COMMERCIAL HVAC PACKAGED EQUIPMENT Split...

81
Copyright © Carrier Corp. 2005 COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems Technical Development Program PRESENTED BY: Ray Chow Sigler

Transcript of COMMERCIAL HVAC PACKAGED EQUIPMENT Split...

Copyright © Carrier Corp. 2005

COMMERCIAL HVACPACKAGED EQUIPMENT

Split Systems

Technical Development Program

PRESENTED BY:

Ray Chow

Sigler

Copyright © Carrier Corp. 2005

Section 7 Summary

Section 6 Installation

Section 5 Controls

Section 4 Accessories

Section 3 System Components

Section 2 System Basics

Section 1 Introduction

Menu

Copyright © Carrier Corp. 2005

SECTION 1

Introduction

SPLIT SYSTEMS

Copyright © Carrier Corp. 2005

Objectives• Identify applications that utilize

the strengths of split systems

• Identify the components of split systems

• Understand the impact codes have onsystem application and selection

• Compare the differences in outdoorand indoor unit types

• Understand key installation issues

Section 1 – Introduction

Copyright © Carrier Corp. 2005

Split Systems Components

Section 1 – Introduction

Condensing Unit

Indoor UnitAHU (Fan Coil)

Indoor UnitFurnace And Coil

Copyright © Carrier Corp. 2005

Split Systems

• Residential to large commercial

• ¾ to 120+ tons

• Applications– Cooling only– Cooling with heat– Heat pump– Furnace with coil

• Utilize packaged products in an applied manner

Section 1 – Introduction

Copyright © Carrier Corp. 2005

• ARI has categories for air, evaporative or water-cooled• Plus 4 ARI heat pump categories (not shown)

• 5 ARI cooling split system categories

ARI System Classification

FanEvapCompCond

Single Package

Split Systems

Section 1 – Introduction

FanEvapComp

Cond+

RemoteCondenser

Cond+Fan

EvapHeat

Comp

Year RoundRemote Condenser

EvapCompCond+

Condensing Unitwith Coil

EvapCompCond+

Fan

Condensing Unitwith Coil + Fan

Cond+EvapHeat Comp

Fan

Year Round Condensing Unitwith Coil + Fan

Copyright © Carrier Corp. 2005

SECTION 2

System Basics

SPLIT SYSTEMS

Copyright © Carrier Corp. 2005

Liquid LineWarm-Temp., High-Pressure Liquid

Suction LineLow-Temp., Low-Pressure Vapor

FilterDrier

Indoor Unit

Outdoor Unit

Split System Basics

SightGlass

Liquid LineSolenoid Valve

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Why Use a Split System?

Flexibility• Aesthetics

• Duct design

• Performance

• Zoning

Section 2 – System Basics

Copyright © Carrier Corp. 2005

• Mix and match indoor and outdoor units

• Closely match load requirements

• Use only manufacturer’sapproved combinations

Flexibility

10-ton condensing unit12½-ton AHU

10-ton AHU

OR

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Residential & Duct Free Systems

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Condensing units include:• Controls

• Compressors

• Condenser Coil

Condensing Units

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Typical Condensing Units

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Typical Indoor Unit

Cased Evaporator Coils Packaged AHU

Central Station AHU

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Heat Pump System

Outdoor Unit• Condenser in cooling• Evaporator in heating

Indoor Unit• Evaporator in cooling• Condenser in heating

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Refrigerant Circuits

Single Circuit

Dual Circuit

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Indoor Unit – Refrigerant Circuits

Section 2 – System Basics

Single Circuit

TXV

LIQUIDLINE

Distributor

LIQUIDLINE

TXV

Filter Drier

Solenoid

Distributor

Dual Circuit

Copyright © Carrier Corp. 2005

ARI Standards

Section 2 – System Basics

Standard #

210/240

340/360

365

Applies to

Unitary Air Conditioners

Air Source UnitaryHeat Pumps (Air-Cooled)

Unitary Air Conditioners

Air Source UnitaryHeat Pumps (Air-Cooled)

