Johnson Controls, Inc. —
CHILLERS WITH LOW-GWP REFRIGERANTS
Fortaleza / 30 March 2016 Eric ColinJohnson Controls, Inc.
Johnson Controls, Inc. 2
Terms & Definitions: RefrigerantsGlobal Warming Potential (GWP)Total energy a gas absorbs over a time period (usually 100 years) compared to carbon dioxide
Low-GWP refrigerantNo uniform definition, but implications of proposed regulations suggest 675-750 GWP range is acceptable based on a number of R-410A alternatives such as R-32. These include natural refrigerants, a number of blends and HFOs.
Hydrofluoro-Olefin (HFO) refrigerantChemical compounds composed of hydrogen, fluorine and carbon ( GWP < 150)
HFO/HFC blends refrigerantBlends of HFOs with HFCs, most commonly R-32 or R-134a, targeted for drop-in and retrofit applications for performance closely matching HFCs, but with reduced GWP < 750.
Natural refrigerantA fluid readily found in nature, but can also be produced with low-GWP. Examples include CO2, ammonia, and hydrocarbons (propane, isobutene, etc.)
Mildly flammableA new class of less flammable refrigerants with a designation of 2L per ASHRAE 34. These are considered difficult to ignite and sustain a flame.
2
Johnson Controls, Inc. 3
Terms & Definitions: Types of chiller systems
Air-cooled� Equipment resides outdoors
� Location on the roof, or on a concrete foundation
� Limited to no direct exposure of refrigerant into building air stream
Water-cooled� Equipment resides indoors in equipment room
� Direct exposure to building air stream
- R134a, R-410A, and R-22 most common.
- Flammable and non-flammable Refrigerant options are being proposed.
- Flammability will affect both indoor and outdoor equipment, but more significantly impact water-cooled products.
Johnson Controls, Inc. 4
100%
90%
65%
33%
3%0% 0%
65%
25%
10%
1% 0%0%
20%
40%
60%
80%
100%
1980 1990 2000 2010 2020 2030 2040 2050
% o
f bas
elin
e
Developing Countries Developed Countries
Eliminate 100%
The mandated HCFC phase-out is proceeding per plan and will prohibit new equipment using R-22 and R-123 globally
Source: U.S. EPA
R-22 phase-out for high ambient applications was a significant challenge for industry and the regions affected. R-410A was not ideal for high ambient and acceptance was limited.
3
Johnson Controls, Inc. 5
Support for an HFC phase-down is growing, and there is convergence leading to a possible global agreement.
0%
20%
40%
60%
80%
100%
2015 2020 2025 2030 2035 2040 2045 2050
% o
f bas
elin
eHFC Phase-Down Proposals
India North America Micronesia European Union
Actions already underway targeting mobile AC & commercial refrigeration which account for 65% or more of the total emissions
Johnson Controls, Inc. 6
Absence of an international agreement is making a transition more complex than in the past
� Asia plays a much greater role in the use and development of key products such as chillers and VRF.
� Regions with hot climates have not generally accepted R-410A, and are holding out with R-22 in the absence of a viable high ambient solution
1987
Developed countries
Developing countries
2014
TIBET
QINGH
AI
Refrigerant manufacturer location
4
Johnson Controls, Inc. 7
The optimal refrigerant choice will vary by application
Low
er p
ress
ure
Med
ium
pre
ssur
e
High temp heat pump
High ambient radiated
Air-cooled condenser
Evaporative-cooled
Water-cooled
Data center
Chilled beam
Comfort cooling
Ice thermal storage
Low-temp brine
Air source heat pump
Hig
her
pres
sure
Climate and application driven designs for heat rejection or heat re-use
Type of cooling needed for comfort or process
Ideal application range will vary by refrigerant
Johnson Controls, Inc. 8
Refrigerant emissions are complicated by a wide variety of end uses across multiple industries.
8
Source: U.S. EPA
(i.e. R410A) (i.e. R134a, R1234yf) (i.e. R123, R245fa)
5
Johnson Controls, Inc. 9
� Challenges to be addressed:� Energy efficiency� Funding requirements� Safety of substitutes� Availability of technologies� Performance and challenges in high ambient temperatures� Second and third conversions� Capacity building� Nonparty trade provisions� Synergies with the UNFCCC (legal, financial aspects)� Relationship with the HCFC phase out� Ecological effects� Implications for human health� Social implications� National policy implications� Challenges to the production sector� Rates of penetration of new alternatives� Exemptions and ways to address lack of alternatives� Technology transfer
According to the Montreal Protocol working group, many factors need to be addressed for a full transition from HFCs can happen.
