RATINGS C33/CH33 COILS WITH G60UHV FURNACES January 2002 CONDENSING UNITS ENGINEERING DATA SUPPLEMENT HS21/HS26/HS27/HS29 ARI RATINGS - HS21 Outdoor Unit Model No LARI Standard 210/240 Ratings Outdoor Unit Model No. Unit Size *S d R ti N b Cooling Capacity Efficiency Total Unit Unit Size *Sound Rating Number Btuh kW SEER EER Unit Watts Indoor Unit Model No. **Expansion Device HS21−036 3 Ton UpĆFlow Coils/Furnace 37,800 11.1 14.15 10.75 3520 C33−36A/B−2 with G60UHV−36 26K34 (LB−85663J) 3 Ton (76 dB) Coils/Furnace 40,500 11.9 14.75 11.15 3625 C33−38A/B−2 with G60UHV−36 26K34 (LB−85663J) Horizontal Coils/Furnace 37,800 11.1 14.15 10.75 3520 CH33−36A/B/C−2F with G60UHV−36 26K34 (LB−85663J) Coils/Furnace 40,000 11.7 14.50 11.10 3600 CH33−42B−2F with G60UHV−36 26K34 (LB−85663J) 40,500 11.9 14.75 11.15 3625 CH33−44/48B−2F with G60UHV−36 26K34 (LB−85663J) HS21−048 4 Ton UpĆFlow Coils/Furnace 49,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Ton (78 dB) Coils/Furnace 50,000 14.7 13.20 9.80 5090 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K) Horizontal Coils/Furnace 50,000 14.7 13.20 9.80 5100 CH33−44/48C−2F with G60UHV−60C−090 26K35 (LB−85663K) Coils/Furnace 51,000 14.9 13.35 9.95 5135 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K) HS21−060 5 Ton UpĆFlow Coils/Furnace 60,000 17.6 14.20 9.80 6120 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 5 Ton (78 dB) Coils/Furnace 61,000 17.9 14.30 9.90 6150 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K) 62,000 18.2 14.20 10.10 6145 C33−60D−2 with G60UHV−60D−135 26K35 (LB−85663K) 63,500 18.6 14.40 10.25 6195 C33−62D−2 with G60UHV−60D−135 26K35 (LB−85663K) Horizontal Coils/Furnace 61,500 18.0 14.50 10.00 6155 CH33−48C−2F with G60UHV−60C−090 26K35 (LB−85663K) Coils/Furnace 62,500 18.3 14.70 10.10 6195 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K) 62,000 18.2 14.40 10.10 6150 CH33−60D−2F with G60UHV−60D−135 26K35 (LB−85663K) 63,000 18.5 14.25 10.20 6170 CH33−62D−2F with G60UHV−60D−135 26K35 (LB−85663K) NOTE − Ratings for all C33 coils include both cased and uncased coils. Includes all heat sizes for this model. LCertified in accordance with USE certification program which is based on ARI Standard 210/240; 95_F (35_C) outdoor air temperature, 80_F (27_C) dbɘ/ɘ67_F (19_C) wb entering evaporator air with 20 ft. (6 m) of connecting refrigerant lines. *Sound Rating Number rated in accordance with test conditions included in ARI Standard 270. **Kit is required and must be ordered extra, unless shown as factory installed. NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. 2002 Lennox Industries Inc.

Transcript of CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with...

Page 1: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGSC33/CH33 COILS WITH G60UHV FURNACES

January 2002

CONDENSING UNITS

ENGINEERING DATA

SUPPLEMENT

HS21/HS26/HS27/HS29

ARI RATINGS − HS21

Outdoor Unit Model No�ARI Standard 210/240 Ratings

Outdoor Unit Model No.Unit Size*S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size*Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. **Expansion Device

HS21−0363 Ton

Up�FlowCoils/Furnace

37,800 11.1 14.15 10.75 3520 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)3 Ton(76 dB)

Coils/Furnace

40,500 11.9 14.75 11.15 3625 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

37,800 11.1 14.15 10.75 3520 CH33−36A/B/C−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

40,000 11.7 14.50 11.10 3600 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

40,500 11.9 14.75 11.15 3625 CH33−44/48B−2F with �G60UHV−36 26K34 (LB−85663J)

HS21−0484 Ton

Up�FlowCoils/Furnace

49,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K)4 Ton(78 dB)

Coils/Furnace

50,000 14.7 13.20 9.80 5090 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K)

HorizontalCoils/Furnace

50,000 14.7 13.20 9.80 5100 CH33−44/48C−2F with G60UHV−60C−090 26K35 (LB−85663K)Coils/Furnace

51,000 14.9 13.35 9.95 5135 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K)

HS21−0605 Ton

Up�FlowCoils/Furnace

60,000 17.6 14.20 9.80 6120 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K)5 Ton(78 dB)

Coils/Furnace

61,000 17.9 14.30 9.90 6150 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K)

62,000 18.2 14.20 10.10 6145 C33−60D−2 with G60UHV−60D−135 26K35 (LB−85663K)

63,500 18.6 14.40 10.25 6195 C33−62D−2 with G60UHV−60D−135 26K35 (LB−85663K)

HorizontalCoils/Furnace

61,500 18.0 14.50 10.00 6155 CH33−48C−2F with G60UHV−60C−090 26K35 (LB−85663K)Coils/Furnace

62,500 18.3 14.70 10.10 6195 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K)

62,000 18.2 14.40 10.10 6150 CH33−60D−2F with G60UHV−60D−135 26K35 (LB−85663K)

63,000 18.5 14.25 10.20 6170 CH33−62D−2F with G60UHV−60D−135 26K35 (LB−85663K)

NOTE − Ratings for all C33 coils include both cased and uncased coils.�Includes all heat sizes for this model.�Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb enteringevaporator air with 20 ft. (6 m) of connecting refrigerant lines.*Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.**Kit is required and must be ordered extra, unless shown as factory installed.

NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.Installation and service must be performed by a qualified installer and servicing agency. 2002 Lennox Industries Inc.

awh
Page 2: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

ARI RATINGS − HS26

Outdoor Unit Model No�ARI Standard/Ratings

Outdoor Unit Model No.Unit Size*S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size*Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. **Expansion Device

HS26−0242 Ton

Up�FlowCoils/Furnace

24,400 7.2 13.30 11.85 2055 C33−24A/B−2 with �G60UHV−36 26K34 (LB−85663J)2 Ton(74 dB)

Coils/Furnace

24,800 7.3 13.50 12.05 2060 C33−30A/B−2 with �G60UHV−36 26K34 (LB−85663J)

25,200 7.4 13.65 12.25 2060 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)

26,000 7.6 14.05 12.55 2070 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

24,600 7.2 13.40 11.95 2055 CH33−24/30A−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

25,200 7.4 13.65 12.25 2060 CH33−36A/B−2F with �G60UHV−36 26K34 (LB−85663J)

25,600 7.5 13.95 12.40 2065 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

HS26−0302 5 Ton

Up�FlowCoils/Furnace

30,800 9.0 13.60 12.15 2540 C33−30A/B−2 with �G60UHV−36 26K34 (LB−85663J)2.5 Ton(76 dB)

Coils/Furnace

31,200 9.1 13.75 12.30 2540 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)

32,600 9.6 14.35 12.80 2550 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

30,600 9.0 13.45 12.05 2535 CH33−24/30A−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

31,200 9.1 13.75 12.30 2540 CH33−36A/B−2F with �G60UHV−36 26K34 (LB−85663J)

32,200 9.4 14.25 12.65 2550 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

HS26−0363 Ton

Up�FlowCoils/Furnace

36,000 10.6 13.75 11.80 3050 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)3 Ton(74 dB)

Coils/Furnace

37,800 11.1 14.40 12.35 3065 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

36,000 10.6 13.70 11.80 3055 CH33−36A/B−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

37,400 11.0 14.20 12.20 3065 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

38,000 11.1 14.40 12.40 3065 CH33−44/48B−2F with �G60UHV−36 26K34 (LB−85663J)

HS26−0423 5 Ton

Up�FlowCoils/Furnace

43,000 12.6 13.90 11.90 3615 C33−44C−2 with G60UHV−60C−090 26K35 (LB−85663K)3.5 Ton(76 dB)

Coils/Furnace

43,500 12.7 14.00 12.00 3620 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K)

44,000 12.9 14.10 12.15 3620 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K)

HorizontalCoils/Furnace

44,000 12.9 14.15 12.15 3625 CH33−48C−2F with G60UHV−60C−090 26K35 (LB−85663K)Coils/Furnace

44,500 13.0 14.30 12.25 3635 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K)

HS26−0484 Ton

Up�FlowCoils/Furnace

51,000 14.9 13.75 11.70 4355 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K)4 Ton(76 dB)

Coils/Furnace

51,500 15.1 13.85 11.80 4360 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K)

HorizontalCoils/Furnace

52,000 15.2 13.95 11.90 4370 CH33−48C−2F with G60UHV−60C−090 26K35 (LB−85663K)Coils/Furnace

52,500 15.4 14.10 12.00 4375 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K)

HS26−0605 Ton

Up�FlowCoils/Furnace

58,500 17.1 13.10 11.25 5205 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K)5 Ton(76 dB)

Coils/Furnace

58,500 17.1 13.15 11.30 5175 C33−60D−2 with G60UHV−60D−135 26K35 (LB−85663K)

60,500 17.7 13.55 11.65 5195 C33−62D−2 with G60UHV−60D−135 26K35 (LB−85663K)

HorizontalCoils/Furnace

59,500 17.4 13.35 11.40 5215 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K)Coils/Furnace

59,000 17.3 13.30 11.40 5185 CH33−60D−2F with G60UHV−60D−135 26K35 (LB−85663K)

60,000 17.6 13.40 11.55 5190 CH33−62D−2F with G60UHV−60D−135 26K35 (LB−85663K)

NOTE − Ratings for all C33 coils include both cased and uncased coils.�Includes all heat sizes for this model.�Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb enteringevaporator air with 20 ft. (6 m) of connecting refrigerant lines.*Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.**Kit is required and must be ordered extra, unless shown as factory installed.

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 2 �

Page 3: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

ARI RATINGS − HS27

Outdoor Unit Model No�ARI Standard/Ratings

Outdoor Unit Model No.Unit Size*S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size*Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. **Expansion Device

HS27−0242 Ton

Up�FlowCoils/Furnace

25,200 7.4 14.55 12.90 1955 C33−24A/B−2 with �G60UHV−36 26K34 (LB−85663J)2 Ton(72 dB)

Coils/Furnace

25,600 7.5 14.80 13.05 1960 C33−30A/B−2 with vG60UHV−36 26K34 (LB−85663J)

26,000 7.6 15.00 13.25 1960 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)

26,800 7.9 15.45 13.65 1965 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

25,400 7.4 14.70 12.95 1960 CH33−24/30A−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

25,800 7.6 15.00 13.15 1960 CH33−36A/B−2F with �G60UHV−36 26K34 (LB−85663J)

26,600 7.8 15.30 13.55 1965 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

HS27−0302.5 Ton

Up�FlowCoils/Furnace

27,600 8.1 14.25 12.60 2190 C33−30A/B−2 with �G60UHV−36 26K34 (LB−85663J)2.5 Ton(72 dB)

Coils/Furnace

28,200 8.3 14.50 12.90 2190 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)

29,600 8.7 15.35 13.50 2195 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

27,200 8.0 14.05 12.45 2185 CH33−24/30A−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

28,400 8.3 14.60 12.95 2190 CH33−36A/B−2F with �G60UHV−36 26K34 (LB−85663J)

29,200 8.6 15.10 13.30 2195 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

HS27−0363 Ton

Up�FlowCoils/Furnace

34,000 10.0 14.20 12.30 2760 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)3 Ton(72 dB)

Coils/Furnace

35,800 10.5 14.90 12.90 2775 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

34,000 10.0 14.15 12.30 2765 CH33−36A/B−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

35,400 10.4 14.70 12.80 2770 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

35,800 10.5 14.90 12.90 2775 CH33−44/48B−2F with �G60UHV−36 26K34 (LB−85663J)

HS27−0423.5 Ton

Up�FlowCoils/Furnace

41,500 12.2 14.70 12.55 3310 C33−44C−2 with G60UHV−60C−090 26K35 (LB−85663K)3.5 Ton(74 dB)

Coils/Furnace

41,500 12.2 14.75 12.50 3315 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K)

42,000 12.3 14.90 12.65 3320 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K)

HorizontalCoils/Furnace

42,500 12.5 15.00 12.80 3320 CH33−48C−2F with G60UHV−60C−090 26K35 (LB−85663K)Coils/Furnace

43,000 12.6 15.15 12.95 3325 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K)

NOTE − Ratings for all C33 coils include both cased and uncased coils.�Includes all heat sizes for this model.�Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb enteringevaporator air with 20 ft. (6 m) of connecting refrigerant lines.*Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.**Kit is required and must be ordered extra, unless shown as factory installed.

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 3 �

Page 4: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

ARI RATINGS − HS29

Outdoor Unit Model No�ARI Standard/Ratings

Outdoor Unit Model No.Unit Size*S d R ti N b

Cooling Capacity Efficiency TotalUnit

Unit Size*Sound Rating Number

Btuh kW SEER EERUnit

Watts Indoor Unit Model No. **Expansion Device

HS29−0242 Ton

Up�FlowCoils/Furnace

25,800 7.6 12.15 11.10 2325 C33−24A/B−2 with �G60UHV−36 26K34 (LB−85663J)2 Ton(74 dB)

Coils/Furnace

26,200 7.7 12.40 11.20 2340 C33−30A/B−2 with �G60UHV−36 26K34 (LB−85663J)

26,600 7.8 12.55 11.30 2350 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)

27,400 8.0 12.95 11.55 2375 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

26,000 7.6 12.30 11.15 2335 CH33−24/30A−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

26,600 7.8 12.65 11.30 2350 CH33−36A/B−2F with �G60UHV−36 26K34 (LB−85663J)

27,400 8.0 12.90 11.55 2370 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

HS29−0302 5 Ton

Up�FlowCoils/Furnace

31,000 9.1 11.65 10.20 3045 C33−30A/B−2 with �G60UHV−36 26K34 (LB−85663J)2.5 Ton(76 dB)

Coils/Furnace

31,400 9.2 11.80 10.30 3055 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)

32,400 9.5 12.10 10.55 3075 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

30,800 9.0 11.55 10.15 3040 CH33−24/30A−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

31,400 9.2 11.80 10.30 3050 CH33−36A/B−2F with �G60UHV−36 26K34 (LB−85663J)

32,400 9.5 12.10 10.55 3075 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

HS29−0363 Ton

Up�FlowCoils/Furnace

37,400 11.0 11.55 10.25 3655 C33−36A/B−2 with �G60UHV−36 26K34 (LB−85663J)3 Ton(76 dB)

Coils/Furnace

39,500 11.6 12.20 10.70 3700 C33−38A/B−2 with �G60UHV−36 26K34 (LB−85663J)

HorizontalCoils/Furnace

37,400 11.0 11.65 10.25 3650 CH33−36A/B−2F with �G60UHV−36 26K34 (LB−85663J)Coils/Furnace

39,000 11.4 12.05 10.55 3690 CH33−42B−2F with �G60UHV−36 26K34 (LB−85663J)

39,500 11.6 12.20 10.70 3700 CH33−44/48B−2F with �G60UHV−36 26K34 (LB−85663J)

HS29−0423 5 Ton

Up�FlowCoils/Furnace

45,000 13.2 11.85 10.45 4310 C33−44C−2 with G60UHV−60C−090 26K35 (LB−85663K)3.5 Ton(78 dB)

Coils/Furnace

45,000 13.2 11.90 10.45 4315 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K)

45,500 13.3 12.00 10.50 4325 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K)

HorizontalCoils/Furnace

45,500 13.3 12.05 10.50 4330 CH33−48C−2F with G60UHV−60C−090 26K35 (LB−85663K)Coils/Furnace

46,000 13.5 12.15 10.60 4345 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K)

HS29−0484 Ton

Up�FlowCoils/Furnace

48,500 14.2 11.70 10.10 4805 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K)4 Ton(80 dB)

Coils/Furnace

49,000 14.4 11.80 10.20 4810 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K)

HorizontalCoils/Furnace

49,500 14.5 11.80 10.30 4815 CH33−48C−2F with G60UHV−60C−090 26K35 (LB−85663K)Coils/Furnace

50,000 14.7 11.95 10.35 4830 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K)

HS29−0605 Ton

Up�FlowCoils/Furnace

59,000 17.3 11.70 10.20 5780 C33−50/60C−2 with G60UHV−60C−090 26K35 (LB−85663K)5 Ton(80 dB)

Coils/Furnace

59,000 17.3 11.75 10.25 5755 C33−60D−2 with G60UHV−60D−135 26K35 (LB−85663K)

60,500 17.7 12.05 10.50 5770 C33−62D−2 with G60UHV−60D−135 26K35 (LB−85663K)

HorizontalCoils/Furnace

60,000 17.6 11.90 10.35 5795 CH33−50/60C−2F with G60UHV−60C−090 26K35 (LB−85663K)Coils/Furnace

59,500 17.4 11.90 10.30 5770 CH33−60D−2F with G60UHV−60D−135 26K35 (LB−85663K)

60,000 17.6 12.00 10.40 5765 CH33−62D−2F with G60UHV−60D−135 26K35 (LB−85663K)

NOTE − Ratings for all C33 coils include both cased and uncased coils.�Includes all heat sizes for this model.�Certified in accordance with USE certification program which is based on ARI Standard 210/240; 95�F (35�C) outdoor air temperature, 80�F (27�C) db�/�67�F (19�C) wb enteringevaporator air with 20 ft. (6 m) of connecting refrigerant lines.*Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.**Kit is required and must be ordered extra, unless shown as factory installed.

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 4 �

Page 5: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS21−036 � LOW SPEED � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F620 295 21.3 6.2 1.29 .73 .88 1.00 20.1 5.9 1.42 .75 .91 1.00 18.9 5.5 1.56 .78 .93 1.00 17.7 5.2 1.69 .80 .96 1.00

63�F(17�C)

720 340 22.0 6.4 1.29 .77 .93 1.00 20.8 6.1 1.43 .79 .95 1.00 19.5 5.7 1.57 .82 .98 1.00 18.4 5.4 1.71 .85 1.00 1.00(17�C)

820 385 22.6 6.6 1.29 .81 .97 1.00 21.4 6.3 1.43 .83 .99 1.00 20.2 5.9 1.57 .86 1.00 1.00 19.0 5.6 1.72 .90 1.00 1.00

67�F620 295 23.0 6.7 1.29 .57 .71 .84 21.7 6.4 1.43 .58 .73 .87 20.4 6.0 1.58 .59 .74 .89 19.0 5.6 1.72 .61 .77 .93

67�F(19�C)

720 340 23.6 6.9 1.29 .59 .74 .89 22.2 6.5 1.43 .60 .76 .92 20.8 6.1 1.58 .62 .79 .95 19.4 5.7 1.73 .63 .82 .98(19�C)

820 385 24.1 7.1 1.29 .61 .78 .93 22.7 6.7 1.43 .63 .80 .96 21.2 6.2 1.58 .64 .83 .99 19.8 5.8 1.74 .66 .86 1.00

71�F620 295 24.9 7.3 1.28 .42 .55 .68 23.5 6.9 1.44 .43 .56 .70 22.1 6.5 1.59 .43 .57 .72 20.6 6.0 1.75 .44 .59 .74

71�F(22�C)

720 340 25.5 7.5 1.28 .43 .57 .71 24.1 7.1 1.44 .44 .58 .73 22.5 6.6 1.60 .44 .60 .76 21.0 6.2 1.76 .45 .62 .79(22�C)

820 385 26.0 7.6 1.28 .44 .59 .75 24.5 7.2 1.44 .44 .61 .77 22.9 6.7 1.60 .45 .63 .80 21.4 6.3 1.76 .46 .65 .83

HS21−036 � HIGH SPEED � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTemperat

ure

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbure

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 36.0 10.6 2.76 .69 .81 .91 34.0 10.0 2.96 .70 .83 .94 32.2 9.4 3.18 .71 .84 .96 30.5 8.9 3.39 .73 .87 .98

63�F(17�C)

1050 495 37.7 11.0 2.81 .72 .86 .97 35.7 10.5 3.01 .74 .88 .98 33.8 9.9 3.24 .76 .90 1.00 32.0 9.4 3.46 .78 .92 1.00(17�C)

1250 590 39.1 11.5 2.85 .76 .90 1.00 37.0 10.8 3.06 .78 .92 1.00 35.1 10.3 3.29 .80 .95 1.00 33.3 9.8 3.51 .82 .97 1.00

67�F850 400 39.0 11.4 2.84 .55 .66 .76 36.9 10.8 3.06 .55 .67 .78 35.1 10.3 3.29 .56 .68 .80 33.3 9.8 3.51 .56 .69 .82

67�F(19�C)

1050 495 40.8 12.0 2.90 .56 .69 .82 38.5 11.3 3.12 .57 .71 .84 36.6 10.7 3.36 .58 .72 .86 34.6 10.1 3.58 .59 .74 .88(19�C)

1250 590 42.0 12.3 2.94 .58 .73 .86 39.7 11.6 3.16 .59 .75 .89 37.6 11.0 3.41 .60 .77 .91 35.7 10.5 3.64 .62 .78 .93

71�F850 400 42.3 12.4 2.95 .42 .52 .63 40.2 11.8 3.18 .42 .53 .64 38.3 11.2 3.44 .42 .54 .65 36.4 10.7 3.68 .42 .54 .66

71�F(22�C)

1050 495 44.2 13.0 3.01 .43 .54 .66 41.9 12.3 3.25 .42 .55 .68 39.8 11.7 3.51 .43 .56 .69 37.9 11.1 3.76 .43 .57 .71(22�C)

1250 590 45.5 13.3 3.05 .43 .56 .70 43.1 12.6 3.30 .43 .58 .71 41.0 12.0 3.56 .44 .59 .73 38.9 11.4 3.82 .44 .60 .75

HS21−036 � LOW SPEED � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F620 295 21.9 6.4 1.29 .72 .87 1.00 20.7 6.1 1.42 .74 .90 1.00 19.4 5.7 1.56 .76 .93 1.00 18.1 5.3 1.70 .79 .96 1.00

63�F(17�C)

720 340 22.7 6.7 1.29 .75 .91 1.00 21.3 6.2 1.43 .78 .95 1.00 20.1 5.9 1.57 .81 .98 1.00 18.8 5.5 1.71 .84 1.00 1.00(17�C)

820 385 23.3 6.8 1.28 .79 .96 1.00 22.0 6.4 1.43 .82 .99 1.00 20.8 6.1 1.57 .85 1.00 1.00 19.6 5.7 1.73 .88 1.00 1.00

67�F620 295 23.8 7.0 1.28 .56 .69 .82 22.4 6.6 1.43 .57 .71 .85 20.9 6.1 1.58 .58 .73 .88 19.5 5.7 1.73 .60 .76 .92

67�F(19�C)

720 340 24.4 7.2 1.28 .58 .73 .87 23.0 6.7 1.43 .59 .75 .91 21.5 6.3 1.58 .61 .77 .94 20.0 5.9 1.74 .62 .81 .97(19�C)

820 385 25.0 7.3 1.28 .60 .76 .92 23.5 6.9 1.43 .62 .79 .95 21.9 6.4 1.59 .63 .82 .99 20.4 6.0 1.74 .65 .85 1.00

71�F620 295 25.8 7.6 1.27 .42 .54 .66 24.3 7.1 1.43 .42 .55 .68 22.8 6.7 1.59 .43 .56 .70 21.3 6.2 1.76 .43 .58 .72

71�F(22�C)

720 340 26.5 7.8 1.27 .43 .56 .70 24.9 7.3 1.43 .43 .57 .72 23.3 6.8 1.60 .43 .59 .74 21.8 6.4 1.76 .44 .61 .77(22�C)

820 385 27.0 7.9 1.26 .43 .58 .73 25.4 7.4 1.43 .44 .60 .75 23.8 7.0 1.60 .44 .61 .79 22.1 6.5 1.77 .45 .64 .82

HS21−036 � HIGH SPEED � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 37.9 11.1 2.81 .68 .79 .90 35.8 10.5 3.02 .69 .81 .93 33.9 9.9 3.24 .70 .83 .94 32.1 9.4 3.46 .72 .85 .97

63�F(17�C)

1050 495 40.0 11.7 2.88 .71 .84 .96 37.7 11.0 3.09 .73 .86 .98 35.7 10.5 3.32 .74 .89 .99 33.8 9.9 3.55 .76 .91 1.00(17�C)

1250 590 41.6 12.2 2.93 .74 .88 .99 39.2 11.5 3.15 .76 .91 1.00 37.2 10.9 3.39 .78 .94 1.00 35.2 10.3 3.63 .80 .96 1.00

67�F850 400 41.3 12.1 2.92 .54 .65 .75 39.1 11.5 3.14 .55 .66 .77 37.1 10.9 3.39 .55 .67 .79 35.2 10.3 3.62 .56 .68 .81

67�F(19�C)

1050 495 43.5 12.7 2.99 .56 .68 .80 41.0 12.0 3.22 .57 .70 .82 38.9 11.4 3.47 .57 .71 .84 36.8 10.8 3.71 .58 .73 .86(19�C)

1250 590 45.0 13.2 3.04 .58 .71 .85 42.4 12.4 3.28 .58 .73 .87 40.2 11.8 3.54 .60 .75 .89 38.1 11.2 3.78 .61 .77 .92

71�F850 400 45.0 13.2 3.04 .42 .52 .62 42.7 12.5 3.29 .42 .52 .63 40.7 11.9 3.56 .42 .53 .64 38.6 11.3 3.81 .42 .54 .65

71�F(22�C)

1050 495 47.3 13.9 3.12 .42 .53 .65 44.8 13.1 3.38 .43 .54 .66 42.6 12.5 3.65 .43 .55 .68 40.4 11.8 3.91 .43 .56 .69(22�C)

1250 590 49.0 14.4 3.19 .43 .56 .68 46.4 13.6 3.45 .43 .56 .70 44.0 12.9 3.73 .43 .58 .72 41.8 12.3 3.99 .44 .59 .73

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 5 �

Page 6: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS21−036 � LOW SPEED � CH33−36A/B/C−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F620 295 21.4 6.3 1.29 .73 .87 .99 20.2 5.9 1.42 .74 .90 1.00 19.0 5.6 1.55 .77 .92 1.00 17.7 5.2 1.68 .80 .96 1.00

63�F(17�C)

720 340 22.1 6.5 1.29 .76 .92 1.00 20.8 6.1 1.42 .78 .95 1.00 19.6 5.7 1.56 .81 .97 1.00 18.4 5.4 1.69 .84 .99 1.00(17�C)

820 385 22.7 6.7 1.29 .80 .95 1.00 21.4 6.3 1.42 .82 .98 1.00 20.2 5.9 1.56 .85 1.00 1.00 19.1 5.6 1.71 .88 1.00 1.00

67�F620 295 23.1 6.8 1.29 .57 .70 .83 21.8 6.4 1.42 .58 .72 .86 20.5 6.0 1.57 .58 .73 .88 19.1 5.6 1.71 .60 .76 .91

67�F(19�C)

720 340 23.8 7.0 1.29 .58 .73 .87 22.4 6.6 1.43 .60 .75 .91 21.0 6.2 1.57 .61 .78 .94 19.6 5.7 1.72 .63 .80 .96(19�C)

820 385 24.2 7.1 1.28 .61 .77 .92 22.8 6.7 1.43 .62 .79 .95 21.4 6.3 1.57 .63 .82 .98 19.9 5.8 1.72 .65 .85 .99

71�F620 295 25.1 7.4 1.28 .42 .54 .67 23.7 6.9 1.43 .43 .56 .69 22.2 6.5 1.58 .43 .57 .71 20.8 6.1 1.74 .43 .58 .73

71�F(22�C)

720 340 25.7 7.5 1.28 .43 .57 .70 24.2 7.1 1.43 .43 .58 .72 22.8 6.7 1.59 .44 .59 .75 21.2 6.2 1.75 .44 .61 .77(22�C)

820 385 26.2 7.7 1.28 .43 .59 .74 24.7 7.2 1.43 .44 .60 .76 23.2 6.8 1.59 .45 .61 .79 21.6 6.3 1.75 .45 .64 .82

HS21−036 � HIGH SPEED � CH33−36A/B/C−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 35.9 10.5 2.77 .69 .80 .91 33.8 9.9 2.97 .70 .82 .94 32.1 9.4 3.19 .71 .84 .96 30.3 8.9 3.39 .73 .87 .98

63�F(17�C)

1050 495 37.6 11.0 2.81 .72 .85 .97 35.5 10.4 3.02 .74 .88 .98 33.6 9.8 3.24 .75 .90 1.00 31.8 9.3 3.46 .77 .92 1.00(17�C)

1250 590 39.0 11.4 2.85 .75 .90 1.00 36.8 10.8 3.06 .77 .92 1.00 34.9 10.2 3.29 .79 .94 1.00 33.1 9.7 3.51 .81 .97 1.00

67�F850 400 38.9 11.4 2.85 .55 .66 .77 36.8 10.8 3.06 .55 .67 .78 35.0 10.3 3.29 .56 .68 .80 33.2 9.7 3.52 .57 .70 .82

67�F(19�C)

1050 495 40.7 11.9 2.90 .56 .69 .81 38.5 11.3 3.12 .57 .70 .83 36.5 10.7 3.36 .58 .72 .85 34.6 10.1 3.58 .59 .74 .88(19�C)

1250 590 42.0 12.3 2.94 .58 .72 .86 39.7 11.6 3.17 .59 .74 .88 37.6 11.0 3.41 .60 .76 .91 35.6 10.4 3.64 .61 .78 .93

71�F850 400 42.2 12.4 2.95 .42 .52 .62 40.0 11.7 3.18 .43 .53 .64 38.1 11.2 3.43 .43 .54 .65 36.3 10.6 3.67 .43 .55 .66

71�F(22�C)

1050 495 44.1 12.9 3.01 .43 .54 .66 41.8 12.3 3.25 .43 .55 .67 39.8 11.7 3.51 .43 .56 .69 37.8 11.1 3.75 .44 .57 .71(22�C)

1250 590 45.5 13.3 3.06 .43 .56 .69 43.1 12.6 3.30 .44 .57 .71 41.0 12.0 3.56 .44 .58 .73 38.9 11.4 3.82 .44 .59 .75

HS21−036 � LOW SPEED � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F620 295 21.7 6.4 1.29 .72 .87 1.00 20.5 6.0 1.42 .74 .89 1.00 19.2 5.6 1.56 .76 .92 1.00 17.9 5.2 1.69 .79 .96 1.00

63�F(17�C)

720 340 22.4 6.6 1.29 .75 .91 1.00 21.1 6.2 1.42 .78 .94 1.00 19.8 5.8 1.56 .80 .97 1.00 18.6 5.5 1.71 .83 .99 1.00(17�C)

820 385 23.0 6.7 1.29 .79 .96 1.00 21.7 6.4 1.43 .81 .99 1.00 20.5 6.0 1.57 .84 1.00 1.00 19.3 5.7 1.72 .87 1.00 1.00

67�F620 295 23.5 6.9 1.28 .56 .69 .82 22.2 6.5 1.43 .57 .71 .85 20.8 6.1 1.57 .58 .73 .88 19.4 5.7 1.72 .59 .75 .91

67�F(19�C)

720 340 24.2 7.1 1.28 .58 .72 .87 22.8 6.7 1.43 .59 .74 .90 21.3 6.2 1.58 .60 .77 .93 19.9 5.8 1.73 .62 .80 .97(19�C)

820 385 24.7 7.2 1.28 .60 .75 .91 23.2 6.8 1.43 .61 .78 .94 21.7 6.4 1.58 .63 .81 .98 20.2 5.9 1.74 .65 .85 1.00

71�F620 295 25.5 7.5 1.28 .42 .54 .66 24.1 7.1 1.43 .42 .55 .68 22.6 6.6 1.59 .42 .56 .69 21.1 6.2 1.75 .43 .58 .72

71�F(22�C)

720 340 26.2 7.7 1.27 .42 .56 .69 24.7 7.2 1.43 .43 .57 .71 23.1 6.8 1.59 .43 .59 .74 21.6 6.3 1.76 .44 .60 .77(22�C)

820 385 26.8 7.9 1.27 .43 .58 .72 25.2 7.4 1.43 .44 .59 .75 23.6 6.9 1.60 .44 .61 .78 22.0 6.4 1.76 .45 .63 .81

HS21−036 � HIGH SPEED � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 37.4 11.0 2.79 .68 .79 .90 35.3 10.3 2.99 .69 .81 .92 33.5 9.8 3.22 .70 .83 .94 31.6 9.3 3.43 .72 .85 .97

63�F(17�C)

1050 495 39.4 11.5 2.85 .71 .84 .95 37.2 10.9 3.06 .72 .86 .97 35.2 10.3 3.29 .74 .88 .99 33.3 9.8 3.51 .76 .90 1.00(17�C)

1250 590 40.9 12.0 2.90 .74 .88 .99 38.6 11.3 3.12 .76 .90 1.00 36.6 10.7 3.35 .78 .93 1.00 34.7 10.2 3.58 .80 .95 1.00

67�F850 400 40.7 11.9 2.89 .54 .65 .75 38.5 11.3 3.11 .54 .66 .77 36.6 10.7 3.35 .55 .67 .79 34.7 10.2 3.58 .56 .68 .80

67�F(19�C)

1050 495 42.8 12.5 2.96 .56 .68 .79 40.5 11.9 3.19 .56 .69 .82 38.4 11.3 3.43 .57 .71 .84 36.3 10.6 3.67 .58 .72 .86(19�C)

1250 590 44.4 13.0 3.01 .57 .71 .84 41.8 12.3 3.24 .58 .73 .86 39.6 11.6 3.50 .59 .74 .89 37.5 11.0 3.73 .61 .77 .91

71�F850 400 44.4 13.0 3.01 .42 .52 .61 42.1 12.3 3.25 .42 .52 .62 40.1 11.8 3.51 .42 .53 .64 38.1 11.2 3.76 .42 .54 .65

71�F(22�C)

1050 495 46.6 13.7 3.08 .42 .53 .64 44.1 12.9 3.34 .42 .54 .66 42.0 12.3 3.61 .43 .55 .67 39.9 11.7 3.86 .43 .56 .69(22�C)

1250 590 48.2 14.1 3.14 .43 .55 .68 45.7 13.4 3.40 .43 .56 .69 43.4 12.7 3.68 .43 .57 .71 41.2 12.1 3.94 .44 .58 .73

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 6 �

Page 7: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS21−036 � LOW SPEED � CH33−44/48B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F620 295 21.9 6.4 1.29 .72 .86 .99 20.6 6.0 1.42 .74 .89 1.00 19.3 5.7 1.56 .76 .92 1.00 18.0 5.3 1.70 .78 .96 1.00