Air ConditioningCondensing Units

Capacity Range

<65,000 Btuh

<65,000 Btuh

65,000 to <250,000 Btuh

65,000 to <250,000 Btuh

>135,000 to <250,000 Btuh

Copyright © Carrier Corp. 2005

EER

)()(

WattsInputPowerTotalBtuhCapacityEER =

11.2EER25.9290EER

kW3.1)(22.8MBtuh290EER

(Watts)InputPowerTotal(Btuh)CapacityEER

=

=

+=

=

Example 25-ton condensing unit @ ARI conditions

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Net vs. Gross Capacity

HeatIFMCapacityGrossCapacityNet

InputPowerTotal(Btuh)CapacityNetEERSystem

-=

=

Section 2 – System Basics

Copyright © Carrier Corp. 2005

BHP Required

Interpolate to derive bhp for 0.44 in. wg

bhp @ 0.44 in. wg = 4.00 bhp

AHU Size Airflowcfm

External Static Pressure (in. wg)0.0 0.2 0.4 0.6

rpm bhp rpm bhp rpm bhp rpm bhp028 10,000 615 3.12 641 3.36 692 3.87 743 4.41

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Btuh274,12Watts

Btuh3.414Watts3,595

Watts3,595HeatIFM

0.83746)(4.00HeatIFM

EfficiencyMotor746)(bhpHeatIFM

=*

=

*=

*=

IFM Heat

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Net Capacity

Net Capacity = Gross Capacity – IFM Heat

Net Capacity = 294 – IFM Heat

Net Capacity = 282 MBtuh

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Total Power Input

Now calculate Total Power Inputusing data from previous slides

( )EfficiencyMotor

746bhpmotorperpowerOFM *=

Section 2 – System Basics

kW29.5InputPowerTotalkW3.1kW3.6kW22.8InputPowerTotal

powerODFpowerIFMpowerCompressorInputPowerTotal

=++=

++=

Copyright © Carrier Corp. 2005

9.6EERSystem

kW29.5MBtuh282EERSystem

InputPowerTotalCapacityCoolingNetEERSystem

=

=

=

System EER

System EER for the 25-ton example system:

Section 2 – System Basics

Copyright © Carrier Corp. 2005

SEER

Applies to:– Single phase power only– Capacity less than 60 MBtuh

Calculated at three conditions and cycle test:– 80/67° F return air, 95° F outdoor air– 80/67° F return air, 82° F outdoor air– 80/57° F return air, 82° F outdoor air– 80/57° F cycle test, 82° F outdoor air

Requires laboratory testing and is not calculated in the field.

Section 2 – System Basics

Copyright © Carrier Corp. 2005

FOR ALL 3 Æ AND WATER-COOLED UNITS ANDAIR-COOLED UNITS ABOVE 60 MBH CAPACITY

• Evaluate equipment efficiency at less than full capacity

• Applicable only to equipment withmore than one stage of capacity

• Weighted average of EERat each capacity step

• Equipment with greater number of capacity steps can moreclosely match the load requirements of the space

• Unless equipment is always operated at 100%capacity, a higher IPLV is preferred

IPLV

Section 2 – System Basics

PARTLOADFACTORCURVE

Copyright © Carrier Corp. 2005

Coefficient of Performance

• Applies to heat pumps that operate on 3-phase power only

• Measures efficiency while operating in the heating mode

• A higher COP indicates a more efficient heat pump

)()(

WattsInputPowerTotalWattsCapacityNetCOP =

Section 2 – System Basics

Copyright © Carrier Corp. 2005

HSPF:• Applies to heat pumps that operate on single phase power

and have a cooling capacity of < 5.5 tons only

• Is similar to SEER in that it measures the seasonallyadjusted efficiency of a heat pump

• Accounts for defrost and required electric heat

• A higher HSPF is a more efficient heat pump

Heating Seasonal Performance Factor

Section 2 – System Basics

Copyright © Carrier Corp. 2005

Energy Codes

Section 2 – System Basics

Many codes rely on ASHRAE 90.1 thatsets minimum efficiency requirements.

