www.eaton.com/virtualization Configuration Guide – XenCenter & IPM User Guide for configuration of IPM and XenCenter Revision History Revision Description By 22 nd June 2011 Created Amita 23 rd June 2011 Updated as per comments from Prashant Amita 3 rd Aug 2011 Updated as per the comments from Vageesha after the validation of Xen Advanced Feature done. Amita

Transcript of Configuration Guide for IPM&XenCenter - Software...

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM

User Guide

for configuration of IPM and XenCenter

Revision History

Revision Description By

22nd

June 2011 Created Amita

23rd

June 2011 Updated as per comments from Prashant

Amita

3rd

Aug 2011 Updated as per the comments from Vageesha after the validation of Xen Advanced Feature done.

Amita

www.eaton.com/virtualization

Configuration Guide-XenCenter & IPM Page 2/20

Contents

1 Introduction..........................................................................................................................................3 2 Intelligent Power Plug-in for XenCenter ..............................................................................................4

2.1 Prerequisites .........................................................................................................................4 2.2 Using Eaton IPM XenCenter Plugin......................................................................................4 2.3 Using IPM with XenCenter....................................................................................................5

3 Power Event in XenCenter ..................................................................................................................7 3.1 Introduction ...........................................................................................................................7 3.2 Download the Script ..............................................................................................................7 3.3 Configure the Web Interface .................................................................................................7 3.4 Test the configuration .........................................................................................................10

4 Xen Maintenance Mode on Power Event ..........................................................................................12 4.1 Concept of maintenance mode...........................................................................................12 4.2 Configuration.......................................................................................................................12 4.2.1 Prerequisites .......................................................................................................................12 4.2.2 Configuring XenCenter and IPM for maintenance mode....................................................12 4.2.3 Configuration of the Scripts maintenancemode.js ..............................................................14 4.2.4 Test of the configuration .....................................................................................................15

5 References ........................................................................................................................................16 Eaton and Virtualization ....................................................................................................................16 Citrix XenServer SDK for Powershell ................................................................................................16 Citrix XenServer and XenCenter .......................................................................................................16 Intelligent Power Manager (Eaton Power Supervisor) ......................................................................16

6 Appendix............................................................................................................................................17

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 3/20

1 Introduction

Eaton’s Intelligent Power Manager discovers and supervises Eaton’s UPSs and ePDUs connected to the network (either by means of a card/proxy).It also provides local computer graceful shutdown. Citrix’s XenCenter platform forms the foundation for virtualization management. Citrix XenCenter is the Windows-native graphical user interface for managing Citrix XenServer hosts. Our objective is to provide a virtualization support for Eaton’s power protection software –Intelligent Power Manager and adding the Xen advanced features like maintenance mode, Power events in IPM. Purpose of this document is to guide user to configure IPM with Xen virtualized environment. Following are the Xen advanced features in IPM:

1. Intelligent Power Plug-in for XenCenter 2. Power Event in XenCenter 3. Xen Maintenance Mode on Power Event

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 4/20

2 Intelligent Power Plug-in for XenCenter

“Intelligent Power Plug-in XenCenter”, a utility developed by Eaton, is a very easy to use and deploy Plug-in to manage IPM from XenCenter. This plug-in provides the facility to integrate Intelligent Power Manager (IPM) with XenCenter environment. Once the plug-in is deployed, a tab in XenCenter will open IPM and allow users to configure and manage IPM from XenCenter environment.

2.1 Prerequisites

Following are the prerequisites for Intelligent Power Plug-in XenCenter: 1. Citrix’s XenCenter installed on physical windows server. 2. IPM installed on any machine in the same network 3. XenServer powershell SDK. (Power shell Snap-In) 4. Domain knowledge of XenServer Infrastructure

2.2 Using Eaton IPM XenCenter Plugin

1. Download the EatonXenPackage from Eaton website 2. Extract zip file to some location 3. Go to folder where files are extracted 4. Double click on InstallXenPlugin.exe, following window will be displayed.

Field Information IPM Hostname/IP Address – Host name or IP address of the machine where IPM is installed. After entering the field, click on one of the following button. 1. Create – Creates (Registers) Plug-in in XenCenter. IPM tab will get added in XenCenter console. 2. Delete – Uninstalls(Unregisters) Plug-in in XenCenter. XenCenter needs to be restarted and plug-

in needs to be rescanned to take an effect. 3. Exit – It exits from the InstallXenPlugin application.

To check Intelligent Power Plug-in in installed properly in XenCenter 1. Open XenCenter and click Tools->Plug-ins 2. Click Re-Scan Plug-in Directory if you are not able to see Eaton IPM Plug-in in List as shown

in below snap-shot

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 5/20

2.3 Using IPM with XenCenter

The “Intelligent Power Manager” tab will now be visible in the XenCenter Console (and in the root folder). IPM is now available and is fully functional with the XenCenter.To learn more about the features and usage of IPM, please consult the IPM User Manual. The IPM screen is shown below, note the “Intelligent Power Manager” tab on the top is selected.