Excerpt: 2015 April 22-24, Montreal Protocol, OEWG Meeting, Bangkok, Thailand
Johnson Controls, Inc. 10
A viable alternative for R-22 is lacking for high ambient applications
Ambient Temperature
°C °F
AHRI 35.0 95.0
Eurovent 35.0 95.0
Hot 52.0 125.6
Extreme 55.0 131.0
6
Johnson Controls, Inc. 11
There are multiple alternatives targeted at replacing R-410A, but no perfect solutions…all have some degree of flammability
Johnson Controls, Inc. 12
There are multiple alternatives targeted at replacing R-134a, but no perfect solutions
7
Johnson Controls, Inc. 13
Natural refrigerants sound like a great solution, but also come with challenges or barriers to entry (or limitations) into commercial markets
R-717(Ammonia)
R-290(Propane)
R-718(Water)
� Good efficiency� Toxicity an issue
for widespread adoption
� Good efficiency� Highly flammable
� Great when using waste energy
� Higher cost� Technology stigma
Johnson Controls, Inc. 14
ODP vs. GWP vs. efficiency vs. safety vs. reliability vs. cost vs. availability vs…..
� Complex choices with no perfect answers
� Trade-offs between low GWP and safety(where flammability is not accepted, applied, or allowed)
� Trade-offs between low GWP and efficiency(unintended consequences of MORE greenhouse gas emissions!)
� Trade-offs between low GWP and product cost(acceptable performance at what cost?)
� A more robust dialog is needed about the real obstacles for low GWP
8
Johnson Controls, Inc. 15
� ASHRAE and ISO have added the mildly flammable refrigerant classification define as flammable, but difficult to ignite and sustain a flame.
15
Flammable refrigerant classifications have been revised to include a mildly flammable classification 2L.
A3
A2
A1
B3
B2
B1
Higher
Refrigerant safety groups
Higher
Lower
No flame propagation
Lower Higher
Fla
mm
abili
ty
Toxicity
A3
A2
A1
B3
B1
Refrigerant safety groups
A2L
B2
B2L
Higher
Lower
No flame propagation
Difficult to ignite & sustain
Lower Higher
Fla
mm
abili
ty
ToxicityA2L: R32, R1234yf, R1234zeB2L: R717
Historically, refrigerants with level 2 or 3 flammability are not permitted or seldom used (where permitted) in commercial applications.
Johnson Controls, Inc. 16
Safety implications for product design, operation and service
� Flammability� Flammability has significant implications on cost, product configuration, and risk for the
manufacturer
� Compliance to regional equipment room and product safety codes:
� Adaptation of wiring, electronics, electrical connections, motors and drives
� Ventilation requirements, safeties, and leak detection for the room and/or equipment
� Liability risk for equipment that we may not maintain
� Implication to Service� Training of technicians on safe use flammable refrigerants.
� Cost of additional equipment and compliance with transportation regulations.
� Regional variation in technician capability and requirements
� Pressure:� Pressure vessel code requirements become a cost driver as the design working
pressure of the refrigerant increases.
� Material compatibility� Oils, materials of construction, etc. to reduce risk of flammable or higher toxicity
refrigerant leakage
9
Johnson Controls, Inc. 17
Building codes & construction practices must be updated & enforced before flammable refrigerants can be used safely in commercial applications.
17
State/Local Gov’t
Local adoption of building codes
LawLocal adoption of
building codes
EnforcementLocal adoption of
building codes
EnforcementLocal adoption of
building codes
UMC, IBCBuilding codes
IBC, GB, CEBuilding codes
ASHRAE 34Refrigerant Safety
Classification
ISO 817GB/T 7778
Refrigerant Safety Classification
ASHRAE 15Safe design, construction, installation &
operation
ISO 5149GB 9237
Design, construction, installation &
operation
Johnson Controls, Inc. —18
� Energy Efficiency Directive (2012/27/EU)� Driving efficiency, leading to reduce waist energy & retrofit buildings� Major impulse due to 3% of governments buildings be renovated each year.� Requires market / government needs compliant contro ls (i.e. B-AWS).
Key Directives In Europe
Energy and Climate related directives in Europe and their impact
EPBD� Energy Performance of Buildings Directive (2010/31/EU)� nZEB* mandatory by Jan. 2019 (public), Jan. 2021 (others)� Driving Efficiency in Buildings, leading to for exa mple smaller more efficient chillers..� … as well as increasing number of controls (OEM) and with higher complexity.
ECODESIGN� Eco-Design Directive (2009/125/EC)� Ban for products below minimum seasonal energy efficiency levels (non CE mark)� Driving efficiency requirements focus on part load efficiency, requiring better controls
FGAS� F-Gas regulation (517/2014)
� Phase down for HFCs used in HVAC (Chillers). Baseline 2015, -79% by 2030
RES� Renewable Energy Sources Directive (2009/28/EC)� Recognize heat pumps as renewable source, if technology meets minimum efficiency requirements.� Driving growth for Heat Pumps
EED
10
Johnson Controls, Inc. —19
� CE marking for Chillers will now include the new Eco-Design Directive (2009/125/EC) that sets out the Minimum Efficiency Performance Standards : MEPS.
� Sets new Minimum standard of Efficiency that must be reached to enable “CE” Certification.
� Units with efficiency below target cannot be sold.
� The building regulations will push for highest possible chiller efficiency, above the MEPS.
� The standards focus off design efficiency replacing ESEER with SCOP (Seasonal coefficient of Performance [H.P.]) - SEPR (Seasonal Efficiency Process Ratio) - SEER. Seasonal Energy Efficiency Ratio).
What is Eco-design
Key Directives In Europe
ECODESIGN
Johnson Controls, Inc. 20
Agriculture, power production, waste and deforestation are key contributors to global greenhouse gas emissions
Chillers use f-gases
Chillers use energy
11
Johnson Controls, Inc. 21
Chillers are a small fraction of the overall greenhouse gas emissions from the mobile & stationary HVAC&R industries
Source: US EPA, Global Mitigation of Non-CO2 Greenhouse gases: 2010-2030. September 2013, EPA-430-R-13-011
Small unitary AC 31%
Large retail food 31%
Motor vehicles 16%
Refrigerated transport 8% Cold storage 6%
Large unitary AC 2%
Medium retail food 2%
Small retail food 1%
Window units & dehumidifiers 1%
PTAC/PTHP <1%
Positive displacement chillers <1%
Centrifugal chillers 1%
Household refrigerators 1%
<2%
Johnson Controls, Inc. 22
Equipment and technology advancements are needed to optimize chillers for low-GWP alternatives or risk an increa se in net CO2 emissions by consuming more energy
� Sources of greenhouse gas emissions from chillers
� Indirect – from power generated by burning fossil fuels� Inefficient equipment
� Poor maintenance
� Incorrect charge
� Lack of controls and optimization
� Misapplication
� Direct – from emissions of refrigerant� Leaks left unrepaired
� Accidental release during servicing
� Refrigerant not properly reclaimed at end of life
Indirect are as high as 95% over the life
of the equipment
12
Johnson Controls, Inc. 23
Refrigerant performance comparison for screw chillers
� R-513A drop-in yields a little extra capacity, but at lower efficiency
� R-1234ze drop-in loses significant capacity. Heat exchangers are oversized and mask efficiency loss.
� Adjusting for equal capacity (all units have same cost basis)
� R-134a provides the best efficiency
Drop-in Adjusted for equal capacity (customer spec)
Capacity Efficiency Capacity Efficiency
R-134a 100 1.00 100 1.00
R-513A 102 0.98 100 0.95
R-1234ze 75 1.00 100 0.91
Johnson Controls, Inc. 24
Efficiency has a much greater impact on emissions than refrigerant GWP
� Total equivalent warming impact (TEWI) provides a net impact of performance including refrigerant emissions and energy consumption
� Energy efficiency is the most effective means of reducing greenhouse gas emissions from chiller products
� R-134a provides best life cycle climate performance with the lowest greenhouse gas emissions of all four refrigerants due to its high efficiency
Emissions due to GWP <2%
Average 98% emissions
due to energy
Assumptions: Air-cooled screw chiller, 5.15 COP, 0 .4 kg CO2/kWh, 15 year chiller life, 2% leak rate, 90% recla im
13
Johnson Controls, Inc. 25
R-134a Low-GWP alternative performance line-up
Larger compressor
Larg
er h
eat
exch
ange
rs
Johnson Controls, Inc. 26
First cost premium for low-GWP is significant vs. current HFC offering for the same customer specifications
Smaller premium realized when able to stay within a model family size range
Refrigerant drives selection into larger equipment for the same specified performance
14
Johnson Controls, Inc. 27
� Many of the new HFO base molecules are being sold in adjacent sectors (foam and automotive).
� Many of the medium and high pressure alternatives are mixtures of existing HFCs with HFOs.
� HFOs will always be some multiple of current HFC prices because they are more complex molecules that require additional production steps to produce.
Low GWP refrigerant options remain expensive compared to today’s refrigerants
Life-cycle cost and environmental performance are essential
� Concerns about climate change are driving creating uncertainty and
confusion in the industry.
� Lacking an international agreement, regional regulations are emerging.
� Higher emitting applications are targeted for some specific bans
(i.e. commercial refrigeration and mobile AC).
� Industry is evaluating potential alternatives to the most common
refrigerants, R22, R404A, R410A and R134a.
� Availability, safety, efficiency, cost and reliability present challenges for
low-GWP refrigerants to become viable solutions.
� Industry must address impact of mildly flammable refrigerants.
� Energy efficiency has the greatest impact on HVAC greenhouse gas
emissions and cost of ownership.