Air-Cooled Split System Requirements• Performance requirements

< 65,000 Btuh 10.0 SEER 1Ø≥ 65,000 – < 135,000 Btuh 10.3 EER≥ 135,000 – < 240,000 Btuh 9.7 EER≥ 240,000 – < 760,000 Btuh 9.5 EER / 9.7 IPLV≥ 760,000 Btuh 9.2 EER / 9.4 IPLV

• Control requirements• Motor hp limits• Economizer requirements• Heat pump requirements

Copyright © Carrier Corp. 2005

IAQ and Sustainability

Section 2 – System Basics

• IAQ – ASHRAE 62– Limits maximum humidity to less than 65%– Indoor unit condensate control– Indoor unit ventilation capability

• Sustainable Design – LEED™– Require meeting ASHRAE 90.1 efficiency

and ASHRAE 62 IAQ features– Optimized energy performance and IAQ

Split System mix and matches providebetter humidity control and flexibility

to meet these requirements

Copyright © Carrier Corp. 2005

SECTION 3

System Components

SPLIT SYSTEMS

Copyright © Carrier Corp. 2005

Rules of Thumb

Section 3 – System Components

Rules of Thumb are considered to be guidelines only• Airflow:

- 400 cfm per nominal ton- Range of 300 to 500 cfm per ton- Today, 350 cfm per ton may be more

appropriate• Mix and Match:

- Nominal and one size up,sometimes one size down,others depend (consult the manufacturer)

• Line Length:- Keep them at 100 ft or less

Copyright © Carrier Corp. 2005

Operating LimitsCooling only equipment:Maximum outdoor air temperatureMinimum return air temperatureMaximum return air temperatureSaturated suction temperature rangeMaximum discharge superheatMinimum discharge superheat

Typical saturated suction temperature rangefor air conditioning duty is 40 to 50° F

Heat Pumps:Maximum outdoor air operating temperature in heatingMinimum outdoor air operating temperature in heating

115° F55° F95° F

25 to 55° F275° F60° F

75° F–20° F

Section 3 – System Components

Copyright © Carrier Corp. 2005

Outdoor Units

Residential1½ to 5 ton

Duct Free¾ to 5 ton

Commercial6 to 100+ ton

Section 3 – System Components

Copyright © Carrier Corp. 2005

Semi-Hermetic Compressor

• Repairable

• CapacityControl

Section 3 – System Components

CylinderUnloader

Copyright © Carrier Corp. 2005

Multiple Compressors

Dual Semi-HermeticReciprocating

Dual Scroll

Section 3 – System Components

Copyright © Carrier Corp. 2005

Multiple Condensing Units

Dual Circuit Indoor Unit

1st Stage Condensing Unit

2nd Stage Condensing Unit

Section 3 – System Components

Copyright © Carrier Corp. 2005

Hot Gas Bypass

• Protects system in low load conditions• Prevents coil icing• Injects hot gas at indoor unit• Activates at minimum step of cooling only

Condenser

Evaporator

LiquidSolenoid

Valve

Hot GasSolenoid

Valve

Compressor

DischargeBypass Valve

Filter Drier

SightGlass

TXV

Section 3 – System Components

Copyright © Carrier Corp. 2005

Alternative Condensing Unit SolutionsWater-Cooled

Condensing Unit

To indoor coil

Compressor

From indoor coil

Triple-Split

Condenser

Section 3 – System Components

Copyright © Carrier Corp. 2005

Heat Pump System

Heating Mode

Accumulator

Compressor

4-WayValve

Bi-flowFilter Drier

OU

TDO

OR

CO

IL IND

OO

RC

OIL

Accurator

TXV with bypassCheck Valves

Section 3 – System Components

Bi-flowTXV

Copyright © Carrier Corp. 2005

Cooling Mode

Heat Pump System

Accumulator

Compressor

4-WayValve

FilterDrier

OU

TDO

OR

CO

IL IND

OO

RC

OIL

Accurator

Bi-flowTXV

Check Valves

Section 3 – System Components

TXV with bypass

Bi-flowFilter Drier

Copyright © Carrier Corp. 2005

Indoor Unit – Air Handler

6 to 30 ton Packaged AHUwith limited options

Central Station AHU

Section 3 – System Components

Copyright © Carrier Corp. 2005

IAQ Features

• Double-Wall

• Dual-Density Insulation

• Foil-Face Insulation

• UV-c Lamps

Double-Wall

Section 3 – System Components

UV-cLamps

Copyright © Carrier Corp. 2005

Constant Volume AHU

• Variable pitch pulleyis set at required airflowat first unit start-up

• Fan then operates ata constant speed

Section 3 – System Components

Copyright © Carrier Corp. 2005

VAV Application

VAV Terminal

Inlet Guide VanesVFD

COIL

MOTOR

SUPPLYFAN

Section 3 – System Components

Copyright © Carrier Corp. 2005

VAV Requirements

Indoor Unit• At least two circuits• Equipped with capacity control valve(s)

