Article Number: Q5009 Products: CitectHMI/SCADA, CitectFacilities, CitectSCADA Batch, CitectSCADA Pocket Versions: 7.0 Summary List of hardware alarms. Error No. Error title Description 256 General software error An internal CitectSCADA software error is detected. Contact Citect Support and provide details on what causes the error. 257 Value is out of range A numeric value is out of range. An out-of-range value has been passed to a function, or an array index is off the end of an array, or a value that is outside of the specified engineering scale has been assigned to a I/O Device variable. You can disable range checking on PLC variables with the CodeSetMode() function. 258 Buffer has been overrun A buffer has been overrun. More data has been passed to a function than it can write to its temporary buffers. Try again by calling the function twice, with half the data in each call. 259 Array has been overrun An array passed to a function is too small for the data requested. Define a larger array or reduce the maximum data size requested. 260 Path does not exist The specified path to a device or file does not exist. During a function call (that tried to open a file), a non-existent path was specified. Call the function again with the correct path. 261 File does not exist The specified file or device does not exist. During a function call (that tried to open a file), the file could not be found. Call the function again with the correct file name. This error will also occur if you try to call TrnDelHistory() on a file that has never been added using TrnAddHistory(). 262 Cannot open file The specified file cannot be opened. During a function call (that tried to open a file), the file could not be opened. There may be a mode error (e.g. from trying to open a read-only file in write mode), or the file may be open by others, or the operating system resources may be too low to open the file. Check that the file does exist (use File Manager), and that you have the correct rights to open it. (Check with your network supervisor that you have correct rights to open the file). Page 1 of 13 25/03/2009 mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

description

Citect Error Code

Transcript of Citect V7.0 Error Codes

Page 1: Citect V7.0 Error Codes

Article Number: Q5009

Products: CitectHMI/SCADA, CitectFacilities, CitectSCADA Batch, CitectSCADA Pocket

Versions: 7.0

Summary

List of hardware alarms.

Error No. Error title Description

256 General software error An internal CitectSCADA software error is detected. Contact Citect Support and provide details on what causes the error.

257 Value is out of range A numeric value is out of range. An out-of-range value has been passed to a function, or an array index is off the end of an array, or a value that is outside of the specified engineering scale has been assigned to a I/O Device variable. You can disable range checking on PLC variables with the CodeSetMode() function.

258 Buffer has been overrun A buffer has been overrun. More data has been passed to a function than it can write to its temporary buffers. Try again by calling the function twice, with half the data in each call.

259 Array has been overrun An array passed to a function is too small for the data requested. Define a larger array or reduce the maximum data size requested.

260 Path does not exist The specified path to a device or file does not exist. During a function call (that tried to open a file), a non-existent path was specified. Call the function again with the correct path.

261 File does not exist The specified file or device does not exist. During a function call (that tried to open a file), the file could not be found. Call the function again with the correct file name. This error will also occur if you try to call TrnDelHistory() on a file that has never been added using TrnAddHistory().

262 Cannot open file The specified file cannot be opened. During a function call (that tried to open a file), the file could not be opened. There may be a mode error (e.g. from trying to open a read-only file in write mode), or the file may be open by others, or the operating system resources may be too low to open the file.

Check that the file does exist (use File Manager), and that you have the correct rights to open it. (Check with your network supervisor that you have correct rights to open the file).

Page 1 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 2: Citect V7.0 Error Codes

263 Cannot read file The specified file cannot be read. Either an error occurred during a read operation, or the end of file was unexpectedly found, or a loss of the file server occurred, or the operating system is out of resources.

264 Cannot write to file The specified file cannot be written to. During a function call (that tried to write to a file), a write error occurred. There could be a disk full error, or a loss of the file server may have occurred, or the operating system is out of resources.

265 Invalid file type An attempt was made to open a file of the wrong type, e.g. you tried to open an ASCII file as a dBASE file.

266 Field not found in file The specified field does not exist in the device or database. A function that is trying to access an individual field in a database cannot find that field. Check that you have specified the correct field name and database name.

267 File mode is invalid An operation has been attempted on a file or device that is of the wrong mode, e.g. you tried to perform a seek on a printer device. Do not use this operation on this type of device.

268 Key not found in file The requested key was not found when a key search was performed on a database device, i.e. the record specified on an indexed search cannot be found. Either the record does not exist or you have specified the wrong key.

