Installation Instructions
CompactLogix EtherNet/IP Web Server Module
Catalog Number 1768-EWEB
Topic Page
Important User Information 2
Minimum Spacing 7
What You Need 8
Install the Modules 8
Wire the Module 14
Connect the Module 15
Configure the Module 16
Confirm Your Installation 16
Remove the EtherNet/IP Web Server Module 17
Troubleshoot the Module 18
Status Indicators 19
Specifications 20
Additional Resources 23
-
2 CompactLogix EtherNet/IP Web Server Module
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 3
North American Hazardous Location Approval
The following information applies when operating this equipment in hazardous locations.
Informations sur lutilisation de cet quipement en environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne conviennent qu' une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livr avec des marquages sur sa plaque d'identification qui indiquent le code de temprature pour les environnements dangereux. Lorsque plusieurs produits sont combins dans un systme, le code de temprature le plus dfavorable (code de temprature le plus faible) peut tre utilis pour dterminer le code de temprature global du systme. Les combinaisons d'quipements dans le systme sont sujettes inspection par les autorits locales qualifies au moment de l'installation.
WARNING:Explosion Hazard -Do not disconnect equipment
unless power has been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
AVERTISSEMENT:Risque dExplosion Couper le courant ou s'assurer que
l'environnement est class non dangereux avant de dbrancher l'quipement.
Couper le courant ou s'assurer que l'environnement est class non dangereux avant de dbrancher les connecteurs. Fixer tous les connecteurs externes relis cet quipement l'aide de vis, loquets coulissants, connecteurs filets ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet quipement inadapt une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est class non dangereux avant de changer les piles.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
4 CompactLogix EtherNet/IP Web Server Module
European Hazardous Location ApprovalThis equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC.
Intertek certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in confidential report No.100014190DAL-001.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15.
WARNING: This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 5
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional installation requirements.
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
6 CompactLogix EtherNet/IP Web Server Module
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. If available, use a static-safe workstation. When not in use, store the equipment in appropriate static-safe
packaging.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 7
Minimum Spacing Plan for this minimum spacing from enclosure walls, wireways, and other equipment.
See Specifications on page 20 for the temperature range.
Item Description
1 105 mm (4 in.)
2 90 mm (3.54 in.)
31609-M
PowerOUT
L1
L2/N
2
1
2
1
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
8 CompactLogix EtherNet/IP Web Server Module
What You Need
Install the Modules
Item Cat. No. or Size
1768 CompactLogix power supply 1768-PA3
1768 CompactLogix controller 1768-L43
1769 end capConnects to the controller as the last module, either: without any 1769-series
modules attached to the controller (1768-series only)
with a combination of 1768-series and 1769-series modules attached to the controller
1769-ECR
RJ45 Ethernet connector See Wire the Module on page 14
DIN rail or mounting screws (one or the other but not both)
DIN rail Either of these sizes:
35 x 7.5 mm (EN 50 022 - 35 x 7.5) 35 x 15 mm (EN 50 022 - 35 x 15)
Screws M4 or #8 panhead screws
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.87 in.) and use end-anchors appropriately.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 9
If You Are Using Screws to Mount Your Modules
The steps in these instructions show how to mount the modules on DIN rail. If you are using screws instead of DIN rail, make these changes to the instructions.
1. Follow the steps in Mount the Controller on the DIN Rail on page 10 to connect the modules together.
2. Use the modules as a template and mark pilot holes on your panel.
3. Drill the pilot holes for M4 or #8 screws.
4. Use M4 or #8 screws to mount the modules to your panel. Use 1.16 Nm (10 lbin) of torque.
5. Ground the module on a ground bus with a dedicated earth ground stake.
6. Connect the ground bus to a functional earth ground on the DIN rail or panel.
7. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional information.
IMPORTANT Do not use screws and DIN rail to mount the modules. It is possible to break the mounting tabs off if you screw the modules to the panel while they are on DIN rail
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
10 CompactLogix EtherNet/IP Web Server Module
Install the DIN RailMount the DIN rail in a suitable location.
