Concealed DuctedSplit SeriesR-407C 24-60 MBH
Ducted Split with Hermetic Compressor Tropical 50 Hz
For more technical information please visit www.coolex.com.kw
-
www.coolex.com.kw1
Table of Contents
INTRODUCTION 2
NOMENCLATURE 2
UNIT RATING SUMMARY 3
OUT STANDING FEATURES 3
STANDARD SPECIFICATIONS 5
OPTIONAL SPECIFICATIONS 6
SELECTION PROCEDURE 7
GENERAL DATA 8
PERFORMANCE DATA TABLES 9
UNIT ELECTRICAL DATA 11
SUPPLY AIR PERFORMANCE 12
UNIT DIMENSIONS 13
WIRING DIAGRAMS 15
NOTES 17
CONTACT DETAILS 17
1. Air Cooled Screw Water Chillers
2. Commercial Packaged Units
3. Residential Packaged Units
4. Air Handling Units
5. Ducted Split Units
6. Fan Coil Units
OTHER COOLEX PRODUCTS
-
www.coolex.com.kw2
NOMENCLATURE
Unit Series Description CHCc- Concealed High Efficiency Condenser, R-407C refrigerantCHEc- Concealed High Efficiency Evaporator, R-407C refrigerant
CODE
2
7
DESCRIPTION
415V / 3 ph / 50hz
240V / 1 ph / 50hz
Cooling Capacity Nominal MBH 24 - 30 36 - 42 48 - 60
INTRODUCTION
COOLEX High Efficiency Concealed Ducted Split Units are designed specifically for tropical opera-tion with high performance, low power consump-tion, easy installation and low noise operations.
COOLEX Concealed Ducted Split Units can be used for cooling or heating with optional duct electric heater.
CHCc 036 A 2
Electrical Specifications
CODE
A
B
C
DESCRIPTION
First Series
Second Series
Third Series
-
www.coolex.com.kw3
Rating Conditions: Indoor Temperature DB = 800 F (26.70 C). WB 670 F (19.40 C).
UNIT RATING SUMMARY
OUT STANDING FEATURES
Indoor Unit Compact design Low profile Low sound power level For ducted application 3 speed motors Easy maintenance Easy installation External terminal box
OUT STANDING FEATURES OUT STANDING FEATURES OUT STANDING FEATURES OUT STANDING FEATURES
Unit Model
CHCc/CHEc -024A7
CHCc/CHEc -030A7
CHCc/CHEc -036A2
CHCc/CHEc -042A2
CHCc/CHEc -048A2
CHCc/CHEc -060A2
AirFlow
(CFM)
Cooling Capacity
(Btu/h)
Total Power (kW) kW/Ton EER
Cooling Capacity
(Btu/h)
Ambient temp 95°F Ambient temp 115°F Ambient temp 118.4°F
Total Power (kW) kW/Ton EER
Cooling Capacity
(Btu/h)
Total Power (kW) kW/Ton EER
900
1000
1200
1400
1600
2000
23,538
30,486
38,908
42,995
49,940
58,411
2.35
2.856
3.57
3.98
4.90
5.51
1.20
1.12
1.10
1.11
1.18
1.13
10.0
10.7
10.9
10.8
10.2
10.6
21,613
27,690
35,100
40,219
47,093
52,845
2.77
3.46
4.10
4.72
5.74
6.56
1.54
1.50
1.40
1.41
1.46
1.49
7.7
8.0
8.6
8.5
8.2
8.1
21,138
27,069
34,552
39,680
45,298
52,665
2.9
3.5
4.3
4.9
5.8
6.7
1.66
1.57
1.50
1.49
1.55
1.54
7.2
7.7
8.0
8.1
7.8
7.8
Outdoor Unit:High efficiency tropical designGalvanized heavy gauge panels, oven baked powder coatedDesigned to operate at severe ambient temperature up to 52°C without tripping24v controlCoil guard protectionExternal service valve with gauge ports
-
www.coolex.com.kw4
OUT STANDING FEATURES
Options & Accessories• Wired Microprocessor controller • Wired digital thermostat• Wireless remote controller• 240Volt controls• Cleanable air filter
Bottom access panel
Bottom sliding coil and drain pan Bottom sliding fan deck
-
www.coolex.com.kw5
GeneralThe side discharge condensing units are provided with the latest advanced technology to provide quiet, reliable performance. The wrap around coil adds aesthetical appeal and gives optimum heat transfer efficiency. The access panels provide access to the compressor and to the control box. Removal of top panel gives access to fan motor and coil.