63�F(17�C)

720 340 22.6 6.6 1.29 .75 .91 1.00 21.3 6.2 1.43 .77 .94 1.00 20.0 5.9 1.57 .80 .97 1.00 18.7 5.5 1.71 .83 1.00 1.00(17�C)

820 385 23.2 6.8 1.28 .79 .96 1.00 21.9 6.4 1.43 .81 .99 1.00 20.7 6.1 1.57 .84 1.00 1.00 19.5 5.7 1.73 .88 1.00 1.00

67�F620 295 23.8 7.0 1.28 .56 .68 .82 22.4 6.6 1.43 .56 .70 .85 20.9 6.1 1.58 .58 .73 .88 19.5 5.7 1.73 .59 .75 .91

67�F(19�C)

720 340 24.4 7.2 1.28 .58 .72 .87 23.0 6.7 1.43 .59 .74 .90 21.5 6.3 1.58 .60 .77 .93 20.0 5.9 1.74 .62 .80 .97(19�C)

820 385 25.0 7.3 1.28 .60 .75 .91 23.5 6.9 1.43 .61 .78 .95 22.0 6.4 1.59 .63 .81 .98 20.4 6.0 1.74 .64 .85 1.00

71�F620 295 25.8 7.6 1.27 .42 .54 .66 24.3 7.1 1.43 .42 .55 .67 22.8 6.7 1.59 .43 .56 .70 21.3 6.2 1.76 .43 .58 .72

71�F(22�C)

720 340 26.5 7.8 1.27 .42 .56 .69 25.0 7.3 1.43 .43 .57 .71 23.4 6.9 1.60 .43 .58 .73 21.8 6.4 1.76 .44 .60 .77(22�C)

820 385 27.1 7.9 1.26 .43 .58 .72 25.5 7.5 1.43 .43 .59 .75 23.8 7.0 1.60 .44 .61 .78 22.2 6.5 1.77 .45 .63 .81

HS21−036 � HIGH SPEED � CH33−44/48B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 37.8 11.1 2.81 .67 .79 .89 35.6 10.4 3.02 .69 .81 .92 33.8 9.9 3.24 .70 .82 .94 31.9 9.3 3.45 .71 .84 .96

63�F(17�C)

1050 495 39.8 11.7 2.87 .70 .83 .95 37.6 11.0 3.09 .72 .85 .97 35.6 10.4 3.32 .73 .88 .99 33.7 9.9 3.54 .75 .90 1.00(17�C)

1250 590 41.5 12.2 2.93 .73 .87 .99 39.1 11.5 3.15 .75 .90 1.00 37.1 10.9 3.39 .77 .92 1.00 35.1 10.3 3.62 .79 .95 1.00

67�F850 400 41.2 12.1 2.92 .54 .64 .75 39.0 11.4 3.14 .54 .65 .76 37.0 10.8 3.39 .55 .66 .78 35.1 10.3 3.62 .56 .68 .80

67�F(19�C)

1050 495 43.5 12.7 2.99 .55 .67 .79 41.0 12.0 3.23 .56 .69 .81 38.9 11.4 3.48 .57 .70 .83 36.8 10.8 3.72 .58 .72 .85(19�C)

1250 590 45.1 13.2 3.05 .57 .70 .83 42.5 12.5 3.30 .58 .72 .86 40.3 11.8 3.55 .59 .74 .88 38.1 11.2 3.79 .60 .76 .90

71�F850 400 45.0 13.2 3.05 .42 .52 .61 42.7 12.5 3.30 .42 .52 .62 40.6 11.9 3.56 .42 .53 .63 38.6 11.3 3.82 .42 .53 .65

71�F(22�C)

1050 495 47.4 13.9 3.13 .42 .53 .64 44.9 13.2 3.39 .42 .54 .65 42.7 12.5 3.67 .42 .55 .67 40.5 11.9 3.93 .43 .56 .68(22�C)

1250 590 49.2 14.4 3.20 .42 .55 .67 46.6 13.7 3.47 .43 .56 .69 44.2 13.0 3.75 .43 .57 .70 42.0 12.3 4.01 .44 .58 .72

HS21−048 � LOW SPEED � C33−48C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F870 410 27.1 7.9 1.82 .75 .90 1.00 25.7 7.5 2.01 .77 .92 1.00 24.3 7.1 2.20 .79 .95 1.00 22.8 6.7 2.39 .81 .97 1.00

63�F(17�C)

970 460 27.7 8.1 1.83 .77 .93 1.00 26.3 7.7 2.02 .80 .95 1.00 24.9 7.3 2.21 .82 .98 1.00 23.4 6.9 2.40 .85 1.00 1.00(17�C)

1070 505 28.3 8.3 1.82 .80 .96 1.00 26.8 7.9 2.02 .82 .98 1.00 25.4 7.4 2.22 .85 1.00 1.00 24.1 7.1 2.41 .88 1.00 1.00

67�F870 410 29.3 8.6 1.82 .58 .72 .86 27.7 8.1 2.02 .59 .74 .88 26.1 7.6 2.22 .60 .76 .91 24.5 7.2 2.42 .62 .78 .94

67�F(19�C)

970 460 29.8 8.7 1.82 .59 .74 .89 28.2 8.3 2.03 .61 .77 .92 26.6 7.8 2.23 .62 .79 .94 24.9 7.3 2.43 .63 .82 .97(19�C)

1070 505 30.3 8.9 1.82 .61 .77 .92 28.6 8.4 2.03 .62 .79 .94 27.0 7.9 2.23 .64 .82 .97 25.3 7.4 2.43 .65 .85 1.00

71�F870 410 31.7 9.3 1.82 .43 .56 .69 30.0 8.8 2.03 .43 .57 .71 28.3 8.3 2.24 .44 .58 .73 26.6 7.8 2.45 .44 .60 .75

71�F(22�C)

970 460 32.2 9.4 1.82 .43 .58 .72 30.5 8.9 2.03 .44 .59 .74 28.8 8.4 2.25 .44 .60 .76 27.0 7.9 2.46 .45 .62 .79(22�C)

1070 505 32.7 9.6 1.81 .44 .59 .74 31.0 9.1 2.03 .45 .60 .76 29.2 8.6 2.25 .45 .62 .79 27.3 8.0 2.46 .46 .64 .82

HS21−048 � HIGH SPEED � C33−48C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1430 675 48.0 14.1 4.01 .70 .84 .96 45.7 13.4 4.29 .72 .86 .97 43.3 12.7 4.57 .73 .88 .99 41.1 12.0 4.85 .75 .90 1.00

63�F(17�C)

1630 770 49.2 14.4 4.05 .73 .87 .99 46.8 13.7 4.33 .75 .89 1.00 44.4 13.0 4.62 .76 .92 1.00 42.2 12.4 4.92 .78 .94 1.00(17�C)

1830 865 50.1 14.7 4.08 .75 .91 1.00 47.7 14.0 4.38 .77 .93 1.00 45.4 13.3 4.67 .79 .95 1.00 43.2 12.7 4.98 .82 .97 1.00

67�F1430 675 51.5 15.1 4.12 .55 .68 .80 49.0 14.4 4.43 .56 .69 .82 46.6 13.7 4.74 .57 .71 .84 44.2 13.0 5.04 .58 .72 .87

67�F(19�C)

1630 770 52.5 15.4 4.16 .57 .70 .84 50.0 14.7 4.47 .58 .72 .86 47.5 13.9 4.79 .59 .74 .88 45.1 13.2 5.10 .60 .75 .90(19�C)

1830 865 53.4 15.6 4.19 .58 .73 .87 50.8 14.9 4.51 .59 .75 .89 48.3 14.2 4.83 .60 .77 .92 45.8 13.4 5.15 .61 .79 .94

71�F1430 675 55.2 16.2 4.25 .42 .53 .65 52.6 15.4 4.58 .42 .54 .66 50.1 14.7 4.92 .42 .55 .68 47.8 14.0 5.27 .43 .56 .69

71�F(22�C)

1630 770 56.3 16.5 4.28 .42 .55 .68 53.6 15.7 4.62 .43 .56 .69 51.1 15.0 4.97 .43 .57 .71 48.7 14.3 5.32 .43 .58 .73(22�C)

1830 865 57.1 16.7 4.31 .43 .57 .70 54.5 16.0 4.66 .43 .58 .72 51.9 15.2 5.01 .43 .59 .74 49.4 14.5 5.37 .44 .60 .76

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 7 �

Page 8: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS21−048 � LOW SPEED � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F870 410 27.4 8.0 1.82 .75 .90 1.00 25.9 7.6 2.01 .78 .93 1.00 24.5 7.2 2.21 .79 .96 1.00 23.0 6.7 2.40 .82 .98 1.00

63�F(17�C)

970 460 28.0 8.2 1.82 .78 .94 1.00 26.6 7.8 2.02 .80 .96 1.00 25.1 7.4 2.21 .83 .99 1.00 23.6 6.9 2.41 .86 1.00 1.00(17�C)

1070 505 28.6 8.4 1.82 .81 .97 1.00 27.1 7.9 2.02 .83 .99 1.00 25.7 7.5 2.22 .86 1.00 1.00 24.3 7.1 2.42 .89 1.00 1.00

67�F870 410 29.6 8.7 1.82 .58 .73 .86 28.0 8.2 2.02 .60 .74 .89 26.4 7.7 2.23 .61 .77 .92 24.7 7.2 2.43 .62 .79 .95

67�F(19�C)

970 460 30.2 8.9 1.82 .60 .75 .90 28.6 8.4 2.03 .61 .77 .93 26.9 7.9 2.23 .62 .80 .95 25.1 7.4 2.43 .64 .82 .98(19�C)

1070 505 30.7 9.0 1.82 .61 .78 .93 29.0 8.5 2.03 .63 .80 .96 27.3 8.0 2.23 .64 .83 .98 25.5 7.5 2.44 .66 .86 1.00

71�F870 410 32.1 9.4 1.81 .43 .56 .70 30.4 8.9 2.03 .44 .57 .71 28.7 8.4 2.24 .44 .59 .73 26.8 7.9 2.46 .44 .60 .76

71�F(22�C)

970 460 32.7 9.6 1.81 .44 .58 .72 30.9 9.1 2.03 .44 .59 .74 29.1 8.5 2.25 .45 .61 .77 27.3 8.0 2.46 .46 .63 .80(22�C)

1070 505 33.2 9.7 1.81 .44 .60 .75 31.4 9.2 2.03 .45 .61 .77 29.5 8.6 2.25 .46 .63 .80 27.6 8.1 2.47 .46 .65 .83

HS21−048 � HIGH SPEED � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1430 675 48.9 14.3 4.01 .70 .84 .95 46.5 13.6 4.30 .71 .86 .97 44.1 12.9 4.58 .73 .88 .99 41.8 12.3 4.87 .75 .90 1.00

63�F(17�C)

1630 770 50.1 14.7 4.05 .73 .87 .98 47.6 14.0 4.35 .74 .89 1.00 45.3 13.3 4.64 .76 .91 1.00 43.0 12.6 4.94 .78 .94 1.00(17�C)

1830 865 51.1 15.0 4.09 .75 .91 1.00 48.7 14.3 4.39 .77 .93 1.00 46.3 13.6 4.69 .79 .95 1.00 44.0 12.9 5.01 .81 .97 1.00

67�F1430 675 52.5 15.4 4.13 .55 .68 .80 50.0 14.7 4.44 .56 .69 .82 47.5 13.9 4.76 .57 .70 .84 45.1 13.2 5.07 .58 .72 .86

67�F(19�C)

1630 770 53.6 15.7 4.17 .57 .70 .84 51.0 14.9 4.49 .57 .71 .86 48.4 14.2 4.81 .59 .73 .88 46.0 13.5 5.13 .59 .75 .90(19�C)

1830 865 54.5 16.0 4.20 .58 .73 .87 51.9 15.2 4.52 .59 .74 .89 49.3 14.4 4.85 .60 .76 .91 46.8 13.7 5.18 .61 .78 .94

71�F1430 675 56.3 16.5 4.25 .42 .53 .65 53.7 15.7 4.60 .42 .54 .66 51.2 15.0 4.95 .42 .55 .67 48.7 14.3 5.30 .42 .56 .69

71�F(22�C)

1630 770 57.4 16.8 4.29 .42 .55 .67 54.8 16.1 4.64 .42 .56 .69 52.2 15.3 5.00 .43 .57 .70 49.7 14.6 5.36 .43 .58 .72(22�C)

1830 865 58.4 17.1 4.32 .43 .56 .70 55.7 16.3 4.68 .43 .57 .72 53.0 15.5 5.04 .44 .58 .73 50.5 14.8 5.41 .44 .60 .75

HS21−048 � LOW SPEED � CH33−44/48C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F870 410 27.5 8.1 1.82 .75 .89 1.00 26.0 7.6 2.02 .76 .92 1.00 24.6 7.2 2.21 .79 .94 1.00 23.1 6.8 2.40 .81 .97 1.00

63�F(17�C)

970 460 28.1 8.2 1.82 .77 .93 1.00 26.6 7.8 2.02 .80 .95 1.00 25.2 7.4 2.21 .82 .98 1.00 23.7 6.9 2.41 .84 1.00 1.00(17�C)

1070 505 28.7 8.4 1.82 .80 .96 1.00 27.2 8.0 2.02 .82 .98 1.00 25.8 7.6 2.22 .85 1.00 1.00 24.4 7.2 2.42 .88 1.00 1.00

67�F870 410 29.7 8.7 1.82 .58 .72 .86 28.1 8.2 2.02 .59 .74 .88 26.5 7.8 2.23 .60 .76 .91 24.8 7.3 2.43 .61 .78 .94

67�F(19�C)

970 460 30.3 8.9 1.82 .59 .74 .89 28.6 8.4 2.03 .60 .77 .92 27.0 7.9 2.23 .62 .79 .94 25.2 7.4 2.43 .63 .82 .97(19�C)

1070 505 30.8 9.0 1.82 .61 .77 .92 29.1 8.5 2.03 .62 .79 .95 27.4 8.0 2.23 .64 .82 .97 25.6 7.5 2.44 .65 .85 1.00

71�F870 410 32.2 9.4 1.81 .43 .56 .69 30.5 8.9 2.03 .43 .57 .70 28.7 8.4 2.24 .44 .58 .73 26.9 7.9 2.46 .44 .60 .75

71�F(22�C)

970 460 32.8 9.6 1.81 .43 .57 .71 31.0 9.1 2.03 .44 .59 .74 29.2 8.6 2.25 .45 .60 .76 27.4 8.0 2.46 .45 .62 .78(22�C)

1070 505 33.3 9.8 1.81 .44 .59 .74 31.5 9.2 2.03 .44 .60 .76 29.6 8.7 2.25 .45 .62 .79 27.7 8.1 2.47 .46 .64 .82

HS21−048 � HIGH SPEED � CH33−44/48C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1430 675 48.9 14.3 4.02 .70 .84 .95 46.5 13.6 4.31 .71 .86 .97 44.1 12.9 4.59 .73 .88 .99 41.8 12.3 4.88 .75 .90 1.00

63�F(17�C)

1630 770 50.1 14.7 4.06 .73 .87 .98 47.6 14.0 4.36 .74 .89 1.00 45.3 13.3 4.65 .76 .91 1.00 42.9 12.6 4.95 .78 .94 1.00(17�C)

1830 865 51.1 15.0 4.10 .75 .90 1.00 48.6 14.2 4.40 .77 .93 1.00 46.3 13.6 4.71 .79 .95 1.00 43.9 12.9 5.02 .81 .97 1.00

67�F1430 675 52.4 15.4 4.14 .55 .68 .80 49.9 14.6 4.45 .56 .69 .82 47.4 13.9 4.77 .57 .70 .84 45.0 13.2 5.09 .58 .72 .86

67�F(19�C)

1630 770 53.6 15.7 4.18 .57 .70 .84 51.0 14.9 4.50 .57 .71 .86 48.4 14.2 4.82 .59 .73 .88 46.0 13.5 5.15 .59 .75 .90(19�C)

1830 865 54.5 16.0 4.21 .58 .73 .87 51.8 15.2 4.54 .59 .74 .89 49.2 14.4 4.87 .60 .76 .91 46.8 13.7 5.20 .61 .78 .94

71�F1430 675 56.3 16.5 4.27 .42 .53 .65 53.7 15.7 4.61 .42 .54 .66 51.1 15.0 4.96 .42 .55 .67 48.7 14.3 5.32 .42 .56 .69

71�F(22�C)

1630 770 57.4 16.8 4.30 .42 .55 .67 54.8 16.1 4.66 .42 .56 .69 52.2 15.3 5.01 .43 .57 .70 49.7 14.6 5.38 .43 .58 .72(22�C)

1830 865 58.3 17.1 4.33 .43 .56 .70 55.6 16.3 4.69 .43 .57 .72 53.0 15.5 5.06 .44 .58 .73 50.5 14.8 5.43 .44 .60 .75

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 8 �

Page 9: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS21−048 � LOW SPEED � CH33−5060C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F870 410 27.8 8.1 1.82 .75 .90 1.00 26.3 7.7 2.02 .76 .92 1.00 24.8 7.3 2.21 .79 .95 1.00 23.3 6.8 2.41 .81 .97 1.00

63�F(17�C)

970 460 28.5 8.4 1.82 .77 .93 1.00 26.9 7.9 2.02 .79 .96 1.00 25.4 7.4 2.22 .82 .98 1.00 23.9 7.0 2.42 .85 1.00 1.00(17�C)

1070 505 29.1 8.5 1.82 .80 .96 1.00 27.6 8.1 2.02 .82 .98 1.00 26.1 7.6 2.23 .85 1.00 1.00 24.7 7.2 2.43 .88 1.00 1.00

67�F870 410 30.1 8.8 1.82 .58 .72 .85 28.5 8.4 2.03 .59 .73 .88 26.8 7.9 2.23 .60 .76 .91 25.1 7.4 2.44 .61 .78 .94

67�F(19�C)

970 460 30.7 9.0 1.82 .59 .74 .89 29.0 8.5 2.03 .60 .77 .91 27.3 8.0 2.24 .62 .79 .95 25.5 7.5 2.44 .64 .82 .97(19�C)

1070 505 31.2 9.1 1.82 .61 .77 .92 29.5 8.6 2.03 .62 .79 .95 27.7 8.1 2.24 .64 .82 .98 25.9 7.6 2.45 .66 .85 1.00

71�F870 410 32.7 9.6 1.81 .43 .56 .69 30.9 9.1 2.03 .43 .57 .71 29.1 8.5 2.25 .44 .58 .73 27.3 8.0 2.47 .44 .59 .75

71�F(22�C)

970 460 33.3 9.8 1.81 .43 .57 .71 31.5 9.2 2.03 .44 .58 .73 29.6 8.7 2.25 .44 .60 .76 27.7 8.1 2.47 .45 .62 .79(22�C)

1070 505 33.8 9.9 1.80 .44 .59 .74 32.0 9.4 2.03 .44 .60 .76 30.1 8.8 2.25 .45 .62 .79 28.1 8.2 2.48 .46 .64 .82

HS21−048 � HIGH SPEED � CH33−50/60C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1430 675 49.7 14.6 4.04 .70 .83 .95 47.2 13.8 4.34 .71 .85 .97 44.8 13.1 4.64 .73 .87 .99 42.5 12.5 4.93 .75 .90 1.00

63�F(17�C)

1630 770 51.0 14.9 4.09 .73 .87 .98 48.5 14.2 4.39 .74 .89 1.00 46.0 13.5 4.70 .76 .91 1.00 43.7 12.8 5.01 .78 .94 1.00(17�C)

1830 865 52.1 15.3 4.12 .75 .90 1.00 49.6 14.5 4.44 .77 .92 1.00 47.0 13.8 4.76 .79 .95 1.00 44.7 13.1 5.08 .81 .97 1.00

67�F1430 675 53.4 15.6 4.17 .55 .67 .80 50.8 14.9 4.49 .56 .69 .81 48.3 14.2 4.82 .57 .70 .83 45.9 13.5 5.15 .58 .72 .85

67�F(19�C)

1630 770 54.6 16.0 4.21 .57 .70 .83 52.0 15.2 4.54 .57 .71 .85 49.4 14.5 4.87 .58 .73 .88 46.9 13.7 5.21 .59 .75 .90(19�C)

1830 865 55.6 16.3 4.24 .58 .72 .87 52.9 15.5 4.58 .59 .74 .89 50.2 14.7 4.92 .60 .76 .91 47.7 14.0 5.27 .61 .78 .94

71�F1430 675 57.4 16.8 4.30 .42 .53 .65 54.7 16.0 4.65 .42 .54 .66 52.1 15.3 5.02 .42 .55 .67 49.7 14.6 5.39 .42 .56 .69

71�F(22�C)

1630 770 58.6 17.2 4.34 .42 .55 .67 55.9 16.4 4.70 .43 .55 .69 53.2 15.6 5.07 .43 .57 .70 50.7 14.9 5.46 .43 .57 .72(22�C)

1830 865 59.6 17.5 4.37 .43 .56 .70 56.8 16.6 4.74 .43 .57 .71 54.1 15.9 5.12 .43 .58 .73 51.6 15.1 5.51 .44 .59 .75

HS21−060 � LOW SPEED � C33−48C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F990 465 34.3 10.1 2.02 .75 .89 1.00 32.5 9.5 2.21 .76 .92 1.00 30.8 9.0 2.40 .78 .94 1.00 29.1 8.5 2.60 .81 .97 1.00

63�F(17�C)

1090 515 34.9 10.2 2.02 .77 .92 1.00 33.2 9.7 2.21 .79 .94 1.00 31.4 9.2 2.40 .81 .97 1.00 29.7 8.7 2.60 .84 .99 1.00(17�C)

1190 560 35.5 10.4 2.01 .79 .95 1.00 33.8 9.9 2.20 .81 .97 1.00 32.1 9.4 2.39 .84 .99 1.00 30.4 8.9 2.59 .86 1.00 1.00

67�F990 465 36.9 10.8 2.00 .58 .72 .85 35.0 10.3 2.19 .59 .74 .88 33.1 9.7 2.38 .60 .76 .90 31.2 9.1 2.59 .61 .78 .93

67�F(19�C)

1090 515 37.5 11.0 1.99 .59 .74 .88 35.6 10.4 2.18 .60 .76 .91 33.6 9.8 2.38 .61 .78 .93 31.6 9.3 2.58 .63 .81 .96(19�C)

1190 560 38.0 11.1 1.99 .60 .76 .91 36.0 10.6 2.18 .62 .79 .94 34.0 10.0 2.37 .63 .81 .96 32.0 9.4 2.58 .64 .83 .98

71�F990 465 39.8 11.7 1.97 .43 .56 .69 37.9 11.1 2.16 .43 .57 .70 35.9 10.5 2.35 .43 .58 .72 33.8 9.9 2.56 .44 .59 .75

71�F(22�C)

1090 515 40.5 11.9 1.96 .43 .57 .71 38.4 11.3 2.15 .44 .59 .73 36.4 10.7 2.34 .44 .60 .75 34.2 10.0 2.55 .45 .61 .78(22�C)

1190 560 41.0 12.0 1.95 .44 .59 .73 38.9 11.4 2.14 .44 .60 .76 36.8 10.8 2.33 .45 .61 .78 34.6 10.1 2.55 .45 .63 .81

HS21−060 � HIGH SPEED � C33−48C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1580 745 58.8 17.2 4.76 .69 .83 .94 56.0 16.4 5.11 .71 .85 .96 53.2 15.6 5.45 .72 .87 .98 50.1 14.7 5.78 .74 .89 1.00

63�F(17�C)

1780 840 60.1 17.6 4.79 .71 .86 .97 57.3 16.8 5.15 .73 .88 .99 54.4 15.9 5.50 .75 .90 1.00 51.3 15.0 5.84 .77 .93 1.00(17�C)

1980 935 61.3 18.0 4.81 .74 .89 .99 58.5 17.1 5.18 .75 .91 1.00 55.5 16.3 5.54 .77 .93 1.00 52.4 15.4 5.89 .80 .96 1.00

67�F1580 745 63.2 18.5 4.86 .55 .67 .79 60.3 17.7 5.23 .55 .68 .81 57.2 16.8 5.60 .56 .69 .83 54.0 15.8 5.96 .57 .71 .85

67�F(19�C)

1780 840 64.5 18.9 4.88 .56 .69 .82 61.5 18.0 5.26 .56 .70 .84 58.4 17.1 5.64 .57 .72 .86 55.0 16.1 6.00 .58 .74 .89(19�C)

1980 935 65.5 19.2 4.90 .57 .71 .85 62.5 18.3 5.29 .58 .72 .87 59.3 17.4 5.67 .59 .74 .89 55.8 16.4 6.04 .60 .77 .92

71�F1580 745 67.8 19.9 4.94 .41 .53 .64 64.8 19.0 5.35 .42 .53 .65 61.7 18.1 5.75 .42 .54 .66 58.3 17.1 6.14 .42 .55 .68

71�F(22�C)

1780 840 69.1 20.3 4.96 .42 .54 .66 66.0 19.3 5.38 .42 .55 .67 62.9 18.4 5.79 .42 .55 .69 59.4 17.4 6.18 .43 .57 .71(22�C)

1980 935 70.2 20.6 4.98 .42 .55 .68 67.0 19.6 5.40 .42 .56 .70 63.7 18.7 5.82 .43 .57 .71 60.2 17.6 6.21 .43 .58 .74

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 9 �

Page 10: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS21−060 � LOW SPEED � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F990 465 34.7 10.2 2.01 .75 .89 1.00 32.9 9.6 2.20 .76 .91 1.00 31.1 9.1 2.39 .78 .94 1.00 29.4 8.6 2.59 .81 .97 1.00

63�F(17�C)

1090 515 35.3 10.3 2.01 .77 .92 1.00 33.6 9.8 2.20 .79 .94 1.00 31.8 9.3 2.39 .81 .97 1.00 30.0 8.8 2.59 .83 .99 1.00(17�C)

1190 560 36.0 10.6 2.00 .79 .95 1.00 34.2 10.0 2.19 .81 .97 1.00 32.4 9.5 2.38 .84 .99 1.00 30.7 9.0 2.58 .86 1.00 1.00

67�F990 465 37.4 11.0 1.99 .58 .72 .85 35.5 10.4 2.18 .59 .73 .88 33.5 9.8 2.37 .60 .76 .90 31.5 9.2 2.58 .61 .78 .93

67�F(19�C)

1090 515 38.0 11.1 1.98 .59 .74 .88 36.0 10.6 2.17 .60 .76 .91 34.0 10.0 2.36 .61 .78 .93 32.0 9.4 2.57 .63 .81 .96(19�C)

1190 560 38.5 11.3 1.97 .60 .76 .91 36.5 10.7 2.16 .62 .78 .93 34.5 10.1 2.36 .63 .81 .96 32.4 9.5 2.57 .65 .83 .98

71�F990 465 40.4 11.8 1.95 .43 .56 .69 38.4 11.3 2.14 .43 .57 .70 36.3 10.6 2.33 .44 .58 .72 34.2 10.0 2.54 .44 .59 .75

71�F(22�C)

1090 515 41.1 12.0 1.94 .43 .57 .71 39.0 11.4 2.13 .44 .58 .73 36.8 10.8 2.32 .44 .60 .75 34.7 10.2 2.54 .45 .61 .78(22�C)

1190 560 41.6 12.2 1.94 .44 .59 .73 39.4 11.5 2.12 .44 .60 .75 37.3 10.9 2.32 .45 .61 .78 35.1 10.3 2.53 .45 .63 .80

HS21−060 � HIGH SPEED � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1580 745 59.6 17.5 4.76 .70 .83 .95 56.8 16.6 5.12 .72 .85 .96 53.9 15.8 5.47 .73 .87 .98 50.8 14.9 5.81 .75 .89 1.00

63�F(17�C)

1780 840 61.0 17.9 4.79 .72 .86 .97 58.2 17.1 5.16 .74 .88 .99 55.2 16.2 5.52 .76 .90 1.00 52.0 15.2 5.87 .78 .93 1.00(17�C)

1980 935 62.3 18.3 4.82 .75 .89 .99 59.4 17.4 5.19 .76 .91 1.00 56.3 16.5 5.56 .78 .93 1.00 53.1 15.6 5.92 .80 .96 1.00

67�F1580 745 64.2 18.8 4.86 .55 .67 .79 61.2 17.9 5.25 .56 .69 .81 58.2 17.1 5.62 .57 .70 .83 54.8 16.1 5.99 .58 .72 .86

67�F(19�C)

1780 840 65.5 19.2 4.88 .57 .70 .82 62.5 18.3 5.28 .57 .71 .85 59.3 17.4 5.66 .58 .73 .87 55.8 16.4 6.03 .59 .75 .89(19�C)

1980 935 66.6 19.5 4.90 .58 .72 .85 63.5 18.6 5.30 .59 .73 .87 60.2 17.6 5.69 .60 .75 .90 56.7 16.6 6.07 .61 .78 .92

71�F1580 745 69.0 20.2 4.94 .42 .53 .65 65.9 19.3 5.36 .42 .54 .66 62.7 18.4 5.77 .43 .55 .67 59.2 17.3 6.17 .43 .56 .69

71�F(22�C)

1780 840 70.3 20.6 4.98 .43 .55 .67 67.2 19.7 5.39 .43 .56 .68 63.9 18.7 5.81 .43 .56 .70 60.3 17.7 6.21 .43 .58 .72(22�C)

1980 935 71.3 20.9 5.00 .43 .56 .69 68.2 20.0 5.42 .43 .57 .71 64.8 19.0 5.84 .44 .58 .73 61.2 17.9 6.25 .44 .59 .75

HS21−060 � LOW SPEED � C33−60D−2 WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F980 465 34.3 10.1 2.02 .74 .89 1.00 32.5 9.5 2.21 .76 .91 1.00 30.7 9.0 2.40 .78 .94 1.00 29.0 8.5 2.61 .80 .96 1.00

63�F(17�C)

1080 510 34.9 10.2 2.01 .76 .92 1.00 33.2 9.7 2.21 .78 .94 1.00 31.4 9.2 2.40 .81 .96 1.00 29.6 8.7 2.60 .83 .99 1.00(17�C)

1180 555 35.6 10.4 2.01 .79 .94 1.00 33.8 9.9 2.20 .81 .97 1.00 32.0 9.4 2.39 .83 .99 1.00 30.3 8.9 2.60 .86 1.00 1.00

67�F980 465 37.0 10.8 1.99 .58 .71 .85 35.1 10.3 2.18 .58 .73 .87 33.2 9.7 2.38 .60 .75 .90 31.1 9.1 2.59 .61 .77 .93

67�F(19�C)

1080 510 37.6 11.0 1.99 .59 .74 .88 35.6 10.4 2.18 .60 .76 .91 33.7 9.9 2.37 .61 .78 .93 31.6 9.3 2.58 .63 .80 .96(19�C)

1180 555 38.2 11.2 1.98 .60 .76 .91 36.2 10.6 2.17 .61 .78 .93 34.1 10.0 2.36 .63 .80 .96 32.0 9.4 2.58 .64 .83 .98

71�F980 465 40.0 11.7 1.96 .43 .56 .68 38.0 11.1 2.14 .43 .57 .70 35.9 10.5 2.34 .43 .58 .72 33.8 9.9 2.55 .44 .59 .74

71�F(22�C)

1080 510 40.7 11.9 1.95 .43 .57 .71 38.6 11.3 2.13 .44 .58 .73 36.5 10.7 2.33 .44 .59 .75 34.3 10.1 2.54 .45 .61 .77(22�C)

1180 555 41.2 12.1 1.94 .44 .58 .73 39.1 11.5 2.13 .44 .60 .75 36.9 10.8 2.32 .45 .61 .78 34.7 10.2 2.54 .45 .63 .80

HS21−060 � HIGH SPEED � C33−60D−2 WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1600 755 60.6 17.8 4.79 .70 .83 .95 57.7 16.9 5.16 .72 .85 .96 54.7 16.0 5.52 .73 .87 .98 51.5 15.1 5.86 .75 .90 1.00

63�F(17�C)

1800 850 62.0 18.2 4.82 .72 .86 .97 59.1 17.3 5.20 .74 .88 .99 56.0 16.4 5.56 .76 .90 1.00 52.8 15.5 5.92 .78 .93 1.00(17�C)

2000 945 63.3 18.6 4.85 .75 .89 .99 60.3 17.7 5.23 .76 .91 1.00 57.2 16.8 5.61 .78 .93 1.00 53.9 15.8 5.97 .80 .96 1.00

67�F1600 755 65.2 19.1 4.89 .56 .68 .80 62.2 18.2 5.28 .56 .69 .81 59.0 17.3 5.67 .57 .70 .83 55.6 16.3 6.04 .58 .72 .86

67�F(19�C)

1800 850 66.6 19.5 4.91 .57 .70 .82 63.5 18.6 5.31 .57 .71 .84 60.2 17.6 5.71 .58 .73 .87 56.7 16.6 6.09 .59 .75 .89(19�C)

2000 945 67.7 19.8 4.93 .58 .72 .86 64.5 18.9 5.34 .59 .73 .88 61.2 17.9 5.74 .60 .75 .90 57.6 16.9 6.12 .61 .78 .93

71�F1600 755 70.0 20.5 4.98 .42 .54 .65 67.0 19.6 5.40 .42 .54 .66 63.7 18.7 5.82 .43 .55 .67 60.1 17.6 6.23 .43 .56 .69

71�F(22�C)

1800 850 71.3 20.9 5.02 .42 .55 .67 68.2 20.0 5.44 .43 .56 .68 64.9 19.0 5.86 .43 .57 .70 61.2 17.9 6.27 .43 .58 .72(22�C)

2000 945 72.4 21.2 5.05 .43 .56 .69 69.2 20.3 5.47 .43 .57 .71 65.9 19.3 5.88 .44 .58 .73 62.1 18.2 6.30 .44 .59 .75

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 10 �

Page 11: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS21−060 � LOW SPEED � C33−62D−2 WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F980 465 34.8 10.2 2.02 .74 .89 1.00 33.0 9.7 2.21 .76 .92 1.00 31.2 9.1 2.40 .79 .94 1.00 29.4 8.6 2.61 .81 .97 1.00

63�F(17�C)

1080 510 35.6 10.4 2.01 .77 .92 1.00 33.7 9.9 2.20 .79 .95 1.00 31.9 9.3 2.40 .81 .97 1.00 30.1 8.8 2.60 .84 1.00 1.00(17�C)

1180 555 36.2 10.6 2.00 .79 .95 1.00 34.4 10.1 2.19 .81 .97 1.00 32.6 9.6 2.39 .84 1.00 1.00 30.9 9.1 2.59 .87 1.00 1.00

67�F980 465 37.6 11.0 1.99 .58 .72 .85 35.6 10.4 2.18 .59 .73 .87 33.6 9.8 2.37 .60 .75 .90 31.6 9.3 2.59 .61 .78 .93

67�F(19�C)

