Classification of Lightning and Faults in...

15
Research Article Classification of Lightning and Faults in Transmission Line Systems Using Discrete Wavelet Transform Pathomthat Chiradeja 1 and Atthapol Ngaopitakkul 2 1 Faculty of Engineering, Srinakharinwirot University, Bangkok 10110, ailand 2 Faculty of Engineering, King Mongkut’s Institute of Technology Ladkrabang, Bangkok 10520, ailand Correspondence should be addressed to Atthapol Ngaopitakkul; [email protected] Received 13 June 2018; Revised 20 August 2018; Accepted 13 September 2018; Published 3 October 2018 Academic Editor: Leonardo Acho Copyright © 2018 Pathomthat Chiradeja and Atthapol Ngaopitakkul. is is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited. In ailand, electrical energy consumption has been rapidly increasing, following economic and population growth. In order to supply constant power to consumers, reliability is an important factor the electric utility needs to consider. Common disturbances that cause severe damage to transmission and distribution systems are lightning and faults. e system operator must deal with these two phenomena with speed and accuracy. us, this study aims to investigate the differential behaviour of transmission systems when disturbance such as lightning strikes and faults occurs in a 115-kV transmission line. e methodology consists of using the ATP/EMTP program to model the transmission system by the 115-kV Electricity Generating Authority of ailand (EGAT) and simulate both lightning and fault signals in the system. e discrete wavelet transforms are then applied to obtain the signals in order to evaluate the characteristics and behaviour of both signals in terms of high-frequency components. e obtained data will then be used to construct the fault and lightning classification algorithm based on DWT and travelling wave theory. e proposed algorithm shows the effectiveness in classifying the fault and lightning based on the transmission system that was modelled aſter the actual system in ailand. us, it can further improve the protection scheme and devices in terms of accuracy and reduce the response time for an operator to address the disturbance and ensure the reliability of the system in the future. 1. Introduction Presently, technological development and economic growth make electricity important in both industry and daily life. erefore, to cater to this demand and improve power systems, the Electricity Generating Authority of ailand (EGAT) has started the innovation of a degenerative trans- mission system in the range of 115-230 kV. e project is expected to be completed in 2017 and will increase the capacity of substations, thus increasing the energy flow in the systems. Aſter the completion of these projects, the growing demand of electricity usage will be met, and electricity will be accessible to large areas. However, the expanding power networks frequently cause power-transmission accidents. ese accidents are divided into 2 types: accidents caused by natural phenomena (lightning) and those caused by the system structure (fault). e accidents caused by natural phenomena seriously damage life and property. However, these do not commonly occur in systems, whereas faults on the power line occur more oſten in complex than in normal networks. e literature review on various researches and studies in the field of fault and lightning on power system has been done. ere are three main objectives of lightning for the researcher to focus on: the electric field, the magnetic field, and the influence of lightning on equipment in power systems. Lin Li and Vladimir A. Rakov [1] recorded infor- mation about lightning incidents in USA from 2004 to 2005 to analyse the characteristic of lightning electromagnetic field. Jun Zou et al. [2] invented a model for estimating the electromagnetic field caused by direct lightning and distribution in the Lightning-Protection System (LPS). e model is based on a double-conductor system, which can be reduced to a two-port equivalent circuit. However, due to a lack of grounding system, the estimation capacity is limited. In addition, there are a number of studies on the Hindawi Mathematical Problems in Engineering Volume 2018, Article ID 1847968, 14 pages https://doi.org/10.1155/2018/1847968

Transcript of Classification of Lightning and Faults in...

Page 1: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

Research ArticleClassification of Lightning and Faults in Transmission LineSystems Using Discrete Wavelet Transform

Pathomthat Chiradeja1 and Atthapol Ngaopitakkul 2

1Faculty of Engineering, Srinakharinwirot University, Bangkok 10110, Thailand2Faculty of Engineering, King Mongkut’s Institute of Technology Ladkrabang, Bangkok 10520, Thailand

Correspondence should be addressed to Atthapol Ngaopitakkul; [email protected]

Received 13 June 2018; Revised 20 August 2018; Accepted 13 September 2018; Published 3 October 2018

Academic Editor: Leonardo Acho

Copyright © 2018 Pathomthat Chiradeja and Atthapol Ngaopitakkul. This is an open access article distributed under the CreativeCommons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided theoriginal work is properly cited.

In Thailand, electrical energy consumption has been rapidly increasing, following economic and population growth. In order tosupply constant power to consumers, reliability is an important factor the electric utility needs to consider. Common disturbancesthat cause severe damage to transmission anddistribution systems are lightning and faults.The systemoperatormust deal with thesetwo phenomena with speed and accuracy. Thus, this study aims to investigate the differential behaviour of transmission systemswhen disturbance such as lightning strikes and faults occurs in a 115-kV transmission line. The methodology consists of using theATP/EMTP program to model the transmission system by the 115-kV Electricity Generating Authority of Thailand (EGAT) andsimulate both lightning and fault signals in the system. The discrete wavelet transforms are then applied to obtain the signals inorder to evaluate the characteristics and behaviour of both signals in terms of high-frequency components.The obtained data willthen be used to construct the fault and lightning classification algorithm based on DWT and travelling wave theory. The proposedalgorithm shows the effectiveness in classifying the fault and lightning based on the transmission system that was modelled afterthe actual system inThailand.Thus, it can further improve the protection scheme and devices in terms of accuracy and reduce theresponse time for an operator to address the disturbance and ensure the reliability of the system in the future.

1. Introduction

Presently, technological development and economic growthmake electricity important in both industry and daily life.Therefore, to cater to this demand and improve powersystems, the Electricity Generating Authority of Thailand(EGAT) has started the innovation of a degenerative trans-mission system in the range of 115-230 kV. The project isexpected to be completed in 2017 and will increase thecapacity of substations, thus increasing the energy flow in thesystems. After the completion of these projects, the growingdemand of electricity usage will be met, and electricity willbe accessible to large areas. However, the expanding powernetworks frequently cause power-transmission accidents.These accidents are divided into 2 types: accidents causedby natural phenomena (lightning) and those caused by thesystem structure (fault). The accidents caused by naturalphenomena seriously damage life and property. However,

these do not commonly occur in systems, whereas faults onthe power line occur more often in complex than in normalnetworks.

