COMBINED FOUNDATION DESIGN (ACI 318-05)
Design For Combined Footing 1
Footing No. Left Overhang (m)
Right Overhang (m)
Length (m)
Width (m)
Thickness (m)
1 0.500 0.500 3.000 4.800 0.500
Page 1 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Footing No. Footing Reinforcement - Main Steel Top Main Steel Bottom Secondary Steel Top Secondary Steel Bottom
1 #16 @ 4749 mm c/c #16 @ 4749 mm c/c #16 @ 4800 mm c/c #16 @ 4800 mm c/c
Page 2 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Combined Footing 1
Input Data
Geometry of Footing
Column Dimensions
Pedestal
Column Dimensions
Pedestal
For Column 34
Column Shape : Rectangular
Column Length - X (Pl) : 0.00 m
Column Width - Z (Pw) : 0.00 m
Include Pedestal? Yes
Pedestal Shape : Rectangular
Pedestal Height (Ph) : 2.80 m
Pedestal Length - X (Pl) : 0.60 m
Pedestal Width - Z (Pw) : 0.60 m
For Column 28
Column Shape : Rectangular
Column Length - X (Pl) : 0.00 m
Column Width - Z (Pw) : 0.00 m
Include Pedestal? Yes
Pedestal Shape : Rectangular
Pedestal Height (Ph) : 2.80 m
Page 3 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Cover and Soil Properties
Concrete and Rebar Properties
Pedestal Length - X (Pl) : 0.60 m
Pedestal Width - Z (Pw) : 0.60 m
Length of left overhang : 0.50 m
Length of right overhang : 0.50 m
Is the length of left overhang fixed? Yes
Is the length of right overhang fixed? Yes
Minimum Width of footing (Wo) : 2.50 m
Maximum Width of Footing (Wo) : 9000.00 mm
Minimum Thickness of footing (Do) : 500.00 mm
Maximum Thickness of Footing (Do) : 1500.00 mm
Maximum Length of Footing (Lo) : 9000.00 mm
Length Increment : 50.00 mm
Depth Increment : 50.00 mm
Pedestal Clear Cover : 50.00 mm
Footing Clear Cover : 50.00 mm
Unit Weight of soil : 960.00 kg/m3
Soil Bearing Capacity : 78.00 kN/m2
Soil Surcharge : 0.00 N/mm2
Depth of Soil above Footing : 1.30 m
Depth of Water Table : 1.00 m
Unit Weight of Concrete 24.000 kN/m3
Compressive Strength of Concrete : 18.300 N/mm2
Yield Strength of Steel : 392.000 N/mm2
Minimum Bar Size : 6
Maximum Bar Size : 8
Minimum Bar Spacing : 50.00 mm
Maximum Bar Spacing : 250.00 mm
------------------------------------------------------
Page 4 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Design Calculations
Footing size calculations
Final footing dimensions are:
Reduction of force due to buoyancy = -11514.82 kgf
Minimum area required from bearing pressure,Amin = Pcritical/qmax : 12.87 m^2
Area from initial length and width,Ao = L x W: 7.50 m^2
Length of footing, L : 3.00 m
Width of footing, W : 4.80 m
Depth of footing, Do : 0.50 m
Area, A : 14.40 m^2
Length of left overhang, Lleft_overhang : 0.50 m
Length of right overhang, Lright_overhang : 0.50 m
------------------------------------------------------
Page 5 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Applied Loads - Allowable Stress Level
LC Axial (kgf)
Shear X (kgf)
Shear Z (kgf)
Moment X (kNm)
Moment Z (kNm)
-
Column Number : 1
4 10222.026 0.000 0.000 0.000 0.000
5 42901.379 0.000 0.000 0.000 0.000
-
Column Number : 2
4 10222.022 0.000 0.000 0.000 0.000
5 42898.562 0.000 0.000 0.000 0.000
Page 6 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Applied Loads - Strength Level
LC Axial (kgf)
Shear X (kgf)
Shear Z (kgf)
Moment X (kNm)
Moment Z (kNm)
-
Column Number : 1
4 10222.026 0.000 0.000 0.000 0.000
5 42901.379 0.000 0.000 0.000 0.000
-
Column Number : 2
4 10222.022 0.000 0.000 0.000 0.000
5 42898.562 0.000 0.000 0.000 0.000
Page 7 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Calculated pressures at four corners
If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise, to account for uplift, areas of
negative pressure will be set to zero and the pressure will be redistributed to remaining corners.
