Compact 5000 I/O Digital 16-point Sourcing Output Modules ... · Installation Instructions Original...

16
Installation Instructions Original Instructions Compact 5000 I/O Digital 16-point Sourcing Output Modules Catalog Numbers 5069-OB16, 5069-OB16F The 5069-OB16 and 5069-OB16F digital 16-point sourcing output modules drive output devices. The data sent to the modules from a controller and some input modules determines the 5069-OB16 and 5069-OB16F module behavior. You can use time-scheduled output control on the 5069-OB16F output modules. Compact 5000 I/O™ modules use the Producer/Consumer communication model. The Producer/Consumer communication model is an intelligent data exchange between module and other system devices in which each module produces data without first being polled. For more information on how to use Compact 5000 I/O modules, see the publications that are listed in A dd it io n a l R esou r c es o n p a g e 13. Summary of Changes Topic Page Module Overview 5 Install a System 5 Install the Removable Terminal Block 7 Install the Module 7 Install the End Cap 8 Wire the Removable Terminal Block 9 Disconnect Wires from the Removable Terminal Block 9 Wiring Diagram 10 Use a Cable Tie 11 Power the System 11 Remove the Module 11 Specifications 12 Additional Resources 13 Topic Page(s) Updated graphics to show lower hook at the bottom of the module 5, 6 Updated module height dimension 6 Added information about how to install an end cap 8 Added information to the wiring diagram 10 Added description about how to use a cable tie with the module 11 Updated content in the specifications 12

Transcript of Compact 5000 I/O Digital 16-point Sourcing Output Modules ... · Installation Instructions Original...

Installation Instructions

Original Instructions

Compact 5000 I/O Digital 16-point Sourcing Output ModulesCatalog Numbers 5069-OB16, 5069-OB16F

The 5069-OB16 and 5069-OB16F digital 16-point sourcing output modules drive output devices. The data sent to the modules from a controller and some input modules determines the 5069-OB16 and 5069-OB16F module behavior. You can use time-scheduled output control on the 5069-OB16F output modules.

Compact 5000 I/O modules use the Producer/Consumer communication model. The Producer/Consumer communication model is an intelligent data exchange between module and other system devices in which each module produces data without first being polled.

For more information on how to use Compact 5000 I/O modules, see the publications that are listed in Additional Resources on page 13.

Summary of Changes

Topic Page

Module Overview 5

Install a System 5

Install the Removable Terminal Block 7

Install the Module 7

Install the End Cap 8

Wire the Removable Terminal Block 9

Disconnect Wires from the Removable Terminal Block 9

Wiring Diagram 10

Use a Cable Tie 11

Power the System 11

Remove the Module 11

Specifications 12

Additional Resources 13

Topic Page(s)

Updated graphics to show lower hook at the bottom of the module 5, 6

Updated module height dimension 6

Added information about how to install an end cap 8

Added information to the wiring diagram 10

Added description about how to use a cable tie with the module 11

Updated content in the specifications 12

COMPACT 5000 Digital 16-point Sourcing Output Modules

ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

ATENCIN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la seccin Recursos adicionales acerca de la instalacin, configuracin y operacin de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalacin y cableado y con los requisitos de todos los cdigos, leyes y estndares vigentes.El personal debidamente capacitado debe realizar las actividades relacionadas a la instalacin, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el cdigo de prctica aplicable.Si este equipo se usa de una manera no especificada por el fabricante, la proteccin provista por el equipo puede resultar afectada.ATENO: Leia este e os demais documentos sobre instalao, configurao e operao do equipamento que esto na seo Recursos adicionais antes de instalar, configurar, operar ou manter este produto. Os usurios devem se familiarizar com as instrues de instalao e fiao alm das especificaes para todos os cdigos, leis e normas aplicveis. necessrio que as atividades, incluindo instalao, ajustes, colocao em servio, utilizao, montagem, desmontagem e manuteno sejam realizadas por pessoal qualificado e especializado, de acordo com o cdigo de prtica aplicvel. Caso este equipamento seja utilizado de maneira no estabelecida pelo fabricante, a proteo fornecida pelo equipamento pode ficar prejudicada.: , , , , . , . , , . , , , , , , , . , .

ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt Weitere Informationenaufgefhrten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten, bevor Sie dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender mssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zustzlich mit den Installations- und Verdrahtungsanweisungen vertraut machen.Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung drfen nur durch ausreichend geschulte Mitarbeiter und in bereinstimmung mit den anwendbaren Ausfhrungsvorschriften vorgenommen werden.Wenn das Gert in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeintrchtigt sein.ATTENTION : Lisez ce document et les documents lists dans la section Ressources complmentaires relatifs linstallation, la configuration et le fonctionnement de cet quipement avant dinstaller, configurer, utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions dinstallation et de cblage en plus des exigences relatives aux codes, lois et normes en vigueur.Les activits relatives linstallation, le rglage, la mise en service, lutilisation, lassemblage, le dmontage et lentretien doivent tre ralises par des personnes formes selon le code de pratique en vigueur.Si cet quipement est utilis dune faon qui na pas t dfinie par le fabricant, la protection fournie par lquipement peut tre compromise.

ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione Altre risorse, riguardanti linstallazione, la configurazione ed il funzionamento dellapparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi, codici e standard applicabili.Le attivit come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.Qualora lapparecchio venga utilizzato con modalit diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.DKKAT: Bu rnn kurulumu, yaplandrlmas, iletilmesi veya bakm ncesinde bu dokman ve bu ekipmann kurulumu, yaplandrlmas ve iletimi ile ilgili lave Kaynaklar blmnde yer listelenmi dokmanlar okuyun. Kullanclar yrrlkteki tm ynetmelikler, yasalar ve standartlarn gereksinimlerine ek olarak kurulum ve kablolama talimatlarn da renmek zorundadr.Kurulum, ayarlama, hizmete alma, kullanma, paralar birletirme, paralar skme ve bakm gibi aktiviteler sadece uygun eitimleri alm kiiler tarafndan yrrlkteki uygulama ynetmeliklerine uygun ekilde yaplabilir.Bu ekipman retici tarafndan belirlenmi amacn dnda kullanlrsa, ekipman tarafndan salanan koruma bozulabilir.

POZOR: Ne zanete instalovat, konfigurovat i provozovat tento vrobek nebo provdt jeho drbu, pette si tento dokument a dokumenty uveden v sti Dodaten zdroje ohledn instalace, konfigurace a provozu tohoto zazen. Uivatel se musej vedle poadavk vech relevantnch vyhlek, zkon a norem nutn seznmit tak s pokyny pro instalaci a elektrick zapojen.innosti zahrnujc instalaci, nastaven, uveden do provozu, uvn, mont, demont a drbu mus vykonvat vhodn prokolen personl v souladu s pslunmi provdcmi pedpisy.Pokud se toto zazen pouv zpsobem neodpovdajcm specifikaci vrobce, me bt naruena ochrana, kterou toto zazen poskytuje.UWAGA: Przed instalacj, konfiguracj, uytkowaniem lub konserwacj tego produktu naley przeczyta niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe rda omawiajce instalacj, konfiguracj i procedury uytkowania tego urzdzenia. Uytkownicy maj obowizek zapozna si z instrukcjami dotyczcymi instalacji oraz oprzewodowania, jak rwnie z obowizujcymi kodeksami, prawem i normami.Dziaania obejmujce instalacj, regulacj, przekazanie do uytkowania, uytkowanie, monta, demonta oraz konserwacj musz by wykonywane przez odpowiednio przeszkolony personel zgodnie z obowizujcym kodeksem postpowania.Jeli urzdzenie jest uytkowane w sposb inny ni okrelony przez producenta, zabezpieczenie zapewniane przez urzdzenie moe zosta ograniczone.OBS! Ls detta dokument samt dokumentet, som str listat i avsnittet vriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller brjar anvnda eller utfra underhllsarbete p produkten. Anvndare mste bekanta sig med instruktioner fr installation och kabeldragning, frutom krav enligt gllande koder, lagar och standarder.tgrder som installation, justering, service, anvndning, montering, demontering och underhllsarbete mste utfras av personal med lmplig utbildning enligt lmpligt bruk.Om denna utrustning anvnds p ett stt som inte anges av tillverkaren kan det hnda att utrustningens skyddsanordningar frstts ur funktion.LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert, configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen.Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in overeenstemming met de geldende praktijkregels.Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.

2 Rockwell Automation Publication 5069-IN007B-EN-P - November 2017

COMPACT 5000 Digital 16-point Sourcing Output Modules

Waste Electrical and Electronic Equipment (WEEE)

At the end of its life, this equipment should be collected separately from any unsorted municipal waste.

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.

This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.

In addition to this publication, see the following: Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more installation requirements. NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations.

Informations sur lutilisation de cet quipement en environnements dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne conviennent qu' une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livr avec des marquages sur sa plaque d'identification qui indiquent le code de temprature pour les environnements dangereux. Lorsque plusieurs produits sont combins dans un systme, le code de temprature le plus dfavorable (code de temprature le plus faible) peut tre utilis pour dterminer le code de temprature global du systme. Les combinaisons d'quipements dans le systme sont sujettes inspection par les autorits locales qualifies au moment de l'installation.

WARNING:Explosion Hazard Do not disconnect equipment unless power has been removed

or the area is known to be nonhazardous. Do not disconnect connections to this equipment unless power

has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

Substitution of components may impair suitability for Class I, Division 2.

If this product contains batteries, they must only be changed in an area known to be nonhazardous.

AVERTISSEMENT:Risque dExplosion Couper le courant ou s'assurer que l'environnement est class non

dangereux avant de dbrancher l'quipement. Couper le courant ou s'assurer que l'environnement est class non

dangereux avant de dbrancher les connecteurs. Fixer tous les connecteurs externes relis cet quipement l'aide de vis, loquets coulissants, connecteurs filets ou autres moyens fournis avec ce produit.