Unit ConstructionThe indoor unit consists of a coil, motor/blower assembly and a drain pan securely mounted on heavy gauge galvanized steel housing.
Condenser CoilsThe coils are built up of ripple finned seamless copper tubes and mechanically bonded to scientifically designed louvered fins. The assembled coils are factory leak tested under water at a pressure of 450 [psig] for quality and leak free unit.
Condenser FansAxial type condenser fan are used which precisely match with extra strong fan motor to ensure efficient hot air dissipation.
Unit CasingThe casing sheet metal is fabricated from hot dipped G90, Zinc coating and zero spangle galvanized steel, oven-baked powder coated.
Evaporator CoilsThe coils are built up of ripple finned seamless copper tubes and mechani-cally bonded to scientifically designed louvered fins. The assembled coils are factory leak tested under water at a pressure of 350 psig for quality and leak free units.
Evaporator Blower Motor The evaporator blower motor is directly drives the evaporator blower conforming to BS/IES standards it is open drip proof type electric motors with built-in thermal protector and perma-nently lubricated ball bearings class B insulation.
Condenser Fan Motor The condenser fan motors are a 4/6 poles electric mo-tor which directly drive the condenser fans confirming to BS/IES standards. They are totally enclosed air over type electric motors with built-in thermal protector class F insulation. Drain Pan
The drain pan is fabricated from galvanized steel. The drain pan is powder coat painted and the outer surface is thermally insulated.
CompressorThe compressors are hermetically sealed type. The compressors are equipped with internal motor pro-tector and necessary accessories for safe operation.
Blower AssemblyThe units are provided with centrifugal fans which are statically and dynamically balanced, designed for low sound level operation
STANDARD SPECIFICATIONS (OUTDOOR UNIT) & (INDOOR UNIT)
-
www.coolex.com.kw6
Display:
a) Room temperature/set temperature display in °C or °F
b) Mode of operation (Cool/Heat/Dry/Fan system control)
c) Error Codes
Duct Electric HeaterA protection box with duct electric heater and safety control can also be provided. Maximum kW Ratings is as shown
OPTIONAL SPECIFICATIONS
MICROPROCESSOR BASED CONTROLLER
CHEc-042 A7
CHEc-048 A7
CHEc-060 A7
4
4
5
CHEc-024 A7
CHEc-030 A7
CHEc-036 A7
2
3
3
Model kW Model kW
-
www.coolex.com.kw7
The below example illustrates the selection procedure to assist using this catalog toselect the appropriate CHEc/CHCc unit that meets the design requirements.