1080 510 38.3 11.2 1.98 .59 .74 .88 36.2 10.6 2.17 .60 .76 .91 34.2 10.0 2.37 .61 .78 .94 32.1 9.4 2.58 .63 .81 .97(19�C)

1180 555 38.8 11.4 1.97 .60 .77 .92 36.8 10.8 2.16 .62 .79 .94 34.7 10.2 2.36 .63 .81 .97 32.5 9.5 2.57 .65 .84 .99

71�F980 465 40.7 11.9 1.95 .43 .56 .69 38.6 11.3 2.13 .43 .57 .70 36.5 10.7 2.33 .44 .58 .72 34.3 10.1 2.54 .44 .59 .75

71�F(22�C)

1080 510 41.4 12.1 1.94 .43 .57 .71 39.2 11.5 2.12 .44 .58 .73 37.1 10.9 2.32 .44 .60 .75 34.8 10.2 2.54 .45 .61 .78(22�C)

1180 555 41.9 12.3 1.93 .44 .59 .74 39.7 11.6 2.12 .44 .60 .76 37.5 11.0 2.31 .45 .62 .78 35.2 10.3 2.53 .45 .63 .81

HS21−060 � HIGH SPEED � C33−62−2 WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1600 755 62.1 18.2 4.82 .71 .84 .95 59.2 17.3 5.20 .72 .85 .97 56.0 16.4 5.58 .73 .88 .99 52.7 15.4 5.94 .75 .90 1.00

63�F(17�C)

1800 850 63.7 18.7 4.85 .73 .86 .98 60.6 17.8 5.24 .74 .89 .99 57.4 16.8 5.63 .76 .91 1.00 54.1 15.9 5.99 .78 .94 1.00(17�C)

2000 945 65.0 19.0 4.88 .75 .90 1.00 61.9 18.1 5.27 .77 .92 1.00 58.7 17.2 5.67 .79 .94 1.00 55.3 16.2 6.05 .81 .97 1.00

67�F1600 755 66.8 19.6 4.91 .56 .68 .80 63.7 18.7 5.32 .56 .69 .82 60.4 17.7 5.72 .57 .71 .84 56.8 16.6 6.11 .58 .73 .86

67�F(19�C)

1800 850 68.2 20.0 4.94 .57 .70 .83 65.0 19.0 5.35 .58 .72 .85 61.6 18.1 5.76 .59 .73 .87 58.0 17.0 6.16 .60 .75 .90(19�C)

2000 945 69.2 20.3 4.98 .58 .73 .86 66.1 19.4 5.39 .59 .74 .88 62.7 18.4 5.79 .60 .76 .91 58.9 17.3 6.19 .61 .78 .93

71�F1600 755 71.6 21.0 5.04 .42 .54 .65 68.4 20.0 5.46 .42 .54 .66 65.1 19.1 5.88 .43 .55 .68 61.5 18.0 6.29 .43 .56 .69

71�F(22�C)

1800 850 72.9 21.4 5.07 .43 .55 .67 69.6 20.4 5.51 .43 .56 .69 66.3 19.4 5.93 .43 .57 .70 62.7 18.4 6.34 .44 .58 .72(22�C)

2000 945 74.0 21.7 5.10 .43 .56 .70 70.7 20.7 5.54 .43 .57 .72 67.2 19.7 5.97 .44 .59 .73 63.5 18.6 6.38 .44 .60 .75

HS21−060 � LOW SPEED � CH33−48C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F990 465 34.6 10.1 2.01 .74 .89 1.00 32.8 9.6 2.21 .76 .91 1.00 31.0 9.1 2.40 .78 .94 1.00 29.2 8.6 2.60 .81 .97 1.00

63�F(17�C)

1090 515 35.3 10.3 2.01 .77 .92 1.00 33.5 9.8 2.20 .79 .94 1.00 31.7 9.3 2.39 .81 .97 1.00 29.9 8.8 2.60 .83 .99 1.00(17�C)

1190 560 35.9 10.5 2.00 .79 .95 1.00 34.1 10.0 2.19 .81 .97 1.00 32.3 9.5 2.39 .84 .99 1.00 30.6 9.0 2.59 .86 1.00 1.00

67�F990 465 37.4 11.0 1.99 .57 .71 .85 35.4 10.4 2.18 .58 .73 .88 33.4 9.8 2.37 .60 .75 .90 31.4 9.2 2.58 .61 .78 .93

67�F(19�C)

1090 515 38.0 11.1 1.98 .59 .74 .88 36.0 10.6 2.17 .60 .76 .91 34.0 10.0 2.36 .61 .78 .93 31.9 9.3 2.58 .63 .81 .96(19�C)

1190 560 38.5 11.3 1.97 .60 .76 .91 36.5 10.7 2.16 .61 .78 .93 34.5 10.1 2.36 .63 .80 .96 32.3 9.5 2.57 .64 .83 .99

71�F990 465 40.5 11.9 1.95 .43 .56 .68 38.4 11.3 2.13 .43 .57 .70 36.3 10.6 2.33 .44 .58 .72 34.1 10.0 2.54 .44 .59 .74

71�F(22�C)

1090 515 41.1 12.0 1.94 .43 .57 .71 39.0 11.4 2.13 .44 .58 .73 36.8 10.8 2.32 .44 .60 .75 34.6 10.1 2.53 .45 .61 .77(22�C)

1190 560 41.7 12.2 1.93 .44 .59 .73 39.5 11.6 2.12 .44 .60 .75 37.3 10.9 2.31 .45 .61 .78 35.0 10.3 2.53 .45 .63 .80

HS21−060 � HIGH SPEED � CH33−48C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1580 745 60.2 17.6 4.78 .70 .83 .94 57.3 16.8 5.14 .72 .85 .96 54.4 15.9 5.49 .73 .87 .98 51.2 15.0 5.83 .75 .89 1.00

63�F(17�C)

1780 840 61.6 18.1 4.81 .72 .86 .97 58.7 17.2 5.18 .74 .88 .99 55.7 16.3 5.54 .76 .90 1.00 52.4 15.4 5.89 .78 .93 1.00(17�C)

1980 935 62.8 18.4 4.83 .75 .89 .99 59.9 17.6 5.21 .76 .91 1.00 56.8 16.6 5.58 .78 .93 1.00 53.6 15.7 5.94 .80 .96 1.00

67�F1580 745 64.7 19.0 4.87 .55 .68 .79 61.8 18.1 5.26 .56 .69 .81 58.6 17.2 5.64 .57 .70 .83 55.2 16.2 6.01 .58 .72 .86

67�F(19�C)

1780 840 66.1 19.4 4.90 .57 .70 .82 63.0 18.5 5.29 .57 .71 .84 59.8 17.5 5.68 .58 .73 .87 56.3 16.5 6.05 .60 .75 .89(19�C)

1980 935 67.2 19.7 4.92 .58 .72 .85 64.1 18.8 5.32 .59 .73 .88 60.8 17.8 5.71 .60 .75 .90 57.2 16.8 6.09 .61 .77 .92

71�F1580 745 69.6 20.4 4.96 .42 .53 .65 66.5 19.5 5.38 .42 .54 .66 63.2 18.5 5.79 .43 .55 .67 59.7 17.5 6.19 .43 .56 .69

71�F(22�C)

1780 840 70.9 20.8 4.99 .42 .55 .67 67.8 19.9 5.41 .43 .55 .68 64.4 18.9 5.83 .43 .57 .70 60.8 17.8 6.23 .43 .58 .72(22�C)

1980 935 71.9 21.1 5.02 .43 .56 .69 68.8 20.2 5.44 .43 .57 .71 65.4 19.2 5.86 .44 .58 .72 61.7 18.1 6.27 .44 .59 .75

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 11 �

Page 12: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS21−060 � LOW SPEED � CH33−50/60C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F990 465 35.2 10.3 2.01 .75 .89 1.00 33.3 9.8 2.21 .76 .91 1.00 31.5 9.2 2.40 .78 .94 1.00 29.7 8.7 2.60 .81 .97 1.00

63�F(17�C)

1090 515 35.8 10.5 2.01 .76 .92 1.00 34.0 10.0 2.20 .79 .94 1.00 32.2 9.4 2.39 .81 .97 1.00 30.4 8.9 2.60 .84 .99 1.00(17�C)

1190 560 36.5 10.7 2.00 .79 .95 1.00 34.7 10.2 2.19 .81 .97 1.00 32.9 9.6 2.39 .83 .99 1.00 31.1 9.1 2.59 .86 1.00 1.00

67�F990 465 38.0 11.1 1.99 .58 .71 .85 36.0 10.6 2.18 .59 .73 .88 34.0 10.0 2.37 .60 .75 .90 31.9 9.3 2.58 .61 .78 .93

67�F(19�C)

1090 515 38.6 11.3 1.98 .59 .74 .88 36.6 10.7 2.17 .60 .76 .90 34.5 10.1 2.36 .61 .78 .93 32.4 9.5 2.58 .63 .81 .96(19�C)

1190 560 39.2 11.5 1.97 .60 .76 .91 37.1 10.9 2.16 .61 .78 .94 35.0 10.3 2.36 .63 .81 .96 32.9 9.6 2.57 .65 .83 .99

71�F990 465 41.1 12.0 1.95 .43 .56 .68 39.0 11.4 2.13 .43 .57 .70 36.9 10.8 2.33 .43 .58 .72 34.7 10.2 2.54 .44 .59 .74

71�F(22�C)

1090 515 41.8 12.3 1.94 .43 .57 .71 39.6 11.6 2.13 .44 .58 .73 37.4 11.0 2.32 .44 .60 .75 35.2 10.3 2.53 .45 .61 .78(22�C)

1190 560 42.4 12.4 1.93 .44 .58 .73 40.1 11.8 2.12 .44 .60 .75 37.9 11.1 2.31 .45 .61 .78 35.6 10.4 2.53 .46 .63 .80

HS21−060 � HIGH SPEED � CH33−50/60C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1580 745 61.0 17.9 4.80 .70 .83 .94 58.1 17.0 5.17 .71 .85 .96 55.1 16.1 5.53 .73 .87 .98 51.8 15.2 5.88 .75 .89 1.00

63�F(17�C)

1780 840 62.5 18.3 4.83 .72 .86 .97 59.6 17.5 5.21 .73 .88 .99 56.5 16.6 5.58 .75 .90 1.00 53.1 15.6 5.94 .77 .92 1.00(17�C)

1980 935 63.9 18.7 4.85 .74 .88 .99 60.8 17.8 5.24 .76 .91 1.00 57.6 16.9 5.62 .78 .93 1.00 54.3 15.9 5.99 .80 .95 1.00

67�F1580 745 65.7 19.3 4.89 .55 .67 .79 62.7 18.4 5.29 .56 .68 .81 59.5 17.4 5.68 .57 .70 .83 56.0 16.4 6.06 .58 .72 .85

67�F(19�C)

1780 840 67.2 19.7 4.92 .56 .69 .82 64.0 18.8 5.33 .57 .71 .84 60.8 17.8 5.72 .58 .72 .86 57.1 16.7 6.11 .59 .74 .89(19�C)

1980 935 68.4 20.0 4.94 .58 .71 .85 65.1 19.1 5.35 .58 .73 .87 61.8 18.1 5.76 .60 .75 .89 58.1 17.0 6.15 .61 .77 .92

71�F1580 745 70.6 20.7 5.00 .42 .53 .64 67.5 19.8 5.42 .42 .54 .65 64.2 18.8 5.84 .43 .55 .67 60.6 17.8 6.25 .43 .56 .69

71�F(22�C)

1780 840 71.9 21.1 5.04 .42 .55 .67 68.8 20.2 5.46 .43 .55 .68 65.4 19.2 5.88 .43 .56 .70 61.8 18.1 6.29 .43 .57 .71(22�C)

1980 935 73.0 21.4 5.07 .43 .56 .69 69.8 20.5 5.50 .43 .57 .70 66.4 19.5 5.92 .44 .58 .72 62.8 18.4 6.33 .44 .59 .74

HS21−060 � LOW SPEED � CH33−60D−2F WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F980 465 34.6 10.1 2.02 .73 .88 1.00 32.8 9.6 2.21 .75 .91 1.00 31.0 9.1 2.40 .77 .93 1.00 29.2 8.6 2.60 .80 .96 1.00

63�F(17�C)

1080 510 35.3 10.3 2.01 .76 .91 1.00 33.5 9.8 2.20 .78 .94 1.00 31.7 9.3 2.39 .80 .96 1.00 29.9 8.8 2.60 .82 .99 1.00(17�C)

1180 555 35.9 10.5 2.00 .78 .94 1.00 34.1 10.0 2.20 .80 .97 1.00 32.3 9.5 2.39 .82 .99 1.00 30.6 9.0 2.59 .85 1.00 1.00

67�F980 465 37.4 11.0 1.99 .57 .70 .85 35.4 10.4 2.18 .58 .72 .87 33.5 9.8 2.37 .59 .74 .90 31.4 9.2 2.58 .61 .77 .92

67�F(19�C)

1080 510 38.0 11.1 1.98 .58 .73 .87 36.0 10.6 2.17 .59 .75 .90 34.0 10.0 2.37 .61 .77 .93 31.9 9.3 2.58 .62 .80 .96(19�C)

1180 555 38.5 11.3 1.98 .60 .75 .90 36.5 10.7 2.17 .61 .77 .93 34.5 10.1 2.36 .62 .80 .96 32.3 9.5 2.57 .64 .82 .98

71�F980 465 40.4 11.8 1.95 .42 .55 .68 38.4 11.3 2.14 .43 .56 .69 36.3 10.6 2.34 .43 .57 .71 34.1 10.0 2.55 .44 .59 .73

71�F(22�C)

1080 510 41.0 12.0 1.95 .43 .57 .70 38.9 11.4 2.13 .43 .58 .72 36.8 10.8 2.33 .44 .59 .74 34.6 10.1 2.54 .44 .60 .76(22�C)

1180 555 41.6 12.2 1.94 .43 .58 .72 39.4 11.5 2.13 .44 .59 .74 37.3 10.9 2.32 .44 .61 .77 35.0 10.3 2.53 .45 .62 .79

HS21−060 � HIGH SPEED � CH33−60D−2F WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1600 755 60.6 17.8 4.79 .70 .83 .94 57.8 16.9 5.16 .71 .85 .96 54.8 16.1 5.52 .72 .87 .98 51.6 15.1 5.86 .74 .89 1.00

63�F(17�C)

1800 850 62.1 18.2 4.82 .72 .86 .97 59.1 17.3 5.20 .73 .88 .99 56.1 16.4 5.56 .75 .90 1.00 52.8 15.5 5.92 .77 .93 1.00(17�C)

2000 945 63.3 18.6 4.85 .74 .89 .99 60.3 17.7 5.23 .76 .91 1.00 57.2 16.8 5.60 .78 .93 1.00 53.9 15.8 5.97 .80 .96 1.00

67�F1600 755 65.3 19.1 4.89 .55 .67 .79 62.3 18.3 5.28 .56 .68 .81 59.1 17.3 5.67 .56 .70 .83 55.6 16.3 6.04 .57 .71 .85

67�F(19�C)

1800 850 66.6 19.5 4.91 .56 .69 .82 63.5 18.6 5.31 .57 .70 .84 60.3 17.7 5.71 .58 .72 .86 56.7 16.6 6.09 .59 .74 .89(19�C)

2000 945 67.8 19.9 4.93 .57 .71 .85 64.6 18.9 5.34 .58 .73 .87 61.2 17.9 5.74 .59 .75 .89 57.6 16.9 6.12 .61 .77 .92

71�F1600 755 70.1 20.5 4.98 .42 .53 .64 67.0 19.6 5.40 .42 .54 .65 63.7 18.7 5.82 .42 .54 .67 60.2 17.6 6.22 .42 .55 .68

71�F(22�C)

1800 850 71.4 20.9 5.02 .42 .54 .66 68.3 20.0 5.44 .42 .55 .68 64.9 19.0 5.86 .43 .56 .69 61.3 18.0 6.27 .43 .57 .71(22�C)

2000 945 72.4 21.2 5.05 .43 .56 .69 69.3 20.3 5.47 .43 .56 .70 65.9 19.3 5.88 .43 .58 .72 62.2 18.2 6.30 .44 .59 .74

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 12 �

Page 13: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS21−060 � LOW SPEED � CH33−62D−2F WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F980 465 34.6 10.1 2.02 .73 .88 1.00 32.8 9.6 2.21 .75 .91 1.00 31.0 9.1 2.40 .77 .93 1.00 29.1 8.5 2.61 .80 .96 1.00

63�F(17�C)

1080 510 35.3 10.3 2.01 .76 .91 1.00 33.5 9.8 2.20 .78 .94 1.00 31.6 9.3 2.40 .80 .97 1.00 29.9 8.8 2.60 .83 .99 1.00(17�C)

1180 555 35.9 10.5 2.00 .78 .95 1.00 34.1 10.0 2.20 .80 .97 1.00 32.3 9.5 2.39 .82 .99 1.00 30.6 9.0 2.60 .85 1.00 1.00

67�F980 465 37.4 11.0 1.99 .57 .70 .84 35.4 10.4 2.18 .58 .72 .87 33.5 9.8 2.37 .59 .74 .89 31.4 9.2 2.59 .60 .77 .92

67�F(19�C)

1080 510 38.1 11.2 1.98 .58 .73 .87 36.0 10.6 2.17 .59 .75 .90 34.0 10.0 2.37 .61 .77 .93 31.9 9.3 2.58 .62 .80 .96(19�C)

1180 555 38.6 11.3 1.97 .60 .75 .90 36.6 10.7 2.16 .61 .77 .93 34.5 10.1 2.36 .62 .80 .96 32.3 9.5 2.57 .64 .82 .98

71�F980 465 40.5 11.9 1.95 .42 .55 .67 38.4 11.3 2.14 .43 .56 .69 36.3 10.6 2.33 .43 .57 .71 34.1 10.0 2.54 .44 .59 .73

71�F(22�C)

1080 510 41.2 12.1 1.94 .43 .56 .70 39.0 11.4 2.13 .43 .57 .72 36.9 10.8 2.32 .43 .59 .74 34.6 10.1 2.54 .44 .60 .76(22�C)

1180 555 41.8 12.3 1.93 .43 .58 .72 39.6 11.6 2.12 .44 .59 .74 37.4 11.0 2.31 .44 .60 .77 35.1 10.3 2.53 .45 .62 .79

HS21−060 � HIGH SPEED � CH33−62D−2F WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1600 755 61.5 18.0 4.79 .70 .83 .94 58.5 17.1 5.17 .72 .85 .96 55.5 16.3 5.54 .73 .87 .98 52.2 15.3 5.89 .75 .89 1.00

63�F(17�C)

1800 850 63.0 18.5 4.82 .72 .86 .97 60.0 17.6 5.21 .74 .88 .99 56.8 16.6 5.59 .75 .90 1.00 53.4 15.6 5.95 .78 .93 1.00(17�C)

2000 945 64.3 18.8 4.85 .74 .89 .99 61.2 17.9 5.24 .76 .91 1.00 58.0 17.0 5.63 .78 .93 1.00 54.6 16.0 6.00 .80 .96 1.00

67�F1600 755 66.2 19.4 4.89 .55 .67 .79 63.1 18.5 5.29 .56 .69 .81 59.9 17.6 5.69 .57 .70 .83 56.4 16.5 6.07 .58 .72 .85

67�F(19�C)

1800 850 67.6 19.8 4.91 .57 .69 .82 64.5 18.9 5.33 .57 .71 .84 61.1 17.9 5.73 .58 .73 .86 57.5 16.9 6.12 .59 .75 .89(19�C)

2000 945 68.7 20.1 4.95 .58 .72 .85 65.6 19.2 5.35 .59 .73 .87 62.2 18.2 5.76 .59 .75 .89 58.5 17.1 6.16 .61 .77 .92

71�F1600 755 71.0 20.8 5.01 .42 .53 .65 67.9 19.9 5.43 .42 .54 .66 64.6 18.9 5.85 .43 .55 .67 61.1 17.9 6.26 .43 .56 .69

71�F(22�C)

1800 850 72.4 21.2 5.04 .42 .55 .67 69.2 20.3 5.47 .43 .55 .68 65.8 19.3 5.90 .43 .56 .70 62.2 18.2 6.30 .43 .58 .72(22�C)

2000 945 73.5 21.5 5.07 .43 .56 .69 70.2 20.6 5.51 .43 .57 .71 66.8 19.6 5.93 .44 .58 .72 63.1 18.5 6.35 .44 .59 .74

HS26−024 � C33−24A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTemperat

ure

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbure

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 23.5 6.9 1.46 .72 .86 .97 22.7 6.7 1.64 .73 .87 .98 21.9 6.4 1.85 .74 .89 1.00 21.0 6.2 2.11 .76 .91 1.00

63�F(17�C)

850 400 24.5 7.2 1.46 .78 .94 1.00 23.7 6.9 1.64 .80 .95 1.00 22.9 6.7 1.86 .81 .97 1.00 21.9 6.4 2.11 .83 .99 1.00(17�C)

1050 495 25.4 7.4 1.46 .84 .99 1.00 24.6 7.2 1.65 .86 1.00 1.00 23.8 7.0 1.86 .87 1.00 1.00 22.9 6.7 2.11 .90 1.00 1.00

67�F650 305 25.0 7.3 1.46 .56 .69 .82 24.1 7.1 1.64 .57 .71 .84 23.2 6.8 1.86 .58 .72 .85 22.2 6.5 2.11 .58 .73 .87

67�F(19�C)

850 400 25.8 7.6 1.47 .60 .76 .91 25.0 7.3 1.65 .61 .77 .93 24.0 7.0 1.86 .61 .79 .94 23.0 6.7 2.11 .63 .81 .96(19�C)

1050 495 26.4 7.7 1.47 .64 .82 .97 25.5 7.5 1.65 .64 .84 .98 24.6 7.2 1.87 .66 .85 .99 23.5 6.9 2.11 .67 .88 1.00

71�F650 305 26.6 7.8 1.47 .42 .55 .67 25.7 7.5 1.65 .42 .55 .68 24.8 7.3 1.86 .43 .56 .69 23.7 6.9 2.11 .43 .57 .71

71�F(22�C)

850 400 27.5 8.1 1.48 .44 .59 .73 26.5 7.8 1.66 .44 .59 .75 25.5 7.5 1.87 .44 .61 .77 24.4 7.2 2.12 .45 .62 .78(22�C)

1050 495 28.0 8.2 1.48 .45 .63 .80 27.0 7.9 1.66 .45 .64 .82 26.0 7.6 1.87 .46 .65 .83 24.8 7.3 2.12 .47 .67 .85

HS26−024 � C33−30A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 23.9 7.0 1.46 .72 .86 .97 23.1 6.8 1.64 .73 .87 .99 22.2 6.5 1.86 .74 .88 1.00 21.3 6.2 2.11 .75 .90 1.00

63�F(17�C)

850 400 25.0 7.3 1.47 .78 .94 1.00 24.2 7.1 1.65 .79 .95 1.00 23.3 6.8 1.86 .81 .96 1.00 22.3 6.5 2.11 .82 .98 1.00(17�C)

1050 495 25.9 7.6 1.47 .84 .99 1.00 25.1 7.4 1.65 .86 1.00 1.00 24.2 7.1 1.86 .88 1.00 1.00 23.3 6.8 2.12 .90 1.00 1.00

67�F650 305 25.4 7.4 1.47 .56 .69 .82 24.6 7.2 1.65 .57 .70 .83 23.6 6.9 1.86 .57 .71 .85 22.6 6.6 2.12 .58 .73 .87

67�F(19�C)

850 400 26.4 7.7 1.47 .60 .75 .91 25.4 7.4 1.66 .60 .77 .92 24.5 7.2 1.87 .62 .78 .94 23.4 6.9 2.12 .63 .81 .96(19�C)

1050 495 27.0 7.9 1.48 .64 .82 .97 26.0 7.6 1.66 .64 .84 .98 25.0 7.3 1.87 .66 .85 1.00 23.9 7.0 2.12 .67 .88 1.00

71�F650 305 27.1 7.9 1.48 .42 .54 .66 26.2 7.7 1.66 .42 .55 .68 25.2 7.4 1.87 .42 .56 .69 24.1 7.1 2.12 .43 .57 .70

71�F(22�C)

850 400 28.0 8.2 1.49 .43 .59 .74 27.0 7.9 1.67 .44 .59 .75 26.0 7.6 1.87 .44 .60 .76 24.9 7.3 2.13 .45 .61 .78(22�C)

1050 495 28.6 8.4 1.49 .45 .63 .80 27.6 8.1 1.67 .46 .63 .82 26.5 7.8 1.88 .46 .65 .84 25.3 7.4 2.13 .47 .67 .86

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 13 �

Page 14: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS26−024 � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 24.2 7.1 1.46 .71 .85 .97 23.4 6.9 1.65 .72 .87 .98 22.5 6.6 1.86 .73 .88 1.00 21.5 6.3 2.11 .75 .90 1.00

63�F(17�C)

850 400 25.4 7.4 1.47 .78 .93 1.00 24.5 7.2 1.65 .79 .95 1.00 23.6 6.9 1.86 .81 .97 1.00 22.5 6.6 2.11 .83 .99 1.00(17�C)

1050 495 26.3 7.7 1.47 .84 1.00 1.00 25.5 7.5 1.66 .86 1.00 1.00 24.6 7.2 1.87 .88 1.00 1.00 23.6 6.9 2.12 .90 1.00 1.00

67�F650 305 25.8 7.6 1.47 .56 .69 .82 24.9 7.3 1.65 .56 .70 .83 24.0 7.0 1.86 .57 .71 .84 22.9 6.7 2.12 .58 .73 .87

67�F(19�C)

850 400 26.8 7.9 1.48 .59 .75 .90 25.8 7.6 1.66 .61 .77 .92 24.8 7.3 1.87 .61 .78 .94 23.7 6.9 2.12 .63 .80 .96(19�C)

1050 495 27.4 8.0 1.48 .64 .82 .97 26.5 7.8 1.67 .65 .84 .99 25.4 7.4 1.88 .66 .86 1.00 24.2 7.1 2.13 .67 .88 1.00

71�F650 305 27.5 8.1 1.48 .42 .54 .66 26.6 7.8 1.67 .42 .55 .67 25.6 7.5 1.87 .43 .56 .68 24.4 7.2 2.12 .43 .56 .70

71�F(22�C)

850 400 28.5 8.4 1.49 .43 .58 .73 27.5 8.1 1.67 .44 .59 .75 26.4 7.7 1.88 .44 .60 .76 25.2 7.4 2.13 .44 .61 .78(22�C)

1050 495 29.1 8.5 1.50 .45 .63 .80 28.0 8.2 1.68 .46 .64 .82 26.9 7.9 1.89 .46 .65 .83 25.7 7.5 2.13 .47 .66 .86

HS26−024 � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 24.9 7.3 1.47 .71 .84 .97 24.0 7.0 1.65 .72 .86 .98 23.0 6.7 1.86 .73 .88 1.00 22.0 6.4 2.11 .75 .90 1.00

63�F(17�C)

850 400 26.1 7.6 1.48 .77 .93 1.00 25.1 7.4 1.66 .79 .95 1.00 24.2 7.1 1.87 .81 .97 1.00 23.1 6.8 2.12 .82 .99 1.00(17�C)

1050 495 27.1 7.9 1.48 .84 1.00 1.00 26.2 7.7 1.66 .85 1.00 1.00 25.3 7.4 1.87 .87 1.00 1.00 24.3 7.1 2.12 .90 1.00 1.00

67�F650 305 26.6 7.8 1.48 .55 .68 .81 25.6 7.5 1.66 .56 .69 .82 24.6 7.2 1.87 .57 .70 .84 23.5 6.9 2.12 .58 .72 .86

67�F(19�C)

850 400 27.7 8.1 1.49 .60 .75 .90 26.6 7.8 1.67 .60 .76 .92 25.6 7.5 1.88 .61 .78 .94 24.4 7.2 2.13 .62 .80 .96(19�C)

1050 495 28.4 8.3 1.49 .63 .81 .97 27.3 8.0 1.67 .64 .83 .99 26.2 7.7 1.88 .66 .85 1.00 25.0 7.3 2.13 .67 .88 1.00

71�F650 305 28.4 8.3 1.49 .42 .54 .66 27.4 8.0 1.67 .42 .55 .66 26.3 7.7 1.88 .43 .55 .68 25.1 7.4 2.13 .43 .56 .69

71�F(22�C)

850 400 29.5 8.6 1.50 .43 .58 .72 28.4 8.3 1.68 .44 .59 .74 27.2 8.0 1.89 .44 .60 .75 26.0 7.6 2.14 .45 .61 .78(22�C)

1050 495 30.1 8.8 1.51 .45 .62 .79 29.0 8.5 1.69 .45 .63 .81 27.8 8.1 1.90 .46 .65 .83 26.5 7.8 2.14 .46 .66 .86

HS26−024 � CH33−24/30A−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 23.7 6.9 1.46 .72 .86 .97 22.9 6.7 1.64 .73 .87 .99 22.0 6.4 1.85 .74 .89 1.00 21.1 6.2 2.11 .75 .91 1.00

63�F(17�C)

850 400 24.7 7.2 1.46 .78 .94 1.00 23.9 7.0 1.65 .79 .95 1.00 23.0 6.7 1.86 .81 .97 1.00 22.1 6.5 2.11 .83 .98 1.00(17�C)

1050 495 25.6 7.5 1.47 .84 .99 1.00 24.8 7.3 1.65 .86 1.00 1.00 24.0 7.0 1.86 .87 1.00 1.00 23.0 6.7 2.11 .90 1.00 1.00

67�F650 305 25.2 7.4 1.46 .56 .69 .82 24.3 7.1 1.65 .57 .70 .83 23.4 6.9 1.86 .58 .72 .85 22.4 6.6 2.11 .58 .73 .87

67�F(19�C)

850 400 26.1 7.6 1.47 .60 .75 .91 25.2 7.4 1.65 .61 .77 .92 24.2 7.1 1.86 .61 .79 .94 23.1 6.8 2.11 .63 .81 .96(19�C)

1050 495 26.7 7.8 1.47 .64 .82 .97 25.7 7.5 1.66 .65 .84 .98 24.8 7.3 1.87 .66 .85 .99 23.7 6.9 2.12 .67 .87 1.00

71�F650 305 26.8 7.9 1.47 .42 .55 .67 25.9 7.6 1.66 .42 .55 .68 24.9 7.3 1.87 .43 .56 .69 23.9 7.0 2.12 .43 .57 .70

71�F(22�C)

850 400 27.7 8.1 1.48 .44 .59 .74 26.7 7.8 1.66 .44 .59 .75 25.7 7.5 1.87 .44 .60 .77 24.6 7.2 2.12 .45 .62 .79(22�C)

1050 495 28.3 8.3 1.48 .45 .63 .80 27.2 8.0 1.67 .45 .64 .82 26.2 7.7 1.87 .46 .65 .83 25.1 7.4 2.12 .47 .66 .86

HS26−024 � CH33−36A/B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 24.1 7.1 1.46 .71 .85 .96 23.3 6.8 1.64 .71 .86 .98 22.4 6.6 1.86 .72 .87 .99 21.4 6.3 2.11 .74 .89 1.00

63�F(17�C)

850 400 25.3 7.4 1.47 .77 .92 1.00 24.4 7.2 1.65 .78 .94 1.00 23.5 6.9 1.86 .80 .96 1.00 22.4 6.6 2.11 .81 .98 1.00(17�C)

1050 495 26.2 7.7 1.47 .82 .98 1.00 25.3 7.4 1.65 .84 1.00 1.00 24.4 7.2 1.86 .86 1.00 1.00 23.5 6.9 2.11 .88 1.00 1.00

67�F650 305 25.8 7.6 1.47 .56 .68 .81 24.9 7.3 1.65 .56 .69 .82 23.9 7.0 1.86 .57 .70 .84 22.9 6.7 2.11 .57 .71 .86

67�F(19�C)

850 400 26.8 7.9 1.48 .59 .74 .89 25.8 7.6 1.66 .60 .76 .91 24.8 7.3 1.87 .61 .77 .93 23.7 6.9 2.12 .61 .79 .95(19�C)

1050 495 27.5 8.1 1.48 .63 .80 .96 26.5 7.8 1.66 .63 .82 .97 25.4 7.4 1.87 .64 .84 .99 24.2 7.1 2.13 .66 .86 1.00

71�F650 305 27.5 8.1 1.48 .42 .54 .66 26.6 7.8 1.66 .42 .54 .66 25.6 7.5 1.87 .42 .55 .68 24.4 7.2 2.12 .43 .56 .69

71�F(22�C)

850 400 28.5 8.4 1.49 .43 .58 .72 27.5 8.1 1.67 .44 .58 .73 26.4 7.7 1.88 .44 .59 .75 25.3 7.4 2.13 .44 .60 .76(22�C)

1050 495 29.2 8.6 1.49 .44 .61 .78 28.1 8.2 1.67 .45 .62 .80 27.0 7.9 1.89 .45 .63 .82 25.8 7.6 2.13 .46 .65 .84

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 14 �

Page 15: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS26−024 � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 24.5 7.2 1.47 .71 .84 .96 23.6 6.9 1.65 .71 .86 .98 22.7 6.7 1.86 .72 .87 1.00 21.7 6.4 2.11 .74 .89 1.00

63�F(17�C)

850 400 25.6 7.5 1.47 .77 .93 1.00 24.7 7.2 1.65 .78 .94 1.00 23.8 7.0 1.87 .79 .96 1.00 22.7 6.7 2.12 .81 .98 1.00(17�C)

1050 495 26.6 7.8 1.48 .83 .99 1.00 25.7 7.5 1.66 .84 1.00 1.00 24.8 7.3 1.87 .86 1.00 1.00 23.8 7.0 2.12 .88 1.00 1.00

67�F650 305 26.1 7.6 1.48 .56 .68 .81 25.2 7.4 1.66 .56 .69 .82 24.3 7.1 1.87 .57 .70 .83 23.2 6.8 2.12 .57 .71 .86

67�F(19�C)

850 400 27.2 8.0 1.48 .59 .74 .89 26.2 7.7 1.67 .60 .76 .91 25.2 7.4 1.87 .61 .77 .93 24.0 7.0 2.12 .62 .79 .95(19�C)

1050 495 27.9 8.2 1.49 .62 .81 .96 26.9 7.9 1.67 .64 .82 .98 25.8 7.6 1.88 .65 .84 1.00 24.6 7.2 2.13 .66 .87 1.00

71�F650 305 28.0 8.2 1.49 .42 .54 .65 27.0 7.9 1.67 .42 .54 .66 26.0 7.6 1.88 .42 .55 .67 24.8 7.3 2.13 .43 .56 .69

71�F(22�C)

850 400 29.0 8.5 1.50 .43 .58 .72 28.0 8.2 1.68 .43 .58 .73 26.9 7.9 1.89 .44 .59 .75 25.6 7.5 2.14 .44 .61 .77(22�C)

