INSTALLATION AND OPERATING INSTRUCTIONS Adiabatic High-Pressure Humidifier 2545099 EN 0902 Condair FF2

Transcript of condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the...

Page 1: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

InstallatIon and operatIng InstructIons

adiabatic High-pressure Humidifier

2545

099

en

090

2

condair FF2

Page 2: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components
Page 3: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

Contents

6 Initialcommissioning 36

6.1 ChecklistinitialcommissioningCondairFF2 36

7 Operation 38

7.1 Displayandoperatingelements 38

7.2 Settingtheunitintooperation 39

7.3 Inspectionsduringoperation 40

7.4 Settingtheunitoutofservice 40

8 Maintenanceandreplacementofcomponents 41

8.1 Importantnotesonmaintenance 41

8.2 Maintenanceintervals 42

8.3 Maintenancework 42

8.4 Resettingthemaintenanceindication 43

8.5 Removalofcomponents 448.5.1 Removalandinstallationofspraynozzles 448.5.2 Replacementofpistonpackings 44

8.6 Changingtheoilofthepistonpump 45

9 Troubleshooting 46

9.1 Importantnotesontroubleshooting 46

9.2 Malfunctionwitherrorindication 46

9.3 Resettingtheerrorindication 46

9.4 Malfunctionwithouterrorindication 47

9.5 Replacingthefuseofthecontrolunit 49

10 Productdata 50

10.1 Technicalspecifications/ambientconditions 50

10.2 Declarationofconformity 51

10 Appendix 52

10.1 Diagramh,x 52

11.2 Commissioaningprotocol(copytemplate) 53

1 Introduction 4

1.1 Totheverybeginning 4

1.2 Notesontheinstallationandoperatinginstructions 4

2 Foryoursafety 6

3 OverviewofCondairFF2 8

3.1 CondairFF2systemoverview 83.1.1 Stand-alonesystem

(masterconfiguration) 83.1.2 Compoundsystem

(master-slaveconfiguration) 93.2 Pumpstation 10

3.3 Humidifierunit 12

3.4 Functionaldescription 14

3.5 Scopeofdelivery 17

4 Notesonplanning 18

4.1 Recordofsite-specificdata 18

4.2 Accessoriesandoptions 19

5 Installationworks 20

5.1 Importantnotesoninstallation 20

5.2 Mountingofthenozzleunit 205.2.1 Notesonpositioningand

mountingofthenozzleunit 205.2.2 Mountingthenozzleunit 21

5.3 Mountingthepumpstation 265.3.1 Notesonpositioningand

mountingthepumpstation 265.3.2 Dimensionandweightsofpumpstation 275.3.3 Mountingthepumpstation 285.3.4 Waterinstallation 29

5.4 MountingthecontrolunitFF2Slave 31

5.5 Electricalinstallation 325.5.1 WiringdiagramMasterunits

(stand-aloneunits) 325.5.2 WiringdiagramSlaveunits 335.5.3 Notesonelectricinstallation 34

Page 4: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

4

LimitationThesubjectoftheseinstallationandoperatinginstructionsisCondairFF2AdiabaticHighPressureHumidifier.Thevariousaccessoriesareonlydescribedinsofarasthisisnecessaryforproperoperationoftheequipment.Furtherinformationonaccessoriescanbeobtainedinthere-spectiveinstructions.

These installation and operating instructions are restricted to the installation,commissioning,operation,servicingandtroubleshootingoftheCondairFF2andismeantforwelltrainedper-sonnelbeingsufficientlyqualifiedfortheirrespectivework.

Theseinstallationandoperatinginstructionsaresupplementedbyvariousseparateitemsofdocu-mentation(installationdrawings,technicalspecifications,etc.).Wherenecessary,appropriatecross-referencesaremadetothesepublicationsintheinstallationandoperatinginstructions.

1 Introduction

WethankyouforhavingpurchasedtheCondairFF2AdiabaticHighPressureHumidifier(“Con-dairFF2”forshort).

The Condair FF2 incorporates the latest technicaladvances and meets all recognized safetystandards.Nevertheless,improperuseoftheCondairFF2mayresultindangertotheuserorthirdpartiesand/orimpairmentofmaterialassets.

Toensureasafe,proper,andeconomicaloperationofthesteamhumidifierCondairFF2,pleaseobserveandcomplywithallinformationandsafetyinstructionscontainedinthepresentinstallationandoperatinginstructionsaswellastheinstructionsgiveninthemanualsforthecomponentsusedinthehumidificationsystem.

Ifyouhavequestions,whicharenotorinsufficientlyansweredinthisdocumentation,pleasecontactyourCondairsupplier.Theywillbegladtoassistyou.

1.2 Notesontheinstallationandoperatinginstructions

1.1 Totheverybeginning

Page 5: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

5

Symbolsusedinthismanual

CAUTION!Thecatchword“CAUTION”designatesnotesinthisinstallation and operating instructions that, ifinstallationandoperatinginstructions that, ifthat,ifneglected,maycausedamageand/ormalfunctionoftheunitorothermaterialassets.

WARNING!Thecatchword“WARNING”usedinconjunctionwiththegeneralcautionsymboldesignatessafetyanddangernotesinthisinstallationandoperatinginstructionsthat, ifneglected,maycausetoinjurytopersons.

DANGER!Thecatchword“DANGER”usedinconjunctionwiththegeneralcautionsymboldesignatessafetyanddangernotesinthisinstallationandoperatinginstructionsthat,ifneglected,mayleadtosevereinjuryorevendeathofpersons.

SafekeepingPleasesafeguardtheseinstallationandoperatinginstructionsinasafeplace,wheretheycanbeimmediatelyaccessed.Iftheequipmentchangeshands,thedocumentationmustbepassedontothenewoperator.

Ifthedocumentationgetsmislaid,pleasecontactyourCondairsupplier.

LanguageversionsTheseinstallationandoperatinginstructionsareavailableinvariouslanguages.PleasecontactyourCondairsupplierforinformation.

CopyrightprotectionThepresentinstallationandoperatinginstructionsisprotectedundertheCopyrightAct.Passing-onandreproductionofthemanual(orpartthereof)aswellasexploitationandcommunicationofthecontentsareprohibitedwithoutwrittenpermissionbythemanufacturer.Violationofcopyrighttermsissubjecttolegalprosecutionandarisesliabilityforindemnification.

Themanufacturerreservestherighttofullyexploitcommercialpatentrights.

Page 6: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

6

2 Foryoursafety

GeneralEverypersonworkingwiththeCondairFF2musthavereadandunderstoodthe installationandoperatinginstructionsbeforecarryingoutanywork.Knowingandunderstanding thecontentsof the installationandoperating instructions isabasicrequirementforprotectingthepersonnelagainstanykindofdanger,topreventfaultyoperation,andtooperatetheunitsafelyandcorrectly.

All ideograms, signs and markings applied to the unit must be observed and kept in readablestate.

QualificationofpersonnelAllactionsdescribedinthepresent installationandoperatinginstructions(installation,operation,maintenance,etc.)mustbecarriedoutonlybywelltrainedandsufficientlyqualifiedpersonnelauthorisedbytheowner.Forsafetyandwarrantyreasonsanyactionbeyondthescopeofthismanualsmustbecarriedoutonlybyqualifiedpersonnelauthorisedbythemanufacturer.

ItisassumedthatallpersonsworkingwiththeCondairFF2arefamiliarandcomplywiththeappro-priateregulationsonworksafetyandthepreventionofaccidents.

IntendeduseTheCondairFF2isintendedexclusivelyforhumidificationinventilationsystemswithinthespeci-fiedoperatingconditions(seechapter10“Productspecifications”).AnyothertypeofapplicationwithouttheexpresswrittenconsentofthemanufacturerisconsideredasnotconformingwiththeintendedpurposeandmayleadtotheCondairFF2becomingdangerous.Operationoftheequipmentintheintendedmannerrequiresthatalltheinformationintheseinstal-lationandoperatinginstructionsisobserved(inparticularthesafetyinstructions)

Page 7: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

7

Dangerthatmayarisefromtheunit

CAUTION! DangerofelectricshockOnemaygetintouchwithlivepartswhenthepumpstation/controlunitisopen.Touchinglivepartsmaycausesevereinjuryordangertolife..Prevention:beforecarryingoutanyworkontheCondairFF2,settheunitoutofoperationasde-scribedinchapter7.4(switchofftheunit,disconnectitfromthemainsandstopthewatersupply)andsecuretheunitagainstinadvertentpower-up.

WARNING!Poorlymaintainedhumidificationsystemsmayendangerhealth.Wheninsufficientlymaintainedharmfulgermscanbuildupintheairductandaffecttheductair.

Prevention:asdescribedinchapter8“Maintenance”,theCondairFF2mustbecleanedinthespecifiedintervalsandthecleaningworkmustbecarriedoutcorrectly.

WARNING!Duringoperationthewatersystemisathighpressure.Inappropriatelyfastenedhosescanbetornoutofthescrewconnectionsduringoperationbythehighpressure.Thereisdangerofinjury,innocircumstancesloosenanyhosesorscrewconnectionsduringoperation.