SELECTION PROCEDURE
Sea level
1000
2000
3000
4000
5000
6000
7000
Altitude[ft]
Correctionfactor
1
0.996
0.990
0.984
0.980
0.974
0.965
0.960
Example :
Design requirements
• Total cooling capacity 33,000 [Btu/hr]
• Sensible cooling capacity 21,000 [Btu/hr]
• Design ambient temperature 115 [°F]
• Evaporator air flow 1100 [CFM]
• Evaporator entering temperature DB/WB 80/67 [°F/°F]
• External static pressure 0.2 [in.wg]
• Altitude 2000 [ft]
• Power supply 415V / 3Ph / 50Hz
*Using the correction factor table at the specified altitude, thereby the required capacity will be:
Corrected capacity = Required capacity /corr. factor
Corrected total capacity = 33,000 [Btu/hr]/0.99 = 33,330 [Btu/hr]
Corrected sensible capacity = 21,000 [Btu/hr]/0.99 = 21,210 [Btu/hr]
From the cooling capacity at performance data tables (page 9), the closest selection model to the required Capacity is CHEc/CHCc 036:
Total capacity = 34,117 [Btu/hr]
Sensible capacity = 22,117 [Btu/hr]
-
www.coolex.com.kw8
GENERAL DATA
Outdoor Units
Compressor
Condenser Fan
Condenser Coil
Weight
Type
Quantity
Refrigerant
Type
Quantity
Airflow, m³/h
(CFM)
Drive
Type
Row Deep
FPI
Total Area, Sq.m
(Sq.Ft)
kg
CHCc 24
1
1
3300
1940
2
16
0.44
4.7
55
CHCc 60
1
2
9000
5300
2
16
0.95
10.2
95
Hermetically Sealed
CHCc 42
1
1
5000
2940
2
16
0.83
8.9
71
CHCc 48
1
2
9000
5300
2
16
0.95
10.2
92
CHCc 36
1
1
4500
2650
2
16
0.63
6.8
64
CHCc 30
1
1
3600
2120
2
16
0.56
6.0
61
Direct
Enhanced Fins and Tubes
Indoor Units
Evaporator Blower
Evaporator Coil
Weight
Type
Airflow, m³/h
(CFM)
Drive
Type
Row Deep
FPI
Total Area, Sq.m
(Sq.Ft)
kg
CHEc 024
1,530
900
2
14
0.23
2.5
38
CHEc 060
3,400
2000
3
11
0.42
4.5
61
CHEc 042
2,380
1400
3
11
0.32
3.4
54
CHEc 048
2,720
1600
2
14
0.42
4.5
58
CHEc 036
2,040
1200
2
14
0.32
3.4
52
CHEc 030
1,700
1000
3
11
0.23
2.5
39
Expansion Devices
Centrifugal Forward Curve DWDI
Direct
Enhanced Fins and Tubes
Capillary
R 407c
Propeller
-
www.coolex.com.kw9
PERFORMANCE DATA TABLESPERFORMANCE DATA TABLESPERFORMANCE DATA TABLESPERFORMANCE DATA TABLESPERFORMANCE DATA TABLES
CHCc-030A7
CHEc-030A7
30,340
27,985
25,622
23,433
31,861
29,387
26,906
24,607
33,051
30,486
27,911
25,526
86
80
74
68
86
80
74
68
86
80
74
68
72
67
62
57
72
67
62
57
72
67
62
57
18,644
18,133
17,347
16,644
19,852
19,308
18,471
17,722
21,186
20,606
19,713
18,914
2.82
2.78
2.75
2.72
2.87
2.84
2.81
2.77
2.91
2.88
2.85
2.82
27,575
25,420
23,254
21,248
28,957
26,695
24,419
22,313
30,038
27,690
25,331
23,147
17,867
17,351
16,541
15,747
19,024
18,475
17,612
16,768
20,303
19,717
18,797
17,895
3.40
3.36
3.32
3.30
3.46
3.42
3.39
3.36
3.52
3.47
3.43
3.41
27,101
24,850
22,837
20,913
28,459
26,095
23,982
21,961
29,522
27,069
24,877
22,781
3.50
3.45
3.41
3.38
3.56
3.52
3.49
3.44
3.61
3.57
3.54
3.50
800
900
1000
17,755
17,186
16,390
15,736
18,904
18,300
17,452
16,755
20,176
19,530