The literature review on various researches and studiesin the field of fault and lightning on power system hasbeen done. There are three main objectives of lightning forthe researcher to focus on: the electric field, the magneticfield, and the influence of lightning on equipment in powersystems. Lin Li and Vladimir A. Rakov [1] recorded infor-mation about lightning incidents in USA from 2004 to 2005to analyse the characteristic of lightning electromagneticfield. Jun Zou et al. [2] invented a model for estimatingthe electromagnetic field caused by direct lightning anddistribution in the Lightning-Protection System (LPS). Themodel is based on a double-conductor system, which canbe reduced to a two-port equivalent circuit. However, dueto a lack of grounding system, the estimation capacity islimited. In addition, there are a number of studies on the

HindawiMathematical Problems in EngineeringVolume 2018, Article ID 1847968, 14 pageshttps://doi.org/10.1155/2018/1847968

Page 2: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

2 Mathematical Problems in Engineering

characteristics of lightning. Andrei Ceclan et al. [3] presenteda procedure for reconstructing the spatial waveforms of thelightning return-stroke current base using a numerical-fieldsynthesis method and Fourier transform.The combination ofthese methods is proven to increase the efficacy of lightningdetection. Ian Cotton et al. [4] compared voltage inducedby lightning and switching on a 1-km pipeline of paralleloverhead transmission line. Although the switching-inducedvoltage is lower than the lightning-induced voltage, eithercan cause damage to devices and systems. Vishwanath Hegdeand Vinoda Shivanand [5] observed induced currents causedby lightning strikes to the ground near a steel-reinforcedconcrete building. The relation among the peak values ofthe induced currents and three main factors, namely, theheight of a building, its roof, and the lightning rods used,is studied. It is found that the building’s height and severalattributes of the lightning rods are the major contributingfactors. Amedeo Andreotti and Luigi Verolino [6] presenteda novel lightning current function that is more complexthan an ideal lightning current function, but obtains anexact waveform; thus, the novel method can completelyreplace the ideal model without any impact on the processingtime. Sometimes, the analysis by a single method is notcomprehensive, so some researches apply various methods toutilize the features of each method in order to obtain the bestresults; for example, Vesna Javor and Predrag D. Rancic [7]presented a novel lightning current function by coordinationbetween differential integral equation and Fourier transform,in which the first-order positive sequence of lightning returnstroke and the subsequent lightning stroke is analysed. Theresults demonstrated that an offered function can be used toanalyse every type of lightning return stroke. Silvestar Sesnicet al. [8] estimated the time of themaximum transient currentat the horizontal axis of finite-ground electrode, using thecoefficient of reflection to analyse the conditions of soil andair by combining the Laplace transform and Cauchy residuetheorem. Afterwards, because of the development of tech-nologies, many researchers began to apply this developmentin their research to improve the accuracy and efficiency, likePooyanManoochehrnia et al. [9] andMarcos Rubinstein [10].Pooyan Manoochehrnia et al. analysed lightning events inSwitzerland from 1999 to 2007 using Benford’s law.The resultsproved that Benford’s law is not suitable for determining theanalytical characteristics of lightning, because it can onlyanalyse low lightning currents.However, the law is reasonableto locate the position of lightning. J. A. Morales and E. A.Orduna [11] installed magnetic sensors in the power systemusing the time detected by sensors to estimate the spreadof the field and the discharge. E. A. A. M. Luz et al. [12]investigated the induced voltage and current at a transformerin a hydroelectric plant using the finite-difference time-domain method. Their analysis was based on computersimulation and was used to determine the effect of a 1-kAlightning strike at phase A. It was found that the inducedvoltage follows the lightning point.

When faults occur in the power systems, the character-istic of voltage and current change. Thus, various method-ologies that analysed the change in the signal have beenused for the protection system.Themethod for fault location

and classification on transmission line has been reviewedin K. Chen et al. research [13]. Mehrdad Majidi et al. [14]proposed a method to predict the location of single-line,line-to-line, double-line-to-ground, and three-phase faultsthat occurred in a transmission network. The observationnetwork was based on 39 buses, and the variable parametersare the resistance and line percentage. The operation ofthis method is unlike that of the conventional method. Theproposed method only requires a phasor measurement unit(PMU). The results showed that fault detection by PMU ishighly efficient. In addition, the subsituation theorem andleast-square method were also used to estimate the voltageand current before and after the fault occurred. Moreover,Liang X. D. et al. [15] used the synchrophasor technologyfor real-time monitoring of a wide-area system. A studyproposed a fault-detection method based on the maximumamplitude of the fault, based on the theoretical and PMUdata when the fault occurred, and resolving the conditionbased on a comparison of the EM when the fault occurred.The results of the presented method show high efficiency fordetecting faults. F. B. Costa et al. [16] observed a two-terminaltransmission system by using the traveling-wavemethod.Theresearch analysis only used the time of the transient; thepolarity and magnitude of the transient were ignored. Thereal-time analysis has high efficiency for detecting and identi-fying internal and external faults. Furthermore, the samplingrate and velocity of wave traveling in a line directly affect thedetection accuracy. Yao Luis et al. [17] had analysed the faultcurrent by using the discrete wavelet transform (DWT) withconsideration of the impact on the mother wavelet, level ofwavelet, sampling frequency, and inception angle of faults onthe behaviour of wavelet current signals. The result verifiesthat all these parameters have an impact on the behaviourof signals, especially at the level of the wavelet. Therefore,a suitable issue between a level and signal waveform isnecessary for the efficiency of signal analysis. Furthermore,Darwish et al. [18] had presented a method to protect along transmission line with an installed compensator. Thismethod chose two dissimilar mother wavelets for analysis,which were simulated and processed by PSCAD/EMTDCand MATLAB. The methodology using convolutional sparseautoencoder to detect and classify faults on transmissionline has been proposed [19]. The research applied DWTbased methodology on high-technology devices for faultprotection system. For instance, Korkal et al. [20] insertedglobal position system (GPS) to detect the time of travelingwaves and locate fault positions byDWT. Nagy et al. [21] usedthe time detected by wireless sensors distributed in the powersystem to locate the fault areas, based on the coefficient ofDWT.

Following the literature reviews above, we concluded thatnumerous researchers focused on various impacts that occurin the system, such as pre- and postattribution of faultsand the influence of faults on devices by using dissimilarmethods: FT and DWT. Each method has an exclusiveproperty. FT and DWT have a similarity in displaying thetime and frequency domains. FT is unable to display timeand frequency together, but DWT is able to do so. From thelightning and fault analyses, both parameters are significantly

Page 3: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

Mathematical Problems in Engineering 3

essential. Therefore, DWT is more appropriate than FT.Although there are numerous studies on lightning and faults,there are only a few that focused on the apparent coexistencein lightning and faults. Consequently, it is impossible todifferentiate both forms. In addition, those case studies areinadequate. Therefore, the objectives of this research areanalysing both lightning and the faults that occur in twoterminal lines of transmission systems. The system understudy is 115-kV transmission line that was modelled afterThailand’s transmission system. The ATP/EMTP softwarehas been used to simulate lightning and fault signal ontransmission line, and DWT based methodology has beenused for the algorithm. The influence of inception angles,phase lines, and the position at which lightning and faultshad occurred in the system has been taken into considerationto evaluate the performance of the proposed methodology invarious case studies.