269 Bad handle specified A bad handle has been passed to a function. You have called a function that requires a device handle, font handle, window handle, etc., but you passed a number that does not associate with a read device, font, or window (e.g. you called WinGoto(100) when no window with the handle "100" exists). Check where the handle or number was retrieved from, and make sure it is the same handle. This error may also occur if you have closed or destroyed the resource and you then try to access it.

271 No more free handles left

All the available file handles have been used, i.e. too many files or databases are open at the same time. Open fewer files at one time or increase the number of file handles in the [CtEdit]DBFiles parameter.

272 Out of memory CitectSCADA is out of memory. Increase the amount of memory in the computer or use smaller databases.

273 Divide by zero An attempt has been made to divide a number by zero.

274 Invalid argument passed An invalid argument has been passed to a Cicode function. This is a general error message and is generated when arguments passed to a function are out of range or are invalid. Check the value of arguments being passed to the function. If arguments are input directly from the operator, you should check that the correct arguments are being passed to the function.

Page 2 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 3: Citect V7.0 Error Codes

275 Overflow A calculation has resulted in a numeric value overflow. Check for operations that will generate large numbers.

276 No privilege for operation

A user has requested an operation for which he or she has no privilege.

277 Not in correct area A user has requested data that does not belong to the current user area.

278 Report already busy A request has been made to run a report that is already running. You can get the current state of a report with the RepGetControl() function. You can ignore this error message (because the report is already running).

279 Report is late for execution

The report cannot run at the rate requested in the configuration. An attempt could have been made to run a report too frequently, and the required data cannot be read from the I/O Device(s) in time for the next report.

280 Invalid report ID specified

The specified report name does not exist, or the user has no privilege to run the report, or the report is not in the current user area. Check the name of the report and the current user's privilege and areas.

281 No server could be found

The specified CitectSCADA server cannot be found. Either the server is not running or there is some communication problem with the network. Check that the network is set up correctly, and the [Lan] Disable parameter is set to 0 (zero), and you are using the same Server Name on both the client and server.

282 Foreground Cicode cannot block

You cannot block the foreground CitectSCADA task. You may have called a blocking function from one of the Page animation databases.

283 Trend has missed samples

The trend cannot run at the rate requested in the configuration. An attempt could have been made to trend the data too frequently, and the required data cannot be read from the I/O Device(s) in time for the next trend. Either increase the performance of the communication link to the PLCs or slow the rate of trend data acquisition.

284 Device is disabled An attempt was made to access a device that is disabled. You can disable any devices (printers and other logging devices) with the DevDisable() function. When CitectSCADA (or your Cicode function) tries to access a disabled device, this error message returns and all output is lost.

285 Foreground Cicode run is too long

The foreground Cicode task is taking too long to animate the display page. The Cicode is too complex and is taking too long to execute. Simplify the Cicode that is animating the page, or increase the [Code] TimeSlice parameter. If you cannot simplify the Cicode, you can create a separate task using TaskNew() to calculate your complex operation, and then use the Display functions to display the results. Cicode running from a TaskNew() call is in background

Page 3 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 4: Citect V7.0 Error Codes

mode and can run as long as required.

286 Out of Cicode threads CitectSCADA has run out of Cicode tasks. Run fewer tasks (e.g. reports, key commands, and Cicode tasks) in parallel, or increase the number of tasks with the [Code]Threads parameter. This error can be caused by a configuration error if you keep creating tasks but do not "kill" them when they are no longer required.

287 Floating point exception trap

An invalid floating-point number has been found. Check the floating-point data from the I/O Device.

288 Out of buffers CitectSCADA is out of dynamic buffers. You have called a function that requests buffer space but no buffers are available. Check which function is causing the error and increase the associated buffers, or slow the rate of transfer to that function. If the error occurs on a server or LAN device, increase the number of buffers with the [Lan]ReadPool parameter.

This error can also occur if something is stopping the release of the buffers, e.g. if network communication has stopped or a PLC has just come off-line. The error 'Out of buffers' can also be generated in the following ways:

Calling QueWrite() when the queue functions have run out of buffers. You can increase the number of queue buffers with the [Code] Queue parameter.

Calling WinFree() to free the last Cicode window. If WinFree() did free the last window, CitectSCADA would have no windows left.