18,625
17,882
CHCc-024A7
CHEc-024A7
Model
24,007
22,479
20,602
18,863
24,510
22,950
21,034
19,258
25,138
23,538
21,573
19,751
86
80
74
68
86
80
74
68
86
80
74
68
72
67
62
57
72
67
62
57
72
67
62
57
15,265
14,665
14,200
13,619
15,726
15,107
14,628
14,030
16,449
15,809
15,301
14,676
2.28
2.26
2.23
2.20
2.35
2.33
2.28
2.25
2.46
2.36
2.31
2.28
22,364
20,640
18,909
17,299
22,833
21,072
19,305
17,661
23,418
21,613
19,799
18,113
15,046
14,400
13,979
13,341
15,500
14,835
14,401
13,743
16,214
15,514
15,064
14,376
2.71
2.69
2.64
2.61
2.78
2.75
2.70
2.67
2.81
2.78
2.73
2.70
21,961
20,434
18,566
16,977
22,150
20,609
18,726
17,123
22,717
21,138
19,206
17,563
2.86
2.85
2.79
2.75
2.93
2.92
2.86
2.82
2.96
2.95
2.88
2.85
725
750
900
14,819
14,173
13,749
13,111
15,267
14,601
14,163
13,507
15,969
15,268
14,815
14,128
Evaporator
CFM
Temp ° F 95 °F 115 °F 118.4 °F
Condenser Ambient Temperature
DB WBCapacity Btu/Hr kw
InputTotal Sen.kw
InputTotal Sen.kw
InputTotal Sen.Capacity Btu/Hr Capacity Btu/Hr
Air Flow
CHCc-036A2
CHEc-036A7
38,493
36,106
33,464
30,352
40,318
37,818
35,051
31,791
41,479
38,908
36,061
32,707
86
80
74
68
86
80
74
68
86
80
74
68
72
67
62
57
72
67
62
57
72
67
62
57
22,585
22,288
21,451
19,790
23,971
23,656
22,768
21,005
25,206
24,874
23,941
22,088
3.48
3.46
3.36
3.30
3.55
3.53
3.43
3.38
3.59
3.57
3.47
3.41
34,800
32,573
30,025
26,415
36,450
34,117
31,450
27,668
37,500
35,100
32,355
28,464
20,928
20,838
20,242
18,800
22,213
22,117
21,485
19,953
23,357
23,257
22,592
20,982
4.10
4.04
4.06
4.02
4.18
4.13
4.15
4.11
4.23
4.17
4.19
4.15
34,139
32,064
29,398
26,197
35,758
33,584
30,791
27,439
36,788
34,552
31,679
28,229
4.22
4.18
4.17
4.13
4.32
4.26
4.25
4.21
4.36
4.32
4.31
4.26
1000
1100
1200
20,630
20,557
19,871
18,252
21,897
21,819
21,091
19,372
23,025
22,943
22,178
20,371
-
www.coolex.com.kw10
PERFORMANCE DATA TABLESPERFORMANCE DATA TABLESPERFORMANCE DATA TABLESPERFORMANCE DATA TABLESPERFORMANCE DATA TABLES
CHCc-048A2
CHEc-048A7
49,624
46,244
43,508
39,456
51,875
48,342
45,482
41,246
53,590
49,940
46,985
42,610
86
80
74
68
86
80
74
68
86
80
74
68
72
67
62
57
72
67
62
57
72
67
62
57
29,343
28,374
27,839
27,526
30,984
29,961
29,395
29,065
32,822
31,739
31,140
30,789
4.78
4.76
4.72
4.58
4.88
4.86
4.81
4.67
4.94
4.92
4.87
4.72
45,406
43,608
39,433
35,784
47,465
45,585
41,222
37,408
49,034
47,093
42,584
38,644
26,653
27,638
27,072
26,493
28,143
29,184
28,586
27,974
29,813
30,915
30,282
29,633
5.61
5.58
5.52
5.44
5.71
5.68
5.63
5.55
5.78
5.75
5.70
5.62
44,803
41,945
38,731
35,469
46,835
43,848
40,487
37,077
48,383
45,298
41,826
38,303
5.76
5.72
5.65
5.56
5.87
5.83
5.76
5.67
5.95
5.90
5.83
5.74
1325
1450
1600
26,533
27,043
26,745
25,918
28,104
28,555
28,242
27,368
29,712
30,249
29,917
28,992
CHCc-042A2
CHEc-042A7
Model
43,099
39,814
36,504
33,412
44,867
41,448
38,002
34,783
46,543
42,995
39,422
36,083