La substitution de composants peut rendre cet quipement inadapt une utilisation en environnement de Classe I, Division 2.

S'assurer que l'environnement est class non dangereux avant de changer les piles.

European Hazardous Location Approval

The following applies to products marked , . Such modules: Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive

94/9/EC. See the EC Declaration of Conformity at http://www.rockwellautomation.com/products/certification for details. The type of protection is "Ex nA IIC T4 Gc" according to EN 60079-15. The 5069-OB16 and 5069-OB16F modules comply to standards: EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate number DEMKO 15 ATEX 1484X . Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations

correspond to Zone 2 classification according to ATEX directive 1999/92/EC.

Rockwell Automation Publication 5069-IN007B-EN-P - November 2017 3

http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://www.rockwellautomation.com/products/certification

COMPACT 5000 Digital 16-point Sourcing Output Modules

IEC Hazardous Location Approval

The following applies to products with IECEx certification: Such modules: Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations

correspond to Zone 2 classification to IEC 60079-0. The type of protection is "Ex nA IIC T4 Gc" according to IEC 60079-15. The 5069-OB16 and 5069-OB16F modules comply to standards IEC 60079-0:6th Edition, IEC-60079-15:4th Edition, reference IECEx certificate number IECEx UL 15.0055X.

Special Conditions for Safe Use

WARNING: This equipment is not resistant to sunlight or other sources of UV radiation. This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in

EN/IEC 60529) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The enclosure must be accessible only by the use of a tool.

This equipment shall be used within its specified ratings defined by Rockwell Automation. Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the rated voltage when applied in

Zone 2 environments. The instructions in the user manual shall be observed. This equipment must be used only with ATEX/IECEx certified Rockwell Automation backplanes. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this

product. Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. Earthing is accomplished through mounting of modules on rail. Devices shall be used in an environment of not more than Pollution Degree 2.

Prevent Electrostatic Discharge

ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. Use a static-safe workstation, if available. Store the equipment in appropriate static-safe packaging when not in use.

Electrical Safety Considerations

ATTENTION: Do not wire more than 1 conductor on any single RTB terminal. In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle

the module. This equipment is certified for use only within the surrounding air temperature range of 060 C (32140 F) The equipment must not be used outside of

this range. Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.

IMPORTANT Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for the purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability for actual use based upon the examples shown in this publication.

4 Rockwell Automation Publication 5069-IN007B-EN-P - November 2017

COMPACT 5000 Digital 16-point Sourcing Output Modules

Module Overview Install a SystemBased on your application design, you must install a CompactLogix 5380 controller or a Compact 5000 I/O EtherNet/IP adapter before you can install the module.

For more information on how to install these components, see Additional Resources on page 13.

Required ComponentsTo install the module, you need these components.

DC OUTPUT

5069-OB16

Module Status Indicator

I/O Status Indicator

Top Interlocking Piece

Bottom Interlocking Piece

DIN Rail Latch

RTB Handle

RTB

MOD Power Bus and SA Power Bus Connectors (isolated from each other internally)

RTB Lower Tab

Lower hook for use with cable tie.

Component Description

Removable terminal blocks

One of the following RTB types. 5069-RTB18-SPRING RTB 5069-RTB18-SCREW RTBIMPORTANT: You must order RTBs separately. RTBs do not ship with Compact 5000 I/O modules. We recommend that you order only the RTB type that your system requires.

End cap An end cap ships with the CompactLogix 5380 controller and the Compact 5000 I/O EtherNet/IP adapters.

Tools

The following tools are needed: Screwdriver Wire stripper WiresFor more information on available wire sizes and wire insulation stripping length, see Specifications on page 12.

Rockwell Automation Publication 5069-IN007B-EN-P - November 2017 5

COMPACT 5000 Digital 16-point Sourcing Output Modules

Dimensions Ground ConsiderationsYou must ground DIN rails according to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

You can use the EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail with Compact 5000 I/O modules.

System Power ConsiderationsA CompactLogix 5380 controller or Compact 5000 I/O EtherNet/IP adapter provides power to the module.

The following power types are available:

Module (MOD) power - System-side power that is required to operate the Compact 5000 I/O modules. MOD power is provided through the MOD power RTB and passed across the MOD power bus.

Sensor/Actuator (SA) power - Field-side power that is used to power field-side devices. SA power is provided through the SA power RTB and passed across the SA power bus.

The first component in the system, that is, the controller or the adapter, establishes an SA power bus.

A system can have more than one SA power bus. You use 5069-FPD field potential distributors to establish a new SA power bus. SA power buses are isolated from each other.

If a system includes Compact 5000 I/O modules that use AC SA power and modules that use DC SA power, you must install them on separate SA power buses.

DC OUTPUT

5069-OB16

IMPORTANT: The module dimensions for the 5069-OB16F output module are the same as what is shown in these graphics.

109.09 mm (4.29 in.)

25.56 mm (1.01 in.)

144.57 mm (5.69 in.)

105.42 mm (4.15 in.)

22 mm (0.87 in.)ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. Refer to Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1 for more information.

6 Rockwell Automation Publication 5069-IN007B-EN-P - November 2017

http://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdf

COMPACT 5000 Digital 16-point Sourcing Output Modules

To keep the modules on separate SA power buses, complete the following steps.

a. Install the modules that use one type of SA power, for example AC, to the right of the adapter or controller, that is, the first SA power bus.

b. Install the 5069-FPD field potential distributor to establish a second SA power bus.

c. Install the modules that use the other type of SA power, for example DC, on the second SA power bus.

Rather than draw current from the SA power bus to power field-side devices, the 5069-OB16 and 5069-OB16F output modules use Local Actuator (LA) power to power field-side devices. You connect an external power supply to terminals 16 and 17, as shown on page 10, to provide LA power to the modules. You must limit LA power to 10 A, max, at 1032V DC.

Install the Removable Terminal Block

1. Hook the bottom of the RTB on the module.

2. Push the RTB against the module until the RTB clicks into place.

3. Push the RTB handle against the RTB until you hear another click.

Install the Module

Install the I/O module next to the right-most device in the system. To install the module, complete these steps.

1. Confirm that MOD power and all sources of SA and LA power are off.

If you remove the module with power applied, the system MOD power bus and SA power bus are affected. For example, you can interrupt MOD power to the other modules in the system. Unintended consequences can occur as a result.

IMPORTANT We recommend that you use separate external power supplies for MOD power and SA power respectively. This practice helps to prevent unintended consequences that can result if you use one supply.

If you use separate external power supplies, the loss of power from one external power supply does not affect the availability of power from the other supply. For example, if separate external power supplies are used and SA power is lost, MOD power remains available for the Compact 5000 I/O modules.

WARNING: If you connect or disconnect the removable terminal block (RTB) with power applied, an electric arc can occur. This could cause an explosion in hazardous location installations.

The removable terminal block (RTB) does not support "Removal and Insertion Under Power" (RIUP) capability. Do not connect or disconnect the removable terminal block (RTB) while power is applied. Be sure that power is removed before proceeding.

WARNING: If you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations.

The module does not support "Removal and Insertion Under Power" (RIUP) capability. Do not connect or disconnect the module while power is applied. Be sure that power is removed before proceeding.

Rockwell Automation Publication 5069-IN007B-EN-P - November 2017 7

COMPACT 5000 Digital 16-point Sourcing Output Modules

2. If an end cap is installed on the right-most module that is installed in the system, remove it and keep for later use.

3. Confirm that the DIN rail latch is closed.

4. If the DIN rail latches are open, gently push the rear latch back until the front latch pops up and clicks.

5. Align the interlocking pieces of the module with the device on the left.

The top interlocking pieces engage first.

6. Push the module toward the DIN rail until a click indicates that the module is locked in place.

7. Verify that the module is installed in one of the following ways: If the module is installed next to a controller or adapter, the

front of the module is set back slightly from the front of the controller or adapter.

If the module is installed next to another I/O module, the fronts of both modules are flush with each other.

Install the End CapYou must install an end cap on the last module in your system.

1. Align the end cap with the interlocking pieces on the module.

2. Push the end cap toward the DIN rail until it locks in place.

ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last module on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.

Open PositionClosed Position

ADAPTER

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

Top Interlocking Pieces

Bottom Interlocking Piece

IMPORTANT You install the end cap after the last module is installed on the DIN rail. This design helps to prevent the end cap from going beyond the locked position.

If you push the end cap beyond the locked position or insert it from the backwards direction, you can damage the MOD power bus and SA power bus connector.

ADAPTER

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

ADAPTER

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

Interlocking Pieces

End Cap

End Cap

8 Rockwell Automation Publication 5069-IN007B-EN-P - November 2017

COMPACT 5000 Digital 16-point Sourcing Output Modules

Wire the Removable Terminal Block

1. Confirm that MOD power and all sources of SA and LA power are turned off.

2. Strip insulation from the wires that you connect to the RTB.

3. Connect the wire to the terminal.

Disconnect Wires from the Removable Terminal Block

Disconnect wires from the RTB.

WARNING: If you connect or disconnect wiring while power is applied, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

RTB Type Action

Screw Strip12 mm (0.47 in.) of insulation from the wires.

Spring Strip 10 mm (0.39 in.) of insulation from the wires.

RTB Type Action

Screw1. Insert the wire into the terminal.2. Turn the screwdriver to close the terminal on the wire. Torque the

screw to 0.4 Nm (3.5 lbin).

Spring Push the wire into the terminal. If the wire is too thin, crimp a wire ferrule on the wire and insert it.

5069-RTB18-SPRING RTB5069-RTB18-SCREW RTB

WARNING: If you connect or disconnect wiring while power is applied, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

RTB Type Action

Screw 1. Turn the screwdriver counter-clockwise to open the terminal.2. Remove the wire.

