Co-ordination of LV Protection Devices DBTP107PRE-En-07/00 E58640.
-
Upload
corinne-fallick -
Category
Documents
-
view
228 -
download
7
Transcript of Co-ordination of LV Protection Devices DBTP107PRE-En-07/00 E58640.
Co-ordination of LV Protection Devices
DBTP107PRE-En-07/00
E58640
DBTP107PRE-En-07/00 2
Contents
Operator needs Availability of electrical energy 3
Co-ordination of LV protection devices 8
Co-ordination techniques 12 The IEC 60947-2 standard 12 Discrimination techniques 16 Limitation 21 Cascading 23
Schneider solutions 24 Masterpact and the incoming end of the installation 25 Compact NS and power distribution 30 Multi 9 circuit-breaker and final distribution 33 Discrimination rules for 1 to 6300 A 34
Conclusion 35
DBTP107PRE-En-07/00 3
From one application to anotheroperator needs are the same
…The availability of electrical energy...
60803
85293
61343
DBTP107PRE-En-07/00 4
The availability of electrical energy
Savings for the operator through:
the continuity of electrical supply
the optimised cost of his installation
…A source of profit for the operator... 60632
63647-7
62242
61485
DBTP107PRE-En-07/00 5
Availability of electrical energy and the LV protection plan
Structure of LV Distribution
Level 1 General LV= incomer Switchboard
Level 2= MSBfeeders
Distribution Level 3 Switchboard = power ordistribution motor
control
Level 4 Final = final distribution switchboards distribution
Loads
E62649
DBTP107PRE-En-07/00 6
Availability of electrical energyand the LV protection plan
Structure of LV Distribution
Installation design
priority / non priority feeders
Protection of LV distribution
level 1 and 2: using Air Circuit-Breaker (ACB) or
Moulded Case Circuit-Breaker (MCCB) with high rating
800 to 6300 A
level 3: using LV industrial Fuse or Moulded Case Circuit-Breaker (MCCB)
63 to 1250 A
level 4: using Miniature Circuit-Breaker (MCB)
1 to 100 A
DBTP107PRE-En-07/00 7
Customer needsContinuity ofelectrical energy supply
Cost of the electrical installation
Co-ordination of protection devices:
discrimination, cascading
& constraint limitation
Protection Plan
Availability of electrical energyand the LV protection plan
DBTP107PRE-En-07/00 8
LV co-ordination techniques
Optimising LV electrical distribution through 3 actions at the Protection Plan Level
1) discrimination to guarantee continuity of supply
2) limitation to reduce constraints
3) cascading to optimise performances
DBTP107PRE-En-07/00 9
Co-ordination of protection devices1) discrimination
Whatever the fault:
overload
short-circuit
insulation fault
only the circuit-breaker located just upstream from the fault trips
4 types of discrimination
current
time
energy
logic
E41139
a
A
CB
DBTP107PRE-En-07/00 10
Co-ordination of protection devices2) limitation
Technique that allow for the harmful effects of short-circuit currentsto be diminished
Limitation reduces effects of the following type: electromagnetic: reduction in EMC disturbances mechanical: reduction of deformation and/or breaks thermal: rise in the life span of trunkings
E62650
E62651
Isc presumed transient peak
Isc presumed steady peak
Isc limited peak
Isc
10 %
Â
tsc t
100 %
t
A2
I2sc
Presumedenergy 100 %
Limitedenergy< 1 %
1 %
100 %
DBTP107PRE-En-07/00 11
Co-ordination of protection devices3) cascading The limiting upstream circuit-breaker helps the downstream
circuit-breakers to open
Technique that allows for the cost of LV electrical distributionto be optimised
E62667
Non priorityfeeder
DBTP107PRE-En-07/00 12
The IEC 60947-2 standardand co-ordination of protection devices
Recognises the 2 co-ordination elements (appendix A) discrimination cascading
Defines testing to guarantee this co-ordination
Characterises the circuit-breakers capable of time discrimination utilisation category B
E55229
DBTP107PRE-En-07/00 13
The IEC 60947-2 standard appendix Adiscrimination
Definition of the discrimination limit Is
Tests to be conducted
E62654
E62653
DBTP107PRE-En-07/00 14
The IEC 60947-2 standard appendix Acascading