86
80
74
68
86
80
74
68
86
80
74
68
72
67
62
57
72
67
62
57
72
67
62
57
24,309
24,148
22,621
21,703
25,881
25,608
23,709
22,748
27,409
27,330
25,303
24,276
3.96
3.92
3.86
3.81
4.04
3.99
3.94
3.89
4.10
4.05
3.99
3.94
42,224
37,243
34,094
31,233
43,957
38,772
35,492
32,515
45,598
40,219
36,818
33,729
23,891
23,823
22,302
21,436
25,041
24,969
23,376
22,467
26,725
26,648
24,947
23,977
4.68
4.65
4.57
4.51
4.78
4.74
4.66
4.60
4.85
4.81
4.73
4.66
39,773
36,744
33,642
30,804
41,405
38,251
35,023
32,069
42,951
39,680
36,331
33,266
4.82
4.78
4.69
4.63
4.91
4.87
4.79
4.73
4.98
4.94
4.86
4.80
1150
1260
1400
23,710
23,664
22,136
21,269
24,851
24,803
23,201
22,291
26,522
26,470
24,761
23,791
Evaporator
CFM
Temp ° F 95 °F 115 °F 118.4 °F
Condenser Ambient Temperature
DB WBCapacity Btu/Hr kw
InputTotal Sen.kw
InputTotal Sen.kw
InputTotal Sen.Capacity Btu/Hr Capacity Btu/Hr
Air Flow
CHCc-060A2
CHEc-060A7
59,242
53,620
46,801
44,086
62,211
56,308
49,147
46,295
64,533
58,411
50,982
48,024
86
80
74
68
86
80
74
68
86
80
74
68
72
67
62
57
72
67
62
57
72
67
62
57
35,933
35,081
33,421
31,499
38,259
37,353
35,586
33,447
40,832
39,864
37,979
36,285
5.54
5.37
5.31
5.11
5.65
5.47
5.42
5.21
5.73
5.55
5.49
5.28
54,104
48,512
42,494
39,021
56,814
50,943
44,624
40,977
58,936
52,845
46,291
42,507
34,490
33,563
30,892
30,699
36,723
35,737
32,893
32,688
39,192
38,140
35,104
34,886
6.48
6.43
6.21
6.11
6.61
6.55
6.32
6.23
6.70
6.64
6.56
6.39
53,013
48,346
41,873
38,752
55,670
50,769
43,972
40,777
57,748
52,666
45,613
42,378
6.65
6.53
6.24
6.21
6.79
6.66
6.37
6.29
6.88
6.75
6.58
6.44
1640
1820
2000
34,305
33,352
30,167
30,102
36,527
35,511
32,121
32,052
38,983
37,899
34,281
34,207
-
www.coolex.com.kw11
UNIT ELECTRICAL DATA
Outdoor Units
Unit Power Supply
Compressor
Volt
Phase
Hz
V - Ph - Hz
RLA
LRA
V - Ph - Hz
Input kW
FLA
CHCc 024
240
1
11.4
60
0.27
1.22
15.5
25
4
CHCc 060
415
3
10
65.5
0.75
0.78x2
14.1
20
2.5
CHCc 042
415
3
7.9
50
0.46
0.78
10.7
15
2.5
CHCc 048
415
3
8.3
61.8
0.78
0.78x2
11.9
20
2.5
CHCc 036
415
3
6.4
46
0.42
0.78
8.8
15
2.5
CHCc 030
240
1
12.2
76
0.25
1.22
16.5
25
4
50
380/420 - 3 - 50220/240 - 1 - 50
Unit Ampacity, Ampere
Max. Fuse Size, Ampere
Minimum Wire Size, mm²
Condenser FanMotor
415 - 3 - 50240 - 1 -50
Indoor Units
Unit Power Supply
Blower Motor
Volt
Phase
Hz
V - Ph - Hz
Motor Hp
Input kW
FLA
CHEc 024 CHEc 060CHEc 042 CHEc 048CHEc 036CHEc 030
240
1
50
240 - 1 - 50
Unit Ampacity, Ampere
Max. Fuse Size, Ampere
Minimum Wire Size, mm²
1/3
0.27
2
2.5
5
1.5
3/4
0.7
4.2
5.3
10
1.5
1/2
0.45
2.8
3.5
5
1.5
3/4
0.6
4.2
5.3
10
1.5
1/2
0.4
2.8
3.5
5
1.5
1/2
0.32
2.8
3.5
5
1.5
FLA : Full Load Amps RLA : Rated Load AmpsLRA : Locked Rotor Amps
LEGEND:
-
www.coolex.com.kw12
SUPPLY AIR PERFORMANCE
External Static Pressure [in.wg]
Model
CHEc-024
CHEc-030
CHEc-036
CHEc-042
CHEc-048
CHEc-060
Air Flow Rate [CFM]