2. Theory

2.1. Discrete Wavelet Transform. Wavelet transform is oneform of signal processing by using mathematical model todescribe the structure of the analysed signal in a practicalform.The assumption is that signals are composed of a set ofsimilar small functions called “MotherWavelet” combined byscaling and shifting. The general equation of wavelet at scale‘a’ and position ‘b’ can be illustrated in (1).

𝜓𝑎,𝑏 (𝑡) = 1√𝑎𝜓(

𝑡 − 𝑏𝑎 ) (1)

where 𝜓(𝑡) = function of mother wavelet; 𝑎 = coefficientof scaling; 𝑏 = coefficient of shifting.

The discrete wavelet transforms (DWT) are analysed byshifting and scaling position of mother wavelet in discontin-uous interval and can be calculated using (2) with n, m and kparameters being integral numbers.

𝐷𝑊𝑇(𝑚, 𝑛) = 1√𝑎𝑚0 ∑𝑘 𝑓 (𝑘)𝜓[

𝑛 − 𝑘𝑏0𝑎𝑚0𝑎𝑚0 ] (2)

where 𝑛 = Number of data; 𝑚 = coefficient of scaling; 𝑘 =coefficient of shifting.

The Daubechies Wavelets (db) have been selected for theproposed algorithm due to the effectiveness in the analysedtransient signal in the power system, especially in case faultand lightning occur on the transmission system [22]. TheDaubechies wavelet transform can be defined as (3).

𝜓 (𝑥) = √22𝑁−1∑𝑘=0

(−1)𝑘 ℎ2𝑁−1−𝑘𝜑 (2𝑥 − 𝑘) (3)

whereℎ2𝑁−1−𝑘 = filter coefficients.

3. Simulation and Result

Thesimulating circuit consists of a sending substation (RYG),receiving substation (CTI), and a load of 150 MVA. The

Table 1: Parameters of the multi-storey model, ] = 300 m/𝜇s.Transmission Tower Parameter

Z1 180 R1 12.390927 L1 0.0024947Z2 180 R2 13.892908 L2 0.0027971Z3 180 R3 13.892908 L3 0.0027971Z4 140 R4 31.248555 L4 0.0062914

distance between RYG and CTI is 88.5 km, and the voltageis 115 kV. The one-line diagram for the simulation circuitis shown in Figure 1(a). A transmission pole used in thisresearch is exhibited in the multistorey transmission towermodel shown in Figure 1(b), which is a structure basedon EGAT. The multistorey model was divided into 4 parts:the top tower, upper phase, middle phase, and lower phase.Each part included a surge impedance (Z), resistance (R),and inductance (L), and the ground part included footingresistance (Rg). All these parameters are shown in Table 1.The detailed parameter of 115 kV transmission line and toweris described in the Appendix.

The objective of this research was to observe the char-acteristic of currents when lightning and faults occur. Thesimulated lightningwas based on 1.2/50 𝜇s, and the amplitudewas 20 kA. The velocity of the lightning wave traveling intoline was that of the speed of light, 300 m/𝜇s. This proceduredetermines the static variables, which are the voltage, distancebetween transmission lines, load capacity, ground resistance,time at which lightning and faults occurred, and amplitude ofthe lightning currents. The study variables are the inceptionangles, phase lines, and positions at which lightning and faultsoccurred.

The simulation in this paper observed three main factors.Thefirst is the position of the lightning and fault, which variedfrom 10% to 90%of the distance of the transmission line, witha step size of 10% of the line distance. The second factor is theinception angle, which varied from 0 to 150 degrees, whereeach observed angle increased by 30 degrees. The third is thephase line, which varied between phase A, phase B, and phaseC. All factors were observed on 5 incidence cases, consistingof 1 lightning case and 4 fault cases. The fault cases weresingle-line, line-to-line, double-line-to-ground, and three-phase faults. In this paper, we show the result of the lightningcase and the single-line-fault, which were the most frequentoccurrences in the power system.

(a) Behaviour of Lightning Strikes in a Transmission Line.In this case, there is a lightning strike at phase A, and theeffects of the two parameters, inception angle and lightningposition, on the characteristic of current at the sending andreceiving substations were observed. Figures 2(a) and 2(b)are the sending and receiving characteristic current graphs.Figures 2(c) and 2(d) are the wavelet-transformed graphsfrom Figures 2(a) and 2(b).

From the sending substation, the three-phase currentssuddenly increase at the time of the lightning strike. Theamplitude of the lightning phase, phase A, is higher than thatof the others, and the amplitude that increases is equal to theamplitude of the lightning current. The other phases, phase

Page 4: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

4 Mathematical Problems in Engineering

CT CT

RYG substation115 kV

88.5 km

CTI substation115 kV

Load 150 MVApf 0.8 lagging

(a)

1.0

Z1

Z2

Z3

Z4

R1

R2

R3

R4

Rg

L1

L2

L3

L4

Part 1 top of tower

Part 2 upper phase

Part 3 middle phase

Part 4 lower phase

Tower footing

d =4.64

d2 =5.50

d3 =5.60

d4 =6.0

l =3.30

l2 =3.70

l3 =3.70

l4 =19.50

(b)

Figure 1: System for simulation. (a) One-line diagram of simulated circuit. (b) Multistorey transmission tower model.

B and phase C, increase as well, because lightning inducesa change in the magnetic field, while, in turn, it induces anincrease in the current of the other phases. From the receivingsubstation, the behaviour of the three currents is similar tothat at the sending substation.

In terms of direction, the current of phase A increases inthe negative direction because of the lightning return stroke.It suddenly occurs in the range of 0.1-10 ms then slowlydecreases and disappears at 100ms. Phase B and phase C havethe opposite changing direction to phaseA, because these twophases are not affected by the return stroke. However, thissimulation only focuses on the time of lightning occurrencein the range of 2-4 ms, so the lightning vanishes after 4 ms.At that time, the three-phase currents return to the normalcondition.

The inception angle varied from 0∘ to 90∘. The waveformof the three-phase currents is sinusoidal, which has amplitudein the positive and negative directions according to theangle; thus, as the inception angle changes, the amplitude ofthe current changes as well. Moreover, when the lightninglocation changes from 30% to 70% of the transmission line,it is found that the current characteristic also depends on

the position of the lightning. The position is referenced fromthe sending substation. Changing the position from 30% to70% of the transmission line means that the distance betweenthe lightning point and the sending substation increases,while the distance between the lightning point and thereceiving substation decreases. This distance directly impactsimpedance inverse current.Thus, the location increase makesthe amplitude of the current at the sending substationdecrease and the amplitude of the current at receivingsubstation increase.

