PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-1© 2014 Mitsubishi Electric US, Inc.
CITY MULTI® H2I® Y-SERIES Hyper-heating Inverter System Design
1. ELECTRICAL WORK ..........................................................................................................................................H2i-YSD-21-1. General Cautions .......................................................................................................................................H2i-YSD-2
2. M-NET CONTROL ...............................................................................................................................................H2i-YSD-62-1. Transmission Cable Length Limitations .....................................................................................................H2i-YSD-62-2. Transmission Cable Specifications ............................................................................................................H2i-YSD-72-3. System Configuration Restrictions .............................................................................................................H2i-YSD-82-4. Address Setting ........................................................................................................................................H2i-YSD-11
3. PIPING DESIGN ...............................................................................................................................................H2i-YSD-233-1. R410A Piping Material..............................................................................................................................H2i-YSD-233-2. Piping Design ...........................................................................................................................................H2i-YSD-243-3. Refrigerant Charge Calculation ................................................................................................................H2i-YSD-26
4. OUTDOOR INSTALLATION ..............................................................................................................................H2i-YSD-274-1. Installation Site Requirements .................................................................................................................H2i-YSD-274-2. Installation Clearance Space ...................................................................................................................H2i-YSD-284-3. Piping Direction ........................................................................................................................................H2i-YSD-304-4. Weather Countermeasures ......................................................................................................................H2i-YSD-354-5. Low Ambient Kit Application Guidelines ...................................................................................................H2i-YSD-36
5. INSTALLATION INFORMATION .......................................................................................................................H2i-YSD-385-1. General precautions .................................................................................................................................H2i-YSD-385-2. Precautions for Indoor unit .......................................................................................................................H2i-YSD-395-3. Precautions for Fresh air intake type indoor unit .....................................................................................H2i-YSD-405-4. Precautions for Outdoor unit/Heat source unit .........................................................................................H2i-YSD-405-5. Precautions for Control-related items.......................................................................................................H2i-YSD-41
6. STANDARD AND SEACOAST (BS) PROTECTION TREATMENT...................................................................H2i-YSD-426-1. H2i Y-Series .............................................................................................................................................H2i-YSD-42
7. CAUTIONS ........................................................................................................................................................H2i-YSD-437-1. Refrigerant Leakage Considerations .......................................................................................................H2i-YSD-43
H2iYSD-2 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
1. ELECTRICAL WORK
OK NO
Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiringregulations, and guidance of each electric power company.Wiring for control (hereinafter referred to as transmission ) shall be (50mm[1-5/8in] or more) apart from power source
source wire in the same conduit.)Be sure to provide designated grounding work to outdoor unit.Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removedat the time of service work.Never connect 100V, 208~230V power source to terminal block of transmission . If connected,electrical parts will be burnt out.
Use 2-core shield cable for transmission . If transmission of different systems are wired with the same multiplecore cable, the resultant poor transmitting and receiving will cause erroneous operations.
Outdoorunit
Indoor unit
Remote
BC controllercontroller
2-core shield cable
2-core shield cable
Outdoorunit
Remotecontroller
Indoor unit
Multiple-core cable
BC controller
wiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission and power cable
cable
cable cables
cable
1-1. General Cautions
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-3© 2014 Mitsubishi Electric US, Inc.
1. ELECTRICAL WORK
1-2. Power Supply for Indoor and Outdoor Units1-2-1. Electrical Characteristics of the Indoor Units
Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor
ModelIndoor Unit IFM
Hz Volts Voltage range MCA(A) FLA(A)PLFY-P08NCMU-ER4
60Hz 208 / 230V 198 to 253V
0.29 / 0.29 0.23 / 0.23PLFY-P12NCMU-ER4 0.35 / 0.35 0.28 / 0.28PLFY-P15NCMU-ER4 0.35 / 0.35 0.28 / 0.28PLFY-P12NBMU-ER2 0.64 / 0.64 0.51 / 0.51PLFY-P15NBMU-ER2 0.64 / 0.64 0.51 / 0.51PLFY-P18NBMU-ER2 0.64 / 0.64 0.51 / 0.51PLFY-P24NBMU-ER2 0.64 / 0.64 0.51 / 0.51PLFY-P30NBMU-ER2 0.64 / 0.64 0.51 / 0.51PLFY-P36NBMU-ER2 1.25 / 1.25 1.00 / 1.00
PMFY-P06NBMU-ER5
60Hz 208 / 230V 188 to 253V
0.25 / 0.25 0.20 / 0.20PMFY-P08NBMU-ER5 0.25 / 0.25 0.20 / 0.20PMFY-P12NBMU-ER5 0.26 / 0.26 0.21 / 0.21PMFY-P15NBMU-ER5 0.33 / 0.33 0.26 / 0.26
PEFY-P06NMAU-E3
60Hz 208 / 230V 188 to 253V
1.05 / 1.05 0.84 / 0.84PEFY-P08NMAU-E3 1.05 / 1.05 0.84 / 0.84PEFY-P12NMAU-E3 1.20 / 1.20 0.96 / 0.96PEFY-P15NMAU-E3 1.45 / 1.45 1.16 / 1.16PEFY-P18NMAU-E3 1.56 / 1.56 1.25 / 1.25PEFY-P24NMAU-E3 2.73 / 2.73 2.18 / 2.18PEFY-P27NMAU-E3 2.73 / 2.73 2.18 / 2.18PEFY-P30NMAU-E3 2.73 / 2.73 2.18 / 2.18PEFY-P36NMAU-E3 3.32 / 3.32 2.66 / 2.66PEFY-P48NMAU-E3 3.41 / 3.41 2.73 / 2.73PEFY-P54NMAU-E3 3.31 / 3.31 2.65 / 2.65
PEFY-P06NMSU-ER2
60Hz 208 / 230V
188 to 253V
0.47 / 0.50 0.32 / 0.31PEFY-P08NMSU-ER2 0.47 / 0.50 0.41 / 0.39PEFY-P12NMSU-ER2 0.68 / 0.74 0.46 / 0.43PEFY-P15NMSU-ER2 1.20 / 1.33 0.47 / 0.45PEFY-P18NMSU-ER2 1.20 / 1.33 0.64 / 0.60PEFY-P24NMSU-ER2 1.57 / 1.73 0.88 / 0.83PEFY-P15NMHU-E2 1.63 / 1.50 1.30 / 1.20PEFY-P18NMHU-E2 1.63 / 1.50 1.30 / 1.20PEFY-P24NMHU-E2 2.11 / 1.83 1.69 / 1.46PEFY-P27NMHU-E2 2.35 / 2.13 1.88 / 1.70PEFY-P30NMHU-E2 2.70 / 2.45 2.16 / 1.96PEFY-P36NMHU-E2 4.16 / 3.67 3.32 / 2.94PEFY-P48NMHU-E2 4.16 / 3.67 3.32 / 2.94PEFY-P54NMHU-E2 4.18 / 3.69 3.34 / 2.95PEFY-P72NMHSU-E
187 to 253V7.7 6.2
PEFY-P96NMHSU-E 8.2 6.6
H2iYSD-4 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
1. ELECTRICAL WORK
Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load AmpsIFM :Indoor Fan Motor
ModelIndoor Unit IFM
Hz Volts Voltage range MCA(A) FLA(A)PCFY-P15NKMU-ER1
60Hz 208 / 230V 188 to 253V
0.44 / 0.44 0.35 / 0.35PCFY-P24NKMU-ER1 0.52 / 0.52 0.41 / 0.41PCFY-P30NKMU-ER1 1.22 / 1.22 0.97 / 0.97PCFY-P36NKMU-ER1 1.22 / 1.22 0.97 / 0.97
PKFY-P06NBMU-E2
60Hz 208 / 230V 198 to 253V
0.19 / 0.19 0.15 / 0.15PKFY-P08NHMU-E2 0.38 / 0.38 0.30 / 0.30PKFY-P12NHMU-E2 0.38 / 0.38 0.30 / 0.30PKFY-P15NHMU-E2 0.38 / 0.38 0.30 / 0.30PKFY-P18NHMU-E2 0.38 / 0.38 0.30 / 0.30PKFY-P24NKMU-E2.TH 0.63 / 0.63 0.50 / 0.50PKFY-P30NKMU-E2.TH 0.63 / 0.63 0.50 / 0.50
PFFY-P06NEMU-E
60Hz 208 / 230V 188 to 253V
0.32 / 0.34 0.25 / 0.27PFFY-P08NEMU-E 0.32 / 0.34 0.25 / 0.27PFFY-P12NEMU-E 0.34 / 0.38 0.27 / 0.30PFFY-P15NEMU-E 0.40 / 0.44 0.32 / 0.35PFFY-P18NEMU-E 0.48 / 0.53 0.38 / 0.42PFFY-P24NEMU-E 0.59 / 0.64 0.47 / 0.51
PFFY-P06NRMU-E
60Hz 208 / 230V 188 to 253V
0.32 / 0.34 0.25 / 0.27PFFY-P08NRMU-E 0.32 / 0.34 0.25 / 0.27PFFY-P12NRMU-E 0.34 / 0.38 0.27 / 0.30PFFY-P15NRMU-E 0.40 / 0.44 0.32 / 0.35PFFY-P18NRMU-E 0.48 / 0.53 0.38 / 0.42PFFY-P24NRMU-E 0.59 / 0.64 0.47 / 0.51
PVFY-P12E00B
60Hz 208 / 230V 188 to 253V
0.52 0.42PVFY-P18E00B 0.78 0.63PVFY-P24E00B 0.99 0.79PVFY-P30E00B 1.33 1.07PVFY-P36E00B 1.51 1.21PVFY-P48E00B 2.02 1.62PVFY-P54E00B 2.04 1.63
PWFY-P36NMU-E-AU60Hz 208 / 230V 188 to 253V
0.09 -PWFY-P72NMU-E-AU 0.09 -
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-5© 2014 Mitsubishi Electric US, Inc.
1. ELECTRICAL WORK
PUHY-HP-T(S)JMUSymbols: MCA : Minimum Circuit Ampacity
SC : Starting Current RLA
5.36.75.35.36.76.7
151515151515
0.920.920.920.920.920.92
Model Outdoor UnitsVoltsHzUnit Combination Voltage range MOCPMCA(A)
CompressorOutput(kW)SC(A)Output(kW)
FanRLA(A) RLA(MAX)(A)
PUHY-HP72TJMU-APUHY-HP96TJMU-A
PUHY-HP144TSJMU-A
PUHY-HP192TSJMU-A PUHY-HP96TJMU-A
PUHY-HP96TJMU-APUHY-HP72TJMU-APUHY-HP72TJMU-A
208 / 230V208 / 230V208 / 230V208 / 230V208 / 230V208 / 230V
60Hz60Hz60Hz60Hz60Hz60Hz
188 to 253V
19.4 / 17.628.2 / 25.519.4 / 17.619.4 / 17.628.2 / 25.528.2 / 25.5
38.4 / 38.452.4 / 52.438.4 / 38.438.4 / 38.452.4 / 52.452.4 / 52.4
59 / 5474 / 6859 / 5459 / 5474 / 6874 / 68
101 / 92127 / 116101 / 92101 / 92127 / 116127 / 116
: Rated Load AmpsMOCP : Maximum Overcurrent Protection
1-2-2. Electrical characteristics of Outdoor unit of cooling mode
To size breakers, see “Recommended Fuse/Breaker Size” in the Specifications table.
H2iYSD-6 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-1. Transmission Cable Length Limitations2-1-1. Using MA Remote controller
2-1-2. Using ME Remote controller
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thickerMax. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7 <=200m[656ft.] 1.25mm2 [AWG16] or thickerMax. length from MA to Indoor a1+a2, a1+a2+a3+a4 <=200m[656ft.] 0.3-1.25 mm2 [AWG22-16]24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14]
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thickerMax. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7, L3+L5 <=200m[656ft.] 1.25mm2 [AWG16] or thickerMax. length from ME to Indoor e1, e2+e3, e4 <=10m[32ft.]*1 0.3-1.25 mm2 [AWG22-16] *124VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm2 [AWG18-14] *1. If the length from ME to Indoor exceed 10m, use 1.25 mm2 [AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.
