Communication manual E94AYCIB INTERBUS MXI moduledownload.lenze.com/TD/E94AYCIB__INTERBUS MXI...
Transcript of Communication manual E94AYCIB INTERBUS MXI moduledownload.lenze.com/TD/E94AYCIB__INTERBUS MXI...
L
Ä.N+øä
1345
1099
INTERBUS
Accessories
Servo Drives 9400 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Communication Manual EN
E94AYCIB
2 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1 About this documentation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 41.1 Document history _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 61.2 Conventions used _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 71.3 Terminology used _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 81.4 Definition of the notes used _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 9
2 Safety instructions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 102.1 General safety and application notes _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 102.2 Device and application-specific safety instructions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 112.3 Residual hazards _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 11
3 Product description _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 123.1 Application as directed _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 123.2 Identification _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 123.3 Product features _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 133.4 Terminals and interfaces _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 14
4 Technical data _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 154.1 General data and operating conditions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 154.2 Protocol data _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 164.3 Communication time _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 164.4 Protective insulation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 174.5 Dimensions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 20
5 Installation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 215.1 Mechanical installation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 22
5.1.1 Assembly _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 225.1.2 Disassembly _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 22
5.2 Electrical installation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 235.2.1 Wiring according to EMC guidelines _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 235.2.2 Wiring of the INTERBUS _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 245.2.3 INTERBUS connection _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 255.2.4 Dimensions of 9-pole sub-D connectors _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 265.2.5 Bus cable specification _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 275.2.6 Bus cable length _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 275.2.7 External voltage supply _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 28
6 Commissioning _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 296.1 Before initial switch-on _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 296.2 Possible settings via DIP switch _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 30
6.2.1 Setting the number of process data words _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 316.2.2 Setting the number of parameter data words _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 326.2.3 Setting the baud rate _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 33
6.3 Settings in »Engineer« _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 346.4 Initial switch-on _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 35
Contents
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 3
Contents
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7 Data transfer _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 36
8 Process data transfer _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 37
9 Parameter data transfer _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 399.1 Addressing of the parameter data _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 399.2 Initialising PCP communication _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 409.3 Supported PMS services _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 41
9.3.1 Initiate _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 419.3.2 Abort _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 419.3.3 Reject _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 419.3.4 Read/Write _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 429.3.5 Get-OD _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 429.3.6 Identify _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 439.3.7 Status _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 44
10 Monitoring _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 4510.1 Interruption of the INTERBUS communication _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 4510.2 Interruption of internal communication _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 46
11 Diagnostics _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 4711.1 LED status displays _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 4711.2 Diagnosing with the »Engineer« _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 48
12 Error messages _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 4912.1 Short overview of the INTERBUS error messages _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 4912.2 Possible causes and remedies _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 50
13 Parameter reference _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 5313.1 Parameters of the standard device that are relevant to communication _ _ _ _ _ _ _ _ _ _ _ _ _ _ 5313.2 Parameters of the communication module for slot MXI1 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 5513.3 Parameters of the communication module for slot MXI2 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 6313.4 Table of attributes _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 71
14 Index _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 74
Your opinion is important to us _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 77
1 About this documentation
4 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1 About this documentation
This documentation exclusively describes the E94AYCIB communication module (INTERBUS).
The features and functions of the communication module are described in detail.
Examples illustrate typical applications.
The theoretical context is only explained as far as it is required for understanding the function ofthe communication module.
This documentation does not describe any software provided by other manufacturers. No warrantycan be given for corresponding data provided in this documentation. For information on how to usethe software, please refer to the host (PLC, master) documents.
All brand names mentioned in this documentation are trademarks of their corresponding owners.
Tip!
More information on the INTERBUS can be found on this internet page:
www.interbus.com
Maintenance activities for the INTERBUS technologies are carried out by the userorganisation PROFIBUS & PROFINET International (PI).
www.profibus.com
Note!
This documentation supplements the mounting instructions supplied with the communication module and the Servo Drives 9400 hardware manual.
The mounting instructions contain safety instructions which must be observed!
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 5
1 About this documentation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Target group
This documentation is intended for all persons who plan, install, commission and maintain thenetworking and remote servicing of a machine.
Tip!
Current documentation and software updates with regard to Lenze products can be foundin the download area at:
www.lenze.com
Information regarding the validity
The information given in this documentation is valid for the following devices:
Screenshots/application examples
All screenshots in this documentation are application examples. Depending on the firmwareversion of the communication module and the software version of the engineering tools installed(e.g. »Engineer«), the screenshots in this documentation may differ from the actual screenrepresentation.
Extension module Type designation From hardware version
From software version
Communication module INTERBUS E94AYCIB PA 01.00
1 About this documentation1.1 Document history
6 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1.1 Document history
Version Description
1.0 03/2009 TD17 Field test version
2.0 06/2009 TD17 General revision
3.0 11/2009 TD17 General revision
4.0 02/2014 TD17 • New layout• General updates
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 7
1 About this documentation1.2 Conventions used
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1.2 Conventions used
This documentation uses the following conventions to distinguish between different types ofinformation:
Type of information Writing Examples/notes
Spelling of numbers
Decimal Normal spelling Example: 1234
Decimal separator Point The decimal point is always used.For example: 1234.56
Hexadecimal 0x[0 ... 9, A ... F] Example: 0x60F4
Binary• Nibble
In inverted commasPoint
Example: ’100’Example: ’0110.0100’
Text
Version information Blue text colour All information that applies to from a certain software version of the device onwards are marked accordingly in this documentation.Example: This function extension is available from software version V3.0 onwards!
Program name » « The Lenze PC software »Engineer«...
Control element bold The OK button ... / The Copy command ... / The Properties tab ... / The Name input field ...
Sequence of menu commands
If several commands are required to execute one function, the single commands are separated by an arrow: Select the File Open command to...
Hyperlink Underlined Optically highlighted reference to another topic. It is activated with a mouse-click in this online documentation.
Icons
Page reference ( 8) Optically highlighted reference to another page. In this online documentation activated via mouse-click.
Step-by-step instructions Step-by-step instructions are indicated by a pictograph.
1 About this documentation1.3 Terminology used
8 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1.3 Terminology used
Term Meaning
Drive Lenze inverter of the "Servo Drives 9400" product series, with which the communication module can be used.Application as directed ( 12)
Inverter
Standard device
Code Parameter which serves to parameterise and monitor the drive. In normal usage, the term is usually referred to as "Index".
Subcode If a code contains several parameters, they are stored in "subcodes".In the documentation, the slash "/" is used as a separator between the code and the subcode (e.g. "C00118/3").In everyday language, the term is also referred to as "subindex".
»Engineer« Lenze PC software which supports you during the "Engineering" process (parameterisation, diagnostics, and configuration) throughout the whole life cycle, i. e. from planning to maintenance of the machine commissioned.
INTERBUS was developed as sensor/actuator bus system for transmitting process data.Maintenance activities for the INTERBUS technologies are carried out by the user organisation PROFIBUS & PROFINET International (PI).
Host PLC, INTERBUS master
PCP Peripherials Communication Protocol for transmitting parameter data
PDO Process data object
PDU Process Data Unit
PMS Peripheral Message Specification
HW Hardware
SW Software
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 9
1 About this documentation1.4 Definition of the notes used
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1.4 Definition of the notes used
The following signal words and symbols are used in this documentation to indicate dangers andimportant information:
Safety instructions
Layout of the safety instructions:
Application notes
Danger!
(characterises the type and severity of danger)
Note
(describes the danger and gives information about how to prevent dangerous situations)
Pictograph Signal word Meaning
Danger! Danger of personal injury through dangerous electrical voltageReference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken.
Danger! Danger of personal injury through a general source of dangerReference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken.
Stop! Danger of property damageReference to a possible danger that may result in property damage if the corresponding measures are not taken.
Pictograph Signal word Meaning
Note! Important note to ensure trouble-free operation
Tip! Useful tip for easy handling
Reference to another document
2 Safety instructions2.1 General safety and application notes
10 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2 Safety instructions
2.1 General safety and application notes
Lenze drive and automation components ...
• must only be used as directed.Application as directed ( 12)
• must never be commissioned if they display signs of damage.
• must never be technically modified.
• must never be commissioned if they are not fully mounted.
• must never be operated without required covers.
• during and after operation can have live, moving and rotating parts, depending on their degree of protection. Surfaces can be hot.
The following applies to Lenze drive components ...
• only use the accessories approved.
• Only use original manufacturer spare parts.
Observe all specifications contained in the enclosed documentation and related documentation.
• This is the precondition for safe and trouble-free operation and for obtaining the product features specified.Product features ( 13)
• The specifications, processes, and circuitry described in this document are for guidance only and must be adapted to your own specific application. Lenze does not take responsibility for the suitability of the process and circuit proposals.
All works on and with Lenze drive and automation components must only be carried out by qualifiedpersonnel. According to IEC 60364 or CENELEC HD 384 these are persons who ...
• are familiar with installing, mounting, commissioning, and operating the product.
• who have the corresponding qualifications for their work.
• who know and can apply all regulations for the prevention of accidents, directives, and laws applicable at the place of use.
Note!
It is absolutely vital that the stated safety measures are implemented in order to prevent serious injury to persons and damage to material assets.
Always keep this documentation to hand in the vicinity of the product during operation.
Danger!
If the following basic safety measures are disregarded, severe injuries to persons and damage to material assets may result.
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 11
2 Safety instructions2.2 Device and application-specific safety instructions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2.2 Device and application-specific safety instructions
• During operation, the communication module must be securely connected to the standard device.
• With external voltage supply, always use a separate power supply unit, safely separated to EN 61800-5-1 in every control cabinet (SELV/PELV).
• Only use cables corresponding to the given specifications.Bus cable specification ( 27)
2.3 Residual hazards
Protection of persons
If Servo Drives 9400 are used on a phase earthed mains with a rated mains voltage 400 V,protection against accidental contact is not guaranteed without external measures.Protective insulation ( 17)
Device protection
The communication module contains electronic components which may be damaged or destroyedby electrostatic discharge.Installation ( 21)
Documentation for the standard device, host (PLC, master), system/machine
All the other measures prescribed in this documentation must also be implemented. Observe the safety instructions and application notes contained in this manual.
3 Product description3.1 Application as directed
12 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3 Product description
3.1 Application as directed
The communication module ...
• is an accessory module that can be used in conjunction with the following standard devices:
• is a device intended for use in industrial power systems.
• should only be used under the operating conditions prescribed in this documentation.
• can only be used in INTERBUS networks.
Any other use shall be deemed inappropriate!
