Complete numerical ground - GE Grid Solutions · Protection. Ground Time Overcurrent . The MIN II...
Transcript of Complete numerical ground - GE Grid Solutions · Protection. Ground Time Overcurrent . The MIN II...
521
SpecializedProtection&Control
g MultilinDigital Energy
• Reducetroubleshootingandmaintenancecost-eventrecording,andanalogy/digitaloscillography
• Designflexibility-Easytouseprogramminglogic• Accesstoinformation-ModbusRTUcommunications• Configurablelogic,curves,digitalI/Os,andLEDs• Followtechnologyevolution-Flashmemoryforproductfield
upgrade• Assetmonitoring-Breakerhealth,andbreakerfailure
protection
• Twosettingsgroups• Passwordprotectionforlocaloperation• Automaticdisplayoflastfaultinformation• AC/DCpowersupply• Accessviafrontpanelkeypadorcommunicationlinks• EnerVistaTMcompatible• IsolatedRS232port
• Directionalgroundprotectionatanyvoltagelevel• Backup/auxiliaryprotectionforlineschemes
• Componentrelayfortransformers,generatorsandmotors
Protection and Control
• 32-eventrecord,analog/digitaloscillography• Groundcurrentmetering• Monitoringofthelast5tripsinformationfromthedisplay
Monitoring and Metering
User Interfaces
• 2x16characterLCDdisplay• 6LEDindicators,4configurableinfunctionandcolor• FrontRS232andrearRS485portsusingModBus®RTU
protocolupto19,200bps• EnerVistaTMsoftware-anindustryleadingsuiteofsoftware
toolsthatsimplifieseveryaspectofworkingwithGEMultilindevices
• 2groundIOC(highandlow)unitsforgroundedsystems• 2groundTOC(highandlow)unitsforgroundedsystems• 2directionalunitsforgroundedsystems• 2directionalovercurrentunitsforpetersencoil• 2directionalovercurrentunitsforisolatedground• Directionalcomparison:schemelogic• 4preconfiguredovercurrentcurves(ANSIorIEC)• Configurablebreakerfailureprotection• ConfigurableI/O• 6outputs:trip,service,4auxiliary
MIN IIGROUND
PROTECTION SySTEMCompletenumericalground
directionalprotection
FEATURES
APPLICATIONS
KEy BENEFITS
522
MIN II Ground Protection SystemSpecializedProtection&Control
www.GEDigitalEnergy.com
OverviewTheMINII,amemberoftheMIIfamilyofprotectionrelays,isamicroprocessorbased relay that provides ground directional protection on distributed networks at any voltage level andbackup/auxiliary ground directionalprotectionfortransformers,generatorsandmotors.Additionallyitcanbeusedtocreateaseparatedirectionalcomparisongroundschemeinpilotchannelsusedfordistancerelaying.TheMINIIrelaycanbeusedinsystemswheretheneutralisrigidlyconnectedtotheground,wheretheconnectionisdonethrougharesistororaPetersencoil,andalsowhere theneutral is isolated fromtheground(ungroundedsystems).Twomodelsareavailable:Models‘E’and‘S’.Basicprotectionfeaturesforthemodel‘E’ (neutral rigidly or through resistor connected to ground) include grounddirectional time delayed overcurrentandground instantaneousovercurrent(two levelseachHisetandLoset).Eachunitcanbeselectedtobedirectionalornot.Forthemodel‘S’(isolatedgroundor connection through Petersen Coil) theMIN IIhas two independentdirectionalunits.Each protection element can beselectively enabled either via the frontpanel or via communication. Flexiblesettings, selectableANSIor IECcurves,plus the choice of a user configurableovercurrent curve enable accuratecoordinationwithotherdevices.TheMIN II has two fixed digital inputsandsixfixeddigitaloutputs.Anoptionis
providedallowingthetwoinputsandfouroftheoutputstobeuserconfigurable.TheMIN II has six fixed status LEDs. Anoption isprovidedallowing fourof theseLEDstobeuserconfigurable.The frontpanelalso featuresa5-buttonkeypad and a 16x2 LCD display that providesaneasytouseuserinterface.The front keypad allows the user to setthe baud rate and relay address forcommunication.AfrontRS232andarearRS485communicationportareprovidedfor computer access using ModBus®RTU protocol. The rear RS485 can be convertedtoanRS232orfiberopticport(plasticorglassfiberoptics)bymeansofusing an external converter, such asGEMultilinDAC300orF485.Windows®basedEnerVistaTM software is provided free ofchargewiththerelaytoallowsetupandconfigurationofMIFIIunits.Computer access allows setting and configuration (inputs, outputs, LEDs andconfigurablelogic)oftheunits,displayofmeteringinformationandrealtimestatusoftheunit .Anoptionisprovidedallowingthe display of event records and an oscillographyrecordforthelastfault .