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 6/20

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 7/20

3 Power Event in XenCenter

3.1 Introduction

The purpose of this task is to forward the power events generated through IPM in XenCenter and integrate alerts. The following are prerequisites:

1. Citrix XenCenter, Citrix XenServer host, XenServer SDK for Powershell. 2. IPM is installed on the machine on which XenCenter is installed. 3. Eaton Software & Scripts Package 4. Security certificate (root certificate) installed on XenCenter machine for every XenServer

host. For more information refer appendix A. 5. The server hosting IPM must enable the execution of third party scripts on the local machine

(minimum access “Remote Signed”) (examples: Set-ExecutionPolicy RemoteSigned

3.2 Download the Script

Extract the EatonXenPackage on the IPM machine and copy the script “CreateEvent.ps1” in the root folder of IPM. Example: “C:\Program Files\EATON\IntelligentPowerManager”

3.3 Configure the Web Interface

Connect to the Web Interface of IPM https://127.0.0.1:4679/ (or through Eaton's Plug-in) and go to the view “Action” on your left.

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 8/20

Click on “Create new action” on your right

Configure the new action with the good parameters

Event criticalities:

Event categories:

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 9/20

Action Type:

Configure the command line:

powershell.\CreateEvent.ps1 –server $IPAddress -UserName $Username -Password $Password -msg "Alert from IPM – {hostname} - {object} = {value} {message}" Parameters: $IPAddress: IP Address Master XenServer in the resource pool. $Username: Username of master XenServer $Password: Password of master XenServer “Message”: Must be between double quotes; a few parameters like {object} {nodeName} can be used after msg. See screen shot below:

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 10/20

3.4 Test the configuration

Select the new action that you have created and click on “Test selected action”

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 11/20

Data on alarms and alerts from Intelligent Power manager is added to System Alerts tab in XenCenter.

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 12/20

4 Xen Maintenance Mode on Power Event

4.1 Concept of maintenance mode

In XenCenter, you can take a server offline temporarily by placing it into Maintenance Mode. When a server in a resource pool is placed into Maintenance Mode, all running VMs will be automatically migrated from it to another server in the same pool. If the server is the pool master, a new master will also be selected for the pool. Eaton uses the same virtual machine migration capability through Citrix’s XenMotion when a UPS is in a critical power situation to move virtual machines off of a server that has a critical power situation. Intelligent Power Manager will now write alarms/alerts into XenCenter, which, in turn, will trigger XenMotion

4.2 Configuration

4.2.1 Prerequisites

1. Citrix XenCenter installed with a resource pool having at least 2 XenServer hosts with guest operating system installed.XenServer tools should be installed on every guest operating system to enable XenMotion Feature.

2. All the guest operating systems should reside in shared iscsi storage. 3. A security certificate (root certificate) should be installed on XenCenter for every

XenServer. 4. The server hosting IPM must enable the execution of third party scripts on the local

machine (minimum access “Remote Signed”) (examples: Set-ExecutionPolicy RemoteSigned)

4.2.2 Configuring XenCenter and IPM for maintenance mode

1. Install the IPM on one of the machines in the subnet 2. Install XenServer SDK for Powershell on the machine where IPM is installed.

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 13/20

3. Extract the Eaton package on the machine where IPM is installed. 4. Copy the file “CreateEvent.ps1” and “MaintenanceMode.ps1” into the root folder of IPM. For

example: “C:\Program Files\EATON\IntelligentPowerManager” 5. Copy the java script file “MaintenanceMode.js” into the folder

IntelligentPowerManager\configs\scripts\ 6. Edit the javascript file, and change all the variables corresponding to the environment as

described in section 4.2.3 below. 7. Restart the IPM service

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 14/20

4.2.3 Configuration of the Scripts maintenancemode.js

//Information about Master XenServer

var server=”IP or Hostname of master XenServer”; //IP or Name of Master XenServer var username="root"; //Username of Master XenServer

var password="eaton01"; //Password of Master XenServer

//From here provide the information about XenServer that needs to be

//put in Maintenance mode along with UPS information // Here we can configured N number of XenServer hosts and UPS

// Following XenServer host must present in XenCenter and must be a part of resource pool.