3.2 Identification
The type designation and hardware and software version of the communication module arespecified on the nameplate:
[3-1] Identification data
Product series Type designation From hardware version
From software version
Servo Drives 9400 HighLine E94AxHExxx 1A 03.00
Servo Drives 9400 PLC E94AxPExxxx VA 02.00
Regenerative power supply module E94ARNxxxx VA 01.00
E94YCIB005
1 Type designation (type)
E94 Product series
A Version
Y Module identification: Extension module
C Module type: Communication module
IB INTERBUS
2 Hardware version (HW)
3 Software version (SW)
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 13
3 Product description3.3 Product features
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.3 Product features
• Interface module for the INTERBUS communication system to be connected to the expansion slots of the Servo Drives 9400
• The communication module can either be supplied internally by the standard device or externally by a separate voltage source.
• Slave functionality
• DIP switch settings:• Number of process data words and parameter data words• Baud rate (500 kbps or 2 Mbps)
• Bus coupling via remote bus according to the RS485 standard
• Up to 10 process data words (20 bytes) can be used.
• 0, 1, 2 order 4 parameter data words can be used.
• The parameter data is transmitted in accordance with the Peripherials Communication Protocol (PCP).
• Access to all Lenze parameters
• Support of the PMS services:• Initiate• Abort• Reject• Read• Write• Get-OD• Identify• Status
3 Product description3.4 Terminals and interfaces
14 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.4 Terminals and interfaces
[3-2] E94AYCIB communication module (INTERBUS)
E94YCIB001B
S205 DIP switches for setting the ...• Number of process data words and
parameter data words• Baud ratePossible settings via DIP switch ( 30)
X205 External voltage supply of the communication module
• 2-pin plug connector with spring connection External voltage supply ( 28)
X206 INTERBUS connection, input (IN)• 9-pole Sub-D plugWiring of the INTERBUS ( 24)
X207 INTERBUS connection, output (OUT)• 9-pin Sub-D socketWiring of the INTERBUS ( 24)
MSMEBSBEDE
LED status displays for diagnostic purposesLED status displays ( 47)
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 15
4 Technical data4.1 General data and operating conditions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4 Technical data
4.1 General data and operating conditions
Range Values
Order designation E94AYCIB
Communication profile INTERBUS
Communication medium RS485
Interface for communication • Input (IN): 9-pole Sub-D plug• Output (OUT): 9-pole Sub-D socket
Network topology Ring
Type of node Slave
Number of nodes • 1 master• 512 slaves
Baud rate 500 kbps or 2 Mbps(can be set via DIP switch or code)
Max. cable length • 400 m at 500 kbps• 150 m at 2 Mbps
(between the single INTERBUS nodes)
Process data words 0 ... 10 words (16 bits/word)(can be set via DIP switch or code)
Parameter data words 0, 1, 2, 4 words (16 bits/word)(can be set via DIP switch or code)The parameter data is transmitted in accordance with the Peripherials Communication Protocol (PCP).
Max. number of data words 10 words (process data word + parameter data words), 16 bits/word
Max. PDU length 64 bytes
Device identification (module ID) • 3 = 0x03 (0 parameter data words)• 227 = 0xE3 (1 parameter data words)• 224 = 0xE0 (2 parameter data words)• 225 = 0xE1 (4 parameter data words)
Voltage supply External supply via separate power supply unit+: U = 24 V DC (+/- 10 %), Imax = 180 mA- : Reference potential for external voltage supply
Conformities, approvals • CE• UL
(see also hardware manual)
Servo Drives 9400 hardware manual
Here you can find the ambient conditions and information on the electromagnetic compatibility (EMC) which also apply to the communication module.
4 Technical data4.2 Protocol data
16 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2 Protocol data
4.3 Communication time
The communication time is the time between the start of a request and the arrival of thecorresponding response.
The communication times in an INTERBUS network depend on the ...
• processing time in the inverter;
• telegram runtime (baud rate / telegram length);
• nesting depth of the network.
processing time within the inverter
There are no interdependencies between parameter data and process data.
Range Values
Process data words 0 ... 10 words (16 bits/word)
Parameter data words 0, 1, 2, 4 words (16 bits/word)The parameter data is transmitted in accordance with the Peripherials Communication Protocol (PCP).
Supported PMS services • Initiate• Abort• Reject• Read• Write• Get-OD• Identify• Status
Note!
The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Data Processing time
Process data Approx. 4 ms+ 0 ... 1 ms+ 1 ... x ms
Update cycleProcessing time in the moduleRuntime of the application task of the technology application used (tolerance)
Parameter data Approx. 30 ms + a tolerance of 20 ms (typically)Some codes may require a longer processing time (see reference manual/»Engineer« online help for the Servo Drive 9400).
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 17
4 Technical data4.4 Protective insulation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.4 Protective insulation
Danger!
Dangerous voltage
If the Servo Drives 9400 are operated on a phase earthed mains with a rated mains voltage 400 V, external measures need to be implemented in order to ensure protection against accidental contact.
Possible consequences:
Death or severe injuries
Protective measures:
If protection against accidental contact is required for the control terminals of the inverter and the connections of the plugged device modules, ...• a double isolating distance must exist.• the components to be connected must be provided with the second isolating
distance.
Note!
The protective insulation provided in Servo Drives 9400 is implemented in accordance with EN 61800-5-1.
4 Technical data4.4 Protective insulation
18 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
The following illustration ...
• shows the arrangement of the terminal strips and the separate potential areas of the Servo Drive 9400.
• serves to determine the decisive protective insulation between two terminals located in differently insulated separate potential areas.
[4-1] Protective insulation in accordance with EN61800-5-1
Note!
The INTERBUS input (X206) is isolated from the voltage supply (X205) and the INTERBUS output (X207).
E94YCIB007
Reinforced insulation
Basic insulation
Functional insulation
Ext. DC
I/O
X4
X6X6
X5
X7X7
X8X8
X3
X2X1
X105X105
X106
X100
X107
MXI1
MXI2
Bus
Ext. DC
MSI
MMI
X207
X206
X205
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 19
4 Technical data4.4 Protective insulation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Example
Which type of protective insulation is used between the bus terminal of the device module in slotMXI1 or MXI2 and the mains terminal X100?
The separate potential area with the better protective insulation is decisive.
• The separate potential area of the bus terminal of the device module has a "functional insulation".
• The separate potential area of the mains terminal has a "reinforced insulation".
Result: The insulation between mains terminal X100 and the bus terminal is of the "reinforcedinsulation" type.
Terminal strip Connection Terminal strip Connection
X100 L1, L2, L3 (Single Drive only) X1 CAN on board 9400
+UG, -UG X2 State bus
X105 U, V, W 24 V (ext.)
Rb1, Rb2 (Single Drive only) X3 Analog inputs/outputs
X106 Motor PTC X4 Digital outputs
X107 Control of the motor holding brake
X5 Digital inputs
X6 Diagnostics
X7 Resolver
X8 Encoder
MXI1, MXI2 Extension module
MMI Memory module
MSI Safety module
X205 External voltage supply (24 V DC)
X206 INTERBUS connection, input (IN)
X207 INTERBUS connection, output (OUT)
4 Technical data4.5 Dimensions
20 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.5 Dimensions
[4-2] Dimensions
E94YCXX005
a 89 mm
b 134 mm
b1 87 mm
e 23 mm
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 21
5 Installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5 Installation
Stop!
Electrostatic discharge
Electronic components within the communication module can be damaged or destroyed by electrostatic discharge.
Possible consequences• The communication module is defective.• Fieldbus communication is not possible or faulty.
Protective measures• Before touching the module, be sure that you are free of electrostatic charge.
5 Installation5.1 Mechanical installation
22 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.1 Mechanical installation
5.1.1 Assembly
[5-1] Assembly
5.1.2 Disassembly
[5-2] Disassembly
E94YCXX001G
E94AYCXX001H
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 23
5 Installation5.2 Electrical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2 Electrical installation
5.2.1 Wiring according to EMC guidelines
In typical systems, standard shielding is sufficient for the INTERBUS cable.
In environments with very strong interferences, the EMC compatibility can be improved by anadditional earthing of the cable shield.
For this observe the following notes:
1. The distance of the additional earthing of the INTERBUS plug (Sub-D, 9-pole) depends on the module slot and is as follows ...• approx 10 cm for the upper slot (MXI1);• approx. 20 cm for the lower slot (MXI2).
2. Measure the appropriate distance along the cables and, starting from this point, remove 2 cm of the cable's plastic sheath.
3. Connect the cable shield to the shield sheet of the Servo Drive 9400.
[5-3] Wiring according to EMC guidelines
Documentation for the standard device, host (PLC, master), system/machine
Observe the notes and wiring instructions contained in this documentation.
E94YCXX008
A Connection to the shield sheet of the Servo Drive 9400
B IncomingINTERBUS line at X206 (IN)
C Outgoing INTERBUS line at X207 (OUT)
D Communication module in slot MXI1 of the Servo Drive 9400
5 Installation5.2 Electrical installation
24 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.2 Wiring of the INTERBUS
For communication with the master and all further components, Servo Drives 9400 have to beassembled with communication modules.
The INTERBUS system has to be designed as a ring. Here, go and return lines are integrated in thesame bus cable. The ring comes from the INTERBUS master via all other nodes back again to themaster.
An INTERBUS ring can consist of maximally 513 nodes (1 master + further slaves (slaves)).
[5-4] INTERBUS ring
E94YCIB008
M: Master (e.g. PLC, Industrial PC)S1 ... Sn: Slaves
500 kBit/s: 400 m
2 MBit/s:
�
150 m�
Servo Drive
9400
E94AYCIB
X206 X207
Servo Drive
9400
E94AYCIB
X206 X207
Servo Drive
9400
E94AYCIB
X206 X207
OUTIN OUTIN IN
M
S2S1 Sn
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 25
5 Installation5.2 Electrical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.3 INTERBUS connection
The INTERBUS of the communication module is connected via the 9-pole Sub-D plug X206 (input)and the 9-pole Sub-D socket X207 (output).
[5-5] INTERBUS terminals X206 (input) and X207 (output)
Assignment of the 9-pole Sub-D plug X206 (IN)
E94YCIB001C
Pin Name Input/output Description
1 DO1 Input RS485: DO1 not inverted
2 DI1 Output RS485: DI1 not inverted
3 GND Reference potential
4 Free not assigned
5 Vcc5 Output 5 V DC
6 /DO1 Input RS485: DO1 inverted
7 /DI1 Output RS485: DI1 inverted
8 Vcc5 Output 5 V DC
9 Free not assigned
5 Installation5.2 Electrical installation
26 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Assignment of the 9-pole Sub-D socket X207 (OUT)
5.2.4 Dimensions of 9-pole sub-D connectors
[5-6] Dimensions of 9-pole sub-D connectors
Pin Name Input/output Description
1 DO2 Output RS485: DO2 not inverted
2 DI2 Input RS485: DI2 not inverted
3 GND Reference potential
4 GND
5 Vcc5 Output 5 V DC
6 /DO2 Output RS485: DO2 inverted
7 /DI2 Input RS485: DI2 inverted
8 Vcc5 Output 5 V DC
9 RBST Signalling input Connection to the outgoing INTERBUS is plugged.
Note!