By considering the sending substation, the waveformof the wavelet suddenly increases in the negative directionat the time of the lightning strike. After that time, thewaveform gradually returns to the initial conditions. Fromthe receiving substation, the behaviour of the wavelet issimilar to the waveform at the sending substation, whichsuddenly increases at the time of the lightning strikes, but thecoefficient is lower than that at the sending substation becauseof the effect of impedance from the lightning position.

Likewise, as shown in Figure 3, the amplitude of thecurrent was dependent on the lightning position. The currentat the sending end tended to decrease and, on the other

Page 5: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

Mathematical Problems in Engineering 5

Sending substation (RYG)

lb

la

lc

−8000

−6000

−4000

−2000

0

2000

4000

Curr

ent (

A)

0.005 0.01 0.015 0.02 0.025 0.030Time (s)

(a)

Receiving substation (CTI)

la

lb

lc

−8000

−6000

−4000

−2000

0

2000

4000

Curr

ent (

A)

0.005 0.01 0.015 0.02 0.025 0.030Time (s)

(b)

Sending end (RYG)

0.001 0.002 0.003 0.004 0.0050Time (s)

0200400600

Coe

ffici

ent

wav

elet

−10000−5000

05000

Curr

ent (

A)

0.001 0.002 0.003 0.004 0.0050Time (s)

(c)

Receiving end (CTI)

−5000

0

5000

Curr

ent (

A)

0100200300

Coe

ffici

ent

wav

elet

0.001 0.002 0.003 0.004 0.0050Time (s)

0.001 0.002 0.003 0.004 0.0050Time (s)

(d)

Figure 2: Case of lightning strike at phase A at 30% of transmission line (inception angle 0∘). (a) All phases at sending substation (RYG).(b) All phases at receiving substation (CTI). (c) Positive sequence at sending substation (RYG). (d) Positive sequence at receiving substation(CTI).

0 10 20 30 40 50 60 70 80 90 100

Lightning A , Inception angle 0

% Location

Sending end (RYG)Receiving end (CTI)

200

400

600

800

1000

1200

1400

Coe

ffici

ent o

f wav

elet

Figure 3: Summary of DWT results when the location of lightningwas varied (inception angle 0∘).

hand, that at the receiving end tended to increase. The resultsof Figures 4(a) and 4(b) indicate two conclusions. First,the inception angle slightly affects the coefficient, but thelightning position strongly affects the coefficient. Second, theinception angle is not affected by the arrival time, but the

lightning position is highly affected by the time of arrivaltime from the distance between the lightning point and theend substation. Thus, the arrival time detected by the nearerstation will be faster than that of the other station.

(b) Behaviour of Single-Line Fault onTransmission Line. In thiscase, a single-line fault occurred at phase A, and the effectof the parameters, the inception angle and fault position,was observed on the characteristic of the current at thesending and receiving substations. Figures 5(a) and 5(b) arethe characteristic current graphs at the sending and receivingsubstations. Figures 5(c) and 5(d) are graphs of Figures 5(a)and 5(b) after the wavelet transform.

From the sending substation, the current at the faultphase, phase A, increased in the positive direction. Thedirection of the change is according to the current waveform.At 2 ms, the time at which the fault occurred, the direction ofthe fault phase is positive, so the amplitude also increases inthe positive direction.The amplitudes of the other two phases,inwhich the fault does not occur, slightly increase because theeffect of the change in the magnetic field is less.

From the receiving substation, the characteristic of thethree-phase currents is similar to that at the sending substa-tion, where the amplitude of the current at phase A is higherthan that at phase B and phase C. The direction of phase A

Page 6: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

6 Mathematical Problems in Engineering

Lightning phase A, Location 40% (RYG)

330

331

332

333

334

335

336

337

Coe

ffici

ent o

f wav

elet

30 60 90 120 150 180 210 240 270 300 3300Angle (degree)

338

(a)

Lightning phase A, Location 40% (CTI)

0 30 60 90 120 150Angle (degree)

180 210 240 270 300 330219

219.5

220

220.5

221

221.5

222

222.5

223

Coe

ffici

ent o

f wav

elet

(b)

Figure 4: Summary ofDWTof positive-sequence current resultswhen inception angles of lightning conditionwere varied (lightning location30%). (a) Sending substation (RYG). (b) Receiving substation (CTI).

Sending substation (RYG)

lalb

lc

−3000

−2000

−1000

0

1000

2000

3000

Curr

ent (

A)

0.005 0.01 0.015 0.02 0.025 0.030Time (s)

(a)

Receiving substation (CTI)

lalb

lc

−3000

−2000

−1000

0

1000

2000

3000

Curr

ent (

A)

0.005 0.01 0.015 0.02 0.025 0.030Time (s)

(b)

Sending end (RYG)

−1000

0

1000

2000

Curr

ent (

A)

0.001 0.002 0.003 0.004 0.0050Time (s)

0.001 0.002 0.003 0.004 0.0050Time (s)

0

10

20

30

Coe

ffici

ent

Wav

elet

(c)

Receiving end (CTI)

−10000

100020003000

Curr

ent (

A)

0

1

2

Coe

ffici

ent

wav

elet

0.001 0.002 0.003 0.004 0.0050Time (s)

0.001 0.002 0.003 0.004 0.0050Time (s)

(d)

Figure 5: Case of phase-A-to-ground fault at 30% of transmission line (inception angle 0∘). (a) All phases at sending substation (RYG). (b) Allphases at receiving substation (CTI). (c) Positive sequence at sending substation (RYG). (d) Positive sequence at receiving substation (CTI).

also changes in the same direction as the sending substationdue to the direction of the current waveform when the faultoccurred. Phase B and phase C slightly change for the samereason mentioned at the sending substation.

In the wavelet graph in Figures 5(c) and 5(d), a peak onlyhappened when the fault occurred.The effect of the inceptionangle and position on the wavelet are considered next.

The results in Figure 6 indicate that the coefficient ofthe wavelet was dependent on the location of the fault. Thedistance directly impacted the impedance, which in turnaffected the inverse current. Thus, the position increase ledto a decrease in the amplitude of the current at the sendingsubstation and an increase in the amplitude of the currentat the receiving substation. The results in Figures 7(a) and

Page 7: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

Mathematical Problems in Engineering 7

0

10

20

30

40

50

60

AG fault, inception angle 0

Coe

ffici

ent o

f wav

elet

Sending end (RYG)Receiving end (CTI)

10 20 30 40 50 60 70 80 90 1000% Location

Figure 6: Summary of DWT results when the location of single linefault condition was varied (inception angle 0∘).