SPEED 0 0.05 0.1 0.15 0.2 0.25 0.3
HIGH
MED
LOW
HIGH
MED
LOW
HIGH
MED
LOW
HIGH
MED
LOW
HIGH
MED
LOW
HIGH
MED
LOW
1122
1065
986
1178
1108
1016
1422
1366
1303
1479
1407
1329
1857
1809
1745
2173
2085
2002
1084
1030
950
1138
1071
979
1379
1322
1261
1434
1362
1286
1822
1768
1696
2124
2029
1965
1039
991
915
1091
1031
942
1336
1282
1223
1389
1320
1247
1777
1722
1650
2082
2002
1912
1011
955
878
1062
993
904
1289
1233
1173
1341
1270
1196
1730
1682
1621
2037
1960
1875
962
916
833
1010
953
858
1242
1190
1126
1292
1226
1149
1695
1635
1580
1991
1910
1827
925
873
791
971
908
815
1189
1195
1075
1237
1231
1097
1652
1590
1536
1942
1861
1775
880
827
742
924
860
764
1141
1091
1026
1187
1124
1047
1593
1526
1448
1894
1816
1730
813
763
686
854
794
707
1089
1035
973
1133
1066
992
1520
1447
1397
1842
1761
1682
739
717
625
776
746
644
1029
981
914
1070
1010
932
1416
1350
1324
1785
1725
1637
695
653
575
730
679
592
963
904
832
1002
931
849
1312
1253
1251
1748
1672
1596
630
-
-
662
-
-
890
-
-
910
-
-
1210
-
-
1681
1613
1522
0.35 0.4 0.45 0.5
-
www.coolex.com.kw13
UNIT DIMENSIONS
Indoor Unit
-
www.coolex.com.kw14
UNIT DIMENSIONS
Outdoor Units
-
www.coolex.com.kw15
WIRING DIAGRAMS
Typical Wiring Diagram
TRANS TRANSFORMER
IBM INDOOR BLOWER MOTOR
CA
P1
BLK BLU
BR
N106
105
104
OFM
CAP
GND
LVTB
LVTB
FIELD WIRING
THERMOSTAT
24Vac
STG1 COOLING
BM CONTROLBMR
S
R
G
Y1
GND
2
Y
S
HPS
124V SEC
TRANS
N
1 3
TDS
L
10CC
R
HIGH VOLTAGE TERMINAL BLOCK
1. MOTORS THERMALLY PROTECTED .
2. USE COPPER CONDUCTORS ONLY.
NOTES
GROUND CAPACITOR
HVTBGNDCAP
BLOWER MOTOR RELAY
LEGEND
BMR
CAPACITOR
CPRCCCAP
LEGEND
GROUNDGNDHVTBHPS
OFM OUT DOOR FAN MOTOR
HIGH VOLTAGE TERMINAL BLOCK
COMPRESSOR CONTACTORCOMPRESSOR
HIGH PRESSURE SWITCH
NOTES:-
TDS
3. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