Comply with the dimensions for width and depth of the 9-pole Sub-D connectors for the INTERBUS terminals X206/X207.
E94YCIB001G
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 27
5 Installation5.2 Electrical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.5 Bus cable specification
The nodes at the bus system must be wired with one of the fieldbus cables that complies with theINTERBUS specification.
A manufacturer of INTERBUS cables is e.g. PHOENIX CONTACT (Germany).
Properties of the bus cable according to the INTERBUS specification
5.2.6 Bus cable length
Set the baud rate according to the length of the bus cable between the single INTERBUS nodes:
Possible settings via DIP switch ( 30)
Settings in »Engineer« ( 34)
Note!
A cable which does not fulfil the requirements of the INTERBUS specification must not be used!
General properties
Cable type Sold by the meter(e.g. PHOENIX CONTACT: IBS RBC meter-T, order no. 28 06 28 6)
No. of conductors 3 x 2, twisted in pairs, with joint shielding
Conductor cross-section > 0.2 mm2
DC-cable resistance < 96 /km
Impedance (characteristic) • 120 ± 20 % (f = 64 kHz)• 100 ± 15 (f > 1 MHz)
Capacitance per unit length < 60 nF/km (f = 800 Hz)
Baud rate Cable length between the single INTERBUS nodes
500 kbps max.400 m
2 Mbps max. 150 m
Note!
Select the baud rate which depends on the data volume, cycle time, and number of nodes just high enough to suit your application.
5 Installation5.2 Electrical installation
28 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.7 External voltage supply
The communication module can be externally supplied with voltage via separate supply cables atthe 2-pin plug connector X205.
External voltage supply of the communication module is required if the communication via the busshould be maintained when the supply of the standard device fails.
The parameters of a standard device separated from the mains cannot be accessed.
Assignment of the plug connector X205
Terminal data
Note!
With external voltage supply, always use a separate power supply unit, safely separated to EN 61800-5-1 in every control cabinet (SELV/PELV).
Name Explanation
+ U = 24 V DC (+/- 10 %)I = 180 mA
- Reference potential for external voltage supply
Range Values
Electrical connection 2-pin plug connector with spring connection
Possible connections Rigid:
1.5 mm2 (AWG 16)
Flexible:
Without wire end ferrule1.5 mm2 (AWG 16)
With wire end ferrule, without plastic sleeve1.5 mm2 (AWG 16)
With wire end ferrule, with plastic sleeve1.5 mm2 (AWG 16)
Stripping length 9 mm
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 29
6 Commissioning6.1 Before initial switch-on
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6 Commissioning
During commissioning, system-related data such as motor parameters, operating parameters,responses, and parameters for fieldbus communication are defined in the inverter. For Lenzedevices, this is done by means of codes.
The codes of the inverter and for communication are saved to the memory module in a non-volatiledata set.
In addition, there are codes for diagnosing and monitoring the stations.
Parameter reference ( 53)
6.1 Before initial switch-on
Note!
When parameterising the communication module, please note that the code number depends on the slot of the standard device into which the communication module is plugged.
The first two digits of the code number indicate the slot:• C13nnn for slot MXI1Parameters of the communication module for slot MXI1 ( 55)
• C14nnn for slot MXI2Parameters of the communication module for slot MXI2 ( 63)
You also have to set the Parameters of the standard device that are relevant to communication ( 53).
Stop!
Before switching on the Servo Drive 9400 and the communication module for the first time, check the entire wiring for completeness, short circuit and earth fault.
6 Commissioning6.2 Possible settings via DIP switch
30 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2 Possible settings via DIP switch
[6-1] DIP switch
E94YCIB001D
The following can be set via the S205 DIP switch:
• Number of the process data wordsswitches: 1 ... 4 ( 31)
• Number of the parameter data wordsswitches: 5 and 6 ( 32)
• Baud rateswitch: 8 ( 33)
Lenze setting: All switches "OFF"
Switch 7 has no function.
Note!
• All DIP switches = "OFF" (Lenze setting):At switch-on, the configuration from the codes gets active (Settings in »Engineer« ( 34)).
• At least one DIP switch = "ON":At switch-on, the values are accepted from the switch positions.
• The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
• Switch off the voltage supply of the communication module and afterwards on again to activate changed settings.
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 31
6 Commissioning6.2 Possible settings via DIP switch
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2.1 Setting the number of process data words
• The number of process data words can be set via the switches 1 ... 4.
• 0 ... 10 process data words can be used.
• The current setting is displayed in the »Engineer« in C13860/2 / C14860/2.
Note!
The data word sum (process data word + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Impermissible settings are reported by the BE LED (red blinking).
LED status displays ( 47)
The communication module then operates internally with the following values:• 2 process data words (PD)• 1 parameter data word (PCP)
DIP switch Number of PD
Switch Max. number of PCP
1 2 3 4
0 OFF OFF OFF OFF 4
1 OFF OFF OFF ON
2 OFF OFF ON OFF
3 OFF OFF ON ON
4 OFF ON OFF OFF
5 OFF ON OFF ON
6 OFF ON ON OFF
7 OFF ON ON ON 2
8 ON OFF OFF OFF
9 ON OFF OFF ON 1
10 ON OFF ON OFF 0
12
34
56
78
ONOFF
6 Commissioning6.2 Possible settings via DIP switch
32 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2.2 Setting the number of parameter data words
• The number of parameter data words can be set via the switches 5 and 6.
• 0, 1, 2 order 4 parameter data words can be used.
• The current setting is displayed in the »Engineer« in C13860/1 / C14860/1.
Note!
The data word sum (process data word + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Impermissible settings are reported by the BE LED (red blinking).
LED status displays ( 47)
The communication module then operates internally with the following values:• 2 process data words (PD)• 1 parameter data word (PCP)
DIP switch Number of PCP Switch Max. number of PD
ID code[hex]5 6
0 OFF OFF 10 0x03
1 OFF ON 9 0xE3
2 ON OFF 8 0xE0
4 ON ON 6 0xE1
12
34
56
78
ONOFF
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 33
6 Commissioning6.2 Possible settings via DIP switch
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2.3 Setting the baud rate
• The baud rate can be set via the switch 8.
• Set the baud rate according to the length of the bus cable between the single INTERBUS nodes.
• The current setting is displayed in the »Engineer« in C13863 / C14863.
Note!
Select the baud rate which depends on the data volume, cycle time, and number of nodes just high enough to suit your application.
DIP switch Switch 8 Baud rate Cable length between adjacent nodes
OFF 500 kbps max. 400 m
ON 2 Mbps max. 150 m
12
34
56
78
ONOFF
6 Commissioning6.3 Settings in »Engineer«
34 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Settings in »Engineer«
How to activate changed settings in the »Engineer«:
1. Execute the device command C00002 = "11: Save start parameters".
2. Carry out a "Reset node" of the node, or switch the voltage supply of the communication module off and then on again.
Note!
The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Impermissible settings are reported by the BE LED (red blinking).
LED status displays ( 47)
The communication module then operates internally with the following values:• 2 process data words• 1 parameter data word
Select the baud rate which depends on the data volume, cycle time, and number of nodes just high enough to suit your application.
Setting Description
PCP data length 0, 1, 2 or 4 parameter data words can be used (C13892 / C14892).
Process data length 1 ... 10 process data words can be used (C13893 / C14893).
Clear process data Setting (C13885 / C14885) the selection of the process data the Servo Drive 9400 is to process for maintaining the internal communication when the INTERBUS has exited the "IBS-ACTIVE" state.
• 0: Use of the last master process data• 1: PDOs are set to the value "0". (Standard setting)
Baud rate Set the baud rate (C13894 / C14894) according to the length of the bus cable between the single INTERBUS nodes:
• 500 kbps: Max. 400 m between the single nodes• 2 Mbps: Max. 150 m between the single nodes
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 35
6 Commissioning6.4 Initial switch-on
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4 Initial switch-on
Documentation for the standard device
Observe the safety instructions and information on residual hazards.
Note!
Establishing communication
In order to establish communication via an externally supplied communication module, the standard device must be switched on as well.
For further communication of the externally supplied module it is not relevant whether the standard device is switched on or not.
Protection against uncontrolled restart
After a fault (e.g. short-term mains failure), it is sometimes undesirable or even impermissible for the drive to restart.
In the Lenze setting of Servo Drives 9400, the restart protection is activated.
The restart behaviour of the inverter can be set via C00142 ("auto restart after mains connection"):
C00142 = "0: Inhibited" (Lenze setting)• The inverter remains inhibited (even if the fault is no longer active).• An explicit controller enable causes the drive to start up in a controlled manner: LOW-
HIGH edge at digital input X5/RFR.
C00142 = "1: Enabled"• An uncontrolled restart of the drive is possible.
7 Data transfer
36 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7 Data transfer
The INTERBUS transmits parameter data, configuration data, diagnostic data, alarm messages andprocess data between the host (master) and the inverters (slaves) participating in the fieldbus.Depending on their time-critical nature, the data are transmitted via different communicationchannels.
Communication channels
The process data channel transmits process data.
• The process data serve to control the inverter.
• The transmission of process data is time-critical.
• Process data are cyclically transferred between the host (master) and the inveters connected to the fieldbus (slaves) (continuous exchange of current input and output data).
• The host (master) can directly access the process data. In the PLC, for instance, the data are directly saved to the IO area.
• 0 ... 10 process data words can be used.
• Process data are not saved in the inverter.
• Process data are e.g. setpoints, actual values, control words, and status words.
The parameter data channel serves to transfer parameter data.
• The parameter data channel provides access to all Lenze codes.
• The transmission of parameter data is usually not time-critical.
• Parameter data are, for instance, operating parameters, diagnostic information, and motor data.
• 0, 1, 2 order 4 parameter data words can be used.
• The parameter data is transmitted in accordance with the Peripherials Communication Protocol (PCP).
• The parameter data channel is identical for both transmission directions.
Note!