Mount the Controller on the DIN Rail
1. Close the DIN rail latches on the controller.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 11
2. Align and press the controller onto the DIN rail until the latches snap closed.
Mount the EtherNet/IP Web Server Module on the DIN Rail
1. Open the DIN rail latches on the module.
2. Align and press the module onto the DIN rail to the left of the controller.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
12 CompactLogix EtherNet/IP Web Server Module
3. Slide module snugly against the controller.
Mount the Power Supply on the DIN Rail
1. Close the DIN rail latches on the power supply.
2. Align and press the power supply onto the DIN rail until the latches snap closed.
3. Slide the power supply snugly against the module.
Mount the I/O Modules on the DIN Rail
1. Close the DIN rail latches on the module.
2. Align the tongue-and-groove slots of the module with the tongue-and-groove slots of the controller and slide the module back towards the DIN rail.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 13
When the module is in place, the DIN rail latches snap closed.
3. Slide the locking tab of the module to the left to lock the module in place.
4. Align the tongue-and-groove slots of the end-cap with the tongue-and-groove slots of the module.
5. Slide the end-cap back towards the DIN rail.
Item Description
1 Locking tab
2 Tongue-and-groove slot
2
2
1
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
14 CompactLogix EtherNet/IP Web Server Module
6. Move the lock latch to the left to lock the endcap on the module.
Wire the ModuleUse an RJ45 connector to connect to the EtherNet/IP network.
Item Description
1 Lock latch
1
8
1
8 ------ NC7 ------ NC6 ------ RD-5 ------ NC4 ------ NC3 ------ RD+2 ------ TD-1 ------ TD+
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 15
Connect the Module
Attach the RJ45 connector to the Ethernet port on the bottom of the module.
WARNING: If you connect or disconnect the cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
IMPORTANT We recommend connecting the module to the network via a100 MB Ethernet switch, which will reduce collisions and lost packets and increase network bandwidth. For detailed EtherNet/IP connection information, see the EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001.
Item Description
1 Ethernet port
1
31611-M
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
16 CompactLogix EtherNet/IP Web Server Module
Configure the ModuleTo configure your module, refer to the configuration chapter of the Web Server Modules User Manual, publication ENET-UM527.
Confirm Your InstallationVerify the following status indicators states.
See Troubleshoot the Module on page 18 if the status indicators are in other states.
Item Description
1 Solid or flashing green
2 Solid green
31608-M
PowerOUT
L1
L2/N
2 2
1
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 17
Remove the EtherNet/IP Web Server Module
1. Turn off power.
2. Open the DIN rail latches of the EtherNet/IP Web Server Module and the module directly left of the EtherNet/IP Web Server module.
3. Slide the EtherNet/IP module to the right with other modules.
4. Slide the controller away from the EtherNet/IP module.
5. Pull the EtherNet/IP module forward off the DIN rail.
IMPORTANT When you turn the CompactLogix power supply off, make sure you wait for all status indicators on the power supply and controller to turn off before disconnecting any part from the system.
If you disconnect the CompactLogix system while the controller is still writing its program to memory, the program write will not be completed and you will lose your program.
PowerOUT
L1
L2/N
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
18 CompactLogix EtherNet/IP Web Server Module
Troubleshoot the ModuleThe three bi-color (red/green)status indicators on the module provide diagnostic information about the module and its connections to the network. If the alphanumeric display and status indicators do not sequence through the expected states, refer to the troubleshooting tables.
Item Description
1 Link status indicator
2 OK status indicator
3 Network status indicator
3 2
1
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 19
Status IndicatorsThe module status indicators provides the following information:
Indicator Status Description
NET Off Module is not powered, or does not have an IP address. Verify there is chassis power and the module is
completely inserted into the chassis and backplane. Make sure the module has been configured.
Flashing Green Module has obtained an IP address, but has no established connections.
Green Module has an IP address and at least one established connection.
Flashing Red One or more of the connections in which the module is the target has timed out.
Red Module has detected that its IP address is already in use. Assign a unique IP address to the module.
Link Off No data transmission.Module is not ready to communicate.
Green Module is ready to communicate.
Flashing Green Data transmission in progress.Module is communicating over the network.
OK Off Module does not have 5V DC power. Verify there is power and the module is properly installed.
Flashing Green Standby mode. Module is not configured.
Green Module is operating correctly.
Flashing Red A minor, recoverable fault has been detected. This could be caused by an error in the configuration.
Red A major, unrecoverable fault has been detected. Recycle power to the module. If this does not clear the fault, replace the module.
Flashing Red and Green
Module performing power-up self-test.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
20 CompactLogix EtherNet/IP Web Server Module
Specifications
Technical Specifications - 1768-EWEB
Attribute 1768-EWEB
Backplane current 834 mA at 5.2V DC
Power consumption 4.34 W
Power dissipation 4.38 W
Isolation (continuous-voltage rating)
30V, Functional Insulation Type, Ethernet network to systemType tested at 710V DC for 60 s
Wire Size Ethernet network connections:RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702
Wiring category(1)
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
2 - on communication ports
North American temp code T4A
IEC temp code T4
Mounting screw torque 1.16 Nm (10 lbin), using M4 or #8 screws
Dimensions (HxWxD), approx. 132 x 56.7 x 105.1 mm (5.20 x 2.23 x 4.12 in.)
Weight, approx. 0.213 kg (7.5 oz)
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 21
Environmental Specifications - 1768-EWEB
Attribute 1768-EWEB
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold) IEC 60068-2-2 (Test Bd, Operating Dry
Heat) IEC 60068-2-14 (Test Nb, Operating
Thermal Shock)
060 C (32...140 F)
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged
Nonoperating Cold) IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating Dry Heat) IEC 60068-2-14 (Test Na, Unpackaged
Nonoperating Thermal Shock)
-4085 C (-40...185 F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged
Damp Heat)
595% noncondensing
Vibration IEC 60068-2-6 (Test Fc, Operating)
5 g @ 10500 Hz
Operating shock IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
30 g
Nonoperating shock IEC 60068-2-27 (Test Ea, Unpackaged
Shock)
50 g
Emissions CISPR 11
Group 1, Class A
ESD immunity IEC 61000-4-2
4 kV contact discharges8 kV air discharges
Radiated RF immunity IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%AM from 302000 MHz10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz1V/m with 1 kHz sine-wave 80%AM from 20002700 MHz
EFT/B immunity IEC 61000-4-4
2 kV at 5 kHz on communication ports
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
22 CompactLogix EtherNet/IP Web Server Module
Surge transient immunity IEC 61000-4-5
2 kV line-earth(CM) on communication ports
Conducted RF immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz80 MHz
Enclosure type rating None (open-style)
Certifications
Certification (when product is marked)(1)
Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A &
B)
C-Tick Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres,
Protection "n" EN 60079-0; General Requirements
II 3 G Ex nA IIC T4
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
(1) See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Environmental Specifications - 1768-EWEB
Attribute 1768-EWEB
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
CompactLogix EtherNet/IP Web Server Module 23
Additional ResourcesThese documents contain additional information concerning related Rockwell Automation products.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
Resource Description
EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001
Provides information about how to use EtherNet/IP modules with vrious Logix5000 controllers.
1768 CompactLogix Controller Installation Instructions, publication 1768-IN004
Provides information for installing a 1768 CompactLogix controller.
1769 CompactLogix Power Supplies Installation Instructions, publication 1768-IN001
Provides information about how to install CompactLogix power supplies.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://ab.com
Provides declarations of conformity, certificates, and other certification details.
Rockwell Automation Publication 1768-IN007B-EN-P - August 2010
-
Rockwell Automation Support
Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.
Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
New Product Satisfaction ReturnRockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
United States or Canada 1.440.646.3434
Outside United States or Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.
