Maharashtra State Electricity Transmission Company
Testing & Communication Circle, Aurangabad
Check List for Testing of B/U Relay Where ever No or Not Applicable (NA) selected, mention specific remarks on separate sheet Page 1 of4
CHECK LIST FOR TESTING OF BACKUP PROTECTION RELAY
EHV Sub Station - Bay - Date -
Relay Make - Type - Sr. No. -
Direction -
Sr. No. Particulars of the test Whether carried out
1 Pickup Test for Ph O/C Element ( R, Y & B )
2 Pickup Test for E/F Element
3 IDMT Ph O/C Time of Operation for 2xIn, 3xIn, 4xIn
4 IDMT E/F Time of Operation for 2xIe, 3xIe, 4xIe
5 DMT(HS) Ph O/C Operational Current & Timing (R, Y & B)
6 DMT(HS) E/F Operational Current & Timing
7 Ph O/C Maximum Torque Angle (Characteristic Angle )
8 E/F Maximum Torque Angle (Characteristic Angle )
9 Configuration of LEDs as per schematic
10 Ph O/C Operation Indications R Ph, Y Ph, B Ph (Flag / LED )
11 E/F Operation Indication ( Flag / LED )
12 DMT(HS) Ph O/C Operation ( Flag / LED )
-
7/27/2019 Check List for Testing of Backup Protection Relay...1
2/4
Maharashtra State Electricity Transmission Company
Testing & Communication Circle, Aurangabad
Check List for Testing of B/U Relay Where ever No or Not Applicable (NA) selected, mention specific remarks on separate sheet Page 2 of4
13 DMT(HS) E/F Operation ( Flag / LED )
14 Communication with relay through laptop
15 Setting changes through laptop / HMI
16 Output Contact Configuration through lap top / HMI
17 Input (opto-coupler) Configuration through lap top / HMI
18 Checking of all Inputs by external simulation on relay display
19 Checking of all Output contacts / relay during testing
20 DR trigger settings adopted as per standard practice
21 DR Trigger checking as per settings adopted
22 DR downloading and conversion to CFG format
23 Calculation and settings of Ph O/C PSM, TMS and DMT (HS)
24 Calculation and settings of E/F PSM, TMS and DMT (HS)
25 Operation of Master Trip Relay by Backup Protection
26Confirm CT star point towards object to be protected is set in the relay.(Confirm P1terminal is towards Bus)
27 Annunciation confirmation on control panel
28 Confirmation of Load current and angle on relay display
29 Confirmation of PT voltages and angle on relay display
-
7/27/2019 Check List for Testing of Backup Protection Relay...1
3/4
Maharashtra State Electricity Transmission Company
Testing & Communication Circle, Aurangabad
Check List for Testing of B/U Relay Where ever No or Not Applicable (NA) selected, mention specific remarks on separate sheet Page 3 of4
30 Confirmation of PT neutral connection to relay by removing 1ph PT fuse
31 Confirmation of Direction with available load current for O/C element
32 Confirmation of Direction with available load current for E/F element33 Confirm testing of relay through TTB, if provided.
34 Confirm blocking of Tripping and CT shorting while testing the relay through TTB
35
36
37
38
39
40
Dy. Ex. Engineer
EHV Testing Unit -Project
Testing Division -LATUR
-
7/27/2019 Check List for Testing of Backup Protection Relay...1
4/4
Maharashtra State Electricity Transmission Company
Testing & Communication Circle, Aurangabad
Check List for Testing of B/U Relay Where ever No or Not Applicable (NA) selected, mention specific remarks on separate sheet Page 4 of4
Remarks about check point where No or NA selected
Sr.No.
Short Description of Check Point Remarks
1.
2.
3.
4.
5.
6.
7.
8.
9.