To verify which function is causing the hardware error, display the {ERRPAGE} and {ERRDESC} fields on the hardware alarm.

289 Name does not exist The specified name does not exist in this context. You are probably using the wrong name.

290 Not finished A request has been made for trend data that has not yet finished trending.

291 File not CitectSCADA format

The specified file is not in CitectSCADA format. The file (trend, graphic, or any other file) is in an invalid format. Check that the name of the file is valid or that the file has not become corrupted.

292 Invalid function The specified function name does not exist. You have tried to create a task, or called a remote procedure, or set an event function that does not exist.

293 File error A general file error has occurred. Either a general hardware error has occurred, or the operating system is out of resources, or the file server is down.

294 File EOF The end of the file was found. An attempt was made to read data off the end of a file or database.

Page 4 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 5: Citect V7.0 Error Codes

295 Cicode stack overflow A Cicode evaluation stack overflow has occurred. There are too many local function variables or nested function calls. Reduce the number of local variables or increase the [Code] Stack parameter.

The Cicode stack is used to store local function variables and function calls. If you have many nested functions and a large number of local function variables, the Cicode stack may overflow. When the Cicode stack overflows, the Cicode that caused the overflow is halted.

You can estimate the size of the stack by counting the maximum number of local function variables in the deepest function calls. For example, if function A has 10 variables and calls function B with 30 variables, which calls function C with 40 variables, the stack needs to be 10 + 30 + 40 = 80 deep.

296 Queue empty An attempt has been made to read an element from an empty queue.

297 Semaphore owner died The owner of a Cicode semaphore was halted, killed, or returned without releasing the semaphore. Reset the shared resource back to a known state (because the task that died may have left it in a mess), and then continue. For example, if you are sharing a printer, do a form feed.

298 Semaphore timeout The requested semaphore was still in use after the specified timeout. Either try to get the semaphore again or abort the operation and tell the operator of the error.

299 Cancelled The specified form or command was cancelled. This error is returned when a user presses the Cancel button on a form. The normal procedure is to abort the operation.

300 Trend not found The trend does not exist at the specified AN and page. A trend function may have been called when the trend is not defined for that AN.

301 Trend pen not found The required trend pen name does not exist in the Trends database or is not in the current user area. Check that the pen name exists and check the current user's privilege and area.

302 Trend data not valid The requested trend data is not valid. Either the I/O Device data was bad, or the CitectSCADA trend server was shut down, or the trend data was disabled.

303 Invalid animation number

The AN specified in the function is not defined. You called one of the DspXXX animation functions, but you specified an animation number that was out of range or that had been deleted.

304 File server failed, stand-by active

CitectSCADA has detected a file server fail condition, and will switch to the standby file server. The file server is down due to failure of the network or of the file server computer. This error is displayed only if you have enabled redundant file servers. If a

Page 5 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 6: Citect V7.0 Error Codes

redundant file server is not enabled, CitectSCADA and Windows crashes when the file server fails. You should report this error to the operators to fix the file server.

305 Conflicting types of animation

The same AN is being used for two different types of animation. This error occurs if you try to display two (or more) incompatible types of animation on the same AN (e.g. you try to display a symbol at a AN where a bar graph is already displayed). Check the configuration. If you need to display a new animation, you must first delete the old animation with the DspDel() function.

306 SQL field value truncated

A maximum of 1000bytes (1Kb) can be returned from a single field call. If the field data is larger than this limit, it is truncated. You have tried to access a database where one of the fields is greater than 1000 bytes in size. Change the database field size to less than 1000 bytes so it can be accessed. In fact, you should change the field size to less than 256 bytes, the maximum allowable length of a Cicode string.

307 SQL database error A general SQL error. Call the SQLErrMsg() function for details of the error.

308 SQL null field data returned

Data has been requested from a field that contained no data, or the SQL server does not support this type of field data. CitectSCADA will return an empty string. Call the SQLFieldInfo() function to list the fields in the database.

309 Trend data is gated You have requested trend data that was gated (set to logging disabled) by the trigger expression (i.e. when it was acquired). The data is returned with the gated values set to 0.

310 Incompatible server version

Two servers are running incompatible versions of the CitectSCADA software. Install the latest version on each server. Contact Citect Support to arrange for an upgrade.

311 Alarm tag synchronize error

When the Alarm server shuts down it writes an alarm save file. If the alarm server is in tag mode (rather than record mode) this message will display. You can set the mode with the [Alarm]SaveStyle parameter. You can ignore this message as it is a warning only.

312 MAPI generic error A generic MAPI error has occurred. Call the MailError() function to retrieve the MAPI error.

313 No MAPI The MAPI mail system is not installed, or incorrectly installed on the computer.

314 MAPI offline The computer is not logged on to the MAPI mail system. Call the MailLogon() function to log on to the MAPI mail system.

315 MAPI no mail No mail was available. This message is returned from the MailRead() function if no mail is available.

316 dBASE record locked The dBASE file is being accessed by another user. Check if the

Page 6 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 7: Citect V7.0 Error Codes

by another dBASE file has been opened in exclusive mode by the other user. This error can also occur if another user is updating the dBASE file, and will most likely occur if it is an indexed database, and the file is on a slow file server. You can adjust dBASE access with the [General]LockRetry and [General]LockDelay parameters.

317 Not in this version The operation is not supported in this version of CitectSCADA. You must upgrade to a higher version.

318 Invalid page function You have called the PageGoto(), PageNext(), PagePrev(), PageDisplay(), or PageLast() as an exit command in the Pages database.

319 Low physical memory CitectSCADA is low on physical memory. Increase available physical memory (not virtual memory). Reduce the size of SMARTDRV cache, close any other windows programs that are running, or add more RAM to your computer. You can set the minimum size of memory required by CitectSCADA with the [Memory]MinPhyK parameter. This parameter sets a value for the minimum physical memory before CitectSCADA will generate this error message.

This error may also occur if your swap file is large (i.e. greater than 20Mb). Reduce the size of your swap file. The swap file is configured with the Windows Control Panel (386 Enhanced icon).

320 Cannot free window The WinFree() function has been called but CitectSCADA has no windows left. (Note that the last window and any child windows owned by the last window cannot be removed.)

21 Font cannot be found The specified font cannot be found. Check the font name.

322 LAN Failure CitectSCADA has detected a failure on the network.

323 Super Genie not Associated

A Super Genie variable has not been associated correctly. This error can occur if a variable passed to the Super Genie is the wrong data type or the variable does not exist. The error will also occur if the Ass() function has not been called for the variable.

325 Project is not compiled Changes have been made to the project while the system was running. Either restart the system or shutdown and re-compile.

326 Could not run the CitectSCADA compiler

The CitectSCADA compiler could not be found. Either the computer has run out of memory, or the compiler has been removed from its directory.

327 User type not found An attempt was made to create a user of a type that has not been defined in the users database.

328 User already exists An attempt was made to create a new user with the same name as an existing user.

Page 7 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 8: Citect V7.0 Error Codes

329 Cannot have mixed trends

An attempt was made to display both a periodic trend and an event trend in the same trend window. Check the project configuration (Trend Tags and Page Trends databases) for mixed trends displayed in a trend window.

336 Event type trend is expected

One of the arguments passed to this trend function is only valid for event type trends.

337 Trend in file does not exist

The trend name inside the trend file does not exist in the trend database. It is likely that the trend file belongs to a trend which is deleted from the system configuration.

338 Plot Functions Sequence Mismatch

Plot functions are to be written in sequence since they depend on the data set up by other plot functions. Please refer to the description section for each Plot Function for the order of plot functions.

339 Plot Marker is not Defined

An undefined plot marker symbol has been used. Use the PlotSetMarker function before the PlotLine, PlotXYLine or PlotMarker functions.

342 Debug break The DebugBreak() Cicode function has been called. This indicates an invalid condition detected in user written Cicode. Enable the Cicode debugger to find the cause of the problem.

343 Foreground Cicode cannot break

A breakpoint has been hit in foreground Cicode. Foreground Cicode cannot be blocked. You can disable this error message in Debug Options, accessed through the Debug menu in the Cicode Editor.

344 Format overflow This error occurs when the string being used to return an error message is not long enough for the information to go into it.

345 Trend data not ready This warning is returned when the trend data is not ready to be returned. Try again later.

346 Dynamic Out of licence points

The dynamic point count has exceeded the point limit. See CitectSCADA Licence Point Count.

347 Assertion failed in user Cicode

An assertion has failed in your Cicode, and the task terminated. Assertions are made using the Assert() function. If you set the [Code]DebugMessage parameter to 1, the assertion logged and the operator prompted.

353 FTP Failure Problems connecting to the FTP server for file copy. Check that the service is running correctly by using a 3rd party tool outside CitectSCADA.

354 Unrecognized object class

The automation object to be used is not known or registered.

355 Object has no interface The automation objects interface no longer exists. This is either a logic or code error.

356 Object automation exception

Generic automation exception code for logging issues

Page 8 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 9: Citect V7.0 Error Codes

357 Too many arguments Formatting issues likely due to too many arguments (automation)

358 Too few arguments Less arguments available than expected (automation)

359 Named object already exists

An object tried to be created when it was already existed and it was not expected to exist. Check your cicode (automation)

360 Unrecognized named object

The name of an object did not match the internal records. Check your cicode (automation).

361 Page CTG/RDB record mismatch

An animation object id was not found in the records. Try a full compile and re-start.

362 Object event queue flooded

CitectSCADA has run out of Cicode tasks while processing ActiveX events. Create fewer concurrent ActiveX events, or increase the number of tasks with the [Code]Threads parameter.

363 Incorrect number of arguments

Internal error in cicode handling of objects. Try a full recompile and restart.

364 No 'this' argument Internal error in cicode handling of objects. Try a full recompile and restart.

374 Date Time Conflict A Date and/or time conflict has occurred. If you are attempting a TrnAddHistory(), make sure that the file you are adding does not have a conflicting time or date with existing trend files.

375 Password Expired The password has expired. Change password or adjust the [general]passwordexpiry settings.

379 Can not modify field The given fiel of Users.DBF is protected from direct user manipulation, so can not be modified.

380 Name Exists The user name specified is already exist in the Users.DBF.

381 File Format Error The file format is not in the desired format. It may be corrupted.

382 Page data / variable tag data mismatch

Page data / variable tag data mismatch with tag-based driver.

384 The code this queue/semaphore was waiting for exited due to an error

Cicode task has been flagged as dead. This will not be an issue if a cicode task was killed deliberately by the cicode logic.

391 Unsupported cicode function in Citect Web Client

A number of cicode functions can only be run in a non Web context. This error is flagging that such a function was tried from a Web client.

402 Cluster not specified Cicode call is ambiguous because no cluster was specified.

Page 9 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 10: Citect V7.0 Error Codes

403 Cluster not found The provided cluster name was not seen as a valid cluster name.

404 Cluster name and tag mismatch

A cluster name and a tag with a cluster name prefix were both passed, but they do not match each other.

405 Cluster not connected The operation cannot continue as the cluster is not connected.

406 Cluster already connected

The operation cannot continue as the cluster is already connected.

407 Databrowse pending Databrowse session currently being connected and is not yet available for further commands.

408 Databrowse not supported

This normally means that data has been requested from the wrong client / server type, i.e. a client request on a server or vice versa.

409 Databrowse type not found

Browse type unknown. Check all versions of citect32 are the same.

410 Databrowse session not found

iSession handle is invalid.

411 Databrowse session exists

Cannot open a session as it already exists.

412 Databrowse session EOF

Cannot browse beyond end of file. No more records left in the browse.

413 Databrowse field not found

The specified field is not present in the file.

414 Databrowse invalid field

The specified field is not valid for this browse function.

415 Databrowse no command

Browse command unknown. Check all versions of citect32 are the same.

416 Databrowse no next cluster

Internal flag that all clusters have been processed. Users use this in cicode to determine that there are no more clusters..

417 Cluster required for operation

The operation cannot continue as the cluster is required for operation of a server.

418 No server of type on cluster

There is no server of the required type configured on the server.

419 Client / Server ID mismatch

An ID given to a Cicode function is not of the correct type.

420 Not available outside This functionality is not available outside a process boundary e.g.

Page 10 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 11: Citect V7.0 Error Codes

process AlarmFirstCatRec is only able to be called from inside the Alarm Server process.

421 Invalid tran handle detected

Citect's internal communications subsystem detected an error whilst trying to send a message.

422 Dial call failed An attempt to make a call to a remote I/O device failed. You can find more information on the cause of this problem (if it is reproducible) by setting [Dial]Debug=1 and [Dial]DebugLevel=3 and looking in the syslog.dat.

423 Subscription value is pending

Occurs when a tag has been subscribed to, and attempted to read the value before the initial value has been retrieved from the server.

424 Tag not found Occurs when attempt to read or subscribe to a tag that does not exist.

425 No connector Not used.

426 Write to named pipe failed

An attempt to send a message via a name pipe has failed.

427 Redirect from non-Cicode task

A function cannot be redirected to another component as a proxy RPC unless it is in the context of a Cicode call.

428 Data browse record is invalid

The specified record is not valid for this browse function.

429 Can't plot symbol to printer

The Cicode PlotMarker() function can only plot a symbol to the display. This error occurs when the PlotMarker() Cicode function is used with a user-defined marker and a printer was specified as the output when PlotOpen() was called.

430 Alarm sort parameters mismatch

The [Alarm]SortMode parameter value on client is different as compared to the value on the alarm server. This value should be same in order to display alarms in correct order on the client.

431 Summary sort parameters mismatch

Values for [Alarm]SummarySort and [Alarm]SummarySortMode parameters on client are different as compared to the values on the alarm server. These values should be same in order to display alarm summary in correct order on the client.

432 Property not ready A specific tag property has been read in synchronous mode, before the value has been retrieved from the server. (similar to subscription value is pending)

433 Cicode type mismatch Some server side changes are now allowed for cicode, without restarting the client. This means that now it is possible to change a tag type to one that now cannot be converted as it was before. Eg val = TagA - TagB, If TagA has been converted from Integer to String, then the cicode will raise a cicode type mismatch as the '-' operation is not supported for strings

Page 11 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 12: Citect V7.0 Error Codes

434 Invalid data conversion Attempt to convert a value to a type that cannot store the value e.g. ULong to Long, and the value is greater than the Long type can handle.

435 Time Server not configured

Configuration Time parameters are incorrect; reconfigure the time synchronization. This error happens when [Time]Disable is false (or not specified) and the [Time]Address is empty or not specified

437 Failed to load security provider

Cannot load or initialize the Windows security provider. This indicates that the installation of operating system may be corrupted or the Windows security provider was not included.

439 Authentication failed Cannot authenticate the given Windows user name and password. Make sure the user name and password are typed in correctly

440 Authentication session does not exist

Cannot find the authentication session during the authentication process for the Windows user. This indicates that there was miscommunications in between client and server.

441 Role checking failed Cannot perform the role-check process for the Windows user. Make sure the roles database in the project is not corrupted.

442 No linked role The given Windows user is not linked to any role defined in the project.

443 Acquire user credentials failed

Cannot obtain the user credential handle from Windows.

444 Acquire user access token failed

Cannot obtain the user access token. This indicates that the security context of the Windows user was invalid.

445 Encrypt data failed Cannot encrypt the user information during the Windows user authentication process. This indicates that the security context of the Windows user was invalid.

446 Decrypt data failed Cannot decrypt the user information during the Windows user authentication process. This indicates that the security context of the Windows user was invalid.

447 The name of the table can not be found in the kernel.

Cicode UsrKernelTableInfo() has asked for a table that does not exist.

449 Invalid logout The logout was called when there is no one logged in or the logged on user is system default user.

1280 Socket error REMOVE, internal offset for socket errors

1330 WSAENETDOWN (10050) Network is down.

1331 Socket unreachable (10051) Network is unreachable.

1332 Network reset (10052) Network dropped connection on reset.

Page 12 of 13

25/03/2009mk:@MSITStore:D:\Control\Scada\Citect\Knowledge%20Base\CitectSCADA_KBas...

Page 13: Citect V7.0 Error Codes

Socket Error Notes Error codes from 0x500 to 0x599 are mapped to the standard Microsoft socket errors that start from 10000. 0x500 = 1280 . See http://msdn2.microsoft.com/en-us/library/ms740668(VS.85).aspx for the fuller descriptions. Generally these errors are beyond CItecSCADAs control, i.e. there is a external reason outside while CitectSCADA can’t use the TCP/IP connection.

Author: Shannon McCullough

1333 Connection aborted (10053) Software caused connection abort.

1334 Connection reset (10054) Connection reset by peer.

1335 No buffers available (10055) No buffer space available.

1340 Socket timeout (10060) Connection timed out.

1341 Connection refused (10061) Connection refused.

1343 Name too long (10063) Item Name too long.

1344 Host down (10064) Host is down.

1345 Host unreachable (10065) No route to host.