Protection
Ground Time Overcurrent
TheMINIIprovidesgroundtimeovercurrentprotectionthatcanbesetfrom0.1to2.4timesIn.Threedifferentcurvetypescanbeselected:ANSI,IEC/BS142andoneuserconfigurable.Thisallowstheselectionoftheoptimumcurveforcoordinationwith
fuses, feeders, motor transformers etc.ANSIandIECcurvesinclude:definitetime,normalinverse,veryinverse,andextremelyinverse. For each curve, different time multipliersmaybeset.CurveTypes:
• ANSI IEC/BS142
• Normalinverse IECA
• Veryinverse IECB
• Extremelyinverse IECC
• Definitetime
Ground Instantaneous Overcurrent units
The MIN II includes two separatelyadjustable ground instantaneousovercurrent units. Each one can beindependentlyenabled.Settingsallowthepickup setpoint tobe set from0.1 to30timesInandatimedelayfrom0to600.00secondstobeset.
Ground Directional Control Theseunitsprovidedirectionalcontroltotheunitsdescribedabove:51G1,51G2,50G1,50G2.Thesupervisionispolarizedbyzero-sequencevoltagewithadjustabletorqueangle.Thedirectionalsupervisionisalsoadjustableindependentlyforeachovercurrentunit.Programmableperfor-mancelogicforpolarizationvoltagelossisincluded.
Isolated Ground Directional Control TheMINIIprovidesdirectionalprotectionforungroundedsystems.Inthistypeofsystemtheneutraliscompletelyisolatedfromtheground,asaresultofthisthe
Functional Block Diagram
51G1 51G2
MIN II Option E
50G1 50G2
52
METERINGOSCILOGRAPHYEVENT RECORDERPROGRAMMABLE I/O AND LEDSPROGRAMMABLE LOGIC
67G1 67G2
EN MIN II OPTION E BLOCK.cdr
MIN II Option S
52
METERINGOSCILLOGRAPHYEVENT RECORDINGCONFIGURABLE I/O AND LEDSCONFIGURABLE LOGIC
67IG1
67IG2
67PC1
67PC2
EN MIN II OPTION S BLOCK.cdr
523
MIN II Ground Protection System
SpecializedProtection&Control
www.GEDigitalEnergy.com
groundfaultcurrentvalueisminimumandproducedonlybythelinecapacitive coupling.
The relay operation is based on thepresenceofthiscapacitivecurrentplusthedetectionofanovervoltagecondition.
Peterson Coil Directional Control
TheMINIIprovidesdirectionalprotectionfor systems where the connectionto the ground is done through aPetersen coil. This scheme is knownas ground resonant circuit or groundfault neutralizer. The relay operationis based on a real power directionalprotection unit , being intrinsically a ground directional function polarized byzerosequencevoltage.The torqueangledefinestheoperationzoneandthethreemagnitudes (residual current , residual voltageandrealpower)definethepickupvalue.
Multiple Setting Groups
Twoseparatesettingsgroupsarestoredin MIN II non volatile memory, withonly one group active at a given time.Switchingbetweensettinggroups1and2 canbedonebymeansof a setting, acommunicationcommandordigitalinputactivation.Settingsaredividedin2categories,mainandadvancedsettings.Thisallowsuserstohaveaccesstomainrelayfunctionalitiesinanextremelysimple,userfriendlywaybyenteringonlymainsettings,whilehavingaccesstocompletefunctionalityformorecomplexusethroughadvancedsettings.
MeteringMIN II provides metering values forgroundcurrent.Theaccuracyis3%inthe completerange.
Event Recording
Eventsconsistofabroadrangeofchangeof state occurrences, including pickups,trips, contact operations, alarms andself test status. The MIN II stores up to24 events time tagged to the nearest millisecond.Thisprovidestheinformationneededtodeterminesequenceofeventswhich facilitates diagnosis of relayoperation. Each event is individuallymaskableinordertoavoidthegenerationof undesired events, and includes thevalues of currents and voltages, andstatusofalltheprotectionelementsatthemomentoftheevent.