The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Please observe the direction of the flow of information:• Input data (Rx data): Process data from the inverter (slave) to the master• Output data (Tx data): Process data from the master to the inverter (slave)
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 37
8 Process data transfer
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8 Process data transfer
Configuring process data (PDO mapping)
The Servo Drives 9400 enable the individual mapping of process data. For this purpose, the»Engineer« is provided with a port configurator.
How to set the PDO mapping with the »Engineer«:
1. The process data mapping to the port variables is executed in the »Engineer« under the Process data objects tab of the corresponding fieldbus communication module:
2. Select the receive object PDO_RX0:
Note!
• The port mapping for the Servo Drive 9400 is no configuration that can be carried out online. For this purpose, an update of the »Engineer« project and a subsequent download of the application is always required.
• The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
8 Process data transfer
38 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3. Click the Edit PDO button.
The selection window for editing the process data object is opened:
Here you can transfer the individual ports from the Port Selection list to the receive PDO "PDO_RX0" by clicking the >> button.
The Up and Down buttons serve to shift the sequence of the ports within the PDOs.
4. Confirm the selection with OK.
5. Repeat the steps 2. to 4. for the transmit object PDO_TX0.
6. Then link the ports to application signals in the technology application selected.
The »FB Editor« can be activated in the multiplexer codes (> C03000), if necessary.
If the »FB Editor« is activated, the multiplexer codes (> C03000) are no longer available. In this case, you must carry out the interconnection directly in the »FB Editor«.
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 39
9 Parameter data transfer9.1 Addressing of the parameter data
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9 Parameter data transfer
The parameter data of Lenze devices are contained in codes which are listed in this documentationand the documentation of the Servo Drive 9400.
Parameter reference ( 53)
9.1 Addressing of the parameter data
The parameters of a Lenze device are not directly addressed via codes but via an index and subindex.
The conversion is made via an offset: 24575 or 0x5FFF
• INTERBUS index (decimal) = 24575 - Lenze code number (decimal)
• INTERBUS index (hexadecimal) = 0x5FFF - Lenze code number (hexadecimal)
Example of C00105 (deceleration time quick stop (QSP)):
• INTERBUS index (decimal) = 24575 - 105 = 24470
• INTERBUS index (hexadecimal) = 0x5FFF - 0x69 = 0x5F96
Parameter changes must be saved via code C00002 of the Servo Drive 9400.
9 Parameter data transfer9.2 Initialising PCP communication
40 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2 Initialising PCP communication
Make entries into the CRL (communication relation list) in order that communication between theINTERBUS master and the communication module can take place.
Make the following entries in the CRL of the INTERBUS master:
Field name Entry
Communication reference 2
Connection type Master slave acyclic
Connection attribute Defined
Max-PDU Sending-High-Prio 0
Max-PDU Sending-Low-Prio 64
Max-PDU Receiving-High-Prio 0
Max-PDU Receiving-Low-Prio 64
Supported Services Request 0x803000
Supported Services Response 0x000000
Maximum SCC 1
Maximum RCC 1
Maximum SAC 1
Maximum RAC 1
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 41
9 Parameter data transfer9.3 Supported PMS services
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3 Supported PMS services
The parameter data is transferred via PMS services.
In the following, only parameters and their contents are given that are returned by the Lenzeinverters. All other transfer parameters of the given PMS services can be obtained from thecorresponding descriptions of the INTERBUS master.
The following PMS services are supported by Lenze inverters:
• Initiate: Establish a connection of the INTERBUS master to the inverter
• Abort: Abort connection
• Reject: Reject impermissible PMS service
• Read: Read parameters
• Write: Write parameters
• Get-OD: Read out the object directory
• Identify: Identification of the inverter
• Status: Read the status of the inverter
9.3.1 Initiate
The "Initiate" PMS service establishes a logic connection between the INTERBUS master and thecommunication module.
The inverter provides the following parameters:
9.3.2 Abort
The "Abort" PMS service aborts a logic connection between the INTERBUS master and thecommunication module.
9.3.3 Reject
The "Reject" PMS service rejects a non-supported PMS service.
Name Value Description
Profile number 0 No profile is supported.
Password 0 The password function of INTERBUS is not supported.
Access groups 0 No access groups exist.
Access-Protection Supported TRUE Access protection is supported.
Version OD 0 Version of the object directory
9 Parameter data transfer9.3 Supported PMS services
42 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.4 Read/Write
The "Read" PMS service reads parameters from the inverter. The inverter outputs the requestedparameter or an error message.
The "Write" PMS service writes on parameters of the inverter. The inverter outputs a positivefeedback or an error message.
The following error messages can occur:
9.3.5 Get-OD
The "Get-OD" PMS service reads out the object description for every parameter and data type.
Error Class Error code Additional Code[hex]
Description
6 3 0x00 No access authorisation
6 5 0x10 Impermissible job parameter
6 5 0x11 Invalid subindex
6 5 0x12 Data length too large
6 5 0x13 Data length too small
6 6 0x00 Object is no parameter
6 7 0x00 Object does not exist
6 8 0x00 Data types do not comply with each other
8 0 0x00 Request cannot be executed
8 0 0x20 Request cannot be executed at the moment
8 0 0x21 Cannot be executed because of local control
8 0 0x22 Cannot be executed because of device state
8 0 0x30 Quit value range / parameter can only be changed when the controller is inhibited.
8 0 0x31 Parameter value too high
8 0 0x32 Parameter value too low
8 0 0x33 Sub parameter outside the value range
8 0 0x34 Value of the subparameter is too high
8 0 0x35 Value of the subparameter is too low
8 0 0x36 Maximum value is lower than minimum value
8 0 0x41 Communication object cannot be displayed on process data
8 0 0x42 Length of the process data exceeded
8 0 0x43 General collision with other values
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 43
9 Parameter data transfer9.3 Supported PMS services
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.6 Identify
The P "Identify" MS service provides information on how to identify the inverter.
The inverter with the plugged-on communication module provides the following parameters forthis:
Example: Visible string "device type" (15 characters)
Example: Visible string "device version" (15 characters)
Parameter Type Description
Device manufacturer Visible string Company name "Lenze"
Device type Visible-string (15 characters) Device name for inverter and communication module
Device version Visible-string (15 characters) Firmware version of the inverter and the communication module
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
E 9 4 A F H B A F C I B
Character Description
1 ... 3 Product range of the inverter and the communication module ("E94" = 9400 series)
4 Blank
5 ... 8 Firmware of the inverter (from C00200/0)• Character 5: Version ("A" = 1st generation)• Character 6 ... 8: Firmware version
• "FHB" = Servo Drive 9400 HighLine• "FRB" = Servo Drive 9400 regenerative power supply module• "VPB" = Servo Drive 9400 PLC
9 Blank
10 ... 14 Firmware of the communication module (from C13900 / C14900)• Character 10: Version ("A" = 1st generation)• Characters 11 ... 14: Firmware version
• "FCIB" = INTERBUS module
15 Blank
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0 5 . 0 0 0 1 . 0 0
Character Description
1 ... 5 Firmware version of the inverter (from C00099/0 = "05.00.xx.yy", without internal revision status ["xx"] and build status ["yy"])
6 Blank
7 ... 11 Firmware version of the communication module (from C13902 / C14902 = "01.00.xx", without internal revision status ["xx"])
12...15 Blank
9 Parameter data transfer9.3 Supported PMS services
44 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.7 Status
The "Status" PMS service provides status information about the inverter.
The inverter provides the following values:
Status Value Description
Logical status 0 = ready for communication Information about the current operating mode of the inverter with regard to communication
Physical status • 0 = ready for operation (device state "OPERATION ENABLED")
• 1 = ready for operation to a limited extent (all other device states)
Information about the current operating status of theinverter.
Local Detail 0 Is not supported.
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 45
10 Monitoring10.1 Interruption of the INTERBUS communication
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10 Monitoring
10.1 Interruption of the INTERBUS communication
An interruption of the INTERBUS communication, e.g. by cable break or failure of the host (PLC,master), is recognised by the communication module.
Responses to communication faults can be set in the Monitoring tab:
If the Servo Drive 9400 does not receive any valid process data in the "IBS-ACTIVE" state, the settingin C13885 / C14885 is taken as a basis for the process data. (Like this the data sent last by the mastercan be used or reset to zero.)
Settings in »Engineer« ( 34)
Settings Description
Response to interrupted INTERBUS communication
When the INTERBUS communication is interrupted, the response set here (C13880/1 / C14880/1) takes place in the inverter.A change in the monitoring response becomes immediately effective.
Response time if the INTERBUS communication is interrupted
If the "IBS-ACTIVE" status (INTERBUS active, cyclic data exchange) is left, the response set under takes place after the response time set here (C13881 / C14881) has elapsed.
• A value of "65535" in this code deactivates the monitoring function. • A change in the monitoring is immediately effective.• The monitoring time elapses when the "IBS-ACTIVE" status is left.• After this response delay has elapsed, the response set is executed with
the error message "INTERBUS: Data exchange stopped [0x00c88131]" ( 52).
10 Monitoring10.2 Interruption of internal communication
46 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10.2 Interruption of internal communication
The response to a communication error between the communication module and the Servo Drive9400 can be set via these codes:
• C01501 (module in slot MXI1)
• C01502 (module in slot MXI2)
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 47
11 Diagnostics11.1 LED status displays
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11 Diagnostics
For purposes of fault diagnostics, the communication module is provided with the LEDs on the front.Furthermore you can carry out the Diagnosing with the »Engineer« ( 48).
11.1 LED status displays
Note!
During normal operation, the LED BS blinks and the LED MS is permanently lit.
LEDs Pos. Colour Status Description
E94YCIB001E
MS Green On The communication module is supplied with voltage and is connected to the standard device.
Blinking The communication module is supplied with voltage, but has no connection to the standard device. (The standard device is either switched off, in the initialisation phase, or not available).
ME Red On An error has occurred in the communication module.
BS Green Blinking The INTERBUS communication has been established via the communication module. The INTERBUS is active. Data cycles are executed.
Off The communication module is not active at the fieldbus. Data cycles are not executed.
BE Red On The INTERBUS communication has been interrupted.Data cycles are not executed.
Blinking Impermissible setting:• Process data words + parameter data words
> 10• Process data words + parameter data words
= 0The communication module has been initialised and operates internally with the following values:
• 2 process data words• 1 parameter data word
DE Red On The communication module is not accepted by the basic device or the basic device is not active (see notes in the documentation relating to the basic device.)
11 Diagnostics11.2 Diagnosing with the »Engineer«
48 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.2 Diagnosing with the »Engineer«
In the »Engineer« under the Diagnostics tab, you will find INTERBUS diagnostics information.