Spring1. Insert and hold a screwdriver in the right-side terminal.2. Remove the wire.3. Pull out the screwdriver.

5069-RTB18-SCREW RTB

5069-RTB18-SPRING RTB

Rockwell Automation Publication 5069-IN007B-EN-P - November 2017 9

COMPACT 5000 Digital 16-point Sourcing Output Modules

Wiring DiagramThe following is an example wiring diagram.The example applies to the 5069-OB16 and 5069-OB16F digital output modules.

DC OUTPUT

5069-OB16

Output Channel 0 (O00)

Output Channel 1 (O01)

Output Channel 2 (O02)

Output Channel 3 (O03)

Output Channel 4 (O04)

Output Channel 5 (O05)

Output Channel 6 (O06)

Output Channel 7 (O07)

Output Channel 8 (O08)

Output Channel 9 (O09)

Output Channel 10 (O10)

Output Channel 11 (O11)

Output Channel 12 (O12)

Output Channel 13 (O13)

Output Channel 14 (O14)

Output Channel 15 (O15)

LA+

LA-

LA-

IMPORTANT: The Local Actuator (LA+ and LA-) connections are used to supply field-side power to the module.

The module does not draw current from the SA power bus that is internal to the system.

24V DC+

Channel ConnectionsThe diagram shows devices that are connected to channels 0, 2, 4, and 6. You are not restricted to using only those channels.

You can connect devices to any channel or combination of channels as needed.

10 Rockwell Automation Publication 5069-IN007B-EN-P - November 2017

COMPACT 5000 Digital 16-point Sourcing Output Modules

Use a Cable TieAfter you connect the required wires to the RTB, you can use a cable tie to bundle the wires. There is a lower hook at the bottom of the module that you use to secure the tied bundle to the module.

1. Make sure that you have a cable tie long enough to contain the wires that are connected to the module.

The maximum width of the cable tie is 4.5 mm (0.18 in).

2. Gather the wires at the bottom of the module.

3. Thread the cable tie through the lower hook at the bottom of the RTB..

4. Wrap the cable tie around the wires and secure it.

Power the SystemAfter you install all Compact 5000 I/O modules, you can turn on MOD power and, if used, SA power to the system.

For more information on MOD power and SA power, see System Power Considerations on page 6.

Remove the Module

1. Confirm that MOD power and all sources of SA and LA power are turned off.

2. If necessary, remove the end cap from the right side of the module.

3. If desired, disconnect wires from the RTB as described on page 9.

4. Press the DIN rail latch down until it clicks and let go of the latch.

5. Pull the module off the DIN rail.

6. To replace the module, follow the steps that are described beginning at Install the Module on page 7.

ATTENTION: Do not remove or replace the module while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.

IMPORTANT Before you remove MOD power and, if used, SA power, consider the effect on your system.

When you remove MOD power from the controller or adapter, you shut down power to all modules in the system. That is, all system-side is removed. When you remove SA power from the controller, adapter or a field potential distributor, all field-side power that is provided by that component is removed.

We strongly recommend that you take the appropriate actions to help prevent unintended consequences that can result from a system power shutdown before removing MOD power or SA power.

ADAPTER

AENTR

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

ADAPTER

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

Rockwell Automation Publication 5069-IN007B-EN-P - November 2017 11

COMPACT 5000 Digital 16-point Sourcing Output Modules

SpecificationsThis table lists a subset of the module specifications. For a list of all specifications, see the Compact 5000 I/O Modules and EtherNet/IP Adapters Technical Data, publication 5069-TD001.

Attribute 5069-OB16 and 5069-OB16F

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

060 C (32140 F)

Temperature, surrounding air, max 60 C (140 F)

Enclosure type rating None (open-style)

Voltage and current ratings

Output ratings 0.5 A resistive per channel @ 1032V DC

MOD Power 75 mA @ 1832V DC

MOD Power Passthrough(1) 9.55 A @ 1832V DC

LA Power 0.5 A per channel @ 1032V DC8 A per module @ 1032V DC

SA Power Passthrough(2) 9.95 A @ 1032V DC

Do not exceed 10A MOD or SA Power (Passthrough) current draw

Isolation voltage300V (continuous), Basic Insulation TypeNo isolation between LA power and output portsNo isolation between individual output ports

Wire size

5069-RTB18-SCREW connections 0.51.5 mm2 (2216 AWG) solid or stranded shielded copper wire rated at 105 C (221 F), or greater,

3.5 mm (0.14 in.) max diameter including insulation, single wire connection only.

5069-RTB18-SPRING connections 0.51.5 mm2 (2216 AWG) solid or stranded shielded copper wire rated at 105 C (221 F), or greater,

2.9 mm (0.11 in.) max diameter including insulation, single wire connection only.

Insulation stripping length

5069-RTB18-SCREW connections 12 mm (0.47 in.)

5069-RTB18-SPRING connections 10 mm (0.39 in.)

