Our energy working for you.™ www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13) Circuit breaker assemblies application guide and option kits Alternator Frame Sizes 2, 3, 4, 5, and YD Description Features Cummins Power Generation circuit breakers are designed to provide a selection of protection methods for over- current and short-current conditions. Our breaker line provides for a wide range of standards with the latest design methods. The range includes dual UL/IEC rated breakers as well as dedicated IEC rated models for International markets. The UL ratings comply with UL489; "Branch Circuit and Service Circuit Breakers" and meet NEMA Standard AB-1. Specs/vendor manuals P-Solid State. LI Sensor Micrologic 3.0 Type F (84%- 100%) (800Amp)/Type E (60%-100%) (1200Amp) Adjusting Plug 0612CT0101R0709 Trip Unit-Section 2, P- Frame-Section 4, Trip Curves-Section 11. Optional P-frame type A (40%-100%) adjusting plug A030H466. Optional P-frame lugs – 800Amp 3/0-600 KCMIL 0332- 4278; 1200Amp 350-600 KCMIL 0332-4279. N-Solid State. LI Sensor STR23SP (40%-100%) 0615CT9901R4-03 Trip Unit-Section 4, Ratings-Section 3. QD-Thermo Magnetic. 0601CT9101R12-03 225/250A Starts on Page 54. Q4-Thermo Magnetic. 0601CT9101R12-03 400 A Frame Starts on Page 78. JG-Thermo-Magnetic. 0611CT0401R05-09 Ratings- Section 1, Wiring Diagrams-Section 4, Trip Curves- Section 6. HG-Thermo-Magnetic. 0611CT0401R05-09 Ratings- Section 1, Wiring Diagrams-Section 4, Trip Curves- Section 6. QOU-Thermo-Magnetic. 0720CT9401R1/05 Ratings- Section 3, Dimensions-Pages 28-31, Trip Curves-Pages 19-27. Enclosure - Sheet steel finished with green epoxy e- coat paint providing a superior all weather finish. Mounting - Mounts directly on either side of the generator set control box and fits within standard skid rails for use with Cummins Power Generation enclosures. Removable panels - Front removable panels provide ease of circuit breaker installation and load cable connection. - Top and bottom panels are for ease of making required conduit holes and provide a vertical adjustment to aid in conduit installation. Conduit - May be run through the top, bottom and side of the enclosure. Connection leads - Generator to breaker, type XLPE insulation, highly flexible, cut-to-length wire. Wire Size varies with circuit breaker amperages. Abbreviations - A = Amperage - Aux = Auxiliary - CSA = Canadian Standards Association - IEC = International Electromechanical Commission - P = Pole - RMS = Root Mean Square - SS = Solid State - TM = Thermal Magnetic - UL = Underwriters Laboratory - V = Volts - VAC = Volts Alternating Current

description

DG

Transcript of Circuit Breaker Assemblies

Page 1: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Circuit breaker assemblies application guide and option kits

Alternator Frame Sizes 2, 3, 4, 5, and YD

Description Features

Cummins Power Generation circuit breakers are designed to provide a selection of protection methods for over-current and short-current conditions. Our breaker line provides for a wide range of standards with the latest design methods. The range includes dual UL/IEC rated breakers as well as dedicated IEC rated models for International markets. The UL ratings comply with UL489; "Branch Circuit and Service Circuit Breakers" and meet NEMA Standard AB-1.

Specs/vendor manuals P-Solid State. LI Sensor Micrologic 3.0 Type F (84%-100%) (800Amp)/Type E (60%-100%) (1200Amp) Adjusting Plug 0612CT0101R0709 Trip Unit-Section 2, P-Frame-Section 4, Trip Curves-Section 11. Optional P-frame type A (40%-100%) adjusting plug A030H466. Optional P-frame lugs – 800Amp 3/0-600 KCMIL 0332-4278; 1200Amp 350-600 KCMIL 0332-4279. N-Solid State. LI Sensor STR23SP (40%-100%) 0615CT9901R4-03 Trip Unit-Section 4, Ratings-Section 3. QD-Thermo Magnetic. 0601CT9101R12-03 225/250A Starts on Page 54. Q4-Thermo Magnetic. 0601CT9101R12-03 400 A Frame Starts on Page 78. JG-Thermo-Magnetic. 0611CT0401R05-09 Ratings-Section 1, Wiring Diagrams-Section 4, Trip Curves-Section 6. HG-Thermo-Magnetic. 0611CT0401R05-09 Ratings-Section 1, Wiring Diagrams-Section 4, Trip Curves-Section 6. QOU-Thermo-Magnetic. 0720CT9401R1/05 Ratings-Section 3, Dimensions-Pages 28-31, Trip Curves-Pages 19-27.

Enclosure - Sheet steel finished with green epoxy e-coat paint providing a superior all weather finish.

Mounting - Mounts directly on either side of the generator set control box and fits within standard skid rails for use with Cummins Power Generation enclosures.

Removable panels

- Front removable panels provide ease of circuit breaker installation and load cable connection.

- Top and bottom panels are for ease of making required conduit holes and provide a vertical adjustment to aid in conduit installation.

Conduit - May be run through the top, bottom and side of the enclosure.

Connection leads - Generator to breaker, type XLPE insulation, highly flexible, cut-to-length wire. Wire Size varies with circuit breaker amperages. Abbreviations - A = Amperage - Aux = Auxiliary - CSA = Canadian Standards Association - IEC = International Electromechanical Commission - P = Pole - RMS = Root Mean Square - SS = Solid State - TM = Thermal Magnetic - UL = Underwriters Laboratory - V = Volts - VAC = Volts Alternating Current

Page 2: Circuit Breaker Assemblies

Our energy working for you.™ www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice.

Frame 2-3 Alternators DGBB/DGBC/DGCA/DGCB/DGCG, DGDB/DGDK, DGFA/DGFB/DGFC/DGFS, DGGD/DGHD/DGHE, DSFAA/DSFAB/DSFAC/DSFAD/DSFAE, DSHAB/DSHAC/DSHAD, GGFD/GGFE, GGHE/GGHF/GGHG/GGHH, GGLA/GGLB Feature Code

Breaker Description (Lugs 0500-3278)

Circuit Breaker

Breaker Model Lead Kit Qty Breaker

Box Kit Inst Sheet

Cup (Ref) (PDC)