OC, OS1, OS2 : Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller
OC, OS1, OS2: Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller
M2
TB7
TB3
IC
(52)
M1 M2 1 2STB5 TB15
1 2TB15
1 2TB15
1 2TB15
1 2TB15
1 2TB 15
1 2TB15
MA
(01)
IC
M1 M2 STB5
(02)
IC
M1 M2 STB5
(04)
IC
M1 M2 STB5
(03)
IC
M1 M2 STB5
(05)
IC
M1 M2 STB5
(07)
IC
M1 M2 STB5
(06)L2
L1L8
MA
MA
MA
OS1
TB7
(51)
OC
M1 M2 S
TB7
TB3
(54 )
OC
a1 a4
a3
L8
L3 L4
a2
A BA B A B
A B
a2
a1
a1
a2
Group1 Group3 Group5
Shielded wire
Shielded wire
S
Power Supply Unit
AG-150A
PAC-SC51KUA
L6L2
L7
A B
SA B
M2M1 M1
M2M1
M2 S M2M1 M1 S
TB3
IC
Group1 Group3 Group5
M1 M2 STB5
ME
(01)
IC
M1 M2 STB5
(02)
IC
M1 M2 STB5
(04)
IC
M1 M2 STB5
(03)
IC
M1 M2 STB5
(05)
IC
M1 M2 STB5
(07)
IC
M1 M2 STB5
(06)
L1
(101)
ME
(105)
ME
(103)
ME
(155)
e3
L4
L5
e2
e4
e1
A B A B A B
A B
M2
TB7
TB3
(53)
OS2
M1
M2 SM1
SA B
SA B
M2
TB7
TB3
(52)
OS1
TB7
(51)
OC
M1 M2 S
TB7
TB3
(54 )
OC L3
Power Supply Unit
AG-150A
PAC-SC51KUA
L6L7
M2M1 M1
M2M1
M2 S M2M1
M2
TB7
TB3
(53)
OS2
M1
M2 SM1 M1 S
TB3
V+V-FG
n
V+V-FG
V+V-FG
n
V+V-FG
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-7© 2014 Mitsubishi Electric US, Inc.
2-2. Transmission Cable Specifications
Type of cable
Cable size
Remarks
Sheathed 2-core cable (unshielded)CVV
Shielding wire (2-core)CVVS, CPEVS or MVVS
Transmission cables ME Remote controller cables
CVVS, MVVS: PVC insulated PVC jacketed shielded control cableCPEVS: PE insulated PVC jacketed shielded communication cable
*1 To wire PAC-YT53CRAU, use a wire with a diameter of 0.3 mm2 [AWG22]*2 The use of cables 0.75 mm2 [AWG18] or greater is recommended for easy handling. CVV: PV insulated PVC sheathed control cable
— Max length : 200m [656ft]
(Li) MA Remote controller cables
When 10m [32ft] is exceeded, use cables withthe same specification as transmission cables.
More than 1.25 [AWG16] 2 0.3 1.25 [AWG22 16] *1 *22 0.3 1.25 [AWG22 16]*2
2. M-NET CONTROL
H2iYSD-8 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-3. System Configuration Restrictions
For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table. A) 1 Group of Indoor units can have 1-16 Indoor units;
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit. D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit.E) Maximum 6 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the Outdoor unit. (Not applicable to TKMU model) F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the power supply unit PAC-SC51KUA. Details refer to 2-3-3-C.*System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor unit would stop power supply to the System controller.
2-3-1. Common restrictions for the CITY MULTI system
Transmission Booster
25PAC-SF46EPA
Power supply unit
5PAC-SC51KUA
Outdoor unit
32Connector TB3 and TB7 total *
Outdoor unitTKMU
Outdoor unit(except TKMU)
0Connector TB7 only
6Connector TB7 only
BM ADAPTER
6BAC-HD150
System Controller
6GB-50ADA-A
*If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32. Not applicable to the PUMY model.
Table 2-3-2 The equivalent power supply
With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into the air-conditioner system to ensure proper system communication according to 2-3-2-A, B, C.2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units, ME remote controller, and System controllers. If the total quantity reaches 40, a PAC-SF46EPA should be set. In this case, Indoor units sized P72 and 96 are counted as 2 indoor units, but MA remote controller(s) and PZ-41SLB are NOT counted. 2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption index. If the total power consumption reaches 32, a PAC-SF46EPA should be set. Yet, if a PAC-SC51KUA or another controller with a built-in power supply is used to supply power at TB7 side, count from index TB3 side only.2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption index, If the total power consumption reaches 6, a PAC-SF46EPA should be set.
2-3-2. Ensuring proper communication power for M-NETIn order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY and Controllers, the transmission power situation for the M-NET should be observed. In some cases, Transmission booster should be used. Taking the power consumption index of Indoor unit sized P06-P54 as 1, the equivalent power consumption index and supply capability index of others are listed at Table 2-3-1 and Table 2-3-2.
LOSSNAY remote controller
LOSSNAY remote controller
LOSSNAYunit
LOSSNAYunit
Outdoor unit
M-NET
0201
if the total quantity of Indoor units and ME remote controllers reaches 40, (Indoor units sized P72 and 96 are counted as 2); or if the total equivalent transmission power consumption reaches 32.
N1
N3
N2Transmission booster (No.1) should be used,
1.The total quantity of Indoor units and ME remote controller should not exceed 40. *Indoor units sized P72 and 96 are counted as 2 units.2.The total equivalent transmission power consumption should not exceed 25.
Within N2, conditions 1,2 should be followed.
N4Within N4, the total equivalent transmission power consumption should not exceed 25.
TB7 TB3
TB7 TB3
if the total equivalent transmission power consumption reaches 5. Transmission booster (No.2) should be used,
PAC-SF46EPA
TRANSMISSION BOOSTER
3.4kg
220-240V:0.7A ~/N
WEIGHT
POWER RATING
MODEL
MADE IN JAPAN
50
UP
PAC-SF46EPA
TRANSMISSION BOOSTER
3.4kg
220-240V:0.7A ~/N
WEIGHT
POWER RATING
MODEL
MADE IN JAPAN
50
UP
Transmissionbooster(No.1)
TransmissionboosterPAC-SF46EPA(No.2)
System example
Power supply unitPAC-SC51KUA
24VDC
Centralized controller(AG-150A-A)
CENTRALIZED CONTROLLER AG-150A
B) Maximum 2 remote controllers for 1 Group;*MA/ME remote controllers cannot be present together in 1group.*To wire PAC-YT53CRAU, use a wire with a diameter of 0.3 mm2 [AWG22]
Table 2-3-1 The equivalent power consumption
*RC: Remote Controller
Indoor unit PWFY ME Remote controller/Adapter
1 7 622 0 1 5 0 1/4 1/2
Sized P06-P54
Sized P72, 96
P36NMU-E-BUCMB P36NMU-E-AU
LOSSNAY
LGH-RX-EPEFY-AF1200CFMR
P72NMU-E-AU
MA RC.
PAC-YT53CRAUPAR-FA32MAPZ-41SLBPZ-60DR-E
PZ-52SFPAC-YG60MCAPAC-YG66DCAPAC-YG63MCA
PAR-U01MEDUPAC-IF01AHC-J
Centralized Remote controller
1/2 1 1/2 2
AG-150A-AEB-50GU-A
ON/OFFcontroller
PAC-YT40ANRA CMS-MNF-B CMS-MNG-E
MN Converter Outdoor unitM-NET Interface/Converter
3 0 0 0
GB-24A LMAP04U-EBAC-HD150
MAC-333PAC-SF83MA-E
TB7 power consumption
4
TC-24B
BCcontroller
ME remotecontroller
ME remotecontroller
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-9© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
The power to System controller (excluding LM-AP) is supplied via M-NET transmission line. M-NET transmission line at TB7 side is called Central control transmission line while one at TB3 side is called Indoor-Outdoor transmission line. There are 3 ways to supply power to the System controller .A) Connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.B) Connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit. C) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC51KUA.
Maximum 3 System controllers can be connected to TB3. If there is more than 1 Outdoor unit, it is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit.
Maximum 6 System controllers can be connected to TB7 and receiving power from the Outdoor unit. It is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit.
2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
2-3-3-B. When connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
2-3-3-C. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC51KUA.
2-3-3. Ensuring proper power supply to System controller
Outdoor unit
MA remote controller
Group Group
Indoor unit
M-NET transmission lines(transmission lines for central controller)
Outdoor unit
ME remote controller
Group Group
Indoor unit
Replacement of CN41 with CN40
Use CN41 as it is.
TB7TB3
System controller (excluding LM-AP)
M-NET transmission lines (Indoor-Outdoor transmission lines)
TB7TB3
System controller Maximum 3 System controllers can be connected to TB3.
Fig. 2-3-3-A
M-NET transmission lines(transmission lines for central controller) MA remote controller
ME remote controller
Group Group
Group Group
Indoor unit
Indoor unit
TB3
Outdoor unit
Outdoor unit
Replacement of CN41 with CN40
Use CN41 as it is.
System controller
TB7
TB7TB3
Maximum 6 System controllers can be connected to TB7.
M-NET transmission lines (Indoor-Outdoor transmission lines)
Fig. 2-3-3-B
PAC-SC51KUA
M-NET transmission lines(transmission lines for central controller) MA remote controller
ME remote controller
Group Group
Group Group
Indoor unit
Indoor unit
TB3
Outdoor unit
Outdoor unit
Use CN41 as it is.
Use CN41 as it is.
System controller
TB7
TB7TB3
CAUTION
M-NET transmission lines (Indoor-Outdoor transmission lines)
Fig. 2-3-3-CWhen using PAC-SC51KUA to supply transmission power, the power supply connector CN41 on the Outdoor units should be kept as it is. It is also a factory setting. 1 PAC-SC51KUA supports maximum 1 AG-150A-A or 1 EB-50GU-A unit due to the limited power 24VDC at its TB3. However, 1 PAC-SC51KUA supplies transmission power at its TB2 equal to 5 Indoor units, which is referable at Table 2-3-2.If PZ-52SF, System controller, ON/OFF controller connected to TB7 consume transmission power more than 5 (Indoor units), Transmission booster PAC-SF46EPA is needed. PAC-SF46EPA supplies transmission power equal to 25 Indoor units.
AG-150A-A/EB-50GU-A*1 are recommended to connect to TB7 because it performs back-up to a number of data. In an air conditioner system has more than 1 Outdoor units, AG-150A-A/EB-50GU-A receiving transmission power through TB3 or TB7 on one of the Outdoor units would have a risk that the connected Outdoor unit failure would stop power supply to AG-150A-A/EB-50GU-A and disrupt the whole system. When applying apportioned electric power function, AG-150A-A/EB-50GU-A are necessary to connected to TB7 and has its own power supply unit PAC-SC51KUA.Note: Power supply unit PAC-SC51KUA is for AG-150A-A/EB-50GU-A.*1: AG-150A-A is an example model of system controllers.
H2iYSD-10 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
1-phase 208-230V AC power supply is needed.The power supply unit PAC-SC51KUA is not necessary when connecting only the LM-AP. Yet, make sure to change the power supply changeover connector CN41 to CN40 on the LM-AP.
2-3-4. Power supply to LM-AP
1-phase 100-240VAC power supply is needed.The power supply unit PAC-SC51KUA is not necessary when only BM ADAPTER is connected.Yet, make sure to move the power jumper from CN41 to CN40 on the BM ADAPTER.
2-3-5. Power supply to BM ADAPTER
2-3-6. Power supply to GB-50ADA-A1-phase 100-240VAC power supply is needed.The power supply unit PAC-SC51KUA is not necessary.GB-50ADA-A supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-11© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-4. Address Setting
BranchNo. setting Unit address No. setting
Rotary switchIn order to constitute CITY MULTI in a complete system, switch operation for setting the unit address No. and connection No. is required.
Address No. of outdoor unit, indoor unit and ME remote controller.The address No. is set at the address setting board. In the case of R2 system, it is necessary to set the same No. at the branch No. switch of indoor unit as that of the BC controller connected. (When connecting two or more branches, use the lowest branch No.)Caution for switch operations
MA remote controller
Be sure to shut off power source before switch setting. If operated with power source on, switch can not operate properly.
When connecting only one remote controller to one group, it is always the main remote controller.When connecting two remote controllers to one group, set one remote controller as the main remote controller and the other as the sub remote controller.
No units with identical unit address shall exist in one whole air conditioner system. If set erroneously, the system can not operate.
2-4-1. Switch operation
0 1 2 3 4 5 6 7 8 9 A B C D
E F 0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
The factory setting is Main .
Setting the dip switchesThere are switches on the back of the top case. Remote controller Main/Sub and other function settings are performed using these switches. Ordinarily, only change the Main/Sub setting of SW1.(The factory settings are ON for SW1, 3, and 4 and OFF for SW2.)
SW No
1
2
4
SW contents MainRemote controllerMain/Sub settingTemperature displayunits setting
Indoor temperature display
ON
Main
Celsius
Yes
OFF
Sub
Fahrenheit
No
Comment
Set one of the two remote controllers at one group to “ON”.
When the temperature is displayed in [Fahrenheit], set to “OFF”.
When you do not want to display the indoor temperature, set to “OFF”.
AUTO mode, set to “OFF”.3Cooling/heating display in AUTO mode Yes No When you do not want to display “Cooling” and “Heating” in the
PAC-YT53CRAU
H2iYSD-12 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-4-2. Rule of setting addressUnit
Indoor unit
ME, LOSSNAYRemote controller(Main)
ME, LOSSNAYRemote controller(Sub)
Address setting
01 ~ 50
52 ~ 99, 100
101 ~ 150
151 ~ 199, 200
NoteExample
The address of outdoor unit + 1
Please reset one of them to an address between 51 and 99 when two addresses overlap.
The address automatically becomes "100" if it is set as "01~ 50"
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
ON/OFF remote controller 000, 201 ~ 250
Loca
l rem
ote
cont
rolle
rS
yste
m c
ontro
ller
The address of main remote controller + 50
The address automatically becomes "200" if it is set as "00"
10 1
10 1
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1
10 1
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1
0 1 2 3 4 5 6 7
8
90 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1100
LMAP04U-E 201 ~ 250
1
1
Fixed
Fixed
2Fixed
Outdoor unit
BC controller(Main)
52 ~ 99, 100Lowest address within the indoor units connected to the BC controller (Sub) plus 50.