Oscillography
MIN II captures current waveforms anddigital channels at 8 samples per cycle.Oneoscillographyrecordwithamaximumlengthof24cycles is stored inmemory.Oscillographyistriggeredeitherbyinternalsignalsoranexternalcontact.TheMINIIcanbeaccessedwithaPCusingtheMIIEnerVistaTMSetupSoftwareviatheRS232communicationportlocatedintherelayfrontpanel.Iftherelaywasfurnishedwiththeappropriateoption,useEnerVistaTM to display last fault information such aseventreportsandanoscillographyrecords.TheMINIIhasadrawoutconstruction in1/4ofa19’’rackcase.
Configurable I/O and LEDs
Twodigital inputsareuserconfigurable.Outofthesixdigitaloutputsincorporated,twohaveafixedfunction(tripandservicerequired), while the other four are userprogrammable. Those configurableoutputs can be assigned either to a setof pre-configured values, or an OR/NOTcombination of the same values. Eachconfigurableoutputcanbeindependentlylatched,andindividuallyselectedasNOorNCbymeansofajumper.Outputs 1 and 2 can be isolated fromoutputs2and3byremovingjumperJX.Fourof the6LED indicatorscanalsobeprogrammedbytheuser.ThefirstLEDhasa fixedassignment (relay inservice), thesecondisfixedfortrip,andtheremainingfour LEDs are configurable in function,memoryandcolor(redorgreen).
Configurable Logic
Uptoamaximumof4configurablelogicschemes can be implemented into theMIN IIbymeansofusingasetof4pre-configured logicgatesand timercells.Agraphical user interface is provided forconfiguration ofMIN II logic. The inputsof the MIN II configurable logic can beassignedtocontactoutputsand/orLEDs.
User Interfaces
Display
Measurement data (actual values), faultreportsforthelastfivetrips,andsettingsare shown on the 16x2 characters LCD display.
Status LEDs
TheMIN II incorporates6LED indicatorsinthefrontplate.ThefirstoneisagreenLEDidentifiedas“READY”,usedtoindicatethe status of the protection elements.When“ON”itmeanstherelayisenergizedand ready to protect , and at least oneprotectionelementhasbeenenabled.ThesecondoneisaredLEDusedforTRIPindication. It will be “ON” when a faultoccurs and the relay energizes the tripoutputs. Once energized, it will remainlatcheduntiltheESC/RESETkeyispressedforthreesecondstoRESETtherelay.Four additional LEDs are programmableinfunctionandcolor.Thefactorydefault
Use the oscillography feature as an accurate troubleshooting and diagnostics tool
524
MIN II Ground Protection SystemSpecializedProtection&Control
www.GEDigitalEnergy.com
Communication Ports
AfrontmountedRS232andarearRS485port allow easy user interface via a PC.ModBus®RTUprotocolisusedforallports.Therelaysupportsbaudratesfrom300to19,200bps.Upto32GEMultilindevicescanbeaddressedonasinglecommunicationschannel. A unique address must beassignedtoeachrelayviaasettingwhenmultiplerelaysareconnected.
MultiNet™ compatible
MultiNetisacommunicationsmodulethatprovides GE Multilin serial ModBus IEDswithModBusTCP/IPcommunicationsoverEthernet,allowingconnectiontofiberopticLANandWANnetworksystems.MultiNet has the capability to connectup to 32 serial ModBus deviceseliminatingcomplexwiringandadditionalcommunicationsconverters,andprovidingastreamlinedandeconomicalEthernethub.Unlikemost communications convertersthat are designed for commercial use,MultiNet is environmentally hardenedtowithstandsevereutilityand industrial conditions.
• ConvertsModbusRTUoverRS485intoModbusTCP/IPoverEthernet
• Supportsboth10BaseTand10BaseFfiberconnections
• Connectupto32RS485serialdevicestoanEthernetnetwork
• ModbusTCP/IPprovidesmultiple
functionsoftheprogrammableLEDsare:GroundTrip,50Trip,andPickup,whilethecolorissettoRED,andthestatusmemoryasself-resetting.TheusermaychangethefunctionandstatusmemorythroughtheuseoftheEnerVistaTMsoftware.TheLEDcolorcanbemodifiedusingtherelay keypad. The statusmemorymaybe programmed either self-resetting or latching.Ifprogrammedasself-resetting,when the associated function dropsout the corresponding LEDs turn off. If programmed as latched, the LED willremain “ON” until the ESC/RESET key ispressed for three seconds to reset therelay.In order to test LEDs, pressing the ESC/RESETkeyforthreesecondswillturn“ON”allLEDs.Whenthekeyisreleased,theLEDswillturnoff(exceptifthefunctionpickupsarestillactive).Thisallowseasytestingoftheequipment.
