    DC Inverter Split Air-Condition Unit

    SERVICE MANUAL

  • 7/22/2019 Chigo Inverters Manual

    2/52

    - 1 -

    Table of Contents

    1. The model and the air conditioning unit parameters...........................................................1

    2. Units operating working conditions and temperature range ............................................8

    3. Units characteristic..................................................................................................................11

    4. Indoor and outdoor units size ...............................................................................................26

    5. Indoor and outdoor unit explosion diagram and spare parts list .....................................30

    6. The analysis of indoor malfunction code ............................................................................35

    7. The analysis of the complete units malfunction code.........................................................50

  • 7/22/2019 Chigo Inverters Manual

    3/52

    - 2 -

    1The model and the air conditioning unit parameters1.1 the model.

  • 7/22/2019 Chigo Inverters Manual

    4/52

    - 3 -

    1.2. The air conditioners parameter.

  • 7/22/2019 Chigo Inverters Manual

    5/52

    - 4 -

  • 7/22/2019 Chigo Inverters Manual

    6/52

    - 5 -

  • 7/22/2019 Chigo Inverters Manual

    7/52

    - 6 -

  • 7/22/2019 Chigo Inverters Manual

    8/52

    - 7 -

  • 7/22/2019 Chigo Inverters Manual

    9/52

    - 8 -

  • 7/22/2019 Chigo Inverters Manual

    10/52

    - 9 -

  • 7/22/2019 Chigo Inverters Manual

    11/52

    - 10 -

    2 RATING CONDITIONS and Operating Limits

    2.1 RATING CONDITIONS

    Standard conditions in accordance with ISO 5151, and EN 14511.

    Cooling:

    Indoor: 27 DB 19 WB

    Outdoor:35DB 24 WB

    Heating:

    Indoor: 20 DB 15 WB

    Outdoor: 7 DB 6 WB

    2.2 Operat ing Limits

    Outdoor

    Upper limit (DB) 46Cooling

    Lower limit (DB) 5

    Upper limit (DB) 24Heating

    Lower limit (DB) -15

    Voltage 1PH 220-240V

  • 7/22/2019 Chigo Inverters Manual

    12/52

    - 11 -

    3 Units characteristic R410a

    Low noise level

    Wide operating range with outdoor air temperatures, cooling:5-46,heating:-15-24

    High efficiency and energy saving Air filters easy to remove and clean

    Twin rotary compressor

    Auto-restart after a power supply blackout

    Single-phase power supply thanks to DC inverter technology low consumption

    Dynamic refrigerant control by DC inverter compressor and circuit, electronic valve and fuzzy logic

    managed by a powerful micro program

    EEV for each indoor unit

  • 7/22/2019 Chigo Inverters Manual

    13/52

    - 12 -

  • 7/22/2019 Chigo Inverters Manual

    14/52

    - 13 -

    The compressors energy consumption graph .

    COP (W/W)/2ND

    The compressors condensing pressure graph .

  • 7/22/2019 Chigo Inverters Manual

    15/52

    - 14 -

    Indoor Units Data

    Indoor Units Capacity For 2.0KW

    Capacity Model

    2.0KW CMV-V20G3A-M75/81/84/85/87/88/95/96

    Cooling Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed

    INDOOR ENTERING AIR DB/WB TEMPERATURE [0C]

    OUTDOOR

    ENTERING AIR DB

    TEMPERATURE

    [0C] DATA 22/15 24/17 27/19 29/21 32/23

    TC 80 - 110 % of nominal

    SC 80 - 105 % of nominal

    -10 - 20

    (protection range) PI 25 - 50 % of nominal

    TC 1.94 2.06 2.18 2.32 2.44

    SC 1.72 1.75 1.79 1.82 1.8525

    PI 0.49 0.50 0.51 0.51 0.53

    TC 1.84 1.96 2.10 2.22 2.34

    SC 1.67 1.70 1.75 1.79 1.8230

    PI 0.55 0.55 0.56 0.57 0.58

    TC 1.74 1.88 2.00 2.12 2.26

    SC 1.63 1.67 1.70 1.73 1.7735

    PI 0.60 0.61 0.62 0.63 0.64

    TC 1.66 1.78 1.90 2.04 2.16

    SC 1.58 1.62 1.65 1.70 1.7340PI 0.66 0.67 0.68 0.69 0.69

    TC 1.54 1.66 1.80 1.92 2.04

    SC 1.53 1.56 1.60 1.63 1.6846

    PI 0.73 0.74 0.74 0.76 0.76

    Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed

    ID COIL ENTERING AIR DB TEMPERATURE [0C]

    OD COIL

    ENTERING

    AIR DB/WB

    TEM PERATU RE

    [0C]