Definition of the current IB and of the reinforced breaking capacity IcuD2+D1 Tests to be conducted
E62680
E62681
DBTP107PRE-En-07/00 15
The IEC 60947-2 standardcategory B circuit-breakers They ensure time discrimination that is characterised by Icw during t Icw must be at least equal to 12 In or 5 kA for In 2500 A
30 kA for In > 2500 A t - standardised delay - of: 0.05 - 0.1 - 0.25 - 0.5 - or 1 s They are subjected to additional testing
E62652
DBTP107PRE-En-07/00 16
Quality of discrimination Comparison of the discrimination limit Is to the
presumed short-circuit current Isc determines the quality of discrimination
total discrimination: Is > Isc
partial discrimination: Is < Isc
if the discrimination limit is equal to the Icu of the upstream circuit-breakerdiscrimination is total
LV discrimination techniques
only D2 trips D1 and D2 trip
E62682
DBTP107PRE-En-07/00 17
Current discrimination
Linked to the natural staging of Long Delay curves of the association
discrimination limit Is = Isd1
discrimination technique generally used in Final Distribution
E62655
DBTP107PRE-En-07/00 18
Time delay t of the upstream circuit-breaker’s Short Delay CR tripping extension of current safety discrimination limit Is = Ii1 (= Icw1)
discrimination technique generally used on the incoming end of the installationthe upstream circuit-breaker is from category B with a high EDW (Icw1 = Icu1)
Time discrimination
E62683
DBTP107PRE-En-07/00 19
Comparison of energy curves (tripping D downstream/nontripping ND upstream) allows for the discrimination limit Is to be determined
Only the manufacturer can guarantee the quality of discriminationof the energy type
Energy discrimination
E62656
E68104
DTripping
NDNontripping
DBTP107PRE-En-07/00 20
Logic discrimination (ZSI)
Circuit-breakers fitted out with electronic trip units a pilot wire between upstream / downstream circuit-breakers no threshold rules
This technique is easily implemented reduces to a minimum constraints from delayed tripping of time discrimination
E62659
DBTP107PRE-En-07/00 21
Technique consists in using the arc voltage to limit short-circuit currents
3 criteria to be considered
early fast high
Technique that has multiple advantages limitation of constraints on the installation better discrimination circuit-breaker cascading
Limitation
I asymetricpeak
Isc
IL
E62660
early fast high
E68105
DBTP107PRE-En-07/00 22
The use of a limiting downstream circuit-breaker extends currentand/or time discrimination with the upstream circuit-breaker
The downstream circuit-breaker by limiting the fault current Id increasesthe discrimination limit Is
Improving discrimination through limitation
E62657
D2non limiting
D2limiting
Iscin D2
Isc (D2)presumed
Is
IsD2 limitingD2 non limiting
Is
DBTP107PRE-En-07/00 23
The use of a limiting upstream circuit-breaker “increases” the breaking capacity of the downstream circuit-breaker
Technique that allows for the installation of a limiting circuit-breaker downstream from circuit-breakers with optimised Breaking Capacities
Cascading
E62661
E62662
DBTP107PRE-En-07/00 24
Schneider solutions
Customer needs Continuity of electrical energy supply
Cost of the electrical installation
Discrimination as a standard in the circuit-breaker ranges
Economical association of circuit-breakers through Cascading
Totally co-ordonated Schneider protection
devices
Constraint Limitation
DBTP107PRE-En-07/00 25
Discrimination upstream: setting the long delay (LR) slope (IDMTL) allows for better discrimination
Discrimination downstream: better time discrimination
thanks to higher Icw on very high Isc (up to 150 kA),
maintains a high levelof discrimination
Limitation of very high constraints
Masterpact offers unequalled performances as a standard for all applications
Masterpact power circuit-breakers
E62663
DBTP107PRE-En-07/00 26
Improving MV/LV discrimination thanks to IDMTL curves
5 suggested slopes:
DT: definite time
SIT: inverse standard time
VIT: very inverse time
EIT: extremely inverse time
HVF: HV compatible fuse
E62664
HVF curvetr = 2 s