LIQUIDLINE

FilterDrier

CapacityControl

Solenoid TXVDistributor

SightGlass

Section 3 – System Components

Copyright © Carrier Corp. 2005

VAV Requirements

Outdoor Unit• Multiple stages of capacity

• Electric control of capacity stages

• Suction line accumulators

• Interface with VAV controller

Section 3 – System Components

Copyright © Carrier Corp. 2005

VAV Controller

• Typically controls discharge air temperature

• Controls:– Compressors– Stages of capacity– Fans

Section 3 – System Components

Copyright © Carrier Corp. 2005

Cased Evaporator Coils

Installed in duct“A” coil design, installed

on twinned furnaces

Section 3 – System Components

Copyright © Carrier Corp. 2005

Residential Coils

Cased Uncased

Section 3 – System Components

Copyright © Carrier Corp. 2005

SECTION 4

Accessories

SPLIT SYSTEMS

Copyright © Carrier Corp. 2005

Economizer

• “Free Cooling”

• Control types– Dry bulb– Enthalpy– Differential enthalpy– CO2

• Demand controlledventilation (DCV)

Return air

Outdoor air

Section 4 – Accessories

Copyright © Carrier Corp. 2005

Heating AccessoriesHot Water or

Steam Coil onPackaged AHU

Electric HeatAccessory onPackaged AHU

Section 4 – Accessories

Copyright © Carrier Corp. 2005

Furnaces

Horizontal Furnace

Twinned Furnaces

Section 4 – Accessories

with downstreamcooling coil

Copyright © Carrier Corp. 2005

Accessories

Plenum

Return AirGrille

Subbase

CondensateDrain

Section 4 – Accessories

Copyright © Carrier Corp. 2005

SECTION 5

Controls

SPLIT SYSTEMS

Copyright © Carrier Corp. 2005

Controls - ThermostatSimple control requirements:

• Indoor fan

• Outdoor fan(s)

• Compressor(s)

• Liquid line solenoid

Section 5 – Controls

Copyright © Carrier Corp. 2005

• Y2 initiates 2nd stage cooling

Two-Stage Thermostat• Y1 initiates 1st stage cooling

Section 5 – Controls

Copyright © Carrier Corp. 2005

Capacity Control Solenoid Valve

Section 5 – Controls

• Y2 opens the liquid linesolenoid valve

• Y1 initiates 1st stage coolingAND opens the liquid linesolenoid valve

Copyright © Carrier Corp. 2005

DDC Control

Section 5 – Controls

User Interface

Copyright © Carrier Corp. 2005

SafetiesOutdoor Unit

– High-pressure switch

– Low-pressure switch

– Discharge gasthermostat

– Oil pressure switch

– Cycle protection

– Compressor over-temperature protection

– Circuit breakers

Section 5 – Controls

Indoor Unit–Motor protection

–Airflow switch

Copyright © Carrier Corp. 2005

Low Ambient Control

• Proper operation of expansion device at low outdoor temps

• Minimum outdoor air operating temperature

• Maintain minimum SCT

• Low ambient controller – OFM motor controller

MINIMUM OUTDOOR-AIR OPERATINGTEMPERATURE

UNIT38AR

CONDTEMP

(F)

MINIMUMOUTDOOR TEMP

(F)

Std.With

Motormaster®Control

Z007Z008Z012

808080

353535

-20S012 80

803535

D012 80 35

Section 5 – Controls

Motormaster® Control

Copyright © Carrier Corp. 2005

Fan Cycling Pressure Switch

• Turn off #2 OFM motorwhen SCT falls too low

• DO NOT cycle #1 OFM motor on/off becausea speed control device is required

OFM Motor

Intermediate SeasonSCT Control Device

#2 #1

Section 5 – Controls

Copyright © Carrier Corp. 2005

Wind BafflesWind baffles may be required in areas ofsustained high winds, at least onthe windward side.