Keypad
A five-buttonkeypadallowsuseraccessfor easy relay interrogationandchangeofsettings.Access to events and oscillographyrecords,andunitconfigurationispossibleonlythroughPCcommunication.
Self-Test Diagnostics
Comprehensiveself-testdiagnosticsoccuratpowerupandcontinuouslyduringrelayoperation.Anyproblemfoundbyself-testscausesanalarmandaneventislogged.
SCADAmastersallowingsimultaneouscommunicationstothesameIED
• Flexiblemountingoptionsallowretro-fittoexistingdevices
• Industriallyhardenedforutilityandindustrialapplications
• Simple“plug&play”devicesetupwithEnerVistaTMsoftware
MultiNetgivesyoutheabilitytoconnectM II serial devices to new or existingEthernetnetworks.Ithasa10Base-FfiberopticinterfacethatprovideshighEMI/RFI immunityandinherentelectricalisolationover long cable runs. MultiNet setup issimple,withaWindows®basedEnerVistaTM software program for installing and configuringthecommunicationdrivers.
EnerVistaTM SoftwareThe EnerVista™ Suite is an industry-leading set of software programs thatsimplifieseveryaspectofusingtherelay.TheEnerVistaTMsuiteprovidesallthetoolsto monit or the status of the protectedasset ,maintain the relay, and integrateinformationmeasuredintoDCSorSCADAmonitoringsystems.Convenientwaveformand Sequence of Events viewers are anintegral part of theMII Setup softwareincludedwitheveryMINIIrelay,tocarryoutpostmortemeventanalysistoensureproperprotectionsystemoperation.
EnerVista™ Launchpad
EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswithallofthesetupandsupporttoolsneededforconfiguringandmaintainingGEMultilinproducts. The setup software withinLaunchpadallowsconfiguringdevices inreal-timebycommunicatingusingserial,Ethernet , or modem connections, orofflinebycreatingsettingfilestobesenttodevicesatalatertime.Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when needed.Documentsmadeavailableinclude:
• Manuals
• ApplicationNotes
Use Programmable Logic to set the MIV II to meet specific application needs
525
MIN II Ground Protection System
SpecializedProtection&Control
www.GEDigitalEnergy.com
• GuideformSpecifications
• Brochures
• WiringDiagrams
• FAQs
• ServiceBulletins
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems.ViewpointMonitoringprovidesacompleteHMIpackagewiththefollowingfunctionality:
• Plug-&-PlayDeviceMonitoring
• SystemSingle-LineMonitoring&Control
• AnnunciatorAlarmScreens
• TrendingReports
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
A5
A6 TRIP
DIG
ITAL
IN
PUTS
(**) A8
A9
A10
CC1
CC2
COM
GND SAFETY GROUND
SDA B12
SDB A12
GND B11
RS
485
OU
T1
B7
OU
T1/2
B8
B9
B10
A7
OU
T3
OU
T4
CO
M
JX
B5
B6 SYST
EM
READ
Y
A
B
GROUND
INPUT
PROGRAMMABLE CONTROLLER
INPUT
TRIP COIL CONTROL POWER
-
+
TRIP COIL
RS232
GROUND BUS
DIG
ITA
L O
UTP
UTS
(**)
(*)
(*)
(*)
A B C
C8
C7 VOLTAGE INPUT
V
N
(**) In the default configuration, inputs and outputs are programmed as follows:
INPUTS CC1: Disable all units CC2: Disable units 50N (50NH and 50NL)
OUTPUTS OUT1: Trip 51G1 OUT2: Trip 51G2 OUT3: Trip 50G1 OUT4: Trip 50G2
POWER SUPPLY
A1 A2 +/L -/N
52a 52a
BREAKER
LOAD
CT CONNECTION WITH DEDICATED TRANSFORMER FOR THE GROUND UNIT
ALTERNATIVE CT WIRING IN RESIDUAL CONNECTION FOR THE GROUND UNIT
POLARIZATION CURRENT
DIRECTION OF TRIP DIRECTION OF TRIP SOURCE
AC OR DC
C3
C3
C1
C1
C5 C4
C4
C2
C2
C6
CURRENT INPUTS
N
N
1 A
1 A
5 A
5 A N
N
N I G
I G
I G
I G
I P
(*) Terminals B12, A12 and B11 must be connected to SELV (safety extra-low voltage) parts (on the PLC). They are not to be tested for hipot test under any circumstance
WARNING: GROUND PC TO RELAY GROUND. OTHERWISE USE UNGROUNDED PC
Multilin MIN II Ground Protection System
Model E g
CURRENT INPUTS
Typical Wiring
6.243( 158,6 )
7.131(181,1)
10.472(266)
6.819(173)
9.276(235,5)
Optional depthreducing collar
MENU
ESC
ENTER
g MII Digital Protection
CUTOUTSIDEFRONT
O0.27 (0.7)
7.0
(178
)4.