Querying the current bus status
C13861 / C14861 displays the bus status of the INTERBUS node:
ValueC13861/14861[hex]
Bus status Description
0xyyy0 IBS-INIT Initialisation
0xyyy1 IBS-ACTIVE The bus is active. Data cycles are executed.
0xyyy2 IBS-READY The bus is ready for operation. No data cycles are executed.
yyy = device-internal use
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 49
12 Error messages12.1 Short overview of the INTERBUS error messages
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12 Error messages
This chapter supplements the error list for the Servo Drive 9400 contained in the reference manualand in the »Engineer« online help with the error messages of the communication module.
12.1 Short overview of the INTERBUS error messages
The following table lists all INTERBUS error messages in the numerical order of the error numbers.Furthermore, the preset error response and - if available - the parameter for setting the errorresponse are specified.
Tip!
If you click on the cross-reference in the first column, you will get a detailed description(causes and remedies) of the corresponding error message.
Reference manual/»Engineer« online help for the Servo Drive 9400
Here you will find general information on diagnostics & fault analysis and on error messages.
Error number Name Response (Lenze setting) Adjustable in
hex dec
0x00c85531 13129009 INTERBUS: No access to the memory 6: Information -
0x00c85532 13129010 INTERBUS: Error while reading the memory 6: Information -
0x00c85533 13129011 INTERBUS: Error while writing into the memory 6: Information -
0x00c86010 13131792 INTERBUS: Internal error 1: No Response -
0x00c86011 13131793 INTERBUS: Internal error 1: No Response -
0x00c86100 13132032 INTERBUS: Internal error 1: No Response -
0x00c86101 13132033 INTERBUS: Internal error 1: No Response -
0x00c86110 13132048 INTERBUS: Internal mapping error 4: Warning locked -
0x00c8641f 13132831 INTERBUS: Parameter set invalid 1: No Response -
0x00c86420 13132832 INTERBUS: Lenze setting loaded 1: No Response -
0x00c88125 13140261 INTERBUS: Invalid configuration 5: Warning -
0x00c88126 13140262 INTERBUS: Reset of communication 1: No Response -
0x00c88127 13140263 INTERBUS: Invalid initialisation 5: Warning -
0x00c88131 13140273 INTERBUS: Data exchange stopped None C13880/1 / C14880/1
0x00c88211 13140497 INTERBUS: Received process data length is contradictory 5: Warning -
0x00c88212 13140498 INTERBUS: Process data length to be sent is contradictory 5: Warning -
12 Error messages12.2 Possible causes and remedies
50 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.2 Possible causes and remedies
This chapter lists all INTERBUS error messages in the numerical order of the error numbers. Possiblecauses and remedies as well as responses to the error messages are described in detail.
INTERBUS: No access to memory [0x00c85531]
INTERBUS: Error while reading the memory [0x00c85532]
INTERBUS: Error while writing into the memory [0x00c85533]
INTERBUS: Internal error [0x00c86010]
INTERBUS: Internal error [0x00c86011]
INTERBUS: Internal error [0x00c86100]
Response (Lenze setting printed in bold) Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause Remedy
Memory could not be accessed. Send module with error description to Lenze.
Response (Lenze setting printed in bold) Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause Remedy
Parameter could not be read. Send module with error description to Lenze.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Parameter could not be written. Send module with error description to Lenze.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Module is defective. Send module with error description to Lenze.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Module is defective. Send module with error description to Lenze.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Module is defective. Send module with error description to Lenze.
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 51
12 Error messages12.2 Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
INTERBUS: Internal error [0x00c86101]
INTERBUS: Internal mapping error [0x00c86110]
INTERBUS: Invalid parameter set [0x00c8641f]
INTERBUS: Lenze setting loaded [0x00c86420]
INTERBUS: Invalid configuration [0x00c88125]
INTERBUS: Reset of the communication stack [0x00c88126]
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error Send module with error description to Lenze.
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The selected PDO mapping is invalid:• An object not supporting the required properties has
been specified.• The data word sum (process data words + parameter
data words) has to consist of 1 ... 10 words (16 bits/word).
Repeat Configuring process data (PDO mapping) ( 37).
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
No active parameter set could be loaded. Download application again (including module).
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Access via standard device to the parameter set in the memory module failed.
Download application again (including module).
Response (Lenze setting printed in bold) Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause Remedy
The active configuration is invalid:• Process data words + parameter data words > 10• Process data words + parameter data words = 0
The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Adapt the number of process data words and parameter data words:
• Process data words + parameter data words = 1 ... 10
Response (Lenze setting printed in bold) Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked warning Information
Cause Remedy
Error when processing the INTERBUS services Execute renewed initialisation by the master.
12 Error messages12.2 Possible causes and remedies
52 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
INTERBUS: Invalid initialisation [0x00c88127]
INTERBUS: Data exchange stopped [0x00c88131]
INTERBUS: Received process data length is contradictory [0x00c88211]
INTERBUS: Process data length to be sent is contradictory [0x00c88212]
Response (Lenze setting printed in bold) Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause Remedy
The INTERBUS initialisation has failed. Execute renewed initialisation by the master.
Response (Lenze setting printed in bold) Setting: C13880/1 / C14880/1
None System fault Fault Trouble Quick stop by troubleWarning locked Warning Information
Cause Remedy
Data exchange via INTERBUS has been stopped. • Check cables and terminals.• Execute renewed initialisation by the master.
Response (Lenze setting printed in bold) Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause Remedy
The number of received I/O data via INTERBUS (display in C13860/2 / C14860/2) does not correspond to the number configured by the device through port mapping (display in C13854/1 / C14854/1).The data word sum (process data word + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Check whether the differing data length is sufficient for the application.If required, adapt the port mapping or the I/O data length of the received data.Configuring process data (PDO mapping) ( 37) Setting the number of process data words ( 31)
Response (Lenze setting printed in bold) Setting: not possible
None System error Error Fault Quick stop by trouble Warning locked Warning Information
Cause Remedy
The number of I/O data to be sent via INTERBUS (display in C13860/2 / C14860/2) does not correspond to the number configured by the device through port mapping (display in C13855/1 / C14855/1).The data word sum (process data word + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Check whether the differing data length is sufficient for the application.If required, adapt the port mapping or the I/O data length of the data to be sent.Configuring process data (PDO mapping) ( 37) Setting the number of process data words ( 31)
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 53
13 Parameter reference13.1 Parameters of the standard device that are relevant to communication
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13 Parameter reference
This chapter supplements the parameter list and the table of attributes contained in the referencemanual and in the »Engineer« online help for the Servo Drive 9400 with the parameters of theE94AYCIB (INTERBUS) communication module.
13.1 Parameters of the standard device that are relevant to communication
In this chapter communication-relevant parameters of the Servo Drive 9400 are listed innumerically ascending order.
C00615
C00636
Reference manual/»Engineer« online help for Servo Drive 9400
Here you will find general information on parameters.
Parameter | Name:
C00615 | Resp. to imp. device conf.Data type: UNSIGNED_32
Index: 23960 = 0x5D98
Response to impermissible device configuration
Selection list
1 Fault
3 Quick stop by trouble
4 Warning Locked
6 Information
0 No response
Subcodes Lenze setting Info
C00615/1 0: No Response Reserved
C00615/2 1: No Response Resp. to imp. module in MXI1
C00615/3 1: No Response Resp. to imp. module in MXI2
C00615/4 0: No Response Reserved
C00615/5 0: No Response Reserved
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C00636 | Resp. to new module in MXI1Data type: UNSIGNED_32
Index: 23939 = 0x5D83
Response for the case where a new module has been plugged into slot 1 of the standard device.
Selection list (Lenze setting printed in bold)
1 Fault
6 Information
5 Warning
4 Warning Locked
3 Quick stop by trouble
0 No response
Read access Write access CINH PLC-STOP No transfer
13 Parameter reference13.1 Parameters of the standard device that are relevant to communication
54 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00637
C01501
C01502
Parameter | Name:
C00637 | Resp. to new module in MXI2Data type: UNSIGNED_32
Index: 23939 = 0x5D83
Response if a new module has been plugged into module slot 2 of the standard device.
Selection list (Lenze setting printed in bold)
1 Fault
6 Information
5 Warning
4 Warning Locked
3 Quick stop by trouble
0 No response
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C01501 | Resp. to comm. error with MXI1Data type: UNSIGNED_32
Index: 23074 = 0x5A22
Response to a communication error between an "intelligent" module in slot 1 and the standard device
Selection list (Lenze setting printed in bold)
0 No response
1 Fault
3 Quick stop by trouble
4 Warning Locked
5 Warning
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C01502 | Resp. to comm. error with MXI2Data type: UNSIGNED_32
Index: 23074 = 0x5A22
Response to a communication error between an "intelligent" module in slot 2 and the standard device
Selection list (Lenze setting printed in bold)
0 No response
1 Fault
3 Quick stop by trouble
4 Warning Locked
5 Warning
Read access Write access CINH PLC-STOP No transfer
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 55
13 Parameter reference13.2 Parameters of the communication module for slot MXI1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.2 Parameters of the communication module for slot MXI1
This chapter lists the parameters of the E94AYCIB communication module (INTERBUS) for slot MXI2of the Servo Drive 9400 in numerically ascending order.
C13231
C13489
C13531
Parameter | Name:
C13231 | Service codeData type: UNSIGNED_64
Index: 11344 = 0x2C50
This code is for device-internal use only and must not be written to by the user.
Value is bit-coded: Info
Bit 0 Bit 0
... ...
Bit 63 Bit 63
Subcodes Lenze setting Info
C13231/1 0
... ...
C13231/32 0
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13489 | Service codeData type: UNSIGNED_8
Index: 11086 = 0x2B4E
This code is for device-internal use only and must not be written to by the user.
Setting range (min. value | unit | max. value)
0 32
Subcodes Lenze setting Info
C13489/1 0 Service code
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13531 | Service codeData type: UNSIGNED_64
Index: 11044 = 0x2B24
This code is for device-internal use only and must not be written to by the user.
Value is bit-coded: Info
Bit 0 Bit 0
... ...
Bit 63 Bit 63
Subcodes Lenze setting Info
C13531/1 0
... ...
C13531/32 0
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
13 Parameter reference13.2 Parameters of the communication module for slot MXI1
56 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13789
C13850
C13851
Parameter | Name:
C13789 | Service codeData type: UNSIGNED_8
Index: 10786 = 0x2A22
This code is for device-internal use only and must not be written to by the user.
Setting range (min. value | unit | max. value)
0 32
Subcodes Lenze setting Info
C13789/1 0 Service code
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13850 | All words from drive to masterData type: UNSIGNED_16
Index: 10725 = 0x29E5
Display of the process data words which are transmitted from the communication module to the master.• In the subcodes 1 ... 32, all process data words to the master are displayed. Only the configured process data
words are valid.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13850/1
...