10 1
BC controller(Sub)
51 ~ 99, 100
The smallest address of indoor unit in same refrigerant system + 50Assign sequential address numbers to the outdoor units in one refrigerant circuit system. OC and OS are automatically detected. (Note 2) Please reset one of them to an address between 51
and 99 when two addresses overlap. The address automatically becomes "100" if it is set
as "01~ 50"
Use the most recent address within the same group of indoor units. Make the indoor units address connected to the BC controller (Sub) larger than the indoor units address connected to the BC controller (Main).If applicable, set the sub BC controllers in an PURY system in the following order: (1) Indoor unit to be connected to the BC controller (Main) (2) Indoor unit to be connected to the BC controller (No.1 Sub) (3) Indoor unit to be connected to the BC controller (No.2 Sub)Set the address so that (1)<(2)<(3)
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
0 1 2 3 4 5 6 7
8
9 0 1 2 3 4 5 6 7
8
9
10 1(Note1)
The smallest group No. to be managed is changeable.
The smallest group No. to be managed + 200
Note1: To set the address to "100", set it to "50"Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected. OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
AG-150A-AGB-50ADA-AGB-24AEB-50GU-A
000, 201 ~ 25010 1100
0 0 0
BAC-HD150 000, 201 ~ 250
10 1100
Settings are made with setting tool of BM ADAPTER.0 0 0
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-13© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
DipSW2-1(Outdoor) : When the System Remote Controller is used, all the Dip SW2-1 at the outdoor units should be set to "ON". * Dip SW2-1 remains OFF when only LM-AP is used.DipSW1-2(LM-AP) : When the LM-AP is used together with System Remote Controller, DipSW1-2 at the LM-AP should be set to "ON".CN40/CN41 : Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission power supply to TB7; (Change jumper at only one outdoor unit when activating the transmission power supply without using a power supply unit.) Change jumper from CN41 to CN 40 at LM-AP will activate transmission power supply to LM-AP itself; Power supply unit is recommended to use for a system having more than 1 outdoor unit, because the central transmission power supply from TB7 of one of outdoor units is risking that the outdoor unit failure may let down the whole system controller system.
Setting at the site
2-4-3. System examples
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected. OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.2. No address setting is needed.3. For a system having more than 16 indoor unit, confirm the need of Booster at 2-3 "System configuration restrictions".
NOTE:
2-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller
Indoor unit
MA R/C MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*3
*3 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*3
*1
To *1 or *2
*2
00 00 00 00 00TB15TB5 TB5TB5 TB5 TB5TB15 TB15 TB15 TB15
Group 2Group 1 Group 3 Group 4
<Two outdoor units> <One outdoor unit>
TB3TB3
0000OC OS
PUHY-HP-TSJMU
TB3
00OC
CN41CN40CN41CN40 CN41CN40
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
PUHY-HP-TJMU
Factory settingOriginal switch setting of the outdoors, indoors, controllers, LM-AP, and BM ADAPTER at shipment is as follows.
Outdoor unit : Address: 00, CN41: ON (Jumper), DipSW2-1: OFF Indoor unit : Address: 00 ME remote controller : Address: 101 LM-AP : Address: 247, CN41: ON (Jumper), DipSW1-2: OFF BM ADAPTER : Address: 000, CN41: ON (Jumper)
H2iYSD-14 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2. Address should be set to Indoor units and central controller.3. For a system having more than 16 indoor unit, confirm the need of Booster at 2-3 "System configuration restrictions".
NOTE:1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected. OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
Indoor unit
MA R/C MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*3
*3 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.*SC can be connected to TB3 side or TB7 side; Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
*3
01 02 03 04 05TB15TB5 TB5TB5 TB5 TB5TB15 TB15 TB15 TB15
*1 *2
201
SC
To *1 or *2 Group 2Group 1 Group 3 Group 4
TB3TB3
5251OC OS
PUHY-HP-TSJMU
TB3
51OC
CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
PUHY-HP-TJMU<Two outdoor units> <One outdoor unit>
2-4-3-2. MA remote controller, Single-refrigerant-system, System Controller
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-15© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7 side, Booster for long M-NET wiring
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main" controller and others as "sub". TC-24A is for exclusive use as a "main" system controller and cannot be used as a "sub" system controller. Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
2. Address should be set to Indoor units, LOSSNAY and central controller.3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
NOTE:1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected. OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*1
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System. For AG-150A, 24V DC should be used with the PAC-SC51KUA.
*1
01 02 03 30TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
MA R/C(Main) (Sub)
MA R/C
TB15
Indoor unit
MA R/CSRU
Wireless R/C
*1
*1
41 45 46TB15TB5 TB5 TB5TB15
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
000 or 201
PSU
Power supply unit (PSU)
(PAC-SC51KUA)*2
SC*3
203
SC*3
Group 2Group 1 Group 21
Group 31 Group 34 Group 35
ME R/C LOSSNAYremote controller
142 143
42 43TB5
LOSSNAY
TB5
Group 33Group 32
TB3
TB7TB7 TB7 TB7 TB7
TB3
5251
OC OSPUHY-HP-TSJMU
TB3TB3
9291
OC OSPUHY-HP-TSJMU
TB3
97
OC
CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
PUHY-HP-TJMU
H2iYSD-16 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller
2-4-3-5. ME remote controller, Single-refrigerant-system, System controller, LOSSNAY
2. Address should be set to Indoor units, system controller and ME remote controllers.3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME R/C consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
NOTE:1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected. OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
2. Address should be set to Indoor units, LOSSNAY central controller, ME remote controllers.3. For a system having more than 16 indoor unit, confirm the need of Booster at 2-3 "System configuration restrictions".
NOTE:
ME R/C ME R/C
Indoor unit
ME R/C104 105 155
01 04 05TB5 TB5 TB5
ME R/C101
Group 1 Group 4 Group 5
201
SC
*SC can be connected to TB3 side or TB7 side; Should SC connected to TB7 side, change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC.
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected. OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
<Two outdoor units> <One outdoor unit>
Group 2 Group 3
ME R/C LOSSNAYremote controller
102 103
02 03TB5
LOSSNAY
TB5
Indoor unit
ME R/C ME R/C ME R/C
01 02 03 04 05TB5 TB5TB5
102
ME R/C
104 105 155
TB5 TB5
ME R/C
101
*1
To *1 or *2
*2
*1
To *1 or *2
*2
Group 2Group 1 Group 3 Group 4
TB3TB3
5251OC OS
PUHY-HP-TSJMU
TB3
51OC
CN41CN40CN41CN40 CN41CN40
OFFDipSW2-1
OFFDipSW2-1
OFFDipSW2-1
PUHY-HP-TJMU<Two outdoor units> <One outdoor unit>
TB3TB3
5251OC OS
PUHY-HP-TSJMU
TB3
51OC
CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
PUHY-HP-TJMU
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-17© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-NET wiring
2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
NOTE:1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected. OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order of their address.
Indoor unit
ME R/C
*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System. For AG-150A-A, 24V DC should be used with the PAC-SC51KUA.*2 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main" controller and others as "sub". TC-24A, AG-150A-A, GB-50ADA-A and GB-24A are for exclusive use as a "main" system controller and cannot be used as a "sub" system controller. Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB3
ME R/C ME R/C
Indoor unit
ME R/C144 145 195
130
*1
41 44 45TB5 TB5 TB5
ME R/C141
ME R/C101
ME R/C102
Group 2Group 1 Group 21
Group 31 Group 34 Group 35
ME R/CLOSSNAY
remote controller
142 143
42 43TB5
LOSSNAY
TB5
Group 32 Group 33
SC *2
202
203
SC *2
TB3
TB7TB7 TB7 TB7 TB7
TB3
201
PSU
Power supply unit (PSU)(PAC-SC51KUA)
5251
OC OSPUHY-HP-TSJMU
SC
TB3TB3
9291
OC OSPUHY-HP-TSJMU
TB3
96
OC
CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
PUHY-HP-TJMU
H2iYSD-18 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
NOTE It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems. It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.
NOTE It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrigerant systems. It is necessary to set on the remote controller by manual when group sets on the different refrigerant system. Please refer to remote controller installation manual.
2-4-3-7. ME remote controller, Multi-refrigerant-system, No Power supply unit
SC201
Group 1
Group 3Group 4
Group 2
ME R/C
01 02 03 04 05
101 105
0910 08 07 06
110 107ME R/C
ME R/C
ME R/C
TB7
TB3
56CN41CN40
OFFDipSW2-1
TB3
TB7TB7
TB3
5251CN41CN40CN41CN40
OFFDipSW2-1
OFFDipSW2-1
OC OCOSPUHY-HP-TSJMU PUHY-HP-TJMU
2-4-3-8. ME remote controller, Multi-refrigerant-system, System Controller at TB7 side, No Power supply unit
Group 1
Group 3Group 4
Group 2
ME R/C
01 02 03 04 05
101 105
0910 08 07 06
110 107ME R/C
ME R/C
ME R/C
TB7
TB3
56CN41CN40
ONDipSW2-1
TB3
TB7TB7
TB3
5251CN41CN40CN41CN40
ONDipSW2-1
ONDipSW2-1
OC OCOSPUHY-HP-TSJMU PUHY-HP-TJMU
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-19© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-4-3-8. LMAP
LMAP(01)
24VDC
(LONWORKS adapter)
PC
LONWORKS card
LONWORKS card
LONWORKS card For other equipments (Lighting, security, elevator etc.)
LMAP can transmit for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
DipSW1-2OFF
247
LONW
OR
KS
PSU
000
AG-150A
Power supply unit(PAC-SC51KUA)
identified by Neuron ID
LMAP(02)
DipSW1-2ON
247identified by Neuron ID
<Three outdoor units> <Two outdoor units> <One outdoor unit>
CN41CN40
CN41CN40
LMAP can transmit max. 50 indoor units;If system controller (SC) is used, DipSW1-2 at LMAP and DipSW5-1 at Outdoor unit should set to "ON".Change Jumper from CN41 to CN40 to activate power supply to LMAP itself for those LMAP connected without system controller (SC).
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*1
*1
01 02 03 42TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
Group 2Group 1 Group 40
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
5251
OC OS1
TB3
51
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
OFFDipSW5-1
OFFDipSW5-1
OFFDipSW5-1
OFFDipSW5-1
OFFDipSW5-1
OFFDipSW5-1
Indoor unit
ME R/C ME R/C ME R/C
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5
ME R/C
101 102 130 180
TB3
Group 2Group 1 Group 21
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
9291
OC OS1
TB3
96
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW5-1
ONDipSW5-1
ONDipSW5-1
ONDipSW5-1
ONDipSW5-1
ONDipSW5-1
ME R/C ME R/C
Indoor unit
ME R/C144 145 195
41 44 45TB5 TB5 TB5
Group 31 Group 34 Group 35
ME R/C
141
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.*2 When a PAR-30MAAU is connected to a group, no other MA remote controllers can be connected to the same group.
PUHY-P-TSKMU/YSKMU PUHY-P-TSKMU/YSKMU PUHY-P-TKMU/YKMU
PUHY-P-TSKMU/YSKMU PUHY-P-TSKMU/YSKMU PUHY-P-TKMU/YKMU
ME R/C PZ-52SF142 143
42 43TB5
LOSSNAY
TB5
Group 32 Group 33
H2iYSD-20 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
PUHY-P-TSJMU/YSJMU PUHY-P-TSJMU/YSJMU PUHY-P-TJMU/YJMU
PUHY-P-TSJMU/YSJMU PUHY-P-TSJMU/YSJMU PUHY-P-TJMU/YJMU
HUB
PC withTG-2000A
LAN
PSU
GB-50ADA-A
000
(PAC-SC51KUA)
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*1
*1
01 02 03 42TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
Group 2Group 1 Group 40
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
5251
OC OS1
TB3
51
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
Indoor unit
ME R/C ME R/C
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5
ME R/C
101 102 130
TB3
Group 2Group 1 Group 21
TB3 TB3
TB7TB7 TB7 TB7 TB7 TB7
TB3
535251
OC OS1 OS2
TB3TB3
9291
OC OS1
TB3
96
OC
CN41CN40CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ME R/C ME R/C
Indoor unit
ME R/C144 145 195
41 44 45TB5 TB5 TB5
Group 31 Group 34 Group 35
ME R/C
141
<Three outdoor units> <Two outdoor units> <One outdoor unit>
PSU
AG-150A-A
24VDC
000
(PAC-SC51KUA)
ME R/CLOSSNAY
remote controller142
143
42 43TB5
LOSSNAY
TB5
Group 32 Group 33
NOTE
2-4-3-9. TG-2000A(*1)+AG-150A-A*2,EB-50GU-AAG-150A-A can control max. 50 indoor units;GB-50ADA-A can control max. 50 indoor units; TG-2000A can control max. 40 of AG-150A-A and EB-50GU-ATG-2000A can control max. 2000 indoor units.