0 (1
01.6
)
(136) 5.35(110) 4.33
EN MIFII DIM C
Dimensions
526
MIN II Ground Protection SystemSpecializedProtection&Control
www.GEDigitalEnergy.com
Technical Specifications
*Specificationssubjecttochangewithoutnotice.
METERINGTHERMAL CAPACITyCurrentCircuits:Continuously: 4xInDuring3Sec: 50xInDuring1Sec: 100xIn
PROTECTIONGROUND TIME OVERCURRENTPickuplevel: 0.1-2.4Ininstepsof0.01CurveShapes: Definite time, inverse, very inverse,
extremelyinverse,userdefined.Timemultiplier: 0.05-2.00instepsof0.01forIECcurves
0.5 - 20.0 in steps of 0.01 for ANSIcurves
Definitetime: 0.00to600.00sinstepsof0.01s.Accuracy: 3%inthewholerange.1%typicalat
ratedcurrent.Timingaccuracy: ±5%+50msofsettimefor2<I<
20timestheActualPickupLevelforIEC/ANSI/definitetimecurves.
GROUND INSTANTANEOUS OVERCURRENTCurrent: FundamentalPickuplevel: 0.1-30Ininstepsof0.01Definitetime: 0.00to600.00sinstepsof0.01sAccuracy: 3%inthewholerange.1%typicalat
ratedcurrent.Timingaccuracy: ±5%+50msofsettimefor2<I<20
timestheActualPickupLevelforIEC/ANSI/definitetimecurves.
GROUND DIRECTIONAL UNITTorqueangle: -90ºto+90ºinstepsof1º.Direction: Forward/ReverseGROUND TIME OVERCURRENTPickuplevels: Current:0.005-0.4Ainstepsof0.001
AVoltage:2-70Vinstepsof0.01VDefinitetime: 0.00to600.00sinstepsof0.01sInstantaneous trip deviation time:
0-99.99secinstepsof100ms
Torqueangle: -90ºto+90ºinstepsof1ºGROUND TIME OVERCURRENT FOR PETERSEN COILPickuplevel: Current: 0.005 - 0.4 A in steps of
0.001AVoltage:2-70Vinstepsof0.01VPower:0.01-4.5W
Definitetime: 0.00to600.00sinstepsof0.01sTorqueangle: 0ºto+180ºinstepsof1º.
MECHANICAL CHARACTERISTICS•Metallicpackagein1/419’’rackand4unitshigh•ProtectionclassIP52(accordingtoIEC529)
ENVIRONMENTALTemperature:Storage: -40ºCto+80ºCOperation: -20ºCto+60ºCHumidity: Upto95%withoutcondensing
INPUTSAC CURRENTSecondary Rated Current:
1Aor5Adependingontheselectedmodel
Frequency: 50/60Hz±3Hz(Theunitcanbesetto50or60Hz)
RelayBurden: <0.1VA@In=5Asecondary <0.02VA@In=1Asecondary
CurrentWithstand: 4xIncontinuously 100xInfor1sec.
AC VOLTAGESecondary Rated Voltage:
50-240Vac
Frequency: 50/60Hz±3Hz(Theunitcanbesetto50or60Hz)
RelayBurden: <0.2VA@120VacVoltageWithstand: 440VaccontinuouslyDIGITAL INPUTSHigh RangeVoltageThreshold: 75VdcMaximumVoltage: 300VdcRelayBurden: 5mA@300VdcLow RangeVoltageThreshold: 12VdcMaximumVoltage: 57VdcRelayBurden: 2mA@57Vdc
Voltage M/C M/C cont.