MV Fuse 80 Abrought to LV
I2t curvetr = 12 s
Short delaythreshold = 4 Ir
DBTP107PRE-En-07/00 27
Ensuring total time discrimination as a standard
Time discrimination with very high Icw (up to 85 kA 1s) thanks to:
a globally reinforced mechanism, enclosure, copper parts
the use of air CTs for measurement
Accuracy zone of the instantaneous tripping threshold(± 10 %)
Maximum time discrimination
Icw = thermal withstand = self-protection DIN threshold
E62675
E62676
NW H2
63047-7
DBTP107PRE-En-07/00 28
Increasing the breaking capacity without sacrificing discrimination
Conciliate high breaking capacity (150 kA) and high Icw (65 kA -1s) Disengagement
E62665
Kinematic chain
Half moon actvating the pole shaft
Effort sensor
E68106
61343
DBTP107PRE-En-07/00 29
Limiting as much as possible the constraints on the incoming end of the installation
Limitation using disengagement for very fast breaking modification of the fixed pole to increase the repulsion force
Time discrimination up to 37 kA
Unequalled performances for a limiting circuit-breaker
Breaking chamber
Magnetic U
U-shaped current loop
E62666
E68106
E62678
Total breaking time
Presumed short-circuitcurrent
Limited current
Intervention time
DBTP107PRE-En-07/00 30
New breaking technology roto-active breaking
Compact NS power distribution
053100
E62669
E62670
Fixed contact
Breakingenclosure
Breakingchamber
Breakingchamber
Mobile contact
Fixed contact
Piston
Short-circuit current
Breaking chamber
Arc
Arc
New breaking technology roto-active breaking pressure (“reflex” tripping)
E62670
E62669
Fixed contact
Breakingenclosure
Breakingchamber
Breakingchamber
Mobile contact
Fixed contact
Piston
Short-circuit current
Breaking chamberBreaking chamber
Short-circuit current
Provides an exceptional limiting capacity
Fixed contact
Breakingenclosure
Breakingchamber
Breakingchamber
Mobile contact
Fixed contact
E62670
E62669
Piston
DBTP107PRE-En-07/00 31
Natural discrimination
Compact NS circuit-breakers have natural discrimination performances
current and/or time tripping curves
natural discrimination energy curvesE62671
E62672
053100
DBTP107PRE-En-07/00 32
Compact NS circuit-breakers have natural Cascading performances
reflex tripping (piston)
Reinforced Breaking Capacity without loss of Discrimination
Simultaneous discrimination and cascading
E62673
053100
D1
D2
DBTP107PRE-En-07/00 33
Final distribution Multi 9 circuit-breakers
Technology with magnetic actuator
Guaranteed performances
ultra rapid breaking
exceptional limitation
total discrimination with circuit-breakers located upstream
E62674
031887
DBTP107PRE-En-07/00 34
Masterpact total discrimination with Compact NS (<630 A) circuit-breakers located
downstream
Compact NS total discrimination as soon as the ratio between ratings is greater than 2.5
Note: it is necessary to conserve current and time threshold staging
The Schneider solution ensures total natural discrimination from 1 to 6300 A
Schneider discrimination rules
DBTP107PRE-En-07/00 35
The Schneider solution: mastering the technique
Continuity of supply thanks to total discrimination
E62679
Compact NS1 to 160 A
CA
production
Recordingbox
Factory assembly line
DBTP107PRE-En-07/00 36
The Schneider solution: mastering the financial aspect Upon installation During operation
Thanks to the quality of limitation of these circuit-breaker ranges
E43481
E43480
DBTP107PRE-En-07/00 37
The Schneider solution: mastering services
Simple and high-performance tools
software: Ecodial 3
catalogue: Exhaustive choice table
E43477
E43478
E43476
LV Catalogue
DBTP107PRE-En-07/00 38
Schneider offers circuit-breaker ranges from 1 to 6300 A with unequalled performances
Standards are respected
Performance of co-ordinations: discrimination as a standard highly economical cascading
Simple and high-performance cataloguesand software
Schneider guarantees a safe and high-performance electrical installation for mastering the LV protection plan
“No one in the world does more with electricity”
CT150fi
E62677
056409
031887
053100E68107