Prevention:alwayscorrectlytightenthehighpressurehosesandscrewconnectionsanddonotloosenanyhosesorscrewconnectionsduringoperation.BeforecarryingoutanyworkontheCon-dairFF2,settheunitoutofoperationasdescribedinchapter7.4(switchofftheunit,disconnectitfromthemainsandstopthewatersupply)andsecuretheunitagainstinadvertentpower-up.

BehaviourincaseofdangerIfitissuspectedthatsafeoperationisnolongerpossible,thentheCondairFF2shouldimmediatelybeshutdownandsecuredagainstaccidentalpower-upaccordingtochapter7.4(switchoffsystems,disconnectitfromthemainsandstopthewatersupply).Thiscanbethecaseunderthefollowingcircumstances:– ifcomponentsoftheCondairFF2aredamaged,wornorbadlysoiled.– iftheCondairFF2doesnotworkcorrectly.– ifconnectorsandlinesareleaking.– afterlongtimestorageunderunfavourableconditions.– aftertransportationunderunfavourableconditions.

AllpersonsworkingwiththeCondairFF2mustreportanyalterationstotheunitthatmayaffectsafetytotheownerwithoutdelay.

ProhibitedmodificationstotheunitNomodificationsmustbeundertakenontheCondairFF2withouttheexpresswrittenconsentofthemanufacturer.

ForthereplacementofdefectivecomponentsuseexclusivelyoriginalaccessoriesandsparepartsavailablefromyourCondairsupplier.

Page 8: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

8

2

1

7

4

3

6

5

8

3 OverviewofCondairFF2

Humidifierunitconsistingof:1 StepvalvesY3,Y4andY52 Nozzleunit3 Dropletseparator(optionorproductofothermanufacturer)4 Flushingvalvehighpressuresystem(option)

Pumpstationconsistingof:5 Pumpunit6 Controlunit7 High-pressurepiping8 Floorstand(option)

3.1 CondairFF2systemoverview

3.1.1 Stand-alonesystem(masterconfiguration)

Page 9: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

9

3.1.2 Compoundsystem(master-slaveconfiguration)

Mastersystemconsistingof:– pumpstation– humidifierunit

Assumingthemaximumpumpcapacityissufficient,thepumpstationofastand-alonesystemmaysupplypressurizedwatertouptothreefurtherFF2systemsbuildingaso-calledmaster-slavecon-figurationasshownbelow.

Slavesystemsconsistingof:– controlunitFF2slave– humidifierunit

Buscable

High-pressurepiping

Slavesystem1

Slavesystem3

Slavesystem2

Page 10: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

10

3.2 Pumpstation

Overview

1 Oilpan2 Connectorhousingdrain3 Jettingpump4 Pumpmotor5 Flush/reliefconnector6 High-pressureconnector7 Supplyconnector8 Stopvalve9 Pressuretransmitter(workingpressure)10 Supplyvalve11 Pressurereducingvalve12 Waterfilter13 Flushingvalve(supply)

14 Conductivitysensor(option)15 Safetyvalvesupplypressure16 Safetyvalveworkingpressure17 Manometerworkingpressure18 Manometersupplypressure19 Minimumpressureswitch(supplypressure)20 Frequencyconverterpumpmotor21 Driverboard22 Ratingplate23 BMSgateway(optione-LINKSFF2)24 Remoteoperation/faultindicationboard(option)25 Displayandcontrolunitwithcontrol26 Floorstand(option)

678

109

1112

13

1415

5

3

2

1

4

25

26

21

20

19

18

17

16

23

24

22

Page 11: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

11

M

Y6

BriefdescriptionofpumpstationThepumpstationconsistsofthecontrolunitandthepumpunitanditissuppliedinahousingreadyforconnection.

Pumpunit:Theoil-lubricatedhighpressurepumpisdirectlymountedtotheelectricmotorandreachesthemaximumcapacityof1’080kg/hatanoperatingpressureof80bar.Assumingthemaximumpumpcapacityissufficient,uptothreefurtherFF2systemsmaybeconnectedtothejettingpumpviathehigh-pressurecircularpiping.

Aminimumpressureswitchcontinuouslymonitorstheminimumsupplypressureandapressuretransmittercontinuouslymonitorstheminimumworkingpressure.Theystoppumpoperationincasetheminimumpressurevaluesdropbelowthelimitforacertaintime.Twosafetyvalvesensurethatthemaximumsupplypressureandthemaximumworkingpressurearenotexceeded.Thepressurereducingvalvemaintainsconstantsupplypressure.

Attheinstallationsite,thesupplylineofdemineralizedwater,thehigh-pressurehoseofthepiping(accessory)andthedrainmustbeconnectedtothejettingpump.

Controlunit:thecontrolunitconsistsofthedisplayandcontrolunit,thedriverboard,thefrequencyconverterforthecontrolofthehighpressurepumpandtheconnectionterminalsforthepowersupply(380...400V/3N~/50-60Hz).Optionallythecontrolunitcanbeequippedwitharemoteoperatingandfaultindicationprint,aconductivitymonitoringandaBMSgateway(e-LINKSFF2)fortheintegrationintoabuildingmanagementsystem(BMS).Thepumpstationiselectricallywiredatthefactory.Attheinstallationsite,thepowersupply,thehumiditycontrollerorhumiditysensor,theremoteoperatingandfaultindication(option),theexternalsafetychainandthestepvalvesmustbeelectricallyconnectedtothecontrolunit.

Stop valve

Supply valve

Pressure reducing valve

Min. pressure switch supply pressure

Manometer supply pressure

Manometer working pressure

Pressure transmitter working pressure

Step valves

Step valvesSlave 1 ... Slave 3

Safety valve working pressure

Safety valve supply “Y2”

Safety valve supply pressure

Water filter

Conductivity sensor (option)

High pressurepump

High pressure piping

Relief valve workingpressure (option)

Page 12: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

12

3.3 Humidifierunit

1 Supportingstructurenozzleunit2 Nozzlepipes3 Spraynozzle4 High-pressurepipingfrompumpstation5 StepvalveY3(1/7)6 StepvalveY4(2/7)7 StepvalveY5(4/7)8 FlushingvalveY6workingpressure(option)

9 Waterdrainafternozzles10 Siphon(bycustomers,

heightadaptedtoductpressure)11 Opendrainfunnel(bycustomers)12 Dropletseparator(optionorproductof

othermanufacturer)13 Waterdrainafterhumidifierunit

4

5

6

7

8

9

10

11

1

3

2

12

10

13

11

Page 13: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

13

NozzleunitThenozzleunitconsistsofseveralnozzlepipes,whichareequippedwiththenecessarynumberofnozzles(system-specific).Theindividualnozzlepipesaredividedintothreedifferentspraycircuits(1/7,2/7and4/7).Thespraycircuitsareconnectedviaahighpressurehosestothecorrespondingstepvalves(eitherdirectlyorviaadistributionblocks).

DropletseparatorTheinstallationofadropletseparatoristhecustomersresponsibility.AnoptionaldropletseparatorisavailablefortheCondairFF2(seeoppositeillustration).Detailedinformationregardingtheoptionaldropletseparatorcanbefoundintheseparatedocumentationtothisproduct.

Page 14: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

14

M

Y3 (1/7)

Y4 (2/7)

Y5 (4/7)

Y2

5

18

22

2324

2526

2728

P/PI 3a

16211

8

9

13

1514

17

2PI

D3b4

7

6

20

19

1211

10

Y6

380..

.400V

/3N~/

50-6

0Hz

3.4 FunctionaldescriptionEl

emen

tary

dia

gram

ofC

onda

irFF

2(s

tand

-alo

nes

yste

m)

1 Pu

mp st

ation

2 Co

ntrol

unit

3a

Exter

nal P

- or P

I-con

trolle

r3b

Int

erna

l PID

contr

oller

4 Re

mote

oper

ation

/fault

indic

ation

relay

5 Po

wer s

upply

6 Fr

eque

ncy c

onve

rter p

ump m

otor

7 Je

tting p

ump

8 St

op va

lve9

Supp

ly va

lve10

Pr

essu

re re

ducin

g valv

e11

W

ater fi

lter

12

Cond

uctiv

ity se

nsor

13

Safet

y valv

e (su

pply

pres

sure

)14

Mi

n. pr

essu

re sw

itch (

supp

ly pr

essu

re)

15

Pres

sure

tran

smitte

r (wo

rking

pres

sure

)16

Flu

shing

valve

Y2 s

upply

pres

sure

17

Safet

y valv

e (wo

rking

pres

sure

)18

Dr

ain pu

mp st

ation

(by c

ustom

ers)

19

High

-pre

ssur

e pipi

ng20

Flu

shing

valve

Y6 w

orkin

g pre

ssur

e (op

tion)

21

Step

valve

s Y3,

Y4 an

d Y5

22

Duct

drain

s with

siph

on (b

y cus

tomer

s)23

Dr

oplet

sepa

rator

24

Spra

y noz

zles

25

Air fi

lter m

in. F

7 (by

custo

mers)

26

Humi

dity s

enso

r (by

custo

mers)

27

Safet

y hum

idista

t (sa

fety c

hain,

by cu

stome

rs)28

Flo

w mo

nitor

ing de

vice

(safet

y cha

in, by

custo

mers)

Curre

ntW

ater

Page 15: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

15

2PI

D3b4

5

Y3 (1/7)

Y4 (2/7)

Y5 (4/7)

22

2324

2526

2728

P/PI 3a

21

20

M

Y3 (1/7)

Y4 (2/7)

Y5 (4/7)

Y2

5

18

22

2324

2526

2728

P/PI 3a

16211

8

9

13

1514

17

2PI

D3b4

7

6

20

19

1211

10

29

Y6Y6

Slav

e 1Sl

ave 2

... S

lave 3

Slav

e 2 ...