1050 495 29.7 8.7 1.50 .45 .62 .78 28.6 8.4 1.68 .45 .63 .80 27.5 8.1 1.89 .45 .64 .82 26.2 7.7 2.14 .46 .65 .84

HS26−030 � C33−30A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 29.5 8.6 1.86 .70 .83 .95 28.6 8.4 2.09 .71 .84 .96 27.6 8.1 2.35 .72 .86 .97 26.5 7.8 2.66 .73 .88 .99

63�F(17�C)

950 450 30.7 9.0 1.86 .75 .90 1.00 29.7 8.7 2.10 .76 .91 1.00 28.7 8.4 2.36 .77 .93 1.00 27.6 8.1 2.67 .79 .95 1.00(17�C)

1150 545 31.7 9.3 1.87 .80 .95 1.00 30.6 9.0 2.11 .81 .97 1.00 29.6 8.7 2.37 .83 .98 1.00 28.5 8.4 2.67 .84 .99 1.00

67�F750 355 31.5 9.2 1.86 .55 .68 .80 30.4 8.9 2.10 .56 .68 .81 29.3 8.6 2.36 .56 .70 .82 28.2 8.3 2.66 .57 .71 .84

67�F(19�C)

950 450 32.6 9.6 1.87 .58 .73 .86 31.4 9.2 2.11 .59 .74 .88 30.3 8.9 2.37 .59 .75 .90 29.1 8.5 2.67 .60 .77 .92(19�C)

1150 545 33.3 9.8 1.87 .61 .78 .93 32.1 9.4 2.11 .62 .79 .94 30.9 9.1 2.38 .63 .81 .96 29.7 8.7 2.68 .64 .83 .97

71�F750 355 33.7 9.9 1.87 .42 .53 .65 32.5 9.5 2.11 .42 .54 .66 31.3 9.2 2.38 .42 .55 .67 30.1 8.8 2.67 .42 .55 .68

71�F(22�C)

950 450 34.8 10.2 1.88 .43 .56 .70 33.5 9.8 2.12 .43 .57 .71 32.3 9.5 2.38 .43 .58 .73 31.0 9.1 2.68 .44 .59 .74(22�C)

1150 545 35.5 10.4 1.88 .44 .60 .75 34.2 10.0 2.13 .44 .61 .77 32.9 9.6 2.39 .45 .62 .79 31.6 9.3 2.69 .45 .63 .80

HS26−030 � C33−36A/B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 29.8 8.7 1.86 .71 .84 .96 28.8 8.4 2.09 .72 .86 .97 27.8 8.1 2.35 .73 .87 .98 26.7 7.8 2.65 .74 .89 1.00

63�F(17�C)

950 450 31.1 9.1 1.86 .76 .91 1.00 30.0 8.8 2.10 .77 .92 1.00 28.9 8.5 2.36 .79 .94 1.00 27.8 8.1 2.66 .80 .96 1.00(17�C)

1150 545 32.1 9.4 1.87 .81 .97 1.00 31.0 9.1 2.10 .82 .98 1.00 29.9 8.8 2.36 .84 .99 1.00 28.8 8.4 2.66 .86 1.00 1.00

67�F750 355 31.8 9.3 1.86 .56 .69 .81 30.7 9.0 2.10 .57 .70 .82 29.6 8.7 2.36 .57 .71 .83 28.4 8.3 2.66 .58 .72 .85

67�F(19�C)

950 450 33.0 9.7 1.87 .59 .74 .88 31.8 9.3 2.11 .60 .75 .89 30.6 9.0 2.37 .60 .76 .91 29.4 8.6 2.67 .62 .78 .93(19�C)

1150 545 33.8 9.9 1.87 .62 .79 .94 32.5 9.5 2.12 .63 .80 .95 31.3 9.2 2.38 .64 .82 .97 30.0 8.8 2.67 .65 .84 .99

71�F750 355 34.1 10.0 1.87 .43 .54 .66 32.8 9.6 2.12 .43 .55 .67 31.6 9.3 2.38 .43 .56 .68 30.4 8.9 2.68 .43 .56 .69

71�F(22�C)

950 450 35.3 10.3 1.87 .43 .57 .71 33.9 9.9 2.12 .44 .58 .72 32.6 9.6 2.39 .44 .59 .74 31.3 9.2 2.68 .45 .60 .76(22�C)

1150 545 36.1 10.6 1.88 .45 .60 .76 34.7 10.2 2.13 .45 .61 .78 33.3 9.8 2.39 .45 .63 .80 31.9 9.3 2.68 .46 .64 .81

HS26−030 � C33−38A/B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 30.9 9.1 1.86 .71 .83 .95 29.8 8.7 2.10 .72 .85 .97 28.7 8.4 2.36 .73 .86 .98 27.6 8.1 2.66 .74 .88 1.00

63�F(17�C)

950 450 32.4 9.5 1.87 .76 .90 1.00 31.2 9.1 2.11 .77 .92 1.00 30.0 8.8 2.37 .78 .94 1.00 28.8 8.4 2.67 .80 .95 1.00(17�C)

1150 545 33.5 9.8 1.87 .81 .96 1.00 32.2 9.4 2.12 .82 .98 1.00 31.0 9.1 2.38 .84 .99 1.00 29.8 8.7 2.67 .85 1.00 1.00

67�F750 355 33.2 9.7 1.87 .56 .68 .80 31.9 9.3 2.12 .56 .69 .81 30.7 9.0 2.38 .57 .70 .83 29.5 8.6 2.67 .58 .71 .85

67�F(19�C)

950 450 34.5 10.1 1.88 .59 .73 .87 33.2 9.7 2.12 .59 .74 .89 31.9 9.3 2.39 .60 .76 .90 30.5 8.9 2.68 .61 .77 .92(19�C)

1150 545 35.5 10.4 1.88 .62 .78 .93 34.0 10.0 2.13 .62 .80 .95 32.7 9.6 2.39 .64 .81 .97 31.3 9.2 2.68 .65 .83 .98

71�F750 355 35.6 10.4 1.88 .43 .54 .65 34.2 10.0 2.13 .43 .54 .66 32.9 9.6 2.39 .43 .55 .67 31.6 9.3 2.68 .43 .56 .68

71�F(22�C)

950 450 36.9 10.8 1.88 .43 .57 .70 35.5 10.4 2.14 .44 .58 .72 34.1 10.0 2.40 .44 .59 .73 32.6 9.6 2.69 .44 .60 .75(22�C)

1150 545 37.9 11.1 1.88 .45 .60 .76 36.3 10.6 2.14 .45 .61 .77 34.8 10.2 2.41 .45 .62 .79 33.3 9.8 2.70 .46 .64 .81

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 15 �

Page 16: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS26−030 � CH33−24/30A−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 29.4 8.6 1.86 .70 .83 .95 28.4 8.3 2.09 .70 .85 .96 27.5 8.1 2.36 .71 .86 .98 26.4 7.7 2.66 .73 .87 .99

63�F(17�C)

950 450 30.5 8.9 1.87 .74 .90 1.00 29.5 8.6 2.10 .76 .91 1.00 28.6 8.4 2.36 .77 .92 1.00 27.5 8.1 2.67 .78 .95 1.00(17�C)

1150 545 31.5 9.2 1.87 .79 .95 1.00 30.5 8.9 2.11 .81 .96 1.00 29.4 8.6 2.37 .82 .98 1.00 28.4 8.3 2.67 .84 .99 1.00

67�F750 355 31.3 9.2 1.87 .55 .67 .79 30.3 8.9 2.10 .55 .68 .81 29.2 8.6 2.37 .56 .69 .82 28.1 8.2 2.67 .56 .70 .84

67�F(19�C)

950 450 32.3 9.5 1.87 .57 .72 .87 31.2 9.1 2.11 .58 .73 .88 30.1 8.8 2.37 .59 .75 .90 28.9 8.5 2.67 .60 .76 .92(19�C)

1150 545 33.1 9.7 1.87 .60 .77 .93 31.9 9.3 2.11 .61 .79 .94 30.8 9.0 2.38 .62 .80 .96 29.5 8.6 2.68 .63 .82 .97

71�F750 355 33.4 9.8 1.88 .42 .53 .65 32.3 9.5 2.12 .42 .53 .65 31.2 9.1 2.38 .42 .54 .66 30.0 8.8 2.68 .42 .55 .68

71�F(22�C)

950 450 34.5 10.1 1.88 .42 .56 .70 33.3 9.8 2.12 .43 .57 .71 32.1 9.4 2.39 .43 .57 .72 30.8 9.0 2.68 .43 .59 .74(22�C)

1150 545 35.2 10.3 1.88 .43 .59 .75 33.9 9.9 2.13 .44 .60 .77 32.7 9.6 2.39 .44 .61 .78 31.4 9.2 2.69 .45 .62 .80

HS26−030 � CH33−36A/B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 29.7 8.7 1.85 .69 .82 .94 28.7 8.4 2.09 .70 .83 .95 27.7 8.1 2.35 .71 .85 .97 26.6 7.8 2.66 .72 .86 .98

63�F(17�C)

950 450 31.0 9.1 1.86 .73 .88 .99 29.9 8.8 2.10 .75 .90 1.00 28.8 8.4 2.36 .76 .92 1.00 27.7 8.1 2.66 .78 .93 1.00(17�C)

1150 545 32.0 9.4 1.87 .78 .94 1.00 30.9 9.1 2.10 .80 .95 1.00 29.8 8.7 2.36 .81 .97 1.00 28.7 8.4 2.66 .83 .98 1.00

67�F750 355 31.8 9.3 1.86 .55 .67 .78 30.7 9.0 2.10 .55 .67 .80 29.6 8.7 2.36 .56 .68 .81 28.4 8.3 2.66 .56 .69 .83

67�F(19�C)

950 450 33.0 9.7 1.87 .57 .71 .85 31.8 9.3 2.11 .58 .72 .87 30.6 9.0 2.37 .59 .73 .88 29.4 8.6 2.67 .59 .75 .90(19�C)

1150 545 33.8 9.9 1.87 .60 .76 .91 32.6 9.6 2.12 .61 .77 .93 31.3 9.2 2.38 .62 .79 .94 30.1 8.8 2.67 .63 .80 .96

71�F750 355 34.0 10.0 1.87 .42 .53 .64 32.8 9.6 2.11 .42 .53 .65 31.6 9.3 2.38 .42 .54 .66 30.4 8.9 2.67 .42 .54 .67

71�F(22�C)

950 450 35.3 10.3 1.87 .42 .56 .68 33.9 9.9 2.12 .43 .56 .70 32.7 9.6 2.39 .43 .57 .71 31.3 9.2 2.68 .43 .58 .73(22�C)

1150 545 36.1 10.6 1.88 .44 .58 .74 34.7 10.2 2.13 .44 .59 .75 33.4 9.8 2.39 .44 .60 .77 32.0 9.4 2.68 .45 .62 .78

HS26−030 � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 30.6 9.0 1.86 .69 .81 .94 29.5 8.6 2.10 .70 .83 .95 28.5 8.4 2.36 .71 .84 .97 27.3 8.0 2.66 .72 .86 .98

63�F(17�C)

950 450 32.0 9.4 1.87 .73 .88 .99 30.8 9.0 2.10 .75 .90 1.00 29.7 8.7 2.37 .76 .91 1.00 28.5 8.4 2.66 .77 .93 1.00(17�C)

1150 545 33.1 9.7 1.87 .78 .94 1.00 31.8 9.3 2.11 .80 .96 1.00 30.7 9.0 2.37 .81 .97 1.00 29.5 8.6 2.67 .83 .99 1.00

67�F750 355 32.8 9.6 1.87 .55 .66 .78 31.6 9.3 2.11 .55 .67 .79 30.4 8.9 2.37 .56 .68 .81 29.2 8.6 2.67 .56 .69 .82

67�F(19�C)

950 450 34.1 10.0 1.87 .57 .71 .85 32.8 9.6 2.12 .58 .72 .87 31.6 9.3 2.38 .59 .73 .88 30.3 8.9 2.67 .59 .75 .90(19�C)

1150 545 35.1 10.3 1.88 .60 .76 .91 33.7 9.9 2.12 .61 .77 .93 32.4 9.5 2.39 .62 .79 .95 31.0 9.1 2.68 .63 .81 .96

71�F750 355 35.2 10.3 1.87 .42 .53 .64 33.9 9.9 2.12 .42 .53 .64 32.6 9.6 2.39 .42 .54 .65 31.3 9.2 2.68 .42 .54 .66

71�F(22�C)

950 450 36.5 10.7 1.88 .43 .55 .68 35.1 10.3 2.13 .43 .56 .70 33.7 9.9 2.39 .43 .57 .71 32.4 9.5 2.69 .43 .58 .73(22�C)

1150 545 37.5 11.0 1.88 .43 .58 .73 36.0 10.6 2.14 .44 .59 .75 34.5 10.1 2.40 .44 .60 .77 33.0 9.7 2.70 .45 .62 .78

HS26−036 � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 35.2 10.3 2.21 .74 .88 .99 34.0 10.0 2.49 .75 .89 .99 32.8 9.6 2.81 .76 .91 1.00 31.5 9.2 3.18 .77 .92 1.00

63�F(17�C)

1220 575 36.3 10.6 2.21 .78 .93 1.00 35.1 10.3 2.49 .79 .94 1.00 33.8 9.9 2.82 .80 .96 1.00 32.5 9.5 3.19 .82 .97 1.00(17�C)

1420 670 37.2 10.9 2.22 .82 .97 1.00 36.0 10.6 2.50 .83 .98 1.00 34.7 10.2 2.82 .85 .99 1.00 33.4 9.8 3.19 .87 1.00 1.00

67�F1020 480 37.4 11.0 2.22 .57 .71 .84 36.2 10.6 2.50 .58 .72 .86 34.8 10.2 2.82 .59 .74 .87 33.4 9.8 3.19 .60 .75 .89

67�F(19�C)

1220 575 38.3 11.2 2.22 .60 .75 .90 37.0 10.8 2.50 .61 .77 .91 35.6 10.4 2.82 .62 .78 .93 34.1 10.0 3.20 .62 .80 .95(19�C)

1420 670 39.0 11.4 2.23 .62 .80 .94 37.6 11.0 2.51 .63 .81 .96 36.2 10.6 2.83 .64 .83 .97 34.7 10.2 3.20 .66 .85 .99

71�F1020 480 40.0 11.7 2.23 .43 .56 .69 38.6 11.3 2.51 .43 .56 .70 37.2 10.9 2.83 .43 .57 .71 35.7 10.5 3.20 .43 .58 .72

71�F(22�C)

1220 575 40.9 12.0 2.24 .44 .58 .73 39.4 11.5 2.52 .44 .59 .74 37.9 11.1 2.84 .44 .60 .76 36.4 10.7 3.21 .45 .61 .78(22�C)

1420 670 41.5 12.2 2.24 .45 .61 .78 40.0 11.7 2.52 .45 .62 .79 38.5 11.3 2.84 .45 .63 .81 36.9 10.8 3.22 .46 .64 .82

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 16 �

Page 17: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS26−036 � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 36.5 10.7 2.22 .72 .86 .98 35.2 10.3 2.50 .73 .88 .99 33.9 9.9 2.82 .74 .89 1.00 32.5 9.5 3.18 .76 .91 1.00

63�F(17�C)

1220 575 37.6 11.0 2.22 .76 .92 1.00 36.3 10.6 2.50 .78 .94 1.00 35.0 10.3 2.82 .79 .95 1.00 33.6 9.8 3.19 .81 .97 1.00(17�C)

1420 670 38.7 11.3 2.23 .81 .97 1.00 37.3 10.9 2.51 .82 .98 1.00 36.0 10.6 2.83 .84 .99 1.00 34.6 10.1 3.20 .86 1.00 1.00

67�F1020 480 38.9 11.4 2.23 .56 .70 .83 37.5 11.0 2.51 .57 .71 .84 36.1 10.6 2.83 .58 .72 .86 34.6 10.1 3.21 .59 .73 .88

67�F(19�C)

1220 575 39.9 11.7 2.24 .59 .74 .89 38.5 11.3 2.52 .60 .75 .90 37.0 10.8 2.84 .60 .77 .92 35.4 10.4 3.21 .62 .79 .94(19�C)

1420 670 40.7 11.9 2.24 .61 .78 .94 39.3 11.5 2.52 .62 .80 .95 37.7 11.0 2.84 .63 .82 .97 36.1 10.6 3.22 .64 .83 .99

71�F1020 480 41.6 12.2 2.24 .42 .55 .67 40.2 11.8 2.53 .42 .55 .68 38.6 11.3 2.85 .43 .56 .70 37.0 10.8 3.22 .43 .57 .71

71�F(22�C)

1220 575 42.6 12.5 2.25 .43 .57 .72 41.1 12.0 2.53 .43 .58 .73 39.5 11.6 2.86 .44 .59 .74 37.8 11.1 3.23 .44 .60 .76(22�C)

1420 670 43.4 12.7 2.26 .44 .60 .76 41.8 12.3 2.54 .45 .61 .77 40.2 11.8 2.86 .45 .62 .79 38.5 11.3 3.24 .45 .63 .81

HS26−036 � CH33−36A/B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 35.0 10.3 2.20 .72 .86 .98 33.8 9.9 2.48 .73 .87 .98 32.6 9.6 2.80 .74 .89 .99 31.3 9.2 3.17 .75 .91 1.00

63�F(17�C)

1220 575 36.1 10.6 2.21 .76 .91 1.00 34.9 10.2 2.49 .77 .93 1.00 33.6 9.8 2.81 .78 .94 1.00 32.3 9.5 3.18 .80 .96 1.00(17�C)

1420 670 37.0 10.8 2.22 .80 .96 1.00 35.8 10.5 2.49 .81 .97 1.00 34.5 10.1 2.82 .83 .98 1.00 33.2 9.7 3.18 .84 .99 1.00

67�F1020 480 37.4 11.0 2.22 .56 .69 .83 36.1 10.6 2.49 .57 .70 .84 34.8 10.2 2.81 .57 .71 .86 33.3 9.8 3.18 .58 .73 .87

67�F(19�C)

1220 575 38.3 11.2 2.22 .58 .73 .88 37.0 10.8 2.50 .59 .74 .89 35.6 10.4 2.82 .60 .76 .91 34.1 10.0 3.19 .61 .78 .93(19�C)

1420 670 39.0 11.4 2.22 .61 .77 .93 37.6 11.0 2.50 .62 .79 .94 36.2 10.6 2.82 .62 .81 .96 34.7 10.2 3.20 .64 .82 .97

71�F1020 480 39.9 11.7 2.23 .42 .54 .67 38.6 11.3 2.51 .42 .55 .68 37.1 10.9 2.83 .43 .56 .69 35.6 10.4 3.20 .43 .57 .70

71�F(22�C)

1220 575 40.8 12.0 2.23 .43 .57 .71 39.4 11.5 2.51 .43 .58 .72 38.0 11.1 2.83 .44 .58 .74 36.4 10.7 3.21 .44 .60 .75(22�C)

1420 670 41.5 12.2 2.24 .44 .59 .75 40.1 11.8 2.52 .44 .60 .76 38.6 11.3 2.84 .44 .61 .78 37.0 10.8 3.21 .45 .62 .80

HS26−036 � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 36.4 10.7 2.21 .72 .86 .98 35.2 10.3 2.49 .73 .88 .99 33.8 9.9 2.81 .75 .89 1.00 32.5 9.5 3.18 .76 .91 1.00

63�F(17�C)

1220 575 37.6 11.0 2.22 .76 .91 1.00 36.3 10.6 2.50 .78 .93 1.00 34.9 10.2 2.82 .79 .95 1.00 33.5 9.8 3.19 .81 .96 1.00(17�C)

1420 670 38.5 11.3 2.23 .80 .96 1.00 37.2 10.9 2.50 .82 .97 1.00 35.9 10.5 2.82 .83 .98 1.00 34.5 10.1 3.19 .85 1.00 1.00

67�F1020 480 38.9 11.4 2.22 .57 .70 .83 37.6 11.0 2.50 .57 .71 .84 36.1 10.6 2.83 .58 .72 .86 34.6 10.1 3.20 .59 .73 .87

67�F(19�C)

1220 575 39.9 11.7 2.23 .59 .74 .88 38.5 11.3 2.51 .60 .75 .90 37.0 10.8 2.83 .61 .76 .91 35.5 10.4 3.21 .62 .78 .93(19�C)

1420 670 40.7 11.9 2.24 .61 .78 .93 39.2 11.5 2.52 .62 .79 .94 37.7 11.0 2.84 .63 .81 .96 36.1 10.6 3.21 .64 .83 .98

71�F1020 480 41.6 12.2 2.24 .43 .55 .67 40.2 11.8 2.52 .43 .55 .68 38.7 11.3 2.84 .43 .56 .69 37.1 10.9 3.22 .43 .57 .71

71�F(22�C)

1220 575 42.7 12.5 2.24 .43 .57 .71 41.2 12.1 2.53 .43 .58 .73 39.6 11.6 2.85 .44 .59 .74 37.9 11.1 3.23 .44 .60 .76(22�C)

1420 670 43.4 12.7 2.25 .44 .60 .76 41.9 12.3 2.53 .45 .61 .77 40.2 11.8 2.86 .45 .62 .79 38.5 11.3 3.23 .45 .63 .81

HS26−036 � CH33−44/48B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 36.8 10.8 2.21 .72 .86 .98 35.5 10.4 2.49 .73 .87 .99 34.2 10.0 2.81 .74 .89 1.00 32.7 9.6 3.17 .76 .91 1.00

63�F(17�C)

1220 575 38.0 11.1 2.21 .76 .91 1.00 36.7 10.8 2.49 .77 .93 1.00 35.3 10.3 2.81 .79 .94 1.00 33.8 9.9 3.18 .81 .96 1.00(17�C)

1420 670 39.0 11.4 2.22 .80 .96 1.00 37.6 11.0 2.50 .82 .97 1.00 36.2 10.6 2.82 .83 .99 1.00 34.8 10.2 3.19 .85 1.00 1.00

67�F1020 480 39.4 11.5 2.22 .57 .70 .82 38.0 11.1 2.50 .57 .71 .84 36.5 10.7 2.82 .58 .72 .86 35.0 10.3 3.19 .59 .73 .87

67�F(19�C)

1220 575 40.4 11.8 2.23 .59 .74 .88 39.0 11.4 2.51 .59 .75 .90 37.4 11.0 2.83 .60 .76 .92 35.8 10.5 3.20 .61 .78 .94(19�C)

1420 670 41.3 12.1 2.23 .61 .78 .93 39.8 11.7 2.51 .62 .79 .95 38.2 11.2 2.83 .63 .81 .96 36.5 10.7 3.21 .64 .83 .98

71�F1020 480 42.1 12.3 2.24 .43 .55 .67 40.7 11.9 2.52 .43 .55 .68 39.1 11.5 2.84 .43 .56 .69 37.5 11.0 3.21 .43 .57 .71

71�F(22�C)

1220 575 43.2 12.7 2.24 .43 .57 .71 41.7 12.2 2.53 .44 .58 .72 40.1 11.8 2.85 .44 .59 .74 38.4 11.3 3.22 .44 .60 .76(22�C)

1420 670 44.1 12.9 2.25 .44 .60 .75 42.5 12.5 2.53 .44 .61 .77 40.8 12.0 2.85 .45 .62 .79 39.0 11.4 3.22 .45 .63 .81

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 17 �

Page 18: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS26−042 � C33−44C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 41.7 12.2 2.68 .78 .93 1.00 40.3 11.8 3.03 .79 .94 1.00 38.7 11.3 3.43 .80 .96 1.00 37.2 10.9 3.87 .82 .98 1.00

63�F(17�C)

1330 630 42.9 12.6 2.69 .82 .98 1.00 41.4 12.1 3.04 .83 1.00 1.00 39.8 11.7 3.44 .85 1.00 1.00 38.2 11.2 3.88 .87 1.00 1.00(17�C)

1530 720 43.9 12.9 2.70 .86 1.00 1.00 42.4 12.4 3.05 .87 1.00 1.00 40.8 12.0 3.44 .89 1.00 1.00 39.1 11.5 3.89 .91 1.00 1.00

67�F1130 535 44.5 13.0 2.70 .62 .76 .89 43.0 12.6 3.05 .62 .76 .91 41.3 12.1 3.45 .63 .78 .92 39.6 11.6 3.90 .64 .79 .94

67�F(19�C)

1330 630 45.6 13.4 2.71 .64 .79 .94 44.0 12.9 3.06 .65 .81 .96 42.2 12.4 3.46 .65 .82 .98 40.4 11.8 3.91 .66 .84 1.00(19�C)

1530 720 46.4 13.6 2.72 .66 .83 .99 44.7 13.1 3.07 .67 .85 1.00 43.0 12.6 3.47 .68 .86 1.00 41.1 12.0 3.91 .69 .88 1.00

71�F1130 535 47.5 13.9 2.73 .47 .60 .73 45.8 13.4 3.08 .47 .60 .74 44.1 12.9 3.48 .47 .61 .75 42.3 12.4 3.93 .47 .62 .76

71�F(22�C)

1330 630 48.6 14.2 2.74 .47 .62 .77 46.8 13.7 3.09 .47 .63 .78 45.0 13.2 3.49 .48 .64 .79 43.1 12.6 3.94 .48 .65 .81(22�C)

1530 720 49.4 14.5 2.74 .48 .64 .80 47.6 14.0 3.10 .49 .65 .82 45.8 13.4 3.50 .49 .66 .84 43.8 12.8 3.95 .49 .68 .86

HS26−042 � C33−48C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 42.2 12.4 2.68 .71 .84 .96 40.8 12.0 3.03 .72 .85 .97 39.2 11.5 3.43 .73 .87 .99 37.6 11.0 3.87 .74 .89 1.00

63�F(17�C)

1330 630 43.4 12.7 2.69 .74 .89 1.00 41.9 12.3 3.04 .75 .90 1.00 40.3 11.8 3.44 .76 .92 1.00 38.6 11.3 3.88 .78 .94 1.00(17�C)

1530 720 44.4 13.0 2.70 .77 .93 1.00 42.9 12.6 3.05 .78 .94 1.00 41.2 12.1 3.44 .80 .96 1.00 39.6 11.6 3.89 .82 .98 1.00

67�F1130 535 45.0 13.2 2.70 .56 .68 .81 43.5 12.7 3.05 .56 .69 .82 41.8 12.3 3.45 .57 .70 .84 40.0 11.7 3.90 .57 .72 .86

67�F(19�C)

1330 630 46.1 13.5 2.71 .57 .71 .85 44.5 13.0 3.06 .58 .73 .87 42.7 12.5 3.46 .59 .74 .89 40.9 12.0 3.91 .60 .76 .91(19�C)

1530 720 46.9 13.7 2.72 .59 .75 .90 45.2 13.2 3.07 .60 .76 .91 43.5 12.7 3.47 .61 .78 .93 41.6 12.2 3.91 .62 .80 .95

71�F1130 535 48.0 14.1 2.73 .42 .54 .65 46.4 13.6 3.08 .42 .54 .66 44.6 13.1 3.48 .42 .55 .67 42.8 12.5 3.93 .43 .56 .69

71�F(22�C)

1330 630 49.1 14.4 2.74 .43 .56 .69 47.4 13.9 3.09 .43 .56 .70 45.6 13.4 3.49 .43 .57 .72 43.6 12.8 3.94 .43 .58 .73(22�C)

1530 720 50.0 14.7 2.74 .43 .58 .73 48.2 14.1 3.10 .44 .59 .74 46.3 13.6 3.50 .44 .60 .76 44.3 13.0 3.95 .44 .61 .77

HS26−042 � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 42.7 12.5 2.69 .70 .84 .96 41.2 12.1 3.04 .71 .85 .97 39.6 11.6 3.43 .72 .87 .99 37.9 11.1 3.88 .74 .89 1.00

63�F(17�C)

1330 630 43.9 12.9 2.70 .74 .88 1.00 42.3 12.4 3.05 .75 .90 1.00 40.7 11.9 3.44 .76 .92 1.00 39.0 11.4 3.89 .78 .94 1.00(17�C)

1530 720 44.9 13.2 2.71 .77 .93 1.00 43.3 12.7 3.06 .79 .95 1.00 41.7 12.2 3.45 .80 .96 1.00 39.9 11.7 3.90 .82 .98 1.00

67�F1130 535 45.6 13.4 2.71 .55 .68 .80 43.9 12.9 3.06 .56 .69 .82 42.2 12.4 3.46 .57 .70 .83 40.4 11.8 3.91 .57 .71 .85

67�F(19�C)

1330 630 46.7 13.7 2.72 .57 .71 .85 45.0 13.2 3.07 .58 .72 .87 43.2 12.7 3.47 .59 .74 .89 41.4 12.1 3.92 .60 .75 .91(19�C)

1530 720 47.5 13.9 2.73 .59 .75 .90 45.8 13.4 3.08 .60 .76 .91 44.0 12.9 3.48 .61 .78 .93 42.1 12.3 3.93 .62 .80 .95

71�F1130 535 48.6 14.2 2.74 .42 .54 .65 46.9 13.7 3.09 .42 .54 .66 45.1 13.2 3.49 .42 .55 .67 43.2 12.7 3.94 .43 .56 .69

71�F(22�C)

1330 630 49.8 14.6 2.75 .43 .56 .69 48.0 14.1 3.10 .43 .56 .70 46.1 13.5 3.50 .43 .57 .71 44.2 13.0 3.95 .43 .58 .73(22�C)

1530 720 50.6 14.8 2.76 .43 .58 .72 48.8 14.3 3.11 .44 .59 .74 46.9 13.7 3.51 .44 .60 .75 44.8 13.1 3.96 .44 .61 .77

HS26−042 � CH33−48C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 42.7 12.5 2.68 .70 .84 .96 41.2 12.1 3.03 .71 .85 .97 39.6 11.6 3.42 .72 .87 .98 38.0 11.1 3.87 .74 .89 1.00

63�F(17�C)

1330 630 43.9 12.9 2.69 .74 .89 1.00 42.4 12.4 3.04 .75 .90 1.00 40.8 12.0 3.43 .76 .92 1.00 39.0 11.4 3.88 .78 .94 1.00(17�C)

1530 720 45.0 13.2 2.70 .77 .93 1.00 43.4 12.7 3.05 .78 .95 1.00 41.7 12.2 3.45 .80 .96 1.00 40.0 11.7 3.89 .82 .98 1.00

67�F1130 535 45.6 13.4 2.70 .56 .68 .81 44.0 12.9 3.05 .56 .69 .82 42.3 12.4 3.45 .57 .70 .83 40.5 11.9 3.90 .57 .71 .85

67�F(19�C)

1330 630 46.7 13.7 2.71 .57 .71 .85 45.0 13.2 3.07 .58 .73 .87 43.3 12.7 3.46 .59 .74 .89 41.4 12.1 3.91 .60 .75 .91(19�C)

1530 720 47.6 14.0 2.72 .59 .75 .90 45.9 13.5 3.07 .60 .76 .91 44.0 12.9 3.47 .61 .78 .93 42.1 12.3 3.92 .62 .80 .95

71�F1130 535 48.7 14.3 2.73 .42 .54 .65 47.0 13.8 3.08 .42 .54 .66 45.2 13.2 3.48 .42 .55 .67 43.3 12.7 3.93 .43 .56 .69

71�F(22�C)

1330 630 49.8 14.6 2.74 .43 .56 .69 48.0 14.1 3.09 .43 .57 .70 46.2 13.5 3.49 .43 .57 .71 44.2 13.0 3.94 .43 .58 .73(22�C)

1530 720 50.7 14.9 2.75 .43 .58 .72 48.8 14.3 3.10 .44 .59 .74 46.9 13.7 3.50 .44 .60 .75 44.9 13.2 3.95 .44 .61 .77

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 18 �

Page 19: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS26−042 � CH33−50/60C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 43.1 12.6 2.69 .70 .84 .96 41.5 12.2 3.04 .71 .85 .98 39.9 11.7 3.43 .72 .87 .99 38.2 11.2 3.88 .74 .89 1.00

63�F(17�C)

1330 630 44.4 13.0 2.70 .74 .88 1.00 42.8 12.5 3.05 .75 .90 1.00 41.1 12.0 3.45 .76 .92 1.00 39.3 11.5 3.89 .78 .94 1.00(17�C)

1530 720 45.4 13.3 2.71 .77 .93 1.00 43.8 12.8 3.06 .79 .95 1.00 42.0 12.3 3.46 .80 .97 1.00 40.3 11.8 3.91 .82 .98 1.00

67�F1130 535 46.0 13.5 2.72 .56 .68 .80 44.4 13.0 3.07 .56 .69 .82 42.6 12.5 3.46 .57 .70 .83 40.8 12.0 3.91 .57 .71 .85

67�F(19�C)

1330 630 47.2 13.8 2.72 .57 .71 .85 45.5 13.3 3.08 .58 .72 .87 43.7 12.8 3.48 .59 .74 .89 41.7 12.2 3.93 .60 .76 .91(19�C)

1530 720 48.2 14.1 2.73 .59 .75 .90 46.4 13.6 3.09 .60 .76 .92 44.5 13.0 3.49 .61 .78 .94 42.5 12.5 3.93 .62 .80 .96

71�F1130 535 49.2 14.4 2.75 .42 .54 .65 47.4 13.9 3.10 .42 .54 .66 45.6 13.4 3.49 .42 .55 .67 43.7 12.8 3.94 .42 .56 .68

71�F(22�C)

1330 630 50.4 14.8 2.75 .43 .56 .69 48.6 14.2 3.11 .43 .56 .70 46.6 13.7 3.51 .43 .57 .71 44.6 13.1 3.96 .43 .58 .73(22�C)

1530 720 51.4 15.1 2.76 .43 .58 .72 49.4 14.5 3.12 .43 .59 .74 47.4 13.9 3.52 .44 .60 .75 45.3 13.3 3.96 .44 .61 .77

HS26−048 � C33−48C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1330 630 49.2 14.4 3.17 .71 .85 .97 47.4 13.9 3.58 .72 .86 .98 45.6 13.4 4.05 .73 .88 .99 43.7 12.8 4.58 .75 .90 1.00

63�F(17�C)

1630 770 50.9 14.9 3.18 .75 .91 1.00 49.1 14.4 3.59 .77 .92 1.00 47.1 13.8 4.07 .78 .94 1.00 45.2 13.2 4.61 .80 .96 1.00(17�C)

1930 910 52.3 15.3 3.20 .80 .96 1.00 50.4 14.8 3.61 .82 .97 1.00 48.5 14.2 4.08 .83 .98 1.00 46.7 13.7 4.61 .85 1.00 1.00

67�F1330 630 52.5 15.4 3.20 .56 .68 .82 50.6 14.8 3.61 .56 .70 .83 48.6 14.2 4.08 .57 .71 .85 46.6 13.7 4.61 .58 .72 .86

67�F(19�C)

