    CL SERIES

    ROOFTOP CONDENSING UNITS

    INSTALLATION, SERVICE

    &

    OWNERS INFORMATION MANUAL

  • 7/29/2019 CL_IOM_070402

    2/54

    2

    TABLE OF CONTENTSSECTION Page

    GENERAL DESCRIPTIONUnpacking..

    0404

    OWNERS INFORMATION......................................

    Wiring Diagrams................................................

    General Maintenance..

    04

    04

    05INSTALLATION.....

    Lifting and Handling..

    Condenser Placement.

    Compressor Compartment Exhaust Fan.

    Mounting Isolation.Access Doors.

    Low Ambient Operation.

    LAC Valve..OROA Valve...

    ORI/ORD Valves

    Condenser Flooding

    Electrical.Refrigerant Piping Connection

    Evaporative-Cooled Condenser Field Piping Connections.

    05

    05

    05

    05

    0505

    05

    0607

    07

    08

    0909

    09

    STARTUPPre Startup..Startup

    Axial Flow Fans.

    111111

    11

    SERVICING & MAINTENANCE.......General ...

    Compressors...

    Refrigerant Filter Driers..

    Evaporator/Heat Exchanger....Charging Refrigerant ..

    Checking Liquid Sub-Cooling

    Checking Evaporator Superheat.

    Adjusting Sub-cooling and Superheat Temperatures.

    Special Charging Instructions.Lubrication......

    Service Information.

    1313

    13

    13

    1314

    14

    14

    15

    1515

    15

    EVAPORATIVE-COOLED CONDENSER SECTION...General Information

    Pre Start-Up

    Maintenance Recommendations.

    Water Quality..AIR-COOLED CONDENSER SECTION...

    REFRIGERANT PIPING FOR CL SERIES............

    Equivalent Line Length..

    Liquid Line Sizing......Suction Line Sizing.....

    Hot Gas Bypass Line Sizing.......Predetermined Line Sizes...TABLE RP-1 Predetermined Line sizes for Dual Circuit CL units with R-410A..

    TABLE RP-2 Predetermined Line sizes for Dual Circuit CL units with R-22...

    TABLE RP-3 Predetermined Line sizes for Single Circuit CL units with R-410A...TABLE RP-4 Predetermined Line sizes for Single Circuit CL units with R-22 ...FIGURE RP-1 Riser height versus total equivalent line length Dual Circuit CL Units with R-410A ..

    FIGURE RP-2 Riser height versus total equivalent line length Dual Circuit CL Units with R-22.. .

    FIGURE RP-3 Riser height versus total equivalent line length Single Circuit CL Units with R-410A

    FIGURE RP-4 Riser height versus total equivalent line length Single Circuit CL Units with R-22 Hot Gas Bypass Line Routing Diagrams

    1616

    17

    20

    2121

    21

    22

    2223

    232426

    27

    28

    28

    2929

    30

    30

    31

    CL SERIES STARTUP FORM 41

  • 7/29/2019 CL_IOM_070402

    3/54

    3

    It is the intent of AAON, Inc. to provide accurate and current specification information. However, in theinterest of product improvement, AAON, Inc. reserves the right to change pricing, specifications, and/or

    design of its products without notice, obligation or liability

    2007 AAON, Inc., all rights reserved throughout the world.

    AAON & AAONAIRE are registered trademarks of AAON, Inc., Tulsa, OK.

    R10110 Rev. B 4-07

  • 7/29/2019 CL_IOM_070402

    4/54

    4

    GENERAL DESCRIPTION

    All AAON 'CL Series' condensers are factory

    assembled, wired, and charged with 15 lbs. ofrefrigerant per system. Models are available for

    air-cooled and evaporative-cooled applications.

    Unpacking:When received, the unit should be checked for

    damage that might have occurred in transit. If

    damage is found it should be noted on thecarriers Freight Bill. A request for inspection by

    carriers agent should be made in writing at once.

    Also, check the unit nameplate to ensure thecorrect model size and voltage have been

    received to match the job requirements.

    OWNER'S INFORMATION

    Warning:

    Failure to observe the following instructions

    will result in premature failure of your system,and possible voiding of the warranty. Never cut off the main power supply to the unit,

    except for complete shutdown. When power is

    cut off from the unit, any compressors usingcrankcase heaters cannot prevent refrigerant

    migration. This means the compressor will cool

    down, and liquid refrigerant may accumulate inthe compressor. Since the compressor is designed

    to pump refrigerant gas, damage may occur whenpower is restored.

    Before unit operation, the main power switch

    must be turned on for at least twenty four hours

    for units with compressor crankcase heaters. Thiswill give the crankcase heater time to clear any

    liquid accumulation out of the compressor before

    it is required to run. Always control the system from the thermostat,

    or control panel, never at the main power supply

    (except for emergency or for complete shutdownof the system).

    Improper installation, adjustment, alteration,

    service, or maintenance can cause property

    damage, personal injury or loss of life.Installation and service must be performed by a

    qualified installer, service agency or if gas fired

    units, the gas supplier. Refer to installationinstructions provided with the unit and this

    manual.

    The compressors must be on a minimum of 4minutes and offfor a minimum of 5 minutes. The

    cycle rate must be no more than 8 starts per hour.

    The compressor life will be seriously

    shortened by reduced lubrication, and the

    pumping of excessive amounts of liquid oil

    and refrigerant.

    Wiring Diagrams:

    A complete set of unit specific wiring diagrams

    in both ladder and point-to-point form arelaminated in plastic and located inside the control

    compartment door.

  • 7/29/2019 CL_IOM_070402

    5/54

    5

    OWNER'S INFORMATION cont.

    General Maintenance:

    When the initial startup is made and on aperiodic schedule during operation, it is

    necessary to perform routine service checks on

    the performance of the condenser. This includes

    reading and recording suction pressures andchecking for normal sub-cooling and superheat.

    See the evaporative-cooled condenser and air-

    cooled condenser sections in this manual forspecific details.

    INSTALLATION

    Lifting and Handling:

    If cables or chains are used to hoist the unitthey must be the same length and care should be

    taken to prevent damage to the cabinet. Before lifting unit, be sure that all shippingmaterial has been removed from unit. Secure

    hooks and cables at all lifting points/lugs

    provided on the unit. Do not push, pull or lift the unit from anything

    other than its base.

    UNIT MUST BE RIGGED AT ALL

    MARKED LIFTING POINTS (Typical)

    Condenser Placement:

    The AAON condenser is designed for outdoorapplications and mounting at ground level or on

    a rooftop. It must be placed on a level and solid

    foundation that has been prepared to support its

    weight. When installed at ground level, a one-piece concrete slab should be used with footings

    that extend below the frost line.

    With ground level installation, care must betaken to protect the coil fins from damage due to

    vandalism or other causes.

    The placement relative to the building airintakes and other structures must be carefully

    selected. Be sure to observe the dimensions that

    are on the rating plate of the condenser foroperational and service clearances, which will

    appear as follows:

    Service Clearances

    LocationUnit Size

    045-135 134-230

    Front - Vestibule Door Side 100" 142"

    Back - Opposite of Front 100" 142"

    Left Side - Condenser End 100" 100"

    Right Side - Opposite of Left 100" 100"

    Top UNOBSTRUCTED

    Condenser coils and fans must be free of any

    obstructions in order to start and operate properlywith a correct amount of airflow.

    For proper unit operation, the immediate areaaround condenser must remain free of debris that

    may be drawn in and obstruct airflow in the

    condensing section. Consideration must be given to obstruction

    caused by snow accumulation when placing the

    unit.

    Compressor Compartment Exhaust Fan:

    Prior to unit operation the compressor

    compartment exhaust fan shipping supportMUST BE removed from the exterior of the unit.

    The exhaust fan also requires the installation of

    the exterior rain hood provided with the unit.

    Mounting Isolation: For roof mounted applications or anytimevibration transmission is a factor, vibration

    isolators may be used.

    Access Doors:

    A lockable access door is provided to the

    compressor and electrical compartment.

    A light switch is on the wall of the compressorcontrol compartment.

    Low Ambient Operation:

    The AAON low ambient (condenser flood-

    back) system is used to operate a refrigerant

    system below 25F outside air temperature. Asthe ambient temperature drops, the condenser

    becomes more effective therefore lowering the

    head pressure. When the head pressure gets too

  • 7/29/2019 CL_IOM_070402

    6/54

    6

    INSTALLATION cont.

    low, there will be insufficient pressure to operate

    the expansion valve properly. During lowambient temperatures, it is difficult to start a

    system because the refrigerant will migrate to the

    cold part of the system (condenser) and make it

    difficult for refrigerant to flow. The AAON low ambient system maintains

    normal head pressure during periods of low

    ambient by restricting liquid flow from thecondenser to the receiver, and at the same time

    bypassing hot gas around the condenser to the

    inlet of the receiver. This backs liquidrefrigerant up into the condenser reducing its

    capacity that in turn increases the condensing

    pressure. At the same time the bypassed hot gas

    raises liquid pressure in the receiver, allowingthe system to operate properly.

    There are different types of low ambient control

    used. The following describe the different

    systems. Inspect the unit to determine the systemused.

    LAC Valve:The LAC valve is a non-adjustable three way

    valve that modulates to maintain receiver

    pressure. As the receiver pressure drops belowthe valve setting (180 psig for R-22 and 295 psig

    for R-410A), the valve modulates to bypass

    discharge gas around the condenser. The

    discharge gas warms the liquid in the receiverand raises the pressure to the valve setting. The

    following schematic shows an example system

    using the LAC valve.

    Piping Schematic of Example system using the LAC valve.

  • 7/29/2019 CL_IOM_070402

    7/54

    7

    INSTALLATION cont.

    OROA Valve:

    This system uses a nonadjustable head pressure

    control valve that performs the function of

    limiting the flow of liquid refrigerant from the

    condenser and at the same time regulates theflow of the hot gas around the condenser to the

    receiver. The valve setpoint is 180 psig. This

    valve is called an OROA valve (Open on Rise of

    Outlet pressure). The following schematicshows an example system using the OROA

    valve.

    Piping Schematic of Example system using the OROA valve.

    ORI/ORD Valves:

    This system uses a two-valve arrangement. The

    head pressure control valve is an inlet pressureregulating valve and responds to changes in

    condensing pressure. This valve is located in the

    discharge of the condenser and is called an ORIvalve (Open on Rise of Inlet pressure). As the

    ambient temperature drops, the condenser

    capacity increases and the condensing pressure

    falls, causing the ORI to modulate toward theclosed position. The condenser bypass valve is a

    pressure differential valve that responds to

    changes in the pressure differential across thevalve. This valve is called an ORD valve (Open

    on Rise of Differential pressure). As the ORI

    starts to restrict liquid flow from the condenser, a

    pressure differential is created across the ORD.

    When the differential reaches the setpoint, theORD starts to open and bypass hot gas to the

    liquid line. The ORI valve is adjustable from 65

    to 225 psig (factory setting of 180 psig). TheORD is not adjustable. On refrigeration systems

    that are too large for a single ORI and ORD

    valve, there will be two ORI and two ORD

    valves in parallel. The schematic on thefollowing page shows an example system using

    the ORI/ORD valves.

  • 7/29/2019 CL_IOM_070402

    8/54

    8

    INSTALLATION cont.

    Piping Schematic of Example system using the ORI/ORD valve.

    The pressure setting of the ORI valve determines

    how well the system will operate. The proper

    setting is a function of the specific system in

    which is installed. Generally, the setting shouldbe equivalent to a condensing temperature of

    90F to 100F or a receiver pressure equivalent

    to a temperature of 80F to 90F. This meansthat as the ambient temperature falls below 70F,

    the head pressure control valve will begin to

    throttle. To adjust the ORI valve, remove the capand turn the adjustment screw with the proper

    size hex wrench (1/4 for ORI-6 and 5/16 forORI-10). A clockwise rotation increases the

    valve setting while a counter-clockwise rotation

    decreases the setting. To obtain the desiredsetting, a pressure gauge should be used at the

    compressor discharge service valve so the effects

    of any adjustment can be observed. Smalladjustments are recommended in order to allow

    the system adequate time to stabilize after each

    adjustment.

    Condenser Flooding:

    In order to maintain head pressure in the

    refrigeration system, liquid refrigerant is backed

    up in the condenser to reduce condenser surface.The following chart shows the percentage that a

    condenser must be flooded in order to function

    properly at the given ambient temperature.

    PERCENTAGE OF CONDENSER TO BE FLOODED

    Ambient

    Temperature

    (F)

    Evaporating Temperature (F)

    0 10 20 30 35 40 45 50

    70 40 24 0 0 0 0 0 0

    60 60 47 33 17 26 20 10 450 70 60 50 38 45 40 33 28

    40 76 68 60 50 56 52 46 42

    30 80 73 66 59 64 60 55 51

    20 86 77 72 65 69 66 62 59

    0 87 83 78 73 76 73 70 68

    -20 91 87 82 77 80 79 76 73

  • 7/29/2019 CL_IOM_070402

    9/54

    9

    INSTALLATION cont.

    During higher ambient temperatures the entire

    condenser is required to condense refrigerant.During these higher ambient temperatures, a

    receiver tank is used to contain the refrigerant

    that was required to flood the condenser during

    low ambient operation. The receiver must besized to contain all of the flooded volume

    otherwise there will be high head pressures

    during higher ambient conditions.

    Electrical:

    The single point electrical power connectionsare made in the electrical control compartment.

    Check the unit data plate voltage to make sure

    it agrees with the power supply. Connect powerto the unit according to the wiring diagram

    provided with the unit. The power and control wiring may be broughtup through the utility entry. Protect the branch

    circuit in accordance with code requirements.

    Control wires and power should not be run inside

    the same conduit. The unit must be electricallygrounded in accordance with the current National

    Electric Code.

    Power wiring is to the unit terminal block ormain disconnect. All wiring beyond this point

    has been done by the manufacturer and cannot be

    modified without effecting the unit'sagency/safety certification.

    Note: Startup technician must check motoramperage to ensure that the amperage listed

    on the motor nameplate is not exceeded.

    Refrigerant Piping Connections

    CL condensing unit refrigerant piping

    connections are located in the upper corner of the

    service vestibule side of the unit (opposite thecondenser section) as shown in the figure.

    The piping connections are protected with ashipping cover that must be removed prior to

    copper connection and installation.

    Evaporative-cooled Condenser Field Piping

    Connections:

    There are two field water connections that must

    be made for the evaporative-cooled condenser.There is a PVC socket city make-up water

    connection and a 2 PVC socket drain

    connection (as shown on the next page). Thisdrain should connect to a sanitary sewer or other

    code permitted drain. These connections can go

    through the base or the wall of the unit.

    There is a cutout in the base with a cap that is1 tall and the cap is sealed to the unit base to

    prevent any leaks in the unit from penetrating

    into the building. Any piping through the baseshould go through a field cutout in this cap. The

    pipes must be sealed to the cap once the piping is

    complete to prevent any leaks in the unit from

    penetrating into the building. A field cutout must be made in the wall if the

    evaporative-cooled condenser piping is to go

    through the unit wall. This cutout must besealed once the piping is installed to prevent

    water from leaking into the unit.

  • 7/29/2019 CL_IOM_070402

    10/54

    10

    Diagram of Evaporative-cooled condenser Section including field water connections and base cutouttap

  • 7/29/2019 CL_IOM_070402

    11/54

    11

    STARTUP

    Pre-Startup:

    After the installation and immediately before thestartup of the condenser be sure that these items

    have been checked.

    1. Verify that electrical power is available to theunit.

    2. Verify that any remote stop/start device is

    requesting the condenser to start.

    While performing the Startup, use the

    Condensing Startup Form at the back of thisbooklet to record motor amps and any other

    comments.

    Startup:

    Use the General Check List at the top of theStartup Form to make a last check that all thecomponents are in place and the power supply is

    energized.

    Note: Condensing fan operation should start

    with the first compressor.

    Cycle through all the compressors to confirmthat all are operating within tolerance.

    When unit is running, observe the system for a

    complete operation cycle to verify that allsystems are functioning properly.

    While performing the check, use the Condenser

    Startup Form to record observations of amps andrefrigerant pressures.

    When all is running properly, place the

    controller in the Run mode and observe the

    system until it reaches a steady state of operation.

    Axial Flow Fans:

    Multi-Wing Z Series Aluminum Fan Blade

    Pitch Angle Setting Instructions:

    Before You Begin, to maintain balance of fan: Mark the hub castings across a joint, so the fan

    hub can be reassembled in the same orientation.

    Mark the location of any balancing weight.Balancing weight will be on the outer bolt circle,

    in the form of washers, and/or longer bolts, or an

    additional balancing nut.

    Number the blades and blade sockets, so thatthey are replaced into their original position.

    If possible, note the location of the pitch setting

    pin in the blade socket, and whether pin islocated in the Hub or Retainer half of the fan.

    Step 1. Determine Boss Location Code: A orB The boss is the center section of the hub

    through which the fan is mounted to the shaft,

    and typically contains either setscrews or a

    center-tapered hole where the bushing inserts.Select boss location A or B:

    A is the boss on air inlet, including AS

    configurations.B is the boss on air discharge, including BS.

    For flange mounted fans, use boss location A for

    R rotation fans, and boss location B for Lrotation fans.

  • 7/29/2019 CL_IOM_070402

    12/54

    12

    STARTUP cont.

    Step 2. Find Blade Pitch Angle:

    ( 20, 25, 27.5, 30, 32.5, 35, 37.5, 40, 45 or 50 ) Carefully disassemble fan on flat surface and

    note in which groove the pin is located. Refer to

    groove number code diagram.

    Using diagrams in step 5, determine if the pinwas in the hub (HUB) or retainer side (RET) of

    fan.

    Using table in step 4, find the possible bladepitch.

    Using table in step 3, select your blade angle

    based on whether your pin was in the HUB orRET.

    Step 3. Determine Hub/Retainer Code: HUBor RET

    Step 4. - Determine Groove Number: 1 or 2 or 3

    or 4

    Step 5. Final AssemblyDefinition of HUB and RET for purposes of

    instructions. For 2-piece hubset:

    Using the HUB or RET code found in Step 3:

    If code is HUB, place the hub down on work

    surface first (one or two pieces, depending onabove).

    If code is RET, place one retainer ring only

    down on the work surface first. (A weighted

    coffee can could be used to elevate the fan fromthe work surface).

    Using the groove number, place the locking pin

    in the groove number that was found in Step 4.

    Insert Blades:

    Place the blade over the pin in the hub/retainer

    blade socket, so that the pin also fits into theappropriate pitch angle groove in the blade.

    Repeat for all blades. Assemble hub set together, aligning the match

    marks that were made.

    Replace any balancing weight to its original

    position. To finish, tighten the bolts in a cross pattern to

    5 to 6 ft-lbs of torque.

    Multi-Wing W Series Black Glass Reinforced

    Polypropylene Fan Blade Pitch Angle SettingInstructions:

    Step 1.Note original position of retaining plates,

    center boss and all hardware including additional

    hardware used for balancing.

    Step 2. Remove all the bolts and nuts.

  • 7/29/2019 CL_IOM_070402

    13/54

    13

    STARTUP cont.

    Step 3. Determine blade rotation on the

    concave side of the blade is a blade markingshowing 6WR, 6WL, 7WL, 7WR, or 9WR. The

    L and R denote the rotation of the blade.

    Step 4. Replace the pitch insert in the blade rootwith an insert of the desired pitch.

    Step 5. Replace blades to their original location.

    Step 6. Replace all nuts, bolts, and washers on

    the fan hub.

    Step 7. Replace retaining plates and center boss

    to original location.

    Step 8. Tighten nuts and bolts to 14 ft-lbs of

    torque.

    SERVICING AND MAINTENANCE

    General:

    Qualified technicians must perform routineservice checks and maintenance. This includesreading and recording the condensing and

    suction pressures and checking for normal sub-

    cooling and superheat (see charging information

    beginning on page 14). Air-cooled and evaporative-cooled condenser

    units require different maintenance

    schedules/procedures. Unit specific instructionsfor both types are included in this manual.

    Compressors:

    The scroll compressors are fully hermetic and

    require no maintenance except keeping the shell

    clean.

    Refrigerant Filter Driers:

    Each refrigerant circuit contains a replaceablecore filter drier. Replacement is recommended

    when there is excessive pressure drop across the

    assembly or moisture is indicated in a liquid linesight glass.

    The filter driers are provided with pressure taps

    and shutoff valves for isolation when changing

    the core. For safety purposes a service manifoldmust be attached prior to filter maintenance.

    Evaporator/Heat Exchangers:

    Normally no maintenance or service work will be

    required for a matching direct expansionevaporator with a thermal expansion valve to

    regulate refrigerant.

  • 7/29/2019 CL_IOM_070402

    14/54

    14

    SERVICING AND MAINTENANCE

    cont.

    Charging Refrigerant:

    Charging a system in the field must be based ondetermination of liquid sub-cooling and

    evaporator superheat. On a system with a

    thermostatic expansion valve liquid sub-coolingis more representative of the charge than

    evaporator superheat but both measurementsmust be taken.

    Before Charging:

    Refer to the Unit Nameplate to determine the

    proper refrigerant to charge the system with.

    The unit being charged must be at or near full

    load conditions before adjusting the charge. Units equipped with hot gas bypass must have

    the hot gas bypass valve closed to get the proper

    charge.

    Units equipped with hot gas reheat must becharged with the hot gas valve closed while the

    unit is in cooling mode. After adding or removing charge the system

    must be allowed to stabilize, typically 10-15

    minutes, before making any other adjustments.

    The type of unit and options determine theranges for liquid sub-cooling and evaporator

    superheat. Refer to Table 1 when determining

    the proper sub-cooling. The vertical rise of the liquid line must be

    known in order to adjust the sub-cooling rangefor proper charge. Units equipped with low ambient (0F) option

    see special charging instructions at the end of the

    charging instructions.

    Checking Liquid Sub-cooling:1. Measure the temperature of the liquid line as

    it leaves the condenser coil.

    2. Read the gauge pressure reading of the liquid

    line close to the point where the temperature was

    taken. You must use liquid line pressure as it

    will vary from discharge pressure due to

    condenser coil pressure drop.3. Convert the pressure obtained in Step 2 to a

    saturated temperature using the appropriate

    refrigerant temperature-pressure chart.4. Subtract the measured liquid line temperature

    in Step 1 from the saturated temperature in Step

    3 to determine the liquid sub-cooling.5. Compare calculated sub-cooling to TABLE 1.

    for the appropriate unit type and options.

    Checking Evaporator Superheat:

    1. Measure the temperature of the suction line

    close to the compressor.

    2. Read gauge pressure at the suction line closeto the compressor.

    3. Convert the pressure obtained in Step 2 to a

    saturated temperature using the appropriaterefrigerant temperature-pressure chart.

    4. Subtract the saturated temperature in Step 3

    from the measured suction line temperature inStep 1 to determine the evaporator superheat.

    5. Compare calculated superheat to TABLE 1 forthe appropriate unit type and options.

    TABLE 1

    Sub-

    cooling

    (F)

    Superheat

    (F)

    Sub-cooling

    W/Hot Gas

    Reheat (F)

    Air Cooled

    Condenser12-18* 8-15** 15-22*

    Evaporative

    Cooled

    Condenser

    6-10* 8-15** 8-12*

    Water

    Cooled

    Condenser

    6-10* 8-15** 8-12*

    * Sub-cooling must be increased by 3F per 20feet of vertical liquid line rise for R-22 and 2F

    for R-410A

    ** Superheat will increase with long suction lineruns.

  • 7/29/2019 CL_IOM_070402

    15/54

    15

    SERVICING AND MAINTENANCE

    cont.

    Adjusting Sub-cooling and Superheat

    Temperatures:

    The system is overcharged if:

    1. the sub-cooling temperature is too high and

    2. the evaporator is fully loaded (low loads onthe evaporator result in increased sub-cooling)

    and3. the evaporator superheat is within the

    temperature range as shown in TABLE 1 (high

    superheat results in increased sub-cooling)

    Correct an overcharged system by reducing the

    amount of refrigerant in the system to lower the

    sub-cooling.

    The system is undercharged if:1. the superheat is too high and

    2. the sub-cooling is too low

    Correct an undercharged system by addingrefrigerant to the system to reduce superheat and

    raise sub-cooling. If the sub-cooling is correct and the superheat is

    too high, the TXV may need adjustment to

    correct the superheat.

    Special Charging Instructions:

    For units equipped with low ambient refrigerant

    flood back option being charged in the summerwhen the ambient temperature is warm:

    Once enough charge has been added to get theevaporator superheat and sub-cooling values tothe correct setting more charge must be added.

    Add approximately 80% of the receiver tank

    volume to the charge to help fill the receiver

    tank. The additional charge is required for thesystem when running in cold ambient conditions.

    For units equipped with low ambient refrigerantflood back option being charged in the winter

    when the ambient temperature is cold:

    1. Once enough charge has been added to get theevaporator superheat and sub-cooling values to

    the correct setting more charge may need to be

    added. If the ambient temperature is 0F nomore charge is required. If the ambient

    temperature is around 40F add approximately

    40% of the receiver tank volume.2. The unit will have to be checked for proper

    operation once the ambient temperature is above

    80F.

    Lubrication:

    All original motors and bearings are furnished

    with an original factory charge of lubrication.Certain applications require bearings be re-

    lubricated periodically. The schedule will vary

    depending on operating duty, temperaturechanges, or severe atmospheric conditions.

    Bearings should be re-lubricated at normal

    operating temperatures, but not when running.Rotate the fan shaft by hand and add only enough

    grease to purge the seals. DO NOT

    OVERLUBRICATE.

    Service Information:

    If the unit will not operate correctly and a servicecompany is required, only a company with

    service technicians qualified and experienced in

    both condensing units and air conditioning arepermitted to service the systems to keep

    warranties in effect. If assistance is required, the

    service technician must contact AAON.

    Note: Service technician must provide the

    model and serial number of the unit in all

    correspondence with AAON.

    Replacement parts for AAON equipment may be

    obtained from AAON. When ordering parts,always reference the unit model number, serial

    number and part number.

  • 7/29/2019 CL_IOM_070402

    16/54

    16

    AAON, Inc.www.aaon.com

    Customer Service Department

    2425 South Yukon Ave Tulsa, OK 74107Phone: 918-583-2266 Fax: 918-382-6364

    ALWAYS USE AAON SPECIFIED PARTS

    To order parts from the AAON Parts storeonline go to www.aaonparts.com.

    EVAPORATIVE-COOLED

    CONDENSER

    Evaporative cooling equipment rejects heat byevaporating a portion of the recirculated water

    spray and discharging it from the unit with the

    hot, saturated air. As the spray water evaporates,it leaves behind the mineral content and

    impurities of the supply water. If these residuals

    are not purged from the water distribution

    system, they will become concentrated and leadto scaling, corrosion, sludge build-up and

    biological fouling.

    A water treatment monitoring and controlsystem has been furnished with this unit. Be sure

    to read the complete manual that has been

    furnished. All water treatment is a combinationof bleed water and chemical treatment for proper

    control of the residuals and to prevent any

    biological contamination.

    GENERAL INFORMATION

    Severe Service:

    The following recommended maintenance

    procedures are basic requirements for normal

    operating environments. For severe operatingconditions, the frequency of inspection and

    service should be increased. Air containing

    industrial and chemical fumes, salt, dust, or otherairborne contaminates and particulates will be

    absorbed by the recirculating water system and

    may form solutions and deposits harmful to theproducts and personnel.

    Safety:

    The recirculating water system contains chemicaladditives for water quality control and biological

    contaminants removed from the air by the

    washing action of the water. Personnel exposedto the saturated effluent, drift, or direct contact

    should use proper precaution. Proper location of

    the evaporative-cooled condenser requires goodjudgment to prevent the air discharge from

    entering fresh air intakes or to avoid allowing

    contaminated building exhaust from entering the

    condenser.

    Follow local and national codes in locating the

    evaporative-cooled condenser but as minimumthe evaporative-cooled condenser sump must be

    15 feet from the nearest intake.

  • 7/29/2019 CL_IOM_070402

    17/54

    17

    EVAPORATIVE-COOLED

    CONDENSER cont.

    Performance:

    Improper location of the evaporative-cooled

    condenser may seriously degrade the capacity ofthe equipment. Make sure the equipment is

    located such that discharge air from the

    condenser does not enter the condenser air inlet.

    Warranties:

    Please refer to the limitation of warranties ineffect at the time of purchase.

    Condenser Tube Inspection:

    The coil is leak tested at 450 P.S.I.G. beforeshipment. AAON will not be responsible for loss

    of refrigerant. It is the responsibility of the

    installer to verify that the system is sealed beforecharging with refrigerant. If the unit is operated

    during low ambient temperature conditions,

    freeze protection for the recirculating watersystem must be provided.

    Freeze Protection:

    In order to prevent water temperatures from

    dropping below 50F, this unit is equipped with a

    variable frequency drive (VFD) on the fan

    motors when the refrigeration system isoperating.

    Recirculating Water System:

    Electric sump heaters are available to keep the

    sump water from freezing when the refrigeration

    system is not operating. An electric resistanceheater is supplied in the vestibule when sump

    heaters are selected.

    Note: The condenser should not be operated

    with the fan on and the pump cycled on and

    off to maintain head pressure control under

    any conditions. The unit is equipped with a

    water temperature controller which varies fan

    speed to maintain sump water temperature.

    This unit is not equipped with a compressor

    discharge pressure controller for fan speed

    modulation and therefore can not be operated

    without water flow.

    PRE START-UP

    Do not start the evaporative-cooled condenser or

    compressors without installation of proper water

    treatment chemicals. Contact your local watertreatment expert for correct selection of water

    treatment chemical, adjustment of chemical feedand bleed rates.

    Cleanliness:

    Dirt and debris may accumulate in the sumpduring shipping and storage. The sump should be

    cleaned prior to start-up to prevent clogging the

    water distribution system. Any surfaces thatshow contamination should be cleaned ONLY

    with a commercial stainless steel cleaner to

    restore the initial appearance. The inlet screensshould be inspected for foreign material.

    Pump Operation:

    Before initial start of the pump, check as follows:

    1. Be sure that pump operates in the direction

    indicated by the arrow on the pump casing.

    Check rotation each time motor leads have beendisconnected.

    2. Check all connections of motor and starting

    device with wiring diagram. Check voltage,phase and frequency of line circuit with motor

    name plate.

    3. Check suction and discharge piping andpressure gauges for proper operation.

  • 7/29/2019 CL_IOM_070402

    18/54

    18

    EVAPORATIVE-COOLED

    CONDENSER cont.

    4. Turn rotating element by hand to assure that it

    rotates freely.

    Running:

    Periodically inspect pump while running, butespecially after initial start-up and after repairs.

    1. Check pump and piping for leaks. Repairimmediately.

    2. Record pressure gauge readings for future

    reference.3. Record voltage, amperage per phase, and kW.

    Condenser Fan Motors:

    The direct-drive condenser motors on AAONevaporative-cooled condensers are 1200-rpm

    premium efficiency motors controlled by a VFD.These motors are totally enclosed air over motorswith weep holes in the bottom end bell so that

    any condensation can drain out of the motor.

    The motors have a small electric resistanceheater installed inside the casing to keep the

    motors warm when they are deactivated. The

    heaters are designed to keep the interior of themotor 10F warmer than the surrounding

    ambient temperature. This prevents condensation

    from forming inside the motor.

    Ensure that fan is tightly mounted to the motorshaft and the motor mounting bolts are aligned

    and secure.

    Water Make-up Valve:

    The sump water level is controlled by a set of

    conductivity probes at different levels in thesump. This water level controller is located in

    the vestibule behind the condenser pump. There

    are four conductivity probes in this controller.

    There is a reference probe (shown as ref on the

    wiring diagram). This probe is one of the twolongest probes. The other long probe is the low

    water level probe (shown as lo on the wiringdiagram). The medium length probe is for the

    medium water level (shown as med on the

    wiring diagram). The short probe is for the highwater level (shown as hi on the wiring

    diagram). There is a solenoid valve in the make-

    up water line that is activated by the water levelcontroller. The water level controller determines

    the level of water in the sump based onconductivity between two probes. If the

    controller sees conductivity between two probes,

    it knows that water is at least at the level of that

    probe. If the water in the sump is below the low probe,

    it will not allow the condenser pump or the sump

    heater to operate. It will activate the make-upwater solenoid to try to fill the sump assuming

    water is flowing to the unit. Once water is above

    the low probe, it will allow the condenser pumpand sump heater (if ordered and the ambient

    temperature is below 40F) to operate. The

    make-up water solenoid will remain activated

    until water gets to the high water level. Themake-up water solenoid will deactivate until

    water gets to the medium water level. In normal

    operation, the water level should swing betweenthe medium and high water levels. The

    maximum high water level should be 1 below

    the overflow drain which occurs after the make-up water valve shuts off when the water level

    reaches the high level probe.

    Make-up water supply pressure should be

    maintained between 15 and 60 psig for proper

    operation of the valve. The make-up water valveassembly should be inspected monthly and

    adjusted as required. Replace the valve seat if

    leakage occurs when the valve is in the closedposition.

  • 7/29/2019 CL_IOM_070402

    19/54

    19

    EVAPORATIVE-COOLED

    CONDENSER cont.

    Water Treatment System:

    All AAON evaporative-cooled condenserscome equipped with a water treatment system

    that should be maintained by a local water

    treatment professional trained in the watertreatment of evaporative condensers. This

    system consists of a controller, three chemicalpumps and storage tanks, a conductivity sensor, a

    motorized ball valve for water bleed, and a water

    meter. One chemical pump and tank is typically used

    for a descaling chemical to prevent scale from

    forming in the condenser. The other two pumps

    and tanks are typically used for two differentbiocides (to kill any microorganisms that could

    grow in the condenser). Two biocides are usedto prevent organisms from becoming resistant toone chemical.

    The mineral content of the water must be

    controlled. All make-up water has minerals in it.As water is evaporated from the condenser, these

    minerals remain. As the mineral content of the

    water increases, the conductivity of the waterincreases. The water treatment controller

    monitors this conductivity. As the water

    conductivity rises above set point, the controller

    will open a motorized ball valve on the dischargeside of the condenser pump and dumps water

    into the condenser drain until conductivity is

    lowered. While the motorized ball valve isopened, the controller will not disperse

    chemicals.

    The chemicals are dispersed by the watertreatment controller based on the scheduled input

    by the water treatment professional. (See the

    separate manual for the water treatment controls

    for specific programming information.)

    The water meter measures the quantity ofmake-up water used by the condenser.

    Any water treatment program must becompatible with stainless steel, copper,

    aluminum, ABS plastic and PVC. Batch feed

    processes should never be used as concentratedchemicals can cause corrosion. Never use

    hydrochloric acid (muratic acid) as it will

    corrode stainless steel.

    Sequence of Operation:

    On a call for cooling, the condenser pump is

    activated. A pressure switch in the pump

    discharge is bypassed for six seconds by a time

    delay relay in order for the pump to establishrecirculating water flow. If flow is not proven

    within the six seconds, the pressure switch opens,

    breaking the safety circuit, thereby shutting downthe entire system. This pressure switch is set to

    close at 3 psi and open at 1 psi.

    A Johnson Controls S350C measures the watertemperature in the pump discharge line. If the

    sump water temperature exceeds 105F, the

    cooling system will be shut down thereby

    preventing damage to the evaporative condenser. If a fault occurs in the evaporative condenser

    fan motor VFD, normally closed fault terminals

    on the VFD will interrupt the safety circuit,thereby shutting down the system.

    If the VFD does fault and cannot be reset, there

    is a VFD bypass switch mounted near the VFD.This switch has four positionsline, off, drive,

    and test. The line position will bypass the

    VFD, sending power to the motor. In thisposition, the condenser fans will run at full

    speed. The off position will not allow powerto pass through the switch. This functions as a

    disconnect switch. The drive position runs

    power through the VFD. This is the normal

    operation for the switch. The test positionroutes power to the VFD but not to the motor.

    This is useful for running tests on the VFD

    without sending power to the motor. A Johnson Controls A350P controls the VFD

    speed. This device sends a 0-10 VDC signal to

    the VFD. This controller is set to maintain asump temperature of 70F. On a rise in sump

    temperature, the controller increases the voltage

    to the VFD, increasing the speed of thecondenser fans. Conversely, on a drop in sump

    temperature, the controller will decrease the

    voltage to the VFD, decreasing the speed of the

    condenser fans. An outside air thermostat does not allow the

    condenser to operate when the ambient

    temperature is below 35F.

  • 7/29/2019 CL_IOM_070402

    20/54

    20

    EVAPORATIVE-COOLED

    CONDENSER cont.

    MAINTENANCE RECOMMENDATIONS

    Pump Maintenance: Cleaning - Remove oil, dust, water, and

    chemicals from exterior of motor and pump.Keep motor air inlet and outlet open. Blow out

    interior of open motors with clean compressedair at low pressure.

    Labeled Motors- It is imperative for repair of a

    motor with Underwriters Laboratories label thatoriginal clearances be held; that all plugs, screws,

    other hardware be fastened securely, and that

    parts replacements be exact duplicates or

    approved equals. Violation of any of the aboveinvalidates Underwriters Label.

    Fan Motor Maintenance:

    Same as pump maintenance

    Access Doors:

    If scale deposits or water is found around the

    access doors, adjust door for tightness. Adjust as

    necessary until leaking stops when door isclosed.

    Bearings - Lubrication:

    Every 6 months or after a prolonged shut down.Use waterproof, lithium based grease. Below

    32F - Esso Exxon or Beacon 325. Above 32F

    Mobil Mobilox EP2, Shell Alvania EP2 orTexaco RB2.

    Recommended Monthly Inspection:

    1. Clean sump section interior. Dirt and other

    impurities which have accumulated in the sump

    should be removed from the sump area. Shut off

    make-up water ball valve and open the drain

    connection for flushing of the sump.2. Clean dirt out of sump using a water hose (not

    a pressure washer).3. Clean sump suction strainer.

    4. Check water operating level. Adjust float as

    required.5. Inspect fan motor(s) and water circulation

    pump(s) and lubricate per the lubrication

    nameplate or manufactures recommendations.

    6. Inspect axial fans and eliminators removingany debris which may have accumulated during

    operation.

    7. Inspect the water distribution system to insure

    that nozzles and spray orifices are functioningcorrectly. The inspection should be made with

    the circulation pump on and fans off.

    Mist Eliminators:

    The mist eliminators must be correctly

    positioned when they are replaced duringcleaning or service.

    Air Inlet:

    Inspect the air inlet louvers and mist eliminatorsinto the condenser section on a monthly basis to

    remove any paper, leaves or other debris that

    may block the airflow.

    Stainless Steel Base Pan:

    The base pan under the tube bundles is stainlesssteel and may sometimes become tarnished due

    to contamination. These surfaces should be

    inspected yearly to ensure they remain clean ofany contamination that may result in damage.

    Any surfaces that show contamination should becleaned ONLY with a commercial stainless steel

    cleaner to restore the initial appearance.

    Propeller Fans and Motors:

    The fans are directly mounted on the motor

    shafts and the assemblies require minimal

    maintenance except to assurance they are clear ofdirt or debris that would impede the airflow.

    Recommended Annual Inspection:

    In addition to the above maintenance activities, a

    general inspection of the unit surface should be

    completed at least once a year. Remove sprayheader and flush out.

    Cleaning:

    Mechanical cleaning, including pressurewashing, should never be performed as surfaces

    and seals could be damaged. Chemical cleaning

    that is safe for stainless steel, copper, aluminum,ABS plastic and PVC is the only acceptable

    means of cleaning the evaporative condenser. A

    proper water treatment program should reducecleaning needs.

  • 7/29/2019 CL_IOM_070402

    21/54

    21

    EVAPORATIVE-COOLED

    CONDENSER cont.

    WATER QUALITY

    Recirculating Water Quality Guidelines:

    Cycles of concentration (the ratio of dissolvedsolids in recirculated water to dissolved solids in

    make-up), should be determined and monitored

    frequently by a competent water treatmentexpert.

    To limit cycles of concentration to maintain theabove guideline, it is necessary to bleed a

    certain portion of the recirculated water. This is

    achieved automatically with a solenoid valve

    actuated by a conductivity meter set at thedesired conductivity corresponding to the desired

    cycles of concentration. It should be noted that

    these are guidelines and even though theseindividual values are met, under certain

    conditions the water quality can be aggressive.

    For example, water with very low alkalinity and

    levels of chlorides and sulfates approachingmaximum recommended levels can be corrosive.

    Mechanical Cleaning:

    Do not attempt to mechanically clean the copper

    tubing in the evaporative-cooled condenser. Do

    not use wire brushes or any other mechanicaldevice on the copper tubing. Severe damage may

    result. Contact your water treatment expert for

    recommendations on chemical cleaningprocedures.

    Parts:

    Contact your local AAON Representative for

    factory authorized parts. Orders must include the

    Serial Number from the product nameplate OR

    visit www.aaonparts.com for more information.

    AIR-COOLED CONDENSER

    The air-cooled condenser section rejects heat by

    passing outdoor air over the fin tube coils forcooling of the hot refrigerant gas from the

    compressors. The heated air will discharge from

    the top of the section through the axial flow fans.

    The condenser coils should be inspected yearlyto ensure unrestricted airflow. If the installation

    has a large amount of airborne dust or other

    material, the condenser coils should be cleanedwith a water spray in a direction opposite to

    airflow. Care must be taken to prevent bending

    of the aluminum fins on the copper tube.

    REFRIGERANT PIPING FOR THE

    CL SERIES

    Note: This section is for information only andis not intended to provide all details required

    by the designer or installer of the refrigerant

    piping between the condensing unit and air

    handling equipment. AAON Inc. is not

    responsible for interconnecting refrigerant

    piping. Consult ASHRAE Handbook 2006

    Refrigeration and ASME Standards.

    General:

    Use only clean type L copper tubing (type K for

    underground) that has been joined with hightemperature brazing alloy.

    All AAON CL condensing units have factory

    furnished liquid and suction line shutoff valves.

    Determining Refrigerant Line size:

    The piping between the condenser and low sidemust assure:

    1. Minimum pressure drop, and

    2. Continuous oil return, and

    3. Prevention of liquid refrigerant slugging, orcarryover

    Minimizing the refrigerant line size is favorable

    from an economic perspective, reducinginstallation costs, and reducing the potential for

    leakage. However, as pipe diameters narrow,

    pressure-reducing frictional forces increase.

  • 7/29/2019 CL_IOM_070402

    22/54

    22

    REFRIGERANT PIPING cont.

    Excessive suction line pressure drop causes loss

    of compressor capacity and increased powerusage resulting in reduced system efficiency.

    Excessive pressure drops in the liquid line can

    cause the liquid refrigerant to flash, resulting in

    faulty expansion valve operation and impropersystem performance. In order to operate

    efficiently and cost effectively, while avoiding

    malfunction, refrigeration systems must bedesigned to minimize both cost and pressure loss.

    The pipe sizes must be selected to meet the

    actual installation conditions, and not simply

    based on the connection sizes at the

    evaporator and/or condensing unit. Refer to

    TABLES RP-1 through RP-4 for connection

    size information.

    Equivalent Line Length:

    All line lengths discussed in this manual, unless

    specifically stated otherwise, are Equivalent Line

    Lengths. The frictional pressure drop throughvalves, fittings, and accessories is determined by

    establishing the equivalent length of straight pipe

    of the same diameter. Always use equivalentline lengths when calculating pressure drop.

    Special piping provisions must be taken when

    lines are run underground, up vertical risers, or inexcessively long line runs.

    Liquid line sizing:

    When sizing the liquid line, it is important tominimize the refrigerant charge to reduce

    installation costs and improve system reliability.

    This can be achieved by minimizing the liquidline diameter. However, reducing the pipe

    diameter will increase the velocity of the liquid

    refrigerant which increases the frictional pressuredrop in the liquid line, and causes other

    undesirable effects such as noise. Maintaining

    the pressure in the liquid line is critical toensuring sufficient saturation temperature,

    avoiding flashing upstream of the TXV, andmaintaining system efficiency. Pressure losses

    through the liquid line due to frictional contact,

    installed accessories, and vertical risers are

    inevitable. Maintaining adequate sub-cooling atthe condenser to overcome these losses is the

    only method to ensure that liquid refrigerantreaches the TXV.

    Liquid risers decrease head pressure. If the

    evaporator section is below the condenser, and

    the liquid line does not include risers, thegravitational force will increase the pressure of

    the liquid refrigerant. This will allow the

    refrigerant to withstand greater frictional losseswithout the occurrence of flashing prior to the

    TXV.

    A moisture indicating sight glass may befactory installed in the liquid line to indicate the

    occurrence of premature flashing or moisture in

    the line. The sight glass should not be used to

    determine if the system is properly charged. Use

    temperature and pressure measurements to

    determine liquid sub-cooling, not the sight

    glass.

    Liquid Line Routing:

    Care should be taken with vertical risers. Whenthe system is shut down, gravity will pull liquid

    down the vertical column, and back to the

    condenser when it is below the evaporator. Thiscould potentially result in compressor flooding.

    A check valve can be installed in the liquid linewhere the liquid column rises above the

    condenser to prevent this. The liquid line is

    typically pitched along with the

    suction line, or hot gas line, to minimize thecomplexity of the configuration.

    Liquid Line Insulation:

    When the liquid line is routed through regions

    where temperature losses are expected, no

    insulation is required, as this may provideadditional sub-cooling to the refrigerant. When

    routing the liquid line through high temperature

    areas, insulation of the line is appropriate toavoid loss of sub-cooling.

    Liquid Line Guidelines:

    In order to ensure liquid at the TXV, frictionallosses must not exceed available sub-cooling. A

    commonly used guideline to consider is a system

    design with pressure losses due to frictionthrough the line not to exceed a corresponding 1-

    2F change in saturation temperature.

  • 7/29/2019 CL_IOM_070402

    23/54

    23

    REFRIGERANT PIPING cont.

    If the velocity of refrigerant in the liquid line is

    too great, it could cause excessive noise or pipingerosion. The recommended maximum velocities

    for liquid lines are 100 fpm from the condenser

    to a receiver tank to discourage fluid backup, and

    300 fpm from receiver tank to the evaporator tominimize valve induced liquid hammer.

    Liquid Line Accessories:

    Liquid line accessories including sight glasses

    and filter driers are available and factory

    installed. The total length equivalent of pressurelosses through valves, elbows and fittings must

    be considered when adding additional

    components in the field. It is a good practice toutilize the fewest elbows that will allow the

    mating units to be successfully joined.

    Suction Line Sizing:

    The suction line is more critical than the liquid

    line from a design and construction standpoint.

    More care must be taken to ensure that adequatevelocity is achieved to return oil to the

    compressor at minimum loading conditions.

    However, reducing the piping diameter toincrease the velocity at minimal load can result

    in excessive pressure losses, capacity reduction,

    and noise at full load.

    Suction Line Routing:

    Pitch the suction line in the direction of flow

    (about 1 ft. per 100 ft of length) to maintain oilflow towards the compressor, and keep it from

    flooding back into the evaporator. Crankcase

    heaters are provided to keep any condensedrefrigerant that collects in the compressor from

    causing damage or wear. Make sure to provide

    support to maintain suction line positioning, andinsulate completely between the evaporator and

    condensing unit.

    It is important to consider part load operationwhen sizing suction lines. At minimum capacity,

    refrigerant velocity may not be adequate to returnoil up the vertical riser. Decreasing the diameter

    of the vertical riser will increase the velocity, but

    also the frictional loss. A double suction riser

    can be applied in this situation. The doublesuction riser is designed to return oil at minimum

    load while not incurring excessive frictionallosses at full load. The double suction riser

    consists of a small diameter riser in parallel with

    a larger diameter riser, and a trap at the base of

    the large riser. At minimum capacity, refrigerantvelocity is not sufficient to carry oil up both

    risers, and it collects in the trap, effectively

    closing off the larger diameter riser, anddiverting refrigerant up the small riser where

    velocity of the refrigerant is sufficient to

    maintain oil flow. At full load, the mass flowclears the trap of oil, and refrigerant is carried

    through both risers. The smaller diameter pipe

    should be sized to return oil at minimum load,

    while the larger diameter pipe should be sized foracceptable pressure drop at full load.

    Suction Line Insulation:

    The entire suction line should be insulated. This

    prevents condensation from forming on the line,

    and reduces any potential loss in capacityassociated with heat gain placing additional load

    on the system.

    Suction Line Guidelines:

    For proper performance, suction line velocitiesless than a 4000 fpm maximum are

    recommended. The minimum velocity required

    to return oil is dependent on the pipe diameter,

    however a general guideline of 1000 fpmminimum may be applied.

    In a fashion similar to the liquid line, a common

    guideline to consider is a system design withpressure losses due to friction through the line

    not to exceed a corresponding 1-2F change in

    saturation temperature. At points where small pipe size can be used to

    provide sufficient velocity to return oil in vertical

    risers at part loads, greater pressure losses areincurred at full loads. This can be compensated

    for by over sizing the horizontal and vertical

    drop sections. This will however require

    additional refrigerant charge.

    Suction Line Accessories:

    If the job requirements specify suctionaccumulators, they must be separately purchased

    and installed.

  • 7/29/2019 CL_IOM_070402

    24/54

    24

    REFRIGERANT PIPING cont.

    Hot Gas Bypass Line:

    Hot Gas Bypass is available for use with DXsystems that may experience low suction

    pressure during the operating cycle. This may be

    due to varying load conditions associated with

    VAV applications or units supplying a largepercentage of outside air. The system is

    designed to divert refrigerant from the

    compressor discharge to the low pressure side ofthe system in order to keep the evaporator from

    freezing and to maintain adequate refrigerant

    velocity for oil return at minimum load. Hot discharge gas is redirected to the

    evaporator inlet via an auxiliary side connector

    (ASC) to false load the evaporator when reducedsuction pressure is sensed. Field piping between

    the condensing unit and the evaporator isrequired.

    See figures RP-5 through RP-10 for hot gas

    bypass piping configurations.

    Hot Gas Bypass Piping Considerations for

    Evaporator Above Condensing Unit:

    Pitch the hot gas bypass line downward in thedirection of refrigerant flow, toward the

    evaporator.

    When installing hot gas bypass risers, a drainleg must be provided at the lowest point in the

    system. The drain leg must be vertical, its

    diameter should be the same as the diameter of

    the riser, and it should be 1 foot long. Install asight glass in the drain leg for observation. Run

    an oil return line, using 1/8 inch capillary tube, 5

    feet in length, from the drain leg to the suctionline. Connect the oil return line below the sight

    glass, 1 inch above the bottom of the drain leg.

    HGBP valves are adjustable. Factory HGBPvalve settings will be sufficient for most

    applications, but may require slight adjustments

    for some make up air or other process coolingapplications.

    Insulate the entire length of the HGBP line witha minimum 1 inch thick Armaflex insulation.

    Refer to figure RP-5 for piping diagram

    Hot Gas Bypass Piping Considerations for

    Evaporator Below Condensing Unit:

    The line must slope downward from the hot gasbypass valve toward the evaporator.

    Refer to figure RP-6 for piping diagram

    Hot Gas Bypass Line Guidelines:

    Choose a small size line to ensure oil return,

    and minimize refrigerant charge.

    Maintain velocities below a maximum of 4000fpm. A general minimum velocity guideline to

    use is approximately 1000 fpm.

    Hot Gas Reheat:

    The AAON modulating hot gas reheat system

    diverts hot discharge gas from the condenser to

    the air handling unit to supply the reheat coiland/or the hot gas bypass valve. Size this line as

    a discharge line.

    Discharge lines should be sized to ensureadequate velocity of refrigerant to ensure oil

    return, avoid excessive noise associated with

    velocities that are too high, and to minimizeefficiency losses associated with friction.

    Pitch the hot gas line in the direction of flow for

    oil return. Insulate the entire length of the hot gas line

    with a minimum 1 inch thick Armaflexinsulation.

    Refer to figures RP-7 through RP-10 for piping

    diagrams.

    Hot Gas Reheat Guidelines:

    Maintain velocities below a maximum of 3500

    fpm. A general minimum velocity guideline is2000 fpm.

    Predetermined Line Sizes:

    To aid in line sizing and selection, AAON has

    predetermined line sizes for comfort cooling

    applications. In order to generate this information, the

    following cycle assumptions are made:

    Saturated suction temperature = 50F, Saturated

    condensing temperature = 125F, Sub-cooling =10F, Superheat = 15F.

    The liquid lines have been chosen to maintain

    velocities between 100 and 350 fpm. Thesuction line diameters are selected to limit

    velocities to a 4000 fpm maximum, while a

    minimum velocity restriction is imposed by theability to entrain oil up vertical suction risers

  • 7/29/2019 CL_IOM_070402

    25/54

    25

    REFRIGERANT PIPING cont.

    (ASHRAE Handbook 2006 - Refrigeration p.

    2.19). Hot gas bypass pipe diameters areselected to maintain velocity below a maximum

    4000 fpm, while a minimum criteria guarantees

    oil return up vertical rise sections, as with the

    suction line (ASHRAE Handbook 2006 Refrigeration p. 2.20).

    Acceptable pressure loss criteria are applied to

    each of the lines: The total equivalent length ofthe liquid line available is determined such that

    3F of liquid sub-cooling remain at the TXV.

    This includes the pressure losses in horizontaland vertical sections, accessories, elbows, etc.

    Recall that the available sub-cooling for the cycle

    is assumed as 10F. To maintain at least 3F sub-cooling as a factor of safety to avoid flashing at

    the TXV, we consider a maximum pressure lossequivalent to a 7F change in saturationtemperature. Pressure losses in the suction line

    are not to exceed 2F. When sizing the hot gas

    bypass line we consider a maximum acceptable

    pressure loss in the hot gas bypass line with R-22to be 20 psi, 30 psi with R-410A refrigerant.

    When to use predetermined line sizing:

    The line sizes presented are not the only

    acceptable pipe diameters, they are however

    appropriate for general comfort coolingapplications, and satisfy common job

    requirements. Examine the conditions,

    assumptions, and constraints used in the

    generation of the predetermined pipe diametersto ensure that this method is applicable to a

    particular case. Do not assume that these line

    sizes are appropriate for every case. ConsultASHRAE Handbook Refrigeration 2006 for

    generally accepted system practices.

    How to use predetermined line sizing:

    First, read the previous section entitled (When to

    use predetermined line sizing) to decide if thismethod is applicable.

    Second, determine the refrigerant being used,AAON offers CL products with R-410A and R-

    22 refrigerants, and the line sizes are notidentical for both.

    Next, determine whether the product is operating

    with single, or dual circuited compressors.

    Locate the appropriate table of line sizes:TABLE RP-1: Dual Circuited R-410A

    condensers

    TABLE RP-2: Dual Circuited R-22 condensersTABLE RP-3: Single Circuited R-410A

    condensers

    TABLE RP-4: Single Circuited R-22 condensersLocate the Model number in the table. For each

    model, the circuits are listed, along with the pipe

    diameters of the connection sizes, and the

    diameters of the predetermined line size.A figure accompanies each table.

    FIGURE RP-1: Dual circuited R-410A

    condensersFIGURE RP-2: Dual circuited R-22 condensers

    FIGURE RP-3: Single circuited R-410A

    condensersFIGURE RP-4 Single circuited R-22 condensers

    Examine the appropriate figure to determine the

    acceptable line dimensions. The figure is shownas total available riser height versus total

    equivalent line length for the liquid line. Thiscurve identifies a region of acceptable piping

    configuration when the predetermined line sizes

    are selected for any model in the table. A piping

    configuration above the curve falls outside theassumptions used to determine the line size and

    will result in a loss of sub-cooling, and additional

    pressure losses in the suction and hot gas bypasslines. The total equivalent line length definition

    includes the height of vertical rise, pressure drop

    through elbows and accessories, and horizontalline length, so elbows, accessories and vertical

    rise must be considered when determining

    horizontal length available from the totalequivalent line length.

    This figure is presented in terms of the liquid

    line, but it assumes that the line lengths for the

    suction and hot gas bypass are similar, as theselines will commonly be routed together to

    minimize the space and cost required for split

    system installation.

  • 7/29/2019 CL_IOM_070402

    26/54

    26

    REFRIGERANT PIPING cont.

    TABLE RP-1 Predetermined Line sizes for Dual Circuit CL units with R-410A

    Tons System

    R-410A

    Connection Size Predetermined Line Size

    Suction Line Liquid Line Hot Gas Bypass Reheat Suction Line Liquid Line Hot Gas Bypass Reheat

    451

    1-3/8 in. 7/8 in. 7/8 in. 7/8 in. 1-5/8 in. 7/8 in. 3/4 in. 1-1/8 in.2

    601

    1-5/8 in. 7/8 in. 7/8 in. 1-1/8 in. 2-1/8 in. 1-1/8 in. 3/4 in. 1-1/8 in.2

    701

    1-5/8 in.7/8 in.

    7/8 in.1-1/8 in.

    2-1/8 in. 1-1/8 in.3/4 in. 1-1/8 in.

    2 1-1/8 in. 1-3/8 in. 7/8 in. 1-3/8 in.

    751

    1-5/8 in. 1-1/8 in. 7/8 in. 1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in. 1-3/8 in.2

    951 1-5/8 in.

    1-1/8 in. 7/8 in.1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in. 1-3/8 in.

    2 2-1/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in. 1-3/8 in.

    100

    1

    1-5/8 in.

    7/8 in.

    7/8 in.

    1-1/8 in.

    2-1/8 in. 1-1/8 in.

    3/4 in. 1-1/8 in.

    21-1/8 in. 1-3/8 in. 7/8 in. 1-3/8 in.

    3

    1101

    1-5/8 in. 1-1/8 in. 7/8 in. 1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in. 1-3/8 in.2

    3

    125

    11-5/8 in.

    1-1/8 in. 7/8 in.1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in.

    1-3/8 in.2

    3 2-1/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in.

    134

    11-5/8 in.

    1-1/8 in. 7/8 in.1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in.

    1-3/8 in.2

    3 2-1/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in.

    135

    1 1-5/8 in. 7/8 in.

    7/8 in.

    1-1/8 in. 2-1/8 in. 1-1/8 in. 3/4 in. 1-1/8 in.

    22-1/8 in. 1-1/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in. 1-3/8 in.

    3

    155

    1 1-5/8 in.

    1-1/8 in. 7/8 in.

    1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in.

    1-3/8 in.22-1/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in.

    3

    170

    1

    2-1/8 in. 1-1/8 in. 7/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in. 1-3/8 in.2

    3

    190

    11-5/8 in. 1-1/8 in.

    7/8 in.

    1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in.

    1-3/8 in.2

    32-1/8 in. 1-1/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in.

    4

    210

    1 1-5/8 in.

    1-1/8 in. 7/8 in.

    1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in.

    1-3/8 in.22-1/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in.3

    4

    230

    1

    2-1/8 in. 1-1/8 in. 7/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in. 1-3/8 in.2

    3

    4

  • 7/29/2019 CL_IOM_070402

    27/54

    27

    REFRIGERANT PIPING cont.

    TABLE RP-2 Predetermined Line sizes for Dual Circuit CL units with R-22

    Tons System

    R-22

    Connection Size Predetermined Line Size

    Suction Line Liquid Line Hot Gas Bypass Reheat Suction Line Liquid Line Hot Gas Bypass Reheat

    451

    1-3/8 in. 5/8 in. 7/8 in. 7/8 in. 2-1/8 in. 7/8 in. 7/8 in. 1-1/8 in.2

    601

    2-1/8 in. 7/8 in. 7/8 in. 1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in. 1-3/8 in.2

    701

    2-1/8 in. 7/8 in. 7/8 in. 1-3/8 in.2-1/8 in.

    1-1/8 in.7/8 in. 1-3/8 in.

    2 2-5/8 in. 1-1/8 in. 1-5/8 in.

    751

    2-1/8 in. 7/8 in. 7/8 in. 1-3/8 in. 2-5/8 in. 1-1/8 in. 1-1/8 in. 1-5/8 in.2

    951 2-1/8 in. 7/8 in.

    7/8 in.1-3/8 in.

    2-5/8 in.1-1/8 in.

    1-1/8 in. 1-5/8 in.2 2-5/8 in. 1-3/8 in. 1-5/8 in. 1-3/8 in.

    100

    1

    2-1/8 in. 7/8 in. 7/8 in. 1-3/8 in.

    2-1/8 in.

    1-1/8 in.

    7/8 in. 1-3/8 in.

    22-5/8 in. 1-1/8 in. 1-5/8 in.

    3

    1101

    2-1/8 in. 7/8 in. 7/8 in. 1-3/8 in. 2-5/8 in. 1-1/8 in. 1-1/8 in. 1-5/8 in.2

    3

    125

    12-1/8 in. 7/8 in.

    7/8 in.1-3/8 in.

    2-5/8 in.1-1/8 in.

    1-1/8 in. 1-5/8 in.2

    3 2-5/8 in. 1-3/8 in. 1-5/8 in. 1-3/8 in.

    134

    12-1/8 in. 7/8 in.

    7/8 in.1-3/8 in.

    2-5/8 in.1-1/8 in.

    1-1/8 in. 1-5/8 in.2

    3 2-5/8 in. 1-3/8 in. 1-5/8 in. 1-3/8 in.

    135

    1 2-1/8 in. 7/8 in.

    7/8 in.

    1-3/8 in. 2-1/8 in. 1-1/8 in. 7/8 in. 1-3/8 in.

    22-5/8 in. 1-3/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in. 1-5/8 in.

    3

    155

    1 2-1/8 in. 7/8 in.

    7/8 in.

    1-3/8 in.

    2-5/8 in.

    1-1/8 in.

    1-1/8 in. 1-5/8 in.22-5/8 in. 1-3/8 in. 1-5/8 in. 1-3/8 in.

    3

    170

    1

    2-5/8 in. 1-3/8 in. 7/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in. 1-5/8 in.2

    3

    190

    12-1/8 in. 7/8 in.

    7/8 in.

    1-3/8 in.

    2-5/8 in.

    1-1/8 in.

    1-1/8 in. 1-5/8 in.2

    32-5/8 in. 1-3/8 in. 1-5/8 in. 1-3/8 in.

    4

    210

    1 2-1/8 in. 7/8 in.

    7/8 in.

    1-3/8 in.

    2-5/8 in.

    1-1/8 in.

    1-1/8 in. 1-5/8 in.22-5/8 in. 1-3/8 in. 1-5/8 in. 1-3/8 in.3

    4

    230

    1

    2-5/8 in. 1-3/8 in. 7/8 in. 1-5/8 in. 2-5/8 in. 1-3/8 in. 1-1/8 in. 1-5/8 in.2

    3

    4

  • 7/29/2019 CL_IOM_070402

    28/54

    28

    REFRIGERANT PIPING cont.

    TABLE RP-3 Predetermined Line sizes for Single Circuit CL units with R-410A

    Tons System

    R-410A

    Connection Size Predetermined Line Size

    Suction Line Liquid Line Hot Gas Bypass Reheat Suction Line Liquid Line Hot Gas Bypass Reheat

    45

    1

    1-1/8 in. 5/8 in. 7/8 in. 7/8 in. 1-3/8 in. 5/8 in. 5/8 in. 3/4 in.2

    3

    4

    60

    1

    1-3/8 in. 5/8 in. 7/8 in. 7/8 in. 1-3/8 in. 3/4 in. 3/4 in. 7/8 in.2

    3

    4

    70

    1 1-3/8 in.

    5/8 in. 7/8 in. 7/8 in.

    1-3/8 in. 3/4 in.

    3/4 in.

    7/8 in.

    2 1-5/8 in. 1-5/8 in. 7/8 in. 1-1/8 in.

    3 1-3/8 in. 1-3/8 in. 3/4 in. 7/8 in.

    4 1-5/8 in. 1-5/8 in. 7/8 in. 1-1/8 in.

    75

    1

    1-5/8 in. 5/8 in. 7/8 in. 7/8 in. 1-5/8 in. 7/8 in. 3/4 in. 1-1/8 in.23

    4

    95

    1

    1-5/8 in.

    5/8 in.

    7/8 in.

    7/8 in. 1-5/8 in. 7/8 in. 3/4 in.

    1-1/8 in.2 7/8 in. 1-1/8 in. 2-1/8 in. 1-1/8 in. 7/8 in.

    3 5/8 in. 7/8 in. 1-5/8 in. 7/8 in. 3/4 in.

    4 7/8 in. 1-1/8 in. 2-1/8 in. 1-1/8 in. 7/8 in.

    TABLE RP-4 Predetermined Line sizes for Single Circuit CL units with R-22

    Tons System

    R-22

    Connection Size Predetermined Line Size

    Suction Line Liquid Line Hot Gas Bypass Reheat Suction Line Liquid Line Hot Gas Bypass Reheat

    45

    1

    1-3/8 in. 5/8 in. 7/8 in. 7/8 in. 1-5/8 in. 5/8 in. 3/4 in. 7/8 in.2

    3

    4

    60

    1

    1-3/8 in. 5/8 in. 7/8 in. 7/8 in. 1-5/8 in. 3/4 in. 7/8 in. 1-1/8 in.2

    3

    4

    70

    1

    1-3/8 in. 5/8 in. 7/8 in. 7/8 in.

    1-5/8 in.

    3/4 in. 7/8 in. 1-1/8 in.2 2-1/8 in.

    3 1-5/8 in.

    4 2-1/8 in.

    75

    1

    1-3/8 in. 5/8 in. 7/8 in. 7/8 in. 2-1/8 in. 3/4 in. 7/8 in. 1-1/8 in.2

    3

    4

    95

    1 1-3/8 in. 5/8 in.

    7/8 in.

    7/8 in.

    2-1/8 in.

    3/4 in. 7/8 in. 1-1/8 in.

    2 2-1/8 in. 7/8 in. 1-3/8 in. 1-1/8 in. 1-1/8 in. 1-3/8 in.

    3 1-3/8 in. 5/8 in. 7/8 in. 3/4 in. 7/8 in. 1-1/8 in.

    4 2-1/8 in. 7/8 in. 1-3/8 in. 1-1/8 in. 1-1/8 in. 1-3/8 in.

  • 7/29/2019 CL_IOM_070402

    29/54

    29

    REFRIGERANT PIPING cont.

    FIGURE RP-1. Riser height versus total equivalent line length for R-410A split system applications with

    dual circuited CL-045 through CL-230 units. The region of acceptable riser height is the lighter area.Select the corresponding predetermined line size from TABLE RP-1 on page 26.

    FIGURE RP-2. Riser height versus total equivalent line length for R22 split system applications with dualcircuited CL-045 through CL-230 units. The region of acceptable riser height is the light area. Select the

    corresponding predetermined line size from TABLE RP-2 on page 27.

    Acceptable Region

    Acceptable Region

  • 7/29/2019 CL_IOM_070402

    30/54

    30

    REFRIGERANT PIPING cont.

    FIGURE RP-3. Riser height versus total equivalent line length for R-410A split system applications with

    single circuited CL-045 through CL-230 units. The region of acceptable riser height is the lighter area.Select the corresponding predetermined line size from TABLE RP-3 on page 28.

    FIGURE RP-4. Riser height versus total equivalent line length for R22 split system applications withsingle circuited CL-045 through CL-230 units. The region of acceptable riser height is the light area.

    Select the corresponding predetermined line size from TABLE RP-4 on page 28.

    Acceptable Region

    Acceptable Region

  • 7/29/2019 CL_IOM_070402

    31/54

    31

    FIGURE RP-2. Hot Gas Bypass Piping Diagram with air handler above condenser.

    Note: Components shown within air

    handler and condensing unit are factory

    installed; all other components are fieldinstalled.

  • 7/29/2019 CL_IOM_070402

    32/54

    32

    FIGURE RP-3. Hot Gas Bypass Piping Diagram with air handler below condenser.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    33/54

    33

    FIGURE RP-4. Hot Gas Reheat Piping Diagram with air handler above condenser.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    34/54

    34

    FIGURE RP-5. Hot Gas Reheat Piping Diagram with air handler below condenser.

    Note: Components shown within air

    handler and condensing unit are factoryinstalled; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    35/54

    35

    FIGURE RP-6. Hot Gas Reheat Piping Diagram with air handler above condenser and field installed

    suction line accumulator.

    Note: Components shown within air

    handler and condensing unit are factory

    installed; all other components are fieldinstalled.

    TO BE INSTALLED IN FIELD

  • 7/29/2019 CL_IOM_070402

    36/54

    36

    FIGURE RP-7. Hot Gas Reheat Piping Diagram with air handler above condenser and field installed

    suction line accumulator.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.TO BE INSTALLED IN FIELD

  • 7/29/2019 CL_IOM_070402

    37/54

    37

    FIGURE RP-8. Reheat/Hot Gas Bypass Piping Diagram with air handler above condenser.

    Note: Components shown within air

    handler and condensing unit are factory

    installed; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    38/54

    38

    FIGURE RP-9. Reheat/Hot Gas Bypass Piping Diagram with air handler below condenser.

    Note: Components shown within air

    handler and condensing unit are factoryinstalled; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    39/54

    39

    FIGURE RP-10. Reheat/Hot Gas Bypass Piping Diagram with air handler evaporator above condenser

    and field installed suction line accumulator.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.

    TO BE INSTALLED IN FIELDTO BE INSTALLED IN FIELD

  • 7/29/2019 CL_IOM_070402

    40/54

    40

    FIGURE RP-11. Reheat/Hot Gas Bypass Piping Diagram with air handler below condenser and field

    installed suction line accumulator.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.TO BE INSTALLED IN FIELD

  • 7/29/2019 CL_IOM_070402

    41/54

    41

    FIGURE RP-5. Hot Gas Bypass Piping Diagram with air handler above condenser.

    Note: Components shown within air

    handler and condensing unit are factory

    installed; all other components are fieldinstalled.

  • 7/29/2019 CL_IOM_070402

    42/54

    42

    FIGURE RP-6. Hot Gas Bypass Piping Diagram with air handler below condenser.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    43/54

    43

    FIGURE RP-7. Hot Gas Reheat Piping Diagram with air handler above condenser.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    44/54

    44

    FIGURE RP-8. Hot Gas Reheat Piping Diagram with air handler below condenser.

    Note: Components shown within air

    handler and condensing unit are factoryinstalled; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    45/54

    45

    FIGURE RP-9. Hot Gas Reheat Piping Diagram with air handler above condenser and field installed

    suction line accumulator.

    Note: Components shown within air

    handler and condensing unit are factory

    installed; all other components are fieldinstalled.

    TO BE INSTALLED IN FIELD

  • 7/29/2019 CL_IOM_070402

    46/54

    46

    FIGURE RP-10. Hot Gas Reheat Piping Diagram with air handler above condenser and field installed

    suction line accumulator.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.TO BE INSTALLED IN FIELD

  • 7/29/2019 CL_IOM_070402

    47/54

    47

    FIGURE RP-11. Reheat/Hot Gas Bypass Piping Diagram with air handler above condenser.

    Note: Components shown within air

    handler and condensing unit are factory

    installed; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    48/54

    48

    FIGURE RP-12. Reheat/Hot Gas Bypass Piping Diagram with air handler below condenser.

    Note: Components shown within air

    handler and condensing unit are factoryinstalled; all other components are field

    installed.

  • 7/29/2019 CL_IOM_070402

    49/54

    49

    FIGURE RP-13. Reheat/Hot Gas Bypass Piping Diagram with air handler evaporator above condenser

    and field installed suction line accumulator.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.

    TO BE INSTALLED IN FIELD

  • 7/29/2019 CL_IOM_070402

    50/54

    50

    FIGURE RP-14. Reheat/Hot Gas Bypass Piping Diagram with air handler below condenser and field

    installed suction line accumulator.

    Note: Components shown within airhandler and condensing unit are factory

    installed; all other components are field

    installed.TO BE INSTALLED IN FIELD

  • 7/29/2019 CL_IOM_070402

    51/54

    Condenser and Condenser Unit Startup Form

    Date:______________Job Name:_____________________________________________________________________

    Address:______________________________________________________________________

    Model Number:_______________________________________________________________________________________________________________________________________________

    Serial Number:_____________________________________________ Tag:_______________

    Startup Contractor:______________________________________________________________Address:__________________________________________________ Phone:_____________

    Pre Startup Checklist

    Installing contractor should verify the following items.

    1. Is there any visible shipping damage? Yes No

    2. Is the unit level? Yes No

    3. Are the unit clearances adequate for service and operation? Yes No4. Do all access doors open freely and are the handles operational? Yes No

    5. Have all shipping braces been removed? Yes No

    6. Have all electrical connections been tested for tightness? Yes No

    7. Does the electrical service correspond to the unit nameplate? Yes No

    8. On 208/230V units, has transformer tap been checked? Yes No

    9. Has overcurrent protection been installed to match the unit nameplate

    requirement? Yes No

    10. Have all set screws on the fans been tightened? Yes No

    11. Do all fans and pumps rotate freely? Yes No

    12. Is all copper tubing isolated so that it does not rub? Yes No

    Ambient Temperature

    Ambient Dry Bulb Temperature ________F Ambient Wet Bulb Temperature ________F

    Compressors / DX Cooling

    Compressor

    Number L1 L2 L3

    HeadPressure

    PSIG

    SuctionPressure

    PSIG

    CrankcaseHeater

    Amps

    1

    2

    34

    5

    6

    7

    8

  • 7/29/2019 CL_IOM_070402

    52/54

    Refrigeration System 1

    PressureSaturated

    Temperature

    Line

    TemperatureSub-cooling Superheat

    Discharge N/A N/A

    Suction N/A

    Liquid N/ARefrigeration System 2

    PressureSaturated

    Temperature

    Line

    TemperatureSub-cooling Superheat

    Discharge N/A N/A

    Suction N/A

    Liquid N/A

    Refrigeration System 3

    PressureSaturated

    Temperature

    Line

    TemperatureSub-cooling Superheat

    Discharge N/A N/ASuction N/A

    Liquid N/A

    Refrigeration System 4

    PressureSaturated

    Temperature

    Line

    TemperatureSub-cooling Superheat

    Discharge N/A N/A

    Suction N/A

    Liquid N/A

    Condenser Fans

    Alignment Check Rotation Nameplate Amps________

    Number hp L1 L2 L3

    1

    2

    3

    4

    5

    6

    Condenser Pump

    Check Rotation Nameplate Amps________

    Number hp L1 L2 L3

    1

    2

  • 7/29/2019 CL_IOM_070402

    53/54

    Maintenance Log

    This log must be kept with the unit. It is the responsibility of the owner and/or

    maintenance/service contractor to document any service, repair or adjustments. AAON Service

    and Warranty Departments are available to advise and provide phone help for proper operationand replacement parts. The responsibility for proper start-up, maintenance and servicing of the

    equipment falls to the owner and qualified licensed technician.

    Entry Date Action Taken Name/Tel.

  • 7/29/2019 CL_IOM_070402

    54/54

    CL SERIES CONDENSING

    UNIT

    INSTALLATION, SERVICE

    &

    OWNERS INFORMATION MANUAL