Xiamen Four-Faith Communication Technology Co., Ltd. Xiamen Four-Faith Communication Technology Co.,Ltd. Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.China http://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax+86 592-5912735 11 Communication between F8114 and F8914 Part One Communication between F8114 and F8914(send ModBus command from the Data Service Center(DSC) to read the IO status of F8914). The networking is as follows: Illustration of Terminal Blocks of F8914. IO1: Digital input/output 0---3.3V IO2: Digital input/output 0---3.3V IO3: Analog voltage input 0---5V IO4: Analog current input 4---20mA IO5: Analog current input 4---20mA PC (runs a TCP Server software) GPRS network F8914(ZigBeeF8114(GPRS+ZigBeeIO1 PIN8 ZigBee network IO2 PIN9 IO3 PIN10 IO4 PIN11 IO5 PIN12

Transcript of Communication between F8114 and F8914(Modbus+Zigbee)

Page 1: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

11

Communication between F8114 and F8914

Part One

Communication between F8114 and F8914(send ModBus

command from the Data Service Center(DSC) to read the IO

status of F8914).

The networking is as follows:

Illustration of Terminal Blocks of F8914.

IO1: Digital input/output 0---3.3VIO2: Digital input/output 0---3.3VIO3: Analog voltage input 0---5VIO4: Analog current input 4---20mAIO5: Analog current input 4---20mA

PC (runs a TCP Server software)

GPRS network

F8914(ZigBee) F8114(GPRS+ZigBee)

IO1PIN8

ZigBee network

IO2PIN9

IO3PIN10

IO4PIN11

IO5PIN12

Page 2: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

22

When IO port is configured as digital output, the function code is 05.When IO port is configured as digital input, the function code is 02.When IO port is configured as analog input, the function code is 04.

F8914 IO Port Address:IO5 as analog input, register address:0X40000IO4 as analog input, register address:0X40001IO3 as analog input, register adress: 0X40002IO2 as digital input, register address:0X20003IO1 as digital input, register address:0X20004

Wiring method of sensorAnalog inputa. Single-wire: Connect the analog output of the sensor to the analog input(IO3/IO4/IO5) of F8914directly.b. Double-wire: Connect the positive of analog output of the sensor to the analoginput(IO3/IO4/IO5) of F8114, and connect the ground wire to GND(PIN2) of F8914.

Digital inputa. Low level input:Connect the input of contact switch to GND of F8914, and connect the outputof contact switch to the digital output of F8914(IO1/IO2).b. High level input:Connect 3.3V voltage output to IO1/IO2, and connect the ground wire to GNDof F8914.

A temperature humidity sensor(double-wire) with analog(current) output is as picture below.

Connect to GND(PIN2/PIN3)

Temperature(PIN1-IO5)

Humidity (PIN1-IO4)

Page 3: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

33

1. Configurations in F8114Data Service Center Settings

IP Modem setting

Use MODBUSfunction

Page 4: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

44

Zigbee Setting

MODBUS Setting

The same asF8914

Crossed configurationwith F8914

The same asF8914

Page 5: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

55

2. Configurations in F8914

When F8114 is connected to DSC, and F8914 joins in the zigbee network. You can send Modbuscommand from DSC to read 8914 IO status. Below are the commands and responses.

The same as F8114

The same as F8114

Crossed configurationwith F8114

The lower baudrate,the longer interval

Only used in ATmode

Page 6: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

66

To read IO4 value(analog input)Request: 01 04 00 F1 00 01 60 39Responds: 01 04 02 01 73 F9 45 (current input 4mA )Response: 01 04 02 02 E9 79 DE (current input 8mA)Response: 01 04 02 03 A5 79 BB (current input 10mA)Response: 01 04 02 05 78 BA C2 (current input 15mA)Response: 01 04 02 07 4D 7B 35 (current input 20mA)

To read IO5 value(analog input)Request: 01 04 00 F0 00 01 31 F9Response: 01 04 02 01 74 B8 87 (current input 4mA )Response: 01 04 02 02 EB F8 1F (current input 8mA)Response: 01 04 02 03 A7 F8 7A (current input 10mA)Response: 01 04 02 05 7B FA 43 (current input 15mA)Response: 01 04 02 07 51 7A FC (current input 20mA)

To read IO3 value(analog input)Request: 01 04 00 F2 00 01 90 39Response: 01 04 02 04 72 3B D5 (voltage input 3.06V)

Notes of the Modbus commands. Take the command 01 04 00 F2 00 01 90 39 for example.F8114

Modbus addr.Functioncode

8914node addr.

Registeraddr.

