Coils Catalogue - ecogroup.com Catalogue. Contact our technical staff ... eco coil code E Direct...

28
Partnerships beyond metals A02 Coils Catalogue Coils Catalogue

Transcript of Coils Catalogue - ecogroup.com Catalogue. Contact our technical staff ... eco coil code E Direct...

Partnerships beyond metals

A02

Coils CatalogueCoils Catalogue

Contact our technical staffto customize your coilin compliance to your project's specific requirementsand for any further informationand details on this geometry,its potentialityand possible applications.

4

Header

End plate

Outlet tube

Expanded collar

Inlet connection tube

Straight tube

Hairpin bend

Fin collar

Hairpin bend side

Return bend side

Return bend

Distributor

Bottom plate

Capillary tube

Fin

Base terminology

5

Number of tubes per circuit

Row

Number of rows Fin spacing

Tube spacing

Row spacing

Number of tubes per row Finned pack length

Number of circuits

Coil dimensions

6

Number of circuits

Position of connections

Air flow directionO Horizontal V Vertical T Horizontal and Vertical

Type of installation

Fin spacing (1/10 mm)

Finned pack length (mm)

Number of rows

Number of tubes per row

Fin material

Fin type

eco coil code

E Direct expansion

C Condensation

R Reversible E/C

W Cold or warm water

H Overheated water

S Steam

S Tinned copper

H Hydrophilic Aluminium

A Aluminium

C Copper

P Pre-painted Aluminium

0712071307220812

0816081708220825

1012101610191022

1025102610351226

13321335

7

Position of connection

Primary liquid inlet

Air flow direction

Type of installation

Connection scheme

8

00771122Geometry 0712 - Ø 7,2 mm tube

Rated tube diameters: Ø 7,2 mm

Tube configuration: StaggeredTube spacing: 25,0 mm Tube material: Copper

Fin type: Corrugated - LouveredRow spacing: 12,5 mm

Fin material: AluminiumFin spacing: From 1,2 to 4,2 mm

Special fin profiles

Main applications

Technical features

Residential AC Automtive AC Heavy vehicle AC

Luvered fin

9

00771133Geometry 0713 - Ø 7 mm tube

Rated tube diameters: Ø 7 mm

Tube configuration: StaggeredTube spacing: 21,0 mm Tube material: Copper

Fin type: CorrugatedRow spacing: 12,7 mm

Fin material: AluminiumFin spacing: From 1,2 to 2,8 mm

Main applications

Technical features

Residential AC Automtive AC Heavy vehicle AC

Refrigerated Transport

10

00772222Geometry 0722 - Ø 7,2 mm tube

Rated tube diameters: Ø 7,2 mm

Tube configuration: StaggeredTube spacing: 25,0 mm Tube material: Copper

Fin type: CorrugatedRow spacing: 21,65 mm

Fin material: AluminiumFin spacing: From 1,6 to 6,0 mm

Main applications

Technical features

Commercial AC Residential AC Automtive AC

Heavy vehicle AC Refrigerated Transport Commercial refrigeration

11

00881122Geometry 0812 - Ø 5/16" tube

Rated tube diameters: Ø 5/16”

Tube configuration: StaggeredTube spacing: 25,0 mm Tube material: Copper - Aluminium

Fin type: CorrugatedRow spacing: 12,5 mm

Fin material: AluminiumFin spacing: From 1,2 to 3,0 mm

Main applications

Technical features

Residential AC Automtive AC Heavy vehicle AC

12

00881166Geometry 0816 - Ø 5/16" tube

Rated tube diameters: Ø 5/16”

Tube configuration: StaggeredTube spacing: 25,4 mm Tube material: Copper - Aluminium

Fin type: CorrugatedRow spacing: 15,88 mm

Fin material: AluminiumFin spacing: From 1,5 to 3,9 mm

Main applications

Technical features

Residential AC Automtive AC Heavy vehicle AC

13

00881177Geometry 0817 - Ø 5/16" tube

Rated tube diameters: Ø 5/16”

Tube configuration: StaggeredTube spacing: 20,0 mm Tube material: Copper - Aluminium

Fin type: CorrugatedRow spacing: 17,32 mm

Fin material: AluminiumFin spacing: From 1,2 to 4,2 mm

Main applications

Technical features

Residential AC Automtive AC Heavy vehicle AC

14

11001122Geometry 1012 - Ø 3/8" tube

Rated tube diameters: Ø 3/8”

Tube configuration: StaggeredTube spacing: 25,0 mm Tube material: Copper - Aluminium

Fin type: CorrugatedRow spacing: 12,5 mm

Fin material: Aluminium - CopperFin spacing: From 1,2 to 3,5 mm

Main applications

Technical features

Automtive AC Heavy vehicle AC Refrigerated Transport

Industrial process cooling

15

11001166Geometry 1016 - Ø 3/8" tube

Rated tube diameters: Ø 3/8”

Tube configuration: StaggeredTube spacing: 25,4 mm Tube material: Copper - Aluminium

Fin type: CorrugatedRow spacing: 15,88 mm

Fin material: AluminiumFin spacing: From 1,5 to 4,2 mm

Main applications

Technical features

Air heaters Fan coils Automtive AC

Heavy vehicle AC Industrial AC Commercial refrigeration

16

11001199Geometry 1019 - Ø 3/8" tube

Rated tube diameters: Ø 3/8”

Tube configuration: StaggeredTube spacing: 25,4 mm Tube material: Copper

Fin type: CorrugatedRow spacing: 19,05 mm

Fin material: AluminiumFin spacing: From 1,6 to 2,5 mm

Main applications

Technical features

Air heaters Fan coils Commercial AC

Refrigerated Transport Industrial process cooling Industrial refrigeration

Industrial AC Commercial refrigeration

17

11002222Geometry 1022 - Ø 3/8" tube

Rated tube diameters: Ø 3/8”

