CO Gas Cooler - NuernbergMesse

22

Transcript of CO Gas Cooler - NuernbergMesse

Page 1: CO Gas Cooler - NuernbergMesse
Page 2: CO Gas Cooler - NuernbergMesse

2

CO2 Gas Cooler: the keystone for efficiency

Katherina Pesenti – Product Manager

Page 3: CO Gas Cooler - NuernbergMesse

3

The Group

15 SALES COMPANIES

16 PRODUCTION FACILITIES

Over 3.200 skilled employees

Consolidated Turnover € 420 million

Listed on the Milan Stock Exchange

Page 4: CO Gas Cooler - NuernbergMesse

4

Markets

Industrial Cooling - Energy & PowerPower generation, Process cooling, Motor cooling

Air conditioningHVAC for buildings and industry units, Data Centres, Hospitals, Transport,Heat pumps, Telecommunications

Refrigeration (Commercial / Industrial)Commercial and industrial refrigeration, All freshconservation, Freezing processes,Foodstuff processes, Storage & Logistics, Seasoning, Display case units, Cabinet

units, Dispenser units, Ice makers, OEM

Page 5: CO Gas Cooler - NuernbergMesse

5

Rediscovering CO2

• CO2 (R-744) widely used as refrigerant in the early 20th century.

• 1930-1940 with the advent of the fluorocarbon chemicals its use almost disappeared

• 2000: Increasing focus on environmental issues created a strong interest in natural refrigerants.

GWP = 1

Not toxic nor flammable

Thermodynamic properties:

➢ High evaporation heat

➢ Low viscosity

High pressures

Low critical point

Page 6: CO Gas Cooler - NuernbergMesse

6

The CO2 challenge

The real challenge is to design plant with an

efficiency level equal or higher than current HFC plants.

1. Cost effectiveness

2. Avoid indirect pollution

TARGETS:

Page 7: CO Gas Cooler - NuernbergMesse

7

Our answer: research & development

CO2private test facility in EUROPE (2010)

Page 8: CO Gas Cooler - NuernbergMesse

8

Our answer: research & development

➢ Behaviour of the fluid during trans-critical cooling

➢ Influence of oil on internal heat exchange

➢ Calculate reliable product performances

CO2private test facility in EUROPE (2010)

Page 9: CO Gas Cooler - NuernbergMesse

9

CO2 Activities

2004 in EUROPE (Coop, Wettingen)

2015 in LATIN AMERICA (Carrefour, Colombia)

2016 in RUSSIA (Magnit, Voskresensk)

2018 in INDIA (INDEE project, Chennai)

2018 in MIDDLE EAST (Al-Salam, Amman)

2019 in ARABIAN GULF (Masdar City, Abu Dhabi)

Gas cooler with water spray system

CO2 worldwide transcritical installation

Page 10: CO Gas Cooler - NuernbergMesse

10

Gas cooler design

TARGETS:

1. High cycle COP Low CO2 outlet temperature

Energy efficient fan consumption2. Energy savings

Page 11: CO Gas Cooler - NuernbergMesse

11

Heat exchanger design

“co

unte

r flo

w”

RO

WS

CO2

AIR

COUNTER-FLOW

High number of ROWS

Reduce approach DT

Minimize the CO2 outlet temperature

HIGHER SYSTEM COP

Page 12: CO Gas Cooler - NuernbergMesse

12

Louvered fins

210,1

74,8

100,0

118,6

133,8

55,9

158,8

139,5

116,2

85,0

62,2

126,1

149,5

177,2

195,7

0

50

100

150

200

250

0,5 1 2 3 4air flow speed, V ( m/s)

smooth fin

waved fin

LU-VE fin

Thanks to the louvered fin is possible to increase the external heat transfer coefficient Hf up to 80%

Hf/ H

f2 m

/s

( re

f H

f= 1

00

fo

r sm

oo

th f

in a

nd

V=

2m

/s)

Page 13: CO Gas Cooler - NuernbergMesse

13

Louvered fins

LOUVERED FIN

• DT at the interface negligible:

< 4% parasitic heat transfer

• High DT at the interface:

> 35% parasitic heat transfer

Impact on gas cooler’s capacity 5-10%

FLAT FIN

Page 14: CO Gas Cooler - NuernbergMesse

14

Whisperer PLUS

New circular silencer that combines the following features:

• Soundproof material

• Conical shape → pressure recovery through diverging duct

➢ Noise level reduction

➢ Increase of the air flow @ same rpm

→ lower energy consumption

Page 15: CO Gas Cooler - NuernbergMesse

15

Whisperer PLUS

Model XAV9X 7923 with EC fans

6 x Ø 910 mm fans

L = ca. 7 m

-5 dB(A)-26%

XAV9X 7923Capacity

[kW]Rpm

Air quantity

[m3/h]

Power consumption

[W]

Sound level

[dB(A)]

No Whisperer 446 700 119.570 5.465 51

With Whisperer 446 650 119.570 4.340 46

Page 16: CO Gas Cooler - NuernbergMesse

16

Adiabatic pre-cooling

How to reduce CO2 outlet temperature in a gas cooler during the warmest days?

T

S

110°C

40°C

35°C

Transcritical conditions

30°C

Adiabatic pre-cooling is a smart choice.

The evaporation of the water on the pads cools down the air by humidifying it.

In this way it is possible to keep the CO2

pressure low and assure a high COP even during summer.

Page 17: CO Gas Cooler - NuernbergMesse

17

Adiabatic pre-cooling - CASE STUDY

Application: Supermarket

Location: Gorinchem (NL)

Year: 2018

Page 18: CO Gas Cooler - NuernbergMesse

18

Adiabatic pre-cooling - CASE STUDY

V-Shape gas cooler with adiabatic pads

Page 19: CO Gas Cooler - NuernbergMesse

19

Adiabatic pre-cooling - CASE STUDY

80 bar

7 August 2018: hottest day of the year

Average temperature: 38°C from 12 AM to 8 PM

Page 20: CO Gas Cooler - NuernbergMesse

20

Adiabatic pre-cooling - CASE STUDY

DRY GAS COOLER

CO2 pressure = 95 bar

CO2 out temp. = 40°C

CO2 pressure = 80 bar

CO2 out temp. = 32°C

COP = 1,5 COP = 2

~ 38°C amb. temp.

Page 21: CO Gas Cooler - NuernbergMesse

21

Conclusions

➢ Counter flow and high number of rows increase the heat exchanger efficiency

➢ Louvered fins not only increase the external heat transfer coefficient but also reduce the parasitic heat transfer to the minimum.

➢ The Whisperer decreases noise and energy consumption

➢ Adiabatic pre-cooling make transcritical CO2 suitable for warmer countries

Page 22: CO Gas Cooler - NuernbergMesse

Thank you for your attention.

22