Registernumber

CRC16

01 04 00 F 2 00 01 90 39

Response 01 04 02 04 72 3B D5F8114

Modbus addr.Functioncode

Bytecount

Acquisitionvalue

CRC16

01 04 02 04 72 3B D5

The acquisition value in HEX. You need to convert it to DEC and calculate with the formulabelow. And then calculate the pratical value according to the measuring range of the sensor.Current type: 3.3/2047 *acquisition value/150 *1000= (mA)Voltage type: 3.3/2047 *acquisition value/12.1*20.16= (V)(The acquisition value should be converted to DEC first)

Page 7: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

77

To set IO1 high/low level(digital output)Request: 01 05 00 F4 FF 00 CD C8 (set IO1 high level)Response:01 05 00 F4 FF 00 CD C8Request: 01 05 00 F4 00 00 8C 38 (set IO1 low level)Response:01 05 00 F4 00 00 8C 38

To query IO1 status(digital output)Request: 01 01 00 F4 00 01 BC 38Response: 01 01 01 01 90 48 (IO1 high level)Response: 01 01 01 00 51 88 (IO1 low level)

To set IO2 high/low level(digital output)Request: 01 05 00 F3 FF 00 7C 09 (set IO2 high level)Response:01 05 00 F3 FF 00 7C 09Request: 01 05 00 F3 00 00 3D F9 (set IO2 low level)Response:01 05 00 F0 00 00 CD F9

To query IO2 status(digital output)Request: 01 01 00 F3 00 01 0D F9Response: 01 01 01 01 90 48 (IO2 high level)Response: 01 01 01 00 51 88 (IO2 low level)

Notes of the Modbus commands. Take the command 01 05 00 F4 FF 00 CD C8 for example.F8114

Modbus addr.Functioncode

8914node addr.

Registeraddr.

Sethigh/level

CRC16

01 05 00 F 4FF 00 CD C800 00 8C 38

Page 8: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

88

To read IO2 status(digital input)Request:01 02 00 F3 00 01 49 F9Response:01 02 01 01 60 48 (IO2 high level)Response:01 02 01 00 A1 88 (IO2 low level)

To read IO1 status(digital input)Request: 01 02 00 F4 00 01 F8 38Response:01 02 01 01 60 48 (IO1 high level)Response:01 02 01 00 A1 88 (IO1 low level)

Notes of the Modbus commands. Take the command 01 02 00 F4 00 01 F8 38 for example.F8114

Modbus addr.Functioncode

8914node addr.

Registeraddr.

Registernumber

CRC16

01 02 00 F 4 00 01 F8 38

Response 01 02 01 00 A1 88F8114

Modbus addr.Functioncode

Byte count IO status CRC16

01 02 0101(high level) 60 4800(low level) A1 88

Page 9: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

99

Part two

Transparent transmission between F8114(with data center)

and F8914

1. Configurations in F8114Data Service Center Settings

IP Modem Setting

Use ZIGBEEfunction

Page 10: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

1010

Zigbee setting

MODBUS Setting

Page 11: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

1111

2. Configurations in F8914

The debug level can be configure as 1 or 2 when you make the test, and the change to 0 when youput it into use.

The same as F8114

The same as F8114

Crossed configurationwith F8114

The lower baudrate,the longer interval

Page 12: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

1212

Part three

Modbus Protocol for GPIO&ADC Acquisition

Illustration of Terminal Blocks of F8114.

IO1: Digital input/output 0---3.3VIO2: Digital input/output 0---3.3VIO3: Digital input/output 0---3.3VIO4: Analog Current input 4---20mAIO5: Analog Current input 4---20mAChanges can be made in hardware to make IO4/IO5 as voltage input(0-5V).

IO Ports configurations in F8114Configure MODBUS work mode as Network RTU and configure the MODBUS address.

Page 13: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

1313

Configure analog and digital quantity work mode.

Send Modbus command from the DSC to F8114 to read the IO value.1. Configure IO1, IO2, IO3 as digital input and IO4, IO5 as analog input.

When IO1 is digital input,the register addr is OX20000 .When IO2 is digital input,the register addr is OX20001 .When IO3 is digital input,the register addr is OX20002 .When IO4 is analog input,the register addr is 0X40000 .When IO5 is analog input,the register addr is 0X40001 .

The examples are below.

Page 14: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

1414

When F8114 is connected to DSC. You can send Modbus command from DSC to read 8914 IOstatus. The commands and responses are as below.