United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Publication 1768-IN007B-EN-P - August 2010 PN-83489
Allen-Bradley, Allen-Bradley, CompactLogix, RSLogix5000, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Supersedes Publication 1768-IN007A-EN-P - September 2006 Copyright 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
1768-IN007B-EN-P, CompactLogix EtherNet/IP Web Server Module Installation InstructionsImportant User InformationNorth American Hazardous Location ApprovalEuropean Hazardous Location ApprovalEnvironment and EnclosurePrevent Electrostatic DischargeMinimum SpacingWhat You NeedInstall the ModulesIf You Are Using Screws to Mount Your ModulesInstall the DIN RailMount the Controller on the DIN RailMount the EtherNet/IP Web Server Module on the DIN RailMount the Power Supply on the DIN RailMount the I/O Modules on the DIN Rail
Wire the ModuleConnect the ModuleConfigure the ModuleConfirm Your InstallationRemove the EtherNet/IP Web Server ModuleTroubleshoot the ModuleStatus IndicatorsSpecificationsAdditional ResourcesBack Cover
/ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth 8 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /FlateEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False
/Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice
Introduction_Catagory Types
This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.
Publication Type and Print Category
Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder MinOrder MaxLife Cycle Usage / Release Option
ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal
APA3D2Application Solution or Customer Success Story5100Presale / External
ARNANAArticle/Editorial/BylineNANAPresale / Internal
/News Release (press releases should not be checked into DocMan or printed)
ATB3, B4D5Application Techniques5100Presale / External
BRA2 Primary, A1NABrochures5100Presale / External
CAC2 Primary, C1NACatalogue150Presale / External
CGNANACatalogue Guide150Presale / External
CLNANACollection550Presale / External
COA5, A6, A9D5Company Confidential InformationNANANA / Confidential
CPE-onlyE-only, D5Competitive Information550NA / Confidential
DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal
DIA1, A3NADirect Mail5100Presale / Internal
DMNANAProduct Demo550Presale / Internal
DSB3D5Dimensions Sheet15Post / External
DUB3D5Document Update15Post / External
GRB2D6Getting Results15Post / External
INB3D5Installation instructions15Post / External
LMNANALaunch KitMaterials550Presale / Internal
PCB3D5Packaging Contents
PLE-only Primary, B3E-onlyPrice List550Presale / Internal
PMB2D6Programming Manual15Post / External
PPA3D1Product Profile NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External
QRB2 Primary, B3, B5D5, D6Quick Reference15Post / External
QSB2 Primary, B3, B5D5, D6Quick Start15Post / External
RMB2D5, D6Reference Manual15Post / External
RNB3D5Release Notes15Post / External
SGB1 Primary, B4D5, D6Selection Guide Colour550Presale / External
SGB2D5, D6Selection Guide B/W550Presale / External
SPA1, A2, A3, A4NAService ProfileSales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal
SRB2, B3D5, D6Specification Rating Sheet5100Presale / External
TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / External
TGB2, B3D6Troubleshooting Guide15Post / External
UMB2 Primary, B4D6User Manual B/W15Post / External
WDB3D5Wiring Diagrams / Dwgs15Post / Internal
WPB3 Primary, B5D5White Paper550Presale / External
Pre-sale / MarketingAll paper in this category is White Brightness, 85% or better. Opacity 87% or better
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements
A14 color170gsm 2pp100# gloss cover, 100# gloss text
A24 color170gsm, folded, 4pp100# gloss cover, 80# gloss text
A34 colorCover 170gsm with Body 120gsm, > 4pp80# gloss cover, 80# gloss text
A42 color80# gloss cover, 80# gloss text
170gsm Silk 120gsm Silk
A52 color80# gloss cover, 80# matt sheet text
170gsm Silk 120gsm Silk
A61 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet text
A74 color cover10 Point Cover C2S
2 color textCategory being deleted50# matte sheet text
Selection Guide
A84 color coverCategory being deleted50# matte sheet text, self cover