Slav

e 3

Mast

er

380..

.400V

/3N~/

50-6

0Hz

230V

/1N~/

50-6

0Hz

Elem

enta

ryd

iagr

amo

fCon

dair

FF2

(mas

ter-

slav

eco

mpo

und

conf

igur

atio

n)

Curre

ntW

ater

Bus

1 Pu

mp st

ation

2 Co

ntrol

unit

3a

Exter

nal P

- or P

I-con

trolle

r3b

Int

erna

l PID

contr

oller

4 Re

mote

oper

ation

/fault

indic

ation

relay

5 Po

wer s

upply

6 Fr

eque

ncy c

onve

rter p

ump m

otor

7 Je

tting p

ump

8 St

op va

lve9

Supp

ly va

lve10

Pr

essu

re re

ducin

g valv

e

11

Wate

r filte

r12

Co

nduc

tivity

sens

or13

Sa

fety v

alve (

supp

ly pr

essu

re)

14

Min.

pres

sure

switc

h (su

pply

pres

sure

)15

Pr

essu

re tr

ansm

itter (

worki

ng pr

essu

re)

16

Flush

ing va

lve Y

2 sup

ply pr

essu

re17

Sa

fety v

alve (

worki

ng pr

essu

re)

18

Drain

pump

stati

on (b

y cus

tomer

s)19

Hi

gh-p

ress

ure p

iping

20

Flush

ing va

lve Y

6 wor

king p

ress

ure

(opti

on)

21

Step

valve

s Y3,

Y4 an

d Y5

22

Duct

drain

s with

siph

on (b

y cus

tomer

s)23

Dr

oplet

sepa

rator

24

Spra

y noz

zles

25

Air fi

lter m

in. F

7 (by

custo

mers)

26

Humi

dity s

enso

r (by

custo

mers)

27

Safet

y hum

idista

t (sa

fety c

hain,

by cu

stome

rs)28

Flo

w mo

nitor

ing de

vice

(safet

y cha

in, by

custo

mers)

29

RJ45

bus c

able

Page 16: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

16

GeneralViathestopvalve(8)thefullydemineralizedwater(alsocalledpermeate)isfedfromthereversingosmosissystem(ROsystem)tothepumpstation(1).

Ifthecontrolunit isoperationalandahumidificationrequestispresent,thesupplyvalve(9)andtheflushingvalve(16)opensimultaneouslyandthepumpcircuitisflushed.Afteracertaintimetheflushingvalve(16)closesagain.Ifthesupplypressureiswithintheadmissiblerangethejettingpump(7)startsandbuildsuptherequiredworkingpressure.Thejettingpumpfeedsthewatertothestepvalves(21)viathehigh-pressurepiping(19).One,twoorallthreestepvalvesopen,dependingonthehumidificationrequired(seestepdiagrambelow).

Thedemineralizedwaterthenflowstotherespectivespraynozzles(24)whereitisatomizedintoafineaerosolmistandabsorbedbytheairpassingby.

Adropletseparator(23)(optionorproductofothermanufacturer)downstreammakesurenoaerosolsarecarriedovertotheairpassingby.Wastewaterflowsdownfromthedropletseparatorstotheductdrains(22)andthesiphons.

Ifthereisnohumidificationrequestthepumpautomaticallystopsafterashorttime.

ControlWithstand-alonesystems(masterconfiguration)thecontrolunitisbuiltintothepumpstation.Thecontrolunitfeaturesaseparatepowersupply(380...400V/3N~/50-60Hz),acontrol/humiditysignalinput,connectorsfortheexternalsafetychainandrelayconnectorsfortheremoteoperationandfault indication(option).Inaddition,thecontrolunit incorporatesthefrequencyconverterforthecontrolofthejettingpump.Withcompoundsystems,eachslave isequippedwithaseparatecontrolunit.Eachcontrolunitfeaturesaseparatepowersupply(230V/1N~/50-60Hz),acontrol/humiditysignalinput,connectorsfortheexternalsafetychainandrelayconnectorsfortheremoteoperationandfaultindication(op-tion).Abuscable(29)connectseachslavecontrolunittothecontrolunitofthemastersystemthatcontrolsthejettingpump.

HumidificationThecontrolofthehumidificationsystemisestablishedviaanexternalP/PIcontroller(3a)orthePIDcontrollerbuiltintothecontrolunit(3b).

Asstandardthehumidificationiseffectedwith7-stagesinaccordancewiththefollowingdiagram.Finergradationsarepossible.ContactyourCondairsupplierifnecessary.

000

100

0 1/7

100

00 100

010

2/7

110

3/7

001

4/7

101

5/7

011

6/7

111

7/7

Step1to7

StepvalveY3(1/7)StepvalveY4(2/7)StepvalveY5(4/7)

Demand[%]

Cap

acity

[%]

Page 17: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

17

MonitoringofjettingpumpTheminimumsupplyandworkingpressurevaluesarepermanentlymonitored.Thejettingpumpautomaticallystopsifoneofthesevaluesisoutsidetheadmissiblerange.Arespectiveerrormes-sageappearsinthedisplay,theredlamp“Error”lightsup.

Inaddition to theelectronicmonitoring the jettingpump isequippedwith twomechanicalsafetyvalvesforthesupplyandworkingpressure.Thesevalvesopeniftheadmissiblesupplypressureorworkingpressureareexceeded.

Inaddition,thecontrolunitofthepumpstationandthesalvecontrolunitscanbeequippedwitharemoteoperatingandfaultindicationprint.Thusthefollowingoperatingconditionscanbedisplayedovertheappropriaterelays:“Error”,“Humidification”,“Maintenance”and“Uniton”.

3.5 Scopeofdelivery

Thedeliveryincludes:

– Pumpstationcompletewithcontrolunitandbuilt-inPIDcontrollerandoptionalitemsasorderedaccordingchapter4.3.

– Nozzleunitincludingmountingaccessories

– High-pressurehoses(2m,5mor10m)forhigh-pressurepiping

– 3manti-chafespiralhose

– RJ45Buscable (20mor10m,other lengthsavailableon request), forcompoundsystemsonly

– SpecialcabletostepvalvesY3,Y4andY5

– Installationandoperatinginstructions(thedocumentyouarecurrentlyreading)

– Installationdrawingwithmountingdimensions

– Tubingdiagram

Page 18: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

18

4 Notesonplanning

PriortodesigningandselectingaCondairFF2humidificationsystemthefollowingpreparatorystepsmustbecarriedout:

• Collectingsite-specificdatarequiredforsystemdesign(seechapter4.1)

• Selectingthedesiredoptions(seechapter4.2)

4.1 Recordofsite-specificdata

YourCondairrepresentativeneedsthefollowingdataforpropersystemdesign:

DuctdimensionsWidth(inner) mm _________Height(inner) mm _________Length(inner,min.1300mm) mm _________Wallthicknessofductintheareaofthewatertubingpass-through mm _________

Airvelocityinduct,or m/s _________

airvolumetobehumidifiedperhour m3/h _________

Airpressure(absolute)inhousing-->notmandatorynecessarily Pa _________

StateofsupplyairpriortohumidificationTemperatureT1 °C _________Humidityx1 g/kg/%rh _________

DesiredstateofairafterhumidificationTemperatureT2 °C _________Humidityx2 g/kg/%rh _________

Importantnotes:– IfaparticularsiteistobeequippedwithseveralFF2systemsdeterminetheabovedataforeach

systemseparately.YourCondairrepresentativewillthenevaluatewhethertheparticularsystemsmaybeoperatedinamaster-slavecompoundconfiguration.

– Evaporatingaerosolscoolsdowntheairinsidetheduct(adiabaticcoolingeffect).Toachievethedesiredairtemperaturethesupplyairmustbeheatedpriortohumidification.

Page 19: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

19

4.2 Accessoriesandoptions

Accessories

Accessory DescriptionHigh-pressurehoseforhigh-pressurepiping

High-pressurehosesforestablishingthehigh-pressurepipingbetweenthehigh-pressureconnectorsofthepump..Hosesof2m,5mor10mlengthavailable (from stock)(fromstock)

Anti-chafespiralhose Theanti-chafespiralhoseprotectsthehigh-pressurehosesinlocationswheretheyaresubjecttogetintouchwitheachotherorwithothersystemcomponents..Length: 3 m:3m

RJ45buscable Thebuscableconnectsthecontrolunitsofamaster-slaveconfiguration..Length: 10 m or 20 m:10mor20m

Options

Option FloorstandforpumpstationFloorstandforpumpstation Floorstandmadeofcorrosionresistantsteel,formounting

thepumpstationataconvenientheightforeasyopera-tion.