*1 TG-2000A (Ver.5.5 or later) supports AG-150A-A (Ver.1 series). TG-2000A (Ver. 6.4 or later) supports EB-50GU-A.*2 AG-150A-A (Ver.1 series) does not support the expansion controller (EC).
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-21© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-4-3-10. LM-AP
LM-AP(01)
24VDC
PC
LONWORKS® card
LONWORKS® card
LONWORKS® card For other equipments (Lighting, security, elevator etc.)
LM-AP can transmit for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
DipSW1-2OFF
247LO
NW
OR
KS®
PSU
000
AG-150A-A
Power supply unit(PAC-SC51KUA)
identified by Neuron ID
LM-AP(02)
DipSW1-2ON
247identified by Neuron ID
CN41CN40
CN41CN40
LM-AP can transmit max. 50 indoor units;If system controller (SC) is used, DipSW1-2 at LM-AP and DipSW2-1 at Outdoor unit should set to "ON".Change Jumper from CN41 to CN40 to activate power supply to LM-AP itself for those LM-AP connected without system controller (SC).
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*1
*1
01 02 03 42TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
Group 2Group 1 Group 40
TB7 TB7
TB3TB3
5251
OC OS
CN41CN40CN41CN40
OFFDipSW2-1
OFFDipSW2-1
Indoor unit
ME R/C ME R/C
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5
ME R/C
101 102 130
TB3
Group 2Group 1 Group 21
TB3
TB7TB7 TB7 TB7 TB7
TB3
5251
OC OS
TB3TB3
9291
OC OS
TB3
96
OC
CN41CN40CN41CN40 CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ME R/C ME R/C
Indoor unit
ME R/C144 145 195
41 44 45TB5 TB5 TB5
Group 31 Group 34 Group 35
ME R/C
141
PUHY-HP-TSJMU
PUHY-HP-TSJMU PUHY-HP-TSJMU PUHY-HP-TJMU
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
ME R/CLOSSNAY
remote controller142
143
42 43TB5
LOSSNAY
TB5
Group 32 Group 33
H2iYSD-22 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
2. M-NET CONTROL
2-4-3-11. BM ADAPTER
BM ADAPTER(01)
HUB
For other equipments (Lighting, security, elevator etc.)
BM ADAPTER can transmit for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
000
BA
Cne
t® BM ADAPTER(02)
000
CN41CN40
BM ADAPTER can transmit max. 50 indoor units;Change Jumper from CN41 to CN40 to activate power supply to BM ADAPTER itself for those BM ADAPTER connected without the power supply unit.
Indoor unit
MA R/C MA R/C(Main) (Sub)
MA R/CSRU
Wireless R/C
*1
*1
01 02 03 42TB15TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5TB15 TB15 TB3 TB15
Group 2Group 1 Group 40
Indoor unit
ME R/C ME R/C
01 02 03 30TB5 TB5TB5 TB2
Transmission BoosterPAC-SF46EPA
TB5
ME R/C
101 102 130
TB3
Group 2Group 1 Group 21
TB3
TB7 TB7 TB7
TB3
OC OS
5251
TB3
91
OC
CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
ME R/C ME R/C
Indoor unit
ME R/C ME R/CLOSSNAY
remote controller142
143144 145 195
41 42 43 44 45TB5 TB5
LOSSNAY
TB5 TB5 TB5
Group 32 Group 33Group 31 Group 34 Group 35
ME R/C
141
PUHY-HP-TSJMU PUHY-HP-TJMU
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
HUB
CN41CN40
TB3
TB7TB7 TB7
TB3
5251
OC OS
TB3
51
OC
CN41CN40CN41CN40 CN41CN40
ONDipSW2-1
ONDipSW2-1
ONDipSW2-1
PUHY-HP-TSJMU PUHY-HP-TJMU<Two outdoor units> <One outdoor unit>
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-23© 2014 Mitsubishi Electric US, Inc.
3-1. R410A Piping Material
3. PIPING DESIGN Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types. A. Type-O : Soft copper pipe (annealed copper pipe), can be easily bent with human's hand. B. Type-1/2H pipe : Hard copper pipe (Straight pipe), being stronger than Type-O pipe of the same radical thickness. The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety under the maximum operation pressure. MITSUBISHI ELECTRIC recommends pipe size as Table 3-1, or You shall follow the local industrial standard. Pipes of radical thickness 0.7mm or less shall not be used.
* The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the local standards.
Size (mm) Size (inch) Radial thickness (mm) Pipe typeø6.35 ø1/4" 0.8 ACR-Annealed or ACR-Drawn Temperø9.52 ø3/8" 0.8 ACR-Annealed or ACR-Drawn Temperø12.7 ø1/2" 0.8 ACR-Annealed or ACR-Drawn Temper
ø15.88 ø5/8" 1.0 ACR-Annealed or ACR-Drawn Temperø19.05 ø3/4" 1.2 ACR-Annealed or ACR-Drawn Temperø22.2 ø7/8" 1.0 ACR-Drawn Temperø25.4 ø1" 1.0 ACR-Drawn Temper
ø28.58 ø1-1/8" 1.0 ACR-Drawn Temperø31.75 ø1-1/4" 1.1 ACR-Drawn Temperø34.93 ø1-3/8" 1.2 ACR-Drawn Temperø41.28 ø1-5/8" 1.4
Radial thickness (mil)[32][32][32][40][48][40][40][40][44][48][56] ACR-Drawn Temper
Table 3-1. Copper pipe size and radial thickness for R410A CITY MULTI.
Flare
Due to the relative higher operation pressure of R410A compared to R22, the flare connection should follow dimensions mentioned below so as to achieve enough the air-tightness.
Flare pipe Pipe size A (For R410A) Flare nut Pipe size (mm[in.]) (mm[in.]) B (For R410A)
ø6.35 [1/4"]ø9.52 [3/8"]
ø12.70 [1/2"]ø15.88 [5/8"]ø19.05 [3/4"] 24.0 [1"]
16.6 [11/16"]19.7 [13/16"]
9.1 [3/8"]13.2 [9/16"]
ø6.35 [1/4"]ø9.52 [3/8"]
ø12.70 [1/2"]ø15.88 [5/8"]ø19.05 [3/4"] 36.0 [1-7/16"]
17.0 [3/4"]22.0 [7/8"]26.0 [1-1/16"]29.0 [1-1/8"]
A
B
H2iYSD-24 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
3. PIPING DESIGN
3-2. Piping Design
Table3-2-1-6. R410A Joint selection rule Total down-stream Indoor capacity Joint ~ P72 CMY-Y102SS-G2 P73 ~ P144 CMY-Y102LS-G2 P145 ~ P234 CMY-Y202S-G2 P235 ~ CMY-Y302S-G2*Concerning detailed usage of Joint parts, refer to its Installation Manual.
Table3-2-1-7. R410A Header selection rule 4-branch Header 8-branch Header 10-branch Header CMY-Y104C-G CMY-Y108C-G CMY-Y1010C-G Total down-stream Indoor capacity <=P72 <=P144 <=P234* CMY-Y104C-G can directly connect PUHY-HP72TJMU, but can NOT directly connect PUHY-HP96TJMU or above; * CMY-Y108C-G can directly connect PUHY-HP72-144T(S)JMU, but can NOT directly connect PUHY-HP192TSJMU* CMY-Y1010C-G can directly connect PUHY-HP72-192T(S)JMU;* CMY-Y104C-G can NOT connect P72, P96 Indoor, but CMY-Y108, Y1010C-G can do;* Concerning detailed usage of Header parts, refer to its Installation Manual.
H
h
H'
The first joint
Joint
b ca
L2L1
IU
IU IUIU
d
IU
IU
f
IU
e
C
D
A
OU
BHeader
Note1. No Joint after Header; Piping direct to Indoor Unit from Header;Note2. If the A/C system is designed to use Cooling-mode under Outside temperature 10°C [50°F], H'<=40m [131ft.];Note3. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better; Piping length needs to consider the actual length and equivalent length which bents are counted. Equivalent piping length = Actual piping length + "M" x Quantity of bent.
IU : Indoor unit , OU : Outdoor unit
g
Fig. 3-2-1A Piping scheme
3-2-1. PUHY-HP-72, 96TJMU Piping
Table3-2-1-1. Piping length (m [ft.]) Item Piping in the figure Max. length Max. equivalent length Total piping length A+B+C+D+a+b+c+d+e+f+g 300 [984'] - Farthest IU from OU (L1) A+C+D+g / A+B+d 150 [492'] 175 [574'] Farthest IU from first Joint (L2) C+D+g / B+d 40 [131'] 40 [131'] Height between OU and IU (OU above IU) H 50 [164'] - Height between OU and IU (OU under IU) H' 40 [131'] - Height between IU and IU h 15 [49'] -OU: Outdoor Unit, IU: Indoor Unit
Table3-2-1-3. Piping "A" size selection rule (mm [in.]) Outdoor and the first Joint Pipe(Liquid) Pipe(Gas) PUHY-HP72TJMU=CMY-Y102SS-G2 ø12.70 [1/2"] ø19.05 [3/4"] PUHY-HP96TJMU=CMY-Y102LS-G2 ø12.70 [1/2"] ø22.20 [7/8"]
Table3-2-1-4. Piping "B","C","D"size selection rule (mm [in.]) Total down-stream Indoor capacity Pipe(Liquid) Pipe(Gas) ~ P54 ø9.52 [3/8"] ø15.88 [5/8"] P55 ~ P72 ø9.52 [3/8"] ø19.05 [3/4"] P73 ~ P108 ø9.52 [3/8"] ø22.20 [7/8"] P109 ~ P144 ø12.70 [1/2"] ø28.58 [1-1/8"] P145 ~ P234 ø15.88 [5/8"] ø28.58 [1-1/8"]
Table3-2-1-5. Piping "a","b","c","d","e","f","g"size selection rule (mm [in.]) Indoor Unit size Pipe(Liquid) Pipe(Gas) P06,P08,P12,P15,P18 ø6.35 [1/4"] ø12.70 [1/2"] P24,P27,P30,P36,P48,P54 ø9.52 [3/8"] ø15.88 [5/8"] P72 ø9.52 [3/8"] ø19.05 [3/4"] P96 ø9.52 [3/8"] ø22.20 [7/8"]
Table3-2-1-2. Bent equivalent length "M" Outdoor Model M (m/bends [ft./bends]) PUHY-HP72TJMU 0.30 [0.99] PUHY-HP96TJMU 0.35 [1.15]
Note4. Indoor capacity is described as its model size; For example, PEFY-P08NMAU-E, its capacity is P06;Note5. Total down-stream Indoor capacity is the summary of the model size of Indoors downstream. For example, PEFY-P06NMAU-E+PEFY-P08NMAU-E: Total Indoor capacity=P06+P08=P14Note6. Piping sized determined by the Total down-stream indoor capacity is NOT necessary to be bigger than the up-stream one. i.e. A>=B; A>=C>=D
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-25© 2014 Mitsubishi Electric US, Inc.
3. PIPING DESIGN
Table3-2-2-4. R410A Joint selection rule Total down-stream Indoor capacity Joint ~ P72 CMY-Y102SS-G2 P73 ~ P144 CMY-Y102LS-G2 P145 ~ P234 CMY-Y202S-G2*First Joint is always CMY-Y202S-G2;*Concerning detailed usage of Joint parts, refer to its Installation Manual.
Outdoor Twinning KitCMY-Y100CBK2
Note1. No Joint after Header; Piping direct to Indoor Unit from Header;Note2. If the A/C system is designed to use cooling-mode under outside temperature 10°C [50°F], H’<=40m [131ft].Note3. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better;
Piping length needs to consider the actual length and equivalent length which bents are counted.Equivalent piping length=Actual piping length+"M" x Quantity of bent.
H (O
U a
bove
IU)
h1
H' (
OU
und
er IU
)
h2
1st Joint
Joint
ba
L2L1
IU
IU IUIU
g
IU
e
IU
d
C
D
IU
f
E
TS
A BHeader
Capped
IU : Indoor unit , OU : Outdoor unitFig. 3-2-1B Piping scheme
c
2m [6.56ft] To indoor unitTo indoor unitTo indoor unit To indoor unit 2m [6.56ft] max
Trap (gas pipe only)
Upward incline
Downward incline
Install the pipes from the outdoor unit to the branch joint with a downward incline.
If the length of pipe between the branch joint and outdoor unit exceeds 2m [6.56ft], provide at rap at a distance 2m [6.56ft] or less from the branch joint.
OK NO
3-2-2. PUHY-HP144-192TSJMU Piping
Table3-2-2-1. Piping length (m [ft.]) Item Piping in the figure Max. length Max. equivalent length Total piping length S+T+A+B+C+D+E+a+b+c+d+e+f+g 300 [984'] - Distance between OU and OU S+T 10[32'] - Height between OU and OU h2 0.1[0.3'] - Farthest IU from OU (L1) S(T)+A+C+D+E+g / S(T)+A+B+c 150 [492'] 175 [574'] Farthest IU from the first Joint (L2) C+D+E+g / B+c 40 [131'] 40 [131'] Height between OU and IU (OU above IU) H 50 [164'] - Height between OU and IU (OU under IU) H' 40 [131'] - Height between IU and IU h1 15 [49'] -OU: Outdoor Unit, IU: Indoor Unit
Table3-2-2-3. Piping "A" size selection rule (mm [in.]) Outdoor and the first Joint Pipe(Liquid) Pipe(Gas) CMY-Y100CBK2=CMY-Y202S-G2 ø15.88[5/8"] ø28.58[1-1/8"]For Piping size "S","T", please refer to specification of the Twining kit CMY-Y100CBK2 at the Outdoor unit's external drawing.
Table3-2-2-2. Bent equivalent length "M" Outdoor Model M (m/bends [ft./bends]) PUHY-HP144TSJMU 0.50 [1.64] PUHY-HP192TSJMU 0.50 [1.64]
OUOU
H2iYSD-26 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
3. PIPING DESIGN
3-3. Refrigerant Charge Calculation
(1) Calculation of additional refrigerant charge Calculate the amount of additional charge based on the length of the piping extension and the size of the refrigerant
line. Use the table to the below as a guide to calculating the amount of additional charging and charge the system
accordingly. If the calculation results in a fraction of less than 0.1kg, round up to the next 0.1kg. For example, if the result of the
12.38kg, round the result up to 12.4kg.
At the time of shipping, the outdoor unit is charged with the refrigerant. As this charge does not include the amount needed for extended piping, additional charging for each refrigerant line will be required on site. In order that future servicing may be properly provided, always keep a record of the size and length of each refrigerant line and the amount of additional charge by writing it in the space provided on the outdoor unit.
A
B C D e
a b c d
Indoor 1: P48 A: 40 m a: 10 m2: P36 B: 10 m b: 5 m3: P15 15 m c: 10 m4: P12 10 m d: 10 m5: P24 e: 10 m
The total length of liquid pipe of each size is as follows:
Total capacity of connecting Indoor units Pt :Pt = P48 + P36 + P15 + P12 + P24 = P135, therefore = 3.5kg
12.7 : A = 40 = 40 m9.52 : B + C + D + a + b + e = 10 + 15 + 10 + 10 + 5 + 10 = 60 m6.35 : c + d = 10 + 10 = 20 m
Example: PUHY-HP96TJMU
P15P36P48 P12 P24
<Additional Charge>
= + + + + + (kg)
(oz) (m) (ft.) x 3.1 [oz/ft.] (ft.) x 2.15 [oz/ft.] (ft.) x 1.29 [oz/ft.] (ft.) x 0.65 [oz/ft.] (ft.) x 0.26 [oz/ft.]
x 0.29 (kg/m)
Additional refrigerant charge
Total length of liquid
(m) x 0.20 (kg/m)
Total length of liquid
(m) x 0.12 (kg/m)
Total length of liquid
(m) x 0.06 (kg/m)
Total length of liquid
(m) x 0.024 (kg/m)
Total length of liquid
= + + + + + 124
+ + + + + 124
(oz) 0 (ft.) x 3.1 (oz/ft.)
Additional refrigerant charge
= 0 0 131 x 1.29 193 x 0.65 64 x 0.26= 436 [oz]
Total length of liquid
x 3.1 (oz/ft.)
0 (ft.) x 2.15 (oz/ft.)
Total length of liquid
x 2.15 (oz/ft.)
131 (ft.) x 1.29 (oz/ft.)
Total length of liquid
x 1.29 (oz/ft.)
193 (ft.) x 0.65 (oz/ft.)
Total length of liquid
x 0.65 (oz/ft.)
64 (ft.) x 0.26 (oz/ft.)
Total length of liquid
x 0.26 (oz/ft.)
= + + + + + 3.5
+ + + + + 3.5
(kg) 0 (m) x 0.29 (kg/m)
Additional refrigerant charge
= 0 0 40 x 0.12 60 x 0.06 20 x 0.024= 12.4 kg
Total length of liquid
x 0.29 (kg/m)
0 (m) x 0.20 (kg/m)
Total length of liquid
x 0.20 (kg/m)
40 (m) x 0.12 (kg/m)
Total length of liquid
x 0.12 (kg/m)
60 (m) x 0.06 (kg/m)
Total length of liquid
x 0.06 (kg/m)
20 (m) x 0.024 (kg/m)
Total length of liquid
x 0.024 (kg/m)
Table3-2-3-1. Value of Total capacity of connecting indoor units
2.0 kg [71 oz]
m [kg]
m [kg]
ft. [oz]
ft. [oz]or
Models 272.5 kg [89 oz]3.0 kg [106 oz]3.5 kg [124 oz]4.5 kg [159 oz]
6.0 kg [212 oz]5.0 kg [177 oz]
Indoor 1: P48 A: 131ft. 32ft.2: P36 B: 32ft. b: 16ft.3: P15 C: 49ft. c: 32ft.4: P12 D: 32ft. d: 32ft.5: P24 e: 32ft.
The total length of liquid pipe of each line is as follows:
Total capacity of connecting Indoor units Pt :Pt = P48 + P36 + P15 + P12 + P24 = P135, therefore = 124oz
A = 131 = 131ft.+ a + b + e = 32 + 49 + 32 + 32 + 16 + 32 = 193ft.
If the calculation results in a fraction of less than 1oz, round up to the next 1oz. For example, if the result of the calculation was 435.1oz, round the result up to 436oz.
Models 28 54Models 55 126Models 127 144Models 145 180Models 181 234Models 235
calculation was
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-27© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
1. No direct thermal radiation to the unit.2. No possibility of annoying the neighbors by the sound of the unit. Valves and refrigerant flow on the outdoor unit may generate noise. 3. Avoid the sites where strong winds blow.4. With strength to bear the weight of the unit.5. Drain flow from the unit is cared at heating mode.6. Enough space for installation and service as shown at 4-2.7. Avoid the sites where acidic solutions or chemical sprays (sulfur series) are used frequently.8. The unit should be secure from combustible gas, oil, steam, chemical gas like acidic solution, sulfur gas and so on.
4-1. Installation Site Requirements
H2iYSD-28 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
1000[39-3/8]
240 [9-15/32]
45°
50 [1-31/32]<C>
(Unit : mm [in.])
<B>
500
[19-11
/16]
H
h
h
H
100*[3-15/16]
450*[17-23/32]
50* [1-31/32] 50* [1-31/32]
<A>
(1) If the distance is 300 mm [11-13/16 in.] or more between the rear side and the wall
15* [19/32] 15* [19/32]
450*[17-23/32]
300*[11-13/16]
<A>(2) If the distance is 100 mm [3-15/16 in.] or more between the rear side and the wall
• Secure enough space around the unit as shown in the figure.In case of single installation
(3) If the wall height (H) of the front, rear or side exceeds the wall height restriction
(4) If there are obstacles at the upper part of the unit
<A> : Top view<B> : Side view<C> : When there is little space up to an obstruction
::
• When the height of the walls on the front, back or on the sides <H> exceeds the wall height limit as defined below, add the height that exceeds the height limit <h> to the figures that are marked with an asterisk.
<Wall height limit> Front: Up to the unit height Back: Up to 500mm [19-11/16 in.] from the unit bottom Side: Up to the unit height
A
BCD : Air outlet guide (Procured at the site)
: FrontUnit height
Back
A
A
AB
CA
D
If the unit cannot be kept clear of the wall, please change the direction of the air outlet of the unit to blow against the wall to avoid air short cycle.
4-2. Installation Clearance Space
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-29© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
In case of collective installation and continuous installation
:: Wall height (H)
(Unit : mm [in.])
A
BC
30
450*
300*
100 450*
100*
450* 100*450 450
15*
450 450
900
300*
300*
1000*
900
300*
• When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and passageways between groups of units as shown in the figures.
• At least two sides must be left open.• As with the single installation, add the height that exceeds the height limit <h> to the figures that are marked with
• If there is a wall at both the front and the rear of the unit, install up to six units consecutively in the side direction and provide a space of 1000mm [33-3/8] or more as inlet space/passage space for each six units.
an asterisk.
: FrontMust be open
[17-23/32] [17-23/32]
[17-23/32] [17-23/32] [17-23/32] [3-15/16]
[39-3/8]
[17-2
3/32]
[17
-23/3
2]
[11-1
3/16]
[11-1
3/16]
[11
-13/1
6]
[11-1
3/16]
[35
-7/16
] [35
-7/16
]
[3-1
5/16
]
[3-15/16]
[1-3/16]
AA
A
AAA
AAA
AB B
B B
B
B
B B
B
B
C
C
C
C
CC
C
C
C
C
H2iYSD-30 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
4-3. Piping Direction
4-3-1. Lifting method
· When lifting the unit with ropes, run the ropes under the unit and use the lifting hole.· Support the unit at four points with two ropes, and avoid giving mechanical shock.· Suspension rope angle must be 40° or less, so as to avoid compressing fan guard.· Use two ropes, each at least 8m [26 ft.] in length· Use ropes strong enough to support the weight of the unit.· Always suspend the unit from four corners. (It is dangerous to suspend a unit from two corners and must not be attempt-
ed.)· Use protective pads to keep the ropes from scratching the panels on the unit.
8 [26]
8 [26]
40°
· Products weighing more than 20 kg [45 LBS] should not be carried alone.· Do not carry the product by the PP bands.· To avoid the risk of injury, do not touch the heat exchanger fins. · Plastic bags may pose a risk of choking hazard to children. Tear plastic bags into pieces before disposing of them.· When lifting and transporting outdoor units with ropes, run the ropes through lifting hole at the unit base. Securely
fix the unit so that the ropes will not slide off, and always lift the unit at four points to prevent the unit from falling.
Exercise caution when transporting products.CAUTION
8 [26]40°
8 [26]
1 HP72 HP962
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-31© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
4-3-2. Installation
30m
m [1
-3/1
6in]
Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure is securely supported. The brackets may bend if they are not securely supported. Fixing bracket for post-
installation-type anchor bolts.
4-3-3. Anchor bolt positions
· Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind or dur-ing an earthquake.
· Install the unit on a durable base made of such materials as concrete or angle steel.· Take appropriate anti-vibration measures (e.g., vibration damper pad, vibration isolation base) to keep vibrations and
noise from being transmitted from the unit through walls and floors.· Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is
securely supported.· Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm [1-3/16in].· This unit is not designed to be anchored with post-installation-type anchor bolts, although by adding fixing brackets
anchoring with such type of anchor bolts becomes possible.
Take into consideration the durability of the base, water drainage route (Drain water is discharged from outdoor unitsduring operation.), piping route, and wiring route when performing foundation work.
Properly install the unit on a surface that can withstand the weight ofthe unit. Unit installed on an unstable surface may fall and cause injury.
WARNING
Take appropriate safety measures against strong winds and earth-quakes to prevent the unit from falling.
WARNING
<HP72, 96>• Individual installation • Collective installation
A A A A
724±
3 [(2
8-13
/32~
28-5
/8)]
724±
3 [(2
8-13
/32~
28-5
/8)]
(For maintenance)
30 [1-3/16]190 [7-1/2]
30 [1-3/16]190 [7-1/2]
Leave a minimum of 30 mm [1-3/16 in.] between units.
760±2 [29-15/16(29-27/32~30)]A
HP72
1060±2 [41-3/4(41-21/32~41-13/16)]
HP96PUHY
(Unit : mm [in.])
H2iYSD-32 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
4-3-5. Refrigerant pipe routing
4-3-4. Installation
Installation base perpendicular to the unit’s front panelInstallation base parallel to the unit’s front panel
When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base ofthe unit does not get blocked with the installation base.When the pipes are routed at the bottom of the unit, the base should be at least 100 mm [3-15/16 in] in height.
The gaps around the edges of through holes for pipes and wires on theunit allow water or mice to enter the unit and damage its parts. Closethese gaps with filler plates.
This unit allows two types of pipe routing:• Bottom piping• Front piping
To prevent small animals, water and snow fromentering the unit and damage its parts, close thegap around the edges of through holes for pipesand wires with filler plates.
CAUTION
Example of closure materials (field-supplied)Fill the gap at the site
· HP72
Bottom view
· HP96(Unit : mm [in.]) (Unit : mm [in.])
Refrigerant servicevalve <liquid>
(Mou
nting
pitc
h)
(Mounting pitch)
Refrigerant service valve <gas>
(5-2
9/32
)15
0
1818
(28-
17/3
2)
(5-2
3/32
)
(3-5
/8)
(3-1
3/32
)
(3-9/32)(5-29/32)
(7-11/32)
(8-23/32)(9-29/32)
(5-3
/16)
(3-5/32)(29-15/16)
(3-5/32) (23/
32)
(28-
13/3
2~28
-5/8
)
(29-
15/1
6)
(23/
32)
2X2-14(9/16)X20(13/16) Oval hole221 150
145
83
(760
)
80 760 80
724(
721~
727)92
86
131
251186
Refrigerant service valve <gas>
Refrigerant service valve <liquid> (M
ount
ing p
itch)
(Mounting pitch)
301 83
(5-2
9/32
)15
0
760
1872
4(72
1~72
7)
(29-
15/1
6)
(28-
13/3
2~28
-5/8
)
(28-
17/3
2)
(23/
32)
2X2-14(9/16)X20(13/16) Oval hole
(3-2
3/32
)(3
-5/1
6)(5
-23/
32)
(3-9/32)(5-29/32)
(5-3
/16) (11-7/8)
(10-11/16)
(8-17/32)
(41-3/4)(3-5/32) (3-5/32) (2
3/32
)
150271
948414
5216
18
8080 1060
131
Bottom view
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-33© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
4-3-6. Twinning on the outdoor unit side
Reducer
±15°
The tilt angle of the reducer should be within ±15° with the horizontal plane.
