Conditions for Dust Explosions Albert Ness SAChE Workshop Sept. 15, 2008.

19
Conditions for Dust Explosions Albert Ness SAChE Workshop Sept. 15, 2008

Transcript of Conditions for Dust Explosions Albert Ness SAChE Workshop Sept. 15, 2008.

Conditions for Dust Explosions

Albert NessSAChE Workshop

Sept. 15, 2008

Dust Explosion Pentagon

Combustible Dust

Confinement

Turbulence (dispersed with

[C] > MEC) Oxidant

Ignition Source

(< 420 microns)

Questions

• Is this a dust explosion?• Why or why not?

Venting

Mental / Visual Exercise

Remember Dispersion Limits?

0

2

4

6

8

10

12

0 50 100 150 200 250 300 350

Dust Concentration (g/m3)

Exp

losi

on P

ress

ure

(bar

)

Minimum Explosive Concentration (MEC)

Minimum Explosible Concentration

• Lower limit 10 – 30 g/M3– Polymethylacrylate 15 g/M3– Ground Dextrose 20 g/M3– Flour 60 g/M3

Questions

• Given a 10M x 10M x 3M room • How many grams of flour are needed

to be above the MEC? • How many 2.2 kg (~ 5 lb) bags of

flour are needed to exceed the MEC?

• How many bags of flour are needed to exceed the MEC in this room?

• Does that seem like a lot of flour on the floor?

18,000

8

Secondary Explosions

Why do we care?

What is the effect?

• Poor housekeeping, and secondary explosions, heighten the damage potential– Larger portion of facility, and more people,

potentially involved– Longer duration events greater impulse more

damage to structures and equipment

Housekeeping

• Importance stressed and guidance provided in NFPA 654– Dust layers >1/32 inch deep are a concern

– Can be hazardous if >5% of floor area covered

– Beams, ductwork, cabling, piping, walls all gather dust and should also be considered

– Construct buildings and equipment for ease of cleaning

2008 - Imperial Sugar, GA

Want Proof?

13 Dead, > 40 injured

Q; Are these layers > 1/32 in?

West Pharmaceuticals, NC6 Dead

37 Injured

2003 - West Pharmaceutical, NC

CTA Acoustics, KY7 Dead

37 Injured

2003 – CTA Acoustics, KY

Case Study – Mill / Cyclone / Baghouse

Organic chips ground to 10 (Kst = 150) Conveyed to cyclone and baghouse for collectionMill

Cyclone &Rotary Valve

Baghouse &Rotary Valve

FAN

P-7

Cooler

P-8

Feed

Questions

• Do the conditions exist for a dust explosion?• Where?• What are potential the ignition sources?• If yes, how would you protect the system?• If there were 10 of these units in a building, how

would you protect them?

Our Answer