To read IO1 status(digital input)Request: 01 02 00 00 00 01 B9 CAResponse:01 02 01 01 60 48 (IO1 is high level)Response:01 02 01 00 A1 88 (IO1 is low level)

To read IO2 status(digital input)Request: 01 02 00 01 00 01 E8 0AResponse:01 02 01 01 60 48 (IO2 is high level)Response:01 02 01 00 A1 88 (IO2 is low level)

To read IO3 status(digital input)Request: 01 02 00 02 00 01 18 0AResponse:01 02 01 01 60 48 (IO3 is high level)Response:01 02 01 00 A1 88 (IO3 is low level)

Notes of the modbus commands. Take the command 01 02 00 02 00 01 18 0A for example.F8114

Modbus addr.Functioncode

Register addr. Register number CRC16

01 02 00 02 00 01 18 0AResponse 01 02 01 01 60 48

F8114Modbus addr.

Functioncode

bytes Register status CRC16

01 02 01 01(high level) 60 4801 02 01 00 (low level) A1 88

To read IO4 value(analog input)Request: 01 04 00 00 00 01 31 CAResponse:01 04 02 00 B8 B9 42 (current input 4mA)Response:01 04 02 02 B9 79 E2 (current input 15mA)Response:01 04 02 03 A3 F9 B9 (current input 20mA)

To read IO5 value(analog input)Request: 01 04 00 01 00 01 60 0AResponse:01 04 02 00 B8 B9 42 (current input 4mA)Response:01 04 02 02 BD 78 21 (current input 15mA)Response:01 04 02 03 A8 B8 7E (current input 20mA)

Page 15: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

1515

Notes of the modbus commands. Take the command 01 04 00 01 00 01 60 0A for example.Modbusaddr.

Functioncode

Register addr. Register number CRC16

01 04 00 01 00 01 60 0A

Response 01 04 02 00 B8 B9 42Modbusaddr.

Functioncode

Bytecount

Acquisitionvalue

CRC16

01 04 02 04 B8 B9 42

The acquisition value in HEX. You need to convert it to DEC and calculate with the formulabelow. And then calculate the pratical value according to the measuring range of the sensor.Current type: 3.3/1023 *acquisition value/150 *1000= (mA)Voltage type: 3.3/1023 *acquisition value/12.1*20.16= (V)(The acquisition value should be converted to DEC first)

2. Configure IO1, IO2, IO3 as digital output.

When IO1 is digital output,the register addr is OX50000 .When IO2 is digital output,the register addr is OX50001 .When IO3 is digital output,the register addr is OX50002 .

To set IO1 high/low level(digital output)Request: 01 05 00 00 FF 00 8C 3A (to set high level)Response:01 05 00 00 FF 00 8C 3ARequest: 01 05 00 00 00 00 CD CA (to set low level)Response:01 05 00 00 00 00 CD CA

Page 16: Communication between F8114 and F8914(Modbus+Zigbee)

Xiamen Four-Faith Communication Technology Co., Ltd.

Xiamen Four-Faith Communication Technology Co.,Ltd.Add:J1-J3,3rd Floor,No.44,GuanRi Road,SoftWare Park,XiaMen .361008.Chinahttp://www.fourfaith.com Tel:+86 592-6300326 6300325 6300324 Fax:+86 592-5912735

1616

To set IO2 high/low level(digital output)Request: 01 05 00 01 FF 00 DD FA (to set high level)Response:01 05 00 01 FF 00 DD FARequest: 01 01 00 01 00 01 AC 0A (to set low level)Response:01 01 00 01 00 01 AC 0A

To set IO3 high/low level(digital output)Request: 01 05 00 02 FF 00 2D FA (to set high level)Response:01 05 00 02 FF 00 2D FARequest: 01 05 00 02 00 00 6C 0A (to set low level)Response:01 05 00 02 00 00 6C 0A

Notes of the modbus commands. Take the command 01 05 00 00 FF 00 8C 3A for example.Modbusaddr.

Functioncode

Register addr.Set high/low

levelCRC16

01 05 00 00FF 00 8C 3A00 00 CD CA

3. Wiring method of sensorAnalog inputa. Single-wire: Connect the analog output of the sensor to the analog input(IO4/IO5) of F8114directly.b. Double-wire: Connect the positive of analog output of the sensor to the analog input(IO4/IO5)of F8114, and connect the ground wire to GND(PIN2) of F8114.

Digital inputa. Low level input:Connect the input of contact switch to GND of F8114, and connect the outputof contact switch to the digital output of F8114(IO1/IO2/ 1O3).b. High level input:Connect 3.3V voltage output to IO1/IO2/ IO3, and connect the ground wire toGND of F8114.