Brkr Box Instl (Ref) Shunt Trip Aux Contacts

or Trip Alarm KB17-2 100A,2P,240V,TM,UL 0320-2238-07 QDL22100 0320-2404-01 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KB18-2 125A,2P,240V,TM,UL 0320-2238-06 QDL22125 0320-2404-03 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KB19-2 150A,2P,240V,TM,UL 0320-2238-05 QDL22150 0320-2404-03 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KB20-2 75A,2P,240V,TM,UL 0320-2238-04 QDL22175 0320-2404-03 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KB21-2 200A,2P,240V,TM,UL 0320-2238-03 QDL22200 0320-2404-03 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KB22-2 225A,2P,240V,TM,UL 0320-2238-02 QDL22225 0320-2404-05 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KB23-2 250A,2P,240V,TM,UL 0320-2238-01 QDL22250 0320-2404-05 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KB24-2 300A,2P,240V,TM,UL 0320-1962-03 Q4L2300 0320-2404-07 1 0320-1982 C530 0319-3240 0625-3277-02 NA NA

KB25-2 350A,2P,240V,TM,UL 0320-1962-02 Q4L2350 0320-2404-07 1 0320-1982 C530 0319-3240 0625-3277-02 NA NA

KB26-2 400A,2P,240V,TM,UL 0320-1962-01 Q4L2400 0320-2404-07 1 0320-1982 C530 0319-3240 0625-3277-02 NA NA

KD17-2 100A,3P,240V,TM,UL 0320-2238-14 QDL32100 0300-3991-01 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KD18-2 125A,3P,240V,TM,UL 0320-2238-13 QDL32125 0300-3991-03 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KD19-2 150A,3P,240V,TM,UL 0320-2238-12 QDL32150 0300-3991-03 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KD20-2 175A,3P,240V,TM,UL 0320-2238-11 QDL32175 0300-3991-03 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KD21-2 200A,3P,240V,TM,UL 0320-2238-10 QDL32200 0300-3991-03 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KD22-2 225A,3P,240V,TM,UL 0320-2238-09 QDL32225 0320-2404-06 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KD23-2 250A,3P,240V,TM,UL 0320-2238-08 QDL32250 0320-2404-06 1 0320-1982 C530 0319-5393-02 0625-3277-10 NA NA

KD24-2 300A,3P,240V,TM,UL 0320-1962-06 Q4L3300 0300-3991-03 2 0320-1982 C530 0319-3240 0625-3277-02 NA NA

KD25-2 350A,3P,240V,TM,UL 0320-1962-05 Q4L3350 0300-3991-03 2 0320-1982 C530 0319-3240 0625-3277-02 NA NA

KD26-2 400A,3P,240V,TM,UL 0320-1962-04 Q4L3400 0300-3991-03 2 0320-1982 C530 0319-3240 0625-3277-02 NA NA

KM41-2 300A,3P,600/690V,SS RMS,UL/IEC 0320-1960-06 NJNL36400E20 0300-3991-03 2 0320-1982 C530 0319-3150 0625-3277-05 0320-1981-02 0320-1981-01

KM42-2 350A,3P,600/690V,SS RMS,UL/IEC 0320-1960-05 NJNL36400E20 0300-3991-03 2 0320-1982 C530 0319-3150 0625-3277-05 0320-1981-02 0320-1981-01

KM43-2 400A,3P,600/690V,SS RMS,UL/IEC 0320-1960-04 NJNL36400E20 0300-3991-03 2 0320-1982 C530 0319-3150 0625-3277-05 0320-1981-02 0320-1981-01

KM44-2 450A,3P,600/690V,SS RMS,UL/IEC 0320-1960-03 NJNL36600E20 0300-3991-03 3 0320-1982 C530 0319-3150 0625-3277-05 0320-1981-02 0320-1981-01

KM45-2 500A,3P,600/690V,SS RMS,UL/IEC 0320-1960-02 NJNL36600E20 0300-3991-03 3 0320-1982 C530 0319-3150 0625-3277-05 0320-1981-02 0320-1981-01

KM46-2 600A,3P,600/690V,SS RMS,UL/IEC 0320-1960-01 NJNL36600E20 0300-3991-03 3 0320-1982 C530 0319-3150 0625-3277-05 0320-1981-02 0320-1981-01

KM58-2 320A,4P,750V,SS RMS,IEC 0320-1960-10 NJNL46400E20 0320-2404-10 1 0320-1982 C530 0319-3150 0625-3277-06 0320-1981-02 0320-1981-01

KM59-2 400A,4P,750V,SS RMS,IEC 0320-1960-09 NJNL46400E20 0320-2404-10 1 0320-1982 C530 0319-3150 0625-3277-06 0320-1981-02 0320-1981-01

KM60-2 500A,4P,750V,SS RMS,IEC 0320-1960-08 NJNL46630E20 0320-2404-11 1 0320-1982 C530 0319-3150 0625-3277-06 0320-1981-02 0320-1981-01

KM61-2 630A,4P,750V,SS RMS,IEC 0320-1960-07 NJNL46630E20 0320-2404-11 1 0320-1982 C530 0319-3150 0625-3277-06 0320-1981-02 0320-1981-01

Page 3: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Frame 2-3 Alternators DGBB/DGBC/DGCA/DGCB/DGCG, DGDB/DGDK, DGFA/DGFB/DGFC/DGFS, DGGD/DGHD/DGHE, DSFAA/DSFAB/DSFAC/DSFAD/DSFAE, DSHAB/DSHAC/DSHAD, GGFD/GGFE, GGHE/GGHF/GGHG/GGHH, GGLA/GGLB (cont) Feature Code

Breaker Description (Lugs 0500-3278)

Circuit Breaker

Breaker Model Lead Kit Qty Breaker

Box Kit Inst Sheet

Cup (Ref) (PDC)

Brkr Box Instl (Ref) Shunt Trip Aux Contacts

or Trip Alarm KS44-2 1200A,3P,600/415V,UL/IEC 0320-2262-02 PJL36120U31E 0320-2404-13 1 0320-1983-01 C530 0319-3134 0625-3275-05 0320-2196-03 0320-2196-01

KS45-2 800A,3P,600/415V,UL/IEC 0320-2261-02 PJL36080U31F 0320-2404-12 1 0320-1983-01 C530 0319-3150 0625-3275-05 0320-2196-03 0320-2196-01

KS59-2 250A,3P,600/525V,TM,UL/IEC 0320-2347-01 JGL36250 0320-2404-06 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS60-2 225A,3P,600/525V,TM,UL/IEC 0320-2347-02 JGL36225 0320-2404-06 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS61-2 200A,3P,600/525V,TM,UL/IEC 0320-2347-03 JGL36200 0300-3991-03 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS62-2 175A,3P,600/525V,TM,UL/IEC 0320-2347-04 JGL36175 0300-3991-03 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS63-2 150A,3P,600/525V,TM,UL/IEC 0320-2346-05 HGL36150 0300-3991-03 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS64-2 125A,3P,600/525V,TM,UL/IEC 0320-2346-06 HGL36125 0300-3991-03 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS65-2 100A,3P,600/525V,TM,UL/IEC 0320-2346-07 HGL36100 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS66-2 90A,3P,600/525V,TM,UL/IEC 0320-2346-08 HGL36090 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS67-2 80A,3P,690/525V,TM,UL/IEC 0320-2346-09 HGL36080 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS68-2 70A,3P,600/525V,TM,UL/IEC 0320-2346-10 HGL36070 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS69-2 60A,3P,600/525V,TM,UL/IEC 0320-2346-17 HGL36060 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS70-2 50A,3P,600/525V,TM,UL/IEC 0320-2346-18 HGL36050 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS71-2 40A,3P,600/525V,TM,UL/IEC 0320-2346-19 HGL36040 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS72-2 30A,3P,600/525V,TM,UL/IEC 0320-2346-20 HGL36030 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS73-2 20A,3P,600/525V,TM,UL/IEC 0320-2346-21 HGL36020 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

KS74-2 15A,3P,600/525V,TM,UL/IEC 0320-2346-22 HGL36015 0300-3991-01 1 0320-1982 C530 0319-3242 0625-3277-03 0320-1981-02 0320-1981-01

Page 4: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Frame 2-3 Alternators DSGAA/DSGAB/DSGAC Feature Code Breaker Description

(Lugs 0500-4668) Circuit Breaker

Breaker Model Lead Kit Qty Breaker

Box Kit Inst Sheet

Cup (Ref) (PDC)

Brkr Box Instl (Ref) Shunt Trip

Aux Contacts or Trip Alarm

KS94-2,KS95-2 40A,3P,600VAC,UL 0320-2346-19 HGL36040 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT04-2,KT05-2 50A,3P,600VAC,UL 0320-2346-18 HGL36050 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT20-2,KT21-2 100A,2P,240VAC,UL 0320-2238-07 QDL22100 0320-2424-01 1 0179-5028-12 0179-5028 0319-6577-02 0179-5028-05 NA NA

KT22-2,KT23-2 100A,3P,240VAC,UL 0320-2238-14 QDL32100 0320-2424-02 1 0179-5028-11 0179-5028 0319-6576-02 0179-5028-04 NA NA

KT24-2,KT25-2 125A,2P,240VAC,UL 0320-2238-06 QDL22125 0320-2424-01 1 0179-5028-12 0179-5028 0319-6577-02 0179-5028-05 NA NA

KT26-2,KT27-2 125A,3P,240VAC,UL 0320-2238-13 QDL32125 0320-2424-02 1 0179-5028-11 0179-5028 0319-6576-02 0179-5028-04 NA NA

KT28-2,KT29-2 150A,2P,240VAC,UL 0320-2238-05 QDL22150 0320-2424-01 1 0179-5028-12 0179-5028 0319-6577-02 0179-5028-05 NA NA

KT30-2,KT31-2 150A,3P,240VAC,UL 0320-2238-12 QDL32150 0320-2424-02 1 0179-5028-11 0179-5028 0319-6576-02 0179-5028-04 NA NA

KT32-2,KT33-2 175A,2P,240VAC,UL 0320-2238-04 QDL22175 0320-2424-01 1 0179-5028-12 0179-5028 0319-6577-02 0179-5028-05 NA NA

KT34-2,KT35.2 175A,3P,240VAC,UL 0320-2238-11 QDL32175 0320-2424-02 1 0179-5028-11 0179-5028 0319-6576-02 0179-5028-04 NA NA

KT36-2,KT37-2 200A,2P,240VAC,UL 0320-2238-03 QDL22200 0320-2424-03 1 0179-5028-12 0179-5028 0319-6577-02 0179-5028-05 NA NA

KT38-2,KT39-2 225A,2P,240VAC,UL 0320-2238-02 QDL22225 0320-2424-03 1 0179-5028-12 0179-5028 0319-6577-02 0179-5028-05 NA NA

KT58-2,KT59-2 60A,3P,600/525V,TM,UL 0320-2346-17 HGL36060 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT60-2,KT61-2 70A,3P,600/525V,TM,UL 0320-2346-10 HGL36070 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT62-2,KT63-2 80A,3P,600/525V,TM,UL 0320-2346-09 HGL36080 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT64-2,KT65-2 90A,3P,600/525V,TM,UL 0320-2346-08 HGL36090 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT66-2,KT67-2 100A,3P,600/525V,TM,U 0320-2346-07 HGL36100 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT68-2,KT69-2 125A,3P,600/525V,TM,U 0320-2346-06 HGL36125 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT70-2,KT71-2 150A,3P,600/525V,TM,,UL 0320-2346-05 HGL36150 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT72-2,KT73-2 175A,3P,600/525V,TM,UL 0320-2347-04 JGL36175 0320-2424-02 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT74-2,KT75-2 200A,3P,600/525V,TM,UL 0320-2347-03 JGL36200 0320-2424-04 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT76-2,KT77-2 200A,3P,240V,TM,UL 0320-2238-10 QDL32200 0320-2424-04 1 0179-5028-11 0179-5028 0319-6576-02 0179-5028-04 NA NA

KT78-2,KT79-2 225A,3P,600/525V,TM,UL 0320-2347-02 JGL36225 0320-2424-04 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT80-2,KT81-2 225A,3P,240V,TM,UL 0320-2238-09 QDL32225 0320-2424-04 1 0179-5028-11 0179-5028 0319-6576-02 0179-5028-04 NA NA

KT82-2,KT83-2 250A,3P,600/525V,TM,UL 0320-2347-01 JGL36250 0320-2424-04 1 0179-5028-10 0179-5028 0319-6316-02 0179-5028-03 0320-1981-02 0320-1981-01

KT84-2,KT85-2 250A,2P,240V,TM,UL 0320-2238-01 QDL22250 0320-2424-03 1 0179-5028-12 0179-5028 0319-6577-02 0179-5028-05 NA NA

KT86-2,KT87-2 250A,3P,240V,TM,UL 0320-2238-08 QDL32250 0320-2424-04 1 0179-5028-11 0179-5028 0319-6576-02 0179-5028-04 NA NA

KT88-2,KT89-2 300A,2P,240V,TM,UL 0320-1962-03 Q4L2300 0320-2424-05 1 0179-5028-13 0179-5028 0319-6578-02 0179-5028-06 NA NA

KT90-2,KT91-2 300A,3P,240V,TM,UL 0320-1962-06 Q4L3300 0320-2424-06 1 0179-5028-13 0179-5028 0319-6578-02 0179-5028-06 NA NA

KT92-2,KT93-2 300A,3P,600/690V,RMS 0320-1960-06 NJNL36400 0320-2424-06 1 0179-5028-09 0179-5028 0319-6304-02 0179-5028-02 0320-1981-02 0320-1981-01

KT94-2,KT95-2 350A,2P,240V,TM,UL 0320-1962-02 Q4L2350 0320-2424-05 1 0179-5028-13 0179-5028 0319-6578-02 0179-5028-06 NA NA

KT96-2,KT97-2 350A,3P,240V,TM,UL 0320-1962-05 Q4L3350 0320-2424-06 1 0179-5028-13 0179-5028 0319-6578-02 0179-5028-06 NA NA

Page 5: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Frame 2-3 Alternators DSGAA/DSGAB/DSGAC (cont)

Feature Code Breaker Description (Lugs 0500-4668)

Circuit Breaker

Breaker Model Lead Kit Qty Breaker

Box Kit Inst Sheet

Cup (Ref) (PDC)

Brkr Box Instl (Ref) Shunt Trip

Aux Contacts or Trip Alarm

KT98-2,KT99-2 350A,3P,600/690V,SS 0320-1960-05 NJNL36400E20 0320-2424-06 1 0179-5028-09 0179-5028 0319-6304-02 0179-5028-02 0320-1981-02 0320-1981-01

KU02-2,KU03-2 400A,2P,240V,TM,UL 0320-1962-01 Q4L2400 0320-2424-05 1 0179-5028-13 0179-5028 0319-6578-02 0179-5028-06 NA NA

KU04-2,KU05-2 400A,3P,240V,TM,UL 0320-1962-04 Q4L3400 0320-2424-06 1 0179-5028-13 0179-5028 0319-6578-02 0179-5028-06 NA NA

KU06-2,KU07-2 400A,3P,600/690V,SS 0320-1960-04 NJNL36400E20 0320-2424-06 1 0179-5028-09 0179-5028 0319-6304-02 0179-5028-02 NA NA

KU08-2,KU09-2 450A,3P,600/690V,SS 0320-1960-03 NJNL36600E20 0320-2424-07 1 0179-5028-09 0179-5028 0319-6304-02 0179-5028-02 0320-1981-02 0320-1981-01

KU10-2,KU11-2 500A,3P,600/690V,SS 0320-1960-02 NJNL36600E20 0320-2424-07 1 0179-5028-09 0179-5028 0319-6304-02 0179-5028-02 0320-1981-02 0320-1981-01

KU12-2,KU13-2 600A,3P,600/690V,SS 0320-1960-01 NJNL36600E20 0320-2424-07 1 0179-5028-09 0179-5028 0319-6304-02 0179-5028-02 0320-1981-02 0320-1981-01

KU14-2,KU15-2 800A,3P,600/415V,SS 0320-2261-02 PJL36080U31F 0320-2424-08 1 0179-5028-08 0179-5028 0319-6651-02 0179-5028-01 0320-2196-03 0320-2196-01

KU16-2,KU17-2 1200A,3P,600/415V,SS 0320-2262-02 PJL36120U31E 0320-2424-09 1 0179-5028-08 0179-5028 0319-6651-02 0179-5028-01 0320-2196-03 0320-2196-01

Page 6: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Frame 4-5 Alternators DFCB/DFCC/DFCE, DFEG/DFEH/DFEJ/DFEK, DQDAA/DQDAB/DQDAC, DQHAA/DQHAB Feature Code

Breaker Description (Lugs 0500-3279/0500-3744 100%)

Circuit Breaker Breaker Model Lead Kit Qty Breaker

Box Kit Inst Sheet

Cup (Ref) (PDC)

Brkr Box Instl (Ref) Shunt Trip

Aux Contacts or Trip Alarm

KM41-2 300A,3P,600/690V,SS RMS,UL/IEC 0320-1960-06 NJNL36400E20 0320-2405-03 1 0320-1995-01 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01

KM42-2 350A,3P,600/690V,SS RMS,UL/IE/C 0320-1960-05 NJNL36400E20 0320-2405-03 1 0320-1995-01 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01

KM43-2 400A,3P,UL 600,IEC 690 0320-1960-04 NJNL36400E20 0320-2405-03 1 0320-1995-01 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01

KM44-2 450A,3P,600/690V,SS RMS,UL/IEC 0320-1960-03 NJNL36600E20 0320-2405-04 1 0320-1995-01 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01

KM45-2 500A,3P,600/690V,SS RMS,UL/IEC 0320-1960-02 NJNL36600E20 0320-2405-04 1 0320-1995-01 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01

KM46-2 600A,3P, UL 600,IEC 690 0320-1960-01 NJNL36600E20 0320-2405-04 1 0320-1995-01 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01

KM58-2 320A,4P,750V,SS RMS,IEC 0320-1960-10 NJNLE46400E20 0320-2405-05 1 0320-1995-01 G543 0319-2431-31 0625-3463-05 0320-1981-03 0320-1981-01

KM59-2 400A,4P,750V,SS RMS,IEC 0320-1960-09 NJNLE46400E20 0320-2405-05 1 0320-1995-01 G543 0319-2431-31 0625-3463-05 0320-1981-03 0320-1981-01

KM60-2 500A,4P,750V,SS RMS,IEC 0320-1960-08 NJNLE46630E20 0320-2405-06 1 0320-1995-01 G543 0319-2431-31 0625-3463-05 0320-1981-03 0320-1981-01

KM61-2 630A,4P,750V,SS RMS, IEC 0320-1960-07 NJNLE46630E20 0320-2405-06 1 0320-1995-01 G543 0319-2431-31 0625-3463-05 0320-1981-03 0320-1981-01

KS29-2# 1200A,3-Pole,UL 600,IEC 415, 100% 0320-2183-01 PJP36120U31E NA 1 NA NA NA NA 0320-2196-02 0320-2196-01

KS30-2# 800A,3-Pole, UL 600, IEC 415, 100% 0320-2182-01 PJP36080U31F NA 1 NA NA NA NA 0320-2196-02 0320-2196-01

KS31-2# 600A,3-Pole, UL 600, IEC 690, 100% 0320-1960-01 NJNL36600E20 NA 1 NA NA NA NA 0320-1981-03 0320-1981-01

KS32-2# 400A,3-Pole, UL 600, IEC 690, 100% 0320-1960-04 NJNL36400E20 NA 1 NA NA NA NA 0320-1981-03 0320-1981-01

KS44-2 1200A,3-Pole,UL 600,IEC 415 0320-2262-02 PJL36120U31E 0320-2405-08 1 0320-1995-01 G543 0319-2431-37 0625-3463-10 0320-2196-02 0320-2196-01

KS45-2 800A,3P,UL 600,IEC 415 0320-2261-02 PJL36080U31F 0320-2405-04 1 0320-1995-01 G543 0319-2431-37 0625-3463-10 0320-2196-02 0320-2196-01 # Contact accessories with model spec and serial number of generator set as these are used on our Thor packages

Page 7: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Frame 5 Alternators DFGB/DFGE

Feature Code

Breaker Description (Lugs 0500-3279)

Circuit Breaker Breaker Model Lead Kit Qty Breaker

Box Kit Inst Sheet

Cup (Ref) (PDC)

Brkr Box Instl (Ref) Shunt Trip

Aux Contacts or Trip Alarm

KR76-2 1200A,Right,3P,UL 600,IEC 415 0320-2262-02 PJL36120U31E 0320-2405-08 1 0320-1995 G543 0319-2431-37 0625-3463-10 0320-2196-02 0320-2196-01

KR77-2 800A,Left,3P,UL 600,IEC 415 0320-2261-02 PJL36080U31F 0320-2405-04 1 0320-1995 G543 0319-2431-37 0625-3463-10 0320-2196-02 0320-2196-01

KS27-2 600A,Left,3P, UL 600,IEC 690 0320-1960-01 NJNL36600E20 0226-4768-25* 1 0320-1995 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01

KS28-2 400A,Right,3P,UL 600,IEC 690 0320-1960-04 NJNL36400E20 0226-4768-26* 1 0320-1995 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01

KS39-2 1200A,Left,3P,UL 600,IEC 415 0320-2262-02 PJL36120U31E 0320-2405-08 1 0320-1995 G543 0319-2431-37 0625-3463-10 0320-2196-02 0320-2196-01

KS40-2 800A,Right,3P,UL 600,IEC 415 0320-2261-02 PJL36080U31F 0320-2405-04 1 0320-1995 G543 0319-2431-37 0625-3463-10 0320-2196-02 0320-2196-01

KS41-2 400A,Left,3P,UL 600,IEC 690 0320-1960-04 NJNL36400E20 0226-4768-25* 1 0320-1995 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01

KS42-2 600A,Right,3P, UL 600,IEC 690 0320-1960-01 NJNL36600E20 0226-4768-26* 1 0320-1995 G543 0319-2431-31 0625-3463-04 0320-1981-03 0320-1981-01 * Order Components Through Parts In Memphis

Page 8: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Frame YD Alternators DSKAA/DSKAB/DSKBA/DSKCA

Feature Code

Breaker Description (Lugs 0500-4935)

Circuit Breaker

Breaker Model Leads (PDC) Qty Breaker

Box Kit Inst Sheet Cup (Ref) (PDC)

Brkr Box Instl (Ref) Shunt Trip

Aux Contacts or Trip Alarm

KS80-2 15A,Right,3P,600VAC,UL 0320-2346-22 HGL36015 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

KS84-2 20A,Right,3P,600VAC,UL 0320-2346-21 HGL36020 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

KS88-2 30A,Right,3P,600VAC,UL 0320-2346-20 HGL36030 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

KS90-2 40A,Right,2P,240VAC,UL 0320-2005-05 QOU240 0226-4645-02 2 Std on Gen 0179-5663 0319-7107-02 0179-5663-02 NA NA

KS94-2 40A,Right,3P,600VAC,UL 0320-2346-19 HGL36040 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

KS96-2 45A,Right,2P,240VAC,UL 0320-2005-04 QOU245 0226-4645-02 2 Std on Gen 0179-5663 0319-7107-02 0179-5663-02 NA NA

KS98-2 50A,Right,2P,240VAC,UL 0320-2005-03 QOU250 0226-4645-02 2 Std on Gen 0179-5663 0319-7107-02 0179-5663-02 NA NA

KT04-2 50A,Right,3P,600VAC,UL 0320-2346-18 HGL36050 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

KT06-2 60A,Right,2P,240VAC,UL 0320-2005-02 QOU260 0226-4645-02 2 Std on Gen 0179-5663 0319-7107-02 0179-5663-02 NA NA

KT10-2 70A,Right,2P,240VAC,UL 0320-2005-01 QOU270 0226-4645-02 2 Std on Gen 0179-5663 0319-7107-02 0179-5663-02 NA NA

KT14-2 80A,Right,2P,240VAC,UL 0320-2006-04 QOU280 0226-4645-02 2 Std on Gen 0179-5663 0319-7107-02 0179-5663-03 NA NA

KT18-2 90A,Right,2P,240VAC,UL 0320-2006-03 QOU290 0226-4645-02 2 Std on Gen 0179-5663 0319-7107-02 0179-5663-03 NA NA

KT20-2 100A,Right,2P,240VAC,UL 0320-2006-02 QOU2100 0226-4645-02 2 Std on Gen 0179-5663 0319-7107-02 0179-5663-03 NA NA

KT22-2 100A,Right,3P,240VAC,UL 0320-2238-14 QDL32100 0226-4645 3 Std on Gen 0179-5608 0319-7051-02 0179-5608-01 NA NA

KT24-2 125A,Right,2P,240VAC,UL 0320-2238-06 QDL22125 0226-4645 2 Std on Gen 0179-5608 0319-7100-02 0179-5608-02 NA NA

KT26-2 125A,Right,3P,240VAC,UL 0320-2238-13 QDL32125 0226-4645 3 Std on Gen 0179-5608 0319-7051-02 0179-5608-01 NA NA

KT28-2 150A,Right,2P,240VAC,UL 0320-2238-05 QDL22150 0226-4645 2 Std on Gen 0179-5608 0319-7100-02 0179-5608-02 NA NA

KT58-2 60A,Right,3P,600/525V,TM,UL/IEC 0320-2346-17 HGL36060 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

KT60-2 70A,Right,3P,600/525V,TM,UL/IEC 0320-2346-10 HGL36070 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

KT62-2 80A,Right,3P,600/525V,TM,UL/IEC 0320-2346-09 HGL36080 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

KT64-2 90A,Right,3P,600/525V,TM,UL/IEC 0320-2346-08 HGL36090 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

KU29-2 25A,Right,3P,600VAC,UL 0320-2346-26 HGL36025 0226-4645-02 3 Std on Gen 0179-5607 0319-7051-02 0179-5607 0320-1981-02 0320-1981-01

Page 9: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Frame YD Alternators GGMA/GGMB/GGMC

Feature Code

Breaker Description (Lugs 0500-4518)

Circuit Breaker

Circuit Brkr Model

Leads & Qty 0226-4971-0X (PDC)

Breaker Box Kit* Inst Sheet Breaker

Bracket Brkr Box Top Panel

Brkr Box Instl (Ref)

-1 -2 -3 -4 KS80-2,KS81-2 15A,Left,3P,600VAC,UL 0320-2346-22 HGL36015 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02 KS84-2,KS85-2 20A,Left,3P,600VAC,UL 0320-2346-21 HGL36020 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02 KS88-2,KS89-2 30A,Left,3P,600VAC,UL 0320-2346-20 HGL36030 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02 KS90-2,KS91-2 40A,Left,2P,240VAC,UL 0320-2005-05 QOU240 2 1 0179-4806-07 0179-4806 0319-6870-02 0319-6147-12 0179-4806-08 KS94-2,KS95-2 40A,Left,3P,600VAC,UL 0320-2346-19 HGL36040 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02

KS96-2,KS97-2 45A,Left,2P,240VAC,UL 0320-2005-04 QOU245 2 1 0179-4806-07 0179-4806 0319-6870-02 0319-6147-12 0179-4806-08

KS98-2,KS99-2 50A,Left,2P,240VAC,UL 0320-2005-03 QOU250 2 1 0179-4806-07 0179-4806 0319-6870-02 0319-6147-12 0179-4806-08 KT04-2,KT05-2 50A,Left,3P,600VAC,UL 0320-2346-18 HGL36050 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02 KT06-2,KT07-2 60A,Left,2P,240VAC,UL 0320-2005-02 QOU260 2 1 0179-4806-07 0179-4806 0319-6870-02 0319-6147-12 0179-4806-08

KT10-2,KT11-2 70A,Left,2P,240VAC,UL 0320-2005-01 QOU270 2 1 0179-4806-07 0179-4806 0319-6870-02 0319-6147-12 0179-4806-08 KT14-2,KT15-2 80A,Left,2P,240VAC,UL 0320-2006-04 QOU280 2 1 0179-4806-07 0179-4806 0319-6870-02 0319-6147-12 0179-4806-05 KT18-2,KT19-2 90A,Left,2P,240VAC,UL 0320-2006-03 QOU290 2 1 0179-4806-07 0179-4806 0319-6870-02 0319-6147-12 0179-4806-05

KT20-2,KT21-2 100A,Left,2P,240VAC,UL 0320-2238-07 QDL22100 4 2 0179-4806-07 0179-4806 0319-6152-02 0319-6147-07 0179-4806-06 KT22-2,KT23-2 100A,Left,3P,240VAC,UL 0320-2238-14 QDL32100 6 2 0179-4806-07 0179-4806 0319-6152-02 0319-6147-07 0179-4806-04

KT24-2,KT25-2 125A,Left,2P,240VAC,UL 0320-2238-06 QDL22125 4 2 0179-4806-07 0179-4806 0319-6152-02 0319-6147-07 0179-4806-06

KT26-2,KT27-2 125A,Left,3P,240VAC,UL 0320-2238-13 QDL32125 6 2 0179-4806-07 0179-4806 0319-6152-02 0319-6147-07 0179-4806-04 KT28-2,KT29-2 150A,Left,2P,240VAC,UL 0320-2238-05 QDL22150 4 2 0179-4806-07 0179-4806 0319-6152-02 0319-6147-07 0179-4806-06 KT30-2,KT31-2 150A,Left,3P,240VAC,UL 0320-2238-12 QDL32150 6 2 0179-4806-07 0179-4806 0319-6152-02 0319-6147-07 0179-4806-04

KT32-2,KT33-2 175A,Left,2P,240VAC,UL 0320-2238-04 QDL22175 4 2 0179-4806-07 0179-4806 0319-6152-02 0319-6147-07 0179-4806-06 KT58-2,KT59-2 60A,Left,3P,600/525V,TM,UL/IEC 0320-2346-17 HGL36060 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02 KT60-2,KT61-2 70A,Left,3P,600/525V,TM,UL/IEC 0320-2346-10 HGL36070 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02

KT62-2,KT63-2 80A,Left,3P,600/525V,TM,UL/IEC 0320-2346-09 HGL36080 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02 KT64-2,KT65-2 90A,Left,3P,600/525V,TM,UL/IEC 0320-2346-08 HGL36090 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02

KU29-2,KU30-2 25A,Left,3P,600VAC,UL 0320-2346-26 HGL36025 3 1 0179-4806-07 0179-4806 0319-6323-02 0319-6147-06 0179-4806-02

* 0179-4806-07 Breaker box kit is only required when adding a breaker and box to the side of the genset without a breaker and box. It also includes leads.

Page 10: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description

KB17-2 An Underwriters Laboratory (UL) listed, 100 amp, 2 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KB18-2 An Underwriters Laboratory (UL) listed, 125 amp, 2 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KB19-2 An Underwriters Laboratory (UL) listed, 150 amp, 2 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KB20-2 An Underwriters Laboratory (UL) listed, 175 amp, 2 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KB21-2 An Underwriters Laboratory (UL) listed, 200 amp, 2 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes

KB22-2 An Underwriters Laboratory (UL) listed, 225 amp, 2 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KB23-2 An Underwriters Laboratory (UL) listed, 250 amp, 2 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KB24-2 An Underwriters Laboratory (UL) listed, 300 amp, 2 pole, in a 400 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KB25-2 An Underwriters Laboratory (UL) listed, 350 amp, 2 pole, in a 400 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KB26-2 An Underwriters Laboratory (UL) listed, 400 amp, 2 pole, in a 400 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

Page 11: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description (cont)

KD18-2 An Underwriters Laboratory (UL) listed, 125 amp, 3 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KD19-2 An Underwriters Laboratory (UL) listed, 150 amp, 3 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KD20-2 An Underwriters Laboratory (UL) listed, 175 amp, 3 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KD21-2 An Underwriters Laboratory (UL) listed, 200 amp, 3 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KD22-2 An Underwriters Laboratory (UL) listed, 225 amp, 3 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KD23-2 An Underwriters Laboratory (UL) listed, 250 amp, 3 pole, in a 250 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KD24-2 An Underwriters Laboratory (UL) listed, 300 amp, 3 pole, in a 400 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes

KD25-2 An Underwriters Laboratory (UL) listed, 350 amp, 3 pole, in a 400 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KD26-2 An Underwriters Laboratory (UL) listed, 400 amp, 3 pole, in a 400 amp frame, 240 volt maximum, thermal magnetic, fixed instantaneous trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

Page 12: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description (cont)

KM41-2 An Underwriters Laboratory (UL)/ International Electrotechnical Commission (IEC) listed, 300 amp, 3 pole, in a 400 amp frame, 600/690 volt maximum, RMS electronic trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KM42-2 An Underwriters Laboratory (UL)/ International Electrotechnical Commission (IEC) listed, 350 amp, 3 pole, in a 400 amp frame, 600/690 volt maximum, RMS electronic trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes

KM43-2 The unit includes a UL listed, CSA certified, IEC rated, 400 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 160 to 400 Amperes. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. IEC rating is 690Vac. UL/CSA interrupting ratings are: 65kA at 240Vac, 35kA at 480Vac, and 18kA at 600Vac

KM44-2 An Underwriters Laboratory (UL)/ International Electrotechnical Commission (IEC) listed, 450 amp, 3 pole, in a 600 amp frame, 600/690 volt maximum, RMS electronic trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KM45-2 An Underwriters Laboratory (UL)/ International Electrotechnical Commission (IEC) listed, 500 amp, 3 pole, in a 600 amp frame, 600/690 volt maximum, RMS electronic trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KM46-2 The unit includes a UL listed, CSA certified, IEC rated, 600 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 240 to 600 Amperes. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. IEC rating is 690Vac. The UL/CSA interrupting ratings are: 65kA at 240Vac, 35kA at 480Vac, and 18kA at 600Vac.

KM58-2 An International Electrotechnical Commission (IEC) 320 amp, 4 pole, in a 400 amp frame, 750 volt maximum, RMS electronic trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes

KM59-2 An International Electrotechnical Commission (IEC)400 amp, 4 pole, in a 400 amp frame, 750 volt maximum, RMS electronic trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KM60-2 An International Electrotechnical Commission (IEC) 500 amp, 4 pole, in a 630 amp frame, 750 volt maximum, RMS electronic trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KM61-2 An International Electrotechnical Commission (IEC) 630 amp, 4 pole, in a 630 amp frame, 750 volt maximum, RMS electronic trip, molded case circuit breaker is mounted on the generator set. Breaker is rated 80% on a continuous basis as installed on the generator set. See Circuit Breaker Outline drawing for mounting location and conduit, wire and lug sizes.

KR76-2 The unit includes a UL listed, CSA certified, IEC rated, 1200 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset right side when viewed from the alternator end. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 720 to 1200 Amperes. Long time pickup, long time delay and instantaneous pickup are adjustable. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. UL/CSA (60 Hz) interrupting ratings are 100kA @ 240Vac, 65kA @ 480Vac, 25kA @ 600Vac. IEC (50/60 Hz) interrupting rating are 65kA Icu/35kA Ics @ 240Vac, 50kA Icu/25kA Ics @ 380/415 Vac.

KR77-2 The unit includes a UL listed, CSA certified, IEC rated, 800 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset left side when viewed from the alternator end. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 672 to 800 Amperes. Long time pickup, long time delay and instantaneous pickup are adjustable. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. UL/CSA (60 Hz) interrupting ratings are 100kA @ 240 Vac, 65kA @ 480Vac, 25kA @ 600 Vac. IEC (50/60 Hz) interrupting rating are 65kA Icu/35kA Ics @ 240Vac, 50kA Icu/25kA Ics @ 380/415 Vac.

Page 13: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description (cont)

KS27-2 The unit includes a UL listed, CSA certified, IEC rated, 600 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset left side when viewed from the alternator end. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 240 to 600 Amperes. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. IEC rating is 690Vac. The UL/CSA interrupting ratings are: 65kA at 240Vac, 35kA at 480Vac, and 18kA at 600Vac.

KS28-2 The unit includes a UL listed, CSA certified, IEC rated, 400 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset right side when viewed from the alternator end. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 160 to 400 Amperes. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. IEC rating is 690Vac. UL/CSA interrupting ratings are: 65kA at 240Vac, 35kA at 480Vac, and 18kA at 600Vac

KS29-2 The unit includes a UL listed, CSA certified, IEC rated, 1200 ampere frame, 3-pole, molded case circuit breaker mounted on the set. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 720 to 1200 amperes. Long time pickup, long time delay and instantaneous pickup are adjustable. The circuit breaker is UL listed at 100% of the frame rating for continuous duty. UL/CSA (60 Hz) interrupting ratings are 100kA @ 240 Vac, 65kA @ 480 Vac, 25kA @ 600 Vac. IEC (50/60 Hz) interrupting rating are 65kA Icu / 35kA Ics @ 240 Vac, 50kA Icu / 25kA Ics @ 380/415 Vac.

KS30-2 The unit includes a UL listed, CSA certified, IEC rated, 800 Ampere frame, 3-pole, molded case circuit breaker mounted on the set. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 672 to 800 amperes. Long time pickup, long time delay and instantaneous pickup are adjustable. The circuit breaker is UL listed at 100% of the frame rating for continuous duty. UL/CSA (60 Hz) interrupting ratings are 100kA @ 240Vac, 65kA at 240Vac, 65kA at 480Vac, and 25kA at 600Vac

KS31-2 The unit includes a UL listed, CSA certified, IEC rated, 600 ampere frame, 3-pole, molded case circuit breaker mounted on the set. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 240 to 600 amperes. The circuit breaker is UL listed at 100% of the frame rating for continuous duty. The IEC rating is 690Vac. The UL/CSA interrupting ratings are: 65kA at 240Vac, 35kA at 480Vac, and 18kA at 600Vac.

KS32-2 The unit includes a UL listed, CSA certified, IEC rated, 400 ampere frame, 3-pole, molded case circuit breaker mounted on the set. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 160to 400 amperes. The circuit breaker is UL listed at 100% of the frame rating for continuous duty. The IEC rating is 690Vac. The UL/CSA interrupting ratings are: 65kA at 240Vac, 35kA at 480Vac, and 18kA at 600Vac.

KS39-2 The unit includes a UL listed, CSA certified, IEC rated, 1200 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset left side when viewed from the alternator end. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 720 to 1200 Amperes. Long time pickup, long time delay and instantaneous pickup are adjustable. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. UL/CSA (60 Hz) interrupting ratings are 100kA @ 240Vac, 65kA @ 480Vac, 25kA @ 600Vac. IEC (50/60 Hz) interrupting rating are 65kA Icu/35kA Ics @ 240Vac, 50kA Icu/25kA Ics @ 380/415 Vac.

KS40-2 The unit includes a UL listed, CSA certified, IEC rated, 800 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset right side when viewed from the alternator end. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 672 to 800 Amperes. Long time pickup, long time delay and instantaneous pickup are adjustable. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. UL/CSA (60 Hz) interrupting ratings are 100kA @ 240 Vac, 65kA @ 480Vac, 25kA @ 600 Vac. IEC (50/60 Hz) interrupting rating are 65kA Icu/35kA Ics @ 240Vac, 50kA Icu/25kA Ics @ 380/415 Vac.

KS41-2 The unit includes a UL listed, CSA certified, IEC rated, 400 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset left side when viewed from the alternator end. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 160 to 400 Amperes. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. IEC rating is 690Vac. UL/CSA interrupting ratings are: 65kA at 240Vac, 35kA at 480Vac, and 18kA at 600Vac.

KS42-2 The unit includes a UL listed, CSA certified, IEC rated, 600 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset right side when viewed from the alternator end. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 240 to 600 Amperes. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. IEC rating is 690Vac. The UL/CSA interrupting ratings are: 65kA at 240Vac, 35kA at 480Vac, and 18kA at 600Vac.

KS44-2 The unit includes a UL listed, CSA certified, IEC rated, 1200 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 720 to 1200 Amperes. Long time pickup, long time delay and instantaneous pickup are adjustable. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. UL/CSA (60 Hz) interrupting ratings are 100kA @ 240Vac, 65kA @ 480Vac, 25kA @ 600Vac. IEC (50/60 Hz) interrupting ratings are 65kA Icu/35kA Ics @ 240Vac, 50kA Icu/25kA Ics @ 380/415 Vac.

KS45-2 The unit includes a UL listed, CSA certified, IEC rated, 800 Ampere frame, 3-pole, molded case circuit breaker mounted on the genset. The circuit breaker has a true RMS, adjustable, electronic, solid-state trip unit with a range of 672 to 800 Amperes. Long time pickup, long time delay and instantaneous pickup are adjustable. The circuit breaker is UL listed at 80% of the frame rating for continuous duty. UL/CSA (60 Hz) interrupting ratings are 100kA @ 240 Vac, 65kA @ 480Vac, 25kA @ 600 Vac. IEC (50/60 Hz) interrupting rating are 65kA Icu/35kA @ 240Vac, 50kA Icu/25kA Ics @ 380/415 Vac.

Page 14: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description (cont)

KS59-2 250 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS60-2 225 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS61-2 200 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS62-2 175 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS63-2 150 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS64-2 125 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS65-2 100 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS66-2 90 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS67-2 80 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS68-2 70 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS69-2 60 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS70-2 50 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS71-2 40 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS72-2 30 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS73-2 20 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS74-2 15 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker. UL listed, at 80% duty for up to 600 Volts. IEC standards for rated operational voltage up to 525 Volts AC.

KS80-2 15 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 600 Volts AC.

KS84-2 20 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 600 Volts AC.

KS88-2 30 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 600 Volts AC.

KS90-2 40 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KS94-2 40 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 600 Volts AC.

KS95-2 40 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 600 Volts AC.

KS96-2 45 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KS98-2 50 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

Page 15: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description (cont)

KT04-2 50 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 600 Volts AC.

KT05-2 50 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 600 Volts AC.

KT06-2 60 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT10-2 70 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT14-2 80 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT18-2 90 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT20-2 100 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT21-2 100 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT22-2 100 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT23-2 100 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT24-2 125 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT25-2 125 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT26-2 125 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT27-2 125 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT28-2 150 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT29-2 150 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT30-2 150 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

Page 16: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description (cont)

KT31-2 150 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT32-2 175 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT33-2 175 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT34-2 175 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT35-2 175 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT36-2 200 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT37-2 200 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT38-2 225 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT39-2 225 Ampere, 2-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the left side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 240 Volts AC.

KT58-2 60 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT59-2 60 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT60-2 70Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT61-2 70 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT62-2 80 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT63-2 80 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT64-2 90 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT65-2 90 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT66-2 100 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

Page 17: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description (cont)

KT67-2 100 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT68-2 125 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT69-2 125 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT70-2 150 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT71-2 150 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT72-2 175 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end

KT73-2 175 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT74-2 200 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT75-2 200 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT76-2 200 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT77-2 200 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT78-2 225 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT79-2 225 Ampere 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC.Mounted on the left side of the generator set as viewed from the alternator end.

KT80-2 225 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240V VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT81-2 225 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT82-2 250 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

Page 18: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description (cont)

KT83-2 250 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 525 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT84-2 250 Ampere, 2-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT85-2 250 Ampere, 2-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT86-2 250 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT87-2 250 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT88-2 300 Ampere, 2-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT89-2 300 Ampere, 2-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT90-2 300 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT91-2 300 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT92-2 300 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT93-2 300 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT94-2 350 Ampere, 2-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT95-2 350 Ampere, 2-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT96-2 350 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT97-2 350 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KT98-2 350 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KT99-2 350 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

Page 19: Circuit Breaker Assemblies

Our energy working for you.™

www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Feature Code Description (cont)

KU02-2 400 Ampere, 2-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KU03-2 400 Ampere, 2-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KU04-2 400 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KU05-2 400 Ampere, 3-Pole, molded case, thermal-magnetic trip circuit breaker, UL listed at 80% duty for rated operational voltage up to 240 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KU06-2 400 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KU07-2 400 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KU08-2 450 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KU09-2 450 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KU10-2 500 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KU11-2 500 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KU12-2 600 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the right side of the generator set as viewed from the alternator end.

KU13-2 600 Ampere, 3-Pole, molded case, solid state true RMS electronic trip circuit breaker, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 690 VAC. Mounted on the left side of the generator set as viewed from the alternator end.

KU14-2 800 Ampere, 3-Pole, molded case, solid state true RMS adjustable electronic trip circuit breaker with a range of 672 to 800 Amperes, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 415 VAC. Mounted on the right side of the generator as veiwed from the alternator end.

KU15-2 800 Ampere, 3-Pole, molded case, solid state true RMS adjustable electronic trip circuit breaker with a range of 672 to 800 Amperes, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 415 VAC. Mounted on the left side of the generator as viewed from the alternator end.

KU16-2 1200 Ampere, 3-Pole, molded case, solid state true RMS adjustable electronic trip circuit breaker with a range of 720 to 1200 Amperes, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 415 VAC. Mounted on the right side of the generator as viewed from the alternator end.

KU17-2 1200 Ampere, 30Pole, molded case, solid state true RMS adjustable electronic trip circuit breaker with a range of 720 to 1200 Amperes, UL listed at 80% duty for up to 600 Volts, IEC standards for rated operational voltage up to 415 VAC. Mounted on the left side of the generator as viewed from the alternator end.

KU29-2 25 Ampere, 3-pole, molded case, thermal-magnetic trip, line circuit breaker is mounted on the right side when viewed from the alternator end of the generator set. The circuit breaker is UL listed at 80% duty for 600 Volts AC.

Page 20: Circuit Breaker Assemblies

Our energy working for you.™ www.cumminspower.com 2013 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. “Our energy working for you.” is a trademark of Cummins Power Generation. Specifications are subject to change without notice. AC-122f (2/13)

Americas 1400 73rd Avenue N.E. Minneapolis, MN 55432 USA Phone: 763 574 5000 Fax: 763 574 5298

Europe, CIS, Middle East and Africa Manston Park Columbus Ave. Manston Ramsgate Kent CT 12 5BF United Kingdom Phone 44 1843 255000 Fax 44 1843 255902

Asia Pacific 10 Toh Guan Road #07-01 TT International Tradepark Singapore 608838 Phone 65 6417 2388 Fax 65 6417 2399

Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect generator sets to any building electrical system except through an approved device or after building main switch is open.

Warning: For professional use only. Must be installed by a qualified service technician. Improper installation presents hazards of electrical shock and improper operation, resulting in severe personal injury and/or property damage.