RTB torque specifications (5069-RTB18-SCREW RTB only) 0.4 Nm (3.5 lbin)

Pilot Duty Rating 0.5 A pilot duty rating per channel @ 1032V DC

North American Temp Code T4

ATEX Temp Code T4

IECEx Temp Code T4

(1) Maximum level of MOD Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.

(2) Maximum level of SA Power current that the module can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.

12 Rockwell Automation Publication 5069-IN007B-EN-P - November 2017

http://literature.rockwellautomation.com/idc/groups/literature/documents/td/5069-td001_-en-p.pdf

COMPACT 5000 Digital 16-point Sourcing Output Modules

Additional Resources

You can view or download publications at http://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative

Resource Description

Compact 5000 I/O Modules and EtherNet/IP Adapters Technical Data, publication 5069-TD001 Provides specifications for Compact 5000 I/O modules and EtherNet/IP adapters.

Compact 5000 I/O Digital Modules in Logix 5000 Control Systems User Manual, publication 5000-UM004 Describes how to use the Compact 5000 I/O digital modules.

EtherNet/IP Communication Modules in Logix 5000 Control Systems User Manual, publication ENET-UM004 Describes how to use Compact 5000 I/O EtherNet/IP adapters.

CompactLogix 5380 Controllers User Manual, publication 5069-UM001 Describes how to use CompactLogix 5380 controllers.

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, http://www.rockwellautomation.com/global/certification/overview.page Provides declarations of conformity, certificates, and other certification details.

Rockwell Automation Publication 5069-IN007B-EN-P - November 2017 13

http://literature.rockwellautomation.com/idc/groups/literature/documents/td/5069-td001_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/um/5000-um004_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/um/enet-um004_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/um/5069-um001_-en-p.pdfhttp://literature.rockwellautomation.com/idc/groups/literature/documents/in/1770-in041_-en-p.pdfhttp://www.rockwellautomation.com/global/certification/overview.pagehttp://www.rockwellautomation.com/global/certification/overview.pagehttp://www.rockwellautomation.com/global/literature-library/overview.page

COMPACT 5000 Digital 16-point Sourcing Output Modules

Notes:

14 Rockwell Automation Publication 5069-IN007B-EN-P - November 2017

COMPACT 5000 Digital 16-point Sourcing Output Modules

Notes:

Rockwell Automation Publication 5069-IN007B-EN-P - November 2017 15

Rockwell Automation SupportUse the following resources to access support information.

Documentation FeedbackYour comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.

Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates. https://rockwellautomation.custhelp.com/

Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page

Direct Dial Codes Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page

Literature Library Installation Instructions, Manuals, Brochures, and Technical Data. http://www.rockwellautomation.com/global/literature-library/overview.page

Product Compatibility and Download Center (PCDC)

Get help determining how products interact, check features and capabilities, and find associated firmware. http://www.rockwellautomation.com/global/support/pcdc.page

Allen-Bradley, Compact 5000, CompactLogix, Rockwell Automation, Rockwell Software, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

Rockwell Automation maintains current product environmental information on its website athttp://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.

Publication 5069-IN007B-EN-P - November 2017 PN-469202Supersedes Publication 5069-IN007A-EN-P -October 2015 Copyright 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page

Compact 5000 I/O Digital 16-point Sourcing Output Modules Installation InstructionsSummary of ChangesModule OverviewInstall a SystemRequired ComponentsDimensionsGround ConsiderationsSystem Power Considerations

Install the Removable Terminal BlockInstall the ModuleInstall the End CapWire the Removable Terminal BlockDisconnect Wires from the Removable Terminal BlockWiring DiagramUse a Cable TiePower the SystemRemove the ModuleSpecificationsAdditional Resources

Back Cover

Introduction_Category Types

This tab summarizes Rockwell Automation Global Sales and Marketing preferred printing standards. It also provides guidance on whether a publication should be released as JIT (print on demand) or if it requires an RFQ for offset printing.Find your publication type in the first section below. Use the assigned Printing Category information to determine the standard print specifications for that document type. The Printing Categories are defined below the Publication Type section. Note there may be slightly different print specifications for the categories, depending on the region (EMEA or Americas).For more information on Global Sales and Marketing Printing Standards, see publication RA-CO004 in DocMan.

Publication Type and Print Category

Publication TypeOff Set Print Category Spec. (See table below)JIT Spec. (See table below)DescriptionOrder Min **Order Max **Life Cycle Usage / Release Option

ADNA - PuttmanNAAdvertisement Reprint ColourNANAPresale / Internal

APA3D2Application Solution or Customer Success Story5100Presale / External

ARNANAArticle/Editorial/BylineNANAPresale / Internal

(press releases should not be checked into DocMan or printed)