    DATA 15 20 25

    -15/-16 TC 1.54 1.42 1.32

    PI 0.40 0.44 0.48

    -10/-12 TC 1.70 1.58 1.49

    PI 0.48 0.52 0.57

    -7/-8 TC 1.82 1.73 1.61

    PI 0.55 0.59 0.63

    -1/-2 TC 1.90 1.80 1.68

    PI 0.58 0.62 0.66

    2/1 TC 1.94 1.82 1.73

  • 7/22/2019 Chigo Inverters Manual

    16/52

    - 15 -

    PI 0.60 0.64 0.68

    7/6 TC 2.50 2.40 2.30

    PI 0.63 0.67 0.71

    10/9 TC 2.64 2.54 2.42

    PI 0.67 0.71 0.75

    15/12 TC 2.78 2.69 2.57

    PI 0.70 0.74 0.78

    1524 TC 85 - 105 % of nominal(Protection Range) PI 80 - 120 % of nominal

    Capacity Correction Factors

    Cooling Capacity Ratio Vs. Outdoor Temperature

    Cooling Capacity Correction Factor

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    25 30 35 40 45

    Outdoor Temperature (deg C)

    Capacity

    Ratio

    32/23

    29/27

    27/19

    24/17

    22/15

    Heating Capacity Ratio Vs. Outdoor Temperature

    Heating Capacity Correction Factor

    0

    0.2

    0.4

    0.6

    0.8

    11.2

    1.4

    -15 -10 -5 0 5 10 15 20

    Outdoor Temperature (deg C)

    Capacity

    Ratio

    15

    20

    25

  • 7/22/2019 Chigo Inverters Manual

    17/52

    - 16 -

    Indoor Units Capacity For 2.5KW

    Capacity Model

    2.5KW CMV-V25G3A-M75/81/84/85/87/88/95/96

    Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed

    INDOOR ENTERING AIR DB/WB TEMPERATURE [0C]

    OUTDOOR

    ENTERING AIR DB

    TEMPERATURE

    [0C] DATA 22/15 24/17 27/19 29/21 32/23

    TC 80 - 110 % of nominal

    -10 - 20 SC 80 - 105 % of nominal

    (protection range) PI 25 - 50 % of nominal

    TC 2.42 2.57 2.73 2.89 3.05

    25 SC 1.72 1.75 1.79 1.82 1.86

    PI 0.58 0.59 0.60 0.61 0.62TC 2.30 2.46 2.62 2.77 2.93

    30 SC 1.67 1.71 1.74 1.78 1.81

    PI 0.65 0.66 0.67 0.68 0.69

    TC 2.18 2.34 2.50 2.66 2.82

    35 SC 1.63 1.66 1.70 1.74 1.77

    PI 0.71 0.72 0.74 0.75 0.76

    TC 2.07 2.23 2.38 2.54 2.70

    40 SC 1.59 1.62 1.66 1.69 1.73

    PI 0.78 0.79 0.80 0.81 0.82

    TC 1.93 2.09 2.24 2.40 2.56

    46 SC 1.53 1.57 1.60 1.64 1.67

    PI 0.86 0.87 0.88 0.89 0.91

    Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed

    ID COIL ENTERING AIR DB TEMPERATURE [0C]

    OD COIL

    ENTERING

    AIR DB/WB

    TEM PERATU RE

    [0C]

    DATA 15 20 25

    -15/-16 TC 1.92 1.77 1.65

    PI 0.49 0.54 0.59

    -10/-12 TC 2.13 1.98 1.86

    PI 0.59 0.64 0.70

    -7/-8 TC 2.28 2.16 2.01

    PI 0.67 0.72 0.77

    -1/-2 TC 2.37 2.25 2.10

    PI 0.71 0.75 0.80

    2/1 TC 2.43 2.28 2.16

    PI 0.73 0.78 0.83

  • 7/22/2019 Chigo Inverters Manual

    18/52

    - 17 -

    7/6 TC 3.12 3.00 2.88

    PI 0.77 0.82 0.87

    10/9 TC 3.30 3.18 3.03

    PI 0.82 0.87 0.92

    15/12TC

    3.48 3.36 3.21PI 0.86 0.90 0.96

    15-24 TC 85 - 105 % of nominal

    (Protection Range) PI 80 - 120 % of nominal

    L E G E N D

    TC Total Cooling Capacity, kW

    SC Sensible Capacity, Kw

    PI Power Input, kW

    WB Wet Bulb Temp., (

    o

    C)DB Dry Bulb Temp., (oC)

    ID Indoor

    OD Outdoor

    Capacity Correction Factors

    Cooling Capacity Ratio Vs. Outdoor Temperature

    Cooling Capacity Correction Factor

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    25 30 35 40 45Outdoor Temperature (deg C)

    Capacity

    Ratio

    32/23

    29/27

    27/19

    24/17

    22/15

  • 7/22/2019 Chigo Inverters Manual

    19/52

    - 18 -

    Heating Capacity Ratio Vs. Outdoor Temperature

    Heating Capacity Correction Factor

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    -15 -10 -5 0 5 10 15 20

    Outdoor Temperature (deg C)

    Capacity

    Ratio

    15

    20

    25

    Indoor Units Capacity For 3.5KW

    Indoor Units Capacity For 3.5KW

    Capacity Model

    CMV-V35G3A-M75/81/84/85/87/88/95/963.5KW

    CMV-V35G3A-P84/94/98

    Cooling Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed

    INDOOR ENTERING AIR DB/WB TEMPERATURE [0C]