7(b) show that the coefficient also depended on the inceptionangle. The waveform of the current is sinusoidal with theamplitude being dependent on the angle, so the inceptionangle changes the amplitude of the current changes as well.

At the sending substation, the characteristic of the posi-tive current is slightly changed; thus, DWT is better than thepositive current because this method can identify the high-frequency component. From the perspective of the waveletsignal, the coefficient of the wavelet is more apparent thanthat of the positive current method. The coefficient suddenlyoccurred at the time of a fault. From the receiving substation,the characteristic of both currents is similar to that at thesending substation, in that the changing amplitude of thepositive current is less and the coefficient of wavelet isobvious.

Further observation was made for other faults, namely,line-to-line, double-line-to-ground, and three-phase faults,in which the angle and position condition were varied as inthe previous section. Figures 8(a), 8(b), and 8(c) illustratethree example cases, in which the inception angle wasconstant, and the fault positionwas varied.Thefigure displaysthat all types of faults had same characteristic, in whichthe relation between the position and the coefficient at thesending and receiving stations was opposite.

Next, the inception angle was varied, and the faultposition was constant. The observed conditions were thesame as the previous. Figures 9(a), 9(b), and 9(c) show thebehaviour of the coefficient when the fault position is 30% ofthe transmission line, and the inception angle was changedfrom 0∘ to 360∘ in the case of line-to-line, double-line-to-ground, and three-phase faults.Thefigure shows that all faultshave the same characteristic. The trend of the coefficient atthe sending substation is the same as that at the receivingsubstation, which is a sinusoidal signal.

In short, the current attributes from the ATP simulationprogram are not comprehensive for the analysis of lightningand faults because the differentiation between these is notobvious. Next, a transformation will be used to make thecurrent waveform more evident.

4. Algorithm for Discrimination betweenFault and Lightning

The previous section described the behaviour of waveletswhen lightning and faults occur in the transmission sys-tem. This section will describe the discrimination algorithmbetween lightning and faults in transmission line.The impor-tant parameters used for classification consist of 3 param-eters: the initial variables, comparison variables, and checkvariables. The initial variable ismaximumDWTcoefficient ofthree-phase current zero sequence.The comparison variablesare maximum DWT coefficient of Phases A, B, and C. Thecheck variables are the normalization of maximum DWTcoefficient of each phase by dividing the comparison variablesby the initial variable. The example of the algorithm process isillustrated as shown in Figure 10, and the equation to calculatethe check variables of phases A, B, and C can be done using(4)–(6), respectively.

𝑆 𝐴𝑐𝑜𝑚 = 𝐼𝑎 𝑆𝑚𝑎𝑥𝑍𝑒𝑟𝑜 𝑆𝑚𝑎𝑥 (4)

𝑆 𝐵𝑐𝑜𝑚 = 𝐼𝑏 𝑆𝑚𝑎𝑥𝑍𝑒𝑟𝑜 𝑆𝑚𝑎𝑥 (5)

𝑆 𝐶𝑐𝑜𝑚 = 𝐼𝑐 𝑆𝑚𝑎𝑥𝑍𝑒𝑟𝑜 𝑆𝑚𝑎𝑥 (6)

where 𝑍𝑒𝑟𝑜 𝑆𝑚𝑎𝑥 = Initial variable, which is the waveletcoefficient of zero sequence. 𝐼𝑎 𝑆𝑚𝑎𝑥 = Comparison vari-able, which is the wavelet coefficient of phase A. 𝐼𝑏 𝑆𝑚𝑎𝑥= Comparison variable, which is the wavelet coefficient ofphase B. 𝐼𝑐 𝑆𝑚𝑎𝑥 = Comparison variable, which is the waveletcoefficient of phase C. 𝑆 𝐴𝑐𝑜𝑚 = Check variable of phase A.𝑆 𝐵𝑐𝑜𝑚 = Check variable of phase B. 𝑆 𝐶𝑐𝑜𝑚 = Check variableof phase C.

Figure 11 shows a flow chart that is used to discriminatebetween lightning and faults. The chart is based on the threepreviously described concepts. Because lightning is far moredevastating than faults, the coefficient of lightning is higherthan that of a fault. The minimum of the wavelet coefficientat a positive sequence has initial variables higher than those ofa fault. For this reason, the chart can separate lightning andfaults based on the minimum positive sequence (Pos min);Pos min higher than 53 indicates lightning. Tables 3 and 4show the result of discrimination based on this flow chart.The data in this table are based on varying the parameters ofinception angle, phase, and location along the transmissionline. Only a maximum positive sequence (Pos Smax) in thelightning case is higher than 53. The other cases, in whichPos Smax is less than 53, are fault cases.

Table 2 shows the parameters in a normal state. Allterms in this case are low, which indicates that the waveletcoefficient of the normal state is low at each phase. Itsinfluence on all the variables in the normal case is low.

Table 3 shows the parameters when lightning strikes atan inception angle of 0∘ and at a location of 30% of thetransmission line. The minimum wavelet coefficient of thepositive sequence is higher than 53, and the initial variablesshow that the value of each phase is clearly different, of which

Page 8: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

8 Mathematical Problems in Engineering

Fault phase A, location 40% (RYG)

30 60 90 120 150 180 210 240 270 300 3300Angle (degree)

0

5

10

15

20C

oeffi

cien

t of w

avel

et

(a)

Fault phase A, location 40% (CTI)

30 60 90 120 150 180 210 240 270 300 3300Angle (degree)

0

5

10

15

Coe

ffici

ent o

f wav

elet

(b)

Figure 7: Summary of DWT of positive sequence current results when inception angles of single line fault condition were varied (Faultlocation 30%). (a) Sending substation (RYG). (b) Receiving substation (CTI).

AB fault, inception angle 0

Sending end (RYG)Receiving end (CTI)

0

10

20

30

40

50

60

Coe

ffici

ent o

f wav

elet

10 20 30 40 50 60 70 80 90 1000% Location

(a)

ABG fault, inception angle 0

Sending end (RYG)Receiving end (CTI)

0

10

20

30

40

50

60

70

80C

oeffi

cien

t of w

avel

et

10 20 30 40 50 60 70 80 90 1000% Location

(b)

ABCG fault, inception angle 0

Sending end (RYG)Receiving end (CTI)

10 20 30 40 50 60 70 80 90 1000% Location

0

10

20

30

40

50

60

Coe

ffici

ent o

f wav

elet

(c)

Figure 8: Summary of DWT results when location of the fault was varied (inception angle 0∘). (a) Line-to-line fault. (b) Double-line-to-ground fault case. (c) Three-phase fault.