2 color text
Selection Guide
A92 color100gsm bond50# matte sheet text, self cover
Selection Guide
Post Sale / Technical Communication
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements
B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S
2 color text50# matte sheet text
B21 color60# Cover
160gsm Colortech & 100gsm Bond50# matte sheet text
B31 color50# matte sheet text, self cover
100gsm bond
B42 color60# Cover
160gsm Colortech & 100gsm Bond50# matte sheet text
B52 color50# matte sheet text, self cover
100gsm bond
Catalogs
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements
C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S
4 color text45# Coated Sheet
C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S
2 color text32#-33# Coated Sheet
JIT / POD
CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements
D14 color170gsm white silk80# gloss cover, coated 2 sides
D24 color120gsm white silk80# gloss text, coated 2 sides, self cover
D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides
D41 color160gsm tab90# index
D51 color80gsm bond20# bond, self cover
D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond
D72 color160gsm tab90# index
D82 color80gsm bond20# bond, self cover
D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond
D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond
Print Spec Sheet
JIT Printing SpecificationsRA-QR005E-EN-P - 5/19/2009
Printing SpecificationYOUR DATA HEREInstructionsNO
(required) Category:D5Select Print Category A,B,C or D from category list, on "Introduction_Catagory Types" tab11 x 17LOOSE -Loose LeafYESPre-sale / MarketingTOP
(required) Finished Trim Size Width:4.75 x 7 (slightly smaller half-size)8.5 x 11PERFECT - Perfect BoundA1LEFT
(required) Publication Number :1768-IN007B-EN-PSample: 2030-SP001B-EN-P3 x 5SADDLE - Saddle StitchA2RIGHTCORNER
Use Legacy NumberNOYES or NO18 x 24 PosterPLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE
Legacy Number if applicable:Sample Legacy Number: 0160-5.3324 x 36 PosterSTAPLED1 -1 positionA3
Publication Title:CompactLogix EtherNet/IP Web Server Module Installation InstructionsSample: ElectroGuard Selling Brief36 x 24 PosterSTAPLED1B - bottom 1 positionA5
(required) Business Group:Marketing CommercialAs entered in DocMan4 x 6STAPLED2 - 2 positionsA6
(required) Cost Center:CMKMKE CM Integrated Arch - 19021As entered in DocMan - enter number only, no description. Example - 19021CMKMKE CM Integrated Arch - 19021CMKMKE Market Access Program - 191054.75 x 7 (slightly smaller half-size)THERMAL - Thermal bound (Tape bound)A7
Binding/Stitching:SADDLE - Saddle StitchReview key on right...Saddle-Stitch Items All page quantities must be divisible by 4.20 sheets max. on 20# (text and cover); 20 sheets = 80-page pub16 sheets max. on 20# (text) and 90# (cover); 16 sheets = 64-page pub
Perfect Bound Items475 sheets max. on 20# no cover; 475 sheets = 950-page pub470 sheets max. w/cover / 90# index unless indicated otherwise); 470 sheets = 940-page pub
Coil Bound Items400 sheets max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 400 sheets = 800-page pub
Tape Bound Items125 sheets max. on 20# no cover; 125 sheets = 250-page pub120 sheets max. w/cover (90# index unless indicated otherwise); 120 sheets = 240-page pub
Double Wire Bound Items250 sheets max. on 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise); 250 sheets = 500-page pub4.75 x 7.75THERMALO - Thermal Bound (Tape bound - offline)A8
(required) Page Count of Publication:24Total page count including cover5.5 x 8.5 (half-size)Wire O - Double Wire Bound (offline)A9
Paper Stock Color:White is assumed. For color options contact your vendor.6 x 4Post Sale / Technical Communication
Number of Tabs Needed:5 tab in stock at RR Donnelley7.385 x 9 (RSI Std)B1
Stitching Location:Blank, Corner or Side8.25 x 10.875B2
Drill Hole YES/NOYESAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of inch from the inner page border.8.25 x 11 (RA product profile std)B3
Glue Location on Pad:Glue location on pads8.375 x 10.875B4
Number of Pages per Pad:Average sheets of paper.. 25, 50 75,100 Max9 x 12 (Folder)B5