1630 770 54.0 15.8 3.21 .58 .73 .88 52.0 15.2 3.62 .59 .74 .89 49.9 14.6 4.09 .60 .76 .91 47.8 14.0 4.63 .61 .78 .93(19�C)

1930 910 55.1 16.1 3.22 .61 .78 .93 53.0 15.5 3.63 .62 .79 .95 50.9 14.9 4.10 .63 .81 .96 48.7 14.3 4.64 .64 .83 .98

71�F1330 630 56.0 16.4 3.23 .42 .54 .66 54.0 15.8 3.64 .42 .55 .67 51.9 15.2 4.11 .43 .55 .68 49.8 14.6 4.64 .43 .56 .70

71�F(22�C)

1630 770 57.6 16.9 3.25 .43 .57 .71 55.4 16.2 3.66 .43 .58 .72 53.2 15.6 4.13 .44 .58 .74 51.0 14.9 4.66 .44 .60 .75(22�C)

1930 910 58.7 17.2 3.26 .44 .60 .75 56.5 16.6 3.67 .44 .60 .77 54.2 15.9 4.14 .45 .62 .79 51.9 15.2 4.68 .45 .63 .81

HS26−048 � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1330 630 49.6 14.5 3.17 .71 .85 .97 47.8 14.0 3.57 .72 .86 .98 45.9 13.5 4.04 .73 .88 .99 44.0 12.9 4.58 .75 .90 1.00

63�F(17�C)

1630 770 51.4 15.1 3.18 .75 .91 1.00 49.5 14.5 3.59 .77 .92 1.00 47.5 13.9 4.07 .78 .94 1.00 45.6 13.4 4.59 .80 .96 1.00(17�C)

1930 910 52.9 15.5 3.20 .80 .95 1.00 50.9 14.9 3.61 .81 .97 1.00 49.0 14.4 4.07 .83 .99 1.00 47.0 13.8 4.61 .85 1.00 1.00

67�F1330 630 53.0 15.5 3.20 .56 .68 .81 51.1 15.0 3.61 .56 .69 .83 49.0 14.4 4.07 .57 .71 .84 46.9 13.7 4.61 .58 .72 .86

67�F(19�C)

1630 770 54.6 16.0 3.22 .58 .73 .87 52.5 15.4 3.62 .59 .74 .89 50.4 14.8 4.09 .60 .76 .91 48.2 14.1 4.63 .61 .78 .93(19�C)

1930 910 55.7 16.3 3.23 .61 .77 .93 53.6 15.7 3.64 .62 .79 .94 51.4 15.1 4.11 .63 .81 .96 49.2 14.4 4.63 .64 .83 .98

71�F1330 630 56.6 16.6 3.24 .42 .54 .66 54.6 16.0 3.65 .42 .55 .67 52.4 15.4 4.11 .42 .55 .68 50.2 14.7 4.65 .43 .56 .69

71�F(22�C)

1630 770 58.2 17.1 3.26 .43 .57 .70 56.0 16.4 3.67 .43 .57 .72 53.8 15.8 4.14 .43 .58 .73 51.5 15.1 4.67 .44 .59 .75(22�C)

1930 910 59.4 17.4 3.27 .44 .59 .75 57.1 16.7 3.68 .44 .61 .77 54.8 16.1 4.15 .45 .61 .79 52.4 15.4 4.68 .45 .63 .80

HS26−048 � CH33−48C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1330 630 50.1 14.7 3.17 .71 .85 .97 48.2 14.1 3.58 .72 .86 .98 46.3 13.6 4.05 .73 .88 .99 44.4 13.0 4.59 .75 .90 1.00

63�F(17�C)

1630 770 51.8 15.2 3.19 .75 .91 1.00 49.9 14.6 3.60 .77 .92 1.00 47.9 14.0 4.07 .78 .94 1.00 46.0 13.5 4.60 .80 .96 1.00(17�C)

1930 910 53.3 15.6 3.21 .80 .96 1.00 51.4 15.1 3.61 .81 .97 1.00 49.4 14.5 4.08 .83 .99 1.00 47.5 13.9 4.62 .85 1.00 1.00

67�F1330 630 53.5 15.7 3.21 .56 .68 .81 51.5 15.1 3.62 .56 .69 .83 49.4 14.5 4.08 .57 .71 .84 47.3 13.9 4.62 .58 .72 .86

67�F(19�C)

1630 770 55.1 16.1 3.22 .58 .73 .87 53.0 15.5 3.63 .59 .74 .89 50.8 14.9 4.10 .60 .76 .91 48.6 14.2 4.63 .61 .78 .93(19�C)

1930 910 56.2 16.5 3.23 .61 .77 .93 54.1 15.9 3.65 .62 .79 .94 51.9 15.2 4.11 .63 .81 .96 49.6 14.5 4.64 .64 .83 .98

71�F1330 630 57.1 16.7 3.24 .42 .54 .66 55.1 16.1 3.66 .42 .54 .67 52.9 15.5 4.12 .42 .55 .68 50.6 14.8 4.66 .43 .56 .69

71�F(22�C)

1630 770 58.7 17.2 3.26 .43 .57 .70 56.5 16.6 3.67 .43 .57 .72 54.2 15.9 4.15 .43 .58 .73 51.9 15.2 4.68 .44 .60 .75(22�C)

1930 910 59.9 17.6 3.27 .44 .59 .75 57.6 16.9 3.69 .44 .61 .77 55.2 16.2 4.16 .45 .62 .79 52.9 15.5 4.69 .45 .63 .80

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 19 �

Page 20: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS26−048 � CH33−50/60C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1330 630 50.5 14.8 3.17 .71 .85 .97 48.6 14.2 3.59 .72 .86 .98 46.6 13.7 4.05 .73 .88 .99 44.6 13.1 4.58 .75 .90 1.00

63�F(17�C)

1630 770 52.3 15.3 3.19 .75 .91 1.00 50.4 14.8 3.60 .77 .92 1.00 48.3 14.2 4.07 .78 .94 1.00 46.3 13.6 4.60 .80 .96 1.00(17�C)

1930 910 53.9 15.8 3.21 .80 .96 1.00 51.9 15.2 3.62 .81 .97 1.00 49.8 14.6 4.09 .83 .99 1.00 47.8 14.0 4.62 .85 1.00 1.00

67�F1330 630 54.0 15.8 3.21 .56 .68 .81 52.0 15.2 3.62 .56 .69 .83 49.8 14.6 4.09 .57 .71 .84 47.7 14.0 4.62 .58 .72 .86

67�F(19�C)

1630 770 55.6 16.3 3.23 .58 .73 .87 53.5 15.7 3.64 .59 .74 .89 51.3 15.0 4.10 .60 .76 .91 49.1 14.4 4.63 .61 .77 .93(19�C)

1930 910 56.9 16.7 3.24 .61 .77 .93 54.7 16.0 3.65 .62 .79 .95 52.4 15.4 4.12 .63 .81 .96 50.1 14.7 4.65 .64 .83 .98

71�F1330 630 57.8 16.9 3.25 .42 .54 .66 55.6 16.3 3.66 .42 .54 .67 53.3 15.6 4.14 .42 .55 .68 51.1 15.0 4.66 .43 .56 .69

71�F(22�C)

1630 770 59.4 17.4 3.27 .43 .57 .70 57.2 16.8 3.69 .43 .57 .72 54.8 16.1 4.15 .44 .58 .73 52.5 15.4 4.68 .44 .59 .75(22�C)

1930 910 60.6 17.8 3.29 .44 .59 .75 58.3 17.1 3.70 .44 .60 .77 55.9 16.4 4.17 .45 .61 .78 53.4 15.6 4.70 .45 .63 .81

HS26−060 � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 57.2 16.8 3.87 .70 .83 .95 55.3 16.2 4.36 .71 .84 .96 53.3 15.6 4.91 .72 .86 .97 51.1 15.0 5.52 .73 .87 .99

63�F(17�C)

1760 830 58.4 17.1 3.88 .72 .86 .98 56.5 16.6 4.37 .73 .87 .99 54.4 15.9 4.92 .74 .89 1.00 52.2 15.3 5.54 .76 .91 1.00(17�C)

1960 925 59.4 17.4 3.89 .74 .89 1.00 57.4 16.8 4.38 .76 .91 1.00 55.3 16.2 4.93 .77 .92 1.00 53.1 15.6 5.55 .79 .94 1.00

67�F1560 735 61.0 17.9 3.90 .55 .67 .80 59.0 17.3 4.38 .56 .68 .81 56.8 16.6 4.94 .56 .69 .82 54.5 16.0 5.55 .57 .70 .84

67�F(19�C)

1760 830 62.1 18.2 3.91 .56 .70 .83 60.0 17.6 4.39 .57 .71 .84 57.8 16.9 4.95 .58 .72 .86 55.4 16.2 5.56 .58 .73 .88(19�C)

1960 925 63.0 18.5 3.91 .58 .72 .86 60.9 17.8 4.40 .58 .73 .88 58.6 17.2 4.95 .59 .74 .89 56.2 16.5 5.57 .60 .76 .91

71�F1560 735 65.0 19.0 3.93 .42 .53 .65 62.9 18.4 4.42 .42 .54 .65 60.6 17.8 4.97 .42 .54 .66 58.2 17.1 5.58 .42 .55 .68

71�F(22�C)

1760 830 66.1 19.4 3.94 .42 .55 .67 63.9 18.7 4.43 .42 .55 .68 61.6 18.1 4.98 .43 .56 .69 59.1 17.3 5.59 .43 .57 .71(22�C)

1960 925 67.0 19.6 3.94 .43 .56 .69 64.8 19.0 4.43 .43 .57 .71 62.4 18.3 4.98 .43 .58 .72 59.9 17.6 5.60 .43 .59 .74

HS26−060 � C33−60D−2 WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 57.1 16.7 3.86 .70 .83 .95 55.2 16.2 4.34 .71 .84 .96 53.2 15.6 4.89 .72 .86 .98 51.0 14.9 5.51 .73 .87 .99

63�F(17�C)

1760 830 58.3 17.1 3.87 .72 .86 .98 56.4 16.5 4.35 .73 .87 .99 54.3 15.9 4.91 .74 .89 1.00 52.1 15.3 5.52 .76 .91 1.00(17�C)

1960 925 59.4 17.4 3.88 .74 .89 1.00 57.4 16.8 4.37 .75 .91 1.00 55.3 16.2 4.91 .77 .92 1.00 53.0 15.5 5.52 .78 .94 1.00

67�F1560 735 61.0 17.9 3.89 .55 .67 .79 58.9 17.3 4.37 .56 .68 .81 56.7 16.6 4.92 .56 .69 .82 54.4 15.9 5.54 .57 .70 .84

67�F(19�C)

1760 830 62.1 18.2 3.90 .56 .69 .83 60.0 17.6 4.38 .57 .70 .84 57.7 16.9 4.93 .58 .72 .86 55.3 16.2 5.54 .58 .73 .88(19�C)

1960 925 63.0 18.5 3.90 .58 .72 .86 60.8 17.8 4.39 .58 .73 .88 58.5 17.1 4.94 .59 .74 .89 56.1 16.4 5.55 .60 .76 .91

71�F1560 735 65.0 19.0 3.92 .42 .53 .65 62.8 18.4 4.41 .42 .54 .66 60.6 17.8 4.95 .42 .54 .66 58.1 17.0 5.56 .42 .55 .68

71�F(22�C)

1760 830 66.1 19.4 3.93 .42 .55 .67 63.9 18.7 4.41 .42 .55 .68 61.6 18.1 4.96 .43 .56 .69 59.1 17.3 5.58 .43 .57 .71(22�C)

1960 925 67.1 19.7 3.94 .43 .56 .69 64.8 19.0 4.42 .43 .57 .71 62.4 18.3 4.97 .43 .58 .72 59.8 17.5 5.59 .44 .59 .74

HS26−060 � C33−62D−2 WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 59.2 17.3 3.87 .70 .83 .95 57.1 16.7 4.36 .71 .85 .97 55.0 16.1 4.90 .72 .86 .98 52.7 15.4 5.51 .73 .88 .99

63�F(17�C)

1760 830 60.4 17.7 3.88 .73 .87 .98 58.4 17.1 4.37 .74 .88 .99 56.2 16.5 4.91 .75 .90 1.00 53.9 15.8 5.52 .76 .92 1.00(17�C)

1960 925 61.5 18.0 3.89 .75 .90 1.00 59.5 17.4 4.37 .76 .91 1.00 57.3 16.8 4.92 .78 .93 1.00 54.9 16.1 5.53 .79 .95 1.00

67�F1560 735 63.1 18.5 3.90 .55 .68 .80 60.9 17.8 4.38 .56 .68 .81 58.6 17.2 4.94 .56 .70 .83 56.2 16.5 5.54 .57 .71 .84

67�F(19�C)

1760 830 64.3 18.8 3.91 .57 .70 .83 62.0 18.2 4.40 .57 .71 .85 59.6 17.5 4.95 .58 .72 .87 57.2 16.8 5.55 .59 .74 .88(19�C)

1960 925 65.2 19.1 3.92 .58 .73 .87 62.9 18.4 4.41 .59 .74 .88 60.5 17.7 4.95 .60 .75 .90 58.0 17.0 5.56 .60 .77 .92

71�F1560 735 67.3 19.7 3.93 .42 .54 .65 65.0 19.0 4.42 .42 .54 .66 62.6 18.3 4.97 .42 .55 .67 60.0 17.6 5.58 .43 .55 .68

71�F(22�C)

1760 830 68.5 20.1 3.94 .42 .55 .67 66.1 19.4 4.43 .43 .56 .69 63.6 18.6 4.98 .43 .56 .70 61.0 17.9 5.59 .43 .57 .71(22�C)

1960 925 69.5 20.4 3.95 .43 .57 .70 67.1 19.7 4.44 .43 .57 .71 64.5 18.9 4.98 .43 .58 .73 61.8 18.1 5.59 .44 .59 .74

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 20 �

Page 21: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS26−060 � CH33−50/60C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 58.1 17.0 3.87 .70 .83 .95 56.1 16.4 4.36 .71 .84 .96 54.0 15.8 4.92 .72 .86 .98 51.8 15.2 5.52 .73 .87 .99

63�F(17�C)

1760 830 59.3 17.4 3.89 .72 .86 .98 57.3 16.8 4.38 .73 .87 .99 55.2 16.2 4.92 .74 .89 1.00 52.9 15.5 5.53 .76 .91 1.00(17�C)

1960 925 60.4 17.7 3.90 .74 .89 1.00 58.3 17.1 4.39 .75 .91 1.00 56.2 16.5 4.93 .77 .92 1.00 53.9 15.8 5.54 .78 .94 1.00

67�F1560 735 62.0 18.2 3.90 .55 .67 .79 59.9 17.6 4.39 .56 .68 .80 57.7 16.9 4.94 .56 .69 .82 55.3 16.2 5.56 .57 .70 .84

67�F(19�C)

1760 830 63.2 18.5 3.91 .56 .69 .82 61.0 17.9 4.40 .57 .70 .84 58.7 17.2 4.96 .58 .72 .86 56.3 16.5 5.56 .58 .73 .88(19�C)

1960 925 64.1 18.8 3.92 .58 .72 .86 61.9 18.1 4.41 .58 .73 .87 59.5 17.4 4.96 .59 .74 .89 57.1 16.7 5.57 .60 .76 .91

71�F1560 735 66.2 19.4 3.94 .42 .53 .64 63.9 18.7 4.42 .42 .54 .65 61.6 18.1 4.98 .42 .54 .66 59.1 17.3 5.59 .42 .55 .68

71�F(22�C)

1760 830 67.3 19.7 3.95 .42 .55 .67 65.0 19.0 4.43 .42 .55 .68 62.6 18.3 4.99 .43 .56 .69 60.1 17.6 5.60 .43 .57 .71(22�C)

1960 925 68.3 20.0 3.95 .43 .56 .69 66.0 19.3 4.44 .43 .57 .70 63.5 18.6 5.00 .43 .58 .72 60.9 17.8 5.60 .43 .58 .73

HS26−060 � CH33−60D−2F WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 57.7 16.9 3.88 .69 .82 .95 55.7 16.3 4.37 .70 .84 .96 53.7 15.7 4.92 .71 .85 .97 51.5 15.1 5.53 .72 .87 .99

63�F(17�C)

1760 830 58.9 17.3 3.89 .71 .86 .98 56.9 16.7 4.38 .72 .87 .99 54.8 16.1 4.93 .74 .89 1.00 52.5 15.4 5.55 .75 .91 1.00(17�C)

1960 925 59.9 17.6 3.90 .74 .89 1.00 57.9 17.0 4.39 .75 .90 1.00 55.8 16.4 4.94 .76 .92 1.00 53.5 15.7 5.55 .78 .94 1.00

67�F1560 735 61.5 18.0 3.91 .55 .66 .79 59.4 17.4 4.39 .55 .67 .80 57.3 16.8 4.95 .56 .68 .82 54.9 16.1 5.56 .56 .70 .83

67�F(19�C)

1760 830 62.7 18.4 3.92 .56 .69 .82 60.5 17.7 4.40 .56 .70 .84 58.3 17.1 4.96 .57 .71 .85 55.8 16.4 5.57 .58 .72 .87(19�C)

1960 925 63.6 18.6 3.92 .57 .71 .86 61.4 18.0 4.41 .58 .72 .87 59.0 17.3 4.97 .58 .74 .89 56.6 16.6 5.58 .59 .75 .91

71�F1560 735 65.6 19.2 3.94 .42 .53 .64 63.4 18.6 4.43 .42 .53 .65 61.1 17.9 4.98 .42 .54 .66 58.7 17.2 5.59 .42 .54 .67

71�F(22�C)

1760 830 66.7 19.5 3.95 .42 .54 .66 64.5 18.9 4.44 .42 .55 .67 62.1 18.2 4.99 .42 .55 .68 59.6 17.5 5.61 .42 .56 .70(22�C)

1960 925 67.7 19.8 3.95 .42 .55 .69 65.4 19.2 4.44 .42 .56 .70 62.9 18.4 5.00 .43 .57 .71 60.4 17.7 5.61 .43 .58 .73

HS26−060 � CH33−62D−2F WITH G60UHV−60D−135 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 58.5 17.1 3.87 .69 .82 .94 56.6 16.6 4.35 .70 .84 .96 54.4 15.9 4.90 .71 .85 .97 52.2 15.3 5.51 .72 .87 .99

63�F(17�C)

1760 830 59.8 17.5 3.88 .71 .85 .98 57.8 16.9 4.36 .72 .87 .99 55.6 16.3 4.91 .73 .89 1.00 53.3 15.6 5.51 .75 .91 1.00(17�C)

1960 925 60.9 17.8 3.89 .74 .89 1.00 58.8 17.2 4.37 .75 .90 1.00 56.6 16.6 4.92 .76 .92 1.00 54.3 15.9 5.52 .78 .94 1.00

67�F1560 735 62.5 18.3 3.90 .55 .66 .79 60.4 17.7 4.38 .55 .67 .80 58.1 17.0 4.93 .55 .68 .81 55.7 16.3 5.54 .56 .69 .83

67�F(19�C)

1760 830 63.7 18.7 3.91 .56 .69 .82 61.5 18.0 4.40 .56 .70 .84 59.2 17.3 4.94 .57 .71 .85 56.7 16.6 5.55 .58 .72 .87(19�C)

1960 925 64.7 19.0 3.92 .57 .71 .85 62.4 18.3 4.40 .58 .72 .87 60.1 17.6 4.94 .58 .74 .89 57.5 16.9 5.55 .59 .75 .91

71�F1560 735 66.7 19.5 3.93 .41 .53 .64 64.5 18.9 4.42 .42 .53 .65 62.1 18.2 4.97 .42 .54 .66 59.6 17.5 5.58 .42 .54 .67

71�F(22�C)

1760 830 68.0 19.9 3.94 .42 .54 .66 65.5 19.2 4.43 .42 .55 .67 63.1 18.5 4.98 .42 .55 .68 60.6 17.8 5.58 .42 .56 .70(22�C)

1960 925 69.0 20.2 3.95 .42 .55 .68 66.5 19.5 4.44 .42 .56 .70 64.0 18.8 4.98 .43 .57 .71 61.4 18.0 5.59 .43 .58 .73

HS27−024 � C33−24A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTemperat

ure

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbure

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 24.3 7.1 1.42 .71 .85 .97 23.5 6.9 1.60 .72 .87 .98 22.7 6.7 1.80 .73 .88 .99 21.7 6.4 2.05 .74 .90 1.00

63�F(17�C)

850 400 25.4 7.4 1.42 .77 .93 1.00 24.6 7.2 1.60 .78 .95 1.00 23.7 6.9 1.80 .80 .96 1.00 22.7 6.7 2.04 .82 .98 1.00(17�C)

1050 495 26.3 7.7 1.43 .84 .99 1.00 25.5 7.5 1.60 .85 1.00 1.00 24.6 7.2 1.80 .87 1.00 1.00 23.7 6.9 2.05 .89 1.00 1.00

67�F650 305 25.9 7.6 1.42 .56 .68 .82 25.0 7.3 1.60 .56 .69 .83 24.1 7.1 1.80 .57 .71 .84 23.1 6.8 2.05 .58 .72 .87

67�F(19�C)

850 400 26.8 7.9 1.43 .59 .75 .90 25.8 7.6 1.61 .60 .76 .92 24.9 7.3 1.81 .61 .78 .94 23.8 7.0 2.05 .62 .80 .96(19�C)

1050 495 27.4 8.0 1.43 .63 .81 .97 26.4 7.7 1.61 .64 .83 .98 25.4 7.4 1.81 .65 .85 1.00 24.4 7.2 2.05 .66 .87 1.00

71�F650 305 27.5 8.1 1.43 .42 .54 .66 26.6 7.8 1.61 .42 .55 .67 25.7 7.5 1.81 .42 .55 .68 24.6 7.2 2.05 .42 .56 .70

71�F(22�C)

850 400 28.4 8.3 1.44 .43 .58 .73 27.5 8.1 1.61 .43 .59 .74 26.4 7.7 1.81 .44 .60 .75 25.3 7.4 2.05 .44 .61 .77(22�C)

1050 495 29.0 8.5 1.44 .45 .62 .79 28.0 8.2 1.61 .45 .63 .81 26.9 7.9 1.82 .46 .64 .82 25.8 7.6 2.05 .46 .65 .85

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 21 �

Page 22: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS27−024 � C33−30A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 24.6 7.2 1.42 .72 .85 .97 23.8 7.0 1.60 .72 .86 .98 22.9 6.7 1.80 .73 .88 .99 21.9 6.4 2.04 .75 .90 1.00

63�F(17�C)

850 400 25.7 7.5 1.42 .78 .94 1.00 24.9 7.3 1.60 .79 .95 1.00 23.9 7.0 1.80 .81 .97 1.00 23.0 6.7 2.04 .82 .98 1.00(17�C)

1050 495 26.7 7.8 1.43 .84 .99 1.00 25.8 7.6 1.60 .85 1.00 1.00 24.9 7.3 1.80 .87 1.00 1.00 24.0 7.0 2.04 .89 1.00 1.00

67�F650 305 26.2 7.7 1.43 .56 .69 .81 25.3 7.4 1.60 .56 .70 .83 24.3 7.1 1.81 .57 .71 .85 23.3 6.8 2.04 .58 .73 .87

67�F(19�C)

850 400 27.1 7.9 1.43 .60 .76 .90 26.2 7.7 1.61 .60 .77 .92 25.2 7.4 1.81 .62 .78 .93 24.1 7.1 2.05 .63 .80 .96(19�C)

1050 495 27.8 8.1 1.43 .64 .82 .97 26.8 7.9 1.61 .65 .83 .98 25.8 7.6 1.81 .65 .85 1.00 24.6 7.2 2.05 .67 .87 1.00

71�F650 305 27.9 8.2 1.43 .42 .54 .66 26.9 7.9 1.61 .42 .55 .68 25.9 7.6 1.81 .42 .56 .69 24.9 7.3 2.05 .43 .56 .70

71�F(22�C)

850 400 28.8 8.4 1.44 .44 .58 .73 27.8 8.1 1.62 .44 .59 .75 26.8 7.9 1.82 .44 .60 .76 25.6 7.5 2.05 .44 .61 .78(22�C)

1050 495 29.5 8.6 1.44 .45 .62 .80 28.4 8.3 1.62 .45 .63 .81 27.3 8.0 1.82 .46 .65 .83 26.1 7.6 2.05 .46 .66 .85

HS27−024 � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 25.0 7.3 1.42 .72 .85 .97 24.1 7.1 1.60 .73 .87 .99 23.2 6.8 1.80 .74 .88 1.00 22.2 6.5 2.04 .76 .90 1.00

63�F(17�C)

850 400 26.1 7.6 1.43 .78 .93 1.00 25.2 7.4 1.60 .80 .95 1.00 24.3 7.1 1.81 .81 .97 1.00 23.2 6.8 2.04 .83 .99 1.00(17�C)

1050 495 27.1 7.9 1.43 .85 .99 1.00 26.2 7.7 1.61 .86 1.00 1.00 25.3 7.4 1.81 .88 1.00 1.00 24.3 7.1 2.05 .90 1.00 1.00

67�F650 305 26.6 7.8 1.43 .56 .69 .82 25.6 7.5 1.61 .57 .70 .84 24.7 7.2 1.81 .57 .71 .85 23.6 6.9 2.05 .58 .73 .87

67�F(19�C)

850 400 27.6 8.1 1.43 .60 .76 .91 26.6 7.8 1.61 .61 .77 .93 25.6 7.5 1.81 .62 .79 .94 24.4 7.2 2.05 .63 .81 .96(19�C)

1050 495 28.3 8.3 1.44 .64 .82 .98 27.2 8.0 1.61 .65 .84 .99 26.2 7.7 1.82 .66 .85 1.00 25.0 7.3 2.05 .67 .88 1.00

71�F650 305 28.3 8.3 1.44 .42 .55 .67 27.4 8.0 1.62 .43 .55 .68 26.3 7.7 1.81 .43 .56 .69 25.2 7.4 2.05 .43 .57 .71

71�F(22�C)

850 400 29.3 8.6 1.45 .44 .59 .73 28.3 8.3 1.62 .44 .60 .75 27.2 8.0 1.82 .44 .61 .77 26.0 7.6 2.06 .45 .62 .78(22�C)

1050 495 30.0 8.8 1.45 .45 .63 .80 28.9 8.5 1.63 .46 .64 .82 27.7 8.1 1.83 .46 .65 .84 26.5 7.8 2.06 .47 .67 .86

HS27−024 � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 25.6 7.5 1.43 .71 .85 .97 24.7 7.2 1.60 .72 .86 .98 23.7 6.9 1.81 .73 .88 1.00 22.7 6.7 2.05 .75 .90 1.00

63�F(17�C)

850 400 26.8 7.9 1.43 .78 .93 1.00 25.9 7.6 1.61 .79 .95 1.00 24.9 7.3 1.81 .81 .97 1.00 23.8 7.0 2.05 .83 .99 1.00(17�C)

1050 495 27.9 8.2 1.44 .84 1.00 1.00 27.0 7.9 1.61 .86 1.00 1.00 26.1 7.6 1.81 .88 1.00 1.00 25.0 7.3 2.05 .90 1.00 1.00

67�F650 305 27.3 8.0 1.43 .56 .69 .81 26.4 7.7 1.61 .57 .70 .83 25.4 7.4 1.81 .57 .71 .84 24.2 7.1 2.05 .58 .72 .86

67�F(19�C)

850 400 28.5 8.4 1.44 .60 .75 .90 27.4 8.0 1.62 .61 .77 .92 26.3 7.7 1.82 .62 .78 .94 25.1 7.4 2.05 .63 .80 .96(19�C)

1050 495 29.2 8.6 1.45 .64 .82 .98 28.1 8.2 1.62 .65 .84 .99 27.0 7.9 1.82 .66 .86 1.00 25.8 7.6 2.06 .67 .88 1.00

71�F650 305 29.2 8.6 1.45 .42 .54 .66 28.2 8.3 1.62 .43 .55 .67 27.1 7.9 1.82 .43 .56 .68 25.9 7.6 2.06 .43 .56 .70

71�F(22�C)

850 400 30.3 8.9 1.46 .44 .58 .73 29.2 8.6 1.63 .44 .59 .75 28.1 8.2 1.83 .44 .60 .76 26.8 7.9 2.06 .45 .62 .78(22�C)

1050 495 31.1 9.1 1.46 .45 .63 .80 29.9 8.8 1.63 .46 .64 .82 28.7 8.4 1.83 .46 .65 .83 27.4 8.0 2.07 .47 .66 .85

HS27−024 � CH33−24/30A−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 24.5 7.2 1.42 .70 .84 .97 23.6 6.9 1.60 .71 .86 .98 22.8 6.7 1.81 .73 .87 .99 21.8 6.4 2.05 .73 .90 1.00

63�F(17�C)

850 400 25.6 7.5 1.43 .76 .93 1.00 24.7 7.2 1.60 .78 .95 1.00 23.8 7.0 1.81 .79 .96 1.00 22.8 6.7 2.05 .82 .98 1.00(17�C)

1050 495 26.5 7.8 1.43 .83 .99 1.00 25.6 7.5 1.61 .84 1.00 1.00 24.8 7.3 1.81 .86 1.00 1.00 23.8 7.0 2.05 .88 1.00 1.00

67�F650 305 26.0 7.6 1.43 .55 .68 .80 25.1 7.4 1.61 .56 .69 .82 24.2 7.1 1.81 .56 .70 .84 23.2 6.8 2.05 .57 .71 .86

67�F(19�C)

850 400 26.9 7.9 1.43 .58 .74 .90 26.0 7.6 1.61 .59 .75 .91 25.0 7.3 1.81 .60 .77 .93 23.9 7.0 2.05 .61 .79 .95(19�C)

1050 495 27.6 8.1 1.44 .62 .80 .97 26.6 7.8 1.61 .63 .82 .98 25.6 7.5 1.81 .64 .84 .99 24.5 7.2 2.05 .66 .86 1.00

71�F650 305 27.7 8.1 1.44 .41 .53 .65 26.8 7.9 1.61 .42 .54 .66 25.8 7.6 1.82 .42 .55 .67 24.7 7.2 2.06 .42 .55 .69

71�F(22�C)

850 400 28.6 8.4 1.44 .43 .57 .72 27.6 8.1 1.62 .43 .58 .73 26.6 7.8 1.82 .43 .59 .75 25.5 7.5 2.06 .44 .60 .77(22�C)

1050 495 29.2 8.6 1.45 .44 .61 .78 28.2 8.3 1.62 .44 .62 .80 27.1 7.9 1.82 .45 .63 .82 25.9 7.6 2.06 .46 .65 .84

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 22 �

Page 23: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS27−024 � CH33−36A/B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 24.6 7.2 1.42 .70 .84 .96 23.8 7.0 1.60 .71 .85 .97 22.9 6.7 1.80 .73 .87 .99 21.9 6.4 2.04 .74 .89 1.00

63�F(17�C)

850 400 25.8 7.6 1.43 .77 .92 1.00 24.9 7.3 1.60 .78 .94 1.00 24.0 7.0 1.80 .80 .95 1.00 22.9 6.7 2.04 .81 .97 1.00(17�C)

1050 495 26.7 7.8 1.43 .82 .98 1.00 25.8 7.6 1.60 .84 1.00 1.00 25.0 7.3 1.81 .86 1.00 1.00 24.0 7.0 2.04 .88 1.00 1.00

67�F650 305 26.3 7.7 1.43 .56 .68 .81 25.4 7.4 1.60 .56 .69 .82 24.4 7.2 1.81 .57 .70 .84 23.4 6.9 2.04 .58 .72 .85

67�F(19�C)

850 400 27.3 8.0 1.43 .59 .74 .89 26.4 7.7 1.61 .60 .75 .91 25.4 7.4 1.81 .60 .77 .93 24.2 7.1 2.05 .61 .79 .94(19�C)

1050 495 28.0 8.2 1.44 .62 .80 .96 27.0 7.9 1.61 .63 .82 .97 26.0 7.6 1.81 .65 .83 .99 24.8 7.3 2.05 .66 .86 1.00

71�F650 305 28.1 8.2 1.44 .42 .54 .65 27.1 7.9 1.61 .42 .54 .66 26.1 7.6 1.81 .42 .55 .68 25.0 7.3 2.05 .42 .56 .69

71�F(22�C)

850 400 29.1 8.5 1.44 .43 .57 .72 28.1 8.2 1.62 .43 .58 .73 27.0 7.9 1.82 .44 .59 .74 25.9 7.6 2.05 .44 .60 .76(22�C)

1050 495 29.8 8.7 1.45 .45 .61 .78 28.7 8.4 1.62 .45 .62 .80 27.6 8.1 1.82 .45 .63 .82 26.4 7.7 2.06 .46 .65 .84

HS27−024 � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F650 305 25.3 7.4 1.43 .72 .85 .97 24.4 7.2 1.60 .73 .87 .99 23.5 6.9 1.81 .74 .88 1.00 22.5 6.6 2.05 .75 .90 1.00

63�F(17�C)

850 400 26.5 7.8 1.43 .78 .93 1.00 25.6 7.5 1.61 .79 .95 1.00 24.6 7.2 1.81 .81 .97 1.00 23.6 6.9 2.05 .82 .98 1.00(17�C)

1050 495 27.5 8.1 1.44 .84 1.00 1.00 26.6 7.8 1.61 .86 1.00 1.00 25.7 7.5 1.82 .87 1.00 1.00 24.7 7.2 2.05 .90 1.00 1.00

67�F650 305 27.1 7.9 1.44 .57 .69 .82 26.1 7.6 1.61 .57 .70 .83 25.1 7.4 1.81 .58 .71 .85 24.0 7.0 2.05 .58 .73 .86

67�F(19�C)

850 400 28.2 8.3 1.44 .60 .76 .90 27.2 8.0 1.62 .61 .77 .92 26.1 7.6 1.82 .62 .78 .94 24.9 7.3 2.06 .63 .80 .96(19�C)

1050 495 28.9 8.5 1.45 .64 .82 .98 27.8 8.1 1.62 .65 .84 .99 26.7 7.8 1.82 .66 .85 1.00 25.5 7.5 2.06 .67 .88 1.00

71�F650 305 28.9 8.5 1.45 .43 .55 .66 27.9 8.2 1.62 .43 .55 .67 26.9 7.9 1.82 .43 .56 .68 25.7 7.5 2.06 .43 .57 .70

71�F(22�C)

850 400 30.1 8.8 1.46 .44 .58 .73 28.9 8.5 1.63 .44 .59 .74 27.8 8.1 1.83 .45 .60 .76 26.6 7.8 2.06 .45 .62 .78(22�C)

1050 495 30.8 9.0 1.46 .45 .62 .79 29.6 8.7 1.63 .46 .63 .81 28.4 8.3 1.83 .46 .65 .83 27.1 7.9 2.07 .47 .66 .85

