Copyright © 2014 Moxa Inc. Released on December 26, 2014 About Moxa Moxa is a leading manufacturer of industrial networking, computing, and automation solutions. With over 25 years of industry experience, Moxa has connected more than 30 million devices worldwide and has a distribution and service network that reaches customers in more than 70 countries. Moxa delivers lasting business value by empowering industry with reliable networks and sincere service for automation systems. Information about Moxa’s solutions is available at www.moxa.com. You may also contact Moxa by email at [email protected]. How to Contact Moxa Tel: +886-2-8919-1230 Fax: +886-2-8919-1231 Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP Moxa Technical Support Team [email protected] Contents 1 Application Description ................................................................... 3 1.1 Objective ................................................................................................. 3 1.2 Goals ....................................................................................................... 3 2 System Topology............................................................................. 3 3 Hardware and Software Requirements ........................................... 4 4 Configuration .................................................................................. 5 4.1 Hardware Installation................................................................................. 5 4.2 PowerFlex 4M Settings ............................................................................... 6 4.3 IAQPoint2 Settings .................................................................................... 7 4.4 MGate 5105-MB-EIP Settings ...................................................................... 7 4.5 Allen-Bradley ControlLogix PLC Settings ....................................................... 9 4.6 RSLinx Settings......................................................................................... 9 4.7 Installing the MGate 5105-MB-EIP EDS File .................................................13 5 Configuring RSLogix 5000 ............................................................. 17 5.1 Creating a New Project .............................................................................17 5.2 Adding a Controller ...................................................................................17 5.3 Adding an EIP Module ...............................................................................18 5.4 Adding MGate 5105-MB-EIP .......................................................................21 5.5 Creating an Ethernet Module......................................................................21 5.6 Creating an MGate Module.........................................................................23

Transcript of Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate...

Page 1: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Copyright © 2014 Moxa Inc. Released on December 26, 2014

About Moxa

Moxa is a leading manufacturer of industrial networking, computing, and automation solutions. With over 25 years of industry experience, Moxa has connected more than 30 million devices worldwide and has a distribution and service network that reaches customers in more than 70 countries. Moxa delivers lasting business value by empowering industry with reliable networks and sincere service for automation systems. Information about Moxa’s solutions is available at www.moxa.com. You may also contact Moxa by email at [email protected].

How to Contact Moxa

Tel: +886-2-8919-1230 Fax: +886-2-8919-1231

Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Moxa Technical Support Team [email protected]

Contents 1 Application Description ................................................................... 3

1.1 Objective ................................................................................................. 3

1.2 Goals ....................................................................................................... 3

2 System Topology ............................................................................. 3

3 Hardware and Software Requirements ........................................... 4

4 Configuration .................................................................................. 5 4.1 Hardware Installation ................................................................................. 5

4.2 PowerFlex 4M Settings ............................................................................... 6

4.3 IAQPoint2 Settings .................................................................................... 7

4.4 MGate 5105-MB-EIP Settings ...................................................................... 7

4.5 Allen-Bradley ControlLogix PLC Settings ....................................................... 9

4.6 RSLinx Settings ......................................................................................... 9

4.7 Installing the MGate 5105-MB-EIP EDS File .................................................13

5 Configuring RSLogix 5000 ............................................................. 17 5.1 Creating a New Project .............................................................................17

5.2 Adding a Controller ...................................................................................17

5.3 Adding an EIP Module ...............................................................................18

5.4 Adding MGate 5105-MB-EIP .......................................................................21

5.5 Creating an Ethernet Module ......................................................................21

5.6 Creating an MGate Module .........................................................................23

Page 2: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 2 of 36

5.7 Tags Description .......................................................................................25

6 RSLogix Ladder Programming ....................................................... 26 6.1 Adding a Subroutine .................................................................................26

6.2 Editing a Subroutine .................................................................................27

6.3 Editing MainRoutine ..................................................................................27

7 Downloading a Project to PLC ....................................................... 30

8 Communication Test ..................................................................... 33 8.1 Monitor Tags ............................................................................................33

8.2 Changing Tag Values .................................................................................34

9 Appendix ....................................................................................... 34 9.1 PowerFlex 4M Modbus Registers .................................................................34

9.2 IAQPoint2 Modbus Registers ......................................................................36

Page 3: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 3 of 36

1 Application Description

1.1 Objective This document describes an application using Allen-Bradley ControlLogix PLC with MGate

5105-MB-EIP.

In this application, Allen-Bradley ControlLogix PLC is used to get input data that MGate

5105-MB-EIP polls from the temperature meter through Modbus Register. Allen-Bradley

ControlLogix PLC evaluates the temperature value and outputs data to MGate 5105-MB-EIP,

which then uses the data to control speed.

1.2 Goals In this document, you will learn the following:

1. Configure Allen-Bradley ControlLogix PLC.

2. Configure MGate 5105-MB-EIP to communicate with a Modbus RTU device.

3. Set up MGate 5105-MB-EIP in RSLogix 5000.

4. Create a basic RSLogix Ladder Programming.

5. Industrial field applications and the job of each role.

2 System Topology

The following figure shows a system architecture in which the Modbus end devices,

PowerFlex 4M and IAQPoint2, are connected to the serial port on MGate 5105-MB-EIP

through RS-485-2W wiring. MGate 5105-MB-EIP and PC (running RSLogix 5000) are

connected to Ethernet switch ports on Allen-Bradley ControlLogix PLC. A fan is connected to

PowerFlex 4M, which powers the fan.

Page 4: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 4 of 36

3 Hardware and Software Requirements

Allen-Bradley ControlLogix PLC − Processor: 1756 L71 ControlLogix5571

− Chassis: 1756-A7

− EIP Module: 1756-EN2TR

MGate 5105-MB-EIP − Firmware Version: V1.1_Build_13111222

− EDS File: MOXA_MGate_EtherNetIP_Adapter.eds

PowerFlex 4M PowerFlex 4M is an adjustable frequency AC drive to power the fan in this application.

IAQPoint2 IAQPoint2 is an indoor air quality monitor. It can detect CO2, temperature, and humidity

levels.

PC (RSLogix 5000)

MGate 5105-MB-EIP

Allen-Brandly

ControlLogix PLC

Power Flex 4M IAQPoint2

Information Level

Control Level

Device Level

Fan

Ethernet

Ethernet

RS-485-2W

Page 5: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 5 of 36

RS Logix 5000 Allen-Bradley ControlLogix PLC Edit Utility released by Rockwell Automation.

− Rev. : V20

− Operating System Support

RSLogix 5000 V20 has been tested on the following operating systems:

− Microsoft Windows 7 Professional (64-bit) with Service Pack 1

− Microsoft Windows 7 Home Premium (64-bit) with Service Pack 1

− Microsoft Windows 7 Home Premium (32-bit) with Service Pack 1

− Microsoft Windows Vista Business (32-bit) with Service Pack 2

− Microsoft Windows XP Professional with Service Pack 3

− Microsoft Windows Server 2008 R2 Standard Edition with Service Pack 1

− Microsoft Windows Server 2008 Standard Edition with Service Pack 2

− Microsoft Windows Server 2003 R2 Standard Edition with Service Pack 2

RSLinx Communication Utility released by Rockwell Automation.

− Rev. :2.59

4 Configuration

4.1 Hardware Installation PowerFlex 4M and IAQPoint2 Connection

− Use RS-485-2W

− Pin assignment

4 5

3

4

5 6

Modbus Port

Page 6: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 6 of 36

PLC Connection

4.2 PowerFlex 4M Settings Serial Port Settings

− Baudrate: 38400

− Set on panel: Command C302 (Comm Data Rate), option 5

Options 0“1200”

1“2400”

2“4800”

3“9600” (Default)

4“19.2K”

5“38.4K”

− Data bit, Parity, Stop bit :8-E-1

− Set on panel: Command C306 (Comm Format), option 1

Options 0“RTU 8-N-1” (Default)

1“RTU 8-E-1”

2“RTU 8-O-1”

3“RTU 8-N-2”

4“RTU 8-E-2”

5“RTU 8-O-2”

Page 7: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 7 of 36

Programmable Settings − Start Source: Modbus port

− Set on panel: Command P106 (Start Source), option 5

Options 0“Keypad” (Default)

