Colstrip Transmission Study Update - Montana...
Transcript of Colstrip Transmission Study Update - Montana...
![Page 1: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/1.jpg)
Cameron Yourkowski Policy Manager 9/22/16
Colstrip Transmission Study Update: Answering the technical questions about using the Colstrip transmission system for new resources. Prepared for: Montana Wind and Transmission Working Group
![Page 2: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/2.jpg)
Overview • Caveats and Disclaimers • Background • Previous Studies and Conclusions • 2016 NTTG Study Request • Remedial Action Schemes (RAS) • Synchronous Condensers • Discussion
![Page 3: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/3.jpg)
Renewable Northwest • Established in 1994 as the Renewable Northwest Project • Mission to promote the expansion of environmental responsible
renewable energy resources in the Northwest • Staff of 10 experts in regional energy policy across the
spectrum from generation and transmission to distributed resources, integration, and storage
• Nearly 60 member organizations across the spectrum from industry to advocacy, for-profit to non-profit
![Page 4: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/4.jpg)
Caveats and Disclaimers:
![Page 5: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/5.jpg)
Background:
• Frequencyresponse,transientstability:• Tripping• Exis8ngATRatColstrip
• Voltagesupport,iner8a,weakgridissues
![Page 6: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/6.jpg)
Previous Studies #1: NTTG 2014-15 Public Policy Study Ques%on:
• LookedatacasewhereColstrip1&2arere8red• 610MWofnewwindwasbuilt.• Two305MWwindplantscapableofbeing
trippedindividually.• ConnectedatBroadview
• Steady-statepowerflowanalysisonly!• AssumedATRwouldpreformthesameastoday.
![Page 7: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/7.jpg)
NTTG 2014-15 Public Policy Study Conclusion:
“Underidealis'ccondi+ons,itmaybepossiblethattwo305MWsourcesofwindgenera+on…....mightreplacethenetoutput(610MW)ofthecoal-firedgenera+onatColstrip.However,givenaColstrip1and2plantre+rement,itisverylikelytheresponseoftheATRmaychange.Theresultsofthisanalysisdonotsuggestorimplythataone-for-onesubs'u'onofwindforcoalisfeasiblewithoutfurtheranalysis.”(March,2015)
![Page 8: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/8.jpg)
Previous Studies # 2:Northwestern Energy “EPA 111-D Consideration:
Retirement of CS units 1&2”
Ques8on:
• LookedatacasewithColstrip1&2re8red• Includedvariousreplacementscenarios:
• Allwind(300MW)• Allgas(300MW)• Wind(300MW)andgas(300MW)mix• Broadview,Colstrip,andAlkaliCreekinterconnec8ons
• Didthesteady-stateandthedynamicanalysis.
![Page 9: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/9.jpg)
Northwestern Energy “EPA 111-D Consideration: Retirement of CS units 1&2”
Conclusion:• “Thetransmissionsystemrespondedsimilarlytooutagesforalleight
cases,bothsteady-stateanddynamically,andwascapableofachieving2200MWofexportsonPath8.”
• “Thepathcapacitywouldnotchangeandfrequencyconcernswouldlessen.”
• “Theaddi8onofanalternateresourceinplaceofcoalwillhaveaneffect
ontheresponseoftheATRandmayverywellnecessitatethedesignofanewRAS.”
• “Again,theseresultneithersuggestnorimplythataone-for-onesubs%tu%onofcoalatColstripforanothertypeofgenera%onisfeasiblewithoutfurtherstudyorpossiblesystemupgrades.”(April,2015)
![Page 10: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/10.jpg)
http://www.nrel.gov/docs/fy15osti/62906.pdf
Previous Studies #3:Western Wind and Solar Integration Study Phase 3 (NREL)
Ques8on:• HighmixofwindandsolararoundtheWECC,
includingMontana• Lookedathighpenetra8onsofrenewables
withandwithoutoneoftheColstripunitsrunning
• Stabilityanalysis,three-phasefaultattheBroadview500KVbus.
![Page 11: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/11.jpg)
http://www.nrel.gov/docs/fy15osti/62906.pdf
Previous Studies #3:Western Wind and Solar Integration Study Phase 3 (NREL)
Conclusion:• “Theanglechangeshowsthattheaccelera8onofthe
[Colstrip]unitsislowerintheHi-Mixcase,asignificantconsidera8onbecauseofthespecializedtypeofstabilityprotec8onusedthere[ATR].”
• “ThisresultsuggeststhatstabilityisnotdegradedintheHi-
Mixcase,andarguablyisslightlyimproved…...Butitdoesnotshowconclusivelythatthestabilitywillinevitablyimprove.” (April,2015)
![Page 12: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/12.jpg)
Current 2016 NTTG Study Request: • Scenario with CS Units 1,2,& 3
retired. • Includes dynamic stability
analysis. • Replace with wind (1494 MW): – 250 MW Natural Gas – Synchronous Condenser
• Results mid-2017
![Page 13: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/13.jpg)
Additional Data Points: • WhatisthecostofanewRAS?
• PreviousNWEInterconnec8onStudies--$1-4M• (Projects#31,99,101,and115)
• WhatisthecostofaSynchronousCondenser?• ERCOT2014Studynew200MVASC=$43M• FirstEnergyconver8ng1257MWcoalplantto5synchronous
condensersfor$60M• Includinga“clutch”ongasplantscanprovideiner8aandvoltage
supporttothegridevenwhentheyarenotgenera8ng.• Capabilityofmodernwindturbines:
• Synthe8ciner8alresponse• Voltagesupportevenwhennotgenera8ng
• “Poten8alMi8ga8onofDynamicReliabilityChallengeswithHighLevelsofVariableEnergyResources,”GEEnergyConsul8ng,WesternInterstateEnergyBoard.April,2015
![Page 14: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/14.jpg)
Going Forward: • There is a need for clear and complete studies
form experts about the challenges and the solutions for transitioning all or part of the CTS to carry new resources. • At what point do we face which problems. • What are the solutions and the expected costs.
![Page 15: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/15.jpg)
How do we get there: • Robust NTTG 2016 Study Report • BPA and NWE working together • Leadership to drive results
![Page 16: Colstrip Transmission Study Update - Montana DEQdeq.mt.gov/Portals/112/Energy/EnergizeMT/Renewables/Documents/Wi… · Colstrip Transmission Study Update: ... • Including a “clutch”](https://reader031.fdocuments.in/reader031/viewer/2022030808/5b16ce9b7f8b9a4a6d8df10a/html5/thumbnails/16.jpg)
Questions and Discussion: