Circuit Protection Devices - Eurogrideurogrid.in/wp-content/uploads/2017/08/Circuit... · IS / IEC...

5
CIRCUIT PROTECTION DEVICES

Transcript of Circuit Protection Devices - Eurogrideurogrid.in/wp-content/uploads/2017/08/Circuit... · IS / IEC...

Page 1: Circuit Protection Devices - Eurogrideurogrid.in/wp-content/uploads/2017/08/Circuit... · IS / IEC 60947 - 3 40 - 63 240/415 50 1P, R2P, 3P, 4P** AC 22 A 690 4 10000-5 to + 55 25

CIRCUITPROTECTIONDEVICES

Page 2: Circuit Protection Devices - Eurogrideurogrid.in/wp-content/uploads/2017/08/Circuit... · IS / IEC 60947 - 3 40 - 63 240/415 50 1P, R2P, 3P, 4P** AC 22 A 690 4 10000-5 to + 55 25

CIRCUIT PROTECTION DEVICESMINIATURE CIRCUIT BREAKER

Precise hammer action Low power consumption, thus cost effective and energy saving 12 plates Arc Chute for effective arc quenching Trip free mechanism Longer electric life Wide range availability Pull up terminals

RANGE:0.5A to 63A – ‘B & C’ Curve

EXECUTION:Single pole (1P), Single pole & Neutral (1P+N), Double pole (2P)Three pole (3P), Three pole & Neutral (3P+N), Four pole (4P)

CURRENT RATINGS (A)0.5, 1, 2, 3, 4, 5, 6, 8, 10, 13, 16, 20,25, 32, 40, 50, 63

FEATURES:

AV~

Hz

kA

VkV

°C

mm2g

Type / SeriesRated Current (In)Rated Voltage (Ue)Rated Frequency (f)No. of Poles (Execution)Rated Short CircuitBreaking CapaciyMagnetic Release Setting (In)Rated Insulation Voltage (Ui)Rated Impulse Voltage (Uimp)Electrical / Mechanical Endurance(No. of operations)32A32AAmbient Working TemperatureTerminal Capacity (max)VibrationShock ResistanceProtection ClassInstallation PositionMountingCase & Cover

B & C0.5 - 63*240/415501P, 1P+N, 2P, 3P, 3P+N, 4P**10(5-10)69042000010000

-5 to + 55

25340mm free fallIP-20Vertical / HorizontalClip on DIN rail (35mm x 7.5mm)Moulded, flame-retardentthermoplastic material

TECHNICAL SPECIFICATIONSABOUT EUROGRIDEurogrid has been serving the electrical industry with a high quality industrial and consumer product range. The brand offers a diversified assemblage of a world class product line that ranges from Circuit Protection Devices, Industrial Switchgear, Fans, Insulation Tapes, Cables, Earthing and Lightning Protection accessories.

With an augmenting use of modern appliances and our passion for innovation, Eurogrid aims at creating eloquent and economically enduring products beautifully packaged to cater to various international markets.

Circut Protection Device02

Page 3: Circuit Protection Devices - Eurogrideurogrid.in/wp-content/uploads/2017/08/Circuit... · IS / IEC 60947 - 3 40 - 63 240/415 50 1P, R2P, 3P, 4P** AC 22 A 690 4 10000-5 to + 55 25

ISOLATOR SWITCHING DEVICES

DESCRIPTION :They are switch disconnectors with independent manual operation, capable of making, carrying and breaking currents under normal circuit conditions, which may includes operating under overload condition and also carry currents under specified abnormal circuit conditions such as those of short circuit for a specified time.

RANGE:40A – 63A & 100A – 125A

EXECUTION:Single pole (1P), Double pole (2P)Three pole (3P) & Four pole (4P)

Low watt lossLonger electric lifeWide rangeValue for moneyLow power consumption, thus cost effective & energy saving

FEATURES:

DESCRIPTION :The flow of current through electrical facilities always invokes risks. Poorly insulated equipment , faulty wires and incorrect use of electrical device cause currents to flow through wrong path (i.e. through the insulation) to the earth. This current is called leakage current. Earth leakage is an electrical hazard and is responsible for electric shocks and fire risk. Earth leakage and its hazards can be prevented by Residual current circuit breaker (RCCB), also popularly known as Earth leakage circuit breaker (ELCB)

EXECUTION:Double pole (2P), Four pole (4P)

RANGE:16A – 63A

RESIDUAL CURRENT CIRCUIT BREAKER

Protection against risk of direct & indirect electric shock and risk of fire Simple and robust operating mechanism Rotary handle with ON/OFF indication in FPDual termination of Bus bar as well as cable connectionAdvance neutralTest button for regular inspectionPositive contact indication

FEATURES:

Standard ConformityRated Current (In)Rated Voltage (Ue)Rated Frequency (f)No. of Poles (Execution)Utilization CategoryRated Insulation Voltage (Ui)Rated Impulse Voltage (Uimp)Electrical / Mechanical Endurance(No. of operations)Ambient Working TemperatureTerminal Capacity (max)VibrationShock ResistanceProtection ClassInstallation PositionMountingCase & Cover

mm 2g

V~Hz

kVV

AIS / IEC 60947 - 340 - 63240/415501P, 2P, 3P, 4P**AC 22 A

690410000

-5 to + 5525540mm free fallIP-20Vertical / HorizontalClip on DIN rail (35mm x 7.5mm)Moulded, flame-retardent thermoplastic material

C

g

2mm

AmAVac

HzV

AkA

Rated Current (In)Sensitivity (In)Rated Voltage (Un)Rated Insulation Voltage (Ui)Rated Frequency (f)Rated Caonditional Short Circuit CapacityResidual Making Breaking CapacityAmbient TemperatureShock Resistance

Vibration ResistanceElectrical / Mechanical Endurance(No. of operations)MountingDegree of ProtectionTerminal Capacity (max)

DP16, 25, 32, 40, 6330, 100, 300240690506

500 A or 10 In whichever is greater-25 to + 5540mm free fall310000

Din Rail (35 mm x 7.5 mm)IP 2025

FP25, 40, 6330, 100, 300415690506

500 A or 10 In whichever is greater-25 to + 5540mm free fall310000

Din Rail (35 mm x 7.5 mm)IP 2025

TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS

Circut Protection Device04

Page 4: Circuit Protection Devices - Eurogrideurogrid.in/wp-content/uploads/2017/08/Circuit... · IS / IEC 60947 - 3 40 - 63 240/415 50 1P, R2P, 3P, 4P** AC 22 A 690 4 10000-5 to + 55 25

RANGE:SPN DB – 6, 8, 12 & 16WTPN DB – 4, 6, 8 & 12W

RAL 7035 (texture)

DESCRIPTION :Super line distribution board is designed to provide a new dimension of protection in homes, offices & industries. It is equipped with stylish colour, elegant curves & distinctive finish that blends with all kinds of interior decor. Super line distribution board offers dual benefits of flexibility & safety , thus enabling safe & efficient distribution of electric power. Super line distribution board a seven-tank phosphate pre-treatment process to ensure anti-rust conditioning, superior finish and lasting strength. Post this process, premium quality powder coating is applied using the state of the art techniques. These boards are also equipped with top and bottom removable gland plates with a number of knockouts. Onus can thus install them either flush or wall mounted. The best designs blend well with the surroundings like our distribution boards. The blended edge make the board look elegant there by complimenting your decor.

SUPER SERIES DISTRIBUTION BOARD

Ultimate protection offered through the metal double door (IP43 degree of protection)Flexibility to open the door from either sides.Pan assembly for ease of installation of MCBs/RCCBsSuitable for the flush and surface mountingAmple spacing for writing to ensure proper distribution of neutral & earth wireShrouded insulated neutral link prevent accidental contact with live parts and makes the board resistant towards shock during fireIP 42

FEATURES:

SPN

TPN

RANGE:TPN – 4, 6, 8 & 12W

COLOUR:RAL 7035(textured)

RANGE:SPN – 4, 6, 8, 12 & 16W

COLOUR:RAL 7035 (textured)

Compact DBs which occupy minimum spaceRaised neutral link for easy wiringSuitable for flush & surface mountingDetachable din bar with end stoppers for easy assembly of breakersSupplied with fully shielded Bus barsLevel marks for providing indication for fitment in wallSupplied with neutral & earth link, top & bottom detachable platesSupplied with masking sheet to protect components from cement during plasteringIP 42

FEATURES:

Suitable for modular as well as non-modular in-comers & modular outgoingTin plated copper Bus bar short circuit withstand-20kA for 0.2sec-17kA for 0.25secFully insulated Bus bar IP 20 in-comer shroudRemovable pan assembly

FEATURES:

Circut Protection Device06

Page 5: Circuit Protection Devices - Eurogrideurogrid.in/wp-content/uploads/2017/08/Circuit... · IS / IEC 60947 - 3 40 - 63 240/415 50 1P, R2P, 3P, 4P** AC 22 A 690 4 10000-5 to + 55 25

+91–22–21021402 / 403+91–22–21020597 / 255

+91–22–21020614

www.eurogrid.in

[email protected]

Eurogrid Industrial Corporation49, Steel Yard House, 5th Floor, Sant Tukaram Road, Lokhand Bazar, Mumbai – 400 009, India