Page 9: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

Mathematical Problems in Engineering 9

Sending station Receiving station

0

10

20

30

40

50

60

Fault phase AB, location 40% (RYG)

Coe

ffici

ent o

f wav

elet

05

1015202530354045

Fault phase AB, location 40% (CTI)

Coe

ffici

ent o

f wav

elet

30 60 90 120 150 180 210 240 270 300 3300Angle (degree)

30 60 90 120 150 180 210 240 270 300 3300Angle (degree)

(a)

Sending station Receiving station

0

10

20

30

40

50

60

70Fault phase ABG, location 40% (RYG)

Coe

ffici

ent o

f wav

elet

0

10

20

30

40

50Fault phase ABG, location 40% (CTI)

Coe

ffici

ent o

f wav

elet

30 60 90 120 150 180 210 240 270 300 3300Angle (degree)

30 60 90 120 150 180 210 240 270 300 3300Angle (degree)

(b)

Sending station Receiving station

0

20

40

60

80

Fault phase ABC, location 40% (RYG)

Coe

ffici

ent o

f wav

elet

0

10

20

30

40

50

60Fault phase ABC, location 40% (CTI)

Coe

ffici

ent o

f wav

elet

30 60 90 120 150 180 210 240 270 300 3300Angle (degree)

30 60 90 120 150 180 210 240 270 300 3300Angle (degree)

(c)

Figure 9: Summary of DWT results when the inception angle of the fault condition was varied (fault location 30%). (a) Line-to-line fault.(b) Double-line-to-ground fault. (c) Three-phase fault.

Page 10: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

10 Mathematical Problems in Engineering

0 0.002 0.0040

200

400

Time (s)

0 0.002 0.0040

5

10

Time (s)

0 0.002 0.0040

50

Scal

e 1

Scal

e 1Sc

ale 1

Scal

e 1

Scal

e 1Sc

ale 1

Scal

e 1

Time (s)

0 0.002 0.004036

Time (s)0 0.002 0.004

0

20

40

Time (s)

Ia_Smax Ib_Smax Ic_Smax

Zero_Smax

Sa_com = Ia_Smax

224.5902

Zero_SmaxSb_com = Ib_Smax

Zero_SmaxSa_com = Ia_Smax

Zero_Smax

56.1444

7.5540

29.7314 7.4324

0 0.002 0.004036

Time (s)

7.4377

0 0.002 0.0040

50

Time (s)

56.1840

Figure 10: Operation for discrimination between lightning and fault.

If

If

lightning

Fault

If S_Acom>0.5S_Phmax

If S_Acom<0.5S_Phmax

If S_Bcom>0.5Ph_max

If S_Bcom<0.5S_Phmax

If S_Ccom>0.5S_Phmax

If S_Ccom<0.5S_Phmax

If S_Acom>0.25S_Phmax

If S_Acom<0.25S_Phmax

If S_Bcom>0.25S_Phmax

If S_Bcom<0.25S_Phmax

If S_Ccom>0.25S_Ph_max

If S_Ccom<0.25S_Ph_max

Lightning

Not lightning

Fault

Not fault

Ground faultNot ground fault

Three-phase fault

If Zero_Smax>0.00153

If Zero_Smax<0.00153

If (S_Acom∗S_Bcom∗S_Ccom)^3<4x10^30

Phase A

Phase B

Phase C

Phase A

Phase B

Phase C

Ground

Lightning

Not lightning Lightning

Not lightning

Fault

Not fault Fault

Not fault

If (S_Acom∗S_Bcom∗S_Ccom)^3>4x10^30

Pos_min<53

Pos_min>53

Figure 11: Flow chart for classification between lightning and fault.

phase A is the highest. Thus, lightning strikes at the phasecase.

Table 4 shows the 3 parameters when single-line faultsoccur in a transmission line. A comparison between Tables3 and 4 shows that the coefficient of the positive sequencein the lightning case is higher than that of the fault cause,which is consistent with the previous one; the coefficient oflightning is higher than any fault case. The initial variables,Ia Smax, Ib Smax, Ic Smax, and coefficient of phase A, are

higher than those of phase B and phase C. Furthermore, thegrounding fault is considered using zero sequence.The valuesindicate that the coefficient of the zero sequence is higherthan 0.00153. According to the flow chart, it is concluded thatthe fault occurring in the transmission line is single-line-to-ground at phase A.

Figure 12 shows the results of lightning and fault clas-sification. The results indicate that the proposed methodclassifies faults and lightning with 100% accuracy with varied

Page 11: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

Mathematical Problems in Engineering 11

Table 2: Variables at normal condition of transmission system.

Normal ConditionInitial variable

Pos Smax Pos Rmax Ia Smax Ib Smax Ic Smax Zero Smax

3.1 x 10−5 9.8 x 10−5 2.6 x 10−5 9.5 x 10−5 2.6 x 10−5 2.4 x 10−5

Compared VariableS Acom S Bcom S Ccom

1.0552 0.0385 1.0552Check Variable

S Phmax S Phmin

1.0552 0.0385

Table 3: Lightning condition.

Initial variableLightning locationon transmission line Voltage angle Pos Smax Pos Rmax Pos min Ia Smax Ib Smax Ic Smax Zero Smax

30% 0∘ 336.9104 222.5332 222.5332 224.5902 56.1444 56.184 7.554Compared variable

Fault location ontransmission line

Voltage angle S Acom S Bcom S Ccom

30% 0∘ 29.7314 7.4324 7.4377Check variable

Fault location ontransmission line

Voltage angle S Phmax S Phmin

30% 0∘ 29.7314 7.4324Result

Type Pos min higher than 53 LightningPhase S Acom higher than other phases,4 times Phase A

Table 4: Single-line-to-ground fault condition.

Initial variableLightning locationon transmission line Voltage angle Pos Smax Pos Rmax Pos min Ia Smax Ib Smax Ic Smax Zero Smax

30% 0∘ 13.3318 8.8739 8.8739 8.8806 2.2321 2.2195 0.0893Compared variable

Fault location ontransmission line Voltage angle S Acom S Bcom S Ccom

30% 0∘ 99.4347 24.9921 24.8515Check variable

Fault location ontransmission line Voltage angle S Phmax S Phmin

30% 0∘ 99.4347 24.8515Result

Type Pos min lower than 53 FaultPhase S Acom higher than other phases,4 times Phase A

inception angle and position. The classification among faultshad lower accuracy than lightning cases. The single-line faulthad a slight error at positions 50% and 80% of transmissionline. The error of the line-to-line fault was slight at positions

20%, 40%, and 50% of line. A slight error was found in thedouble-line-to-ground fault at positions near the terminalline. The last fault case was the three-phase fault. Three-phase faults, as shown in Figure 12(d), have an accuracy trend

Page 12: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

12 Mathematical Problems in Engineering

99

100

101In case of lightning

% A

vera

ge a

ccur

acy

20 30 40 50 60 70 80 9010

% Location of transmission line(a)