Tube configuration: StaggeredTube spacing: 25,0 mm Tube material: Copper - Aluminium

Fin type: Corrugated - LouveredRow spacing: 21,65 mm

Fin material: Aluminium - CopperFin spacing: From 1,2 to 6,0 mm

Special fin profiles

Main applications

Technical features

Air heaters Fan coils Commercial AC

Residential AC Air handling units Automtive AC

Heavy vehicle AC Refrigerated Transport Industrial process cooling

Industrial refrigeration Industrial AC Commercial refrigeration

Waved lanced fin

Louvered fin

Waved fin

Intake fin

18

11002255Geometry 1025 - Ø 3/8" tube

Rated tube diameters: Ø 3/8”

Tube configuration: In lineTube spacing: 25,0 mm Tube material: Copper - Aluminium

Fin type: Corrugated - PlainRow spacing: 25,0 mm

Fin material: Aluminium - CopperFin spacing: From 1,6 to 6,0 mm

Special fin profiles

Main applications

Technical features

Air heaters Fan coils Refrigerated Transport

Industrial refrigeration Industrial AC No frost

Commercial refrigeration Display cabinets evaporators

Plain fin

19

11002266Geometry 1026 - Ø 3/8" tube

Rated tube diameters: Ø 3/8”

Tube configuration: StaggeredTube spacing: 30,0 mm Tube material: Copper

Fin type: Corrugated - PyramidalRow spacing: 25,98 mm

Fin material: AluminiumFin spacing: From 1,2 to 3,2 mm

Special fin profiles

Main applications

Technical features

Commercial AC

Pyramidal fin

20

11003355Geometry 1035 - Ø 3/8" tube

Rated tube diameters: Ø 3/8”

Tube configuration: In lineTube spacing: 35,0 mm Tube material: Copper

Fin type: PlainRow spacing: 35,0 mm

Fin material: AluminiumFin spacing: From 3,0 to 12,0 mm

Main applications

Technical features

Display cabinets evaporators

21

11222266Geometry 1026 - Ø 3/8" tube

Rated tube diameters: Ø 12 mm

Tube configuration: StaggeredTube spacing: 30,0 mm Tube material: Copper

Fin type: Corrugated - PyramidalRow spacing: 25,98 mm

Fin material: AluminiumFin spacing: From 1,2 to 3,2 mm

Special fin profiles

Main applications

Technical features

Commercial AC Industrial process cooling Industrial refrigeration

Industrial AC

Pyramidal fin

22

11333322Geometry 1332 - Ø 1/2" tube

Rated tube diameters: Ø 1/2”

Tube configuration: StaggeredTube spacing: 37,5 mm Tube material: Copper

Fin type: Corrugated - IntakeRow spacing: 32,48 mm

Fin material: Aluminium - CopperFin spacing: From 1,6 to 10,5 mm

Special fin profiles

Main applications

Technical features

Air heaters Commercial AC Air handling units

Industrial process cooling Industrial refrigeration Industrial AC

Display cabinets evaporators

Intake fin

23

11333355Geometry 1335 - Ø 1/2" tube

Rated tube diameters: Ø 1/2”

Tube configuration: In lineTube spacing: 35,0 mm Tube material: Copper

Fin type: PlainRow spacing: 35,0 mm

Fin material: AluminiumFin spacing: From 3,0 to 12,0 mm

Main applications

Technical features

Display cabinets evaporators

24

3333,,3333xx2288,,887733,33x28,87 - Ø 1/2" tube

Rated tube diameters: Ø 1/2”

Tube configuration: StaggeredTube spacing: 33,33 mm Tube material: Copper - Stainless steel

Fin type: Sine form - PlainRow spacing: 28,87 mm

Fin material: Aluminium - CopperFin spacing: From 1,6 to 6,0 mm

Special fin profiles

Main applications

Technical features

Air heaters Air handling units Industrial process cooling

Industrial refrigeration Industrial AC

Plain fin

25

4400xx3344,,6644 Geometry 40x34,64 - Ø 15mm tube

Rated tube diameters: Ø 15 mm

Tube configuration: StaggeredTube spacing: 40 mm Tube mat.: Copper-Aluminium-Titanium

Fin type: Sine form - PlainRow spacing: 34,64 mm

Fin material: Aluminium - CopperFin spacing: From 1,8 to 10,0 mm

Main applications

Technical features

Air handling units Industrial process cooling Industrial refrigeration

Industrial AC

Special fin profiles

Plain fin

As a result of continuing research and design by our technical laboratories aimed at offering top quality and innovative products, the information given in this guidemay be subject to modification at any time without prior notice; it is up to the user to keep up to date on all possible modifications.

No part of this publication may be reproduced or duplicated without prior permission; we decline any responsibility for possible mistakes or omissions, and we reservethe right to make amendments deemed necessary, without prior notice and at any time.

II - edition, August 2009

CCOC0908A02EI

ProjectLuvata G&C dpt.

PicturesLuvata Heat Transfer Solutions Division

Archives

www.luvata.comHead Office: 33050 Pocenia (UD) Italy - Via Giulio Locatelli, 22tel. +39 0432 772 001fax +39 0432 779 594e-mail: [email protected]

About Luvata

Heat Transfer Solutions Division

Luvata is the leading global metals supplier of solutions, services, components and materials for the manufacturing and construction industries. Luvata’s solutionsare used in industries such as power generation, architecture, automotive, transport, medicine, air-conditioning, industrial refrigeration and consumer products.The company’s success can be attributed to its longevity, technological excellence and strategy of building partnerships beyond metals.

CCOC

0908

A02E

I