1“3-Wire”

2“2-Wire”

3“2-W Lvl Sens”

4“2-W Hi Speed”

5“Comm Port”

Speed Reference: Modbus port − Set on panel: Command P108 (Speed Reference), Option 5

Options 0“Drive Pot” (Default)

1“InternalFreq”

2“0-10V Input”

3“4-20mA Input”

4“Preset Freq”

5“Comm Port”

− Modbus Slave ID Setting: 100 (default)

4.3 IAQPoint2 Settings Serial Port Settings Use the touch panel (the default access password is 2967) to configure the following

settings for the serial port:

− Baudrate: 38400

− Parity: Even(Default)

− Address (Slave ID): 1(Default)

4.4 MGate 5105-MB-EIP Settings Configure MGate 5105-MB-EIP as shown in the following figures.

Serial Port Settings

Page 8: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 8 of 36

Protocol Conversion Setting

EtherNet/IP Setting

Modbus RTU/ASCII Settings

Master Settings

Modbus Commands

Note: For more information on Modbus registers for PowerFlex and IAQPoint 2, refer to

the appendix

Page 9: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 9 of 36

4.5 Allen-Bradley ControlLogix PLC Settings 1. Install 1756-L71 Processor in 1756-A7 Chassis slot 0.

2. Install 1756-EN2TR EIP Module in 1756-A7 Chassis slot 1.

3. Use the key to set the Switch Controller to REM.

4.6 RSLinx Settings 1. Configuring Drivers

a. In the RSLinx Classic Gateway screen, click Communications > Configure

Drivers.

b. In the Configure Drivers screen, select EtherNet/IP Driver from the Available

Driver Types drop-down list and click Add New. Then, enter a driver name and

click OK.

Page 10: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 10 of 36

c. In the screen that appears, select the network interface and click OK.

d. The screen shows that driver status is Running. Click Close.

Page 11: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 11 of 36

2. Searching for an EIP Device

a. Click Communications > RSWho to start searching for EIP devices on the

network.

The system displays the search result under the AB_ETHIP-1 node.

Page 12: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 12 of 36

b. Right-click 1756-EN2TR and select Device Properties.

A screen appears to indicate that the device Revision is 4.004.

Page 13: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 13 of 36

4.7 Installing the MGate 5105-MB-EIP EDS File 1. Run the EDS Hardware Install setup wizard and click Add.

Page 14: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 14 of 36

2. Select Register a single file and specify the directory for the MGate 5105-MB-EIP

Adapter EDS file; then, click Next.

3. If the EDS file verification is successful, click Next.

Page 15: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 15 of 36

4. Accept the default device icon for MGate 5105-MB-EIP or click Change icon to select

a new one. Click Next to continue.

Page 16: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 16 of 36

5. Click Next.

6. After the installation process is complete, click Finish.

Page 17: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 17 of 36

5 Configuring RSLogix 5000

5.1 Creating a New Project Start RSLogix 5000 and create a new project. Click File > New.

5.2 Adding a Controller In the New Controller screen, make sure that you specify the appropriate controller type,

controller firmware version, chassis type and slot.

In this example, the 1756-L71 ControlLogix5571 Controller is selected with Revision 20,

Page 18: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 18 of 36

Chassis Type 1756-A7 7-Slot ControlLogix Chassis, and Slot 0. In addition, specify a

project name (for example, Demo).

5.3 Adding an EIP Module 1. In the Controller Organizer tree menu, right-click 1756Backplane under I/O

configuration and select New Module.

Page 19: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 19 of 36

2. In the Select Module Type screen, select 1756-EN2TR and click Create.

Page 20: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 20 of 36

3. In the New Module screen, enter a name and the IP address; then, click Change in

the Module Definition area.

4. In the Module Definition screen, select 4 in the Revision fields as shown in the

following figure. Click OK.

Page 21: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 21 of 36

5.4 Adding MGate 5105-MB-EIP You can add MGate 5105-MB-EIP by creating a new Ethernet Module or an MGate module.

Note: For an MGate module, connection parameter configuration (assembly

instance path) is not required.

5.5 Creating an Ethernet Module 1. In the Controller Organizer tree menu, right-click Ethernet and select New Module.

Page 22: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 22 of 36

2. Select Ethernet module and click Create.

Page 23: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 23 of 36

3. In the New Module screen, configure the fields as follows:

− Name: Enter MGate5105.

− Comm Format: Select Data – INT from the drop-down list.

− IP Address: Select this option and enter the IP address.

− Connection Parameters: Set the Size (Input 8 and Output 2) and the Assembly Instance

(Input 110 and Output 100) that is determined by MGate 5105-MB-EIP.

5.6 Creating an MGate Module 1. In the Select Module Type screen, select MGate and click Create.

Page 24: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 24 of 36

2. Configure the module name and IP address; then click Change.

Page 25: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 25 of 36

3. In the Module Definition screen, Select INT (unit: 16bits) from the drop-down list and

set the input size as 8 and output size as 2.

5.7 Tags Description In the Controller Organizer tree menu, select Controller Tags under Controller Demo to

view all the tags you have created. Verifying that all the required tags are created and

configure the Description fields associated with the input and output data tags.

Page 26: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 26 of 36

6 RSLogix Ladder Programming

6.1 Adding a Subroutine 1. In the Controller Organizer tree menu, click Tasks > MainTask. Then, right-click

MainProgram and select New Routine.

2. In the New Routine screen, enter “Init” in the Name field and click OK.

Page 27: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 27 of 36

6.2 Editing a Subroutine 1. Click the Init subroutine under Tasks > MainTask.

2. Drag a NEQ instruction to Rung 0; then, set input Source A as

MGate5105:I.Data[3] and input Source B as 2.

3. Drag a MOV instruction to the end of Rung 0; then set Source as 2 and input Dest

as MGate5105:O.Data[0].

The settings for Rung 0 checks the value of the PowerFlex logic command register. If the

register value is not equal to 2, the PLC outputs this register as 2 and sets PowerFlex to

Start Mode.

6.3 Editing MainRoutine 1. Click the MainRoutine task under Tasks > MainTask.

2. Drag a Examine On instruction to Rung 0. The S:FS input indicates that this routine

is run once.

3. Drag a Jump To Subroutine instruction to the end of Rung 0 and set Routine Name

as “Init”.

To remove the Input Par, Input Par, and Return Par parameters that are not required,

right-click on the parameters and select Remove Instruction Parameter.

Page 28: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 28 of 36

4. Add Rung 1 and drag a GEQ instruction to Rung 1; then, set Source A as

MGate5105:I.Data[6] and input Source B as “250”.

5. Drag a MOV instruction to the end of Rung 1; then, set Source as “600” and Dest

input as MGate5105:O.Data[1].

The settings for Rung 1 checks the value of the IAQPoint2 Temperature register. If the

register value is not 250, the PLC outputs the PowerFlex speed register as 600. This

means that if the temperature is greater than 25.0 C, PowerFlex speed is changed to 60

Hz.

6. Add Rung 2 and drag a GEQ instruction to Rung 2; then, set Source A as

MGate5105:I.Data[6] and input Source B as “245”.

7. Drag a LES instruction to Rung 2 and set input Source A as MGate5105:I.Data[6]

and input Source B as “250”.

8. Drag a MOV instruction to the end of Rung 1 and set Source as “600” and input Dest

as MGate5105:O.Data[1].

Page 29: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 29 of 36

The settings for Rung 2 checks the value of the IAQPoint2 temperature register. If the

range of the register value is between 245 and 250, the PLC would output PowerFlex Speed

register as 500. This means that if the temperature range is between 24.5 C and 25.0 C,

PowerFlex speed is changed to 50 Hz.

9. Add Rung 3~7 as shown in the following figure.

The following table shows the logic of Rung 1~7.

Rung Temperature (C ) Drive Speed (MHz. )

>= <

1 250 - 60

2 245 250 50

3 240 245 40

4 235 240 30

5 230 235 20

Page 30: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 30 of 36

Rung Temperature (C ) Drive Speed (MHz. )

6 225 230 10

7 - 225 0

7 Downloading a Project to PLC

1. Select File > Save to save this project.

2. Select Communications >Who Active to search for the target PLC.

Page 31: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 31 of 36

3. In the Who Active screen, expand the EtherNet/IP network node and select

Backplane > 00, 1756-L71 LOGIX5571; then, click Download to download the

project to the PLC.

When a message appears to warn you to that you are downloading an offline project to the

PLC, click Download to continue.

Page 32: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 32 of 36

The RSLogix 5000 main screen displays green indicators as shown in the following figure.

Page 33: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 33 of 36

8 Communication Test

8.1 Monitor Tags Select Controller Tags to view all the tags that you have created. You can monitor the

IAQPoint2 and PowerFlex register values using Input Tags.

For example, if you use a hairdryer to warm up IAQPoint2, this will increase the values of

MGate5105:I.Data[6] and MGate5105:I.Data[4] tags.

Page 34: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 34 of 36

8.2 Changing Tag Values You can change the value of Output Tags. For example, if you set the value of

MGate5105:O.Data[0] to 1, PowerFlex changes to Stop Mode.

9 Appendix

9.1 PowerFlex 4M Modbus Registers Logic Command Register

− Address: 8192

− Access: R/W

− Value:

Bit(s) Description

0 1 = Stop, 0 = Not Stop

1 1 = Start, 0 = Not Start

Reference Register: Setting Speed − Address: 8193

− Access: R/W

− Value: A decimal value entered as xxx.x where the decimal point is fixed. For example,

a decimal of 100 equals to 10.0 Hz and 543 equals to 54.3 Hz.

Logic Status Register − Address: 8448

− Access: R

− Value:

Bit(s) Description

0 1 = Ready, 0 = Not Ready

1 1 = Active (Running), 0 = Not Active

2 1 = Cmd Forward, 0 = Cmd Reverse

3 1 = Rotating Forward, 0 = Rotating Reverse

4 1 = Accelerating, 0 = Not Accelerating

5 1 = Decelerating, 0 = Not Decelerating

Page 35: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 35 of 36

Bit(s) Description

6 1 = Alarm, 0 = No Alarm

7 1 = Faulted, 0 = Not Faulted

8 1 = At Reference, 0 = Not At Reference

9 1 = Reference Controlled by Comm

10 1 = Operation Cmd Controlled by Comm

11 1 = Parameters have been locked

12 Digital Input 1 Status

13 Digital Input 2 Status

14, 15 Not Used

Feedback Register: Running Speed − Address: 8451

− Access: R

− Value: A xxx.x decimal value where the decimal point is fixed. For example, a decimal

of 123 equals to 12.3 Hz and 300 equals to 30.0 Hz.

Drive Error Codes Register − Address: 8449

− Access: R

− Value:

Value (Decimal) Description

0 No Fault

2 Auxiliary Input

3 Power Loss

4 Under Voltage

5 Overvoltage

6 Motor Stalled

7 Motor Overload

8 Heat sink Over temperature

12 HW Overcurrent (300%)

13 Ground Fault

Page 36: Configuring Allen-Brandly ControlLogix PLC with - Moxa · PDF filePC (RSLogix 5000) MGate 5105-MB-EIP Allen-Brandly ControlLogix PLC Power Flex 4M IAQPoint2 Information Level Control

Moxa Tech Note Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP

Copyright © 2014 Moxa Inc. Page 36 of 36

Value (Decimal) Description

29 Analog Input Loss

33 Auto Restart Tries

38 Phase U to Ground Short

39 Phase V to Ground Short

40 Phase W to Ground Short

41 Phase UV Short

42 Phase UW Short

43 Phase VW Short

63 Software Overcurrent

64 Drive Overload

70 Power Unit Fail

80 AutoTune Fail

81 Communication Loss

100 Parameter Checksum Error

122 I/O Board Fail

9.2 IAQPoint2 Modbus Registers Gas display Register: CO2

− Address: 101

− Access: R

− Value: This reports gas concentration. If the CO2 sensor is fitted, this will report in ppm

from 0 to 5000.

Temperature C Register − Address: 102

− Access: R

− Value: This reports temperature in tenths of a degree Celsius.

Humidity Register − Address: 103

− Access: R

− Value: This reports the relative humidity in percentages from 0 to 100.