Note: See the following drawing for the fitting position of the twinning pipe.
The tilt angle of the twinning pipeThe tilt angle of the twinning pipe must be within ±15° with the horizontal plane. Tilting the twinning pipe more than specified will cause damage to the unit.
The length of the straight part of the pipe before the branchingFor the twinning kit, always use the accessory piping parts. The length of the straight part of pipe connected in front of the twinning pipe must be 500 mm (19 in) or longer. (Connect the field piping so that the length of the straight part of pipe connected in front of the twinning pipe can be 500 mm (19 in) or longer.) If the length is less than 500 mm (19 in), it will cause damage to the unit.
To Indoor unit
Less than 2 m (6 ft)
To Indoor unit2m (6 ft)
200 mm (7 in) or over
Trap (gas pipe only)
The piping connectionWhen connecting the twinning kit to the outdoor unit, note the following:If the length of piping from the twinning kit to the outdoor unit is more than 2 m (6 ft), install a trap within 2 m (6 ft) from the outdoor unit. The height of the trap must be 200 mm (7 in) or higher.
When installing the twinning kit in a higher position than the outdoor unit base, make sure that the twinning kit is installed in a position lower than 200 mm (7 in) from the outdoor unit base.
<2 m (6 ft) or less>
<PUHY-HP144TSJMU-A>
<PUHY-HP192TSJMU-A>
<More than 2 m (6 ft)>
Outdoor unit 1 Outdoor unit 2
200 mm (7 in) or less
Twinning pipe1
To Indoor unit
To indoor unitTwinning pipe 1
200mm [7 in.]or less
Outdoor unit 1 Outdoor unit 2
H2iYSD-34 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
Field piping
Field piping
Twinning kit
The length of the straight pipe
must be 500 mm [19 in.] or longer
See the following drawing for connecting the pipes between the outdoor units.
<PUHY-HP144 TSJMU-A>
<PUHY-HP192TSJMU-A>
4-3-7. Twinning on the outdoor unit side
The length of the straight pipe must be 500mm[19in.] or longer.If not, it may cause improper operation.
CAUTION
Field pipingTwinning kit
The length of the straight pipe
must be 500 mm [19 in.] or longer
Field piping
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-35© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
4-4. Weather Countermeasures• Snow hood
Countermeasure to wind
Outlet Inlet
Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installation.
Note:1.Height of frame base for snow damage prevention (H) shall be twice as high as expected snowfall. Width of frame base shall
not exceed that of the unit. The frame base shall be made of angle steel, etc., and designed so that snow and wind slip through the structure. (If frame base is too wide, snow will be accumulated on it.)
2.Install unit so that wind will not directly lash against openings of inlet and outlet ducts.3.Build frame base at customer referring to this figure. Material: Galvanized steel plate 1.2T [1/16 in T] Painting: Overall painting with polyester powder Color: Munsell 5Y8/1 (same as that of unit)4.When the unit is used in a cold region and the heating operation is continuously performed for a long time when the outside air
temperature is below freezing, install a heater to the unit base or take other appropriate measures to prevent water from freezing on the base.
5.Do not use a snow hood made of stainless steel, which may cause the unit to rust. If the use of a stainless snow hood is the only option, contact the sales office before installing it.
Wind
Install the outdoor unit where seasonal winds do not blow directly against the unit, such as behind a building.
Install the outdoor unit to avoid having seasonal winds against the front of air outlet/inlet on the unit.
Unit : mm[in]
<Side view><Front view> <Front view>
750 [29-17/32]
453[17-27/32]760 [29-15/16]
(760)[29-15/16]
1210 [47-21/32]
H13
24 [5
2-5/
32]
1324
[52-
5/32
]
(1220)[48-1/16]
1206 [47-1/2]906 [35-11/16]
453[17-27/32]
453[17-27/32]
453[17-27/32]
453[17-27/32]910 [35-27/32]
H86
[3-1
3/32
]
86[3
-13/
32]
800
[31-
1/2]
800
[31-
1/2]
(920)[36-1/4]
A
B
B
B
B
B
H2iYSD-36 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
4-5. Low Ambient Kit Application GuidelinesGeneral Unit Placement and Clearances• Outdoor units should be located in an area protected from prevailing winds.• In high wind locations, it may be advisable to install the outdoor units within a walled area.• Hood discharge should be directed away from or perpendicular to the prevailing winds. Do not direct the hood discharge towards prevailing winds. • When using the low ambient components, add an additional 7” to the standard mounting clearances.
Equipment SupportsWhen modules are combined, they should be placed a minimum of 1-3/16” apart. By doing so, only one set of side wind deflectors (SWD-1) are required per group of modules.
The equipment support must be firmly attached to the ground or structure. The outdoor unit must be properly attached to the equipment support with 3/8” stainless steel or equal strength to at least a grade 5 bolt.
Note: If the outdoor unit is located in an area with continuous high winds, additional braced may be required. Contact your distributor for assistance.
Top View Prevailing
Wind
Outdoor Units Building Wall
12"
1-3/16"
Note: Equipment supports must elevate the unit at least 12” above the average expected snow depth or 12” above the ground, whichever is higher. The equipment supports must be an open construction to minimize snow drifting and/or ice formation during defrost.
OK
If the units are surrounded by an enclosure, the hood must be positioned that the air is directed out and over the walls to prevent air recirculation.
Minimum 3/8” stainless steel or
harder bolts
Concrete Pad
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-37© 2014 Mitsubishi Electric US, Inc.
4. OUTDOOR INSTALLATION
Safety strap Provided by others
Important! For all roof top
installations, safety straps must be
attached between the hood(s) and the unit mounting structure.
Additional Rooftop Mounting GuidelinesGround-level installation is preferred for outdoor units that include a low ambient kit. If ground-level installation is not possible, follow general, as well all additional installation guidelines for rooftop mounting. If you have any questions, please contact your distributor.
Note:Low ambient hood(s) increase the overall height of the outdoor units and make them more susceptible to wind stresses. Follow all guidelines when using these for rooftop applications.
• Straps must be attached to the hood where they will not interfere with the movement of the dampers.
Note:For all rooftop installation, safety straps must be attached between the hood(s) and the equipment support structure. Straps should be 3/16” (or larger) vinyl-coated cables.
• Straps must be connected to both the hood and mounting structure through using ¼” diameter (or larger) bolt.
• The outdoor unit and equipment support should be firmly attached to the structure. If the equipment support does not at-tach to the structure, refer to the support manufacturer’s guidelines for proper size and construction.
Depending on location, exposure and other factors influencing wind access or blockage, additional support may be required such as shown at right. Contact your distributor for assistance.
H2iYSD-38 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
5. INSTALLATION INFORMATION
4 - 77
5. Installation information DATA U8
SYSTEM DESIGN
System Y
5. Installation information5-1. General precautions5-1-1. Usage
�The air-conditioning system described in this Data Book is designed for human comfort.�This product is not designed for preservation of food, animals, plants, precision equipment, or art objects. To prevent quality loss, do not use the product for purposes other than what it is designed for.�To reduce the risk of water leakage and electric shock, do not use the product for air-conditioning vehicles or vessels.
5-1-2. Installation environment�Do not install any unit other than the dedicated unit in a place where the voltage changes a lot, large amounts of mineral oil (e.g., cutting oil) are present, cooking oil may splash, or a large quantity of steam can be generated such as a kitchen.�Do not install the unit in acidic or alkaline environment.�Installation should not be performed in the locations exposed to chlorine or other corrosive gases. Avoid near a sewer.�To reduce the risk of fire, do not install the unit in a place where flammable gas may be leaked or inflammable material is present.�This air conditioning unit has a built-in microcomputer. Take the noise effects into consideration when deciding the in-stallation position. Especially in a place where antenna or electronic device are installed, it is recommended that the air conditioning unit be installed away from them.�Install the unit on a solid foundation according to the local safety measures against typhoons, wind gusts, and earth-quakes to prevent the unit from being damaged, toppling over, and falling.
5-1-3. Backup system�In a place where air conditioner's malfunctions may exert crucial influence, it is recommended to have two or more sys-tems of single outdoor units with multiple indoor units.
5-1-4. Unit characteristics�Heat pump efficiency depends on outdoor temperature. In the heating mode, performance drops as the outside air tem-perature drops. In cold climates, performance can be poor. Warm air would continue to be trapped near the ceiling and the floor level would continue to stay cold. In this case, heat pumps require a supplemental heating system or air circu-lator. Before purchasing them, consult your local distributor for selecting the unit and system.�When the outdoor temperature is low and the humidity is high, the heat exchanger on the outdoor unit side tends to collect frost, which reduces its heating performance. To remove the frost, Auto-defrost function will be activated and the heating mode will temporarily stop for 3-10 minutes. Heating mode will automatically resume upon completion of defrost process.�Air conditioner with a heat pump requires time to warm up the whole room after the heating operation begins, because the system circulates warm air in order to warm up the whole room.�The sound levels were obtained in an anechoic room. The sound levels during actual operation are usually higher than the simulated values due to ambient noise and echoes. Refer to the section on "SOUND LEVELS" for the measurement location.�The total capacity of the connected indoor units can be greater than the capacity of the outdoor unit. However, when the connected indoor units operate simultaneously, each unit's capacity may become smaller than the rated capacity. �When the unit is started up for the first time within 12 hours after power on or after power failure, it performs initial startup operation (capacity control operation) to prevent damage to the compressor. The initial startup operation requires 90 minutes maximum to complete, depending on the operation load.
5-1-5. Relevant equipment�Use an earth leakage breaker (ELB) with medium sensitivity, and an activation speed of 0.1 second or less.�Consult your local distributor or a qualified technician when installing an earth leakage breaker.�If the unit is inverter type, select an earth leakage breaker for handling high harmonic waves and surges.�Leakage current is generated not only through the air conditioning unit but also through the power wires. Therefore, the leakage current of the main power supply is greater than the total leakage current of each unit. Take into consideration the capacity of the earth leakage breaker or leakage alarm when installing one at the main power supply. To measure the leakage current simply on site, use a measurement tool equipped with a filter, and clamp all the four power wires together. The leakage current measured on the ground wire may not accurate because the leakage current from other systems may be included to the measurement value.�Do not install a phase advancing capacitor on the unit connected to the same power system with an inverter type unit and its equipment.�If a large current flows due to the product malfunctions or faulty wiring, both the earth leakage breaker on the product side and the upstream overcurrent breaker may trip almost at the same time. Separate the power system or coordinate all the breakers depending on the system's priority level.
5-1. General precautions
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-39© 2014 Mitsubishi Electric US, Inc.
5. INSTALLATION INFORMATION5. Installation information DATA U8
SYSTEM DESIGN 4 - 78
Syst
em Y
5-1-6. Unit installation�Your local distributor or a qualified technician must read the Installation Manual that is provided with each unit carefully before performing installation work.�Consult your local distributor or a qualified technician when installing the unit. Improper installation by an unqualified person may result in water leakage, electric shock, or fire.�Ensure there is enough space around each unit.
5-1-7. Optional accessories �Only use accessories recommended by Mitsubishi Electric. Consult your local distributor or a qualified technician when installing them. Improper installation by an unqualified person may result in water leakage, electric leakage, system breakdown, or fire.�Some optional accessories may not be compatible with the air conditioning unit to be used or may not suitable for the installation conditions. Check the compatibility when considering any accessories.�Note that some optional accessories may affect the air conditioner's external form, appearance, weight, operating sound, and other characteristics.
5-1-8. Operation/Maintenance�Read the Instruction Book that is provided with each unit carefully prior to use.�Maintenance or cleaning of each unit may be risky and require expertise. Read the Instruction Book to ensure safety. Consult your local distributor or a qualified technician when special expertise is required such as when the indoor unit needs to be cleaned.
5-2. Precautions for Indoor unit5-2-1. Operating environment
�The refrigerant (R410A) used for air conditioner is non-toxic and nonflammable. However, if the refrigerant leaks, the oxygen level may drop to harmful levels. If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.�If the units operate in the cooling mode at the humidity above 80%, condensation may collect and drip from the indoor units.
5-2-2. Unit characteristics�The return air temperature display on the remote controller may differ from the ones on the other thermometers.�The clock on the remote controller may be displayed with a time lag of approximately one minute every month.�The temperature using a built-in temperature sensor on the remote controller may differ from the actual room tempera-ture due to the effect of the wall temperature.�Use a built-in thermostat on the remote controller or a separately-sold thermostat when indoor units installed on or in the ceiling operate the automatic cooling/heating switchover.�The room temperature may rise drastically due to Thermo OFF in the places where the air conditioning load is large such as computer rooms.�Be sure to use a regular filter. If an irregular filter is installed, the unit may not operate properly, and the operation noise may increase.�The room temperature may rise over the preset temperature in the environment where the heating air conditioning load is small.