Dropletseparator Dropletseparator in frameconstructionmadeofcorro-sionresistantsteelequippedwithcollectormesheswithaspecialbiocidecoating.Withunfavourableflowconditionsand/orhighairspeedintheductadditionallyadeflectionsheetisprovidedfortheoptimizationoftheincidentairflowofthefirstdropletseparator.

Remoteoperatingandfaultindication

Printwithrelaycontactsfortheremoteindicationofthefollowingoperatingconditions:Uniton,Humidification,ErrorandMaintenance.

Conductivitymonitoring Theconductivitymonitoring,consistingoftheconduc-tivitysensorandtheconductivityprint,monitorstheelectricalconductivityofthewaterandoutputsanerrormessageifthelowerlimitvalueisexceeded.

FlushingvalveY6 Flushingvalvefortheautomaticflushingofthehighpressurepipingduringoperation.Theflushingvalveisinstalleddirectlytothestepvalveblock.

e-LINKSFF2 GatewaytoconnecttheCondairFF2toabuildingman-agementsystem.Twoversionsareavailable:BACnet/IPorLonWorks

Page 20: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

20

QualificationofpersonnelAllinstallationworkmustbeperformedonlybypersonsfamiliarwiththeCondairFF2AdiabaticHighPressureHumidifierandsufficientlyqualifiedforsuchwork.

Allworkconcerningtheelectricinstallationmustbeperformedonlybyadequatelyqualifiedpersonnel(electricianorworkmanwithequivalenttraining).

SafetyForall installationwork theventilationsystem inwhich theCondairFF2willbeinstalled is toberenderedinoperativeandpreventedfromfurtherinadvertentoperation.

ThepumpstationandpossibleSlavecontrolunitsmaybeconnectedtoelectricmainsonlyafterallinstallationworkhasbeencompleted.

GeneralnotesAllstatementsrelatingtothecorrectpositioningandinstallationoftheparticularcomponentsoftheCondairFF2(seechapter5.2and5.3)mustbefollowedandcompliedwith.

WheninstallingcomponentsoftheCondairFF2usethefixingmaterialssuppliedwiththeunit.Iffixingwiththematerialssuppliedisnotpossibleinyourparticularcase,selectamethodoffixingthatisofsimilarstability.Incaseofdoubt,pleasecontactyourCondairsupplier.

5.2 Mountingofthenozzleunit

5.2.1 Notesonpositioningandmountingofthenozzleunit

Thesystem-specificdimensionsforthepositioningofthenozzleunitintheductaretobefoundintheinstallationdocuments,whichareprovidedwithyoursystem.

In addition to the installation instructionsplease observe the following complementary notesonmounting:

– Caution,fullydemineralizedwaterisaggressive!TheCondairFF2systemusesfullydem-ineralizedwater.Allcomponents(duct/monoblock,mountingaccessories,drainline,etc.)inthehumidifierunitareamustbemadeofstainlesssteel(DIN1.4301/AISI304orbetter)orplasticresistanttofullydemineralizedwater.

– Fortheinstallationandmaintenanceofthehumidifierunittheventilationduct/monoblockmustbeequippedwithaviewingwindowandasufficientlylargemaintenanceaccessdoor.

– Inthehumidifierunitareatheventilationduct/monoblockmustbewaterproof.

– Iftheambientairiscoldtheventilationductmustbeisolatedtopreventthehumidifiedairfromcondensatingatthewalls.

– Important!AtthesiteofinstallationanairfiltermeetingtheF7qualityspecificationsorbettermustbeinstalledbeforethehumidifierunit.

5 Installationworks

5.1 Importantnotesoninstallation

Page 21: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

21

– Thesectionoftheductholdingthehumidifierunitmustbeequippedwithatubhavingtwowaterdrains,onebeforeandoneafterthedropletseparators.Makesurethewaterinthetubhasunhamperedaccesstothedrains.Eachwaterdrainmustbeconnectedtothesewagesystemseparately,viaasiphon.Forhygienicreasonstheseshouldbeopendrainstothesewagelineofthesite.Important:Theeffectiveheightofthesiphondependsontheductpressure.Theproperlayoutofthedrainingsystemisthecustomer’sduty.

– Theminimumdistanceof0,4mbetweenthehumidifierunitandapossibleheatingunitaswellasthemountingdimensionsaccordingtothesystemdiagrammustbecompliedwith.

– Topreventwaterdropsfrombreakingawayatthedropletseparatorstheairflowtothehumidi-fierunitmustbeuniformwithregardtotheentirediameter.Airrectifiersorperforatedplatesmustbeinstalledbeforethehumidifierunit,asrequired.

– Theadmissibleairvelocityintheductbeforethehumidifierunitis0.5...4.0m/s.

– Ifsilencersareinstalledintheairconditioningunit,makesuretheyareinstalledwithaminimumdistanceof3mbeforeoraftertheCondairFF2.

5.2.2 Mountingthenozzleunit

1. Installingtheverticalmountingrails:markthepositionofthefixingstrapsattheductwall,thendrilltheø3.3mmfixingholes.Important!Makesurethatthefixingholesintheleftandrightductwallareexactlyalignedoppositeeachotherandthattheaxesoftheupperandlowerfixingholesareatrightanglestotheceilingoftheduct.Then,fixtheverticalmountingrailstothewalloftheductwiththefixingstrapsandtheself-tap-pingscrewsprovided.

Page 22: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

22

3. Mountingthenozzlepipes:Fixnozzlepipestothepipesupportsusingthefixingstraps,screwsandwashersprovided(positioningof thenozzlepipesaccording to the installationdrawing).Beforetighteningthefixingstraps,makesuretheoutletopeningsof thenozzlesarealignedexactlyhorizontalinflowdirection.

2. Mountingthepipesupports:Fixthepipesupportstotheverticalmountingrailsusingthescrewsandslidingnutsprovided(verticalpositionaccordingtotheinstallationdrawing).Important!Alignoppositepipesupportsexactlyhorizontal.

Page 23: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

23

4. Mountingthecentralsupportrail(onlyforductswithawidtha>2m):Fixcentralsupportrailtothenozzlepipesusingthefixingstraps,screws,washersandslidingnutsprovided.Fixlowerandupperanglebrackettothecentralsupportrailusingthescrews,washersandslidingnutsprovided.Finallyfixtheanglebracketstotheductceilingandtheductbottomusingtheself-tappingscrewsprovided(firstdrilltheø3.3mmholes).

5. Mountingthedistributionblocks(systemswithmorethanthreenozzlepipesonly):Fixdistributionblockstotheverticalmountingrailsusingthescrewsandwashersprovided(position-ingaccordingtotheinstallationdrawing).

Page 24: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

24

6. Mountingthestepvalveblock:Fixthestepvalveblockattheappropriatepositiontotheductusingtheself-tappingscrewsprovided.Then,drillductpassagesø32.5mmandclose theholes insideandoutsidewith the rubbersleevesprovided.

7. Connectingthehigh-pressurehosestothestepvalveblock:Connect thehigh-pressurehosestothestepvalveblock,thenleadthehosesthroughtherubbersleevesintotheductasshownintheillustrationbelow.

Page 25: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

25

8. Connectingthehigh-pressurehosestothespraycircuits:Connectthehigh-pressurehosestotheappropriatedistributionblocksandnozzlepipes(positionofthespraycircuitsaccordingtotheinstallationdrawing).Makesurethehosesarenotkinked(ifnecessary,leadhosesinabowtotheconnector).

1/72/7

4/7

Page 26: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

26

Pleaseobservethefollowingnotesonpositioningandmounting:

– Placethepumpstationinawaythat:

– thedistancetothehumidifierunitisasshortaspossible.Note:High-pressurehosesof2m,5mor10mlengthareavailablefromstock.

– itisfreelyaccessibleandthereisenoughspaceforconvenientoperationandmaintenance(min.freespacearoundpumpstation:laterally0.5m,infront0.6m).

– Thepumpstationisdesignedfortheoperationinprotectedroomsandmustthereforenotbeinstalledoutside.

– Donotinstallthepumpstationinexposedlocationsorlocationswithheavydustload.

– Thepumpstationmustbeinstalledonlyinalocationhavingawaterdrainonthefloor.Ifthisisnotpossible,itismandatorytoprovidewatersensorstosafelyinterruptwatersupplyincaseofleakage.Furthermore,chooseasuitablelocationthatpreventsdamagetomaterialassetsincaseofleakage.

– Thepumpstation isdesignedforinstallationonaload-carryingfloororontheoptionalfloorstand.Thepumpstationor the floorstandmustbe fixedwithscrewsto the floor (protectionagainstshiftingandtilting).Caution!Donotinstallthepumpstationtovibratingcomponents.

5.3 Mountingthepumpstation

5.3.1 Notesonpositioningandmountingthepumpstation

Page 27: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

27

89577

0

904

662

2583

347,5855

181,5

38

602

24837

6538

min. 500min. 500

min

. 800

404

5.3.2 Dimensionandweightsofpumpstation

alldimensionsinmm

Weightofpumpstation: approx.80kgWeightoffloorstand: approx.6kg

Page 28: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

28

5.3.3 Mountingthepumpstation

347,5

855

120

120

347,5

327.5

327.5

120

120

347,5

327.5

327.5

Mountthepumpstationatthedesiredlocationinaccordancewiththefollowingfiguredirectlytothefloor(leftfigure)ormounttheunitontheoptionalfloorstand(rightfigure).