HS27−030 � C33−30A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 26.5 7.8 1.57 .67 .83 .97 25.5 7.5 1.78 .68 .84 .99 24.4 7.2 2.01 .70 .86 1.00 23.4 6.9 2.26 .71 .88 1.00

63�F(17�C)

950 450 27.7 8.1 1.57 .73 .91 1.00 26.5 7.8 1.78 .75 .93 1.00 25.5 7.5 2.01 .77 .96 1.00 24.4 7.2 2.26 .78 .98 1.00(17�C)

1150 545 28.7 8.4 1.57 .79 .98 1.00 27.5 8.1 1.79 .82 1.00 1.00 26.5 7.8 2.02 .83 1.00 1.00 25.5 7.5 2.27 .86 1.00 1.00

67�F750 355 28.4 8.3 1.57 .53 .65 .78 27.3 8.0 1.79 .53 .66 .80 26.1 7.6 2.02 .54 .67 .82 25.0 7.3 2.27 .55 .69 .84

67�F(19�C)

950 450 29.5 8.6 1.57 .56 .70 .87 28.2 8.3 1.79 .57 .72 .90 27.0 7.9 2.02 .58 .74 .92 25.9 7.6 2.27 .59 .75 .94(19�C)

1150 545 30.3 8.9 1.57 .59 .76 .95 29.0 8.5 1.79 .60 .78 .97 27.7 8.1 2.02 .61 .81 .99 26.5 7.8 2.27 .62 .83 1.00

71�F750 355 30.5 8.9 1.56 .40 .51 .63 29.2 8.6 1.79 .40 .52 .64 28.0 8.2 2.03 .40 .53 .65 26.8 7.9 2.28 .41 .53 .66

71�F(22�C)

950 450 31.7 9.3 1.56 .41 .54 .68 30.2 8.9 1.79 .41 .55 .69 28.9 8.5 2.03 .42 .56 .71 27.6 8.1 2.28 .42 .58 .73(22�C)

1150 545 32.4 9.5 1.56 .42 .58 .73 30.9 9.1 1.79 .43 .59 .76 29.5 8.6 2.03 .43 .60 .78 28.2 8.3 2.28 .44 .61 .81

HS27−030 � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 27.2 8.0 1.57 .66 .82 .97 26.2 7.7 1.77 .68 .84 .99 25.2 7.4 2.00 .69 .86 1.00 24.2 7.1 2.25 .70 .89 1.00

63�F(17�C)

950 450 28.3 8.3 1.57 .72 .92 1.00 27.2 8.0 1.78 .74 .94 1.00 26.2 7.7 2.01 .76 .96 1.00 25.2 7.4 2.26 .78 .98 1.00(17�C)

1150 545 29.3 8.6 1.57 .79 .99 1.00 28.2 8.3 1.78 .81 1.00 1.00 27.2 8.0 2.01 .83 1.00 1.00 26.2 7.7 2.26 .85 1.00 1.00

67�F750 355 29.0 8.5 1.57 .52 .64 .77 27.8 8.1 1.78 .53 .65 .80 26.7 7.8 2.01 .53 .66 .82 25.6 7.5 2.26 .54 .68 .84

67�F(19�C)

950 450 30.0 8.8 1.57 .55 .69 .87 28.8 8.4 1.78 .56 .71 .90 27.6 8.1 2.01 .57 .73 .93 26.4 7.7 2.27 .58 .75 .95(19�C)

1150 545 30.7 9.0 1.57 .58 .76 .95 29.4 8.6 1.79 .59 .78 .98 28.2 8.3 2.02 .60 .80 .99 27.0 7.9 2.27 .61 .83 1.00

71�F750 355 31.0 9.1 1.57 .39 .50 .62 29.8 8.7 1.79 .39 .51 .63 28.6 8.4 2.02 .39 .52 .64 27.4 8.0 2.27 .40 .52 .65

71�F(22�C)

950 450 32.0 9.4 1.56 .40 .53 .67 30.7 9.0 1.79 .40 .55 .68 29.4 8.6 2.02 .41 .55 .70 28.1 8.2 2.27 .41 .57 .72(22�C)

1150 545 32.7 9.6 1.56 .41 .57 .73 31.3 9.2 1.79 .42 .58 .75 29.9 8.8 2.03 .42 .59 .78 28.6 8.4 2.28 .43 .61 .80

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 23 �

Page 24: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS27−030 � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 28.4 8.3 1.57 .66 .81 .97 27.3 8.0 1.78 .67 .83 .99 26.2 7.7 2.01 .68 .86 1.00 25.1 7.4 2.26 .69 .88 1.00

63�F(17�C)

950 450 29.7 8.7 1.57 .72 .91 1.00 28.5 8.4 1.78 .73 .93 1.00 27.3 8.0 2.01 .75 .96 1.00 26.2 7.7 2.26 .77 .98 1.00(17�C)

1150 545 30.7 9.0 1.57 .78 .99 1.00 29.6 8.7 1.79 .81 1.00 1.00 28.5 8.4 2.02 .83 1.00 1.00 27.4 8.0 2.27 .85 1.00 1.00

67�F750 355 30.4 8.9 1.57 .51 .63 .77 29.2 8.6 1.78 .52 .65 .79 28.0 8.2 2.02 .53 .66 .81 26.8 7.9 2.27 .53 .67 .83

67�F(19�C)

950 450 31.5 9.2 1.57 .55 .69 .87 30.2 8.9 1.79 .55 .70 .90 28.9 8.5 2.02 .56 .72 .92 27.7 8.1 2.27 .57 .74 .95(19�C)

1150 545 32.3 9.5 1.57 .58 .75 .95 30.9 9.1 1.79 .59 .78 .98 29.6 8.7 2.02 .60 .80 1.00 28.3 8.3 2.27 .61 .83 1.00

71�F750 355 32.6 9.6 1.56 .39 .50 .61 31.3 9.2 1.79 .39 .50 .62 29.9 8.8 2.03 .39 .51 .63 28.7 8.4 2.28 .39 .52 .65

71�F(22�C)

950 450 33.8 9.9 1.56 .40 .53 .66 32.3 9.5 1.79 .40 .54 .68 30.9 9.1 2.03 .40 .55 .70 29.5 8.6 2.28 .41 .56 .71(22�C)

1150 545 34.6 10.1 1.56 .41 .56 .72 33.0 9.7 1.79 .41 .58 .75 31.5 9.2 2.03 .42 .59 .77 30.1 8.8 2.28 .42 .60 .80

HS27−030 � CH33−24/30A−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 26.4 7.7 1.57 .67 .83 .98 25.4 7.4 1.77 .68 .85 .99 24.5 7.2 2.00 .69 .87 1.00 23.6 6.9 2.26 .70 .89 1.00

63�F(17�C)

950 450 27.4 8.0 1.57 .72 .92 1.00 26.4 7.7 1.78 .74 .94 1.00 25.5 7.5 2.00 .76 .96 1.00 24.5 7.2 2.26 .78 .98 1.00(17�C)

1150 545 28.3 8.3 1.57 .79 .98 1.00 27.3 8.0 1.78 .81 .99 1.00 26.4 7.7 2.01 .83 1.00 1.00 25.5 7.5 2.26 .86 1.00 1.00

67�F750 355 28.0 8.2 1.57 .52 .65 .78 27.0 7.9 1.78 .53 .65 .81 26.0 7.6 2.01 .53 .67 .83 25.0 7.3 2.26 .54 .68 .85

67�F(19�C)

950 450 28.9 8.5 1.57 .55 .70 .88 27.8 8.1 1.78 .56 .71 .90 26.7 7.8 2.01 .57 .73 .92 25.7 7.5 2.26 .58 .75 .95(19�C)

1150 545 29.5 8.6 1.57 .58 .76 .96 28.4 8.3 1.79 .59 .78 .97 27.3 8.0 2.01 .60 .81 .99 26.2 7.7 2.27 .61 .83 1.00

71�F750 355 29.9 8.8 1.57 .39 .51 .62 28.8 8.4 1.79 .39 .51 .63 27.7 8.1 2.02 .39 .52 .64 26.6 7.8 2.27 .40 .53 .66

71�F(22�C)

950 450 30.8 9.0 1.57 .40 .54 .68 29.6 8.7 1.79 .40 .55 .69 28.4 8.3 2.02 .41 .56 .71 27.3 8.0 2.27 .41 .57 .72(22�C)

1150 545 31.4 9.2 1.57 .41 .57 .73 30.1 8.8 1.79 .42 .58 .76 28.9 8.5 2.03 .42 .60 .78 27.8 8.1 2.27 .43 .61 .80

HS27−030 � CH33−36A/B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 27.3 8.0 1.57 .66 .81 .96 26.3 7.7 1.78 .67 .83 .98 25.3 7.4 2.00 .68 .85 .99 24.3 7.1 2.26 .69 .87 1.00

63�F(17�C)

950 450 28.4 8.3 1.57 .71 .90 1.00 27.4 8.0 1.78 .73 .92 1.00 26.4 7.7 2.01 .74 .94 1.00 25.3 7.4 2.26 .76 .97 1.00(17�C)

1150 545 29.4 8.6 1.57 .77 .97 1.00 28.3 8.3 1.79 .79 .99 1.00 27.3 8.0 2.01 .81 1.00 1.00 26.3 7.7 2.26 .84 1.00 1.00

67�F750 355 29.2 8.6 1.57 .51 .63 .77 28.1 8.2 1.79 .52 .64 .79 27.0 7.9 2.02 .53 .65 .80 25.9 7.6 2.26 .53 .66 .83

67�F(19�C)

950 450 30.2 8.9 1.57 .54 .68 .86 29.0 8.5 1.79 .55 .70 .88 27.9 8.2 2.02 .56 .71 .90 26.7 7.8 2.27 .57 .74 .93(19�C)

1150 545 30.9 9.1 1.57 .57 .74 .94 29.7 8.7 1.79 .58 .77 .96 28.5 8.4 2.02 .59 .79 .98 27.3 8.0 2.27 .60 .81 1.00

71�F750 355 31.2 9.1 1.57 .39 .50 .61 30.0 8.8 1.79 .39 .50 .62 28.8 8.4 2.02 .39 .51 .63 27.7 8.1 2.27 .39 .52 .64

71�F(22�C)

950 450 32.3 9.5 1.57 .40 .53 .66 31.0 9.1 1.79 .40 .54 .67 29.7 8.7 2.03 .40 .55 .69 28.5 8.4 2.28 .41 .56 .70(22�C)

1150 545 33.0 9.7 1.57 .41 .56 .72 31.6 9.3 1.80 .41 .57 .74 30.3 8.9 2.03 .41 .58 .76 29.0 8.5 2.28 .42 .59 .78

HS27−030 � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 28.0 8.2 1.57 .70 .84 .97 27.0 7.9 1.78 .71 .86 .99 25.9 7.6 2.01 .72 .88 1.00 24.8 7.3 2.26 .73 .90 1.00

63�F(17�C)

950 450 29.2 8.6 1.57 .75 .92 1.00 28.1 8.2 1.79 .77 .94 1.00 27.0 7.9 2.02 .79 .96 1.00 25.9 7.6 2.27 .80 .98 1.00(17�C)

1150 545 30.2 8.9 1.57 .81 .98 1.00 29.1 8.5 1.79 .83 .99 1.00 28.0 8.2 2.02 .85 1.00 1.00 27.0 7.9 2.27 .87 1.00 1.00

67�F750 355 30.0 8.8 1.57 .55 .67 .80 28.8 8.4 1.79 .56 .68 .82 27.7 8.1 2.02 .56 .69 .84 26.5 7.8 2.27 .57 .71 .86

67�F(19�C)

950 450 31.1 9.1 1.57 .58 .73 .88 29.8 8.7 1.79 .59 .74 .90 28.6 8.4 2.03 .59 .76 .93 27.4 8.0 2.27 .61 .77 .95(19�C)

1150 545 31.9 9.3 1.57 .61 .78 .95 30.6 9.0 1.79 .62 .80 .97 29.2 8.6 2.03 .63 .83 .99 28.0 8.2 2.28 .64 .85 1.00

71�F750 355 32.2 9.4 1.57 .41 .53 .64 30.9 9.1 1.79 .41 .54 .66 29.6 8.7 2.03 .42 .54 .67 28.4 8.3 2.28 .42 .55 .68

71�F(22�C)

950 450 33.4 9.8 1.57 .42 .56 .70 31.9 9.3 1.80 .43 .57 .72 30.5 8.9 2.03 .43 .58 .73 29.2 8.6 2.28 .43 .59 .75(22�C)

1150 545 34.1 10.0 1.57 .44 .59 .76 32.6 9.6 1.80 .44 .61 .77 31.2 9.1 2.04 .44 .62 .80 29.8 8.7 2.29 .45 .63 .82

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 24 �

Page 25: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS27−036 � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 33.5 9.8 1.96 .74 .89 1.00 32.4 9.5 2.21 .75 .90 1.00 31.2 9.1 2.49 .77 .92 1.00 30.0 8.8 2.82 .78 .94 1.00

63�F(17�C)

1220 575 34.5 10.1 1.97 .78 .94 1.00 33.3 9.8 2.21 .80 .96 1.00 32.2 9.4 2.49 .82 .97 1.00 30.9 9.1 2.82 .83 .99 1.00(17�C)

1420 670 35.3 10.3 1.97 .83 .99 1.00 34.2 10.0 2.21 .84 .99 1.00 33.0 9.7 2.50 .86 1.00 1.00 31.9 9.3 2.82 .88 1.00 1.00

67�F1020 480 35.5 10.4 1.97 .57 .72 .85 34.3 10.1 2.22 .58 .73 .87 33.0 9.7 2.50 .59 .74 .89 31.6 9.3 2.83 .60 .76 .91

67�F(19�C)

1220 575 36.3 10.6 1.98 .60 .76 .91 35.0 10.3 2.22 .61 .78 .93 33.7 9.9 2.50 .62 .79 .95 32.3 9.5 2.83 .63 .81 .96(19�C)

1420 670 36.9 10.8 1.98 .63 .81 .96 35.6 10.4 2.22 .64 .82 .97 34.3 10.1 2.50 .65 .84 .99 32.9 9.6 2.83 .66 .86 1.00

71�F1020 480 37.8 11.1 1.98 .43 .56 .69 36.5 10.7 2.23 .43 .57 .71 35.2 10.3 2.51 .43 .57 .72 33.7 9.9 2.84 .43 .58 .73

71�F(22�C)

1220 575 38.5 11.3 1.99 .44 .59 .74 37.2 10.9 2.23 .44 .60 .75 35.8 10.5 2.51 .44 .61 .77 34.4 10.1 2.84 .45 .62 .79(22�C)

1420 670 39.1 11.5 1.99 .45 .62 .79 37.7 11.0 2.24 .45 .63 .81 36.3 10.6 2.51 .46 .64 .82 34.8 10.2 2.84 .46 .65 .84

HS27−036 � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 35.0 10.3 1.97 .73 .88 1.00 33.8 9.9 2.21 .74 .89 1.00 32.6 9.6 2.49 .75 .91 1.00 31.2 9.1 2.83 .77 .93 1.00

63�F(17�C)

1220 575 36.1 10.6 1.97 .77 .94 1.00 34.9 10.2 2.22 .79 .95 1.00 33.6 9.8 2.50 .81 .97 1.00 32.3 9.5 2.83 .82 .99 1.00(17�C)

1420 670 37.1 10.9 1.98 .82 .98 1.00 35.9 10.5 2.22 .84 .99 1.00 34.6 10.1 2.50 .85 1.00 1.00 33.4 9.8 2.83 .87 1.00 1.00

67�F1020 480 37.2 10.9 1.98 .57 .70 .84 35.9 10.5 2.22 .57 .72 .86 34.6 10.1 2.51 .58 .73 .88 33.1 9.7 2.83 .59 .74 .90

67�F(19�C)

1220 575 38.2 11.2 1.98 .59 .75 .90 36.8 10.8 2.23 .60 .76 .92 35.4 10.4 2.51 .61 .78 .94 33.9 9.9 2.84 .62 .80 .97(19�C)

1420 670 38.9 11.4 1.99 .62 .80 .96 37.5 11.0 2.24 .63 .81 .97 36.0 10.6 2.52 .64 .83 .99 34.5 10.1 2.84 .65 .85 1.00

71�F1020 480 39.7 11.6 1.99 .42 .55 .68 38.4 11.3 2.24 .42 .56 .69 36.9 10.8 2.52 .42 .57 .70 35.4 10.4 2.84 .43 .57 .72

71�F(22�C)

1220 575 40.6 11.9 2.00 .43 .58 .73 39.2 11.5 2.24 .43 .59 .74 37.7 11.0 2.53 .44 .60 .76 36.1 10.6 2.85 .44 .61 .77(22�C)

1420 670 41.3 12.1 2.01 .44 .61 .77 39.8 11.7 2.25 .45 .62 .79 38.2 11.2 2.53 .45 .63 .81 36.6 10.7 2.85 .46 .64 .83

HS27−036 � CH33−36A/B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 33.3 9.8 1.96 .73 .88 .99 32.2 9.4 2.21 .74 .89 1.00 31.0 9.1 2.49 .75 .91 1.00 29.8 8.7 2.82 .77 .92 1.00

63�F(17�C)

1220 575 34.3 10.1 1.96 .77 .93 1.00 33.2 9.7 2.21 .79 .94 1.00 32.0 9.4 2.49 .80 .96 1.00 30.7 9.0 2.82 .82 .98 1.00(17�C)

1420 670 35.1 10.3 1.97 .81 .97 1.00 34.0 10.0 2.21 .83 .98 1.00 32.8 9.6 2.49 .85 .99 1.00 31.6 9.3 2.82 .87 1.00 1.00

67�F1020 480 35.4 10.4 1.97 .57 .71 .84 34.2 10.0 2.21 .58 .72 .86 32.9 9.6 2.50 .58 .73 .87 31.6 9.3 2.83 .59 .74 .89

67�F(19�C)

1220 575 36.2 10.6 1.97 .59 .75 .90 35.0 10.3 2.22 .60 .76 .91 33.7 9.9 2.50 .61 .78 .93 32.3 9.5 2.83 .62 .79 .95(19�C)

1420 670 36.8 10.8 1.98 .62 .79 .95 35.6 10.4 2.22 .63 .81 .96 34.3 10.1 2.50 .64 .82 .98 32.8 9.6 2.83 .65 .85 .99

71�F1020 480 37.7 11.0 1.98 .43 .55 .68 36.5 10.7 2.22 .43 .56 .69 35.1 10.3 2.51 .43 .57 .71 33.7 9.9 2.83 .43 .58 .72

71�F(22�C)

1220 575 38.5 11.3 1.98 .43 .58 .73 37.2 10.9 2.23 .44 .59 .74 35.8 10.5 2.51 .44 .60 .75 34.4 10.1 2.84 .44 .61 .77(22�C)

1420 670 39.1 11.5 1.99 .44 .61 .77 37.8 11.1 2.23 .45 .62 .79 36.4 10.7 2.51 .45 .63 .80 34.9 10.2 2.84 .45 .64 .82

HS27−036 � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 34.6 10.1 1.97 .73 .87 .99 33.4 9.8 2.21 .74 .89 1.00 32.2 9.4 2.50 .75 .91 1.00 30.9 9.1 2.83 .77 .92 1.00

63�F(17�C)

1220 575 35.6 10.4 1.97 .77 .93 1.00 34.4 10.1 2.22 .78 .95 1.00 33.2 9.7 2.50 .80 .96 1.00 31.8 9.3 2.83 .82 .98 1.00(17�C)

1420 670 36.5 10.7 1.98 .81 .97 1.00 35.3 10.3 2.22 .83 .99 1.00 34.1 10.0 2.51 .85 1.00 1.00 32.8 9.6 2.83 .87 1.00 1.00

67�F1020 480 36.8 10.8 1.98 .57 .70 .84 35.6 10.4 2.23 .57 .71 .85 34.2 10.0 2.51 .58 .73 .87 32.8 9.6 2.84 .59 .74 .89

67�F(19�C)

1220 575 37.7 11.0 1.98 .59 .75 .90 36.4 10.7 2.23 .60 .76 .92 35.0 10.3 2.51 .61 .78 .94 33.5 9.8 2.84 .62 .80 .95(19�C)

1420 670 38.4 11.3 1.99 .62 .79 .95 37.1 10.9 2.23 .63 .81 .97 35.6 10.4 2.52 .64 .83 .98 34.1 10.0 2.84 .65 .84 .99

71�F1020 480 39.3 11.5 1.99 .42 .55 .68 37.9 11.1 2.24 .43 .56 .69 36.5 10.7 2.52 .43 .57 .71 35.0 10.3 2.85 .43 .57 .72

71�F(22�C)

1220 575 40.2 11.8 2.00 .43 .58 .72 38.8 11.4 2.24 .44 .59 .74 37.3 10.9 2.52 .44 .60 .75 35.8 10.5 2.85 .44 .61 .77(22�C)

1420 670 40.9 12.0 2.00 .44 .61 .77 39.4 11.5 2.25 .45 .62 .79 37.9 11.1 2.53 .45 .63 .80 36.3 10.6 2.86 .46 .64 .82

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 25 �

Page 26: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS27−036 � CH33−44/48B−2F WITH G60UHV−36 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 34.9 10.2 1.97 .73 .88 .99 33.7 9.9 2.21 .74 .89 1.00 32.4 9.5 2.50 .75 .91 1.00 31.1 9.1 2.83 .77 .93 1.00

63�F(17�C)

1220 575 36.0 10.6 1.97 .77 .93 1.00 34.7 10.2 2.22 .79 .95 1.00 33.4 9.8 2.50 .80 .97 1.00 32.1 9.4 2.83 .82 .98 1.00(17�C)

1420 670 36.9 10.8 1.98 .82 .98 1.00 35.7 10.5 2.22 .83 .99 1.00 34.4 10.1 2.51 .85 1.00 1.00 33.2 9.7 2.83 .87 1.00 1.00

67�F1020 480 37.2 10.9 1.98 .57 .70 .84 35.9 10.5 2.23 .57 .71 .86 34.6 10.1 2.51 .58 .73 .87 33.1 9.7 2.84 .59 .74 .89

67�F(19�C)

1220 575 38.1 11.2 1.99 .59 .75 .90 36.8 10.8 2.23 .60 .76 .92 35.4 10.4 2.51 .61 .78 .94 33.8 9.9 2.84 .62 .80 .95(19�C)

1420 670 38.9 11.4 1.99 .62 .79 .95 37.5 11.0 2.24 .63 .81 .97 36.0 10.6 2.52 .64 .83 .98 34.4 10.1 2.84 .65 .85 1.00

71�F1020 480 39.7 11.6 2.00 .42 .55 .68 38.4 11.3 2.24 .43 .56 .69 36.9 10.8 2.52 .43 .57 .70 35.3 10.3 2.85 .43 .57 .72

71�F(22�C)

1220 575 40.7 11.9 2.00 .43 .58 .72 39.2 11.5 2.25 .44 .59 .74 37.7 11.0 2.53 .44 .60 .75 36.1 10.6 2.85 .44 .61 .77(22�C)

1420 670 41.4 12.1 2.01 .44 .61 .77 39.9 11.7 2.25 .45 .62 .78 38.3 11.2 2.53 .45 .63 .81 36.7 10.8 2.85 .46 .64 .82

HS27−042 � C33−44C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 40.4 11.8 2.42 .71 .85 .97 39.0 11.4 2.74 .73 .87 .99 37.6 11.0 3.10 .74 .88 1.00 36.0 10.6 3.51 .75 .91 1.00

63�F(17�C)

1330 630 41.5 12.2 2.43 .75 .90 1.00 40.1 11.8 2.74 .76 .92 1.00 38.6 11.3 3.10 .78 .94 1.00 37.0 10.8 3.51 .79 .96 1.00(17�C)

1530 720 42.4 12.4 2.43 .79 .95 1.00 41.0 12.0 2.75 .80 .96 1.00 39.5 11.6 3.11 .82 .98 1.00 38.0 11.1 3.52 .84 .99 1.00

67�F1130 535 43.0 12.6 2.44 .56 .69 .82 41.5 12.2 2.76 .57 .70 .84 40.0 11.7 3.11 .57 .71 .85 38.3 11.2 3.52 .58 .73 .87

67�F(19�C)

1330 630 44.0 12.9 2.45 .58 .73 .87 42.5 12.5 2.76 .59 .74 .89 40.9 12.0 3.12 .60 .75 .91 39.2 11.5 3.53 .61 .77 .92(19�C)

1530 720 44.8 13.1 2.45 .60 .76 .92 43.2 12.7 2.76 .61 .78 .93 41.5 12.2 3.12 .62 .80 .95 39.8 11.7 3.53 .63 .81 .97

71�F1130 535 45.9 13.5 2.46 .42 .54 .66 44.3 13.0 2.77 .42 .55 .67 42.7 12.5 3.13 .42 .56 .69 40.9 12.0 3.54 .43 .57 .70

71�F(22�C)

1330 630 46.9 13.7 2.47 .43 .57 .70 45.3 13.3 2.78 .43 .57 .71 43.6 12.8 3.14 .43 .58 .73 41.8 12.3 3.54 .44 .59 .75(22�C)

1530 720 47.6 14.0 2.48 .44 .59 .74 46.0 13.5 2.79 .44 .60 .76 44.2 13.0 3.14 .44 .61 .77 42.4 12.4 3.55 .45 .62 .79

HS27−042 � C33−48C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 40.4 11.8 2.42 .72 .85 .97 39.0 11.4 2.74 .73 .87 .99 37.6 11.0 3.10 .74 .88 1.00 36.0 10.6 3.51 .75 .91 1.00

63�F(17�C)

1330 630 41.5 12.2 2.43 .75 .91 1.00 40.1 11.8 2.74 .76 .92 1.00 38.6 11.3 3.10 .78 .94 1.00 37.1 10.9 3.51 .79 .95 1.00(17�C)

1530 720 42.5 12.5 2.43 .79 .95 1.00 41.0 12.0 2.75 .80 .96 1.00 39.5 11.6 3.11 .82 .98 1.00 38.0 11.1 3.52 .84 .99 1.00

67�F1130 535 43.1 12.6 2.44 .56 .69 .82 41.6 12.2 2.76 .57 .70 .83 40.0 11.7 3.11 .57 .71 .85 38.4 11.3 3.52 .58 .72 .87

67�F(19�C)

1330 630 44.0 12.9 2.45 .58 .73 .87 42.5 12.5 2.76 .59 .74 .89 40.9 12.0 3.12 .60 .75 .90 39.2 11.5 3.53 .61 .77 .92(19�C)

1530 720 44.8 13.1 2.45 .60 .77 .92 43.2 12.7 2.76 .61 .78 .93 41.6 12.2 3.12 .62 .79 .95 39.8 11.7 3.53 .63 .81 .97

71�F1130 535 45.9 13.5 2.46 .42 .54 .66 44.4 13.0 2.77 .42 .55 .68 42.7 12.5 3.13 .42 .56 .69 41.0 12.0 3.54 .43 .57 .70

71�F(22�C)

1330 630 46.9 13.7 2.47 .43 .57 .70 45.3 13.3 2.78 .43 .57 .71 43.6 12.8 3.14 .43 .58 .73 41.8 12.3 3.54 .44 .59 .75(22�C)

1530 720 47.7 14.0 2.48 .44 .59 .74 46.0 13.5 2.79 .44 .60 .76 44.3 13.0 3.14 .44 .61 .77 42.4 12.4 3.55 .45 .62 .79

HS27−042 � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 40.8 12.0 2.43 .72 .86 .98 39.4 11.5 2.74 .73 .87 .99 37.9 11.1 3.10 .74 .89 1.00 36.3 10.6 3.51 .76 .91 1.00

63�F(17�C)

1330 630 41.9 12.3 2.44 .76 .91 1.00 40.5 11.9 2.75 .77 .92 1.00 39.0 11.4 3.11 .78 .94 1.00 37.4 11.0 3.52 .80 .96 1.00(17�C)

1530 720 42.9 12.6 2.44 .80 .95 1.00 41.5 12.2 2.76 .81 .96 1.00 39.9 11.7 3.12 .82 .98 1.00 38.3 11.2 3.52 .84 .99 1.00

67�F1130 535 43.5 12.7 2.45 .57 .70 .82 42.0 12.3 2.76 .57 .71 .84 40.4 11.8 3.12 .58 .72 .86 38.7 11.3 3.53 .59 .73 .87

67�F(19�C)

1330 630 44.5 13.0 2.46 .59 .73 .87 43.0 12.6 2.77 .59 .75 .89 41.3 12.1 3.12 .60 .76 .91 39.5 11.6 3.54 .61 .78 .93(19�C)

1530 720 45.3 13.3 2.46 .61 .77 .92 43.7 12.8 2.77 .62 .78 .94 42.0 12.3 3.13 .63 .80 .95 40.2 11.8 3.54 .64 .82 .97

71�F1130 535 46.4 13.6 2.47 .43 .55 .67 44.8 13.1 2.78 .43 .56 .68 43.2 12.7 3.14 .43 .56 .69 41.4 12.1 3.54 .43 .57 .71

71�F(22�C)

1330 630 47.5 13.9 2.48 .43 .57 .71 45.8 13.4 2.79 .43 .58 .72 44.1 12.9 3.14 .44 .59 .74 42.3 12.4 3.55 .44 .60 .75(22�C)

1530 720 48.3 14.2 2.49 .44 .59 .75 46.6 13.7 2.79 .44 .60 .76 44.8 13.1 3.15 .45 .61 .78 42.9 12.6 3.56 .45 .62 .80

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 26 �

Page 27: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS27−042 � CH33−48C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 41.3 12.1 2.43 .72 .85 .98 39.9 11.7 2.74 .72 .87 .99 38.4 11.3 3.10 .74 .88 1.00 36.8 10.8 3.51 .75 .90 1.00

63�F(17�C)

1330 630 42.5 12.5 2.44 .75 .90 1.00 41.0 12.0 2.75 .76 .92 1.00 39.5 11.6 3.11 .78 .94 1.00 37.8 11.1 3.52 .79 .96 1.00(17�C)

1530 720 43.5 12.7 2.44 .79 .95 1.00 42.0 12.3 2.76 .80 .96 1.00 40.4 11.8 3.12 .82 .98 1.00 38.8 11.4 3.52 .84 .99 1.00

67�F1130 535 44.1 12.9 2.45 .56 .69 .82 42.6 12.5 2.76 .56 .70 .84 40.9 12.0 3.12 .57 .71 .85 39.2 11.5 3.53 .58 .72 .87

67�F(19�C)

1330 630 45.1 13.2 2.46 .58 .73 .87 43.5 12.7 2.77 .59 .74 .89 41.9 12.3 3.12 .60 .75 .91 40.1 11.8 3.54 .60 .77 .93(19�C)

1530 720 45.9 13.5 2.46 .60 .76 .92 44.3 13.0 2.77 .61 .78 .94 42.6 12.5 3.13 .62 .79 .95 40.7 11.9 3.54 .63 .81 .97

71�F1130 535 47.0 13.8 2.47 .42 .54 .66 45.4 13.3 2.78 .42 .55 .67 43.7 12.8 3.14 .43 .56 .69 41.9 12.3 3.54 .43 .56 .70

71�F(22�C)

1330 630 48.1 14.1 2.48 .43 .57 .70 46.4 13.6 2.79 .43 .57 .71 44.7 13.1 3.14 .43 .58 .73 42.8 12.5 3.55 .44 .59 .74(22�C)

1530 720 48.9 14.3 2.49 .44 .59 .74 47.2 13.8 2.80 .44 .60 .76 45.4 13.3 3.15 .44 .61 .77 43.4 12.7 3.56 .45 .62 .79

HS27−042 � CH33−50/60C−2F WITH G60UHV−60C−090 COOLING CAPACITYOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1130 535 41.7 12.2 2.43 .72 .86 .98 40.3 11.8 2.74 .73 .87 .99 38.7 11.3 3.10 .74 .89 1.00 37.1 10.9 3.51 .76 .91 1.00

63�F(17�C)

1330 630 42.9 12.6 2.44 .76 .91 1.00 41.4 12.1 2.75 .77 .92 1.00 39.8 11.7 3.11 .78 .94 1.00 38.2 11.2 3.52 .80 .96 1.00(17�C)

1530 720 43.9 12.9 2.45 .79 .95 1.00 42.4 12.4 2.76 .81 .97 1.00 40.8 12.0 3.11 .82 .98 1.00 39.2 11.5 3.52 .84 .99 1.00

67�F1130 535 44.6 13.1 2.45 .57 .70 .83 43.0 12.6 2.76 .57 .71 .84 41.3 12.1 3.12 .58 .72 .86 39.6 11.6 3.53 .59 .73 .87

67�F(19�C)

1330 630 45.7 13.4 2.46 .59 .73 .88 44.0 12.9 2.77 .59 .75 .89 42.3 12.4 3.13 .60 .76 .91 40.5 11.9 3.53 .61 .78 .93(19�C)

1530 720 46.5 13.6 2.47 .61 .77 .92 44.8 13.1 2.78 .62 .79 .94 43.0 12.6 3.13 .63 .80 .96 41.2 12.1 3.53 .64 .82 .98

71�F1130 535 47.6 14.0 2.48 .42 .55 .67 46.0 13.5 2.78 .43 .55 .68 44.2 13.0 3.14 .43 .56 .69 42.3 12.4 3.54 .43 .57 .71

71�F(22�C)

1330 630 48.7 14.3 2.49 .43 .57 .71 47.0 13.8 2.80 .43 .58 .72 45.1 13.2 3.15 .44 .59 .73 43.2 12.7 3.55 .44 .60 .75(22�C)

1530 720 49.6 14.5 2.50 .44 .59 .75 47.8 14.0 2.80 .44 .60 .76 45.9 13.5 3.15 .45 .61 .78 43.9 12.9 3.55 .45 .63 .80

HS29−024 � C33−24A/B−2 WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTemperat

ure

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbure

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 25.7 7.5 1.76 .75 .89 1.00 24.4 7.2 1.91 .76 .91 1.00 23.0 6.7 2.04 .79 .94 1.00 21.7 6.4 2.17 .81 .96 1.00

63�F(17�C)

850 400 26.3 7.7 1.78 .78 .92 1.00 24.9 7.3 1.92 .80 .95 1.00 23.6 6.9 2.06 .82 .97 1.00 22.3 6.5 2.19 .85 .99 1.00(17�C)

950 450 26.8 7.9 1.79 .81 .96 1.00 25.4 7.4 1.94 .83 .98 1.00 24.1 7.1 2.08 .85 1.00 1.00 22.8 6.7 2.21 .88 1.00 1.00

67�F750 355 27.4 8.0 1.81 .58 .72 .86 26.0 7.6 1.95 .59 .74 .88 24.5 7.2 2.09 .60 .76 .91 23.0 6.7 2.22 .62 .79 .93

67�F(19�C)