    OUTDOOR

    ENTERING AIR DB

    TEMPERATURE

    [0C] DATA 22/15 24/17 27/19 29/21 32/23

    TC 80 - 110 % of nominal

    -10 - 20 SC 80 - 105 % of nominal

    (protection range) PI 25 - 50 % of nominal

    TC 3.40 3.61 3.82 4.06 4.2725 SC 3.03 3.09 3.15 3.21 3.27

    PI 0.86 0.87 0.89 0.90 0.93TC 3.22 3.43 3.68 3.89 4.10

    30 SC 2.94 3.00 3.09 3.15 3.21PI 0.96 0.97 0.99 1.00 1.02

    TC 3.05 3.29 3.50 3.71 3.96

    35 SC 2.88 2.94 3.00 3.06 3.12

    PI 1.06 1.08 1.09 1.11 1.12

    TC 2.91 3.12 3.33 3.57 3.78

    40 SC 2.79 2.85 2.91 3.00 3.06

    PI 1.16 1.18 1.19 1.21 1.22

    TC 2.70 2.91 3.15 3.36 3.5746 SC 2.70 2.76 2.82 2.88 2.97

    PI 1.28 1.30 1.31 1.33 1.34

  • 7/22/2019 Chigo Inverters Manual

    20/52

    - 19 -

    Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed

    ID COIL ENTERING AIR DB TEMPERATURE [0C]

    OD COIL

    ENTERING

    AIR DB/WB

    TEM PERATU RE

    [0C]

    DATA 15 20 25

    -15/-16 TC 2.56 2.36 2.20

    PI 0.67 0.73 0.80

    -10/-12 TC 2.84 2.64 2.48

    PI 0.80 0.87 0.94

    -7/-8 TC 3.04 2.88 2.68

    PI 0.91 0.98 1.04

    -1/-2 TC 3.16 3.00 2.80

    PI 0.95 1.02 1.09

    2/1 TC 3.24 3.04 2.88

    PI 0.99 1.05 1.12

    7/6 TC 4.16 4.00 3.84

    PI 1.04 1.11 1.18

    10/9 TC 4.40 4.24 4.04

    PI 1.11 1.18 1.24

    15/12 TC 4.64 4.48 4.28

    PI 1.17 1.23 1.301524 TC 85 - 105 % of nominal

    (Protection Range) PI 80 - 120 % of nominal

    Capacity Correction Factors

    Cooling Capacity Ratio Vs. Outdoor Temperature

    Cooling Capacity Correction Factor

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.21.4

    25 30 35 40 45

    Outdoor Temperature (deg C)

    Capacity

    Ratio

    32/23

    29/27

    27/19

    24/17

    22/15

  • 7/22/2019 Chigo Inverters Manual

    21/52

    - 20 -

    Heating Capacity Ratio Vs. Outdoor Temperature

    Heating Capacity Correction Factor

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    -15 -10 -5 0 5 10 15 20Outdoor Temperature (deg C)

    Capacity

    Ratio

    15

    20

    25

    Indoor Units Capacity For 5.0KW

    Capacity Model

    5.0KW CMV-V50G3A-P75/81/84/85/87/88/95/96

    Cooling Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed

    INDOOR ENTERING AIR DB/WB TEMPERATURE [0C]

    OUTDOOR

    ENTERING AIR DB

    TEMPERATURE

    [0C] DATA 22/15 24/17 27/19 29/21 32/23

    TC 80 - 110 % of nominal

    -10 - 20 SC 80 - 105 % of nominal

    (protection range) PI 25 - 50 % of nominal

    TC 4.85 5.15 5.45 5.80 6.1025 SC 4.55 4.64 4.73 4.82 4.91

    PI 1.23 1.25 1.28 1.29 1.33TC 4.60 4.90 5.25 5.55 5.85

    30 SC 4.41 4.50 4.64 4.73 4.82PI 1.37 1.39 1.42 1.44 1.47

    TC 4.35 4.70 5.00 5.30 5.65

    35 SC 4.32 4.41 4.50 4.59 4.68

    PI 1.51 1.54 1.56 1.59 1.61

    TC 4.15 4.45 4.75 5.10 5.40

    40 SC 4.19 4.28 4.37 4.50 4.59

    PI 1.65 1.68 1.70 1.73 1.75TC 3.85 4.15 4.50 4.80 5.10

    46 SC 4.05 4.14 4.23 4.32 4.46PI 1.83 1.86 1.87 1.90 1.92

  • 7/22/2019 Chigo Inverters Manual

    22/52

    - 21 -

    Heating Capacity (KW)---Run Model (Unit A,B,C or D),220-240V,Indoor fan at high speed

    ID COIL ENTERING AIR DB TEMPERATURE [0C]

    OD COIL

    ENTERING

    AIR DB/WB

    TEM PERATU RE

    [0C]

    DATA 15 20 25

    -15/-16 TC 3.71 3.42 3.19

    PI 0.97 1.06 1.16

    -10/-12 TC 4.12 3.83 3.60

    PI 1.16 1.26 1.37

    -7/-8 TC 4.41 4.18 3.89

    PI 1.32 1.42 1.51-1/-2 TC 4.58 4.35 4.06

    PI 1.38 1.48 1.58

    2/1 TC 4.70 4.41 4.18

    PI 1.43 1.53 1.63

    7/6 TC 6.03 5.80 5.57

    PI 1.51 1.61 1.71

    10/9 TC 6.38 6.15 5.86

    PI 1.61 1.71 1.80

    15/12 TC 6.73 6.50 6.21

    PI 1.69 1.79 1.88

    15-24 TC 85 - 105 % of nominal

    (Protection Range) PI 80 - 120 % of nominal

  • 7/22/2019 Chigo Inverters Manual

    23/52

    - 22 -

    Capacity Correction Factors

    Cooling Capacity Ratio Vs. Outdoor Temperature

    Cooling Capacity Correction Factor

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    25 30 35 40 45

    Outdoor Temperature (deg C)

    Capacity

    Ratio

    32/23

    29/27

    27/19

    24/17

    22/15

    Heating Capacity Ratio Vs. Outdoor Temperature

    Heating Capacity Correction Factor

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    -15 -10 -5 0 5 10 15 20

    Outdoor Temperature (deg C)

    Capacity

    Rat

    io

    15

    20

    25

  • 7/22/2019 Chigo Inverters Manual

    24/52

    - 23 -

    Capacity Correction Factor Due to Tubing Length (One Way)

    Cooling

    Heating

  • 7/22/2019 Chigo Inverters Manual

    25/52

    - 24 -

    Pressure Curve

    Model

    CMV-V40H13AD CMV-50V3A-E2 CMV-V71T3AT CMV-V80T3AQ

    Cooling--------------Test Model

    Heating-----------Test Model

  • 7/22/2019 Chigo Inverters Manual

    26/52

    - 25 -

    ELECT RICAL D ATA

    Model CMV-V40H13AD

    Power Supply 220-240V 1PH 50Hz

    Connected to OutdoorMaximum Current 8 A

    Inrush Current 15A

    Starting Current 1A

    Circuit breaker 20A

    Power supply wiring - No. x cross section 31.5 mm26680mm

    Interconnecting cable - No. x cross section 41.0 mm26300mm

    Model CMV-50V3A-E2

    Power Supply 220-240V 1PH 50Hz

    Connected to Outdoor

    Maximum Current 11 A

    Inrush Current 35A

    Starting Current 1A

    Circuit breaker 20A

    Power supply wiring - No. x cross section 32.5 mm26480mm

    Interconnecting cable - No. x cross section 41.0 mm26300mm

    Model CMV-V52E23AT

    Power Supply 220-240V 1PH 50Hz

    Connected to Outdoor

    Maximum Current 11A

    Inrush Current 35A

    Starting Current 1A

    Circuit breaker 20A

    Power supply wiring - No. x cross section 32.5 mm26480mm

    Interconnecting cable - No. x cross section41.0 mm26300mm

    Model CMV- V71T3AT

    Power Supply 220-240V 1PH 50Hz

    Connected to Outdoor

    Maximum Current 16A

    Inrush Current 35A

    Starting Current 2A

    Circuit breaker 20A

    Power supply wiring - No. x cross section 32.5 mm2

    6480mmInterconnecting cable - No. x cross section 41.0 mm

    26200mm

  • 7/22/2019 Chigo Inverters Manual

    27/52

    - 26 -

    Model CMV-V80T3AQ

    Power Supply 220-240V 1PH 50Hz

    Connected to Outdoor

    Maximum Current 16A

    Inrush Current 35A

    Starting Current 2A

    Circuit breaker 20A

    Power supply wiring - No. x cross section 32.5 mm26480mm

    Interconnecting cable - No. x cross section 41.0 mm216100mm

    Note:

    Inrush current is the current when power is up. (charging the DC capacitors at outdoor unit

    controller).

    Starting current is the current when starting the compressor

  • 7/22/2019 Chigo Inverters Manual

    28/52

    - 27 -

    4. OUTLINE DIMENSI ON OF OUTDOOR AND INDOOR

    4.1 Outline dimension of outdoor Units

    CMV-V40H13AD

    CMV-50V3A-E2/ CMV-V52E23AT

  • 7/22/2019 Chigo Inverters Manual

    29/52

    - 28 -

    CMV- V71T3AT/ CMV-V80T3AQ

    4 2 the outdoor unit mounting dimensions

  • 7/22/2019 Chigo Inverters Manual

    30/52

    - 29 -

    the bodys dimension mounting dimensionsDimensions

    Code

    outdoor

    units typeA B C D E

    CMV-V40H13AD 845 304 542 510 278

    CMV-50V3A-E2 900 352 590 505 310

    CMV-V52E23AT 900 352 590 505 310

    CMV-V71T3AT/

    CMV-V80T3AQ900 388 837 600 358

    4 3 The indoor unit mounting dimensions

    unitmm

  • 7/22/2019 Chigo Inverters Manual

    31/52

    - 30 -

    the bodys dimension mounting dimensionsDimensions

    Code

    indoor

    units type

    A B C D E F

    CMV-V20G3A/MXX 800 280 195 490 / /

    CMV-V25G3A/MXX 800 280 195 490 / /

    CMV-V35G3A/MXX 800 280 195 490 / /

    CMV-V35G3A/PXX 900 296 220 583 257.5 257.5

    CMV-V50G3A/PXX 900 296 220 583 257.5 257.5

  • 7/22/2019 Chigo Inverters Manual

    32/52

    31

    5 The outdoor unit structure exploded view .5.1 outdoor unit :CMV-V40H13AD

    NO. description name number

    1 Front Grill 1

    2 Front Plate 1

    3 Axial flow fan 1

    4 Motor 1

    5 Motor support 16 Condenser 1

    7 Top panel 1

    8 Electric box 1

    9 Rear Grill 1

    10 Right panel 1

    11 handle 1

    12 Valve installation plate 1

    13 A DN4 DN4 valve 1

    14 A DN8 DN8 valve 1

    15 B DN4 DN4 valve 1

    16 B DN8 DN8 valve 1

    17 Capillary Assy 1

    18 Electronic expansion valve 2

    19 Four-way valve assembly 1

    20 Steam liquid segregator 1

    21 Compressor 1

    22 Partition board 1

    23 Base 1

  • 7/22/2019 Chigo Inverters Manual

    33/52

    32

    5.2 outdoor un it : CMV-50V3A-E2/ CMV-V52E23AT

  • 7/22/2019 Chigo Inverters Manual

    34/52

    33

    NO. description name number

    1 front grill 1

    2 front panel 1

    3 fan 14 motor 1

    5 motor bracket assemble 1

    6 left grill 1

    7 left pole 1

    8 top cover 1

    9 rear grill 1

    10 condenser 1

    11 4-way valve 1

    12 muffle 113 filter 1

    14 controllor 1

    15 control box cover 1

    16 electrical control box 1

    17 A DN8 DN8 valve for A unit 1

    18 A DN4 DN4 valve for A unit 1

    19 B DN8 DN8 valve for B unit 1

    20 B DN4 DN4 valve for B unit 1

    21 valve installation plate 122 handle 1

    23 right panel 1

    24 expand valve 2

    25 compressor 1

    26 compressor pad 1

    27 partition board 1

    28 base assemble 1

  • 7/22/2019 Chigo Inverters Manual

    35/52

    34

    5.3outdoor unit : CMV-V71T3AT/ CMV-V80T3AQ

  • 7/22/2019 Chigo Inverters Manual

    36/52

    35

    NO. description name number

    1 top panel 1

    2 electric box 1

    3 rear Grill 1

    4 partition board 15 four-way valve 1

    6 electronic expansion valve 1

    7 desiccation filter 1

    8 right panel 1

    9 large handle 1

    10 valve installation plate 1

    11 oil separator 1

    12 high-pressure tank 1

    13 compressor 114 base 1

    15 condenser 1

    16 motor support 1

    17 DC motor 1

    18 axial flow fan 1

    19 front Grill 1

    20 front Plate 1

    21 left protect net 1

    22 left panel 123 vapor-liquid separator 1

    24 back panel 2

    25 DN10 DN10 cut-off valve 1

    26 DN8 DN8 cut-off valve 1

    27 electronic control box support plate 1

    28 small hand-pumped 1

    29 front maintenance board 1

  • 7/22/2019 Chigo Inverters Manual

    37/52

    36

    6The analysis of indoor malfunction code internal wiring get loose, whichwill cause malfunction.

    indoor detailed malfunction1.when indoor unit live wire is disconnected its lamp panel cant display.

    Live wire is off

    2.when the transformers secondary and primary disconnect or indoor fuse is off the indoor unit lamppanel cant display.

    Transformer secondary is off

    Transformer primary is off

    The relevant transfomer primarysocket

  • 7/22/2019 Chigo Inverters Manual

    38/52

    37

    Indoor unit fuse is off.

    The indoor unit fuse

    The condition that the lamp panel

    cant display

    3.1when the indoor null line is off the system displays F1 code 2when indoor communication wire is off the system also displays F1 code

    The inserted slice to null line

    The indoor unit null line is off

  • 7/22/2019 Chigo Inverters Manual

    39/52

    38

    2the indoor communication wire isoff.

    Communication wire socket.

    the indoor lamp panel displays F1 code.

    4. when indoor fan mainline or feedback wire is offthe indoor lamp panel displays F4 code. After directlyinsert it wellTo restart the unit to recover normal .

    Indoor fan mainline is off

    The relevant socket with indoor fan mainline

  • 7/22/2019 Chigo Inverters Manual

    40/52

    39

    indoor fan feedback wire is off

    the relevant socket with indoor feedback

    wire

    The lamp panel displays F4 code.

    5.when indoor sensor has the problem, the lamp will display F2 F3 code. When indoor coil outlet , inletand middle temperature sensor appear malfunction, the lamp panel displays F3 code; when indoor

    temperature sensor appears fault, the lamp panel shows F2 fault code.

    Indoor temperature sensor plug

    the relevant socket of indoor temperature

    sensor plug

  • 7/22/2019 Chigo Inverters Manual

    41/52

    40

    The lamp panel alternately displays F2,F3fault code.

    6.when outdoor temperature sensor is off or loose contact the indoor lamp panel displays F6 faultcode.

    the relevant socket of outdoor temp.

    sensor.

    The outdoor temperature sensor isoff or loose contact.

  • 7/22/2019 Chigo Inverters Manual

    42/52

    41

    The indoor lamp panel displays F6fault code.

    7.when the system appears mode conflict the indoor lamp panel shows d1 code.

    the indoor lamp panel showsd1code.

    8.when the system is in the defrosting conditionThe lamp panel displays dF code.

    The lamp panel displays dF code.

  • 7/22/2019 Chigo Inverters Manual

    43/52

    42

    The outdoor electrical control fault code of the America 12K model .1.the outdoor module temperature sensor is off or loose contact the lamp panel shows F6 code.

    the outdoor module temperature sensor

    is off or loose contact .

    the relevant socket with the outdoormodule temperature sensor plug .

    The lamp panel shows F6 code .

    2.The outdoor unit DC busbar voltage is abnormal the lamp panel shows F7code.

    The PN power wire are off .

  • 7/22/2019 Chigo Inverters Manual

    44/52

    43

    The lamp panel shows F7code.

    3.the outdoor module drive wire is off the lamp panel shows FC code .

    The outdoor module drive wire is off .

    The matching socket with the outdoormodule drive wire

    The matching socket with the outdoormodule drive wire .

    The outdoor module drive wire isoff .

  • 7/22/2019 Chigo Inverters Manual

    45/52

    44

    The lamp panel shows FC code .

    4the wave filtering board and mainboard power wire is off or loose contactthe lamp panel shoes F1 code .the wave filtering board and mainboard powerwire is off or loose contact

    The matching socket with the wavefiltering board and mainboard power wire

    the lamp panel shoes F1 code .

  • 7/22/2019 Chigo Inverters Manual

    46/52

    45

    5. the evaporator middle temperature and condenser middle temperature sensor is off the lamp paneldisplays P8 code .

    the evaporator middle temperature andcondenser middle temperature sensor is off

    the lamp panel displays P8 code

  • 7/22/2019 Chigo Inverters Manual

    47/52

    46

    The 67th

    style indoor lamp panel

    The timing lamp The turbo lamp The running lamp

    The indoor unit faulty display:

    Faulty contents Trouble display

    Communication faultThe running lamp lightens all the timethe turbo lamp

    lightens 2 times and then extinguish 2 seconds

    Indoor fan faultThe running lamp lightens all the timethe turbo lamp

    lightens 5 timesand then extinguish 2 seconds

    Indoor temp. sensor faultThe running lamp lightens all the timethe turbo lamp

    lightens 3 times and then extinguish 2 seconds

    Indoor coil outlet temp. sensor faultThe running lamp lightens all the timethe turbo lamp

    lightens 4 timesand then extinguish 2 seconds

    Indoor coil inlet temp. sensor fault The running lamp lightens all the timethe turbo lamplightens 4 times and then extinguish 2 seconds

    Indoor coil middle temp. sensor faultThe running lamp lightens all the timethe turbo lamp

    lightens 4 times and then extinguish 2 seconds

    Mode conflictThe running lamp lightens 1 time and then extinguish

    1 second

    Defrosting or anti cold airThe timing lamp lightens 1 time and then extinguish

    1 second

    The outdoor unit faulty display:

    Faulty contents Trouble display

    the outdoor unit transducer module

    protection faulty

    The timing lamp lightens all the timethe turbo lamp

    lightens 2 times and then extinguish 2 seconds

    over current of outdoor unit The timing lamp lightens all the timethe turbo lamplightens 3 times and then extinguish 2 seconds

    discharge temp. of compressor too high,

    outside ambient temp. too high, switch

    temp. of compressor crust cut off, temp.

    of module too high

    The timing lamp lightens all the timethe turbo lamp

    lightens 4 times and then extinguish 2 seconds

    The outdoor unit DC busbar voltage is

    abnormal

    The timing lamp lightens all the timethe turbo lamp

    lightens 7 times and then extinguish 2 seconds

    lack refrigerant or reverse valve faultThe timing lamp lightens all the timethe turbo lamp

    lightens 8 times and then extinguish 2 seconds

    outdoor sensor faultThe running lamp lightens all the timethe turbo lamp

    lightens 7 times and then extinguish 2 seconds

    outdoor unit drive fault, start compressor

    failure

    The running lamp lightens all the timethe turbo lamp

    lightens 6 times and then extinguish 2 seconds

  • 7/22/2019 Chigo Inverters Manual

    48/52

    47

    The 85th

    style indoor lamp panel

    The timing lamp The sleeping lamp The running lamp

    Faulty contents Trouble display

    Communication faultThe timing lamp lightens all the timethe sleeping lamp

    lightens 2 times and then extinguish 2 seconds

    Indoor fan faultThe timing lamp lightens all the timethe sleeping lamp

    lightens 5 times and then extinguish 2 seconds

    Indoor temp. sensor faultThe timing lamp lightens all the timethe sleeping lamp

    lightens 3 times and then extinguish 2 seconds

    Indoor coil outlet temp. sensor faultThe timing lamp lightens all the timethe sleeping lamp

    lightens 4 times and then extinguish 2 seconds

    Indoor coil inlet temp. sensor faultThe timing lamp lightens all the timethe sleeping lamp

    lightens 4 times and then extinguish 2 seconds

    Indoor coil middle temp. sensor faultThe timing lamp lightens all the timethe sleeping lamp

    lightens 4 times and then extinguish 2 seconds

    Mode conflictThe timing lamp lightens 1 time and then extinguish

    1 second

    Defrosting or anti cold airThe running lamp lightens 1 time and then extinguish

    1 second

    Faulty contents Trouble display

    the outdoor unit transducer module

    protection faulty

    The running lamp lightens all the timethe sleeping lamp

    lightens 2 times and then extinguish 2 seconds

    over current of outdoor unitThe running lamp lightens all the timethe sleeping lamp

    lightens 3 times and then extinguish 2 seconds

    discharge temp. of compressor too high,

    outside ambient temp. too high, switch

    temp. of compressor crust cut off, temp.

    of module too high

    The running lamp lightens all the timethe sleeping lamp

    lightens 4 times and then extinguish 2 seconds

    The outdoor unit DC busbar voltage is

    abnormal

    The running lamp lightens all the timethe sleeping lamp

    lightens 7 times and then extinguish 2 seconds

    lack refrigerant or reverse valve faultThe running lamp lightens all the timethe sleeping lamp

    lightens 8 times and then extinguish 2 seconds

    outdoor sensor faultThe timing lamp lightens all the timethe sleeping lamp

    lightens 7 times and then extinguish 2 seconds

    outdoor unit drive fault, start compressor

    failure

    The timing lamp lightens all the timethe sleeping lamp

    lightens 6 times and then extinguish 2 seconds

  • 7/22/2019 Chigo Inverters Manual

    49/52

    48

    6.3 The malfunction of indoor and outdoor unit

    1The common malfunction code analysis and solutions!The faultcode

    The fault content The reason of fault and its solutions

    F1 The communication fault

    1The communication wire is broken off. Please checkwhether the wire is disentwined;2Please check whether the electrical control board isdamaged. It should be replaced when it is damaged;

    3Please check whether the power ground wire is reliable;

    4Please check whether the unit is abnormal caused by theexternal interference. If it is, then find the interferingsources, and remove them.

    F2The indoor temperature

    sensor fault

    1Check whether the resistance of sensor is normal,otherwise replace it;

    2Check whether the sensor wire is short circuit or opencircuit, and whether the plug is well contacted, whetherthere is welding off or rosin joint on the electric controlboard, repair it if there is any above;

    3When the 1 and 2 are both normal, then the componentor integrated circuit is damaged, the electric control board

    should be replaced.

    F3The indoor coil

    temperature sensor fault

    1Check whether the resistance of sensor is normal,

    otherwise replace it;

    2Check whether the sensor wire is short circuit or opencircuit, and whether the plug is well contacted, whetherthere is welding off or rosin joint on the electric controlboard ,repair it if there is any above;

    3When the 1 and 2 are both normal, then the componentor integrated circuit is damaged, the electric control board

    should be replaced.

    F4

    Indoor PG motor fault(tap motor hasnt so

    breakdown )

    1Check whether the contact of the plug of the motor wire

    and socket is well. Please make sure it is well contacted;

    2Check whether the indoor motor has damaged, the

    motor should be replaced when it is damaged;

    3Check whether the controllable silicon and other

    components on the electric control board have damaged

    replace the controllable silicon or electric control boardwhen they are damaged;

    4Check whether the indoor fan is unobstructed whenrunning, please fix the indoor fan again when it isobstructed.

    F5 IPM protection

    1Check whether the supply voltage is out of ranging from150 to 270V(overvoltage and undervoltage protection);Measuring the actual current, if the current is greater thanthe rated current of 2A,it is over-temperature protection;If the above are normal, that is IPM module internal circuit

    fault protection, so please replace the IPM module.

    F6 The outdoor sensor fault

    1Check whether the resistance of sensor is normal,otherwise replace it;

    2Check whether the sensor wire is short circuit or opencircuit, and whether the plug is well contacted, whetherthere is welding off or rosin joint on the electric control

    board, repair it if there is any above;

    3When the 1 and 2 are both normal ,then the componentor integrated circuit is damaged, the electric control boardshould be replaced.

  • 7/22/2019 Chigo Inverters Manual

    50/52

    49

    F7

    The outdoor coiltemperature sensor fault

    Including the

    mid-point of tube

    inspiratory gas

    1Check whether the resistance of sensor is normal,otherwise replace it;

    2Check whether the sensor wire is short circuit or opencircuit, and whether the plug is well contacted, whether

    there is welding off or rosin joint on the electric controlboard, repair it if there is any above;

    3When the 1 and 2 are both normal, then the componentor integrated circuit is damaged, the electric control boardshould be replaced.

    F9 Exhaust gas sensor failure

    1Check whether the resistance of sensor is normal,otherwise replace it;

    2Check whether the sensor wire is short circuit or open

    circuit, and whether the plug is well contacted, whetherthere is welding off or rosin joint on the electric controlboard, repair it if there is any above;

    3When the 1 and 2 are both normal, then the componentor integrated circuit is damaged, the electric control boardshould be replaced.

    FAThe communication faultbetween the wire

    controller and the indoorPCB

    1 check whether the wire controllers connecting wire isshort circuit or loose, please make it connect well;

    2 Check the connecting linewire controllerPCBwhether they are loose or have a bad contact. Please

    make them have a good contact.

    FCoutdoor unit driving fault,

    starting compressor

    failure

    1Turn on the power again, and then check whether theoperation of the compressor is normal;

    2Check whether the connection of the compressor iscorrect or reliable, otherwise repair it;

    3Check whether the components on the electric control

    board have been damaged, if they are damaged, thecomponents or the electric control board should be

    replaced.;4Check whether the connecting wires are disentwinedbetween the Intelligent Power Module board and the main

    board, otherwise make the wires connect firmly .

    FF

    The outdoor DC motorfault

    1Check the resistance value of the DC motor port. If it isshort circuit, please change the DC motor;

    2Check the voltage value of the DC motor port

    VCC(15Vdc)Vdm(340Vdc),please change the PCB board

    if the voltage values are abnormal;

    3if all the voltage values of the DC motor port are

    normalthe Vsp voltage0~5vis also ok ,it shows that the

    inner PCB board of the DC motor is damaged, then changethe DC motor.

    FH

    The indoor unit

    EEPROM error

    1Check whether there are false weld and bad contact etcbetween the EEPROM chip block and the electroniccontrol board ;

    2Check whether the EEPROM chip pin is broken foot

    and the direction of installation is in line with the

    EEPROM block;

    3When the procedure of EEPROM chip and itself havefault it will appear the code FH. That is the need to replacethe EEPROM chip.

    dF Defrosting state The unit is in defrosting statethat is normal.

    dI Mode conflictWhen the running mode for No.1 indoor unit is differentfrom No.2 indoor unit, the dF is displayed.

  • 7/22/2019 Chigo Inverters Manual

    51/52

    50

    The faultcode

    The fault content The reason of fault and solution

    P1

    Indoor coil

    temperature

    over-temperature

    protection for heating

    (thermal overload),

    outdoor coil

    temperature

    overheating protection

    for cooling (cooling

    overload)

    1Check whether the ambient temperature is over the rangeof air-conditioning running temperature ;

    2Check whether the indoor coil temperature is higher thanor equal to 63 degrees when heating and check whetherthe outdoor coil temperature is higher than or equal to 65

    degrees when cooling, it will appear protection if thevalue is over the above;

    3Check whether the parameters of indoor and outdoor coiltemperature sensors are normal, if abnormal, pleasereplace the sensors;

    4If the above are normal, check whether the main controlboard output parameters are normal, if abnormal, pleasereplace the main control board.

    P2

    The outdoor unit

    inverter module

    protection fault

    1Check whether the connection of the compressor is reliable,

    otherwise connect firmly again;

    2Check whether the fixation between the IPM module and

    the radiator is firm.;3Check whether the compressor is well, otherwise replace it;

    4Check whether the IPM module is abnormal, otherwisereplace it.

    P3Over current of

    outdoor unit

    1Check whether the ambient temperature exceeds theoperation range for the air conditioner;

    2Check whether the current detection circuit is abnormal, theelectric control should be replaced when it is abnormal..

    P4

    discharge temperature of

    compressor is too high, theoutside ambienttemperature

    over-temperature, switchoff the compressor shelltemperature, moduletemperatureover-temperature

    1Check whether the pressure is normal when the unit isrunning, if it is abnormal, you should detect the leakage andthen welding and adding refrigerant;

    2Check whether the ambient temperature is too high or too

    low, when the temperature is more than -20 degrees and less55 degrees, it can disappear automatically;

    3Check whether temperature switch of compressor isdamage, it should be replaced if it is damaged.

    P7

    The outdoor unit DC

    generatrix voltage is

    abnormal

    1Check whether the supply voltage is out of ranging from150 to 270V;

    2Check the voltage detection circuit of the IPM base board isabnormal, if it is abnormal, the IPM base board or the electriccontrol board should be replaced.

    P8lack refrigerant or reverse

    valve fault

    1Check whether the high and low pressure valves have beenopened, otherwise open the valves;

    2Check whether the indoor coil pipe temperature sensor is

    normal, if it is abnormal, the sensor should be replaced;3Check whether the indoor coil temperature sensor hung in

    the airplease plug it in a correct position if the indoor coiltemperature sensor hung in the air;

    4Check the system pressure is abnormal, if it is abnormal,yon should detect leakage and the welding and adding therefrigerant.;

    5Please change the outdoor PCB board , if all above arenormal.

    PA

    protection when indoor

    pipe temperature is toolow (Anti-icing)

    1Check whether the ambient temperature is over the rangeof air-conditioning running temperature;

    2Check the indoor coil temperature is less than or equal to-1 degrees, if more than this value it will be the protectionof;

    3Check whether the indoor coil temperature sensor

  • 7/22/2019 Chigo Inverters Manual

    52/52

    parameters are normal, if abnormal it is the replacementof the sensor;

    4If the above are normal, check whether the main controlboard output parameters are normal, if abnormal ,pleasereplace the main control board.

    PC

    Outdoor ambienttemperature

    over-temperatureprotection (including highand low)

    1Check whether the outdoor ambient temperature is toohigh or too low, when the ambient temperature is lower

    than (T> -20, T