Page 29: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

29

Y3Y5

Y4

Y3Y5

Y4

Y6 **

5.3.4 Waterinstallation

Notesonwaterinstallation– Usehosestoconnectthesupplyflushinglineandthetubdraintoanopendrainfunnel(make

suretoinstallthehosescorrectly).

– TheworkingpressureflushingvalveY6(**)ismounteddirectlytothestepvalveblockoftheMasterunit(stand-alonesystem)orthelastSlaveunit(Compoundsystems).Thedrainhoseoftheflushingvalveistobeconnectedtoanopendrainfunnel(makesuretoinstallthehosecorrectly).

– Useonlytheoptionalhigh-pressurehosestoestablishthehigh-pressurepipingbetweenthehigh-pressureconnectionofthepumpstationandthestepvalveblock(orbetweenstepvalveblocksoftheSlaveunits,respectively).Otherhosesmaygetdamagedinoperationandcausesystembreakdown.

Master

Slave 1...3

M20x1.5

ø19 mm hose connector or G 1/2" inside thread

Page 30: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

30

– Important!Beforeconnecting,allwaterhosesmustbeflushedwithfullydemineralizedwaterforatleast10minutes.Removethesealingcapsfromtheconnectorsjustshortlybeforeinstallingthehoses.

– Installthehigh-pressurehosesinawaythattheydonotgetintouchwitheachotherorothersystemcomponents.Wherethisisnotpossibleforanyreasonprotectthehigh-pressurehosesusingthesuppliedanti-chafespiralhose.Inthelocationsexposedtochafingwraptheanti-chafespiralhosehelicallyaroundthehigh-pressurehoses(s).

Page 31: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

31

5.4 MountingthecontrolunitFF2Slave

1. Unlockandswivelup the transparentcover, thenunlock the twohinges(seedetail “A”)andremovethecover.

2. Undothe6screws,thencarefullyliftthecontrolunitcoveranddisconnectthecablesontheelectronic.

3. Breakoutthe4oblongholesinthebottomoftheunithousingandfixthecontrolunittothewallusing4screws.

4. Connectthevoltagesupply,thecontrolsignal,etc.tothecorrespondingterminalsinthecontrolunitaccordingtheappropriatewiringdiagram(seechapter5.5.2).Important:allcablesmustbeleadintothecontrolunitviathecableglands.

CAUTION!Theelectroniccomponentsinsidethecontrolunitareverysensitivetoelectrostaticdischarge.Whentheunitisopenforinstallationwork,appropriatemeasuresmustbetakentoprotectthesecomponentsagainstdamagecausedbyelectrostaticdischarge(ESDprotection).

Detail“A”

Detail“B”1.

2.

3.

236mm

280mm22

0m

m

306

mm

Page 32: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

32

5.5 Electricalinstallation

5.5.1 WiringdiagramMasterunits(stand-aloneunits)

B1 Pressure transmitter 1...10VB2 Active humidity controller or humidity sensorB3 Minimum pressure switch (supply pressure)B4 Conductivity monitoring print (option)B5 Conductivity sensor (option)B6 Temperature sensor motor coilB7 Ventilator interlockF1 Fuse 6.3A, slow-acting (power supply control unit)F2 Fuse 1A, slow-acting (Relay 230V)F3 Fuse 630mA, quick-acting (step valves)F4 Fuse 200mA, quick-acting (analogue entry)F5 Fuse 200mA, quick-acting (24 VDC supply)F6 External fuse 10A, slow-acting (voltage supply 3x400V)H Remote operating and fault indication (option)J Cable bridge (must be removed, if B7 is connected)JP3 Jumper must be set, if Slave unit is connectedK Main contactor

K1 External safety chain (safety humidistat, flow control, ventilator interlock, etc.)

M Motor high-pressure pumpQ External service switch (min. contact clearance 3

mm) or plug-type connector (installation mandatory)S1 Unit switchU Frequency converter pump motorV Ventilator pump motorX Bus connection Master-Slave systemsY1 Supply valveY2 Flushing valve supply pressureY3 Step valve 1/7Y4 Step valve 2/7Y5 Step valve 4/7Y6 Flushing valve working pressure (option)

NN

UV/FanDrain ValveInlet Valve

EnableFC

Y1

Y2

41

2 5

L1 N L1 N

X1

Y3

Y4

X2

L1 L3 NL2

3 x 400V

L1 L3 PENL2

Q

F6

φ

L1 L2 L3

J

F21AT

F3630mAT

RS485 MasterSlave System

X8 X3

U V W B7 T1T2

T5

T6

31

5 Y5NStage 3Stage 2Stage 1

NPump

NHighP

F16.3AT

200mAF

F4F5 X4

X6

X7X9X10X11

Y6

GND +

OptionConductivity

M3~

B6

B4 V

K

B5

B3

B7

S1

U

X

B1

24V5V

Y- +

X

B2

B4 Drive EnableB2 +24VB5 Run forward

GN

DP

ress

GN

DIn

put+

Inpu

t+

+24V

Res

1R

es2

Lev/

TpP

min

.+2

4V

GN

DO

ut F

C+

X5

Fron

t Pan

el

P N P1

L1 N SC

1S

C2

PT1

PT2

H

Err

or

Ser

vice

Ste

am

Uni

t On

K1

JP3

Page 33: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

33

5.5.2 WiringdiagramSlaveunits

B2 Active humidity controller or humidity sensorB7 Ventilator interlockF1 Fuse 6.3A, slow-acting (power supply control unit)F2 Fuse 1A, slow-acting (Relay 230V)F3 Fuse 630mA, quick-acting (step valves)F4 Fuse 200mA, quick-acting (analogue entry)F5 Fuse 200mA, quick-acting (24 VDC supply)F6 External fuse 10A, slow-acting (voltage supply 3x400V)H Remote operating and fault indication (option)J Cable bridge (must be removed, if B7 is connected)JP3 Jumper must be set on last if Slave unit

K1 External safety chain (safety humidistat, flow control, ventilator interlock, etc.)

Q External service switch (min. contact clearance 3 mm) or plug-type connector (installation mandatory)

S1 Unit switchX Bus connection Master-Slave systemsY3 Step valve 1/7Y4 Step valve 2/7Y5 Step valve 4/7Y6 Flushing valve working pressure (option)

NN

UV/FanDrain ValveInlet Valve

EnableFC

41

2 5

L1 N L1 N

X1

Y3

Y4

X2

J

F21AT

F3630mAT

RS485 MasterSlave System

X8

31

5 Y5NStage 3Stage 2Stage 1

NPump

NHighP

F16.3AT

200mAF

F4F5

X6

X7X9X10X11

Y6

S1

X

24V5V

Y- +

X

B2G

ND

Pre

ss

GN

DIn

put+

Inpu

t+

+24V

Res

1R

es2

Lev/

TpP

min

.+2

4V

GN

DO

ut F

C+

P N P1

L1 N SC

1S

C2

PT1

PT2

HE

rror

Ser

vice

Ste

am

Uni

t On

L1 PEN230 V

Q

F6

B7

K1

from Master

to next Slave

JP3

Page 34: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

34

– Theelectricinstallationmustbecarriedoutaccordingtothewiringdiagramsinchapters5.5.1and5.5.2andtheapplicablelocalregulations.Allinformationgiveninthewiringdiagrammustbefollowedandobserved.

– Allcablesmustbeleadintotheunitviathecableopenings.

– Makesurethecablesdonotscrubonanycomponent.

– Thesupplyvoltagemustcomplywiththevoltageinthecorrespondingwiringdiagram.

TheelectricalinstallationoftheCondairFF2includes:

Installation Master SlavePowersupply Master:380...400V/3N~/50-60Hz Slave:230V/1N~/50-60HzConnectionofpowersupplytoterminalsL1,L2,L3,NandPE(Master)orL1,NandPE(Slave)respectively,accordingtothecorrespondingwiringdiagram.TheserviceswitchQ(disconnectsall3wireswithaminimumcontactclear-anceof3mm)andthefusesF6(max.10A,slow-blow)aremandatory.Cablesectionaccordingtotheapplicablelocalregulations.

CAUTION!Beforeconnectingmakesurethelocalmainsvoltageandfrequencymeetthevaluesstatedontheratingplateofthepumpstation/Slavecontrolunit.

x x

Stepvalves(Y3,Y4andY5)UsethesuppliedcabletoconnectthestepvalvesY3,Y4andY5toterminalsX6accordingthewiringdiagram.Note:Consultthewiringdiagramforthenumberingofwires.Inaddition,thevalvedesignations(Y3...Y5)areimprintedonthecable.Important:exclusivelyusethecableincludedinthedelivery!

x x

Externalcontrollerorhumiditysensor(B1orB2)ConnectexternalcontrollerorhumiditysensortoterminalX2.

Admissiblecontrolsignalsseechapter10.1.Externalsafetychain(K1)Serialconnectionofpotential-freecontactsofexternalmonitoringdevices(safetyhumidistat,flowmonitoringdevice,releaseswitch,etc.)toterminalsSC1andSC2.Important!Ifnomonitoringdevicesareconnectedacablebridge(J)mustbeinstalledtotheterminalsSC1andSC2.