850 400 27.8 8.1 1.82 .60 .76 .90 26.4 7.7 1.96 .61 .77 .92 24.9 7.3 2.11 .63 .80 .94 23.4 6.9 2.24 .64 .82 .97(19�C)

950 450 28.2 8.3 1.83 .62 .78 .93 26.7 7.8 1.98 .63 .81 .95 25.2 7.4 2.12 .64 .83 .97 23.7 6.9 2.25 .66 .86 .99

71�F750 355 29.3 8.6 1.85 .43 .56 .70 27.8 8.1 2.01 .44 .58 .72 26.3 7.7 2.15 .44 .59 .73 24.7 7.2 2.29 .44 .60 .76

71�F(22�C)

850 400 29.8 8.7 1.86 .44 .58 .73 28.2 8.3 2.02 .44 .60 .75 26.6 7.8 2.17 .45 .61 .77 25.0 7.3 2.30 .45 .63 .80(22�C)

950 450 30.2 8.9 1.87 .44 .60 .76 28.6 8.4 2.03 .45 .62 .78 26.9 7.9 2.18 .45 .63 .80 25.3 7.4 2.31 .46 .65 .83

HS29−024 � C33−30A/B−2 WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 26.1 7.6 1.78 .75 .89 .99 24.7 7.2 1.92 .76 .91 1.00 23.3 6.8 2.06 .78 .94 1.00 21.9 6.4 2.19 .81 .96 1.00

63�F(17�C)

850 400 26.7 7.8 1.79 .77 .92 1.00 25.3 7.4 1.94 .79 .94 1.00 23.9 7.0 2.08 .82 .97 1.00 22.5 6.6 2.21 .85 .99 1.00(17�C)

950 450 27.2 8.0 1.80 .80 .96 1.00 25.8 7.6 1.95 .83 .98 1.00 24.4 7.2 2.10 .85 1.00 1.00 23.1 6.8 2.23 .88 1.00 1.00

67�F750 355 27.8 8.1 1.82 .58 .72 .85 26.3 7.7 1.97 .59 .74 .88 24.8 7.3 2.11 .60 .76 .90 23.3 6.8 2.24 .61 .78 .93

67�F(19�C)

850 400 28.3 8.3 1.83 .60 .75 .89 26.8 7.9 1.98 .61 .77 .92 25.2 7.4 2.13 .62 .79 .94 23.7 6.9 2.26 .64 .82 .97(19�C)

950 450 28.8 8.4 1.84 .61 .78 .92 27.2 8.0 1.99 .63 .80 .95 25.6 7.5 2.14 .64 .82 .97 24.0 7.0 2.27 .66 .85 1.00

71�F750 355 29.8 8.7 1.87 .43 .56 .69 28.3 8.3 2.03 .43 .57 .71 26.6 7.8 2.18 .43 .59 .73 25.0 7.3 2.31 .44 .60 .76

71�F(22�C)

850 400 30.3 8.9 1.88 .44 .58 .72 28.7 8.4 2.04 .44 .59 .74 27.1 7.9 2.19 .44 .61 .77 25.4 7.4 2.33 .45 .62 .80(22�C)

950 450 30.7 9.0 1.89 .44 .60 .75 29.1 8.5 2.05 .45 .61 .78 27.4 8.0 2.20 .45 .63 .80 25.7 7.5 2.34 .46 .65 .83

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 27 �

Page 28: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−024 � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 26.4 7.7 1.78 .74 .88 .99 25.0 7.3 1.93 .76 .91 1.00 23.5 6.9 2.06 .78 .94 1.00 22.1 6.5 2.19 .81 .96 1.00

63�F(17�C)

850 400 27.0 7.9 1.80 .77 .92 1.00 25.6 7.5 1.94 .79 .95 1.00 24.1 7.1 2.09 .82 .97 1.00 22.7 6.7 2.22 .84 .99 1.00(17�C)

950 450 27.6 8.1 1.81 .80 .95 1.00 26.1 7.6 1.96 .82 .98 1.00 24.7 7.2 2.11 .85 1.00 1.00 23.3 6.8 2.24 .88 1.00 1.00

67�F750 355 28.2 8.3 1.82 .58 .72 .85 26.7 7.8 1.98 .58 .73 .87 25.1 7.4 2.12 .60 .75 .90 23.5 6.9 2.25 .61 .78 .93

67�F(19�C)

850 400 28.8 8.4 1.84 .59 .74 .89 27.2 8.0 1.99 .60 .76 .91 25.6 7.5 2.14 .62 .79 .94 23.9 7.0 2.27 .64 .82 .97(19�C)

950 450 29.2 8.6 1.85 .61 .77 .93 27.6 8.1 2.00 .63 .80 .95 25.9 7.6 2.15 .64 .83 .97 24.3 7.1 2.28 .66 .85 1.00

71�F750 355 30.3 8.9 1.87 .43 .56 .69 28.7 8.4 2.03 .43 .57 .70 27.0 7.9 2.18 .44 .58 .73 25.3 7.4 2.32 .44 .60 .75

71�F(22�C)

850 400 30.8 9.0 1.89 .44 .58 .72 29.1 8.5 2.05 .44 .59 .74 27.4 8.0 2.20 .45 .61 .76 25.7 7.5 2.34 .45 .62 .79(22�C)

950 450 31.3 9.2 1.90 .44 .59 .75 29.5 8.6 2.06 .45 .61 .77 27.8 8.1 2.21 .45 .63 .80 26.0 7.6 2.35 .46 .65 .83

HS29−024 � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 27.1 7.9 1.81 .73 .87 .99 25.6 7.5 1.95 .75 .90 1.00 24.1 7.1 2.09 .77 .93 1.00 22.6 6.6 2.22 .80 .96 1.00

63�F(17�C)

850 400 27.8 8.1 1.82 .76 .91 1.00 26.2 7.7 1.97 .78 .94 1.00 24.7 7.2 2.12 .81 .97 1.00 23.2 6.8 2.25 .83 1.00 1.00(17�C)

950 450 28.4 8.3 1.84 .79 .95 1.00 26.8 7.9 1.99 .82 .98 1.00 25.3 7.4 2.14 .84 1.00 1.00 23.9 7.0 2.28 .87 1.00 1.00

67�F750 355 29.1 8.5 1.85 .57 .71 .84 27.5 8.1 2.01 .58 .72 .86 25.8 7.6 2.16 .59 .75 .89 24.1 7.1 2.29 .61 .77 .92

67�F(19�C)

850 400 29.7 8.7 1.87 .59 .74 .88 28.0 8.2 2.02 .60 .76 .91 26.3 7.7 2.17 .62 .78 .93 24.6 7.2 2.31 .63 .81 .97(19�C)

950 450 30.2 8.9 1.88 .61 .77 .92 28.5 8.4 2.04 .62 .79 .94 26.7 7.8 2.19 .64 .82 .97 25.0 7.3 2.32 .65 .85 1.00

71�F750 355 31.3 9.2 1.90 .42 .55 .68 29.6 8.7 2.07 .43 .56 .70 27.8 8.1 2.22 .44 .58 .72 26.0 7.6 2.36 .44 .59 .74

71�F(22�C)

850 400 31.9 9.3 1.92 .43 .57 .71 30.1 8.8 2.08 .44 .58 .73 28.3 8.3 2.24 .44 .60 .76 26.5 7.8 2.38 .45 .62 .78(22�C)

950 450 32.4 9.5 1.93 .44 .59 .74 30.5 8.9 2.10 .45 .61 .76 28.7 8.4 2.25 .45 .62 .79 26.8 7.9 2.39 .46 .64 .82

HS29−024 � CH33−24/30A−2F WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 25.9 7.6 1.77 .74 .89 .99 24.6 7.2 1.91 .76 .91 1.00 23.2 6.8 2.05 .78 .94 1.00 21.9 6.4 2.18 .81 .96 1.00

63�F(17�C)

850 400 26.5 7.8 1.79 .78 .92 1.00 25.1 7.4 1.93 .80 .95 1.00 23.8 7.0 2.07 .82 .97 1.00 22.4 6.6 2.20 .84 .99 1.00(17�C)

950 450 27.0 7.9 1.80 .80 .96 1.00 25.7 7.5 1.94 .83 .98 1.00 24.3 7.1 2.09 .85 .99 1.00 23.0 6.7 2.22 .88 1.00 1.00

67�F750 355 27.6 8.1 1.81 .58 .72 .86 26.2 7.7 1.96 .59 .74 .88 24.7 7.2 2.10 .60 .76 .90 23.2 6.8 2.23 .62 .78 .93

67�F(19�C)

850 400 28.1 8.2 1.82 .60 .75 .89 26.6 7.8 1.97 .61 .77 .92 25.1 7.4 2.12 .62 .79 .94 23.6 6.9 2.25 .64 .82 .97(19�C)

950 450 28.5 8.4 1.83 .61 .78 .93 27.0 7.9 1.99 .63 .80 .95 25.5 7.5 2.13 .64 .83 .97 23.9 7.0 2.26 .66 .85 .99

71�F750 355 29.6 8.7 1.86 .43 .56 .70 28.1 8.2 2.02 .43 .57 .71 26.5 7.8 2.16 .44 .58 .73 24.9 7.3 2.30 .44 .60 .76

71�F(22�C)

850 400 30.1 8.8 1.87 .44 .58 .72 28.5 8.4 2.03 .44 .59 .75 26.9 7.9 2.18 .45 .61 .77 25.2 7.4 2.32 .45 .63 .79(22�C)

950 450 30.5 8.9 1.88 .44 .60 .76 28.9 8.5 2.04 .45 .61 .78 27.2 8.0 2.19 .46 .63 .80 25.5 7.5 2.33 .46 .65 .83

HS29−024 � CH33−36A/B−2F WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 26.3 7.7 1.78 .73 .87 .99 24.9 7.3 1.92 .75 .90 1.00 23.5 6.9 2.06 .77 .92 1.00 22.0 6.4 2.18 .79 .95 1.00

63�F(17�C)

850 400 26.9 7.9 1.79 .76 .91 1.00 25.5 7.5 1.94 .78 .93 1.00 24.0 7.0 2.08 .80 .96 1.00 22.6 6.6 2.21 .83 .98 1.00(17�C)

950 450 27.5 8.1 1.81 .79 .94 1.00 26.0 7.6 1.95 .81 .97 1.00 24.5 7.2 2.10 .83 .99 1.00 23.2 6.8 2.23 .86 1.00 1.00

67�F750 355 28.2 8.3 1.82 .57 .71 .84 26.7 7.8 1.97 .58 .72 .86 25.1 7.4 2.12 .59 .75 .89 23.6 6.9 2.25 .60 .76 .92

67�F(19�C)

850 400 28.8 8.4 1.84 .59 .73 .88 27.2 8.0 1.99 .60 .75 .90 25.6 7.5 2.13 .61 .78 .93 24.0 7.0 2.26 .63 .80 .95(19�C)

950 450 29.2 8.6 1.85 .60 .76 .91 27.6 8.1 2.00 .62 .78 .94 26.0 7.6 2.15 .63 .81 .96 24.3 7.1 2.28 .65 .84 .99

71�F750 355 30.3 8.9 1.87 .43 .55 .68 28.7 8.4 2.03 .43 .56 .69 27.0 7.9 2.18 .43 .57 .71 25.4 7.4 2.32 .44 .59 .74

71�F(22�C)

850 400 30.9 9.1 1.88 .43 .57 .71 29.2 8.6 2.04 .43 .58 .73 27.5 8.1 2.20 .44 .60 .75 25.8 7.6 2.34 .45 .61 .78(22�C)

950 450 31.3 9.2 1.89 .44 .59 .74 29.6 8.7 2.06 .44 .60 .76 27.9 8.2 2.21 .45 .62 .78 26.1 7.6 2.35 .46 .64 .81

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 28 �

Page 29: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−024 � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F750 355 27.1 7.9 1.79 .73 .87 .99 25.6 7.5 1.94 .75 .89 1.00 24.1 7.1 2.08 .77 .92 1.00 22.6 6.6 2.21 .79 .95 1.00

63�F(17�C)

850 400 27.7 8.1 1.81 .76 .91 1.00 26.2 7.7 1.96 .78 .94 1.00 24.7 7.2 2.10 .80 .96 1.00 23.2 6.8 2.23 .83 .99 1.00(17�C)

950 450 28.3 8.3 1.82 .79 .94 1.00 26.8 7.9 1.97 .81 .97 1.00 25.2 7.4 2.12 .83 .99 1.00 23.8 7.0 2.26 .86 1.00 1.00

67�F750 355 29.1 8.5 1.84 .57 .70 .83 27.5 8.1 1.99 .58 .72 .86 25.8 7.6 2.14 .59 .74 .88 24.2 7.1 2.27 .60 .76 .92

67�F(19�C)

850 400 29.7 8.7 1.86 .59 .73 .87 28.0 8.2 2.01 .60 .75 .90 26.3 7.7 2.16 .61 .78 .93 24.6 7.2 2.29 .63 .80 .96(19�C)

950 450 30.2 8.9 1.87 .60 .76 .91 28.5 8.4 2.02 .61 .78 .94 26.8 7.9 2.17 .63 .81 .96 25.0 7.3 2.31 .65 .84 .99

71�F750 355 31.3 9.2 1.89 .42 .55 .67 29.6 8.7 2.05 .43 .56 .69 27.8 8.1 2.21 .44 .58 .71 26.1 7.6 2.35 .44 .59 .74

71�F(22�C)

850 400 31.9 9.3 1.91 .43 .57 .71 30.1 8.8 2.07 .44 .58 .72 28.3 8.3 2.22 .44 .59 .75 26.5 7.8 2.36 .45 .61 .78(22�C)

950 450 32.4 9.5 1.92 .44 .59 .73 30.6 9.0 2.08 .44 .60 .75 28.7 8.4 2.24 .45 .62 .78 26.9 7.9 2.38 .45 .64 .81

HS29−030 � C33−30A/B−2 WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 30.4 8.9 2.31 .73 .87 .98 29.3 8.6 2.59 .74 .88 .99 28.2 8.3 2.90 .75 .90 1.00 27.0 7.9 3.25 .77 .91 1.00

63�F(17�C)

950 450 30.9 9.1 2.33 .76 .90 1.00 29.9 8.8 2.60 .77 .91 1.00 28.7 8.4 2.91 .78 .93 1.00 27.5 8.1 3.26 .80 .95 1.00(17�C)

1050 495 31.4 9.2 2.34 .78 .93 1.00 30.3 8.9 2.61 .79 .94 1.00 29.2 8.6 2.92 .81 .96 1.00 28.0 8.2 3.27 .83 .98 1.00

67�F850 400 32.3 9.5 2.35 .57 .70 .83 31.1 9.1 2.62 .58 .72 .85 29.9 8.8 2.93 .59 .73 .86 28.6 8.4 3.29 .59 .74 .89

67�F(19�C)

950 450 32.7 9.6 2.36 .58 .73 .87 31.6 9.3 2.63 .59 .74 .88 30.3 8.9 2.94 .60 .76 .90 29.0 8.5 3.30 .61 .77 .92(19�C)

1050 495 33.1 9.7 2.37 .60 .76 .90 31.9 9.3 2.64 .61 .77 .91 30.7 9.0 2.95 .62 .79 .93 29.3 8.6 3.30 .63 .80 .95

71�F850 400 34.4 10.1 2.39 .43 .55 .68 33.2 9.7 2.67 .43 .56 .69 31.9 9.3 2.98 .43 .57 .70 30.5 8.9 3.34 .43 .58 .72

71�F(22�C)

950 450 34.8 10.2 2.40 .43 .57 .71 33.6 9.8 2.68 .43 .58 .72 32.3 9.5 2.99 .44 .59 .73 30.9 9.1 3.35 .44 .60 .75(22�C)

1050 495 35.2 10.3 2.41 .44 .59 .73 34.0 10.0 2.68 .44 .59 .75 32.6 9.6 3.00 .44 .60 .76 31.2 9.1 3.36 .45 .62 .78

HS29−030 � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 30.7 9.0 2.32 .73 .86 .98 29.6 8.7 2.59 .74 .88 .99 28.5 8.4 2.90 .75 .89 1.00 27.2 8.0 3.25 .77 .92 1.00

63�F(17�C)

950 450 31.3 9.2 2.33 .75 .89 1.00 30.2 8.9 2.61 .76 .91 1.00 29.0 8.5 2.92 .78 .93 1.00 27.7 8.1 3.27 .80 .95 1.00(17�C)

1050 495 31.8 9.3 2.34 .78 .92 1.00 30.7 9.0 2.62 .79 .94 1.00 29.5 8.6 2.93 .80 .96 1.00 28.2 8.3 3.28 .82 .98 1.00

67�F850 400 32.6 9.6 2.36 .57 .70 .83 31.5 9.2 2.63 .57 .71 .84 30.2 8.9 2.94 .58 .73 .86 28.9 8.5 3.29 .59 .74 .88

67�F(19�C)

950 450 33.1 9.7 2.37 .58 .73 .86 32.0 9.4 2.64 .59 .74 .88 30.7 9.0 2.95 .60 .75 .90 29.3 8.6 3.31 .61 .77 .92(19�C)

1050 495 33.6 9.8 2.38 .60 .75 .90 32.4 9.5 2.65 .61 .77 .91 31.0 9.1 2.96 .62 .78 .93 29.6 8.7 3.32 .63 .80 .95

71�F850 400 34.8 10.2 2.40 .43 .55 .68 33.6 9.8 2.68 .43 .56 .69 32.2 9.4 2.99 .43 .57 .70 30.8 9.0 3.35 .44 .57 .72

71�F(22�C)

950 450 35.3 10.3 2.41 .43 .57 .70 34.1 10.0 2.69 .44 .57 .72 32.7 9.6 3.01 .44 .58 .73 31.2 9.1 3.36 .44 .60 .75(22�C)

1050 495 35.7 10.5 2.42 .44 .58 .73 34.4 10.1 2.70 .44 .59 .74 33.0 9.7 3.01 .44 .60 .76 31.5 9.2 3.37 .45 .62 .78

HS29−030 � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 31.6 9.3 2.34 .72 .86 .98 30.4 8.9 2.61 .73 .87 .99 29.2 8.6 2.92 .74 .89 1.00 27.9 8.2 3.27 .76 .91 1.00

63�F(17�C)

950 450 32.2 9.4 2.36 .74 .89 1.00 31.1 9.1 2.63 .76 .90 1.00 29.8 8.7 2.93 .77 .93 1.00 28.5 8.4 3.29 .79 .94 1.00(17�C)

1050 495 32.8 9.6 2.36 .77 .92 1.00 31.6 9.3 2.64 .79 .94 1.00 30.3 8.9 2.95 .80 .96 1.00 29.0 8.5 3.30 .82 .98 1.00

67�F850 400 33.7 9.9 2.38 .57 .69 .82 32.5 9.5 2.66 .57 .70 .84 31.1 9.1 2.97 .58 .72 .86 29.7 8.7 3.32 .59 .73 .88

67�F(19�C)

950 450 34.3 10.1 2.39 .58 .72 .86 33.0 9.7 2.67 .58 .73 .88 31.6 9.3 2.98 .59 .75 .89 30.2 8.9 3.33 .60 .76 .91(19�C)

1050 495 34.7 10.2 2.41 .59 .75 .89 33.5 9.8 2.68 .60 .76 .91 32.1 9.4 2.99 .61 .78 .93 30.5 8.9 3.35 .62 .80 .95

71�F850 400 36.0 10.6 2.43 .43 .55 .67 34.7 10.2 2.71 .43 .55 .68 33.3 9.8 3.02 .43 .56 .70 31.7 9.3 3.38 .43 .57 .71

71�F(22�C)

950 450 36.6 10.7 2.44 .43 .56 .70 35.2 10.3 2.72 .43 .57 .71 33.8 9.9 3.03 .43 .58 .72 32.2 9.4 3.39 .44 .59 .74(22�C)

1050 495 37.0 10.8 2.45 .44 .58 .72 35.7 10.5 2.73 .44 .59 .74 34.2 10.0 3.05 .44 .60 .75 32.6 9.6 3.40 .44 .61 .77

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 29 �

Page 30: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−030 � CH33−24/30A−2F WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 30.2 8.9 2.31 .73 .87 .98 29.2 8.6 2.59 .74 .88 .99 28.1 8.2 2.90 .75 .90 1.00 26.9 7.9 3.25 .77 .92 1.00

63�F(17�C)

950 450 30.7 9.0 2.32 .75 .90 1.00 29.7 8.7 2.60 .77 .91 1.00 28.6 8.4 2.91 .78 .93 1.00 27.4 8.0 3.26 .80 .95 1.00(17�C)

1050 495 31.2 9.1 2.33 .78 .93 1.00 30.2 8.9 2.61 .79 .94 1.00 29.0 8.5 2.92 .81 .96 1.00 27.8 8.1 3.27 .82 .97 1.00

67�F850 400 32.0 9.4 2.34 .57 .71 .84 30.9 9.1 2.62 .58 .72 .85 29.7 8.7 2.93 .58 .73 .87 28.4 8.3 3.28 .59 .75 .89

67�F(19�C)

950 450 32.5 9.5 2.35 .58 .73 .87 31.4 9.2 2.63 .59 .74 .88 30.1 8.8 2.94 .60 .76 .90 28.8 8.4 3.29 .61 .77 .92(19�C)

1050 495 32.9 9.6 2.36 .60 .76 .90 31.7 9.3 2.64 .61 .77 .92 30.5 8.9 2.95 .62 .79 .94 29.2 8.6 3.30 .63 .80 .95

71�F850 400 34.1 10.0 2.38 .43 .55 .68 32.9 9.6 2.66 .43 .56 .69 31.7 9.3 2.98 .43 .57 .71 30.3 8.9 3.33 .44 .58 .72

71�F(22�C)

950 450 34.5 10.1 2.39 .43 .57 .71 33.4 9.8 2.67 .43 .58 .72 32.1 9.4 2.99 .44 .59 .74 30.7 9.0 3.34 .44 .60 .75(22�C)

1050 495 35.0 10.3 2.40 .44 .59 .74 33.7 9.9 2.68 .44 .60 .75 32.4 9.5 2.99 .44 .60 .76 31.0 9.1 3.35 .45 .62 .78

HS29−030 � CH33−36A/B−2F WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 30.6 9.0 2.32 .72 .85 .97 29.6 8.7 2.59 .73 .86 .98 28.4 8.3 2.90 .74 .88 .99 27.2 8.0 3.25 .76 .90 1.00

63�F(17�C)

950 450 31.2 9.1 2.33 .74 .88 .99 30.1 8.8 2.61 .75 .90 1.00 28.9 8.5 2.92 .76 .92 1.00 27.7 8.1 3.27 .78 .94 1.00(17�C)

1050 495 31.7 9.3 2.34 .77 .91 1.00 30.6 9.0 2.62 .78 .93 1.00 29.4 8.6 2.93 .79 .95 1.00 28.1 8.2 3.28 .81 .96 1.00

67�F850 400 32.7 9.6 2.36 .56 .69 .82 31.5 9.2 2.64 .57 .70 .83 30.3 8.9 2.95 .57 .71 .85 28.9 8.5 3.30 .58 .73 .87

67�F(19�C)

950 450 33.2 9.7 2.37 .58 .72 .85 32.0 9.4 2.65 .58 .73 .87 30.7 9.0 2.96 .59 .74 .88 29.4 8.6 3.31 .60 .76 .91(19�C)

1050 495 33.6 9.8 2.38 .59 .74 .88 32.4 9.5 2.66 .60 .75 .90 31.1 9.1 2.97 .61 .77 .92 29.7 8.7 3.32 .62 .78 .94

71�F850 400 34.8 10.2 2.40 .43 .55 .67 33.6 9.8 2.68 .43 .55 .68 32.3 9.5 3.00 .43 .56 .69 30.9 9.1 3.35 .43 .57 .70

71�F(22�C)

950 450 35.4 10.4 2.41 .43 .56 .69 34.1 10.0 2.69 .43 .57 .70 32.8 9.6 3.01 .43 .58 .72 31.3 9.2 3.36 .44 .58 .73(22�C)

1050 495 35.8 10.5 2.42 .43 .58 .72 34.5 10.1 2.70 .44 .58 .73 33.1 9.7 3.02 .44 .59 .75 31.7 9.3 3.37 .44 .60 .76

HS29−030 � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F850 400 31.5 9.2 2.33 .71 .85 .97 30.4 8.9 2.61 .73 .87 .98 29.2 8.6 2.92 .74 .88 .99 27.9 8.2 3.27 .75 .90 1.00

63�F(17�C)

950 450 32.1 9.4 2.35 .74 .88 .99 31.0 9.1 2.62 .75 .90 1.00 29.7 8.7 2.93 .76 .92 1.00 28.4 8.3 3.28 .78 .94 1.00(17�C)

1050 495 32.7 9.6 2.36 .76 .91 1.00 31.5 9.2 2.63 .78 .93 1.00 30.3 8.9 2.94 .79 .95 1.00 28.9 8.5 3.29 .81 .97 1.00

67�F850 400 33.7 9.9 2.38 .56 .69 .82 32.4 9.5 2.65 .57 .70 .83 31.1 9.1 2.96 .58 .71 .85 29.7 8.7 3.31 .58 .73 .87

67�F(19�C)

950 450 34.3 10.1 2.39 .57 .71 .85 33.0 9.7 2.66 .58 .73 .86 31.6 9.3 2.98 .59 .74 .88 30.2 8.9 3.32 .60 .76 .90(19�C)

1050 495 34.7 10.2 2.40 .59 .74 .88 33.4 9.8 2.67 .60 .75 .90 32.1 9.4 2.99 .61 .77 .92 30.6 9.0 3.34 .61 .78 .94

71�F850 400 35.9 10.5 2.42 .43 .55 .67 34.6 10.1 2.70 .43 .55 .68 33.3 9.8 3.01 .43 .56 .69 31.7 9.3 3.37 .43 .57 .70

71�F(22�C)

950 450 36.5 10.7 2.44 .43 .56 .69 35.2 10.3 2.71 .43 .57 .70 33.7 9.9 3.03 .43 .58 .72 32.2 9.4 3.38 .44 .58 .73(22�C)

1050 495 37.0 10.8 2.45 .43 .57 .71 35.6 10.4 2.72 .44 .58 .73 34.2 10.0 3.04 .44 .59 .74 32.6 9.6 3.40 .44 .60 .76

HS29−036 � C33−36A/B−2 WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 36.8 10.8 2.74 .73 .87 .98 35.5 10.4 3.06 .74 .88 .99 34.2 10.0 3.43 .76 .90 1.00 32.8 9.6 3.85 .77 .91 1.00

63�F(17�C)

1220 575 37.8 11.1 2.76 .77 .92 1.00 36.5 10.7 3.09 .78 .93 1.00 35.2 10.3 3.45 .80 .95 1.00 33.8 9.9 3.87 .81 .97 1.00(17�C)

1420 670 38.7 11.3 2.78 .81 .96 1.00 37.4 11.0 3.10 .83 .98 1.00 36.1 10.6 3.47 .84 .99 1.00 34.7 10.2 3.89 .86 1.00 1.00

67�F1020 480 39.0 11.4 2.78 .57 .71 .83 37.7 11.0 3.11 .58 .72 .85 36.2 10.6 3.47 .59 .73 .87 34.8 10.2 3.90 .59 .74 .88

67�F(19�C)

1220 575 39.9 11.7 2.80 .59 .75 .89 38.5 11.3 3.12 .60 .76 .91 37.1 10.9 3.49 .61 .77 .92 35.5 10.4 3.92 .62 .79 .94(19�C)

1420 670 40.6 11.9 2.81 .62 .79 .94 39.2 11.5 3.14 .63 .80 .95 37.7 11.0 3.51 .64 .82 .97 36.2 10.6 3.93 .65 .84 .98

71�F1020 480 41.6 12.2 2.83 .43 .55 .68 40.1 11.8 3.16 .43 .56 .69 38.6 11.3 3.53 .43 .57 .70 37.1 10.9 3.96 .43 .58 .72

71�F(22�C)

1220 575 42.5 12.5 2.85 .44 .58 .72 41.0 12.0 3.18 .44 .59 .74 39.4 11.5 3.55 .44 .60 .75 37.8 11.1 3.98 .45 .61 .77(22�C)

1420 670 43.1 12.6 2.86 .45 .61 .77 41.6 12.2 3.19 .45 .62 .78 40.0 11.7 3.57 .45 .63 .80 38.4 11.3 4.00 .46 .64 .82

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 30 �

Page 31: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−036 � C33−38A/B−2 WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 38.5 11.3 2.78 .72 .86 .98 37.1 10.9 3.10 .73 .88 .99 35.7 10.5 3.46 .75 .89 1.00 34.2 10.0 3.89 .76 .91 1.00

63�F(17�C)

1220 575 39.7 11.6 2.80 .77 .91 1.00 38.3 11.2 3.12 .78 .93 1.00 36.8 10.8 3.49 .79 .95 1.00 35.3 10.3 3.92 .81 .97 1.00(17�C)

1420 670 40.7 11.9 2.82 .81 .96 1.00 39.3 11.5 3.14 .82 .97 1.00 37.9 11.1 3.51 .84 .99 1.00 36.4 10.7 3.94 .85 1.00 1.00

67�F1020 480 41.0 12.0 2.82 .57 .70 .82 39.5 11.6 3.15 .57 .71 .84 38.0 11.1 3.52 .58 .72 .86 36.4 10.7 3.94 .59 .74 .88

67�F(19�C)

1220 575 42.0 12.3 2.85 .59 .74 .88 40.5 11.9 3.17 .60 .76 .90 39.0 11.4 3.54 .61 .77 .92 37.3 10.9 3.97 .62 .79 .94(19�C)

1420 670 42.9 12.6 2.86 .62 .78 .93 41.3 12.1 3.19 .63 .80 .95 39.7 11.6 3.57 .63 .81 .97 38.0 11.1 3.99 .65 .83 .98

71�F1020 480 43.7 12.8 2.87 .43 .55 .67 42.2 12.4 3.21 .43 .55 .68 40.6 11.9 3.59 .43 .56 .69 39.0 11.4 4.01 .43 .57 .71

71�F(22�C)

1220 575 44.8 13.1 2.90 .43 .58 .72 43.2 12.7 3.23 .44 .58 .73 41.6 12.2 3.60 .44 .59 .75 39.8 11.7 4.04 .44 .60 .76(22�C)

1420 670 45.6 13.4 2.91 .44 .60 .76 44.0 12.9 3.25 .45 .61 .78 42.3 12.4 3.62 .45 .62 .79 40.5 11.9 4.06 .45 .63 .81

HS29−036 � CH33−36A/B−2F WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 36.6 10.7 2.75 .72 .86 .97 35.3 10.3 3.06 .73 .87 .98 34.0 10.0 3.43 .74 .89 .99 32.7 9.6 3.85 .75 .90 1.00

63�F(17�C)

1220 575 37.7 11.0 2.77 .76 .90 1.00 36.4 10.7 3.09 .77 .92 1.00 35.0 10.3 3.46 .78 .94 1.00 33.6 9.8 3.88 .80 .96 1.00(17�C)

1420 670 38.6 11.3 2.78 .80 .95 1.00 37.3 10.9 3.11 .81 .96 1.00 35.9 10.5 3.47 .82 .98 1.00 34.6 10.1 3.89 .84 .99 1.00

67�F1020 480 39.0 11.4 2.79 .56 .69 .82 37.6 11.0 3.11 .57 .70 .84 36.2 10.6 3.48 .58 .72 .85 34.7 10.2 3.90 .59 .73 .87

67�F(19�C)

1220 575 39.9 11.7 2.80 .59 .73 .88 38.5 11.3 3.13 .59 .75 .89 37.1 10.9 3.49 .60 .76 .91 35.5 10.4 3.93 .61 .78 .93(19�C)

1420 670 40.6 11.9 2.82 .61 .77 .92 39.2 11.5 3.14 .62 .79 .94 37.7 11.0 3.51 .63 .80 .95 36.1 10.6 3.94 .64 .82 .97

71�F1020 480 41.5 12.2 2.83 .42 .55 .67 40.1 11.8 3.16 .43 .55 .68 38.6 11.3 3.53 .43 .56 .69 37.1 10.9 3.96 .43 .57 .70

71�F(22�C)

1220 575 42.5 12.5 2.85 .43 .57 .71 41.0 12.0 3.18 .43 .58 .72 39.5 11.6 3.55 .44 .59 .74 37.9 11.1 3.98 .44 .60 .75(22�C)

1420 670 43.2 12.7 2.86 .44 .60 .75 41.7 12.2 3.19 .44 .60 .76 40.1 11.8 3.57 .45 .62 .78 38.5 11.3 4.00 .45 .63 .80

HS29−036 � CH33−42B−2F WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 37.9 11.1 2.77 .72 .85 .97 36.6 10.7 3.10 .73 .87 .98 35.2 10.3 3.47 .74 .88 .99 33.8 9.9 3.89 .75 .90 1.00

63�F(17�C)

1220 575 39.1 11.5 2.80 .76 .90 1.00 37.7 11.0 3.12 .77 .92 1.00 36.3 10.6 3.49 .78 .94 1.00 34.8 10.2 3.92 .80 .95 1.00(17�C)

1420 670 40.1 11.8 2.81 .80 .95 1.00 38.7 11.3 3.14 .81 .96 1.00 37.2 10.9 3.51 .83 .98 1.00 35.8 10.5 3.94 .84 .99 1.00

67�F1020 480 40.5 11.9 2.82 .56 .69 .82 39.0 11.4 3.14 .57 .70 .83 37.5 11.0 3.52 .58 .71 .85 36.0 10.6 3.95 .58 .73 .87

67�F(19�C)

1220 575 41.5 12.2 2.84 .59 .73 .88 40.0 11.7 3.17 .59 .75 .89 38.5 11.3 3.54 .60 .76 .91 36.9 10.8 3.97 .61 .78 .93(19�C)

1420 670 42.3 12.4 2.86 .61 .77 .92 40.8 12.0 3.18 .62 .79 .94 39.2 11.5 3.56 .63 .80 .95 37.5 11.0 3.99 .64 .82 .97

71�F1020 480 43.2 12.7 2.87 .42 .54 .67 41.7 12.2 3.20 .43 .55 .68 40.1 11.8 3.58 .43 .56 .69 38.5 11.3 4.01 .43 .57 .70

71�F(22�C)

1220 575 44.2 13.0 2.89 .43 .57 .71 42.6 12.5 3.23 .43 .58 .72 41.0 12.0 3.60 .44 .59 .73 39.4 11.5 4.04 .44 .60 .75(22�C)

1420 670 45.0 13.2 2.91 .44 .60 .75 43.4 12.7 3.24 .44 .60 .76 41.7 12.2 3.62 .45 .61 .78 40.0 11.7 4.06 .45 .63 .80

HS29−036 � CH33−44/48B−2F WITH G60UHV−36 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1020 480 38.4 11.3 2.77 .72 .85 .97 37.1 10.9 3.10 .73 .87 .98 35.6 10.4 3.47 .74 .88 .99 34.2 10.0 3.89 .75 .90 1.00