5-2-3. Unit installation�For simultaneous cooling/heating operation type air conditioners (R2, WR2 series), the G-type BC controller cannot be connected to the P144 outdoor unit model or above, and the G- and GA-type BC controllers cannot be connected to the P264 model or above. The GB- and HB-type BC controllers (sub) cannot be connected to the outdoor unit directly, and be sure to use them with GA- and HA-type BC controllers (main).�The insulation for low pressure pipe between the BC controller and outdoor unit shall be at least 20 mm thick. If the unit is installed on the top floor or in a high-temperature, high-humidity environment, thicker insulation may be necessary.�Do not have any branching points on the downstream of the refrigerant pipe header.�When a field-supplied external thermistor is installed or when a device for the demand control is used, abnormal stop of the unit or damage of the electromagnetic contactor may occur. Consult your local distributor for details.�When indoor units operate a fresh air intake, install a filter in the duct (field-supplied) to remove the dust from the air.�The 4-way or 2-way Airflow Ceiling Cassette Type units that have an outside air inlet can be connected to the duct, but need a booster fan to be installed at site. Refer to the chapter "Indoor Unit" for the available range for fresh air intake volume. �Operating fresh air intake on the indoor unit may increase the sound pressure level.
5-2. Precautions for Indoor unit
5. Installation information DATA U8
SYSTEM DESIGN 4 - 78
Syst
em Y
5-1-6. Unit installation�Your local distributor or a qualified technician must read the Installation Manual that is provided with each unit carefully before performing installation work.�Consult your local distributor or a qualified technician when installing the unit. Improper installation by an unqualified person may result in water leakage, electric shock, or fire.�Ensure there is enough space around each unit.
5-1-7. Optional accessories �Only use accessories recommended by Mitsubishi Electric. Consult your local distributor or a qualified technician when installing them. Improper installation by an unqualified person may result in water leakage, electric leakage, system breakdown, or fire.�Some optional accessories may not be compatible with the air conditioning unit to be used or may not suitable for the installation conditions. Check the compatibility when considering any accessories.�Note that some optional accessories may affect the air conditioner's external form, appearance, weight, operating sound, and other characteristics.
5-1-8. Operation/Maintenance�Read the Instruction Book that is provided with each unit carefully prior to use.�Maintenance or cleaning of each unit may be risky and require expertise. Read the Instruction Book to ensure safety. Consult your local distributor or a qualified technician when special expertise is required such as when the indoor unit needs to be cleaned.
5-2. Precautions for Indoor unit5-2-1. Operating environment
�The refrigerant (R410A) used for air conditioner is non-toxic and nonflammable. However, if the refrigerant leaks, the oxygen level may drop to harmful levels. If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.�If the units operate in the cooling mode at the humidity above 80%, condensation may collect and drip from the indoor units.
5-2-2. Unit characteristics�The return air temperature display on the remote controller may differ from the ones on the other thermometers.�The clock on the remote controller may be displayed with a time lag of approximately one minute every month.�The temperature using a built-in temperature sensor on the remote controller may differ from the actual room tempera-ture due to the effect of the wall temperature.�Use a built-in thermostat on the remote controller or a separately-sold thermostat when indoor units installed on or in the ceiling operate the automatic cooling/heating switchover.�The room temperature may rise drastically due to Thermo OFF in the places where the air conditioning load is large such as computer rooms.�Be sure to use a regular filter. If an irregular filter is installed, the unit may not operate properly, and the operation noise may increase.�The room temperature may rise over the preset temperature in the environment where the heating air conditioning load is small.
5-2-3. Unit installation�For simultaneous cooling/heating operation type air conditioners (R2, WR2 series), the G-type BC controller cannot be connected to the P144 outdoor unit model or above, and the G- and GA-type BC controllers cannot be connected to the P264 model or above. The GB- and HB-type BC controllers (sub) cannot be connected to the outdoor unit directly, and be sure to use them with GA- and HA-type BC controllers (main).�The insulation for low pressure pipe between the BC controller and outdoor unit shall be at least 20 mm thick. If the unit is installed on the top floor or in a high-temperature, high-humidity environment, thicker insulation may be necessary.�Do not have any branching points on the downstream of the refrigerant pipe header.�When a field-supplied external thermistor is installed or when a device for the demand control is used, abnormal stop of the unit or damage of the electromagnetic contactor may occur. Consult your local distributor for details.�When indoor units operate a fresh air intake, install a filter in the duct (field-supplied) to remove the dust from the air.�The 4-way or 2-way Airflow Ceiling Cassette Type units that have an outside air inlet can be connected to the duct, but need a booster fan to be installed at site. Refer to the chapter "Indoor Unit" for the available range for fresh air intake volume. �Operating fresh air intake on the indoor unit may increase the sound pressure level.
H2iYSD-40 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
5. INSTALLATION INFORMATION
4 - 79
5. Installation information DATA U8
SYSTEM DESIGN
System Y
5-3. Precautions for Fresh air intake type indoor unit5-3-1. Usage
�This unit mainly handles the outside air load, and is not designed to maintain the room temperature. Install other air con-ditioners for handling the air conditioning load in the room.
5-3-2. Unit characteristics�This unit cannot perform the drying operation. The unit will continue the fan operation and blow fresh air (air that is not air-conditioned) when the Heating Thermo-OFF or Cooling Thermo-OFF mode is selected.�The fan may stop tentatively when the unit is connected to the simultaneous cooling/heating operation type outdoor unit (R2, WR2 series) or during the defrost cycle.�This unit switches the Thermo ON or OFF depending on the room temperature. The outside air is directly supplied into the room during Thermo OFF. Take caution of the cold supply air due to low outside air temperature and of condensation in the room due to high humidity of the outside air.�Outside air temperature ranges for the operation must be as follows:Cooling: 21ºCD.B./15.5ºCW.B. ~ 43ºCD.B./35ºCW.B.Heating: -10ºCD.B.~ 20ºCD.BThe unit is forced to operate Thermo OFF (fan operation) when the outside air temperature is as follows.Cooling: 21ºCD.B or below; Heating: 20ºCD.B or above�Either a remote controller (sold separately) or a remote sensor (sold separately) must be installed to monitor the room temperature.�If only this unit is used as an indoor unit, condensation may form at the supply air grill while the unit is operated in the cooling mode. This unit cannot operate dehumidifying.�Use the unit in the way that the airflow rate will not exceed the 110% of the rated airflow.
5-4. Precautions for Outdoor unit/Heat source unit5-4-1. Installation environment
�Outdoor unit with salt-resistant specification is recommended to use in a place where it is subject to salt air.�Even when the unit with salt-resistant specification is used, it is not completely protected against corrosion. Be sure to follow the directions or precautions described in Instructions Book and Installation Manual for installation and mainte-nance. The salt-resistant specification is referred to the guidelines published by JRAIA (JRA9002).�Install the unit in a place where the flow of discharge air is not obstructed. If not, the short-cycling of discharge air may occur.�Provide proper drainage around the unit base, because the condensation may collect and drip from the outdoor units. Provide water-proof protection to the floor when installing the units on the rooftop.�In a region where snowfall is expected, install the unit so that the outlet faces away from the direction of the wind, and install a snow guard to protect the unit from snow. Install the unit on a base approximately 50 cm higher than the expect-ed snowfall. Close the openings for pipes and wiring, because the ingress of water and small animals may cause equip-ment damage. If SUS snow guard is used, refer to the Installation Manual that comes with the snow guard and take caution for the installation to avoid the risk of corrosion.�When the unit is expected to operate continuously for a long period of time at outside air temperatures of below 0ºC, take appropriate measures, such as the use of a unit base heater, to prevent icing on the unit base. (Not applicable to the PUMY series)�Install the snow guard so that the outlet/inlet faces away from the direction of the wind.�When the snow accumulates approximately 50 cm or more on the snow guard, remove the snow from the guard. Install a roof that is strong enough to withstand snow loads in a place where snow accumulates.�Provide proper protection around the outdoor units in places such as schools to avoid the risk of injury.�A cooling tower and heat source water circuit should be a closed circuit that water is not exposed to the atmosphere. When a tank is installed to ensure that the circuit has enough water, minimize the contact with outside air so that the oxygen from being dissolved in the water should be 1 mg/L or less.�Install a strainer (50 mesh or more recommended) on the water pipe inlet on the heat source unit.�Interlock the heat source unit and water circuit pump.�Note the followings to prevent the freeze bursting of pipe when the heat source unit is installed in a place where the ambient temperature can be 0ºC or below. �Keep the water circulating to prevent it from freezing when the ambient temperature is 0ºC or below. �Before a long period of non use, be sure to purge the water out of the unit.
5-4-2. Circulating water�Follow the guidelines published by JRAIA (JRA-GL02-1994) to check the water quality of the water in the heat source unit regularly.�A cooling tower and heat source water circuit should be a closed circuit that water is not exposed to the atmosphere. When a tank is installed to ensure that the circuit has enough water, minimize the contact with outside air so that the oxygen from being dissolved in the water should be 1 mg/L or less.
4 - 79
5. Installation information DATA U8
SYSTEM DESIGN
System Y
5-3. Precautions for Fresh air intake type indoor unit5-3-1. Usage
This unit mainly handles the outside air load, and is not designed to maintain the room temperature. Install other air con-ditioners for handling the air conditioning load in the room.
5-3-2. Unit characteristicsThis unit cannot perform the drying operation. The unit will continue the fan operation and blow fresh air (air that is not air-conditioned) when the Heating Thermo-OFF or Cooling Thermo-OFF mode is selected.The fan may stop tentatively when the unit is connected to the simultaneous cooling/heating operation type outdoor unit (R2, WR2 series) or during the defrost cycle.This unit switches the Thermo ON or OFF depending on the room temperature. The outside air is directly supplied into the room during Thermo OFF. Take caution of the cold supply air due to low outside air temperature and of condensation in the room due to high humidity of the outside air.Outside air temperature ranges for the operation must be as follows:Cooling: 21ºCD.B./15.5ºCW.B. ~ 43ºCD.B./35ºCW.B.Heating: -10ºCD.B.~ 20ºCD.BThe unit is forced to operate Thermo OFF (fan operation) when the outside air temperature is as follows.Cooling: 21ºCD.B or below; Heating: 20ºCD.B or aboveEither a remote controller (sold separately) or a remote sensor (sold separately) must be installed to monitor the room temperature.If only this unit is used as an indoor unit, condensation may form at the supply air grill while the unit is operated in the cooling mode. This unit cannot operate dehumidifying.Use the unit in the way that the airflow rate will not exceed the 110% of the rated airflow.
5-4. Precautions for Outdoor unit/Heat source unit5-4-1. Installation environment
Outdoor unit with salt-resistant specification is recommended to use in a place where it is subject to salt air.Even when the unit with salt-resistant specification is used, it is not completely protected against corrosion. Be sure to follow the directions or precautions described in Instructions Book and Installation Manual for installation and mainte-nance. The salt-resistant specification is referred to the guidelines published by JRAIA (JRA9002).Install the unit in a place where the flow of discharge air is not obstructed. If not, the short-cycling of discharge air may occur.Provide proper drainage around the unit base, because the condensation may collect and drip from the outdoor units. Provide water-proof protection to the floor when installing the units on the rooftop.In a region where snowfall is expected, install the unit so that the outlet faces away from the direction of the wind, and install a snow guard to protect the unit from snow. Install the unit on a base approximately 50 cm higher than the expect-ed snowfall. Close the openings for pipes and wiring, because the ingress of water and small animals may cause equip-ment damage. If SUS snow guard is used, refer to the Installation Manual that comes with the snow guard and take caution for the installation to avoid the risk of corrosion.When the unit is expected to operate continuously for a long period of time at outside air temperatures of below 0ºC, take appropriate measures, such as the use of a unit base heater, to prevent icing on the unit base. (Not applicable to the PUMY series)Install the snow guard so that the outlet/inlet faces away from the direction of the wind.When the snow accumulates approximately 50 cm or more on the snow guard, remove the snow from the guard. Install a roof that is strong enough to withstand snow loads in a place where snow accumulates.Provide proper protection around the outdoor units in places such as schools to avoid the risk of injury.5. Installation information DATA U8
SYSTEM DESIGN 4 - 80
Syst
em Y
5-4-2. Unit characteristicsWhen the Thermo ON and OFF is frequently repeated on the indoor unit, the operation status of outdoor units maybecome unstable.
5-4-3. Relevant equipmentProvide grounding in accordance with the local regulations.
5-5. Precautions for Control-related items5-5-1. Product specification
To introduce the MELANS system, a consultation with us is required in advance. Especially to introduce the electricity charge apportioning function or energy-save function, further detailed consultation is required. Consult your local distrib-utor for details.Billing calculation for AG-150A, GB-50ADA, TG-2000A, or the billing calculation unit is unique and based on our original method. (Backup operation is included.) It is not based on the metering method, and do not use it for official business purposes. It is not the method that the amount of electric power consumption (input) by air conditioner is calculated. Note that the electric power consumption by air conditioner is apportioned by using the ratio corresponding to the operation status (output) for each air conditioner (indoor unit) in this method.In the apportioned billing function for AG-150A and GB-50ADA, use separate watthour meters for A-control units, K-control units, and packaged air conditioner for City Multi air conditioners. It is recommended to use an individual watthour meter for the large-capacity indoor unit (with two or more addresses).When using the peak cut function on the AG-150A or GB-50ADA, note that the control is performed once every minute and it takes time to obtain the effect of the control. Take appropriate measures such as lowering the criterion value. Pow-er consumption may exceed the limits if AG-150A or GB-50ADA malfunctions or stops. Provide a back-up remedy as necessary.The controllers cannot operate while the indoor unit is OFF. (No error) Turn ON the power to the indoor unit when operating the controllers.When using the interlocked control function on the AG-150A, GB-50ADA, PAC-YG66DCA, or PAC-YG63MCA, do not use it for the control for the fire prevention or security. (This function should never be used in the way that would put people's lives at risk.) Provide any methods or circuit that allow ON/OFF operation using an external switch in case of failure.
5-5-2. Installation environmentThe surge protection for the transmission line may be required in areas where lightning strikes frequently occur.A receiver for a wireless remote controller may not work properly due to the effect of general lighting. Leave a space of at least 1 m between the general lighting and receiver.When the Auto-elevating panel is used and the operation is made by using a wired remote controller, install the wired remote controller to the place where all air conditioners controlled (at least the bottom part of them) can be seen from the wired remote controller. If not, the descending panel may cause damage or injury, and be sure to use a wireless remote controller designed for use with elevating panel (sold separately).Install the wired remote controller (switch box) to the place where the following conditions are met.
Where installation surface is flatWhere the remote controller can detect an accurate room temperatureThe temperature sensors that detect a room temperature are installed both on the remote controller and indoorunit. When a room temperature is detected using the sensor on the remote controller, the main remote controlleris used to detect a room temperature. In this case, follow the instructions below.
Install the controller in a place where it is not subject to the heat source. (If the remote controller faces direct sunlight or supply air flow direction, the remote controller cannot detect an accurate room temperature.) Install the controller in a place where an average room temperature can be detected. Install the controller in a place where no other wires are present around the temperature sensor. (If other wires are present, the remote controller cannot detect an accurate room temperature.)
To prevent unauthorized access, always use a security device such as a VPN router when connecting AG-150A, GB-50ADA, or TG-2000A to the Internet.
5-3. Precautions for Fresh air intake type indoor unit
5-4. Precautions for Outdoor unit/Heat source unit
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-41© 2014 Mitsubishi Electric US, Inc.
5. INSTALLATION INFORMATION
5. Installation information DATA U8
SYSTEM DESIGN 4 - 80
Syst
em Y
5-4-3. Unit characteristics�When the Thermo ON and OFF is frequently repeated on the indoor unit, the operation status of outdoor units may be-come unstable.
5-4-4. Relevant equipment�Provide grounding in accordance with the local regulations.
5-5. Precautions for Control-related items5-5-1. Product specification
�To introduce the MELANS system, a consultation with us is required in advance. Especially to introduce the electricity charge apportioning function or energy-save function, further detailed consultation is required. Consult your local distrib-utor for details.�Billing calculation for AG-150A, GB-50ADA, TG-2000A, or the billing calculation unit is unique and based on our original method. (Backup operation is included.) It is not based on the metering method, and do not use it for official business purposes. It is not the method that the amount of electric power consumption (input) by air conditioner is calculated. Note that the electric power consumption by air conditioner is apportioned by using the ratio corresponding to the operation status (output) for each air conditioner (indoor unit) in this method.�In the apportioned billing function for AG-150A and GB-50ADA, use separate watthour meters for A-control units, K-control units, and packaged air conditioner for City Multi air conditioners. It is recommended to use an individual watthour meter for the large-capacity indoor unit (with two or more addresses).�When using the peak cut function on the AG-150A or GB-50ADA, note that the control is performed once every minute and it takes time to obtain the effect of the control. Take appropriate measures such as lowering the criterion value. Pow-er consumption may exceed the limits if AG-150A or GB-50ADA malfunctions or stops. Provide a back-up remedy as necessary.�The controllers cannot operate while the indoor unit is OFF. (No error) Turn ON the power to the indoor unit when operating the controllers.�When using the interlocked control function on the AG-150A, GB-50ADA, PAC-YG66DCA, or PAC-YG63MCA, do not use it for the control for the fire prevention or security. (This function should never be used in the way that would put people's lives at risk.) Provide any methods or circuit that allow ON/OFF operation using an external switch in case of failure.
5-5-2. Installation environment�The surge protection for the transmission line may be required in areas where lightning strikes frequently occur.�A receiver for a wireless remote controller may not work properly due to the effect of general lighting. Leave a space of at least 1 m between the general lighting and receiver.�When the Auto-elevating panel is used and the operation is made by using a wired remote controller, install the wired remote controller to the place where all air conditioners controlled (at least the bottom part of them) can be seen from the wired remote controller. If not, the descending panel may cause damage or injury, and be sure to use a wireless remote controller designed for use with elevating panel (sold separately).�Install the wired remote controller (switch box) to the place where the following conditions are met.
�Where installation surface is flat�Where the remote controller can detect an accurate room temperature
The temperature sensors that detect a room temperature are installed both on the remote controller and indoorunit. When a room temperature is detected using the sensor on the remote controller, the main remote controlleris used to detect a room temperature. In this case, follow the instructions below.
� Install the controller in a place where it is not subject to the heat source. (If the remote controller faces direct sunlight or supply air flow direction, the remote controller cannot detect an accurate room temperature.)
� Install the controller in a place where an average room temperature can be detected.� Install the controller in a place where no other wires are present around the temperature sensor.
(If other wires are present, the remote controller cannot detect an accurate room temperature.) �To prevent unauthorized access, always use a security device such as a VPN router when connecting AG-150A, GB-50ADA, or TG-2000A to the Internet.
5-5. Precautions for Control-related items
H2iYSD-42 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
6. STANDARD AND SEACOAST (BS) PROTECTION TREATMENT
Component Base Material Standard Models
Seacoast Protection
Models (-BS)
Surface Treatment
Coating Thickness
External Surface Internal Surface
External Panel Base Alloyed Galvanized Steel Sheet ● ● Thermoset Polyester-resin
Powder Coating ≥70μm ≥70μm
External Front Panel Alloyed Galvanized Steel Sheet
● Polyester-resin Coating ≥15μm ≥5μm
● Thermoset Polyester-resin Powder Coating ≥85μm ≥75μm
Pillar Alloyed Galvanized Steel Sheet
● Polyester-resin Coating ≥30μm
● Thermoset Polyester-resin Powder Coating ≥70μm ≥70μm
Compressor CoverGalvanized Steel Sheet ● No Treatment
Galvanized Aluminum Sheet ● Thermoset Polyester-resin
Powder Coating ≥70μm ≥70μm
Fin Guard Steel Wires ● ● Weather-resistant Polypropylene-resin Coating ≥300μm ≥300μm
Fan Guard and Drum Weather-resistant Polypropylene Plastic ● ● No Treatment
Fan Weather-resistant Acrylic Nitrile Styrene Plastic ● ● No Treatment
Fan Motor Frame Galvanized Steel Sheet ● ● No Treatment
Fan Motor Shaft High-carbon S35C Steel ● ● Rust-prevention Coating
Fan Motor Support Galvanized Steel Sheet● No Treatment
● Thermoset Polyester-resin Powder Coating ≥70μm ≥70μm
Heat Exchanger (Fin Only) Aluminum Plate
●Cellulose- and Polyurethane- resin Coating (Blue Fin) (no unusual rust development to 480 hours)
≥1μm
●Cellulose- and Polyurethane-resin Coating (Blue Fin) (no unusual rust development to 960 hours)
≥1 - 1.5μm
Electrical Parts BoxGalvanized Steel Sheet ● No Treatment
Galvanized Aluminum Sheet ● Thermoset Polyester-resin
Powder Coating ≥70μm
Printed Circuit Board Epoxy Resin● No Treatment
● Polyurethane Coating ≥10μm
Screws Steel ● ● Zinc-nickel Alloy Plating with a Chromate Film ≥5μm
Application GuideDistance from the Sea
984′ (300m) 1,640′ (500m) 3,281′ (1km)Direct Exposure to Sea BreezesFacing Inland Seacoast Protection (-BS) Models Standard ModelsFacing Sea Seacoast Protection (-BS) ModelsOn an Island Seacoast Protection (-BS) ModelsIndirect Exposure to Sea BreezesFacing Inland Seacoast Protection (-BS) Models Standard ModelsFacing Sea Seacoast Protection (-BS) ModelsOn an Island Seacoast Protection (-BS) Models
For optimum performance, follow the cautions listed below.1. Avoid installing the unit in a location that is subjected to direct sea winds.2. Do not attach a sunshade to the unit. Let the rain wash away any salt residue that may adhere to the unit.3. Unit should be installed following instructions for proper operation and to ensure optimum water drainage.4. Periodically wash the unit.5. If the panels become scratched, repair as soon as possible.6. Inspect the unit at regular intervals. Paint the unit or replace parts when necessary. Material Thermoset Polyester-resin
Powder CoatingCellulose- and Polyurethane-
resin Coating (Blue Fin)
Test Conditions
Salt-spray Test Method: JIS K2371 based on ISO9227
Salt-spray Test Method: JIS Z2371 based on ISO9227
Test Results
Conform to JRA9002 Criteria (960-hour test)
No unusual rust development to
480 hours
No unusual rust development to
960 hours
“Blue Fin” treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants.
6-1. H2i Y-Series
PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014) H2iYSD-43© 2014 Mitsubishi Electric US, Inc.
7. CAUTIONS
7-1. Refrigerant Leakage Considerations
In the United States safety classification of refrigerants is governed by ASHRAE Standard 34. Standard 34 prescribes safety group and flammability classifications for refrigerants. These groups are shown below:
Mitsubishi VRF systems utilize R410A refrigerant. ASHRAE Standard 34 assigns a classification of A1 to this refrigerant, placing it in the lowest toxicity and no flame propagation category.
ASHRAE Standard 34 also prescribes maximum permissible concentration levels of any such refrigerant in an occupied space to protect the occupants from asphyxiation and or toxicity. ASHRAE Standard 34-2010, Addendum l sets the concentrations level to 26lbs/Mcf for R410A refrigerant.
ASHRAE Standard 15 prescribes safe design practices for refrigeration systems and references Standard 34 within when establishing where additional measures must be taken when refrigerant concentration level limits prescribed by Standard 34 are exceeded. Most state codes reference the International Mechanical Code (IMC). Chapter 11 of the IMC governs the safe design and install of refrigeration systems and references ASHRAE 15 & 34 for requirements of allowable concentration levels and other safety measures for designing refrigeration systems.
In any VRF design, it is imperative that the designer ensures that in the event of a major leakage of all system refrigerant into a single enclosed occupied space, that these concentration limits are not exceeded in order to protect the occupants.
ASHRAE Standard 15 specifies that the smallest occupied space volume to consider in event of a major leakage is that space volume which does not connect through permanent openings such as transfer openings or HVAC ducts. In any event the following must be evaluated for each smallest enclosed area:
Area Leakage Concentration Level (lbs/Mcf) = Total VRF System Charge (lbs) / [Area Volume (ft3)/1000] Total VRF System Charge = Factory Charge + Trim Charge In Field
If a particular space, per this calculation, exceeds the concentration limit of 26 lbs/Mcf, the volume must be increased through connectivity to maintain the leakage concentration level below the threashold.
When determining smallest space volume when spaces are connected, ASHRAE 15 does not specifically address how much free area is required to claim connectivity of spaces. The Japanese Refrigeration Standard, JRA GL-13;2012, specifies that 0.15% of the floor area must be provided for a transfer opening to claim connectivity to an adjacent space. This can be used as guide, but again is not referenced to any specific US recognized codes / standard. Always consult the local code / jurisdiction for requirements with regard to refrigerant leakage in any event.
An example of a countermeasure to claim connectivity of spaces is shown below. In this example a dedicated outdoor air / or ventilation system is continuously supplying fresh air to the smallest occupied space. A transfer opening or a door under cut is provided so that the space is communicating with an adjacent space. A low wall exhaust could also be provided equal to the fresh air delivery amount to promote the capture of any leaked refrigerant. Utilizing a low wall exhaust in areas where space occupants are sleeping would be beneficial since R410A is heavier than air and will tend to migrate towards the floor.
H2iYSD-44 PUHY-HP-T(S)JMU, -Y(S)JMU SYSTEM DESIGN (November 2014)© 2014 Mitsubishi Electric US, Inc.
7. CAUTIONS
Counter Measure Example for Critical Space VolumesCreating Connectivity of Spaces
E/AVRF
F/A From DOAS
Low Wall Exh
Door Undercut0.15% Floor Area
R410A Heavier than Air
Connectivity of Spaces
Critical Space