CAUTION!DonotconnectanyexternalvoltagetoterminalsSC1andSC2..

x x

5.5.3 Notesonelectricinstallation

Page 35: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

35

Installation Master SlaveRemoteoperationandfaultindication(option)Fourpotential-freerelaycontactsareavailableforremoteoperationandfaultindication.Thefollowingstatesofoperationcanbecommunicatedremotely:– “Error”: Thisrelayisactivatedincaseofmalfunction.– “Humidification”: Thisrelaycloseswhenhumidificationstarts.– “Maintenance”: Thisrelayisactivatedifoneofthepresetmaintenance

countersexpires.– “Uniton”: Thisrelaycloseswhenthecontrolunitispoweredupvia

themainsswitch.Themaximumcontactloadis:250V/5A.Foractuatingrelaysorsmallcontactorsuseappropriateinterferencesuppres-sors.

x x

FlushingvalveY6workingpressure(option)ConnecttheflushingvalveY6accordingtothewiringdiagramtotheterminalsNandHighPoftheterminalblockX7usingthesuppliedcable.

x x

InterconnectionMaster-SlaveMasterandSlave(s)areinterconnectedaccordingtothewiringdiagramsviatheRJ45cableavailableasaccessories.

InadditiontheJumperJP3mustbesetonthedriverboardoftheMasterandthelastSlave.

x x

Note:ThereareseparatedocumentationsavailableforRS485Modbusande-LINKSFF2.

Page 36: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

36

6 Initialcommissioning

ItismandatorythattheinitialcommissioningiscarriedoutbyanauthorisedservicetechnicianofyourCondairsupplieraccordingtothefollowingchecklist.Thechecklistmustbefilledoutduringthefirstcommissioningandsignedbythecorrespondingservicetechnician.

6.1 ChecklistinitialcommissioningCondairFF2

Agency:_______________________________ Client:_______________________________Location:______________________________ Date:________________________________Pump: ________________________________ Serialnumber:_________________________Nozzletype:____________________________ Humidificationcapacity:__________________Demandsignal:_________________________ Softwareversion:_______________________

1. Visualinspection

Hosesproperlyfixedandanti-chafespiralhosemounted,wherenecessary?

Connectionshigh-pressurepipingpumpstation-stepvalveblock

Hoseconnectionsintheduct

ConnectionY3tospraycircuit1/7

ConnectionY4tospraycircuit2/7

ConnectionY5tospraycircuit4/7

2. Control/Configuration

AretheelectricinstallationsoftheMasterandtheSlaves(ifavailable)correctlydoneinaccordancewiththeappropriatewiringdiagram?Speciallyobserve:– Arethecablesofthestepvalvescorrectlyconnected?– Isthecontrolsignalcorrectlyconnected?– Istheexternalsafetychainconnected(MasterandSlaves)oristhecablebridgeJ

connectedinstead?– Isthepowersupplycorrectlyconnectedandcorrectlyfused?Withcompoundsystems:IstheterminatingresistorJP3setonthedriverboardoftheMasterandthelastSlave.Arethecontrolunits(MasterandSlave)correctlyconfigured(switchoncontrolunitsandcheckconfiguration).Speciallyobserve:– Isthecontrolsignalcorrectlyconfigured(istheinternalcontrollerdeactivated,ifan

externalcontrollerisconnected)?– IsthenumberofSlaveunitscorrectlyconfiguredinthecontrolunitoftheMaster?– Isthepowerlimitcorrectlyconfigured?

Page 37: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

37

3. Pumpstation

Controloftheoillevelinthepump

Flushsupplylineforatleastfor5...10minutes-->thenconnect

Flushhigh-pressurepipingfor5...10minutes

Roomequippedwithfloordrain?

Flushinglineandhousingdrainconnectedandhosessecured?

Flowpressure2...10bar?

Stopvalveopen?

Noleakagesatthepump?

4. Nozzleunit

Nozzlepipestight?

Drainwithinthehumidificationdistancepresentandconnectedviaasiphon?Doestheheightofthesiphoncomplywiththeexpectedductpressure?Sprayangleofthenozzles(min.50°,optimal70°)

Minimumdistancefromthefirstnozzletotheductwallaccurate(nodropformationontheductwall)?Step1/7

Step2/7

Step3/7

Step4/7

Step5/7

Step6/7

Step7/7

5. Dropletseparator

Dropletseparatorcorrectlyinstalled,accordingtotheregulationsofthemanufacturer?

Drainafterthedropletseparatorpresentandconnectedviaasiphon?Doestheheightofthesiphoncomplywiththeexpectedductpressure?Nodropthrowafteratleast1houroffullload(fanandhumidifier)

Remarks: _________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

Date:_________________________________ Signature: _________________________

Page 38: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

38

7 Operation

7.1 Displayandoperatingelements

DisplayandcontrolunitFunction: ConfigurationoftheCondairFF2. Indicationofoperatingparameters. Resetofmaintenancecounter. redLED“Error”Function: TheLED lights in caseof amalfunction of

theunit.Furtheroperationisnotpossibleanylonger.Thetypeofmalfunctionisshowninthedisplay,seechapter9).

TheLEDflashesincaseofatemporarymal-functionoftheunit.Furtheroperationoftheunitisstillpossible.

TheLED flashesalternatelywith thegreenLEDif theexternalsafetychain(ventilationinterlockhastriggered)isopen.Assoonasthesafetychainisclosedagain,theindicationdisappears.

yellowLED“Maintenance”Function: TheLEDlightsifthemaintenanceisdue.

greenLED“Humidification”Function: TheLEDlightsiftheunithumidifies. TheLEDflashesalternatelywiththered

LEDiftheexternalsafetychain(e.g.ven-tilationinterlockhastriggered)isopen.Assoonasthesafetychainisclosedagain,theindicationdisappears.

FlushkeyFunction: Manualflushingofthesupplyline.After

havingpressedtheflushkey,theflushingiscontrolledviathedisplayandcontrolunit.

UnitswitchFunction: Switchestheunitonandoff.Theswitchis

illuminatedwhentheunitisswitchedon.

Page 39: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

39

Important!Theproceduredescribedhereafterassumesthatthesystemhasbeeninstalledcorrectlyandinitialcommissioninghasbeencarriedoutdulybyaservicetechnicianofthemanufacturer/distributor.

ProceedasfollowstosettheCondairFF2intooperation:

1. Checkallsystemcomponentsandinstallationsforpossibledamage.

WARNING!

Adamagedsystemorasystemwithdamagedinstallationsmustnotbesetintooperation.

2. Openthestopvalveofthewatersupplyline.

3. Activatetheserviceswitchofthepowersupplylinetothepumpstation,andifpresenttotheSlavecontrolunits.

4. Actuatethepowerswitchofthepumpstation,andifpresentoftheSlavecontrolunits.

Thecontrolcarriesoutasystemtestandthesupplylineisflushed.DuringthetestallthreeLED’slightuptemporarilyandthedisplayshowstheoppositemessage.

7.2 Settingtheunitintooperation

Ifafailureoccursduringthesystemtest,acorrespondingerrormessageisshowninthedisplay.

After the system test the unit is in normal operation mode.The dis-playshowsthestandardoperatingdisplay(firstpageoftheindicationlevel).Note:ThecontentsofthestandardoperatingdisplaydependsontheactualoperatingstatusandontheconfigurationoftheCondairFF2andcandifferfromtheoppositedisplay.

Assoonasahumiditydemandispresent,thesupplyvalveopensandthepumpstarts.Assoonasthenecessaryworkingpressureisreached,onetwoorallthreestepvalvesopendependingonthecurrentdemandandtheCondairFF2humidifies.Note:Ifahumiditydemandispresentbutsincethelast flushingof thesupplylinemorethan1hourhaspassed,thesupplylineisflushedfirstandthenthepumpisstarted.

Note:fordetailedinformationregardingtheoperationofthecontrolunitandthesettingspleaseobservetheinformationgivenintheseparateoperatinginstructionstothecontrolunitFF2.

STARTUP: FF2

INIT MODUL

StandbyFF2

05.01.2009 12.00.00Menu Set

Demand :100%FF2

05.01.2009 12.00.00Menu Set

Page 40: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

40

7.3 Inspectionsduringoperation

DuringoperationtheCondairFF2andthehumidificationsystemhavetobeinspectedweekly.Onthisoccasioncheckthefollowing:

• thewholehumidificationsystemforanyleakage.

• thenozzleunitandtheothersystemcomponentsforcorrectfixingandanydamage.

• theelectricinstallationforanydamage.

• theoperatingdisplayforanywarningorerrormessage

Iftheinspectionrevealsanyirregularities(e.g.leakage,errorindication)oranydamagedcomponentstaketheCondairFF2outofoperationasdescribedinchapter7.4.Then,letthedamageormalfunc-tionberesolvedbyaqualifiedspecialistoraservicetechnicianofyourCondairsupplier.