% A

vera

ge a

ccur

acy

90

95

100

In case of single-line-to-ground fault

20 30 40 50 60 70 80 9010% Location of transmission line

(b)

% A

vera

ge a

ccur

acy

90

95

100

In line-to-line fault

20 30 40 50 60 70 80 9010% Location of transmission line

(c)

% A

vera

ge a

ccur

acy

70

75

80

85

In case of double-line-to-ground fault

20 30 40 50 60 70 80 9010% Location of transmission line

(d)

% A

vera

ge a

ccur

acy

70

80

90

100

In three-phase fault

20 30 40 50 60 70 80 9010% Location of transmission line

(e)

Figure 12: Accuracy of each type of fault when inception angle and phase were varied. (a) Lightning type. (b) Single-line fault. (c) Line-to-linefault. (d) Double-line-to-ground fault. (e) Three-phase fault.

similar to that of the double-line-to-ground fault, which hasa slight error at the terminal end, at positions 70% to 90% ofthe line.

5. Conclusion

This research aimed to analyse the behaviour and charac-teristics of transmission system when lightning and faults

occur. Analyses were performed by obtaining the signal andhigh-frequency component from a wavelet transform. Fromthe characteristic, the three-phase currents were found toincrease to higher values than the normal state currents. Theincreasing currents of the lightning phase are higher thanthosewithout lightning, because this phase is directly affectedby the lightning current, whereas the others are indirectlyaffected by the change in themagnetic fields.Thefields induce

Page 13: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

Mathematical Problems in Engineering 13

Table 5: Parameter of 115 kV transmission line and tower.

Tower characteristicTower Name DA1Conductor size 795 MCMACSR/GARuling span 330 m. (Distance from tower to tower)

Conductor characteristicSize 795 MCMACSR/GADiameter 26.80 mm.Number of conductors 1 conductor per bundleCurrent capacity 845 A per conductorMax. sag of conductor 10.55 m.

Overhead ground wire characteristicSize 3/8” (HS) Galvanized steelDiameter 9.144 mm.Number of conductors 1 conductor

an increase in current. The behaviour of faults is similar tothat of lightning, in which the amplitude of the fault phaseincreases and the others slightly increase. The change in thefaults is lower than that in lightning because the short-circuitcurrent caused by lightning is higher due to the amplitude oflightning currents. However, the short-circuit current causedby faults is low because of the fault phase. The short-circuitcurrents depend on the fault phase, so a three-phase fault,which has the maximum fault phase, has the highest short-circuit currents. Simultaneously, a single-phase fault, whichhas the minimum fault phase, has the least short-circuitcurrents. The positive currents originate from three-phasecurrents separated into three elements: positive, negative, andzero sequences. The positive sequence was observed, andthe direction of positive currents was found to depend onthe direction of the lightning and fault phase. Based on thewavelet transform, it was shown that the coefficient of thewavelet depends on the inception angle and the position ofthe lightning and faults. Because the original current is sinu-soidal, which has positive- and negative-amplitude currentsvarying in angles, the coefficient changes according to theangle. In addition, the positions also affect the coefficientbecause the distance between the reference and accidentpositions caused an impedance. This research referencedaccident points from the sending substation; thus, as thedistance increases, the coefficient of the wavelet detected atthe sending substation decreases. Meanwhile, the trends atthe receiving substation are the opposite.

The result from the proposed classification algorithm, theproposed method, classifies faults and lightning with 100%accuracy in all case study, while in case of fault it can achievelower accuracy due to the slight error in detecting the highfrequency component of DWT in different types of fault. Oneof the reasons is the current signal in some types of faultwhen applied DWT generated the similar coefficient value.This result, in the algorithm, identifies wrong types of faults.In case of lightning, the algorithm can correctly identifybecause the lightning signal has significant differentiatecharacteristic.

Appendix

The details of 115 kV transmission line and tower fromEGAT transmission system using in ATP/EMTP softwaresimulation are shown in Table 5. The calculation of surgeimpedance for high voltage transmission tower using insimulation based on IEEE and CIGRE can be calculated byusing (A.1)–(A.4).

𝑍𝑖 = 60 log𝑒 cot{0.5 tan−1 ( 𝑑𝑖2ℎ𝑖)} (A.1)

Δ𝑅𝑖 ={{{{{{{{{

2𝑍1(𝑙1 + 𝑙2 + 𝑙3)𝐼𝑛 (1

0.8144) ; (𝑖 = 123)2𝑍4(𝑙4) 𝐼𝑛 (

10.8144) ; (𝑖 = 4)

(A.2)

𝑅𝑖 = Δ𝑅𝑖𝑙𝑖 (A.3)

𝐿 𝑖 = 4𝐻V ⋅ 𝑅𝑖 (A.4)

Data Availability

The data used to support the findings of this study areavailable from the corresponding author upon request.

Conflicts of Interest

The authors declare that they have no conflicts of interest.

Acknowledgments

The research presented in this paper is part of a researchproject sponsored by the Srinakharinwirot UniversityResearch Fund. The authors would like to gratefullyacknowledge the financial support for this research.

Page 14: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

14 Mathematical Problems in Engineering

References

[1] L. Li and V. A. Rakov, “Distribution of currents in the lightningprotective system of a residential building - Part II: Numericalmodeling,” IEEE Transactions on Power Delivery, vol. 23, no. 4,pp. 2447–2455, 2008.

[2] J. Zou, J. Lee, Y. Ji, S. Chang, B. Zhang, and J. He, “Transientsimulation model for a lightning protection system usingthe approach of a coupled transmission line network,” IEEETransactions on Electromagnetic Compatibility, vol. 49, no. 3, pp.614–622, 2007.

[3] A. Ceclan, V. Topa, D. D. Micu, and A. Andreotti, “Lightning-inverse reconstruction by remote sensing and numerical-fieldsynthesis,” IEEE Transactions on Magnetics, vol. 49, no. 5, pp.1657–1660, 2013.

[4] I. Cotton, K. Kopsidas, and Y. Zhang, “Comparison of transientand power frequency-induced voltages on a pipeline parallelto an overhead transmission line,” IEEE Transactions on PowerDelivery, vol. 22, no. 3, pp. 1706–1714, 2007.

[5] V. Hegde and V. Shivanand, “On the influence of steel geometryon the induced currents in steel reinforced concrete buildingdue to a nearby lightning strike to ground,” IEEE Transactionson Electromagnetic Compatibility, vol. 57, no. 3, pp. 418–424,2015.

[6] A. Andreotti and L. Verolino, “A new channel-base currentfunction for lightning studies,” IEEE Transactions on Electro-magnetic Compatibility, vol. 57, no. 6, pp. 1539–1546, 2015.

