CHEVRON - Flow Rates and Shock Pressures Through Tube Ruptures Heat Exchanger
-
Upload
ramirezisaac6843 -
Category
Documents
-
view
244 -
download
1
Transcript of CHEVRON - Flow Rates and Shock Pressures Through Tube Ruptures Heat Exchanger
Appendix F. Flow Rates and Shock Pressures Through Tube Ruptures
Methods to calculate tube rupture flow rates and shock pressures are given here for shell and tube exchangers containing gases, two-phase mixtures, and liquids.
Chevron Corporation F-1 April 1998
Appendix F Heat Exchanger and Cooling Tower Manual
F1.0 High-pressure Gases and Two-phase MixturesWhen the high-pressure fluid is part or all gas, the flow through the rupture may or may not be choked (limited by the gas reaching sonic velocity). If it is choked, flow through the rupture is independent of the low-pressure side. Otherwise, the response of the low-pressure side affects the rupture flow. The rupture flow may be choked on one side of the break and subsonic on the other side. Rupture flow from both sides of a break is maximum for a break at one end.
Rupture flow rates have been calculated for the usual range of conditions in heat exchangers and are given below in Equation F-1 and Figure F-1. For definitions, see the nomenclature section at the end of this appendix.
(Eq. F-1)
Equation F-1, with CF = 1, is the equation for isentropic (frictionless) choke flow from both sides of the break. CF is the ratio of actual flow with friction to the flow rate for choked isentropic flow with a break at one end and is given in Figure F-1.
Two-phase flow through a rupture is similar to all-gas flow. Initially, the two-phase rupture flow is mostly gas. The gas usually accelerates rapidly to near sonic speeds by virtue of its internal energy, whereas liquid is dragged along by viscous shear and accelerates much more slowly. The presence of liquid reduces the gas flow area and adds to frictional resistance of the gas flow. Treating liquid-gas mixtures on the high-pressure side as if they were all gas is conservative and is recommended.
The high-pressure fluid on the low-pressure side displaces and compresses the low-pressure fluid. The pressure rise on the low-pressure side depends on the volume flow rate into the low-pressure side, the compressibility of the low-pressure fluid and the flow area of the connected piping. The fluid compressibility and pipe sizes on the low-pressure side are usually the same for inlet and outlet lines for single phase fluids but may be significantly different for liquid-gas mixtures.
Equation F-2 below is a volume balance: volume flow rate of high-pressure fluid into the low-pressure side equals rate at which volume is made available by the compression waves in the inlet and outlet piping.
(Eq. F-2)
M·
R 2CF AT ρH g PH kH2
kH 1+----------------
kH 1+kH 1–---------------
⋅ ⋅ ⋅
0.5
⋅=
M·
R 2AL1 GL ρHFL PLR PL–( ) gρL1 KL1⋅------------------------
0.5⋅ ⋅ ⋅=
April 1998 F-2 Chevron Corporation
Heat Exchanger and Cooling Tower Manual Appendix F
where:
(Eq. F-3)
For single phase service on the low-pressure side, fluid properties and pipe sizes for inlet and outlet lines are usually equal. Then GL = 1 and Equation F-2 becomes:
(Eq. F-4)(From Equation F-3)
Solving Equations F-1 and F-2 simultaneously, with ρHFL = ρH (PLR/PH) for high-pressure gas, results in:
(Eq. F-5)
where:
(Eq. F-6)
Equation F-6 is plotted in Figure F-2.
Figure F-2 applies to any low-pressure fluid. Liquid cases are toward the right side of the figure, gas cases toward the left, and two-phase cases in the middle.
GL12--- 1
AL2
AL1----------
ρL1
ρL2---------
KL1
KL2----------
0.5
+=
M·
R 2AL ρHFL PLR PL–( ) gρL KL⋅------------------
0.5⋅=
PLR
PH----------
12---
PL
PH-------
PL
PH-------
2
4 X+ 0.5
+=
XCF
GL-------
AT
AL1----------
ρL1
ρH---------
KL1
PH----------
kH2
kH 1+----------------
kH 1+kH 1–---------------
0.5
=
Chevron Corporation F-3 April 1998
Appendix F Heat Exchanger and Cooling Tower Manual
Fig. F-1 Factor for Friction and Flow Regime
April 1998 F-4 Chevron Corporation
Heat Exchanger and Cooling Tower Manual Appendix F
Fig. F-2 Rupture Pressure on Low-Pressure Side Due to High-Pressure Gas
Chevron Corporation F-5 April 1998
Appendix F Heat Exchanger and Cooling Tower Manual
F2.0 High-Pressure LiquidsTube rupture with high-pressure liquid involves decompression waves in the high-pressure system similar to the compression waves in the low-pressure system. Choked liquid flow does not occur at conditions encountered in heat exchangers.
The relationship between rupture flow and decompression is given by:
(Eq. F-7)
Equal pipe sizes and fluid properties are assumed for the high-pressure inlet and outlet lines.
The rupture flow rate and pressure drop across the break for a tube break at one end (worst case) are related as follows:
(Eq. F-8)
where:
(Eq. F-9)
Solving Equations F-7, F-8, and F-3 simultaneously results in:
(Eq. F-10)
(Eq. F-11)
(Eq. F-12)
M·
R 2AH PH PHR–( )g ρH⋅KH
-------------- 0.5
=
M·
R 2CFL AT 4 3⁄( )g ρH PHR PLR–( )⋅( )0.5⋅=
CFL12--- 1
3 2⁄3 2⁄ F L D⁄⋅+------------------------------------
0.5+=
PLR PL–
PH PL–----------------------
Z
2---
1 SH+( )
SH2
--------------------- 14Z---
SH
1 SH+----------------
2
+0.5
1–
=
PH PHR–
PH PL–----------------------- SH
PLR PL–
PH PL–----------------------
=
M·
R
2CFL AT 4 3⁄( )g ρH PH PL–( )⋅[ ]0.5⋅-------------------------------------------------------------------------------------------- 1 1 SH+( )
PLR PL–
PH PL–----------------------
–0.5
=
April 1998 F-6 Chevron Corporation
Heat Exchanger and Cooling Tower Manual Appendix F
where:
(Eq. F-13)
and
(Eq. F-14)
Equations F-10 and F-12 are plotted in Figures F-3 and F-4 respectively.
Fig. F-3 Rupture Pressure on Low-Pressure Side Due to High-Pressure Liquid
SH GL
AL1
AH----------
ρH
ρL1---------
KH
KL1----------
0.5
=
Z 4 3⁄( )CFL2
AT
AH--------
2 KH
PH PL–-------------------
=
Chevron Corporation F-7 April 1998
Appendix F Heat Exchanger and Cooling Tower Manual
F3.0 Effective Bulk ModulusEffective bulk modulus is the pressure change per unit of volume change.
(Eq. F-15)
Expansion or contraction of the pipe, as well as compression or decompression of fluid, contribute to the effective bulk modulus.
The effective bulk modulus, including pipe flexibility, is:
(Eq. F-16)
where C = 0.91 for restrained piping.
The effective bulk modulus is typically 10% less than the liquid bulk modulus. Equation F-16 is appropriate for liquid systems. Bulk modulus data for liquids are available in various reference books including the Fluid Flow Manual.
Fig. F-4 Liquid Rupture Flow Rate
K∆P
∆V V⁄----------------=
KKF
1KF D C⋅ ⋅
E tp⋅------------------------+
----------------------------------=
April 1998 F-8 Chevron Corporation
Heat Exchanger and Cooling Tower Manual Appendix F
Bulk modulus for gases and two-phase flow may be calculated as follows:
(Eq. F-17)
where:
(Eq. F-18)
Only gas phase compressibility is included in Equation F-17. Liquid phase compressibility and pipe flexibility are insignificant in comparison to gas phase compressibility.
F4.0 Two-Phase DensityTwo-phase density of low-pressure fluid may be calculated as follows:
(Eq. F-19)
F5.0 ApplicationsThe use of the equations and graphs in this appendix is illustrated in the examples following the nomenclature section below.
The units indicated in the nomenclature section are consistent with the equations. The equations, however, are presented in terms of dimensionless parameters or ratios where practical. Any consistent units may be used in those cases. Bulk modulus, elastic modulus, and fluid pressure all have the same units. Where these variables appear as ratios in the examples, psi units are used; otherwise psf units are used.
Example 1 is for high-pressure gas and low-pressure liquid. Post-rupture pressure on the low-pressure side is 83% of the initial pressure of the high-pressure fluid and governs the design of the low-pressure side.
Example 2 is for high-pressure gas and low-pressure steam generation. Post-rupture pressure on the low-pressure side is insignificant and does not affect design pres-sure.
KL
PL-------
R 1+R
------------- PLR
PL---------- 1–
1PLR
PL----------
–1– kL⁄--------------------------------------------=
R ρ1 ρg⁄( ) Y1 Y–-------------
=
ρρg
Y ρg ρ1⁄( ) 1 Y–( )+--------------------------------------------------=
Chevron Corporation F-9 April 1998
Appendix F Heat Exchanger and Cooling Tower Manual
Example 3 is for high-pressure liquid and low-pressure liquid. Post-rupture pres-sure on the low-pressure side is about 40% of the initial pressure of the high-pres-sure liquid and governs the design of the low-pressure side.
F6.0 Nomenclature
A = Flow area of tube or pipe, ft2
C = Pipe restraint factor
CF = Actual tube rupture flow/isentropic choke flow
CFL = Actual tube rupture flow/frictionless liquid flow
D = Inside diameter of pipe, ft
E = Modulus of elasticity of pipe, psf
F = Darcy-Weisbach friction factor
g = 32.17 lb/slug
GL = Factor for dissimilar inlet and outlet piping
k = Ratio of specific heats (Cp/Cv)
K = Effective bulk modulus of fluid and pipe, psf
KF = Bulk modulus of fluid, psf
L = Flow length through broken tube, ft
= Rupture flow rate, lb/sec
P = Pressure, psfa
∆P = Increment of pressure, psf
R is defined by Equation F-18.
SH is defined by Equation F-13.
tp = Pipe wall thickness, ft
V = Volume, ft3
∆V = Increment of volume, ft3
X is defined by Equation F-6.
Y = Weight fraction vapor
Z is defined by Equation F-14.
ρ = density, lb/ft3
M·
R
April 1998 F-10 Chevron Corporation
Heat Exchanger and Cooling Tower Manual Appendix F
Subscripts:
Example 1
High-Pressure Hydrogen Gas and Low-pressure Cooling Water
Gas
Cooling Water
Tube
Low-Pressure Piping
1 - Inlet piping, low pressure side (LPS)
2 - Outlet piping, LPS
g - Gas, LPS
H - High-pressure side, normal conditions
HR - High-pressure side, rupture conditions
HFL - High-pressure fluid on low pressure side
l - Liquid
L - Low-pressure side, normal conditions
LR - Low-pressure side, rupture conditions
R - Rupture conditions
T - Tube
PH = Pressure = 2000 psia = 288,000 psfa
ρH = Density = 0.459 lb/ft3
kH = Ratio of specific heats = 1.4
PL = Pressure = 65 psia = 9360 psfa
ρL = Density = 62 lb/ft3
KF = Bulk modulus = 315,000 psi = 45,360,000 psf
Inside diameter = 0.482 in. = 0.0402 ft
Inside Diameter = 4.026 in.
tp = Wall thickness = 0.237 in.
E = Elastic modulus = 29 × 106 psi = 4.2 × 109 psf
GL = 1 (similar inlet and outlet)
Chevron Corporation F-11 April 1998
Appendix F Heat Exchanger and Cooling Tower Manual
(Eq. F-20)
Assume CF = 0.5
(Eq. F-21)
=
(Eq. F-22)
(Eq. F-23)
PLR = 0.83 (2000) = 1660 psia
CF from Figure F-1 is 0.5; therefore assumed value above is okay.
(Eq. F-24)
=
= 1.79lb/sec Total Flow from Rupture
KL
KF
1KF D C⋅ ⋅
E tp⋅------------------------+
----------------------------------315,000
1315,000
29,000,000---------------------------
4.0260.237-------------
0.91+
------------------------------------------------------------------------ 269,700psi= = =
XCF
GL-------
AT
AL1----------
ρL1
ρH---------
KL1
PH----------
kH2
kH 1+----------------
kH 1+kH 1–---------------
0.5
=
0.51
------- .4824.026-------------
2 620.459-------------
269,7002000
------------------- 1.4
22.4-------
2.40.4-------
0.5
0.662=
PLR
PH----------
12---
PL
PH-------
PL
PH-------
2
4X+ 0.5
+12---
652000------------
652000------------
24 0.662( )+
0.5+ 0.83= = =
M·
R 2CF AT ρH g PH kH2
kH 1+----------------
kH 1+kH 1–---------------
⋅ ⋅
0.5
⋅=
2 0.5( ) 3.14( ) 0.0402( )2[ ]4
-------------------------------------------- 0.459 32.17( ) 288,000( ) 1.4( ) 22.4-------
2.40.4-------
0.5
April 1998 F-12 Chevron Corporation
Heat Exchanger and Cooling Tower Manual Appendix F
Example 2
High-Pressure Hydrogen Gas and Low-Pressure Steam Generator
Gas
BFW/Steam
Tube
BFW Piping
(Eq. F-25)
Steam PipingInside diameter = 7.981 in.
Y2 = Weight fraction vapor = 1 (1/R2 = 0)
Assume PLR/PL = 1.13
PH = Pressure = 2000 psia = 288,000 psfa
ρH = Density = 0.459 lb/ft3
kH = Ratio of specific heats = 1.4
PL = Pressure = 165 psia = 23,760 psfa
ρl = Liquid Density = 55 lb/ft3
ρg = Vapor density = 0.36 lb/ft3
kL = Ratio of vapor specific heats = 1.28
KF = Liquid bulk modulus = 183,000 psi = 26.4 × 107 psf
Inside diameter = 0.482 in. = 0.0402 ft
Inside diameter = 2.067 in.
tp = Wall thickness = 0.154 in.
E = Elastic modulus = 29 × 106 psi = 4.2 × 109 psf
Y1 = Weight fraction vapor = 0 (R1 = 0)
KL1
KF
1KFDC
Etp----------------+
-------------------------183,000
1183,000
29,000,000---------------------------
2.0670.154-------------
0.91+
------------------------------------------------------------------------ 169,000 psi= = =
Chevron Corporation F-13 April 1998
Appendix F Heat Exchanger and Cooling Tower Manual
(Eq. F-26)
KL2 = 1.43 (165) = 236 psi
(Eq. F-27)
Assume CF = 0.675
(Eq. F-28)
=
(Eq. F-29)
(Eq. F-30)
PLR = 0.0935 (2000) = 187 psia
PLR/PL = 187/165 = 1.13; therefore assumed value above is okay.
CF from Figure F-1 is 0.675; therefore assumed value above is okay.
(Eq. F-31)
KL2
PL----------
11
R2------+
PLR
PL---------- 1–
1PLR
PL----------
–1– kL⁄----------------------------------------------
1( ) 1.13 1–( )1 1.13( )– 1– 1.28⁄----------------------------------------- 1.43= = =
GL12--- 1
AL2
AL1----------
ρL1
ρL2---------
KL1
KL2----------
0.5
+12--- 1
7.9812.067-------------
2 550.36----------
169,900236
------------------- 0.5
+ 2472= = =
XCF
GL-------
AT
AL1----------
ρL1
ρH---------
KL1
PH----------
kH2
kH 1+----------------
kH 1+kH 1–---------------
0.5
=
0.6752472-------------
0.4822.067-------------
2 550.459-------------
169,9002000
------------------- 1.4
22.4-------
2.40.4-------
0.5
0.001025=
PLR
PH---------
12---
PL
PH------
PL
PH------
2
4X+0.5
+12--- 165
2000------------
1652000------------
24 0.001025( )+
0.5+ 0.0935= = =
M·
R 2CF AT ρH g PHkH2
kH 1+----------------
kH 1+kH 1–---------------
⋅ ⋅
0.5
⋅=
April 1998 F-14 Chevron Corporation
Heat Exchanger and Cooling Tower Manual Appendix F
=
(Eq. F-32)
= 2.42 lb/sec Total Flow from Rupture
Example 3
High-Pressure Liquid and Low-Pressure Cooling Water
High-Pressure Liquid
Cooling Water
Tube
High-Pressure Piping
(Eq. F-33)
PH = Pressure = 400 psia = 57,600 psfa
ρH = Density = 50 lb/ft3
KFH = Bulk modulus = 200,000 psi = 28,800,000 psf
Viscosity = 0.000672 lb/ft⋅sec = 1 CP
PL = Pressure = 65 psia = 9,360 psfa
ρL = Density = 62 lb/ft3
KFL = Bulk modulus = 315,000 psi = 45,360,000 psf
D = Inside Diameter = 0.56 in.
L = Length = 480 in. = 40 ft
Inside diameter = 4.026 in.
tp = Wall thickness = 0.237 in.
E = Elastic modulus = 29 × 106 psi = 4.2 × 109 psf
2 0.675( ) 3.14( ) 0.0402( )2[ ]4
-------------------------------------------- 0.459 32.17( ) 288,000( ) 1.4( ) 22.4-------
2.40.4-------
0.5
KH
KFH
1KFHDC
Etp--------------------+
-----------------------------200,000
1200,000
29,000,000---------------------------
4.0260.237-------------
0.91+
------------------------------------------------------------------------ 180,700 psi= = =
Chevron Corporation F-15 April 1998
Appendix F Heat Exchanger and Cooling Tower Manual
Low-Pressure Piping
(Eq. F-34)
(Eq. F-35)
Assume Friction Factor F = 0.0126
(Eq. F-36)
(Eq. F-37)
from Figure F-3 (0.318 from Equation F-10)
from Figure F-4 (0.669 from Equation F-12)(Eq. F-38)
Inside Diameter = 4.026 in.
tp = Wall thickness = 0.237 in.
E = Elastic modulus = 29 × 106 psi = 4.2 × 109 psf
GL = 1 (Similar Inlet and Outlet)
PLR = 65 + 0.32 (400 - 65) = 172 psia
KH
KFL
1KFLDC
Etp-------------------+
-----------------------------315,000
1315,000
29,000,000---------------------------
4.0260.237-------------
0.91+
------------------------------------------------------------------------ 269,700 psi= = =
SH GL
AL1
AH----------
ρH
ρL1---------
KH
KL1----------
0.5
14.0264.026-------------
2 5062------
180,700269,700-------------------
0.50.735= = =
CFL12--- 1
3 2⁄3 2⁄ FL D⁄+--------------------------------
0.5+
12--- 1
3 2⁄3 2⁄ 0.0126 480( ) 0.56⁄+-------------------------------------------------------------
0.5+ 0.675= = =
Z 4 3⁄( )CFL2
AT
AH--------
2 KH
PH PL–-------------------
4 3⁄( ) 0.675( )2 0.564.026-------------
4 180,700400 65–---------------------
0.123= = =
PLR PL–
PH PL–---------------------- 0.32=
M·
R
2CFLAT 4 3⁄( )g ρH PH PL–( )⋅[ ]0.5--------------------------------------------------------------------------------------- 0.67=
April 1998 F-16 Chevron Corporation
Heat Exchanger and Cooling Tower Manual Appendix F
(Eq. F-39)
= 15.7 lb/sec Total Flow from Rupture
Check assumed friction factor (above value is okay).
M·
R 0.67 2( ) 0.675( )3.14
0.5612
---------- 2
4----------------------------- 4 3⁄( ) 32.17( ) 50( ) 400 65–( )144[ ]0.5=
Chevron Corporation F-17 April 1998