ATB3, B4D5Application techniques5100Presale / External

BRA2 Primary, A1NABrochures5100Presale / External

CAC2 Primary, C1NACatalogue150Presale / External

CGNANACatalogue Guide150Presale / External

CLNANACollection550Presale / External

COA5, A6, A9D5Company Confidential InformationNANANA / Confidential

CPE-onlyE-only, D5Competitive Information550NA / Confidential

DCE-onlyE-onlyDiscount SchedulesNANAPresale / Internal

DIA1, A3NADirect Mail5100Presale / Internal

DMNANAProduct Demo550Presale / Internal

DSB3D5Dimensions Sheet15Post / External

DUB3D5Document Update15Post / External

GRB2D6Getting Results15Post / External

INB3 Primary, B2D5, D6Installation instructions15Post / External

LMNANALaunch Materials550Presale / Internal

PCB3D5Packaging Contents

PLE-only primary, B3E-onlyPrice List550Presale / Internal

PMB2D6Programming Manual15Post / External

PPA3D1Profile (Single Product or Service). NOTE: Application Solutions are to be assigned the AP pub type.5100Presale / External

QRB2 primary, B3, B5D5, D6Quick Reference15Post / External

QSB2 primary, B3, B5D5, D6Quick Start15Post / External

RMB2D5, D6Reference Manual15Post / External

RNB3D5Release Notes15Post / External

SGB1 Primary, B4D5, D6Selection Guide Colour550Presale / External

SGB2D5, D6Selection Guide B/W550Presale / External

SPA1, A2, A3, A4NASales Promotion NOTE: Service profiles are to be assigned the PP pub type.5100Presale / Internal

SRB2, B3D5, D6Specification Rating Sheet5100Presale / External

TDB2 Primary B3, B4, B5D5, D6Technical Data550Presale / External

TGB2, B3D6Troubleshooting Guide15Post / External

UMB2 Primary, B4D6User Manual B/W15Post / External

WDB3D5Wiring Diagrams / Dwgs15Post / Internal

WPB3 Primary, B5D5White Paper550Presale / External

** Minimum order quantities on all JIT items are based on the publication length. **

Publication lengthMinimum Order Quantity

77 or more pages1 (no shrink wrap required)

33 to 76 pages25

3 to 32 pages50

1 or 2 pages100

Pre-sale / MarketingAll paper in this category is White Brightness, 90% or better. Opacity 90% or better

CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

A14 color170 gsm 2pp100# gloss cover, 100# gloss text

A24 color170 gsm , folded, 4pp100# gloss cover, 80# gloss text

A34 colorCover 170 gsm with Body 120 gsm, > 4pp80# gloss cover, 80# gloss text

A42 color170gsm Silk 120gsm Silk80# gloss cover, 80# gloss text

A52 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet text

A61 color170gsm Silk 120gsm Silk80# gloss cover, 80# matt sheet text

A74 color cover2 color textSelection GuideCategory being deleted10 Point Cover C2S50# matte sheet text

A84 color coverCategory being deleted50# matte sheet text, self cover

2 color text

Selection Guide

A92 color100gsm bond50# matte sheet text, self cover

Selection Guide

Gray shading indicates Obsolete Print Catagories

Post Sale / Technical Communication

CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

B14 color cover270gsm Gloss 100gsm bond10 Point Cover C2S

2 color text50# matte sheet text

B21 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

B31 color100gsm bond50# matte sheet text, self cover

B42 color160gsm Colortech & 100gsm Bond90# Cover50# matte sheet text

B52 color100gsm bond50# matte sheet text, self cover

Catalogs

CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

C14 color cover270gsm Gloss 90gsm silk10 Point Cover C2S

4 color text45# Coated Sheet

C24 color cover270gsm Gloss 80gsm silk10 Point Cover C2S

2 color text32#-33# Coated Sheet

JIT / PODAll paper in this category is White Brightness, 82% or better. Opacity 88% or better

CategoryColor OptionsAP, EMEA Paper RequirementsCanada, LA, US Paper Requirements

D14 color170gsm white silk80# gloss cover, coated 2 sides

D24 color120gsm white silk80# gloss text, coated 2 sides, self cover

D34 colorCover 170gsm with Body 120gsm80# gloss cover, 80# gloss text coated 2 sides

D41 color160gsm tab90# index

D51 color80gsm bond20# bond, self cover

D61 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

D72 color160gsm tab90# index

D82 color80gsm bond20# bond, self cover

D92 colorCover 160gsm tab with Body 80gsm bond90# index, 20# bond

D10Combination: 4 color cover, with 2 color bodyCover 160gsm with Body 80gsm90# index, 20# bond

Gray shading indicates Obsolete Print Catagories

Just In Time (JIT) or Off Set (OS)?

Use these guidelines to determine if your publication should be JIT (just in time/print on demand) or if it would be more economical to print OS (offset/on a press). OS print jobs require an RFQ (Request For Quote) in US. If your job fits into the Either category, an RFQ is recommended, but not required. In the US, RA Strategic Sourcing will discourage or reject RFQs for jobs that fall within the JIT category. Guidelines differ for black & white and color printing, so be sure to check the correct tables.

