Civil Design
-
Upload
basusoumen2011 -
Category
Documents
-
view
8 -
download
0
Transcript of Civil Design
Sheet1Clarifier Civil design Input data1SBC OF SOIL =45T/SQMH2/Dt =2.62INNER DIMETER OF CLARIFLOCCULATOR =35.8MBending Moment Coefficient =0.037423TOTAL HEIGHT OF CLARIFLOCCULATOR =5.2MMax Bending Moment =52.62KN/M4WALL THICKNESS OF CLARIFLOCCULATOR =0.29M Min thk reqd for M25=420mm5BASE RAFT THICKNESS0.275MZ for resisting bending=14016666.666666666mm36SHAFT DIAMETER OF CLARIFLOCCULATOR =1MBending Stress=0.26N/sqmm7SHAFT WALL THICKNESS OF CLARIFLOCCULATOR=0.2MHopp tension Coeff=0.2858CANTILEVER LENGTH OF R.C.C. LOUNDER =0.8MHoop tension=265.28kN9VERTICAL HEIGHT OF R.C.C. LOUNDER =1.1MHoop stress=0.91N/sqmm10THICKNESS OF R.C.C LOUNDER =0.2MCombined Stress=0.8511RUBBLE SOLING THICKNESS0M12FOUNDING DEPTH =1M13WIDTH OF WALL FTNG=0.8M14THICKNESS OF WALL FTNG=0.8M
OUTPUT DATA:-1WT OF LAUNDER WALL656.25QUANTITIES2WT OF LAUNDER SLAB467.221EXCAVATION =194.60CU.M.3WT OF WATER IN LAUNDER954.542BACKFILLING =58.38CU.M.4WT OF PLATFORM LOAD 501.133TRANSPORTATION =136.22CU.M.5WT OF WALL4308.784P.C.C.113.03CU.M.6WT OF WATER IN TANK52343.086R.C.C.587.30CU.M.7SLF WT OF BASE RAFT6920.367REINFORCEMENT =58.73M.T.TOTAL13775.838W/P COMPOUND =4698.38K.G.9SHUTTERING CURVED =1609.69SQ.M.WIDTH OF FTNG REQD0.2710WATER BARS =611.83M11RUBBLE SOLING=0.00CU.M.12INSERT PLATES =0.50M.T.13PUDDLE PIPES =0.50M.T.14HAND RAILING =113.38M15HYDROTESTING5231.65CU.M.
85.6