Section 5 – Controls

WINDBAFFLE

Copyright © Carrier Corp. 2005

SECTION 6

Installation

SPLIT SYSTEMS

Copyright © Carrier Corp. 2005

Power SupplyMinimum Circuit Ampacity (MCA)

determines required wire size

MCA = (1.25 * Current of largest motor)+ Sum of all other loads

MCA of a condensing unit = (1.25 * RLA of compressor)+ (FLA of OFM motors+ Control amps)

MCA of indoor unit with electric heat = (1.25 * FLA of largest motor)+ (1.25 * FLA of electric heater)+ Sum of all other loads

Section 6 – Installation

Copyright © Carrier Corp. 2005

MOCPDefines MAXIMUM size ofovercurrent protective device

A smaller device may be used, if nuisance trips are not a problem

MOCP = (2.25 * Current of largest motor) + Sum of all other loads

Round down to the next lower standard rating,but not lower than the MCA value

Section 6 – Installation

Copyright © Carrier Corp. 2005

• Fuse or Circuit Breaker

Protective Device

Section 6 – Installation

Usage defined by code and availability

• HACR Breaker

Copyright © Carrier Corp. 2005

CONDENSINGUNIT

Disconnect• Located within “line of sight”

• Field-installed or factory-supplied

• Fused or non-fused

Section 6 – Installation

Field-installed disconnect

Factory-installed disconnect

FUSEDDISCONNECTSWITCH

Copyright © Carrier Corp. 2005

Installation

• Consult manufacturer’s instructions

• Locate indoor and outdoor unitsas close together as possible

• Keep refrigerant pipingas short as possible

• Provide adequate clearancefor service access and airflow

Section 6 – Installation

Copyright © Carrier Corp. 2005

Sound

• Understand sound power (both indoor and outdoor)• Utilize sound reduction accessories when available• Consider the effect of sound when recommending

unit location• Isolate and support refrigerant tubing

Section 6 – Installation

Copyright © Carrier Corp. 2005

ElevationLIQUID LINE – 38AKS012-024 UNITS

UNIT38AKS

MAXALLOW.

LIFT(ft)

LIQUID LINE

Max Allow.Pressure

Drop(psi)

Max Allow.TempLoss(°F)

012014016024

65678287

7 2

NOTE: Data above is for units at 45° F saturatedsuction and 95° F entering air.

Section 6 – Installation

LIQUID LIFT

Copyright © Carrier Corp. 2005

Suction Riser

• Refrigerant velocity insuction riser must behigh enough to entraincompressor oil with therefrigerant

• Double suction riser orreduced diameter risermay be required

• Consult manufacturer’srecommendations

Section 6 – Installation

Copyright © Carrier Corp. 2005

Maximum Length of Refrigerant Piping

• Piping length depends on the application

• Heat pumps – 100 linear feet

• Consult manufacturer’s recommendations

Section 6 – Installation

Copyright © Carrier Corp. 2005

Long Lines Require:1. Liquid line solenoid valve(s)

LONG LINE = 75 LINEAR FEET OR LONGER

Lift vs. Run

Long Line Applications

Section 6 – Installation

LIFT

2. Suction line accumulator(s)

Copyright © Carrier Corp. 2005

SECTION 7

Summary

SPLIT SYSTEMS

Copyright © Carrier Corp. 2005

Summary

Section 8 – Summary

• Identified applications that utilize thestrengths of split systems

• Identified the components of split systems

• Discussed the impact that codes haveon system application and selection

• Compared the differences inoutdoor and indoor unit types

• Reviewed key installation issues

Copyright © Carrier Corp. 2005

Work Session 1

Work Session 1

SPLIT SYSTEMS

Work Session 1Multiple-choice questions may have more than one correct answer; identify all correct selections.

1. A typical commercial split system includes _______.

a) an indoor unit only c) an indoor and an out unit

b) a compressor, an indoor fan, an evapora- d) a compressor, an indoor fan, an evapo-tor and condenser as one or more rator and condenser as a packagesections

2. True or False? All commercial split systems are at least dual circuit. __________

3. True or False? Net capacity will always be greater than gross capacity. __________

4. SEER applies to _____

a. units which are cooling and heat single phase units under 65,000 Btuh

Copyright © Carrier Corp. 2005

Technical Development Program

Thank YouThis completes the presentation.

TDP-634 Split SystemsArtwork from Symbol Library used by permission ofSoftware Toolboxwww.softwaretoolbox.com/symbols