7.4 Settingtheunitoutofservice

Important!ForhygienicreasonswestronglyrecommendtoleavetheCondairFF2onallthetime,eveninperiodswhennohumidificationisrequired.Thiswaythewatercircuitisflushedonaregularschedulethuspreventingtheformationofunwantedmicroorganisms.

ProceedafollowstoputtheCondairFF2outofservice,e.g.formaintenancework:

1. Switchoffthepumpstationand/orallSlavecontrolunits(ifpresent).

2. Shutoffthelinesupplyingdemineralizedwaterfromthereversingosmosissystemanddraintheline,asrequired.

3. Closethestopvalveofthesupplylineandsecureittopreventinadvertentopening.

4. Switchonthepumpstationagainandwaituntilautomaticpressurereliefhastakenplace(approx.1minute),thenswitchthepumpstationoffagain.

5. TurnofftheserviceswitchinthemainssupplylinestothepumpstationandtotheSlavecontrolunits(ifpresent),thensecuretheserviceswitchesagainstinadvertentswitchingon.

6. Hygiene!Letthefanoftheventilationsystemrununtilthehumidifierunitisdry.

7. Incaseyouneedtocarryoutmaintenancework,switchtheventilationunitoffandsecureittopreventinadvertentpowerup(seeinstructionmanualoftheventilationsystem).

Page 41: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

41

8 Maintenanceandreplacementofcomponents

QualificationofpersonnelAllmaintenanceworkmustbecarriedoutonlybywellqualifiedandtrainedpersonnelauthorisedbytheowner.MaintenanceandrepairoftheelectricalinstallationoftheCondairFF2mustbecarriedoutonlybyqualifiedpersonnel(e.g.electrician)beingawareofpossibledangerandimplications.

Itistheowner’sresponsibilitytoverifyproperqualificationofthepersonnel.

GeneralnoteTheinstructionsanddetailsformaintenanceworkmustbefollowedandupheld.

Onlythemaintenanceworkdescribedinthisdocumentationmaybecarriedout.

OnlyuseoriginalCondairsparepartstoreplacefaultyparts.

SafetyBeforemaintenanceisinitiated,theCondairFF2mustbetakenoutofoperationinaccord-ancewithinstructionsinchapter7.4andprotectedagainstunintentionalswitchingon.Beforeservicingthehumidificationunit, theventilationsystemmustbesetoutofoperation(consult thedocumentationoftheventilationsystem).

TheCondairFF2mustbecleanedintherequiredintervalsandthecleaningworkhastobecarriedoutcorrectly.

WARNING!Poorlymaintainedhumidificationsystemsmayendangerhealth.Thereforeitismandatorytoobservethespecifiedmaintenanceintervalsandtocarryoutmaintenanceworkinstrictaccordancewiththeinstructions.

8.1 Importantnotesonmaintenance

Page 42: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

42

8.2 Maintenanceintervals

Toensuresafe,hygienicandeconomicoperationoftheCondairFF2itscomponentsmustbeperiodi-callymaintained.ForthatpurposetheCondairFF2hasafixedadjustedmaintenancecounter.

W20 Oil changeWARNING

Demand :100%Menu INFO

As soon as the set maintenance interval time has expired, the oppositemaintenancemessageindicatesthatamaintenanceortheoilchangeofthehigh-pressurepumpisdue.Alistoftheworkwhichhastobecarriedoutcanbefoundinchapter8.3.

8.3 Maintenancework

Important:theintervaltimeforthefirstmaintenanceisfixsetto50hoursaftertheinitialcommis-sioning!Afterwards,themaintenanceintervaltimechangesautomaticallyto2000hours.

Systemcomponent WorktobecarriedoutPumpstation Checkwaterfilterandclean,asrequired.

Removeoilfrompumpreplacewithnewoil(oilquality:HD-SAE30motoroilor15W40multigradeoil) (see chapter 8.6).(seechapter8.6)..Iftheoilintheinspectionglassismilkywhite(oilcontainswater)thepistonpackingsmustbereplaced(seechapter8.5.2).8.5.2)..Check jettingpumpand installations for leakage.HavedefectivecomponentsrepairedorreplacedbyaCondairservicetechnicianCheckelectricalconnectionsandwires.Havedefectivecomponentsrepairedorreplacedbyaqualifiedtechnician.

Nozzleunit Checkscrewingofbaseframeforproperfastening.In humidification mode set the nominal humidity value to 100 %andcheckthesprayingangleofthespraynozzles(sprayingcone:optimum70°,50°stilladmissible).Ifthecheckissuccessfulsetthenominalhumiditybacktothecorrectvalue.Removespraynozzles (seechapter8.5.1)andclean them inanultrasonicbath,asrequired.Replacedefectivenozzles.Checkhoses,tubingandconnectionsforpossibleleakage.Fastenscrewingorreplacedefectivecomponents,asrequired.Checknozzlesforproperfastening.Moderatelytighten(torque:ap-prox.4Nm)nozzleswith13mmopen-endwrench,asrequired.

Page 43: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

43

Systemcomponent WorktobecarriedoutHumidifierhousing/watertub

Checkwatertub(behindthedropletseparators)fordepositsorac-cumulationofwater.Ifcheckrevealsaconsiderableamountofaccumulatedwater,checkwaterdrainanddropletseparators.Note:Waterdropsandsmallaccumulationsofwaterinthetubbehindthedropletseparatorsarebasicallyinherenttothesystem.Cleanthewatertubandthewetareaofthehumidifierhousing(alsobehindthedropletseparators)withacombinedcleaning/disinfec-tionagent.Thenrinseallcomponentswithhygienicallycleanwater fromthereversingosmosissystemandrubdry.

Dropletseparator Seeseparatedocumentationofthedropletseparator.Checklist“Maintenance” Afterhavingcarriedoutallmaintenancework,fillinthe“Maintenance

checklist”.

Aftercompletingmaintenancework,themaintenanceindication(yellowLEDlights)mustbereset.Note:Ifthemaintenanceindicationisnotresetwithin168hoursanerrormessageistriggered.

Selectthemaintenancemenu:Path:Main menu > User > Password entry: 8808 > Maintenance

Select“Pumpstation”inthemaintenancemenu,thenpressthe<Set>key.

Select“OilChange”,thenpressthe<Set>key.

Theresetdialogueshowsupinthedisplay.Pressthe<Yes>keytoresetthemaintenancecounterandthemaintenancemessage.Note:Pressthe<No>keyifyouwishtoaborttheresetprocedure.

To return to the standard operating display press the <Esc> key severaltimes.

WartungPump station:Set

Esc Set

are you sure? Oil Change

No Yes

Pump stationOil Change :Set

Esc Set

8.4 Resettingthemaintenanceindication

Page 44: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

44

8.5 Removalofcomponents

8.5.1 Removalandinstallationofspraynozzles

1. Putthesystemoutofserviceaccordingtochapter7.4andsecureittopreventinadvertentstart-up.

2. Usea13mmopen-endwrenchtoremovethespraynozzle.

3. CheckO-ring,replaceifnecessary.

4. Screwinneworcleanedspraynozzleandmoderatelytighten(torque:4Nm)withopen-endwrench.

8.5.2 Replacementofpistonpackings

Theinstructionsforthereplacementofthepistonpackings,isprovidedwiththesparepartsetoftheappropriatepump.

Page 45: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

45

8.6 Changingtheoilofthepistonpump

WARNING!Strictlyfollowalllocalregulationsonenvironmentalprotectionwhenchangingtheoil.Bringtheoldoiltowasteoilcollectingpoint.Innocasedisposeofoilintotheenvironment!

1. Putthesystemoutofserviceaccordingtochapter7.4andsecureittopreventinadvertentstart-up.

2. Openthewasteoilscrew(dependingonthemodelthescrewisonthebottomoronthesideofthepump)usingaopen-endwrenchandlettheoildrainintotheexistingoiltub.Note: If theoil ismilkywhite (oilcontainswater) thepistonpackingsmustbereplaced(seechapter7.5.2).

3. Installthewasteoilscrewandfastenitwiththeopen-endwrench.

4. Carefullyremovetheoiltub,thenemptythetubintoalockablewasteoilcontainer.Correctlydisposeofthewasteoilaccordingtheapplicablelocalregulation.

5. Cleanoiltubandrelocateitunderthepumpagain.

6. Removetheyellow-blackoilfillercapandtopupHD-SAE30motoroilor15W40multigradeoil(approx.0.4l...1.0ldependingonthemodel)untilthelevelisjustinthemiddleoftheinspectionglass(locatedabovethewasteoilscrew).

7. Relocatetheoilfillercap.

Page 46: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

46

9 Troubleshooting

Malfunctionsduringoperationareindicatedbyacorrespondingwarningmessage(operationstillpossible,redLEDflashes)orerrormessage(operationnotpossibleanylonger,redLEDlights)inthedisplayofthepumpstationortheSlavecontrolunit.DetailedinformationtheretocanbefoundintheseparateoperatinginstructionsforFF2controlunit.

9.3 Resettingtheerrorindication

Toresettheerrorindication:

Disconnectthepumpstation/Slavecontrolunitfromthemainsforapprox.5seconds,thenreconnectagain.

Note:Ifthefaulthasnotbeeneliminated,theerrorindicationreappearsafterashortwhile.

