP (BENT)AT TWO BLOCK COURSES
1 1/
2"
5-24
Construction Details
CONTEC AAC BLOCK WALL
2 #3 BARS @RING BEAM, TYP
VERTICALREINFORCEMENT
(SPACING PER STRUCTUALDESIGN)
EXTERIOR WALL OVER REINFORCED CONCRETE
VENTILATED CRAWL SPACE
MAS-04
CONTEC AAC FLOOR PANEL
CONCRETE SLAB
#3 BENT AT BAR AT GROVE-TONGUEFLOOR PANELS
MORTAR LEVELINGBED (TYPE M)
OV
ER
LAP
MIN
IMU
M2'
-0"
FOUNDATION
CONCRETE WALL
DPC (DAMP PROOF COURSE)(IF REQUIRED)
MINIMUM BEARINGLENGTH (3")
5-25
Co
nstru
ction
Details
EXPANSION JOINT STRIPS
MAS-41
GALVANIZED METAL STRIPS
(BENT AS SHOWN)
EVERY TWO BLOCK LAYER
3/8" THICKNESS
CONTEC AAC
BLOCK WALL
SEAL WITH BACKER ROD
AND CAULKING
1 1/
2"
5-2
6
Construction Details
TYPICAL U-BLOCK/BOND BEAM INTERSECTION
MAS-13
#5 BENT BARSTOP & BOTTOM
AT CORNERS
CONTEC U-BLOCKBOND BEAM FILLEDW/3000 psi CONCRETE
#5 BAR TOP & BOTTOM
#5 BAR TOP & BOTTOM
2'-O
" LA
P M
IN.
PLAN VIEW
2"-0"8"
2"
2"
8"
"T" INTERSECTION
#5 BENT BARSTOP & BOTTOM
AT CORNERS
2'-O
"
#5 BAR TOP & BOTTOM
CONTEC U-BLOCKBOND BEAM FILLEDW/3000 psi CONCRETE
2'-0" #5 BAR TOP & BOTTOM
PLAN VIEW"L" INTERSECTION
5-27
Construction Details
DET-01
WOOD TRUSS
ROOF RAFTERS
SHEATING AND ROOFINGPLYWOOD
SOFIT
MOLDING
CONTEC AAC U-BLOCKCONTINUOUS BOND BEAM
ANCHOR BOLT¿ 1/2"AT 2'-0" O.C.
CONTEC AAC O-BLOCK
3/8"
VERTICAL REINFORCEMENT
BLOCKTHICKNESS
WALL SECTION AT ROOF
5-28
Co
nstru
ction
Details
DET-02
CONTEC AAC U-BLOCKCONTINUOUS BOND BEAM
ANCHOR BOLT¿ 1/2"AT 2'-0" O.C.
CONTEC AAC O-BLOCK
VERTICAL REINFORCEMENT
CONTEC AAC O-BLOCK
WOOD BEAM2'-0" O.C.
2"x8" SUPPORT(WOOD)
METAL ACCESSORY(HANGERS)
PLYWOOD
MORTAR LEVELINGBED (TYPE M)
BLOCKTHICKNESS
WALL SECTION AT FLOOR
5-2
9
Co
nstru
ction
Details
DET-03
CONTINUOUS BOND BEAM
ANCHOR BOLT¿ 1/2"AT 2'-0" O.C.
CONTEC AACO-BLOCK
VERTICAL REINFORCEMENT
CONTEC AACO-BLOCK
WOOD BEAMAT 2'-0"
2"x8" SUPPORT(WOOD)
METAL ACCESSORY(HANGERS)
MORTARCEMENT-SANDFOR LEVELING
PLYWOOD
BLOCKTHICKNESS
WALL SECTION AT FLOOR
5-3
0
Co
nstru
ction
Details
DET-04
CONTEC AACU-BLOCK
CONTEC BLOCKVERTICAL REINFORCEMENT
CONTEC AAC BLOCKCOURSES(SECOND FLOOR)
DRYPACK
BLOCKTHICKNESS
1 1/
2"
3/16MORTARADJUSTMENT
(TYPE M OR S)
STEEL PLATE6"x10"x578"
METAL JOIST
WALL SECTION AT JOIST FLOOR
5-3
1
Co
nstru
ction
Details
OV
ER
LA
P L
EN
GH
T
VERTICALREINFORCEMENT(AMOUNT AND SPACING PERSTRUCTURAL DESIGN)
CONTEC AAC O-BLOCK FILLED WITH CONCRETE
MAS-06
FOUNDATION
FILL WITH EPOXY
2'-0
"
3/4"
(AN
CH
OR
DR
ILL)
LEN
GT
H 1
0"
2"
MORTAR LEVELING BED(TYPE M)
VERTICAL REINFORCEMENT ANCHORAGE TO FOUNDATION(ALTERNATIVE OPTION)
DPC (DAMP PROOF COURSE)IF REQUIRED
FINISH
5-3
2
Construction Details
BAR(VERTICALREINFORCEMENT)
AACSTD-BLOCK/AAC O-BLOCK
MAS-06
FOUNDATION(ACCORDING TO
STRUCTURAL DESIGN)
3/4" 2"
MORTAR LEVELING BED(TYPE M)
CONTEC AAC BLOCK WALLTYPICAL SECTION
8'-0
"
AACU-BLOCK(AT 9'-0" MAXIMUM SPACINGOF HEIGHT WALL)
WOOD PLATEANCHOR BOLT
AT 2'-6" O.C.
5-33
Construction Details
OV
ER
LA
P 2
5"
VERTICALREINFORCEMENT
CONTEC AAC BLOCK WALL
FLOOR SLAB
CEMENT-SANDFOR LEVELING
MAS-05
FOUNDATION
5-34
Construction Details
5-35
Construction Details
5-36