Black & White Printing

Color Printing

Color Printing

Print Spec Sheet

JIT Printing SpecificationsRA-QR005J-EN-P - 6/14/2013

Printing SpecificationYOUR DATA HEREInstructionsNO

(required) Publication Number:5069-IN007B-EN-PSample: 2030-SP001B-EN-P11 x 17LOOSE -Loose LeafYESPre-sale / MarketingTOP

Use Legacy Number:YES or NO8.5 x 11PERFECT - Perfect BoundA1LEFT

Legacy Number if applicable:Sample Legacy Number: 0160-5.338.375 x 10.875SADDLE - Saddle StitchA2RIGHTCORNER

Publication Title:Compact 5000 I/O Digital 16-point Sourcing Output ModulesSample: ElectroGuard Selling Brief80 character limit - must match DocMan Title8.25 x 11 (RA product profile std)PLASTCOIL - Plastic Coil (Coil Bound)A4BOTTOMSIDE

Used in Manufacturing:YESYES or NO - If Yes, must have Part No. listed below8.25 x 10.875STAPLED1 -1 positionA3

Part Number:PN-469202If SAP Part Number, be sure to enter PN- before the number7.385 x 9 (RSI Std)STAPLED1B - bottom 1 positionA5

(required) CategoryD5Select Print Category A,B,C or D from category list, on "Introduction_Category Types" tab6 x 4STAPLED2 - 2 positionsA6

Paper Stock Color:White is assumed. For color options contact your vendor5.5 x 8.5 (half-size)THERMAL - Thermal bound (Tape bound)A7

Ink Color:One color assumes BLACK / 4 color assume CMYK / Indicate PMS number here4.75 x 7.75THERMALO - Thermal Bound (Tape bound - offline)A8

(required) Page Count ofPublication:16Total page count including cover. Enter PAGE count, not SHEET count4.75 x 7 (slightly smaller half-size)A9

(required) Finished Trim Size Width:8.5 x 11This is sheet size, before folding4.25" x 5.50"Post Sale / Technical Communication

Fold:SampleReview key below. Leave blank if folded for saddle stitching4 x 6B1

Finished Fold Size:4.25" x 5.5"This is size after folding is completed3 x 5B2

Binding/Stitching:SADDLE - Saddle StitchReview key below9 x 12 (Folder)B3None

Stitching Location:SIDEBlank, Corner or SideA4 (8 x 11 ) (210 x 297 mm)B4Half or V or Single Fold

Drill Hole (Yes/No):NOAll drilled publications use the 5-hole standard, 5/16 inch-size hole and a minimum of inch from the inner page border.A5 (5.83 x 8.26) (148 x 210 mm)B5C or Tri-Fold

Number of Tabs Needed:5 tab in stock at RR Donnelley36 x 24 PosterCatalogsDbleParll

Number of Pages per Pad:Average sheets of paper. 25, 50 75,100 Max24 x 36 PosterC1Sample

Glue Location on Pad:Glue location on pads18 x 24 PosterC2Short (must specify dimensions between folds in Comments)

(required) Business Group:Marketing CommercialAs entered in DocManJIT/PODZ or Accordian Fold

(required) Cost Center:19134 - IAIf your Business Unit is Marketing Commercial, add the appropriate division name after 19134 using the chart on the right. All other Business Units: Enter only the number as in DocMan, no description. Example - 1902119134 - Commerc 19134 - OEM 19134 - Compone 19134 - Power C19134 - Global 19134 - Process 19134 - IA 19134 - Service 19134 - IMC 19134 - Safety 19134 - Industr 19134 - Softwar19134 - Mkt Dig 19134 - US MarkeD1Microfold or French Fold - designate no. of folds in Comments - intended for single sheet only to be put in box for manufacturing

Comments:After the publication is printed, two folds are needed. First, fold the top to the bottom and then fold from the left to the right. After folding, the PN should show on the lower right corner.D2Double Gate

FoldsHalf, V, Single C or Tri

Dble Parll

Z or Accordian Microfold or French

Double Gate

Short FoldSaddle-Stitch Items All page quantities must be divisible by 4.Note: Stitching is implied for Saddle-Stitch -no need to specify in Stitching Location.80 pgs max. on 20# (text and cover)76 pgs max. on 20# (text) and 24# (cover)72 pgs max. on 24# (text and cover)

Perfect Bound Items940 pgs max. w/cover (90# index unless indicated otherwise)70 pgs. min. for spine without words200 pgs min. for spine with words

Plastcoil Bound Items530 pgs max. of 20# (if adding cover deduct equivalent number of pages to equal cover thickness) (90# index unless indicated otherwise)

Tape Bound Items250 pgs max. on 20# no cover240 pgs max. w/cover (90# index unless indicated otherwise)D3

D4

D5

D6

D7

D8

D9

MBD000B020A.bin

MBD000B020C.bin

MBD000B020B.bin

MBD000B0206.bin

MBD000B0208.bin

MBD000B0209.bin

MBD000B0207.bin

MBD000B0204.bin

MBD000B0205.bin

MBD000B0203.bin

/ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

/CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice