Cost optimal facade design solutions of office buildings

Tallinn 10.10.2013

Martin ThalfeldtPhD student in TUTwww.nzeb.ee

OBJECTIVES• Developing energy and cost efficient facade design

principles for nearly zero energy building (non-residential)

• Studies so far: window U>1.0

• Questions: optimal size of windows, highly transparent or solar protection glazing, external shading or not, insulation thickness, facade vs PV

• Influenced: daylight, heating, cooling, electric lighting, investment

• Study procedures: Energy and indoor simulations + financial calculations of

a generic office floor model Number of window panes up to 5, U=0.21 Financial feasability -> min. 20 year NPV Best possible energy efficiency

METHODS• Criteria for most financially feasible case is minimum

net present value, which includes investment cost and 20 year energy use.

• Calculations according to Estonian energy efficiency requirements

Smallest energy consumption ≠ min €

STEP 1 MINIMUM WINDOW SIZE• Average daylight factor ≥ 2% • Minimum sized windows

𝑨𝒘=¿¿

STEP 1 MINIMUM WINDOW SIZEGla-zing

U, W/(m2K)

g, - τvis, -

2/C 1.1 0.61 0.78

3/C 0.54 0.49 0.70

4/C 0.32 0.36 0.63

3/SC 0.54 0.36 0.60

5/C 0.21 0.24 0.56

2/D 1.0 0.27 0.50

3/D 0.54 0.24 0.45

STEP 2 HIGHLY TRANSPARENT OR SOLAR PROTECTION GLAZING?

Highly transparent glazing allows reaching better energy efficiency!

Delivered energy Primary energy

STEP 3 NUMBER OF PANES AND INSULATION THICKNESS IN BALANCE!

• 3 pane glazing – insulation 200 mm (U=0,16)

• 4 pane glazing – insulation 250 mm (U=0,13)

• 5 pane glazing – insulation 390 mm (U=0,09)

STEP 4 ENERGY EFFICIENT FACADE SOLUTIONS

MOST ENERGY EFFICIENT FACADE SOLUTION

No of panes

WWR, %

Ext. shading

Insulation thickness, mm

Primary energy, kWh/m2

Invest-ment€/m2

20 year NPV€/m2

Lõuna 5 60% No 390 86.3 136.1 168.0

Ida 5 60% Yes 390 84.6 175.8 211.9

Lääs 5 60% Yes 390 84.7 175.8 211.9

Põhi 5 60% No 390 87.3 136.1 170.2

FINANCIALLY MOST FEASIBLE SOLUTION

No of panes

WWR, %

Ext. shading

Insulation thickness, mm

Primary energy, kWh/m2

Invest-ment€/m2

20 year NPV€/m2

Lõuna 3 37.5% No 200 96.7 96,3 140.3

Ida 3 37.5% No 200 95.7 89,9 140.6

Lääs 3 37.5% No 200 97.3 89,9 142.1

Põhi 3 37.5% No 200 97.8 96,3 143.4

Office floor primary energy=93.6 x 1.2 = 112.6 kWh/m2

Office floor primary energy=85.5 x 1.2 = 102.6 kWh/m2

COOLING CAPACITIES

• Window size affects cooling capacities in addition to energy consumption

• Triple glazing with WWR ca 25% might be a more sensible solution

FROM LOW ENERGY TO NZEB

3 panes, WWR 37.5% (Cost optimal)4 panes, WWR 37.5% (North 60%)5 panes, WWR 29.5%5 panes, WWR 60% (Energy efficient)

CONCLUSION• Space heating dominates in case of double and triple windows, the

proportion of heating reduces as no of panes increases

• Smaller windows result in better energy efficiency in case of double and triple glazing

• Financially most feasible case is triple glazing with high thermal resistance (U=0.54 g=0.49), window to wall ratio ca 25%, insulation thickness 200 mm (U=0.16)

• Best energy efficiency was achieved with quintuple glazing (U=0.21 g=0.24), window to wall ratio 60%, insulation thickness 390 mm (U=0.09)

• In case of quadruple glazing (U=0.32 g=0.36) the optimal window to wall ratio is ca 40%

• External shading is not necessary if windows are sized according to average daylight factor 2%

• It is more reasonable to use cost optimal facade solution and install more PV panels

• Necessity to study the influence of external shading control strategies and double facade on energy efficiency occurred