63�F(17�C)

1220 575 39.6 11.6 2.80 .76 .90 1.00 38.2 11.2 3.12 .77 .92 1.00 36.8 10.8 3.49 .78 .93 1.00 35.2 10.3 3.92 .80 .95 1.00(17�C)

1420 670 40.6 11.9 2.81 .79 .95 1.00 39.2 11.5 3.14 .81 .96 1.00 37.7 11.0 3.51 .82 .98 1.00 36.2 10.6 3.94 .85 .99 1.00

67�F1020 480 41.0 12.0 2.82 .56 .69 .82 39.5 11.6 3.14 .57 .70 .83 38.0 11.1 3.52 .58 .71 .85 36.4 10.7 3.95 .59 .73 .87

67�F(19�C)

1220 575 42.0 12.3 2.84 .59 .73 .87 40.5 11.9 3.17 .59 .75 .89 38.9 11.4 3.54 .60 .76 .91 37.3 10.9 3.97 .61 .77 .93(19�C)

1420 670 42.8 12.5 2.86 .61 .77 .92 41.3 12.1 3.18 .62 .79 .94 39.7 11.6 3.56 .63 .80 .96 38.0 11.1 3.99 .64 .82 .97

71�F1020 480 43.7 12.8 2.87 .43 .54 .67 42.2 12.4 3.20 .43 .55 .68 40.6 11.9 3.58 .43 .56 .69 38.9 11.4 4.01 .43 .57 .70

71�F(22�C)

1220 575 44.8 13.1 2.89 .43 .57 .71 43.2 12.7 3.23 .44 .58 .72 41.5 12.2 3.60 .44 .59 .73 39.8 11.7 4.04 .44 .60 .75(22�C)

1420 670 45.6 13.4 2.91 .44 .59 .75 44.0 12.9 3.24 .44 .60 .76 42.3 12.4 3.62 .45 .61 .78 40.5 11.9 4.06 .45 .62 .80

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 31 �

Page 32: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−042 � C33−44C−2 WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1180 555 44.0 12.9 3.32 .71 .85 .96 42.5 12.5 3.70 .72 .86 .98 40.9 12.0 4.14 .74 .88 .99 39.2 11.5 4.64 .75 .90 1.00

63�F(17�C)

1330 630 44.9 13.2 3.34 .74 .88 .99 43.4 12.7 3.72 .75 .89 1.00 41.7 12.2 4.16 .76 .91 1.00 40.0 11.7 4.66 .78 .93 1.00(17�C)

1480 700 45.7 13.4 3.36 .76 .91 1.00 44.1 12.9 3.74 .78 .93 1.00 42.5 12.5 4.18 .79 .94 1.00 40.7 11.9 4.67 .81 .96 1.00

67�F1180 555 46.9 13.7 3.38 .56 .69 .82 45.3 13.3 3.76 .57 .70 .83 43.6 12.8 4.19 .57 .71 .84 41.7 12.2 4.69 .58 .72 .86

67�F(19�C)

1330 630 47.7 14.0 3.40 .58 .71 .85 46.0 13.5 3.78 .58 .73 .86 44.3 13.0 4.21 .59 .74 .88 42.3 12.4 4.72 .60 .75 .90(19�C)

1480 700 48.4 14.2 3.41 .59 .74 .88 46.7 13.7 3.79 .60 .75 .90 44.8 13.1 4.23 .60 .77 .91 42.9 12.6 4.73 .62 .78 .94

71�F1180 555 49.9 14.6 3.44 .42 .55 .66 48.2 14.1 3.83 .43 .55 .67 46.4 13.6 4.27 .43 .56 .69 44.5 13.0 4.77 .43 .56 .70

71�F(22�C)

1330 630 50.8 14.9 3.46 .43 .56 .69 49.0 14.4 3.85 .43 .57 .70 47.1 13.8 4.28 .43 .58 .72 45.1 13.2 4.79 .44 .58 .73(22�C)

1480 700 51.4 15.1 3.47 .43 .58 .72 49.6 14.5 3.86 .44 .58 .73 47.7 14.0 4.30 .44 .59 .74 45.7 13.4 4.80 .44 .60 .76

HS29−042 � C33−48C−2 WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1180 555 44.0 12.9 3.32 .71 .85 .96 42.5 12.5 3.70 .72 .86 .98 40.9 12.0 4.14 .74 .88 .99 39.2 11.5 4.64 .75 .90 1.00

63�F(17�C)

1330 630 44.9 13.2 3.34 .74 .88 .99 43.4 12.7 3.72 .75 .89 1.00 41.7 12.2 4.16 .76 .91 1.00 40.0 11.7 4.66 .78 .93 1.00(17�C)

1480 700 45.7 13.4 3.36 .76 .91 1.00 44.1 12.9 3.74 .78 .93 1.00 42.5 12.5 4.18 .79 .94 1.00 40.7 11.9 4.67 .81 .96 1.00

67�F1180 555 46.9 13.7 3.38 .56 .69 .82 45.3 13.3 3.76 .57 .70 .83 43.6 12.8 4.19 .57 .71 .84 41.7 12.2 4.69 .58 .72 .86

67�F(19�C)

1330 630 47.7 14.0 3.40 .58 .71 .85 46.0 13.5 3.78 .58 .73 .86 44.3 13.0 4.21 .59 .74 .88 42.3 12.4 4.72 .60 .75 .90(19�C)

1480 700 48.4 14.2 3.41 .59 .74 .88 46.7 13.7 3.79 .60 .75 .90 44.8 13.1 4.23 .60 .77 .91 42.9 12.6 4.73 .62 .78 .94

71�F1180 555 49.9 14.6 3.44 .42 .55 .66 48.2 14.1 3.83 .43 .55 .67 46.4 13.6 4.27 .43 .56 .69 44.5 13.0 4.77 .43 .56 .70

71�F(22�C)

1330 630 50.8 14.9 3.46 .43 .56 .69 49.0 14.4 3.85 .43 .57 .70 47.1 13.8 4.28 .43 .58 .72 45.1 13.2 4.79 .44 .58 .73(22�C)

1480 700 51.4 15.1 3.47 .43 .58 .72 49.6 14.5 3.86 .44 .58 .73 47.7 14.0 4.30 .44 .59 .74 45.7 13.4 4.80 .44 .60 .76

HS29−042 � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1180 555 44.4 13.0 3.33 .71 .85 .96 42.9 12.6 3.71 .72 .86 .98 41.2 12.1 4.14 .73 .88 .99 39.5 11.6 4.64 .75 .89 1.00

63�F(17�C)

1330 630 45.3 13.3 3.35 .74 .88 .99 43.8 12.8 3.73 .75 .89 1.00 42.1 12.3 4.16 .76 .91 1.00 40.3 11.8 4.65 .78 .93 1.00(17�C)

1480 700 46.1 13.5 3.37 .76 .91 1.00 44.5 13.0 3.74 .78 .93 1.00 42.8 12.5 4.17 .79 .95 1.00 41.0 12.0 4.67 .81 .96 1.00

67�F1180 555 47.3 13.9 3.39 .56 .69 .81 45.7 13.4 3.77 .57 .70 .83 44.0 12.9 4.20 .57 .71 .84 42.0 12.3 4.70 .58 .72 .86

67�F(19�C)

1330 630 48.2 14.1 3.40 .57 .71 .85 46.5 13.6 3.79 .58 .72 .86 44.7 13.1 4.22 .59 .74 .88 42.7 12.5 4.72 .60 .75 .90(19�C)

1480 700 48.9 14.3 3.42 .59 .74 .88 47.1 13.8 3.80 .60 .75 .90 45.3 13.3 4.24 .60 .77 .91 43.3 12.7 4.73 .61 .78 .94

71�F1180 555 50.5 14.8 3.45 .42 .54 .66 48.7 14.3 3.84 .43 .55 .67 46.9 13.7 4.28 .43 .56 .68 44.8 13.1 4.78 .43 .56 .70

71�F(22�C)

1330 630 51.3 15.0 3.47 .43 .56 .69 49.5 14.5 3.86 .43 .57 .70 47.6 14.0 4.30 .43 .57 .71 45.5 13.3 4.79 .44 .58 .73(22�C)

1480 700 52.0 15.2 3.48 .43 .58 .72 50.2 14.7 3.88 .44 .58 .73 48.2 14.1 4.31 .44 .59 .74 46.1 13.5 4.81 .44 .60 .76

HS29−042 � CH33−48C−2F WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1180 555 44.5 13.0 3.33 .71 .85 .96 42.9 12.6 3.71 .72 .86 .98 41.3 12.1 4.15 .74 .88 .99 39.5 11.6 4.64 .75 .90 1.00

63�F(17�C)

1330 630 45.4 13.3 3.35 .74 .88 .99 43.8 12.8 3.73 .75 .89 1.00 42.2 12.4 4.16 .76 .91 1.00 40.4 11.8 4.66 .78 .93 1.00(17�C)

1480 700 46.2 13.5 3.37 .76 .91 1.00 44.6 13.1 3.75 .77 .93 1.00 42.9 12.6 4.18 .79 .94 1.00 41.1 12.0 4.68 .81 .96 1.00

67�F1180 555 47.4 13.9 3.39 .56 .69 .81 45.8 13.4 3.77 .57 .70 .83 44.0 12.9 4.21 .57 .71 .84 42.1 12.3 4.71 .58 .72 .86

67�F(19�C)

1330 630 48.3 14.2 3.41 .58 .71 .85 46.5 13.6 3.79 .58 .72 .86 44.7 13.1 4.23 .59 .74 .88 42.8 12.5 4.72 .60 .75 .90(19�C)

1480 700 49.0 14.4 3.42 .59 .74 .88 47.2 13.8 3.81 .60 .75 .90 45.3 13.3 4.24 .60 .77 .91 43.4 12.7 4.74 .62 .78 .94

71�F1180 555 50.5 14.8 3.46 .42 .54 .66 48.8 14.3 3.84 .43 .55 .67 46.9 13.7 4.28 .43 .56 .68 44.9 13.2 4.78 .43 .56 .70

71�F(22�C)

1330 630 51.4 15.1 3.48 .43 .56 .69 49.6 14.5 3.86 .43 .56 .70 47.7 14.0 4.30 .43 .57 .71 45.6 13.4 4.80 .44 .58 .73(22�C)

1480 700 52.1 15.3 3.49 .43 .57 .71 50.2 14.7 3.88 .44 .58 .73 48.3 14.2 4.32 .44 .59 .74 46.2 13.5 4.82 .44 .60 .76

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 32 �

Page 33: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−042 � CH33−50/60C−2F WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1180 555 44.9 13.2 3.34 .71 .85 .96 43.3 12.7 3.72 .72 .86 .98 41.6 12.2 4.15 .73 .88 .99 39.8 11.7 4.64 .75 .89 1.00

63�F(17�C)

1330 630 45.8 13.4 3.37 .74 .88 .99 44.2 13.0 3.74 .75 .90 1.00 42.5 12.5 4.18 .76 .91 1.00 40.6 11.9 4.67 .78 .93 1.00(17�C)

1480 700 46.7 13.7 3.38 .76 .91 1.00 45.0 13.2 3.76 .78 .93 1.00 43.2 12.7 4.20 .79 .95 1.00 41.4 12.1 4.69 .81 .97 1.00

67�F1180 555 47.9 14.0 3.40 .56 .69 .81 46.2 13.5 3.79 .56 .70 .83 44.4 13.0 4.22 .57 .71 .84 42.5 12.5 4.72 .58 .72 .86

67�F(19�C)

1330 630 48.8 14.3 3.43 .57 .71 .85 47.0 13.8 3.81 .58 .73 .86 45.2 13.2 4.24 .59 .74 .88 43.1 12.6 4.74 .60 .75 .90(19�C)

1480 700 49.5 14.5 3.44 .59 .74 .88 47.7 14.0 3.82 .60 .75 .90 45.8 13.4 4.27 .61 .77 .92 43.7 12.8 4.76 .62 .78 .94

71�F1180 555 51.1 15.0 3.47 .42 .54 .66 49.3 14.4 3.86 .43 .55 .67 47.4 13.9 4.30 .43 .55 .68 45.3 13.3 4.80 .43 .57 .70

71�F(22�C)

1330 630 52.0 15.2 3.49 .43 .56 .69 50.1 14.7 3.88 .43 .56 .70 48.2 14.1 4.32 .43 .57 .71 46.0 13.5 4.83 .44 .58 .73(22�C)

1480 700 52.7 15.4 3.51 .43 .57 .72 50.8 14.9 3.90 .44 .58 .73 48.7 14.3 4.34 .44 .59 .74 46.6 13.7 4.84 .44 .60 .76

HS29−048 � C33−48C−2 WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1430 675 47.6 14.0 3.55 .74 .88 .99 45.8 13.4 4.01 .75 .90 1.00 44.0 12.9 4.54 .76 .91 1.00 42.1 12.3 5.17 .78 .93 1.00

63�F(17�C)

1630 770 48.6 14.2 3.56 .77 .92 1.00 46.8 13.7 4.03 .78 .93 1.00 44.9 13.2 4.57 .80 .95 1.00 43.0 12.6 5.19 .82 .97 1.00(17�C)

1830 865 49.5 14.5 3.58 .80 .95 1.00 47.7 14.0 4.04 .81 .96 1.00 45.8 13.4 4.59 .83 .98 1.00 43.9 12.9 5.20 .85 .99 1.00

67�F1430 675 50.6 14.8 3.59 .58 .71 .85 48.7 14.3 4.06 .58 .72 .86 46.7 13.7 4.60 .59 .74 .88 44.6 13.1 5.22 .60 .76 .90

67�F(19�C)

1630 770 51.4 15.1 3.61 .59 .74 .89 49.5 14.5 4.07 .60 .76 .90 47.5 13.9 4.61 .61 .77 .92 45.3 13.3 5.25 .62 .79 .94(19�C)

1830 865 52.1 15.3 3.62 .61 .78 .92 50.1 14.7 4.09 .62 .79 .94 48.1 14.1 4.62 .63 .81 .96 45.9 13.5 5.26 .64 .83 .97

71�F1430 675 53.8 15.8 3.65 .43 .56 .69 51.8 15.2 4.12 .43 .57 .70 49.7 14.6 4.66 .43 .58 .71 47.6 14.0 5.30 .44 .58 .73

71�F(22�C)

1630 770 54.7 16.0 3.66 .44 .58 .72 52.6 15.4 4.14 .44 .59 .73 50.5 14.8 4.68 .44 .60 .75 48.3 14.2 5.31 .45 .61 .77(22�C)

1830 865 55.4 16.2 3.68 .44 .60 .75 53.3 15.6 4.15 .44 .61 .77 51.1 15.0 4.70 .45 .62 .78 48.8 14.3 5.33 .45 .63 .80

HS29−048 � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1430 675 48.1 14.1 3.56 .74 .88 .99 46.3 13.6 4.02 .75 .89 1.00 44.4 13.0 4.56 .76 .91 1.00 42.4 12.4 5.18 .78 .93 1.00

63�F(17�C)

1630 770 49.1 14.4 3.57 .77 .92 1.00 47.3 13.9 4.04 .78 .93 1.00 45.4 13.3 4.57 .80 .95 1.00 43.4 12.7 5.19 .81 .97 1.00(17�C)

1830 865 50.0 14.7 3.59 .80 .95 1.00 48.2 14.1 4.05 .81 .97 1.00 46.3 13.6 4.59 .83 .98 1.00 44.4 13.0 5.22 .85 .99 1.00

67�F1430 675 51.1 15.0 3.61 .58 .71 .85 49.2 14.4 4.07 .58 .72 .86 47.2 13.8 4.61 .59 .74 .88 45.0 13.2 5.24 .60 .76 .90

67�F(19�C)

1630 770 52.0 15.2 3.62 .59 .74 .89 50.0 14.7 4.08 .60 .76 .90 47.9 14.0 4.63 .61 .77 .92 45.8 13.4 5.25 .62 .79 .94(19�C)

1830 865 52.7 15.4 3.63 .61 .77 .92 50.7 14.9 4.10 .62 .79 .94 48.6 14.2 4.65 .63 .81 .96 46.4 13.6 5.27 .64 .83 .98

71�F1430 675 54.4 15.9 3.67 .43 .56 .69 52.4 15.4 4.14 .43 .56 .70 50.3 14.7 4.68 .43 .57 .71 48.0 14.1 5.32 .44 .58 .73

71�F(22�C)

1630 770 55.3 16.2 3.68 .43 .58 .72 53.2 15.6 4.15 .44 .59 .73 51.0 14.9 4.70 .44 .60 .75 48.8 14.3 5.34 .44 .61 .77(22�C)

1830 865 56.0 16.4 3.70 .44 .60 .75 53.9 15.8 4.16 .45 .61 .77 51.7 15.2 4.72 .45 .62 .79 49.4 14.5 5.35 .45 .63 .81

HS29−048 � CH33−48C−2F WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1430 675 48.5 14.2 3.55 .74 .88 .99 46.7 13.7 4.01 .75 .89 1.00 44.8 13.1 4.55 .76 .91 1.00 42.8 12.5 5.17 .78 .93 1.00

63�F(17�C)

1630 770 49.6 14.5 3.57 .77 .92 1.00 47.7 14.0 4.03 .78 .93 1.00 45.8 13.4 4.56 .80 .95 1.00 43.8 12.8 5.18 .81 .97 1.00(17�C)

1830 865 50.5 14.8 3.59 .80 .95 1.00 48.6 14.2 4.04 .81 .97 1.00 46.7 13.7 4.58 .83 .98 1.00 44.8 13.1 5.21 .85 .99 1.00

67�F1430 675 51.6 15.1 3.60 .57 .71 .85 49.6 14.5 4.07 .58 .72 .86 47.6 14.0 4.60 .59 .74 .88 45.4 13.3 5.23 .60 .76 .90

67�F(19�C)

1630 770 52.5 15.4 3.62 .59 .74 .89 50.5 14.8 4.08 .60 .76 .90 48.4 14.2 4.62 .61 .77 .92 46.2 13.5 5.24 .62 .79 .94(19�C)

1830 865 53.2 15.6 3.63 .61 .77 .92 51.2 15.0 4.10 .62 .79 .94 49.0 14.4 4.64 .63 .81 .96 46.8 13.7 5.26 .64 .83 .98

71�F1430 675 54.9 16.1 3.66 .43 .56 .69 52.9 15.5 4.13 .43 .57 .70 50.7 14.9 4.67 .43 .57 .71 48.5 14.2 5.31 .44 .58 .73

71�F(22�C)

1630 770 55.8 16.4 3.68 .44 .58 .72 53.7 15.7 4.15 .44 .59 .73 51.5 15.1 4.69 .44 .60 .75 49.2 14.4 5.33 .45 .61 .77(22�C)

1830 865 56.6 16.6 3.69 .44 .60 .75 54.4 15.9 4.16 .44 .61 .77 52.1 15.3 4.71 .45 .62 .78 49.8 14.6 5.34 .45 .63 .80

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 33 �

Page 34: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−048 � CH33−50/60−2F WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1430 675 48.9 14.3 3.56 .74 .88 .99 47.0 13.8 4.02 .75 .89 1.00 45.1 13.2 4.55 .76 .91 1.00 43.1 12.6 5.17 .78 .93 1.00

63�F(17�C)

1630 770 49.9 14.6 3.58 .76 .92 1.00 48.1 14.1 4.03 .78 .93 1.00 46.1 13.5 4.57 .80 .95 1.00 44.1 12.9 5.20 .81 .97 1.00(17�C)

1830 865 50.9 14.9 3.59 .80 .95 1.00 49.0 14.4 4.06 .81 .97 1.00 47.0 13.8 4.59 .83 .99 1.00 45.0 13.2 5.22 .85 1.00 1.00

67�F1430 675 52.0 15.2 3.61 .58 .71 .84 50.0 14.7 4.08 .58 .72 .86 47.9 14.0 4.61 .59 .74 .88 45.8 13.4 5.24 .60 .75 .90

67�F(19�C)

1630 770 53.0 15.5 3.63 .59 .74 .89 51.0 14.9 4.09 .60 .75 .90 48.8 14.3 4.63 .61 .77 .92 46.5 13.6 5.27 .62 .79 .94(19�C)

1830 865 53.8 15.8 3.64 .61 .77 .92 51.6 15.1 4.11 .62 .79 .94 49.4 14.5 4.65 .63 .81 .96 47.2 13.8 5.28 .64 .83 .98

71�F1430 675 55.5 16.3 3.67 .43 .56 .69 53.3 15.6 4.15 .43 .56 .70 51.1 15.0 4.69 .43 .57 .71 48.9 14.3 5.32 .44 .58 .73

71�F(22�C)

1630 770 56.4 16.5 3.69 .43 .58 .72 54.2 15.9 4.16 .44 .58 .73 52.0 15.2 4.71 .44 .59 .75 49.6 14.5 5.35 .45 .61 .77(22�C)

1830 865 57.1 16.7 3.71 .44 .60 .75 54.9 16.1 4.18 .44 .61 .77 52.6 15.4 4.73 .45 .62 .79 50.2 14.7 5.36 .45 .63 .81

HS29−060 � C33−50/60C−2 WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 57.5 16.9 4.47 .71 .84 .96 55.5 16.3 5.04 .72 .86 .97 53.4 15.6 5.67 .73 .87 .98 51.1 15.0 6.37 .74 .89 .99

63�F(17�C)

1760 830 58.7 17.2 4.46 .73 .87 .98 56.7 16.6 5.03 .74 .89 .99 54.6 16.0 5.67 .76 .90 1.00 52.3 15.3 6.36 .77 .92 1.00(17�C)

1960 925 59.8 17.5 4.46 .76 .90 1.00 57.8 16.9 5.03 .77 .92 1.00 55.6 16.3 5.66 .78 .93 1.00 53.3 15.6 6.36 .80 .95 1.00

67�F1560 735 61.4 18.0 4.46 .56 .68 .81 59.4 17.4 5.02 .56 .69 .82 57.2 16.8 5.66 .57 .70 .83 54.8 16.1 6.35 .58 .72 .85

67�F(19�C)

1760 830 62.6 18.3 4.45 .57 .71 .84 60.5 17.7 5.02 .58 .72 .85 58.2 17.1 5.65 .58 .73 .87 55.8 16.4 6.34 .59 .74 .89(19�C)

1960 925 63.6 18.6 4.45 .58 .73 .87 61.4 18.0 5.01 .59 .74 .89 59.0 17.3 5.64 .60 .76 .90 56.6 16.6 6.33 .61 .77 .92

71�F1560 735 65.7 19.3 4.46 .42 .54 .66 63.6 18.6 5.01 .42 .54 .67 61.3 18.0 5.63 .43 .55 .68 58.8 17.2 6.33 .43 .56 .69

71�F(22�C)

1760 830 66.8 19.6 4.47 .43 .55 .68 64.6 18.9 5.03 .43 .56 .69 62.2 18.2 5.65 .43 .57 .70 59.8 17.5 6.34 .43 .58 .72(22�C)

1960 925 67.7 19.8 4.49 .43 .57 .71 65.4 19.2 5.05 .43 .58 .72 63.0 18.5 5.67 .44 .59 .73 60.5 17.7 6.35 .44 .60 .75

HS29−060 � C33−60D−2 WITH G60UHV−60D−135 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 57.4 16.8 4.47 .71 .84 .96 55.5 16.3 5.04 .72 .85 .97 53.3 15.6 5.67 .73 .87 .98 51.1 15.0 6.37 .74 .88 .99

63�F(17�C)

1760 830 58.7 17.2 4.46 .73 .87 .98 56.7 16.6 5.03 .74 .89 .99 54.5 16.0 5.67 .75 .90 1.00 52.2 15.3 6.36 .77 .92 1.00(17�C)

1960 925 59.8 17.5 4.46 .75 .90 1.00 57.7 16.9 5.03 .77 .92 1.00 55.6 16.3 5.66 .78 .93 1.00 53.3 15.6 6.36 .80 .95 1.00

67�F1560 735 61.5 18.0 4.46 .56 .68 .80 59.4 17.4 5.02 .56 .69 .82 57.1 16.7 5.65 .57 .70 .83 54.8 16.1 6.35 .58 .71 .85

67�F(19�C)

1760 830 62.7 18.4 4.45 .57 .70 .84 60.5 17.7 5.02 .58 .72 .85 58.2 17.1 5.65 .58 .73 .87 55.8 16.4 6.34 .59 .74 .89(19�C)

1960 925 63.6 18.6 4.45 .58 .73 .87 61.4 18.0 5.01 .59 .74 .88 59.0 17.3 5.64 .60 .76 .90 56.6 16.6 6.33 .61 .77 .92

71�F1560 735 65.7 19.3 4.48 .42 .54 .66 63.5 18.6 5.04 .42 .54 .66 61.2 17.9 5.66 .43 .55 .67 58.8 17.2 6.34 .43 .56 .69

71�F(22�C)

1760 830 66.8 19.6 4.50 .43 .55 .68 64.5 18.9 5.06 .43 .56 .69 62.2 18.2 5.68 .43 .57 .70 59.7 17.5 6.36 .43 .58 .72(22�C)

1960 925 67.7 19.8 4.52 .43 .57 .70 65.4 19.2 5.07 .43 .58 .72 63.0 18.5 5.70 .44 .58 .73 60.4 17.7 6.37 .44 .59 .75

HS29−060 � C33−62D−2 WITH G60UHV−60D−135 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 59.0 17.3 4.47 .71 .84 .96 56.9 16.7 5.03 .72 .86 .97 54.7 16.0 5.67 .73 .87 .99 52.4 15.4 6.37 .75 .89 1.00

63�F(17�C)

1760 830 60.3 17.7 4.46 .74 .88 .99 58.2 17.1 5.03 .75 .89 1.00 56.0 16.4 5.66 .76 .91 1.00 53.7 15.7 6.36 .78 .93 1.00(17�C)

1960 925 61.5 18.0 4.46 .76 .91 1.00 59.4 17.4 5.02 .77 .92 1.00 57.1 16.7 5.66 .79 .94 1.00 54.8 16.1 6.35 .81 .96 1.00

67�F1560 735 63.1 18.5 4.46 .56 .69 .81 60.9 17.8 5.02 .56 .69 .82 58.6 17.2 5.65 .57 .71 .84 56.2 16.5 6.34 .58 .72 .85

67�F(19�C)

1760 830 64.2 18.8 4.48 .57 .71 .84 62.0 18.2 5.04 .58 .72 .86 59.6 17.5 5.66 .59 .74 .88 57.2 16.8 6.34 .60 .75 .89(19�C)

1960 925 65.2 19.1 4.50 .59 .74 .88 62.9 18.4 5.06 .60 .75 .89 60.5 17.7 5.67 .60 .76 .91 58.0 17.0 6.36 .61 .78 .93

71�F1560 735 67.2 19.7 4.53 .43 .54 .66 65.0 19.0 5.09 .42 .55 .67 62.6 18.3 5.71 .43 .55 .68 60.0 17.6 6.40 .43 .56 .70

71�F(22�C)

1760 830 68.4 20.0 4.55 .43 .56 .69 66.0 19.3 5.11 .43 .57 .70 63.6 18.6 5.74 .43 .57 .71 61.0 17.9 6.42 .44 .58 .73(22�C)

1960 925 69.3 20.3 4.56 .43 .57 .71 66.9 19.6 5.13 .44 .58 .73 64.4 18.9 5.76 .44 .59 .74 61.8 18.1 6.44 .44 .60 .76

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 34 �

Page 35: CONDENSING UNITS HS21/HS26/HS27/HS2949,000 14.4 13.05 9.70 5060 C33−48C−2 with G60UHV−60C−090 26K35 (LB−85663K) 4 Coils/FurnaceTon (78 dB) 50,000 14.7 13.20 9.80 5090 C33−50/60C−2

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HS29−060 � CH33−50/60C−2F WITH G60UHV−60C−090 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 58.4 17.1 4.49 .71 .84 .95 56.3 16.5 5.06 .72 .85 .97 54.2 15.9 5.70 .73 .87 .98 51.9 15.2 6.40 .74 .88 .99

63�F(17�C)

1760 830 59.7 17.5 4.48 .73 .87 .98 57.6 16.9 5.05 .74 .89 .99 55.4 16.2 5.69 .75 .90 1.00 53.1 15.6 6.39 .77 .92 1.00(17�C)

1960 925 60.8 17.8 4.48 .75 .90 1.00 58.7 17.2 5.05 .77 .92 1.00 56.5 16.6 5.69 .78 .93 1.00 54.1 15.9 6.38 .80 .95 1.00

67�F1560 735 62.5 18.3 4.48 .56 .68 .80 60.4 17.7 5.05 .56 .69 .82 58.1 17.0 5.68 .57 .70 .83 55.7 16.3 6.37 .57 .71 .85

67�F(19�C)

1760 830 63.7 18.7 4.48 .57 .70 .84 61.5 18.0 5.04 .58 .72 .85 59.2 17.3 5.67 .58 .73 .87 56.7 16.6 6.37 .59 .74 .89(19�C)

1960 925 64.7 19.0 4.50 .58 .73 .87 62.4 18.3 5.05 .59 .74 .88 60.1 17.6 5.68 .60 .75 .90 57.6 16.9 6.36 .61 .77 .92

71�F1560 735 66.7 19.5 4.53 .42 .54 .66 64.5 18.9 5.09 .42 .54 .66 62.1 18.2 5.71 .43 .55 .67 59.7 17.5 6.40 .43 .56 .69

71�F(22�C)

1760 830 67.9 19.9 4.55 .43 .55 .68 65.6 19.2 5.11 .43 .56 .69 63.2 18.5 5.73 .43 .57 .70 60.6 17.8 6.43 .43 .58 .72(22�C)

1960 925 68.8 20.2 4.56 .43 .57 .70 66.5 19.5 5.12 .43 .58 .72 64.0 18.8 5.76 .44 .58 .73 61.4 18.0 6.44 .44 .59 .75

HS29−060 � CH33−60D−2F WITH G60UHV−60D−135 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 57.9 17.0 4.49 .71 .84 .95 55.9 16.4 5.06 .72 .85 .97 53.7 15.7 5.70 .73 .87 .98 51.5 15.1 6.40 .74 .89 .99

63�F(17�C)

1760 830 59.1 17.3 4.48 .73 .87 .98 57.1 16.7 5.05 .74 .89 .99 54.9 16.1 5.69 .75 .90 1.00 52.6 15.4 6.39 .77 .92 1.00(17�C)

1960 925 60.2 17.6 4.48 .75 .90 1.00 58.2 17.1 5.05 .77 .92 1.00 56.0 16.4 5.69 .78 .93 1.00 53.7 15.7 6.39 .80 .95 1.00

67�F1560 735 61.9 18.1 4.48 .56 .68 .80 59.8 17.5 5.05 .56 .69 .82 57.6 16.9 5.68 .57 .70 .83 55.2 16.2 6.38 .58 .71 .85

67�F(19�C)

1760 830 63.1 18.5 4.47 .57 .71 .84 61.0 17.9 5.04 .58 .72 .85 58.6 17.2 5.67 .58 .73 .87 56.2 16.5 6.37 .59 .74 .89(19�C)

1960 925 64.1 18.8 4.47 .59 .73 .87 61.9 18.1 5.04 .59 .74 .88 59.5 17.4 5.67 .60 .76 .90 57.0 16.7 6.36 .61 .77 .92

71�F1560 735 66.2 19.4 4.50 .42 .54 .66 64.0 18.8 5.06 .42 .54 .66 61.6 18.1 5.69 .43 .55 .68 59.2 17.3 6.37 .43 .56 .69

71�F(22�C)

1760 830 67.3 19.7 4.52 .43 .55 .68 65.0 19.0 5.08 .43 .56 .69 62.6 18.3 5.71 .43 .57 .70 60.1 17.6 6.39 .43 .58 .72(22�C)

1960 925 68.2 20.0 4.54 .43 .57 .71 65.9 19.3 5.10 .43 .58 .72 63.5 18.6 5.72 .44 .58 .73 60.9 17.8 6.40 .44 .59 .75

HS29−060 � CH33−62D−2F WITH G60UHV−60D−135 COOLING CAPACITY − TXV Systems OnlyOutdoor Air Temperature Entering Outdoor Coil

EnteringTotalAi

85�F (29�C) 95�F (35�C) 105�F (41�C) 115�F (46�C)EnteringWet Bulb

TotalAir

Volume TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

TotalCooling Comp

Sensible To TotalRatio (S/T)

Wet BulbTempera�

ture

VolumeCoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulb

CoolingCapacity

CompMotor

kW

Ratio (S/T)Dry Bulbture

cfm L/s kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

kBtuh kW

MotorkW

Input 75�F24�C

80�F27�C

85�F29�C

63�F1560 735 58.4 17.1 4.48 .71 .84 .95 56.3 16.5 5.05 .72 .85 .97 54.1 15.9 5.69 .73 .87 .98 51.8 15.2 6.39 .74 .88 1.00

63�F(17�C)

1760 830 59.7 17.5 4.48 .73 .87 .98 57.6 16.9 5.04 .74 .88 .99 55.4 16.2 5.68 .75 .90 1.00 53.0 15.5 6.38 .77 .92 1.00(17�C)

1960 925 60.8 17.8 4.47 .75 .90 1.00 58.7 17.2 5.04 .77 .91 1.00 56.5 16.6 5.67 .78 .93 1.00 54.1 15.9 6.37 .80 .95 1.00

67�F1560 735 62.5 18.3 4.47 .56 .68 .80 60.4 17.7 5.04 .56 .69 .82 58.1 17.0 5.67 .57 .70 .83 55.7 16.3 6.36 .57 .71 .85

67�F(19�C)

1760 830 63.7 18.7 4.49 .57 .70 .84 61.5 18.0 5.04 .58 .71 .85 59.2 17.3 5.67 .58 .73 .87 56.7 16.6 6.35 .59 .74 .88(19�C)

1960 925 64.7 19.0 4.50 .58 .73 .87 62.4 18.3 5.07 .59 .74 .88 60.0 17.6 5.69 .60 .76 .90 57.5 16.9 6.37 .61 .77 .92

71�F1560 735 66.7 19.5 4.54 .42 .54 .65 64.4 18.9 5.10 .42 .54 .66 62.1 18.2 5.72 .43 .55 .67 59.6 17.5 6.42 .43 .56 .69

71�F(22�C)

1760 830 67.8 19.9 4.56 .43 .55 .68 65.6 19.2 5.12 .43 .56 .69 63.1 18.5 5.75 .43 .57 .70 60.5 17.7 6.44 .43 .58 .72(22�C)

1960 925 68.8 20.2 4.58 .43 .57 .70 66.4 19.5 5.14 .43 .58 .72 63.9 18.7 5.77 .44 .58 .73 61.4 18.0 6.45 .44 .59 .75

Ratings − HS21/HS26/HS27/HS29 Coil and Furnace Matches Page 35 