2. USE COPPER CONDUCTORS ONLY.105°C TYPE OR ITS EQUIVALENT.
1. ANY WIRE REPLACEMENT, SHOULD BE OF THE
TIME DELAY SWITCHTERMINAL BLOCK OR TERMINATION POINT
RATINGS.TO BE PROVIDED BY THE USER, WITH RELEVANT
CLOSE (PSIG)
310 ± 10
OPEN (PSIG)
420 ± 10
SET POINTSNAME
HPS
INDOOR UNIT
OUTDOOR UNIT
FIELD WIRING
4. ALL FIELD WIRING TO COMPLY WITH NEC OR LOCAL CODE
LOW VOLTAGE TERMINAL BLOCKLVTB
WH
ITE
WHITE
BROWN
BMR
IBMCAP
BLA
CK
HVTB
NL
240V
LPS
LPS LOW PRESSURE SWITCH
42 ± 5LPS 25 ± 5
LHVTB
N
CC
CPR
R CS
-
www.coolex.com.kw16
WIRING DIAGRAMS
Microprocessor Based Controller (Optional)
FIELD WIRING
GND
CAP
OFM
104
105
106
BR
N
BLU
BLK
OUTDOOR UNIT
CA
P1
L
N
HVTB
LPS
CC
INDOOR UNIT
HPS
1
2
3
1
2
3
ATB
ATB
TRANS TRANSFORMER
HIGH VOLTAGE TERMINAL BLOCK
1. MOTORS THERMALLY PROTECTED .
2. USE COPPER CONDUCTORS ONLY.
NOTES
GROUND
ELECTRONIC CONTROL BOARD
COMPRESSOR
CAPACITOR
HVTB
GND
CAP
COMP
ECB
INDOOR BLOWER MOTOR
LEGEND
IBM
AUXILIARY TERMINAL BLOCKATBCAPACITOR
CPRCCCAP
LEGEND
GROUNDGND
HVTB
LPSHPS
OFM OUT DOOR FAN MOTORHIGH VOLTAGE TERMINAL BLOCK
LOW PRESSURE SWITCH
COMPRESSOR CONTACTORCOMPRESSOR
HIGH PRESSURE SWITCH
NOTES:-
N
3. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER
2. USE COPPER CONDUCTORS ONLY.105°C TYPE OR ITS EQUIVALENT.
1. ANY WIRE REPLACEMENT, SHOULD BE OF THE
NEUTRAL TERMINAL BLOCKTERMINAL BLOCK OR TERMINATION POINT
RATINGS.TO BE PROVIDED BY THE USER, WITH RELEVANT
42 ± 5
CLOSE (PSIG)
310 ± 10
OPEN (PSIG)
25 ± 5
420 ± 10
SET POINTS
LPS
NAME
HPS
FIELD WIRING
4. ALL FIELD WIRING TO COMPLY WITH NEC OR LOCAL CODE
SCR
CPR
CC
N
HVTBL
HIGH
MED
LOW
CONID
N1
N2
LP
HP
N3
N4
COM
PLL
HTR
240v10v
TRANS
WH
ITE
BR
OW
N
GNDIBM
LOW (RED)
MED (BLUE)
CAP
HIGH (BLACK)
COM (WHITE)
IND
OO
R C
OIL S
EN
SO
R
TO NEUTRALECB
THERMOSTAT
PR
IS
EC
-
www.coolex.com.kw17
NOTES
-
www.coolex.com.kw18