C13850/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13851 | All words from master to driveData type: UNSIGNED_16
Index: 10724 = 0x29E4
Display of the process data words which are transmitted from the master to the communication module.• In the subcodes 1 ... 32, all process data words to the master are displayed. Only the configured process data
words are valid.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13851/1
...
C13851/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 57
13 Parameter reference13.2 Parameters of the communication module for slot MXI1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13852
C13853
C13854
Parameter | Name:
C13852 | All words to the basic deviceData type: UNSIGNED_16
Index: 10723 = 0x29E3
Display of the process data words which are transmitted from the communication module to the standard device.• In the subcodes 1 ... 32, all process data words from the communication module are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13852/1
...
C13852/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13853 | All words to the basic deviceData type: UNSIGNED_16
Index: 10722 = 0x29E2
Display of the process data words which are transmitted from the standard device to the communication module.• In the subcodes 1 ... 32, all process data words from the standard device are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13853/1
...
C13853/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13854 | Length of ports mapped into receive PDOData type: UNSIGNED_8
Index: 10721 = 0x29E1
Display of the total data length (in bytes) of the ports that have been entered into the receive PDO.The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).Configuring process data (PDO mapping) ( 37)
Display area (min. value | unit | max. value)
0 64
Subcodes Info
C13854/1 Length of the ports entered into the receive PDO
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
13 Parameter reference13.2 Parameters of the communication module for slot MXI1
58 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13855
C13860
C13861
Parameter | Name:
C13855 | Length of ports mapped into send PDOData type: UNSIGNED_8
Index: 10720 = 0x29E0
Display of the total data length (in bytes) of the ports that have been entered into the send PDO.The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).Configuring process data (PDO mapping) ( 37)
Display area (min. value | unit | max. value)
0 64
Subcodes Info
C13855/1 Length of the ports entered into the send PDO
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13860 | SettingsData type: UNSIGNED_8
Index: 10715 = 0x29DB
Display of the set number of the• Parameter data words• Process data words
The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Display area (min. value | unit | max. value)
0 10
Subcodes Info
C13860/1 Display of parameter data length (PCP)
C13860/2 Display of process data length
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13861 | Bus statusData type: BITFIELD_16Index: 10714 = 0x29DA
Display of the current bus statusMeaning of the resulting hexadecimal values:
• 0xyyy0 = IBS-INIT• 0xyyy1 = IBS-ACTIVE• 0xyyy2 = IBS-READYQuerying the current bus status ( 48)
Value is bit-coded: Info
Bit 0 Bit 0
... ...
Bit 15 Bit 15
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 59
13 Parameter reference13.2 Parameters of the communication module for slot MXI1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13862
C13863
C13880
Parameter | Name:
C13862 | CounterData type: UNSIGNED_16
Index: 10713 = 0x29D9
Counter for cycles and INTERBUS resets
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13862/1 Data cycles per second
C13862/2 Total data cycles
C13862/3 Number of INTERBUS resets
C13862/4 Number of ID cycles
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13863 | Active baud rateData type: UNSIGNED_8
Index: 10712 = 0x29D8
Display of the set baud rate
Selection list (read only) Info
0 500 kbps
1 2.00 Mbps
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13880 | Monitoring ReactionData type: UNSIGNED_8
Index: 10695 = 0x29C7
Monitoring response in case of a communication fault• A change in the monitoring response becomes immediately effective.Interruption of the INTERBUS communication ( 45)
Selection list Info
0 No response
1 Fault
3 Quick stop by trouble
4 Warning Locked
6 Information
Subcodes Lenze setting Info
C13880/1 0: No Response Response to interrupted INTERBUS communication
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
13 Parameter reference13.2 Parameters of the communication module for slot MXI1
60 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13881
C13885
C13892
Parameter | Name:
C13881 | Response time if the INTERBUS communication is interruptedData type: UNSIGNED_16
Index: 10694 = 0x29C6
If the "IBS-ACTIVE" status (INTERBUS is active and data is cyclically exchanged) is quit, the response parameterised in C13880/1 is executed after the monitoring time set for the data exchange has elapsed.
• A value of "65535" in this code deactivates the monitoring function. • A change in the monitoring is immediately effective.Interruption of the INTERBUS communication ( 45)
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 65535 ms
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Clear process dataData type: UNSIGNED_8
Index: 10690 = 0x29C2
Setting which process data of the inverters are to be further processed for maintaining the internal communication if the INTERBUS failed.
Selection list (Lenze setting printed in bold) Info
0 Use of the last master process data
1 Process data are set to the value '0'
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13892 | PCP data lengthData type: UNSIGNED_8
Index: 10683 = 0x29BB
Setting of the number of the parameter data words to be used (PCP)The setting is activated ...
• if all DIP switches (S205) are in the "OFF" position;• after executing the "11: Save start parameters" device command via standard device code C00002 and
performing another mains switching of the communication module/drive afterwards.Setting the number of process data words ( 31)
Selection list (Lenze setting printed in bold) Info
0 No PCB data
1 1 word
2 2 words
4 4 words
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 61
13 Parameter reference13.2 Parameters of the communication module for slot MXI1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13893
C13894
C13900
Parameter | Name:
C13893 | Process data lengthData type: UNSIGNED_8
Index: 10682 = 0x29BA
Setting of the number of the process data words to be usedThe setting is activated ...
• if all DIP switches (S205) are in the "OFF" position;• after executing the "11: Save start parameters" device command via standard device code C00002 and
performing another mains switching of the communication module/drive afterwards.Setting the number of process data words ( 31)
Selection list (Lenze setting printed in bold) Info
0 No process data
1 1 word
2 2 words
3 3 words
4 4 words
5 5 words
6 6 words
7 7 words
8 8 words
9 9 words
10 10 words
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13894 | Baud rateData type: UNSIGNED_8
Index: 10681 = 0x29B9
setting the baud rateThe setting is activated ...
• if all DIP switches (S205) are in the "OFF" position;• after executing the "11: Save start parameters" device command via standard device code C00002 and
performing another mains switching of the communication module/drive afterwards.Setting the baud rate ( 33)
Selection list (Lenze setting printed in bold) Info
0 500 kbps
1 2.00 Mbps
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13900 | Firmware product typeData type: VISIBLE_STRING
Index: 10675 = 0x29B3
Display of the product type (string with a length of 8 bytes)• The following identification code is displayed: "E94AFCIB".
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
13 Parameter reference13.2 Parameters of the communication module for slot MXI1
62 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13901
C13902
C13920
Parameter | Name:
C13901 | Firmware compilation dateData type: VISIBLE_STRING
Index: 10674 = 0x29B2
Display of the compilation date of the firmware (string with a length of 20 bytes)• The date ("MMM TT JJJJ") and the time ("hh:mm:ss") are output, e.g. "Mar 21 2005 12:31:21".
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13902 | Firmware versionData type: VISIBLE_STRING
Index: 10673 = 0x29B1
Display of the firmware version (string with a length of 8 bytes)The identification code is output, e.g. "01.00.00".
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13920 | Display of DIP switch positionData type: BITFIELD_8
Index: 10655 = 0x299F
Display of the current DIP switch position• The set parameter data length (PCP) is displayed in C13860/1.• The set process data length is displayed in C13860/2.• The set baud rate is displayed in C13863.Possible settings via DIP switch ( 30)
Value is bit-coded: Info
Bit 0 DIP 8 Baud rate
Bit 1 DIP 7 No response
Bit 2 DIP 6 Number of parameter data words (PCP)
Bit 3 DIP 5
Bit 4 DIP 4 Number of process data words
Bit 5 DIP 3
Bit 6 DIP 2
Bit 7 DIP 1
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 63
13 Parameter reference13.3 Parameters of the communication module for slot MXI2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.3 Parameters of the communication module for slot MXI2
This chapter lists the parameters of the E94AYCIB communication module (INTERBUS) for slot MXI2of the Servo Drive 9400 in numerically ascending order.
C14231
C14489
C14531
Parameter | Name:
C14231 | Service codeData type: UNSIGNED_64
Index: 10344 = 0x2868
This code is for device-internal use only and must not be written to by the user!
Value is bit-coded: Info
Bit 0 Bit 0
... ...
Bit 63 Bit 63
Subcodes Lenze setting Info
C14231/1 0
... ...
C14231/32 0
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14489 | Service codeData type: UNSIGNED_8
Index: 10086 = 0x2766
This code is for device-internal use only and must not be written to by the user!
Setting range (min. value | unit | max. value)
0 32
Subcodes Lenze setting Info
C14489/1 0 Service code
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14531 | Service codeData type: UNSIGNED_64
Index: 10044 = 0x273C
This code is for device-internal use only and must not be written to by the user!
Value is bit-coded: Info
Bit 0 Bit 0
... ...
Bit 63 Bit 63
Subcodes Lenze setting Info
C14531/1 0
... ...
C14531/32 0
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
13 Parameter reference13.3 Parameters of the communication module for slot MXI2
64 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14789
C14850
C14851
Parameter | Name:
C14789 | Service codeData type: UNSIGNED_8
Index: 9786 = 0x263A
This code is for device-internal use only and must not be written to by the user!
Setting range (min. value | unit | max. value)
0 32
Subcodes Lenze setting Info
C14789/1 0 Service code
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14850 | All words to masterData type: UNSIGNED_16
Index: 9725 = 0x25FD
Display of the process data words which are transmitted from the communication module to the master.• In the subcodes 1 ... 32, all process data words to the master are displayed. Only the configured process data
words are valid.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C14850/1
...
C14850/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14851 | All words from masterData type: UNSIGNED_16
Index: 9724 = 0x25FC
Display of the process data words which are transmitted from the master to the communication module.• In the subcodes 1 ... 32, all process data words to the master are displayed. Only the configured process data
words are valid.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C14851/1
...
C14851/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 65
13 Parameter reference13.3 Parameters of the communication module for slot MXI2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14852
C14853
C14854
Parameter | Name:
C14852 | All words to standard deviceData type: UNSIGNED_16
Index: 9723 = 0x25FB
Display of the process data words 1 ... 32 transferred from the communication module to the standard device.• In the subcodes 1 ... 32, all process data words from the communication module are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C14852/1
...
C14852/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14853 | All words from standard deviceData type: UNSIGNED_16
Index: 9722 = 0x25FA
Display of the process data words 1 ... 32 transferred from the standard device to the communication module.• In the subcodes 1 ... 32, all process data words from the standard device are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C14853/1
...
C14853/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14854 | Length of ports mapped into receive PDOData type: UNSIGNED_8
Index: 9721 = 0x25F9
Display of the total data length (in bytes) of the ports that have been entered into the receive PDO.The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).Configuring process data (PDO mapping) ( 37)
Display area (min. value | unit | max. value)
0 64
Subcodes Info
C14854/1 Length of the ports entered into the receive PDO
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
13 Parameter reference13.3 Parameters of the communication module for slot MXI2
66 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14855
C14860
C14861
Parameter | Name:
C14855 | Length of ports mapped into send PDOData type: UNSIGNED_8
Index: 9720 = 0x25F8
Display of the total data length (in bytes) of the ports that have been entered into the send PDO.The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).Configuring process data (PDO mapping) ( 37)
Display area (min. value | unit | max. value)
0 64
Subcodes Info
C14855/1 Length of the ports entered into the send PDO
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14860 | SettingsData type: UNSIGNED_8
Index: 9715 = 0x25F3
Display of the set number of the• Parameter data words• Process data words
The data word sum (process data words + parameter data words) has to consist of 1 ... 10 words (16 bits/word).
Display area (min. value | unit | max. value)
0 10
Subcodes Info
C14860/1 Display of parameter data length (PCP)
C14860/2 Display of process data length
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14861 | Bus statusData type: BITFIELD_16
Index: 9714 = 0x25F2
Display of the current bus statusMeaning of the resulting hexadecimal values:
• 0xyyy0 = IBS-INIT• 0xyyy1 = IBS-ACTIVE• 0xyyy2 = IBS-READYQuerying the current bus status ( 48)
Value is bit-coded: Info
Bit 0 Bit 0
... ...
Bit 15 Bit 15
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 67
13 Parameter reference13.3 Parameters of the communication module for slot MXI2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14862
C14863
C14880
Parameter | Name:
C14862 | CounterData type: UNSIGNED_16
Index: 9713 = 0x25F1
Counter for cycles and INTERBUS resets
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C14862/1 Data cycles per second
C14862/2 Total data cycles
C14862/3 Number of Interbus resets
C14862/4 Number of ID cycles
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14863 | Active baud rateData type: UNSIGNED_8
Index: 9712 = 0x25F0
Display of the set baud rate
Selection list (read only) Info
0 500 kbps
1 2.00 Mbps
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14880 | Reaction on communication faultData type: UNSIGNED_8
Index: 9695 = 0x25DF
Monitoring response in case of a communication fault• A change in the monitoring response becomes immediately effective.Interruption of the INTERBUS communication ( 45)
Selection list Info
0 No response
1 Fault
3 Quick stop by trouble
4 Warning Locked
6 Information
Subcodes Lenze setting Info
C14880/1 0: No Response Response to interrupted INTERBUS communication
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
13 Parameter reference13.3 Parameters of the communication module for slot MXI2
68 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14881
C14885
C14892
Parameter | Name:
C14881 | Response time if the INTERBUS communication is interruptedData type: UNSIGNED_16
Index: 9694 = 0x25DE
If the "IBS-ACTIVE" status (INTERBUS is active and data is cyclically exchanged) is quit, the response parameterised in C14880/1 is executed after the monitoring time set for the data exchange has elapsed.
• A value of "65535" in this code deactivates the monitoring function. • A change in the monitoring is immediately effective.Interruption of the INTERBUS communication ( 45)
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 65535 ms
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14885 | Clear process dataData type: UNSIGNED_8
Index: 9690 = 0x25DA
Setting which process data of the inverters are to be further processed for maintaining the internal communication if the INTERBUS failed.
Selection list (Lenze setting printed in bold) Info
0 Use of the last master process data
1 Process data are set to the value '0'
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14892 | PCP data lengthData type: UNSIGNED_8
Index: 9683 = 0x25D3
Setting of the number of the parameter data words to be used (PCP)The setting is activated ...
• if all DIP switches (S205) are in the "OFF" position;• after executing the "11: Save start parameters" device command via standard device code C00002 and
performing another mains switching of the communication module/drive afterwards.Setting the number of process data words ( 31)
Selection list (Lenze setting printed in bold) Info
0 No PCB data
1 1 word
2 2 words
4 4 words
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 69
13 Parameter reference13.3 Parameters of the communication module for slot MXI2
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14893
C14894
C14900
Parameter | Name:
C14893 | Process data lengthData type: UNSIGNED_8
Index: 9682 = 0x25D2
Setting of the number of the process data words to be usedThe setting is activated ...
• if all DIP switches (S205) are in the "OFF" position;• after executing the "11: Save start parameters" device command via standard device code C00002 and
performing another mains switching of the communication module/drive afterwards.Setting the number of process data words ( 31)
Selection list (Lenze setting printed in bold) Info
0 No process data
1 1 word
2 2 words
3 3 words
4 4 words
5 5 words
6 6 words
7 7 words
8 8 words
9 9 words
10 10 words
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14894 | Baud rateData type: UNSIGNED_8
Index: 9681 = 0x25D1
setting the baud rateThe setting is activated ...
• if all DIP switches (S205) are in the "OFF" position;• after executing the "11: Save start parameters" device command via standard device code C00002 and
performing another mains switching of the communication module/drive afterwards.Setting the baud rate ( 33)
Selection list (Lenze setting printed in bold) Info
0 500 kbps
1 2.00 Mbps
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14900 | Firmware product typeData type: VISIBLE_STRING
Index: 9675 = 0x25CB
Display of the product type (string with a length of 8 bytes)• The following identification code is displayed: "E94AFCIB".
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
13 Parameter reference13.3 Parameters of the communication module for slot MXI2
70 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14901
C14902
C14920
Parameter | Name:
C14901 | Firmware compilation dateData type: VISIBLE_STRING
Index: 9674 = 0x25CA
Display of the compilation date of the firmware (string with a length of 20 bytes)• The date ("MMM TT JJJJ") and the time ("hh:mm:ss") are output, e.g. "Mar 21 2005 12:31:21".
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14902 | Firmware versionData type: VISIBLE_STRING
Index: 9673 = 0x25C9
Display of the firmware version (string with a length of 8 bytes)The identification code is output, e.g. "01.00.00".
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14920 | Display of DIP switch positionData type: BITFIELD_8Index: 9655 = 0x25B7
Display of the current DIP switch position• The set parameter data length (PCP) is displayed in C13860/1.• The set process data length is displayed in C13860/2.• The set baud rate is displayed in C13863.Possible settings via DIP switch ( 30)
Value is bit-coded: Info
Bit 0 DIP 8 Baud rate
Bit 1 DIP 7 No response
Bit 2 DIP 6 Number of parameter data words (PCP)
Bit 3 DIP 5
Bit 4 DIP 4 Number of process data words
Bit 5 DIP 3
Bit 6 DIP 2
Bit 7 DIP 1
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 71
13 Parameter reference13.4 Table of attributes
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13.4 Table of attributes
The table of attributes contains information required for communication with the inverter viaparameters.
How to read the table of attributes:
Column Meaning Entry
Code Parameter name Cxxxxx
Name Parameter short text (display text) Text
Index dec Index under which the parameter is addressed.The subindex for array variables corresponds to the Lenze subcode number.
24575 - Lenze code number Is only required for access via a bus system.
hex 0x5FFF - Lenze code number
Data DS Data structure E Single variable(only one parameter element)
A Array variable(several parameter elements)
DA Number of array elements (subcodes) Number
DT Data type BITFIELD_8 1 byte, bit-coded
BITFIELD_16 2 bytes, bit-coded
BITFIELD_32 4 bytes, bit-coded
INTEGER_8 1 byte, with sign
INTEGER_16 2 bytes with sign
INTEGER_32 4 bytes, with sign
UNSIGNED_8 1 byte without sign
UNSIGNED_16 2 bytes without sign
UNSIGNED_32 4 bytes, without sign
VISIBLE_STRING ASCII string
OCTET_STRING
Factor Factor for data transmission via a bus system, depending on the number of decimal positions
Factor 1 no decimal positions10 1 decimal position100 2 decimal positions1000 3 decimal positions
Access R Read access Reading permitted
W Write access Writing permitted
CINH Controller inhibit required Writing is only possible if controller inhibit is set
13 Parameter reference13.4 Table of attributes
72 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Table of attributes
Code Name Index Data Access
dec hex DS DA DT Factor R W CINH
C13231 Service code 11344 0x2C50 A 32 UNSIGNED_64
C13489 Service code 11086 0x2B4E A 1 UNSIGNED_8 1
C13531 Service code 11044 0x2B24 A 32 UNSIGNED_64
C13789 Service code 10786 0x2A22 A 1 UNSIGNED_8 1
C13850 All words from drive to master 10725 0x29E5 A 32 UNSIGNED_16 1
C13851 All words from master to drive 10724 0x29E4 A 32 UNSIGNED_16 1
C13852 All words to the basic device 10723 0x29E3 A 32 UNSIGNED_16 1
C13853 All words to the basic device 10722 0x29E2 A 32 UNSIGNED_16 1
C13854 Length of ports mapped into receive PDO
10721 0x29E1 A 1 UNSIGNED_8 1
C13855 Length of ports mapped into send PDO 10720 0x29E0 A 1 UNSIGNED_8 1
C13860 Settings 10715 0x29DB A 2 UNSIGNED_8 1
C13861 Bus status 10714 0x29DA E 1 BITFIELD_16
C13862 Counter 10713 0x29D9 A 4 UNSIGNED_16 1
C13863 Active baud rate 10712 0x29D8 E 1 UNSIGNED_8 1
C13880 Monitoring Reaction 10695 0x29C7 A 1 UNSIGNED_8 1
C13881 Response time if the INTERBUS communication is interrupted
10694 0x29C6 E 1 UNSIGNED_16 1
C13885 Clear process data 10690 0x29C2 E 1 UNSIGNED_8 1
