Comprehensive HVAC Assignment Part 1
-
Upload
fain-design-services -
Category
Documents
-
view
214 -
download
0
description
Transcript of Comprehensive HVAC Assignment Part 1
-
Figure 1.1
Tower
Schematic
Piping
Diagram
CAE-464 MTRP 3
95 oF
85 oF
78 oF EWB
12 ft.
-
Problem 1Piping and Pumping
Given:
A 1000 ton refrigeration system is provided with a cooling tower and associated condenser water piping and pumping system.
The condenser water is cooled from 95 F to 85 F with 78 F WB air
The tower schematic piping diagram is shown in Figure 1.1
The condenser water flow rate is based on three gpm of condenser water per ton
The condenser water velocity is nominally eight feet per second.
The system is provided with two 50% capacity pumps and the suction and discharge pipe sizes and as shown.
The pump curve is shown on Figure 1.2
The breakdown of water flow paths and components is shown in Table 1.1
CAE-464 MTRP 4
-
Problem 1Piping and Pumping
Find:
A. Determine to remaining even pipe sizes in the system (Schedule 40, steel)
B. Calculate the system head requirements (Pipe friction factor = 0.02). Strainer data is shown in Figure 1.3, Triple Duty Valve data is shown in Figure 1.4
C. From the pump curve, determine the appropriate impeller size of each pump (Use the defined impeller sizes shown on the pump curve)
D. Develop a new curve showing the performance of one pump and two pumps running
E. Determine the system resistance curve accounting for the static head
F. Plot this system resistance curve on the combined pump curves. Identify the duty point on the curve
G. Determine the flow rate and head of one pump running
H. Determine the net positive suction head NPSH available and the NPSH required for the pumps
CAE-464 MTRP 5
-
Figure 1.2Pump Curve
CAE-464 MTRP 7
-
Figure 1.3Strainer Curve
CAE-464 MTRP 8
-
Figure 1.4Triple Duty Valve
Use 100 % Curve
L
o
s
s
i
n
f
e
e
t
CAE-464 MTRP 9
-
recoverypostfinalrecoverypostrecoverypost2
1.11.21.31.4