//--------------------START SETUP 1 ------------------------------ //--------------------HOST1/UPS 1 ------------------------------

//Information about XenServer host and its corresponding UPS (XenServer Host and Server 1)

var host1=” IP or Hostname of 1st XenServer host “; // the name of the host in XenCenter (IP or Name)

var statusUPS1 = UserFunctions.getNodeData("166.99.170.147");//Name of the Node in IPM (IP,DNSName or other)

//The UPS1 link to the Host1 //if the status of the UPS1 is on Battery, the Host1 enter in maintenance mode

if(statusUPS1 && statusUPS1["UPS.PowerSummary.PresentStatus.ACPresent"] != 1 ) {

UserFunctions.exec("powershell ./MaintenanceMode.ps1 -MasterServer "+server+" -UserName "+username+" -Password "+password+" -host1 "+host1+"

-IsStartMaintenance 1");

} //if the status of the UPS1 is on the sector, the Host1 exit the maintenance mode

else if(statusUPS1["UPS.PowerSummary.PresentStatus.ACPresent"] == 1) {

UserFunctions.exec("powershell ./MaintenanceMode.ps1 -MasterServer "+server+" -UserName

"+username+" -Password "+password+" -host1 "+host1+"

-IsStartMaintenance 0"); }

//--------------------END SETUP1 ------------------------------

//--------------------START SETUP 2 ------------------------------

//--------------------HOST2/UPS 2 ------------------------------ var host2="IP or Hostname of 2nd XenServer host";

var statusUPS2 = UserFunctions.getNodeData("IP or hostname of UPS or Node Name in IPM that is powering host2");

//The UPS2 link to the Host2 if(statusUPS2 && statusUPS2["UPS.PowerSummary.PresentStatus.ACPresent"] != 1 )

{ UserFunctions.exec("powershell ./MaintenanceMode.ps1 -MasterServer "+server+" -UserName

"+username+" -Password "+password+" -host2 "+host2+"

-IsStartMaintenance 1"); }

else if(statusUPS2["UPS.PowerSummary.PresentStatus.ACPresent"] == 1) {

UserFunctions.exec("powershell ./MaintenanceMode.ps1 -MasterServer "+server+" -UserName

"+username+" -Password "+password+" -host2 "+host2+"

-IsStartMaintenance 0"); }

//--------------------END SETUP2 ------------------------------

// ... // ...

// ...

//--------------------START SETUP N ------------------------------ //--------------------HOST N/UPS N ------------------------------

var hostx="IP or Hostname of n-th XenServer host";

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 15/20

var statusUPSx = UserFunctions.getNodeData("IP or hostname of UPS or Node Name in IPM that

is powering host n");

//The UPSx link to the Hostx if(statusUPSx && statusUPSx["UPS.PowerSummary.PresentStatus.ACPresent"] != 1 )

{ UserFunctions.exec("powershell ./MaintenanceMode.ps1 -MasterServer "+server+" -UserName

"+username+" -Password "+password+" -hostx "+hostx+"

-IsStartMaintenance 1"); }

else if(statusUPSx["UPS.PowerSummary.PresentStatus.ACPresent"] == 1) {

UserFunctions.exec("powershell ./MaintenanceMode.ps1 -MasterServer "+server+" -UserName "+username+" -Password "+password+" -hostx "+hostx+"

-IsStartMaintenance 0");

} //--------------------END SETUPN ------------------------------

4.2.4 Test of the configuration

To test the installation, perform a power failure on the UPS and see if the corresponding XenServer host goes in Maintenance mode. Besides, removing from the UPS, the user can initiate a utility failure test from the website of the network management card. To get to the Network management card website, type in the IP address of the network management card.

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 16/20

5 References

Eaton and Virtualization

Please visit http://www.eaton.com/virtualization

Citrix XenServer SDK for Powershell

Please visit http://community.citrix.com/display/xs/Download+SDKs for more information about installation and download of Powershell SDK. Please http://tinyurl.com/6yx9rg6 for all power shell sdk commands.

Citrix XenServer and XenCenter

Please visit http://www.citrix.com/English/ps2/products/product.asp?contentID=683148 for more information about download and installation of XenServer and XenCenter

Intelligent Power Manager (Eaton Power Supervisor)

Please visit http://download.mgeops.com/ for more information about download and installation of IPM

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 17/20

6 Appendix

A . Installation of SSL Cerificate for XenServer While using Xen features like power events, maintenance mode, user may face problems related to SSL certificate. Since, for every XenServer, there is a SSL certificate associated with it; user has to install these certificates in trusted store. Following are the steps to install the SSL certificate. Following steps are applicable to Internet Explorer. These steps may vary according to Web Browsers. 1. In web browser, enter the hostname/IP address of XenServer for which you want to install SSL certificate. The SSL certificate is as shown below.

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 18/20

2. To install SSL certificate, click on The Certificate error tab shown on the right side of the address bar.

3. Click on View Certificates to view it as shown below.

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 19/20

4. Click on “Install certificate” to install it and then Certificate Import Wizard will be displayed. Click on “Place all certificates in the following store”.

Click Browse and select Trusted Root Certification Authorities->Local Computer as shown in the figure below.

www.eaton.com/virtualization

Configuration Guide – XenCenter & IPM Page 20/20

To view the installed certificate, click start-> run. Enter “certmgr.msc”. The following window will be displayed. In the Trusted Root Certification Authorities->Certificates ,all the installed SSL certificates will be stored.

Same steps are followed for installing SSL certificates for all the XenServers. These steps are to be followed on the windows machine on which XenCenter is installed and a given XenServer should be added in server list of XenCenter..