C13892 PCP data length 10683 0x29BB E 1 UNSIGNED_8 1
C13893 Process data length 10682 0x29BA E 1 UNSIGNED_8 1
C13894 Baud rate 10681 0x29B9 E 1 UNSIGNED_8 1
C13900 Firmware product type 10675 0x29B3 E 1 VISIBLE_STRING
C13901 Firmware compilation date 10674 0x29B2 E 1 VISIBLE_STRING
C13902 Firmware version 10673 0x29B1 E 1 VISIBLE_STRING
C13920 Display of DIP switch position 10655 0x299F E 1 BITFIELD_8
C14231 Service code 10344 0x2868 A 32 UNSIGNED_64
C14489 Service code 10086 0x2766 A 1 UNSIGNED_8 1
C14531 Service code 10044 0x273C A 32 UNSIGNED_64
C14789 Service code 9786 0x263A A 1 UNSIGNED_8 1
C14850 All words from drive to master 9725 0x25FD A 32 UNSIGNED_16 1
C14851 All words from master to drive 9724 0x25FC A 32 UNSIGNED_16 1
C14852 All words to the basic device 9723 0x25FB A 32 UNSIGNED_16 1
C14853 All words to the basic device 9722 0x25FA A 32 UNSIGNED_16 1
C14854 Length of ports mapped into receive PDO
9721 0x25F9 A 1 UNSIGNED_8 1
C14855 Length of ports mapped into send PDO 9720 0x25F8 A 1 UNSIGNED_8 1
C14860 Settings 9715 0x25F3 A 2 UNSIGNED_8 1
C14861 Bus status 9714 0x25F2 E 1 BITFIELD_16
C14862 Counter 9713 0x25F1 A 4 UNSIGNED_16 1
C14863 Active baud rate 9712 0x25F0 E 1 UNSIGNED_8 1
C14880 Monitoring Reaction 9695 0x25DF A 1 UNSIGNED_8 1
C14881 Response time if the INTERBUS communication is interrupted
9694 0x25DE E 1 UNSIGNED_16 1
C14885 Clear process data 9690 0x25DA E 1 UNSIGNED_8 1
C14892 PCP data length 9683 0x25D3 E 1 UNSIGNED_8 1
C14893 Process data length 9682 0x25D2 E 1 UNSIGNED_8 1
C14894 Baud rate 9681 0x25D1 E 1 UNSIGNED_8 1
C14900 Firmware product type 9675 0x25CB E 1 VISIBLE_STRING
C14901 Firmware compilation date 9674 0x25CA E 1 VISIBLE_STRING
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 73
13 Parameter reference13.4 Table of attributes
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14902 Firmware version 9673 0x25C9 E 1 VISIBLE_STRING
C14920 Display of DIP switch position 9655 0x25B7 E 1 BITFIELD_8
Code Name Index Data Access
dec hex DS DA DT Factor R W CINH
Index
74 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14 Index
AAbort (PMS service) 41
Active baud rate (C13863) 59
Active baud rate (C14863) 67
Addressing of the parameter data 39
All words from drive to master (C13850) 56
All words from master to drive (C13851) 56
All words from the master (C14851) 64
All words from the standard device (C14853) 65
All words to the basic device (C13852) 57
All words to the basic device (C13853) 57
All words to the master (C14850) 64
All words to the standard device (C14852) 65
Application as directed 12
Application notes 9
Approvals 15
Assembly 22
BBaud rate 15
Baud rate (C13894) 61
Baud rate (C14894) 69
Before initial switch-on 29
Bus cable length 27
Bus cable specification 27
Bus state (C13861) 58
Bus state (C14861) 66
CC00615 | Resp. to imp. device conf. 53
C00636 | Resp. to new module in MXI1 53
C00637 | Resp. to new module in MXI2 54
C01501 | Resp. to comm. error with MXI1 54
C01502 | Resp. to comm. error with MXI2 54
C13231 | Service code 55
C13489 | Service code 55
C13531 | Service code 55
C13789 | Service code 56
C13850 | All words from drive to master 56
C13851 | All words from master to drive 56
C13852 | All words to the basic device 57
C13853 | All words to the basic device 57
C13854 | Length of ports mapped into receive PDO 57
C13855 | Length of ports mapped into send PDO 58
C13860 | Settings 58
C13861 | Bus state 58
C13862 | Counter 59
C13863 | Active baud rate 59
C13880 | Monitoring Reaction 59
C13881 | Response time if the INTERBUS communication is interrupted 60
C13885 | Clear process data 60
C13892 | PCP data length 60
C13893 | Process data length 61
C13894 | Baud rate 61
C13900 | Firmware product type 61
C13901 | Firmware compilation date 62
C13902 | Firmware version 62
C13920 | Display of DIP switch position 62
C14231 | Service code 63
C14489 | Service code 63
C14531 | Service code 63
C14789 | Service code 64
C14850 | All words to master 64
C14851 | All words from master 64
C14852 | All words to standard device 65
C14853 | All words from standard device 65
C14854 | Length of ports mapped into receive PDO 65
C14855 | Length of ports mapped into send PDO 66
C14860 | Settings 66
C14861 | Bus state 66
C14862 | Counter 67
C14863 | Active baud rate 67
C14880 | Response to communication fault 67
C14881 | Response time if the INTERBUS communication is interrupted 68
C14885 | Clear process data 68
C14892 | PCP data length 68
C14893 | Process data length 69
C14894 | Baud rate 69
C14900 | Firmware product type 69
C14901 | Firmware compilation date 70
C14902 | Firmware version 70
C14920 | Display of the DIP switch position 70
Cable length 15
Clear process data (C13885) 60
Clear process data (C14885) 68
Codes 53
Commissioning 29
Communication channels 36
Communication medium 15
Communication profile 15
Communication time 16
Configuring process data (PDO mapping) 37
Conformities 15
Connections 14
Conventions 7
Conventions used 7
Counter (C13862) 59
Counter (C14862) 67
CRL (communication relation list) 40
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17 75
Index
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
DData transfer 36
Device and application-specific safety instructions 11
Device identification 15
Device protection 11
Diagnostics 47
Diagnostics with the »Engineer« 48
Dimensions 20
Dimensions of 9-pole Sub-D connectors 26
DIP switch settings 30
Disassembly 22
Display of DIP switch position (C13920) 62
Display of the DIP switch position (C14920) 70
Document history 6
EElectrical installation 23
E-mail to Lenze 77
Error messages 49Causes and remedies 50Short overview 49
Error messages (PCP services Read / Write) 42
Error number0x00c85531 500x00c85532 500x00c85533 500x00c86010 500x00c86011 500x00c86100 500x00c86101 510x00c86110 510x00c8641f 510x00c86420 510x00c88125 510x00c88126 510x00c88127 520x00c88131 520x00c88211 520x00c88212 52
Establishing communication 35
FFeedback to Lenze 77
Firmware compilation date (C13901) 62
Firmware compilation date (C14901) 70
Firmware product type (C13900) 61
Firmware product type (C14900) 69
Firmware version (C13902) 62
Firmware version (C14902) 70
GGeneral data 15
General safety and application notes 10
Get-OD (PMS service) 42
IIBS-ACTIVE 48
IBS-INIT 48
IBS-READY 48
Identification 12
Identify (PMS service) 43
Information regarding the validity 5
Initial switch-on 35
Initialising PCP communication 40
Initiate (PMS service) 41
Installation 21
INTERBUSData exchange stopped (error message) 52Error: Lenze Setting Loaded (error message) 51Internal error (error message) 50, 51Internal mapping error (error message) 51Invalid Configuration (error message) 51Invalid initialisation (error message) 52Invalid Parameter Set (error message) 51Memory
No Access (error message) 50Read Error (error message) 50Write Error (error message) 50
Process data length to be sent is contradictory (error message) 52Received process data length is contradictory (error message) 52Reset of the communication stack (error message) 51
INTERBUS connection 25
INTERBUS error messagesCauses and remedies 50Short overview 49
INTERBUS ring 24
Interface for communication 15
Interfaces 14
Interruption of internal communication 46
Interruption of the INTERBUS communication 45
LLayout of the safety instructions 9
LED status displays 47
Length of ports mapped into receive PDO (C13854) 57
Length of ports mapped into receive PDO (C14854) 65
Length of ports mapped into send PDO (C13855) 58
Length of ports mapped into send PDO (C14855) 66
Index
76 Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
MMax. number of data words 15
Max. PDU length 15
Mechanical installation 22
Module ID 15
Monitoring 45
Monitoring Reaction (C13880) 59
NNameplate 12
Network topology 15
Number of nodes 15
OOperating conditions 15
PParameter data addressing 39
Parameter data transfer 39
Parameter data words 15
Parameter reference 53
Parameters of the communication module for slot MXI1 55
Parameters of the communication module for slot MXI2 63
Parameters of the standard device that are relevant to communication 53
PCP data length (C13892) 60
PCP data length (C14892) 68
PDO mapping 37
PMS services 16, 41
Process data length (C13893) 61
Process data length (C14893) 69
Process data transfer 37
Process data words 15
Processing time 16
Product description 12
Product features 13
Protection against uncontrolled restart 35
Protection of persons 11
Protective insulation 17
Protocol data 16
QQuerying the bus status 48
Querying the current bus status 48
RRead (PMS service) 42
Reject (PMS service) 41
Residual hazards 11
Resp. to comm. error with MXI1 (C01501) 54
Resp. to comm. error with MXI2 (C01502) 54
Resp. to imp. device config. (C00615) 53
Resp. to new module in MXI1 (C00636) 53
Resp. to new module in MXI2 (C00637) 54
Response time if the INTERBUS communication (C13881) is interrupted 60
Response time if the INTERBUS communication (C14881) is interrupted 68
Response to communication fault (C14880) 67
SSafety instructions 9, 10
Screenshots/application examples 5
Service code (C13231) 55
Service code (C13489) 55
Service code (C13531) 55
Service code (C13789) 56
Service code (C14231) 63
Service code (C14489) 63
Service code (C14531) 63
Service code (C14789) 64
Settings (C13860) 58
Settings (C14860) 66
Settings in the »Engineer« 34
Status (PMS service) 44
Status displays (LEDs) 47
Supported PMS services 41
System error messages 49
TTable of attributes 71
Target group 5
Technical data 15
Terminals 28
Terminology used 8
Thick-cable properties 27
Type of node 15
UUsing the communication module 12
VVoltage supply 15
Voltage supply (external) 28
WWiring according to EMC guidelines 23
Wiring of the INTERBUS 24
Write (PCP service) 42
77
Your opinion is important to usThese instructions were created to the best of our knowledge andbelief to give you the best possible support for handling our product.
Perhaps we have not succeeded in achieving this objective in everyrespect. If you have suggestions for improvement, please e-mail usto:
Thank you very much for your support.
Your Lenze documentation team
L
E94AYCIB communication module (INTERBUS) · Communication Manual · EDS94AYCIB · 13451099 · DMS 4.0 EN · 02/2014 · TD17
Lenze Automation GmbHPostfach 10 13 52, D-31763 HamelnHans-Lenze-Straße 1, D-31855 AerzenGermany
+49 5154 82-0 +49 5154 82-2800 [email protected] www.lenze.com
ServiceLenze Service GmbHBreslauer Straße 3, D-32699 ExtertalGermany
008000 24 46877 (24 h helpline) +49 5154 82-1112 [email protected]