9.2 Malfunctionwitherrorindication

9.1 Importantnotesontroubleshooting

QualificationofpersonnelHavefaultseliminatedbyadequatelyqualifiedandtrainedpersonnelonly.Malfunctionscausedbytheelectricalinstallationmustberepairedbyauthorizedpersonnel(e.g.electrician)only.RepairworkonthehighpressurepumpmayonlybecarriedoutbyyourCondairrepresenta-tive’sservicetechnician.

SafetyWheneliminatingfaults,theCondairFF2mustbetakenoutofoperation,asdescribedinchapter7.4,andpreventedfromfurtherinadvertentoperation.Makesurethepowersupplytothepumpstation/Slavecontrolunitsiscutoff(testwithvolt-agetester)andthatthestopvalveinthewatersupplylineisclosed.

Page 47: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

47

Thefollowingtableprovideserrorsthatdonotissuemessages,notesonthecauseofmalfunctionandinformationonhowtoeliminatethesourceoftrouble.

Error Cause RemedyWaterdepositsintheductsec-tionoutsideofthewatertub

Dropletseparatordefective. Check/Replacedropletsepa-rator

Excessairvelocity(>4m/s) induct.

Reduce air velocity in duct(<4m/s).

Faultylocationofspraynoz-zlesorsprayingcircuitsnotconnectedtoappropriatenozzles.

Checklocationofnozzlesandpiping of spraying circuits ac-cordingtothenozzlediagram.

CondairFF2humidifiesper-manently.

Nominalhumidityvaluetoohigh.

Reduce nominal humidity val-ue.

Ambienthumidityverylow. Nomeasurestobetaken,justwait.

Theinternalcontrollerisactivated,althoughanexternalcontrollerisconnected

Deactivateinternalcontroller.

Maximumhumidificationcapacitynotreached.

Wrongsystemdesign(capacitytoolow).

ContactyourCondairsupplier.

Stepvalve(s)Y3,Y4orY5de-fective.

Checkthefunctionofthestepvalvesbyincreasingthenominalhumidityvalue.Important! Reset the nominalhumidity to the correct valueafterchecking.

Spraynozzlesclogged. Remove nozzles (see chap-ter8.5.1)andcleanorreplacethem

Hosestonozzlepipesareleak-ingordisconnected,ornozzlepipesareleaking.

Checkhoses/nozzlepipesandseal,asrequired

Controlunitisswitchedonbutthedisplayofthecontrolunitdoesnotshowanything.

Serviceswitchinpowersupplylineisoff.

SetserviceswitchinpowersupplylinetoOnposition.

FusesF6of thepowersupplylineblown

HaveanelectricianreplacefusesF6ofthepowersupplyline.

FuseF1ofcontrolunitblown HaveanelectricianreplacefuseF1ofthecontrolunit(seechapter9.5).

Displayorcontrolboarddefec-tive

HaveaCondairservicetechni-cianreplacethedisplayorthecontrolboard.

9.4 Malfunctionwithouterrorindication

Page 48: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

48

Error Cause RemedyExcessivefluctuationsofhumiditycontrol.

Faulty electrical connection ofsprayvalvesY3,Y4andY5orsprayingcircuitsnotconnectedtoappropriatenozzles.

Have an electrician connectspray valves Y3, Y4 and Y5correctly(seewiringdiagram).Checkpipingofsprayingcircuitsandrectify,asrequired

Duringahumidificationcyclewaterisflowingviathedrainlineintothefunnelalthoughthereisnoflushing.

FlushingvalveY2(supplyline)soiledordefective.

Haveanexpertcheck/cleanorreplaceflushingvalveY2.

Safetyvalve(supplypressureorworkingpressure)wronglyset,soiledordefective.

Haveanexpertcorrectlysetup,cleanorreplacethesafetyvalves(supplypres-sure:8bar,workingpres-sure:100bar).

Page 49: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

49

9.5 Replacingthefuseofthecontrolunit

DANGER!Dangerofelectricshock!Onemaygetintouchwithlivepartswhenthepumpstation/controlunitisopen.Touchinglivepartsmaycausesevereinjuryordangertolife.

Therefore,beforeopeningthepumpstation/controlunit:switchoffthepumpstation/controlunit,disconnectitfromthemainsandprotectitagainstinadvertentswitchingon.

CAUTION!Theelectroniccomponentsinsidethecontrolunitareverysensitivetoelectrostaticdischarge.Whencarryingoutworkontheopenunit,appropriatemeasuresmustbetakentoprotectthesecomponentsagainstdamagecausedbyelectrostaticdischarge(ESDprotection).

Replacementofthecontrolunitfusesmustbecarriedoutbyqualifiedandauthorisedpersonnelonly(e.g.electrician).

Master Slave

Locationofthefuses/Notesonreplacingthefuses

Designation Type RemarksF1 6.3A,slow-acting VoltagesupplycontrolunitF2 1A,slow-acting Relay230VF3 630mA,slow-acting StepvalvesF4 200mA,quick-acting AnalogueinputF5 200mA,quick-acting 24VDCvoltagesupply

F3

F2

F1

F5F4

F3

F2

F1

F4

F5

Page 50: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

50

10 Productdata10.1 Technicalspecifications/ambientconditions

Humidifierunitbuilt-inlength min1.3m

Specificationoffilterbeforehumidifier min.F7

Max.supplyairtemperaturebeforehumidifier 50°C

Airvelocity,rangeofuse 0.5...4.0m/s

Lossofpressurewithregardtocross-sectionofduct approx.75PaatwL2.3m/s

Nozzlecapacities(at80barspraypressure) 5kg/h

Effectivehumidificationdistance 0.8...1.3m

Humidificationcapacity 35....1080kg/h

Pumpstation(controlandjettingpump)Dimensionsofpumpstation(HeightxWidthxDepth) 904x662x404mm

Weightofpumpstation max.80kg

Jettingpumpsupplyvoltage 380...400V/3N~/50...60Hz

Activeoutputofjettingpumpmotor 1.5kW / 4.0kW

Currentconsumptionofjettingpumpmotor 1.7...4.3A / 4.4...6.9A

Powerconsumptionofcontrol 60VA

Workingpressureofjettingpump(Standard) 80bar

Oilcapacityofjettingpump(capacitydependingonpumpsize)

approx.0.4l...1.0l

Admissiblesupplywatertemperaturebeforejettingpump 5...35°C

Admissiblewaterpressure(yieldpressure)beforejettingpump 2...10bar

AdmissibleconductivityofwatersuppliedbyROsystem 3...15µS/cmnoadditives,max.100KBE/ml

Controlsignals 0...10VDC,2...10VDC0...5VDC,1...5VDC,0...16VDC,3,2...16VDC,0...20mA,4...20mA

Controlaccuracy upto±4%rh

Watersupplyconnection 19mmhoseconnectororG1/2"insidethread

Flushinglineconnection 19mmhoseconnectororG1/2"insidethread

Tubdrainconnection 19mmhoseconnectororG1/2"insidethread

Connectorhigh-pressurehose M20x1.5(outsidethread)

Admissibleambienttemperature 5...35°C

Admissibleambienthumidity max. 75 %rh, non-condensing

Testcertificates CEapprovalmark

Protectionclassofjettingpump/control IP31

Page 51: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

51

10.2 Declarationofconformity

Wedeclareunderoursoleresponsibilitythatthepumpstationusedintheadiabatichigh-pressurehumidifierCondairFF2complywiththefollowingstandards:

– EN292-1

– EN292-2

– EN50081-1(1992)

– EN50082-2(1995)

– EN61000-4-2(1995)

– EN61000-4-3(1996)

– EN61000-4-4(1995)

– EN61000-4-5(1995)

– EN61000-4-6(1996)

– EN61000-4-8(1993)

– EN61000-4-11(1994)

WalterMeier(KlimaInternational)AGPfäffikon,january5,2009

Page 52: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

52

10 Appendix10.1 Diagramh,x

Page 53: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

53

11.2 Commissioaningprotocol(copytemplate)

Cond

air F

F2

Main

tena

nce r

ecor

d

Unit

type

Seria

l num

ber

Com

miss

ioni

ngSo

ftwar

e ver

sion

Loca

tion

Resp

onsib

leIn

tern

al no

.

Date

Tim

ePe

rmea

t con

duc-

tanc

e�if

poss

ible�

�if p

ossib

le�[µ

S/cm

]

Load

pre

ssur

e be

fore

pum

p [b

ar]

Load

pre

ssur

e af

ter p

ump

[bar

]

Wor

king

hour

s

[h]

Rem

arks

rega

rdin

g th

e main

tena

nce

Signature

Seite

Page 54: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

Notes

Page 55: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

© Walter Meier (climate International) ltd. 2009, printed in switzerlandtechnical modifications reserved

Page 56: condair FF2 · PDF file1.2 Notes on the installation and ... – if components of the Condair FF2 are damaged, worn or badly soiled. ... For the replacement of defective components

reg.no. 40002-2

Manufacturer:Walter Meier (climate International) ltd.talstr. 35-37, p.o. Box, cH-8808 pfäffikon (switzerland)phone +41 55 416 61 11, Fax +41 55 416 62 62www.waltermeier.com, [email protected]

solutions for Indoor climate