History
1978: Introduction of MV-Connex, 24 kV - 36 kV - 52 kV
1988: HV-CONNEX Size 4, 72,5 kV
1994: HV-CONNEX Size 5S, 145 kV
1999: HV-CONNEX Size 6, 170 kV
2002: HV-CONNEX Size 6S, 245 kV
2006: Plug-In Outdoor Bushing Size 6, 170 kV
2007: Surge Arrester for HV CONNEX Size 4
![Page 3: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/3.jpg)
HV-CONNEXCable Termination Systemsfor high voltage networks
![Page 4: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/4.jpg)
Motivation: Dry TypeGIS / Transfomer compartment completely enclosed at
manufacturing site
Connection without expensive gas or oil works on-site
Quick Assembly
Works at the transformer and assembly of the cable termination are
completely independent
GIS or transformer compartment
![Page 5: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/5.jpg)
Size Classification
Max. Diameter over
conductor /
insulation
Cross Section *
IN
Um
50,4 mm / 75 mm
1600 mm²
2500A
72,5kV
Size 4
64,9 mm / 110,5mm
2500 mm²
2500A
170kV
Size 6
50,4 mm / 76 mm
1600 mm²
2500A
145kV
Size 5-S
64,9 mm / 110,5mm
2500 mm²
2500A
245kV
Size 6-S
*valid only, if values comply to max. diameter over insulation / max. diameter over conductor
![Page 6: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/6.jpg)
Socket- The heart of the system
![Page 7: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/7.jpg)
TransformerTesting: IEC 60137
Dimensions: EN 50299
Cable TerminationTesting: IEC 60840 bzw. IEC 62076
GISRoutine Test: IEC 62271-203
Type Test: IEC 60840 Iec 62076
Dimensions: IEC 62271-209
![Page 8: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/8.jpg)
Examples of Usage “Transformer”
![Page 9: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/9.jpg)
Further Transformer applications
HK Macau Siemens
Irkutsk Russia
Oberhasli Switzerland EBG
![Page 10: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/10.jpg)
Examples of Usage “GIS”
![Page 11: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/11.jpg)
HV - Cable Termination System – Application switchgear
![Page 12: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/12.jpg)
Pfisterer ConnexTerminales enchufables hasta 245 kV
Aplicaciónes de GIS
� Terminal enchufable Connex en seco� Terminal convencional
![Page 13: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/13.jpg)
Routine Tests
• Routine Test according to (EN50089 / DIN
EN 60137 / DIN EN 62271-203 / DIN EN
50089)
• Visual Examination
• Meausurements
• Material Test
• Temperature Test (-40°C – 110°C)
• Rated Power Frequency Voltage (460kV)
• Partial Discharge (< 5pC at 2*U0)
• Gas Tightness (Helium; < 4*10-7 bar cm³/s)
• Pressure Test (2*design pressure 1min)
• X-Ray Test
![Page 14: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/14.jpg)
Features of the Separable Connecting System
An interface for oil and gas insulated components
A complete connection system for cables, overhead lines and surge
arresters
Prefabricated and routine tested components
Quick and reliable assembly
Rapid and simple disconnection in the event of faults
Connection without expensive gas or oil works on-site
Works at the transformer and assembly of the cable termination are
independent of each other
Worldwide References several thousand HV accessories in use
worldwide tens of thousands for medium voltage
![Page 15: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/15.jpg)
HV Connex – Off Shore
Off Shore Version Optional
available
![Page 16: Conectores Pfisterer Sn Hv Connex en 2011](https://reader031.fdocuments.in/reader031/viewer/2022020708/55349c744a795983608b4b51/html5/thumbnails/16.jpg)
Low Temperature Test
Accessories for temperatures down to -50°C
System Size 5-S
Connector / Socket / dummy plug / bushing
System Size 6 (test performed with limited values)
Connector / Socket / dummy plug
Accessories for temperature down to -25°C
Bushing Size 6