Summary of adjusted pressures at four corners
Load Case
Pressure at corner 1
(q1)
(kgf/m^2)
Pressure at corner 2
(q2)
(kgf/m^2)
Pressure at corner 3
(q3)
(kgf/m^2)
Pressure at corner 4
(q4)
(kgf/m^2)
Area of footing in
uplift (Au)
(sq. m)
5 7910.9153 7910.1328 7910.1328 7910.9153 0.00
5 7910.9153 7910.1328 7910.1328 7910.9153 0.00
5 7910.9153 7910.1328 7910.1328 7910.9153 0.00
5 7910.9153 7910.1328 7910.1328 7910.9153 0.00
Load Case
Pressure at corner 1 (q1)
(kgf/m^2)
Pressure at corner 2 (q2)
(kgf/m^2)
Pressure at corner 3 (q3)
(kgf/m^2)
Pressure at corner 4 (q4)
(kgf/m^2)
5 7910.9153 7910.1328 7910.1328 7910.9153
5 7910.9153 7910.1328 7910.1328 7910.9153
5 7910.9153 7910.1328 7910.1328 7910.9153
5 7910.9153 7910.1328 7910.1328 7910.9153
------------------------------------------------------
Page 8 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Check for stability against overturning:-
Load Case Moment X (kNm)
Moment Z (kNm)
Resisting Moment X
(kNm)
Resisting Moment Z
(kNm) Ratio X Ratio Z
4 0.000 0.000 1142.780 714.236 N/A 21046227.354
5 0.000 0.028 2680.966 1675.602 N/A 60656.672
------------------------------------------------------
Page 9 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Calculations of Footing Thickness
Footing thickness is calculated based on the ultimate load cases
Check for Punching Shear
Effective depth, deff, increased until 0.75*Vc Punching Shear Force
Punchng Shear Force, Vu = 36406.89 kgf
Effective depth, deff, increased until 0.75*Vc Punching Shear Force
Punchng Shear Force, Vu = 36404.64 kgf
Check for One-Way Shear
For Column 1
Total Footing Depth, Do = 0.50m
Calculated Effective Depth,deff = Do - clear cover - Db/2 : 0.44 m
For rectangular column, = Bcol / Dcol : 1
From ACI Cl.11.12.2.1, for column
4.18 m
Equation 11-33, Vc1 402957.28 kgf
Equation 11-34, Vc2 419940.15 kgf
Equation 11-35, Vc3 268638.19 kgf
Punching shear strength,Vc=
0.75 x minimum of (Vc1,Vc2,Vc3) 201478.64 kgf
0.75 * Vc > Vu hence, OK
For Column 2
Total Footing Depth, Do = 0.50m
Calculated Effective Depth,deff = Do - clear cover - Db/2 : 0.44 m
For rectangular column, = Bcol / Dcol : 1
From ACI Cl.11.12.2.1, for column
4.18 m
Equation 11-33, Vc1 402957.28 kgf
Equation 11-34, Vc2 419940.15 kgf
Equation 11-35, Vc3 268638.19 kgf
Punching shear strength,Vc=
0.75 x minimum of (Vc1,Vc2,Vc3) 201478.64 kgf
0.75 * Vc > Vu hence, OK
------------------------------------------------------
Critical load case for maximum shear force along the length of footing :
5
Critical Shear force,Vu For the critical load case: 7321.59 kgf
Point of occurance of Vu Critical one-way shear position: 1.244 m
From ACI c1. 11.3.1.1,Vc154389.76 kgf
Page 10 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
0.75 x Vc = 115792.32 kgf
Since 0.75 * Vc > Vu hence, OK
------------------------------------------------------
Page 11 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Design of flexure
Bottom Reinforcement
Top Reinforcement
Distribution Reinforcement
Critical load case : 4
Required Effective Depth : 0.44 m
, from ACI Cl.10.2.7.3 max[0.85-0.05x(Fc-4),0.65]= 0.8500
From ACI Cl. 10.3.2, 0.0204
From ACI Cl. 10.3.3, 0.0153
From ACI Cl. 7.12.2, 0.0020
Modular Ratio,m 25.2009
Ultimate Moment : 7.85 kNm
Point of occurrence of the ultimate moment along the length of footing :
0.48 m
Nominal Moment Capacity : 8.73 kNm
Required : 0.002000
Area of main steel required, As =
* W * deff :
7.44 in2
Critical load case : 4
Required Effective Depth : 0.44 m
, from ACI Cl.10.2.7.3 max[0.85-0.05x(Fc-4),0.65] 0.8500
From ACI Cl. 10.3.2, 0.0204
From ACI Cl. 10.3.3, 0.0153
From ACI Cl. 7.12.2, 0.0020
Modular Ratio,m 25.2009
Ultimate Moment : 25.05 kNm
Point of occurrence of the ultimate moment along the length of footing :
1.52 m
Nominal Moment Capacity : 27.84 kNm
Required : 0.002000
Area of main steel required, As = *
W * deff :
7.44 in2
Critical Moment for distribution steel : 92.0974 kNm
Nominal moment Capacity : 102.3304 kNm
Point of occurance of the critical moment : 0.5000 m
Required : 0.000444
Area of distribution steel required, As = * L *
deff :
4.65 in2
Provided minimum Area for distribution steel along Z(Top reinforcement), Astmin = 0.18% of
c/s :
4.65 in2
Page 12 of 13Strip Footing Design
6/3/2011file://C:\Staad.foundation 5\CalcXsl\Combined.xml
Provided Reinforcement
Based on spacing reinforcement increment; provided reinforcement is
Based on spacing reinforcement increment; provided reinforcement is
Based on spacing reinforcement increment; provided reinforcement is
Based on spacing reinforcement increment; provided reinforcement is
Main bar no. for top Reinforcement: 16
Spacing of top reinforcement bar : 187.65 mm
# 16 @ 4749 mm o.c.
Main bar no. for bottom Reinforcement: 16
Spacing of bottom reinforcement bar : 187.65 mm
# 16 @ 4749 mm o.c.
Distribution bar no.: 16
Spacing of distribution bars : 190.00 mm
# 16 @ 4800 mm o.c.
Distribution bar no.(Top): 16
Spacing of distribution bars(Top) : 190.00 mm
# 16 @ 4800 mm o.c.