[7] V. Javor and P. D. Rancic, “A channel-base current functionfor lightning return-stroke modeling,” IEEE Transactions onElectromagnetic Compatibility, vol. 53, no. 1, pp. 245–249, 2011.

[8] S. Sesnic, D. Poljak, and S. V. Tkachenko, “Analytical modelingof a transient current flowing along the horizontal groundingelectrode,” IEEE Transactions on Electromagnetic Compatibility,vol. 55, no. 6, pp. 1132–1139, 2013.

[9] P. Manoochehrnia, F. Rachidi,M. Rubinstein,W. Schulz, andG.Diendorfer, “Benford’s law and its application to lightning data,”IEEE Transactions on Electromagnetic Compatibility, vol. 52, no.4, pp. 956–961, 2010.

[10] M. Rubinstein, J.-L. Bermudez, V. Rakov, F. Rachidi, and A.Hussein, “Compensation of the instrumental decay inmeasuredlightning electric field waveforms,” IEEE Transactions on Elec-tromagnetic Compatibility, vol. 54, no. 3, pp. 685–688, 2012.

[11] J. A. Morales and E. Orduna, “Patterns extraction for lightningtransmission lines protection based on principal componentanalysis,” IEEE LatinAmerica Transactions, vol. 11, no. 1, pp. 518–524, 2013.

[12] E. S. Andrade Melo Luz, R. M. E. S. de Oliveira, and P. LopesMacHado, “Calculation of lightning-induced voltages and cur-rents on the transformers courtyard of tucuruı hydroelec-tric generation plant using the finite-difference time-domainmethod,” IEEE Latin America Transactions, vol. 14, no. 4, pp.1600–1611, 2016.

[13] K. Chen, C. Huang, and J. He, “Fault detection, classificationand location for transmission lines and distribution systems: areview on the methods,” High Voltage, vol. 1, no. 1, pp. 25–33,2016.

[14] M. Majidi, M. Etezadi-Amoli, and M. S. Fadali, “A sparse-data-driven approach for fault location in transmission networks,”IEEETransactions on Smart Grid, vol. 8, no. 2, pp. 548–556, 2017.

[15] X. Liang, S.A.Wallace, andD.Nguyen, “Rule-baseddata-drivenanalytics for wide-area fault detection using synchrophasor

data,” IEEE Transactions on Industry Applications, vol. 53, no.3, pp. 1789–1798, 2017.

[16] F. B. Costa, A. Monti, F. V. Lopes, K. M. Silva, P. Jambor-salamati, and A. Sadu, “Two-terminal traveling-wave-basedtransmission-line protection,” IEEE Transactions on PowerDelivery, vol. 32, no. 3, pp. 1382–1393, 2017.

[17] X. Yao, L. Herrera, S. Ji, K. Zou, and J. Wang, “Characteris-tic study and time-domain discrete-wavelet-transform basedhybrid detection of series DC arc faults,” IEEE Transactions onPower Electronics, vol. 29, no. 6, pp. 3103–3115, 2014.

[18] H. A. Darwish, M. Hesham, A.-M. I. Taalab, and N. M.Mansour, “Close accord on DWT performance and real-timeimplementation for protection applications,” IEEE Transactionson Power Delivery, vol. 25, no. 4, pp. 2174–2183, 2010.

[19] K. Chen, J. Hu, and J. He, “Detection and classification oftransmission line faults based on unsupervised feature learningand convolutional sparse autoencoder,” IEEE Transactions onSmart Grid, vol. 9, no. 3, pp. 1748–1758, 2018.

[20] M. Korkali, H. Lev-Ari, and A. Abur, “Traveling-wave-basedfault-location technique for transmission grids via wide-areasynchronized voltage measurements,” IEEE Transactions onPower Systems, vol. 27, no. 2, pp. 1003–1011, 2012.

[21] N. I. Elkalashy, M. Lehtonen, H. A. Darwish, A.-M. I. Taalab,and M. A. Izzularab, “DWT-based detection and transientpower direction-based location of high-impedance faults dueto leaning trees in unearthedMV networks,” IEEE Transactionson Power Delivery, vol. 23, no. 1, pp. 94–101, 2008.

[22] J. Klomjit, A. Ngaopitakkul, and B. Sreewirote, “Comparison ofmother wavelet for classification fault on hybrid transmissionline systems,” in Proceedings of the 2017 IEEE 8th InternationalConference on Awareness Science and Technology (iCAST), pp.527–532, Taichung, November 2017.

Page 15: Classification of Lightning and Faults in …downloads.hindawi.com/journals/mpe/2018/1847968.pdfmodel is based on a double-conductor system, which can bereduced toatwo-portequivalent

Hindawiwww.hindawi.com Volume 2018

MathematicsJournal of

Hindawiwww.hindawi.com Volume 2018

Mathematical Problems in Engineering

Applied MathematicsJournal of

Hindawiwww.hindawi.com Volume 2018

Probability and StatisticsHindawiwww.hindawi.com Volume 2018

Journal of

Hindawiwww.hindawi.com Volume 2018

Mathematical PhysicsAdvances in

Complex AnalysisJournal of

Hindawiwww.hindawi.com Volume 2018

OptimizationJournal of

Hindawiwww.hindawi.com Volume 2018

Hindawiwww.hindawi.com Volume 2018

Engineering Mathematics

International Journal of

Hindawiwww.hindawi.com Volume 2018

Operations ResearchAdvances in

Journal of

Hindawiwww.hindawi.com Volume 2018

Function SpacesAbstract and Applied AnalysisHindawiwww.hindawi.com Volume 2018

International Journal of Mathematics and Mathematical Sciences

Hindawiwww.hindawi.com Volume 2018

Hindawi Publishing Corporation http://www.hindawi.com Volume 2013Hindawiwww.hindawi.com

The Scientific World Journal

Volume 2018

Hindawiwww.hindawi.com Volume 2018Volume 2018

Numerical AnalysisNumerical AnalysisNumerical AnalysisNumerical AnalysisNumerical AnalysisNumerical AnalysisNumerical AnalysisNumerical AnalysisNumerical AnalysisNumerical AnalysisNumerical AnalysisNumerical AnalysisAdvances inAdvances in Discrete Dynamics in

Nature and SocietyHindawiwww.hindawi.com Volume 2018

Hindawiwww.hindawi.com

Di�erential EquationsInternational Journal of

Volume 2018

Hindawiwww.hindawi.com Volume 2018

Decision SciencesAdvances in

Hindawiwww.hindawi.com Volume 2018

AnalysisInternational Journal of

Hindawiwww.hindawi.com Volume 2018

Stochastic AnalysisInternational Journal of

Submit your manuscripts atwww.hindawi.com