Break 0.2 seg
MaxLoad
DC Resist
24Vdc 16A 48A 16A 384W48Vdc 16A 48A 2.6A 125W125Vdc 16A 48A 0.6A 75W250Vdc 16A 48A 0.5A 125W
DC Induct.24Vdc 16A 48A 8A 192W48Vdc 16A 48A 1.3A 62W125Vdc 16A 48A 0.3A 37.5W
(L/R=40ms) 250Vdc 16A 48A 0.25A 62.5WAC Resist 120Vdc 16A 48A 16A 720W
250Vdc 16A 48A 16A 4000WAC Induct PF=0.4
120Vdc 16A 48A 16A 720W250Vdc 16A 48A 16A 1250W
COMMUNICATIONSLocalCommunication: Alphanumeric display; 3 button
frontalkeypadRemoteCommunication:(localorremotePCandcommunicationsnet):Protocol: ModBus®RTUBaudrate: 300to19200bpsDB9connectorforRS232portsonthefront (1)andRS485ontherear
POWER SUPPLyLOW RANGERatedDCVoltage: 24to48VdcMin./Max.DCVoltage: 19/58VdcHIGH RANGERatedDCVoltage: 110to250VdcMin./Max.DCVoltage: 88/300VdcRatedACVoltage: 110to230Vac@48–62HzMin./Max.AVVoltage: 88/264Vac@48–62HzPowerConsumption: Max.=15WBackuptime: (date, timeand logmemory)with
outpowersupplyvoltage>1week
PACKAGINGApproximateWeight:Net: 8.8lbs(4kgs)Ship: 9.9lbs(4.5kgs)
TyPE TESTSTEST STANDARD CLASSInsulationTestVoltage:
IEC60255-5 2kV,50/60Hz1minSurgeTestVoltage:
IEC60255-5 5kV,0.5J.(3positivepulsesand3negative.)
1MHzInterference:IEC60255-22-1 III
ElectrostaticDischarge:IEC60255-22-2 IVEN61000-4-2 8kVincontact,
Radiointerference: 15kVthroughairIEC60255-22-3: III40MHz,151MHz,450MHzandcellularphone
Radiated Electromagnetic fields with amplitude modulation
ENV50140 10V/mRadiated Electromagnetic fields with amplitude modulationCommon mode ENV50141 10V/mRadiated Electromagnetic fields with frequency modulation
ENV50204 10V/mFastTransients: ANSI/IEEEC37.90.1 IV
IEC60255-22-4 IVBSEN61000-4-4 IV
Magnetic fields at industrial frequency:
EN61000-4-8 30AV/mPowerSupplyinterruptions:
IEC60255-11Temperature: IEC57(CO)22RFEmission: EN55011 BSinusoidalVibration:
IEC60255-21-1 IIShock: IEC60255-21-2 IInsulationTest: IEC255-5(Testedon
CTs,PowerSupplyterminals,ContactInputsandContactOutputs)
APPROVALSCE: Conformsto89/336/CEEand73/23/CEEISO: ManufacturedtoanISO9001registeredprogram
OUTPUTSTRIPPING CONTACTSContactCapacity:Max.OperatingVoltage: 400VacContinuousCurrent: 16AMakeandCarry: 30ABreaking: 4000VAOUTPUT RELAySConfiguration: 6Electro-Mechanical
FormCContactMaterial: Silveralloysuitedfor
inductiveloadsOperateTime: 8msMaxRatingsfor100,000operations:
OrderingMINII * * 0 * E 0 0 * 0 * Description Relay N BasicModel L Withlogicforteleprotectionschemes(seeNote1)Curve A ANSICurves I IECCurves(seeNote2)Ground E Groundedsystem(In=1or5A) S Isolatedground/PetersenCoilPowerSupply LO 24-48Vdc(Range:19~58Vdc) HI 110-250Vdc(Range:88~300Vdc)- 110-240Vac(Range:88~264Vac)ConformalCoating O Withoutconformalcoating H Conformalcoating
• ViewGuideformSpecifications
• Downloadtheinstructionmanual
• Reviewapplicationsnotesandsupportdocuments
• BuyaMINIIonline
• ViewtheMINIIbrochure
Visitwww.GEMultilin.com/MINIIto: